Multi-conductor Lighting Busbar System 25-32-40 A
DL
E L E K T R İ K
2-3
6-7
11-12
14-15
17
18
19
20
4
5
8
13
16
9-10
E-LINE DL
CONTENTS
Introduction
Order Code System
Technical Characteristics
Standard Components
Special Straight Length
Feeder Boxes
Tap-Off Plugs
Tap-Off Boxes
Support Systems
DL Joint Installation
DL Tap-Off Plug Installation
EC Certificate of Conformity
Product Overview
Certificate
3000
330
330
750
750 750 750
750 750 420
420
2
E DLLINE
General Characteristics
8 Plug-in Points are provided on a
Standard 3 m Length
A total of 8 plug-ins on both sides
of the busbar is provided as standard.
Safety
Earth contacts of the tap-off plugs make first during assembly,
and the contact breaks last during disassembly.
Colour Coded Covers
Indicate The Phases
The covers of the single phase, 10
Amp, wired tap-off plugs of the EAE
DL Lighting busbar systems are
designed with different colours
to indicate which phase the light
fittings are fed.
Tap-off Plugs
Arrangement of E-Line DL Busbar systems are designed with
different contacts to prevent incorrect assembly.
E-Line DL Busbar Trunking Systems are used in buildings with an energy requirement between 25A-40A.
They are designed to feed lighting fittings due to the characteristics of the 10A-25A tap-off plugs.
EAE Busbar Systems are manufactured using the latest production technologies available worldwide
according to ISO 9001 standards with certified Quality Assurance systems. The products are
designed and tested in accordance with IEC 60439-2.
3
E L E K T R İ K
Silver Coated Joint Contacts
The contacts at the joining points of the busbar
and the contacts of all tap-off units are silver
coated. The silver coating minimises the contact
impedances, thus preventing the over-heating of
the contacts in case of possible over-loads.
Tin Coated Conductors
Formation of Copper Oxide is prevented by
coating the electrolytic copper conductors with
full size tin. By this feature, the contact
resistances are minimised. The contacts of
the tap-off plugs compress the conductor
within the busbar from two surfaces.
Fast, Easy and
Secure Assembly
Provided with single action
by driving the mechanical
and electrical joint silver
coated springed contacts
towards each other. You
only need to tighten one
bolt to fix the joint.
Full Isolation
The busbar conductors are coated in flameproof
insulation material. Total security
regarding human safety is provided
even when the body is severely
damaged due to external heavy
impacts that may occur.
2 5 2 5 B --
25 A 2
32 A 3
40 A 4
25 A 2
32 A 3
40 A 4
DL T DSS
4
E L E K T R İ K
E DLLINE
Busbar
Current Rating 1
Busbar
Current Rating 2
STD
X
B1
B2
B1
B2
BUSBAR TYPE
BUSBAR CURRENT RATING 1
BUSBAR CURRENT RATING 2
COMPONENT
CONDUCTOR CONFIGURATION
COMPONENT REFERENCES
Order Code System
Busbar Type
2 Conductors 2
3 Conductors 3
4 Conductors 4
5 Conductors 5
2 Conductors 2
3 Conductors 3
4 Conductors 4
5 Conductors 5
1st
Conductor Configuration
2nd
Conductor Configuration
UNPAINTED / PAINTED
UNPAINTED
PAINTED
-
B
Paint
Standard Length
Special Length
Feeder Box
End Feeder Box
Underfloor Feeder
Underfloor End Feeder
5
E L E K T R İ K
E DLLINE
V
Hz
kA
kA
m / m
m / m
m / m
W / m
mm²
mm²
mm²
kg/m
kg/m
50/60
kA
rms
R
X
Z
I²R
20
1
DL 2424 DL 3434 DL 4444
�
�
�
IEC 60439 1-2
f
IP 55
Icw
Ip
2.50
4.00
21
5.42
2.02
5.61
3.85
3.20
18.30
3.20
1.40
1.50
4.00
6.50
21
2.90
1.27
3.17
5.65
6.00
18.30
6.00
1.60
1.72
AIn 25 32 40
3.00
5.00
21
4.46
1.62
4.47
5.24
4.00
18.30
4.00
1.43
1.55
10001000Ui 1000
Technical Characteristics
Rated Current
Standards
Rated Insulation Voltage
Rated Frequency
Protection Degree
Short-Circuit (1 sec)
Short-Circuit (Peak)
Short Circuit(Peak)Tested 1 msec.
Resistance
Reactance
Impedance
Joule Losses At In
L1, L2, L3, N (Cross Section)
PE (Housing)
PE (Conductor)
Weight (4 Conductors)
Weight (5 Conductors)
Voltage Drop Calculation
U=
U=
I.2L (R.cos
3.I.L (R.cos
V
V
).10
).10
-3
-3
+X.sin�
+X.sin�
Generally Voltage drop of a busbar system can be calculated with the following formula.
;For single phase
The maximum permitted load for the support of light fittings of the system is 15 kg. concentrated or
20 kg. distributed for a recommended support span of every 2 meters without any deformation of
the housing.
For three phase ;
�
�
�
�
U =
I =
L =
R =
X =
Voltage Drop
Rated Current
Length of Line
Resistance
Reactance
m
m
m
m
�
�
� V
A
m
�
Standard Elements
E L E K T R İ K
CPE
6
E DLLINE
3000
330
330
750
750 750 750
750 750 420
420
CPE
7
E L E K T R İ K
E DLLINE
4+4
4+4
4+4
25
32
40
4+2
4+2
4+2
25
32
40
DL 2222 2x25 A Busbar
DL 3232 2x32 A Busbar
DL 4242 2x40 A Busbar
25
32
40
2+2
2+2
2+2
DL 2525 2x25 A Busbar
DL 3535 2x32 A Busbar
DL 4545 2x40 A Busbar
5+5
5+5
5+5
25
32
40
DL 2523 2x25 A Busbar
DL 3533 2x32 A Busbar
DL 4543 2x40 A Busbar
5+3
5+3
5+3
25
32
40
DL 2323 2x25 A Busbar
DL 3333 2x32 A Busbar
DL 4343 2x40 A Busbar
25
32
40
3+3
3+3
3+3
DL 2424 2x25 A Busbar
DL 3434 2x32 A Busbar
DL 4444 2x40 A Busbar
DL 2422 2x25 A Busbar
DL 3432 2x32 A Busbar
DL 4442 2x40 A Busbar
For non-standard product, please contact our technical office.
PE (PE Housing)
PE (PE Housing)
CPE conductor is separate. It is not connected the regular housing earth.
CPE conductor is separate. It is not connected the regular housing earth.
CPE conductor is separate. It is not connected the regular housing earth.
PE (PE Housing)
PE (PE Housing)
PE (PE Housing)
Standard Elements
The body is manufactured from 0,50 mm galvanised sheet metal as standard.
PE (PE Housing)
Current (A) Conductor Conf.D es c r ip t io n Order Code
Current (A) Conductor Conf.D es c r ip t io n Order Code
Current (A) Conductor Conf.D es c r ip t io n Order Code
Current (A) Conductor Conf.D es c r ip t io n Order Code
Current (A) Conductor Conf.D es c r ip t io n Order Code
Current (A) Conductor Conf.D es c r ip t io n Order Code
3024786
3024788
3024790
3024792
3024794
3024796
3024798
3024800
3024802
3024804
3024806
3024808
3024810
3024812
3024814
3024816
3024818
3024820
E L E K T R İ K
4+2
4+2
4+2
25
32
40
5+5
5+5
5+5
25
32
40
5+3
5+3
5+3
25
32
40
25
32
40
3+3
3+3
3+3
25
32
40
2+2
2+2
2+2
8
E DLLINE
4+4
4+4
4+4
25
32
40
PE (PE Housing)
PE (PE Housing)
PE (PE Housing)
DL 2525 2x25 A
DL 3535 2x32 A