Upload
adil-rezouk
View
234
Download
0
Embed Size (px)
Citation preview
7/29/2019 Motor Controls Troubleshooting of Electric Motors
1/34
Motor Controls &
Troubleshooting of ElectricMotors
7/29/2019 Motor Controls Troubleshooting of Electric Motors
2/34
Introduction to Motor Controls
Devices that pass power to the motor
1. Relays
2. Contactors
3. Starters
The contacts are controlled by a coil in the control circuit
The starting relay is only in the circuit for a short period of time
The type of motor control device is determined by the size of the motor
7/29/2019 Motor Controls Troubleshooting of Electric Motors
3/34
Run-load and Locked-rotor current
Run load amperage (RLA)
1. Also called full load amperage (FLA)
2. Current drawn while the motor is running
Locked rotor amperage (LRA)
1. Amperage drawn at start-up
2. Approximately five times the RLA
Both currents must be considered when selecting a control
device
7/29/2019 Motor Controls Troubleshooting of Electric Motors
4/34
Relays
Relay
Uses a magnetic coil to close one or more sets of contacts.
Cannot be repaired considered a throw a away device.
Used for light duty applications
Can be used as a pilot duty relay (A relay used for switching loads such as another relay or
solenoid valve coils. The pilot duty relay contacts are located in a second control circuit. Pilot
duty relays are rated in volt-amperes (VA).)
The contacts must be able to handle the current draw of the load
Can have normally-open (NO) contacts, normally-closed (NC) contacts, or both normally open
and normally closed contacts
7/29/2019 Motor Controls Troubleshooting of Electric Motors
5/34
Relays, Contactors, & Starters
http://www.calcentron.com/PDF_Documents/AEG_PDF/aeg_starters_pdf/aeg_mini-relays_sh04.pdfhttp://www.dnagroup.com/cgi-bin/view_services.cgi?request=detail&prod_num=2-POLE&aisle_id=24http://www.dnagroup.com/cgi-bin/view_services.cgi?request=detail&prod_num=1-POLE&aisle_id=23http://www.temcocontrols.com/images/mr3000.jpg7/29/2019 Motor Controls Troubleshooting of Electric Motors
6/34
Contactor
Larger versions of the relay
Has moveable and stationary contacts
Holding coils of different voltage ratings are available
Can have one or more sets of contacts
Some are equipped with auxiliary contacts
Use exact replacement whenever possible
7/29/2019 Motor Controls Troubleshooting of Electric Motors
7/34
Motor Starters
Described as a contactor with overload protection built in
Can be rebuilt
1. Should be replaced when the become pitted
2. Heaters and holding coils can also be replaced As the contacts become pitted the resistance increases
7/29/2019 Motor Controls Troubleshooting of Electric Motors
8/34
Motor Protection
Because of the cost of electric motors they need to be protected from
damage Fuses protect the entire circuit, not the components
Motors can operate at a slightly higher current for a short period of time
Very small motors do not have overload protection
The larger the motor, the more elaborate the protection should be
Motor protection can be inherent (internal) or external
7/29/2019 Motor Controls Troubleshooting of Electric Motors
9/34
Inherent (Internal) Motor Protection
Internal thermal overloads, OR
Thermally activated bimetal snap disc
7/29/2019 Motor Controls Troubleshooting of Electric Motors
10/34
External Motor Protection
Devices that pass power to the holding coil of the starter or contactor
The device can open its contacts when a current overload occurs, causingthe holding coil to de-energize
The trip point and type of overload protection is determined by the
manufacturer
The overload protection takes the service factor into consideration
Phase monitoring devices that shut down power if leg is lost to prevent
single phasing three phase motors
7/29/2019 Motor Controls Troubleshooting of Electric Motors
11/34
Temperature Sensing Devices
Bi-metal element
1. Heated by a device called a heater
2. The heater is in series with the load and senses the load current
3. The bimetal warps when it becomes too warm
4. The bimetal interrupts the circuit feeding the holding coil of the starter
Solder pot
1. Uses a low-melting solder
2. The solder melts when excessive heat is generated
3. The excessive heat is generated from an over-current condition
7/29/2019 Motor Controls Troubleshooting of Electric Motors
12/34
Magnetic Overload Devices
Not attached to the starter
Not affected by ambient temperature
Very accurate overload device
7/29/2019 Motor Controls Troubleshooting of Electric Motors
13/34
Restarting the Motor
If a motor shuts off on a safety, it should not beimmediately restarted
The cause for the overload must be found
The motor must be given enough time to cooldown
Many control circuits have manual resets to
prevent automatic restarting Some controls reset only after a pre-determied
time period
Time delay devices prevent the unit from short
cycling
7/29/2019 Motor Controls Troubleshooting of Electric Motors
14/34
Electric Motor Troubleshooting
Problems are either mechanical or electrical
Mechanical problems often appear to be electrical problems
Technicians must be able to diagnose the problems correctly
7/29/2019 Motor Controls Troubleshooting of Electric Motors
15/34
Mechanical Motor Problems
Normally occur in the bearings or drive connection
Bearing Failure (tight or worn)
1. Lack of lubrication
2. Excessive grit in the bearing
3. Over-tight belts
7/29/2019 Motor Controls Troubleshooting of Electric Motors
16/34
Removing Drive Assemblies
Pulley, coupling, or fan wheel must be removed from a motor
shaft with care
1. The fit can be very tight
2. The assembly must not be damaged
3. Special pulley pullers can be used
Set screws are tightened to the motor shaft
1. Set screw is made of hardened steel
2. Tightened to the flat portion of the shaft
The end of the motor shaft should not be hammered
7/29/2019 Motor Controls Troubleshooting of Electric Motors
17/34
Removing Drive Assemblies
7/29/2019 Motor Controls Troubleshooting of Electric Motors
18/34
Belt Tension
Over-tightened can cause motor failure and or bearing damage
A belt tension gauge should be used
7/29/2019 Motor Controls Troubleshooting of Electric Motors
19/34
Pulley Alignment
Drive and driven pulleys should be properly aligned
Drive mechanisms can become damaged
Belt life can be reduced
Belts can skip off the pulleys
7/29/2019 Motor Controls Troubleshooting of Electric Motors
20/34
Electrical Problems
Easy to diagnose
Motor may smell burned
An open motor winding
A short circuit from the winding to ground
A short circuit from winding to winding
7/29/2019 Motor Controls Troubleshooting of Electric Motors
21/34
Open Windings
Can be found with an ohmmeter
There should be a measurable resistance between the common,
start, and run terminals
A reading of infinite resistance is an indication that the winding
is open
7/29/2019 Motor Controls Troubleshooting of Electric Motors
22/34
Shorted Motor Windings
Caused when winding insulation develops a hole
An alternative current path is created
This path reduces the resistance of the winding
The current flow through the winding will increase
1. Motor overload may trip
2. Circuit breaker may trip
Short in the run winding
1. Motor may start
2. Motor will draw excessive current
Short in the start winding
1. Motor may not start
2. If it does start it will draw excessive current on start-up
Three-phase motor windings should all have the same resistance
h d
7/29/2019 Motor Controls Troubleshooting of Electric Motors
23/34
Short Circuit to Ground (Frame)
There should be no detectable circuit from a winding to ground
Motors should be checked for grounds using a good quality ground
ohmmeter
1. The meter should be set to its highest setting
2. Megohmmeters (megger) can detect 10,000,000 ohm range
Dirty motors may show resistance from winding to ground if the
atmosphere is damp
Hermetic compressors may show a slight ground1. The oil may be dirty
2. Liquid refrigerant in the compressor worsens the condition
3. A suction line drier may help clean the oil
7/29/2019 Motor Controls Troubleshooting of Electric Motors
24/34
Single-Phase Motor Starting Problems
Fairly easy to troubleshoot
Check for full power to motor
1. Low voltage
2. Loose connection
3. Undersized wire
4. Low voltage from electrical panel
5. Measure voltage at the motor terminals
6. Voltage must be within 10% of rated voltage
7/29/2019 Motor Controls Troubleshooting of Electric Motors
25/34
Open Motors
Checked with voltage supplied to both windings
Start windings is removed when motor reaches 75% of rated
speed
Uses centrifugal switch
The opening and closing of the switch can be heard
7/29/2019 Motor Controls Troubleshooting of Electric Motors
26/34
CSCR Motors
Have the start winding energized all the time
The start capacitor stays in the circuit whenever the
motor is energized
7/29/2019 Motor Controls Troubleshooting of Electric Motors
27/34
Symptoms of Electric Motor Starting Problems
Motor hums and then shuts off
Motor runs for a short period and shuts off
Motor will not try to start
7/29/2019 Motor Controls Troubleshooting of Electric Motors
28/34
Types of Problems to Consider
Motor mechanical problem
Electrical problem
Motor circuit problem
Motor load problem
If motor and load turn freely, technician should check motor windings
If motor hums and does not start, starting components should be checked
7/29/2019 Motor Controls Troubleshooting of Electric Motors
29/34
Checking Capacitors
Capacitors can be checked with an analog ohmmeter
Ohmmeter leads placed across a charged capacitor can cause
damage to the meter
7/29/2019 Motor Controls Troubleshooting of Electric Motors
30/34
Procedure for Checking Capacitors
Turn power off to the and remove capacitor lead
Short across a charged capacitor
Set ohmmeter to the R X 10 scale
Touch meter leads to capacitor terminals
A good capacitor would show the ohmmeter needle sweeping up to zero (0) ohms value and begin to
fall back toward infinity Internal shorted capacitors needle will sweep to (0) ohms value and fall back toward infinity
If the ohmmeter needle will not rise at all, switch the meter leads on the capacitor and look for a needle
deflection that rises and returns to infinity
No meter scale reading indicates an open capacitor
If the capacitor has a bleed resistor, the ohmmeter will sweep to 0 ohms and fall back to the resistance
value of the bleed resistor.
7/29/2019 Motor Controls Troubleshooting of Electric Motors
31/34
Identification of Capacitors
Run Capacitors
1. Metal case
2. Oil filled
3. If the capacitor swells, it should be replaced
4. Have identified terminals which should be connected to the start terminals
Start capacitors1. Dry tape
2. Encased in plastic (bakelite)
3. Older capacitors should be encased in paper
Over current can cause the vent at the top to bulge If the capacitor pops it should be replaced
7/29/2019 Motor Controls Troubleshooting of Electric Motors
32/34
7/29/2019 Motor Controls Troubleshooting of Electric Motors
33/34
Wiring and Connectors
Wiring must be in good condition
Loose connections
1. Can cause oxidation
2. Oxidation causes an increase in resistance
3. Resistance creates heat
4. Could result in low voltage at the motor5. Low voltage at the motor can result in higher motor amperage draws
7/29/2019 Motor Controls Troubleshooting of Electric Motors
34/34
Troubleshooting Hermetic Motors
Can only be checked electrically from the outside
Can have the same problems as open motors
1. Grounded circuit
2. Open circuit
3. Short circuit
Starting components must also be checked