REDs, REDtestProtectEarth leakage protectionAutomatic recloser
The REDs and the REDtest, REsidual current Device recloser, is made up of a residual current device and a recloser.The REDs and REDtest REsidual current Devices offer the following functions:
b protection of people against direct and indirect contacts b protection of installations against insulation faults b disconnection of on-load electric circuits, already protected against overloads and
short-circuits b automatic restart after insulation monitoring of the downstream circuit.
REDtest provides the following additional functions: b automatic and periodical test of the device, without breaking downstream circuit
(REDtest).Only used on TT and TN-S earthing grounding systems.
REDs 2P
REDtest
REDs 4P
IEC 61008, EN 61008
DB
1228
58 IMQ only for REDs, cat. no. 18687 and 18689
Country approval pictograms
Catalogue numbersREDs residual current circuit breakers REDsA type Width in mod.
of 9 mm2P Sensitivity 30 mA 300 mA
DB
1228
85 Rating 25 A 18687 18688 840 A 18689 1869063 A 18691 18692
Voltage rating (Ue) 230 VFrequency rating 50Hz4P Sensitivity 30 mA 300 mA
DB
1228
85 1 N 3 5 7
2 N 4 6 8
Rating 25 A 18264 18265 1440 A 18266 1826763 A 18268 18269
Voltage rating (Ue) 400 VFrequency rating 50 Hz
REDtest residual current circuit breakersA Type Width in mod.
of 9 mm2P Sensitivity 30 mA
DB
1228
89 Rating 25 A 18280 1040 A 18281
Voltage rating (Ue) 230 VFrequency rating 50 Hz
Residual current circuit breakers 2P 4PMaking and breaking capacity, rated residual current (Im = Im)
630 A 630 A
Breaking capacity in association with protection device
6000 A (gL 63 A) 10,000 A (gL 80 A)
CM902017E Version : 1.0 26/06/2012
DB
4045
26D
B40
4527
DB
1228
93
3
REDs, REDtestProtectEarth leakage protectionAutomatic recloser
Circuit-breaker (MCB)or Fuse (FU)
Fig. 1
Fig. 2
Coordination table, max short-circuit current (kA rms)Circuit-breakers, fuse / A type REDs, REDtest coordination
Circuit-breakers FuseDPN DPN N iC60 C120 NG125 gL 63 gL 80
REDs A type 2PNetwork 230 VL/N
25 A 6 6 10 10 10 6 -40 A 6 6 10 10 10 6 -63 A - - 10 10 10 6 -
REDs A type 4PNetwork 400 VL/N
25 A 6 10 10 10 10 - 1040 A 6 10 10 10 10 - 1063 A - 10 10 10 10 - 10
REDtest A type 2PNetwork 230 VL/N
25 A 6 6 6 6 6 6 -40 A 6 6 6 6 6 6 -
REDsREDtest
REDs /REDtest
REDs
MCB FU
OperationREDsThe REDs operates in the residual current device mode, without automatic restart,when the sliding cover is open, i.e. to the right in the Auto Off position (Fig. 1).
The automatic restart mode and the Autotest are activated, when the sliding cover isclosed, i.e. to the left in the Auto On position (Fig. 2).
Test
REDtest b The REDtest carries out automatic testing of earth leakage protection every
months.The test consists in opening and reclosing the REDtest, during which time continuity of supply of the downstream installation is guaranteed.Autotest: after checking installation insulation, the REDtest monitors its residual current device, without breaking the downstream power supply (bypass by bypass contact).
d This is only possible in manual mode, i.e. sliding cover open in the Auto Off position. You can then manually test the device by pressing the Test key. The downstream installation is then temporarily broken. You must then manually reclose the RED by activating the O-l lever to power supply the downstream circuit.
LED 1 LED 2Test good Green ON OFF Fault yellow ON OFF -
LED 1LED 2
b REDs 2P, 4P: supply from above or below
CM902017EVersion : 1.0 26/06/2012
DB
4045
27D
B40
4530
4
Operation ON mode: temporary network faultREDs, REDtest
ProtectEarth leakage protectionAutomatic recloser
REDs, REDtest
LED 1LED 2
The built-in automatic recloser automatically recloses the residual current deviceafter checking insulation of the downstream circuit.Rd: lower level of insulation resistance, if RRdo = reclose
10
1
0
1
0
t=5s
t
CM902017E Version : 1.0 26/06/2012
DB
4045
31
5
Operation ON mode: long network fault (cont.)REDtestIf the circuit is faulty for a length of time "greater than 5 seconds", the switch is prohibited from reclosing.
b The installation is faulty: the earth resistance is lower than Rd.
ProtectEarth leakage protectionAutomatic recloser
REDs, REDtest
In 30 mARd 30 kRdo 70 k
1
01
01
0
t=5s1
0TestLED
LED 1
Default
Connection
DB
1239
47 Type Tighteningtorque
Copper cablesRigid Flexible or
ferrule
N, L 2 N.m 35 mm2 35 mm2
DB
4045
35 AUX 0.4 N.m 2.5 mm2 2.5 mm2
Connection by tunnel terminal with guard
DB
1229
45
DB
1229
46
3.5 / 5.5 mm12 mm
9 mm
PZ1 /PZ2
PH0
CM902017EVersion : 1.0 26/06/2012
DB
4045
33
6
ProtectEarth leakage protectionAutomatic recloser
REDs, REDtest
DB
4045
34D
B40
4532
AUX
AUX
LN
L1L2L3N
N
N
1 3
N1 3 5 7
2 4
N2 4 6 8
LOAD
LOAD
LINE
LINE
L N
L N
REDs2P
REDs4P
REDtest
LN
N
AUX
NL
N
N
1 3
2 4
NL
L N
L N
N L1 L2L3
N L1L2L3
N L
N L
Load
Wiring of non-polarized white wires
Wiring of non-polarized white wires
Load
Load
5...230 V a / cmax: 100 mA cos = 1
5...230 V a / cmax: 100 mA cos = 1
CM902017E Version : 1.0 26/06/2012
DB
1233
10D
B12
3314
7
ProtectEarth leakage protectionAutomatic recloser
REDs, REDtest
Technical data.Main characteristics 2P 4PCommon technical data REDs, REDtest REDs
Earthing grounding systems TT and TN-S onlyImpulse withstand voltage (Uimp) 4 kVInsulation voltage (Ui) 500 V8/20 s wave immunity level 250 Tropicalisation Treatment 2 (relative humidity: 95 % at 55C)Operating temperature -5C to +40CStorage temperature -20C to +60CProtection class IP20 at terminalsAdditional characteristicsResidual current device
Tripping time In: y 300 ms5 In: y 40 ms
Number of cycles (O-C) 1 000 4 000Fixed sensitivity releases for all ratings Instantaneous releaseTest button min operating voltage b 100 V
b 195 V (REDtest)170 V
RecloserMax duration of a restart cycle 90 s < 10 sMaximum number of consecutive restart attempts (if no earth fault)
3
Min interval between 2 closings 180 s 30 sInsulation fault presence monitoring YesRestart in event of transient insulation fault YesStopping restart cycle if insulation fault present
b Yes, during 15 minutes b Yes (REDtest)
Not operating resistance to earth (Rd) 8 k (30 mA), 2.5 k (300 mA)Operating resistance to earth (Rdo) 16 k (30 mA), 5 k (300 mA)Power consumed by the electronics b REDs: 0 VA
b REDtest: 8 VAIndication
REDs status indication Mechanical:by O-l (open-closed) 2-position lever
b Electrical: by 2 indicator lights on the front panel:
v left: red/yellow LED v right: green LED
Remote: by 1 built-in auxiliary contactAuxiliary contact
Voltage rating (Ue) 5...230 V AC/DCInsulation voltage (Ui) 350 VCurrent rating (ln) Min: 0.6 mA
Max: 100 mA, power factor = 1Type Configurable: intermittent 1 Hz or NOConnection by tunnel terminal Flexible or rigid cable: max 2.5 mm2
DB
1233
12
IP20 IP40
Clip on DIN rail 35 mm.
Indifferent position of installation.
CM902017EVersion : 1.0 26/06/20128
Weight (g)Reclosers 2P 4P
REDs 360 b 25/40 A: 670 b 63 A: v 30 mA: 720 v 300 mA: 680
REDtest 370 -
Dimensions (mm)D
B11
6691
REDs 2P
DB
1166
92
REDs 4P
DB
1097
99
REDtest
ProtectEarth leakage protectionAutomatic recloser
REDs, REDtest
CM902017E Version : 1.0 26/06/2012 9