sensors Article Monitoring of Grouting Compactness in a Post-Tensioning Tendon Duct Using Piezoceramic Transducers Tianyong Jiang 1,† , Qingzhao Kong 2,† , Wenxi Wang 3 , Linsheng Huo 4 and Gangbing Song 2, * 1 College of Civil Engineering and Architecture, Changsha University of Science and Technology, Changsha 410114, China; [email protected] 2 Department of Mechanical Engineering, University of Houston, Houston, TX 77004, USA; [email protected] 3 College of Civil Engineering, Hunan University, Changsha 410082, China; [email protected] 4 School of Civil Engineering, Dalian University of Technology, Dalian 116024, China; [email protected] * Correspondence: [email protected]; Tel.: +1-713-743-4525 The co-first author Dr. Jiang and Dr. Kong have equal contribution to this manuscript as co-first authors. Academic Editors: Dipen N. Sinha and Cristian Pantea Received: 13 July 2016; Accepted: 17 August 2016; Published: 22 August 2016 Abstract: A post-tensioning tendon duct filled with grout can effectively prevent corrosion of the reinforcement, maintain bonding behavior between the reinforcement and concrete, and enhance the load bearing capacity of concrete structures. In practice, grouting of the post-tensioning tendon ducts always causes quality problems, which may reduce structural integrity and service life, and even cause accidents. However, monitoring of the grouting compactness is still a challenge due to the invisibility of the grout in the duct during the grouting process. This paper presents a stress wave-based active sensing approach using piezoceramic transducers to monitor the grouting compactness in real time. A segment of a commercial tendon duct was used as research object in this study. One lead zirconate titanate (PZT) piezoceramic transducer with marble protection, called a smart aggregate (SA), was bonded on the tendon and installed in the tendon duct. Two PZT patch sensors were mounted on the top outside surface of the duct, and one PZT patch sensor was bonded on the bottom outside surface of the tendon duct. In the active sensing approach, the SA was used as an actuator to generate a stress wave and the PZT sensors were utilized to detect the wave response. Cement or grout in the duct functions as a wave conduit, which can propagate the stress wave. If the cement or grout is not fully filled in the tendon duct, the top PZT sensors cannot receive much stress wave energy. The experimental procedures simulated four stages during the grout pouring process, which includes empty status, half grouting, 90% grouting, and full grouting of the duct. Experimental results show that the bottom PZT sensor can detect the signal when the grout level increases towards 50%, when a conduit between the SA and PZT sensor is formed. The top PZT sensors cannot receive any signal until the grout process is completely finished. The wavelet packet-based energy analysis was adopted in this research to compute the total signal energy received by PZT sensors. Experimental results show that the energy levels of the PZT sensors can reflect the degree of grouting compactness in the duct. The proposed method has the potential to be implemented to monitor the tendon duct grouting compactness of the reinforced concrete structures with post tensioning. Keywords: lead zirconate titanate (PZT); smart aggregate; reinforced concrete; post-tensioning tendon duct; grout; grouting compactness 1. Introduction With the widespread use of reinforced concrete structures using post-tensioning tendons, there is a potential problem during construction: the tendon duct may not be fully grouted. This results in Sensors 2016, 16, 1343; doi:10.3390/s16081343 www.mdpi.com/journal/sensors

Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

sensors

Article

Monitoring of Grouting Compactness ina Post-Tensioning Tendon Duct UsingPiezoceramic TransducersTianyong Jiang 1,†, Qingzhao Kong 2,†, Wenxi Wang 3, Linsheng Huo 4 and Gangbing Song 2,*

1 College of Civil Engineering and Architecture, Changsha University of Science and Technology,Changsha 410114, China; [email protected]

2 Department of Mechanical Engineering, University of Houston, Houston, TX 77004, USA; [email protected] College of Civil Engineering, Hunan University, Changsha 410082, China; [email protected] School of Civil Engineering, Dalian University of Technology, Dalian 116024, China; [email protected]* Correspondence: [email protected]; Tel.: +1-713-743-4525† The co-first author Dr. Jiang and Dr. Kong have equal contribution to this manuscript as co-first authors.

Academic Editors: Dipen N. Sinha and Cristian PanteaReceived: 13 July 2016; Accepted: 17 August 2016; Published: 22 August 2016

Abstract: A post-tensioning tendon duct filled with grout can effectively prevent corrosion of thereinforcement, maintain bonding behavior between the reinforcement and concrete, and enhance theload bearing capacity of concrete structures. In practice, grouting of the post-tensioning tendon ductsalways causes quality problems, which may reduce structural integrity and service life, and even causeaccidents. However, monitoring of the grouting compactness is still a challenge due to the invisibilityof the grout in the duct during the grouting process. This paper presents a stress wave-based activesensing approach using piezoceramic transducers to monitor the grouting compactness in real time.A segment of a commercial tendon duct was used as research object in this study. One lead zirconatetitanate (PZT) piezoceramic transducer with marble protection, called a smart aggregate (SA), wasbonded on the tendon and installed in the tendon duct. Two PZT patch sensors were mounted onthe top outside surface of the duct, and one PZT patch sensor was bonded on the bottom outsidesurface of the tendon duct. In the active sensing approach, the SA was used as an actuator to generatea stress wave and the PZT sensors were utilized to detect the wave response. Cement or grout inthe duct functions as a wave conduit, which can propagate the stress wave. If the cement or grout isnot fully filled in the tendon duct, the top PZT sensors cannot receive much stress wave energy. Theexperimental procedures simulated four stages during the grout pouring process, which includesempty status, half grouting, 90% grouting, and full grouting of the duct. Experimental results showthat the bottom PZT sensor can detect the signal when the grout level increases towards 50%, when aconduit between the SA and PZT sensor is formed. The top PZT sensors cannot receive any signaluntil the grout process is completely finished. The wavelet packet-based energy analysis was adoptedin this research to compute the total signal energy received by PZT sensors. Experimental resultsshow that the energy levels of the PZT sensors can reflect the degree of grouting compactness in theduct. The proposed method has the potential to be implemented to monitor the tendon duct groutingcompactness of the reinforced concrete structures with post tensioning.

Keywords: lead zirconate titanate (PZT); smart aggregate; reinforced concrete; post-tensioningtendon duct; grout; grouting compactness

1. Introduction

With the widespread use of reinforced concrete structures using post-tensioning tendons, there isa potential problem during construction: the tendon duct may not be fully grouted. This results in

Sensors 2016, 16, 1343; doi:10.3390/s16081343 www.mdpi.com/journal/sensors

Page 2: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 2 of 13

voids or inefficient protection for the steel tendons. Over the long term, water may enter the tendonducts in the voids, resulting in corrosion of the tendons [1,2]. Therefore, to guarantee the durabilityof reinforced concrete structures with post-tensioning tendons, the tendon ducts must be completelyfilled with concrete to avoid water intrusion and corrosion of steel tendons.

Non-destructive inspection of ducts plays a critical role in the quality assurance of construction [3].Non-destructive testing (NDT) techniques, including ultrasonic, impact-echo (IE), ground penetratingradar (GPR), are presented by Muldoon et al. for the investigation of tendon ducts [4]. Wang et al.applied ultrasonic method to detect the grouting quality of pre-stressed corrugated ducts [5].The defects were set in the duct, including empty duct, 1/4 grouting, half grouting, 3/4 groutingand full grouting. The results showed that the quality of duct grouting can be effectively evaluatedby ultrasonic detection. Krause et al. described the use of an ultrasonic array system combinedwith 3D reconstruction computation [6]. This system was applied to the examination of transversalducts in a bridge plate. Schickert et al. adopted the synthetic aperture focusing technique (SAFT)of ultrasonic reconstruction to detect the tendon ducts containing faults [7]. Muldoon et al. tested aseries of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University ofEdinburgh using a range of NDT techniques including impact-echo (I-E), stack imaging of spectralamplitudes based on the impact-echo (SIBIE) and ultrasonic tomography [4]. Yamada et al. developedthe Stack Imaging of Spectral Amplitudes Based on Impact-Echo (SIBIE) procedure to improve theimpact-echo method [2]. It was demonstrated that the non-grouted tendon-duct can be identified withreasonable accuracy by the SIBIE procedure. Maierhofer showed the recent applications of groundpenetrating radar (GPR) at frequencies from 500 MHz to 2.5 GHz for detection of different defects inconcrete structures [8]. The technique is well suited for locating tendon ducts at depths up to 50 cm,and to detecting voids and detachments. Another application of GPR is presented by Bungey et al.,who adopted the GPR based method to monitor the grouting deficiencies in the suggested non-metallicducts [9]. In general, the existing research on detection of grout quality requires bulky tools andequipment, and the reported methods are not suitable for real time monitoring, which motivatesus to develop a low-cost and real-time method to monitor the grouting process and to evaluate thegrouting compactness.

With the advantages of availability in different shapes, high bandwidth, low price, and the abilityto be employed as an actuator and sensor simultaneously, the lead zirconate titanate (PZT)-basedactive sensing approach has been widely recognized as one of the most promising structural healthmonitoring (SHM) techniques [10–17]. In additional, a numerical modelling of PZT-based structuralhealth monitoring has also been studied [18]. To further use PZT material for practical applicationsof structural damage evaluation, Chalioris et al. proposed a wireless admittance monitoring systemto detect damage to reinforced concrete steel bars [19]. Due to the fragility of PZT material, Songet al. developed a PZT-based multi-functional smart aggregate (SA), which can be deployed in adistributed fashion, for SHM of concrete structures in recent years [20–22]. A proposed wavelet packetenergy index was verified to be effective in the experimental study on CFST (concrete-filled steeltube) specimens with artificially simulated debonding using PZT patches and SAs [23,24]. Wu et al.performed an investigation to detect debonding in reinforced concrete structures utilizing built-inpiezoelectric discs as sensors and actuators in a pitch-catch mode [25,26]. Qin et al. developed anactive sensing approach using smart aggregates (SAs) to detect the initiation and to monitor thedevelopment of bond-slip of steel plate concrete beams [27]. Chalioris et al. applied impedance-basedtechnology and analyzed the smart aggregates’ admittance signatures that can successfully evaluatethe damage levels in the shear-critical reinforced concrete beam [28]. The SAs can be utilized as bothactuator and sensor by taking advantage of the piezoelectricity of piezoceramic material. Hence, theproposed smart aggregates are capable of performing comprehensive monitoring of concrete structures,including early age strength monitoring [29], impact detection and evaluation [20], and structuralhealth monitoring [21].

Page 3: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 3 of 13

This paper proposes a stress wave-based active sensing approach using piezoceramic transducersto monitor the grouting compactness of post-tensioning tendon duct for reinforced concrete structures.The proposed method is capable of monitoring the grouting compactness in real time. In the proposedmethod, one PZT-based SA, which was bonded on the tendon, was utilized as an actuator. Meanwhile,three waterproofed PZT patches used as sensors were mounted on the top and bottom surfaces(outside) of a tendon duct before casting. Grout in the duct functions as the wave conduit which allowsthe passage of the stress wave. If the duct is 100% filled with the grout, the stress wave generatedby the SA will propagate to reach both the top and bottom surfaces of the tendon duct via the grout.However, without the presence of any grout, the stress wave will fail to reach either the top or thebottom of the duct. With partially filled grout, the stress wave may reach or fail to reach one or bothof the top or bottom surface of the duct. In addition, the wavelet packet-based energy analysis wasadopted in this research to compute the total signal energy received by PZT sensors. In this research,four different grout stages, including empty, half grouting, 90% grouting, and full grouting, wereexperimentally studied. In order to simulate these four situations in one specimen, the grout waspoured to reach each stage in the increment of five days. The eventual 100% grouting condition can beconfirmed when the PZT sensors on the top surface of the duct detect the stress wave and report highlevels of energy.

2. Piezoceramic Transducers

2.1. Compressive Mode PZT Transducers

Piezoelectric material generates electric charge when subjected to a stress or strain (the directpiezoelectric effect) and also produces a stress or strain when an electric field is applied in the poleddirection (the converse piezoelectric effect). Lead zirconate titanate (PZT) is one of the most commonlyused piezoelectric materials and can be cut into small sizes as sensors. An often used shape is thepatch, as shown in Figure 1. The structure of the PZT patch is shown in Figure 2. When PZT patch is incompression mode, it can expand and shrink along the poling direction corresponding to the appliedvoltage, as shown in Figure 3. In recent years, PZT sensors have been employed in many applicationsof structural health monitoring. Wang et al. monitored the bolt loosening in the two-plated structureusing PZT patches and presented the degree of bolt lessening by the calculated signal energy [12].Du et al. mounted distributed PZT patches on a pipeline segment to detect the crack severity using thedeveloped crack damage index [30].

Sensors 2016, 16, 1343 3 of 13

structures, including early age strength monitoring [29], impact detection and evaluation [20], and structural health monitoring [21].

This paper proposes a stress wave-based active sensing approach using piezoceramic transducers to monitor the grouting compactness of post-tensioning tendon duct for reinforced concrete structures. The proposed method is capable of monitoring the grouting compactness in real time. In the proposed method, one PZT-based SA, which was bonded on the tendon, was utilized as an actuator. Meanwhile, three waterproofed PZT patches used as sensors were mounted on the top and bottom surfaces (outside) of a tendon duct before casting. Grout in the duct functions as the wave conduit which allows the passage of the stress wave. If the duct is 100% filled with the grout, the stress wave generated by the SA will propagate to reach both the top and bottom surfaces of the tendon duct via the grout. However, without the presence of any grout, the stress wave will fail to reach either the top or the bottom of the duct. With partially filled grout, the stress wave may reach or fail to reach one or both of the top or bottom surface of the duct. In addition, the wavelet packet-based energy analysis was adopted in this research to compute the total signal energy received by PZT sensors. In this research, four different grout stages, including empty, half grouting, 90% grouting, and full grouting, were experimentally studied. In order to simulate these four situations in one specimen, the grout was poured to reach each stage in the increment of five days. The eventual 100% grouting condition can be confirmed when the PZT sensors on the top surface of the duct detect the stress wave and report high levels of energy.

2. Piezoceramic Transducers

2.1. Compressive Mode PZT Transducers

Piezoelectric material generates electric charge when subjected to a stress or strain (the direct piezoelectric effect) and also produces a stress or strain when an electric field is applied in the poled direction (the converse piezoelectric effect). Lead zirconate titanate (PZT) is one of the most commonly used piezoelectric materials and can be cut into small sizes as sensors. An often used shape is the patch, as shown in Figure 1. The structure of the PZT patch is shown in Figure 2. When PZT patch is in compression mode, it can expand and shrink along the poling direction corresponding to the applied voltage, as shown in Figure 3. In recent years, PZT sensors have been employed in many applications of structural health monitoring. Wang et al. monitored the bolt loosening in the two-plated structure using PZT patches and presented the degree of bolt lessening by the calculated signal energy [12]. Du et al. mounted distributed PZT patches on a pipeline segment to detect the crack severity using the developed crack damage index [30].

Figure 1. The photo of two PZT patches. Figure 1. The photo of two PZT patches.

Page 4: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 4 of 13Sensors 2016, 16, 1343 4 of 13

(a) (b)

Figure 2. The two drawings of the PZT patch: (a) Top view; (b) Front view.

(a) (b)

Figure 3. Schematic of PZT patch with compressive mode: (a) 3D view; (b) Front view.

2.2. Smart Aggregates

For the sake of protecting a fragile PZT patch which could work in concrete, a smart aggregate (SA) was designed by sandwiching a waterproofed PZT patch with two marble protections. A Bayonet Neill-Concelman (BNC) connector is made at the end of the wires to connect the SA with the sensing instrument. The structure of a SA including the schematic and the photo is shown in Figure 4. Benefiting from the extraordinary physical properties of marble material, SAs can be safely embedded in a concrete structure, and perform long-term structural health monitoring. Several applications of SAs in structural health monitoring have been reported in recent years [23,31].

(a)

(b)

Figure 4. The structure of a smart aggregator: (a) Schematic; (b) A photo of SA with a BNC connector.

3. Detection Principles

3.1. Active Sensing Approach

In this research, an active sensing approach using PZT transducers is developed to monitor the grouting compactness in post-tensioning tendon duct. The schematic principle is shown in Figure 5. The SA in the post-tensioning tendon duct functions as an actuator to generate stress waves. If the duct is 100% filled with the grout, the stress wave will propagate to reach both the top and bottom surfaces of the tendon duct via the grout. However, without the presence of any grout or cement, the stress wave will fail to reach either the top or the bottom surfaces of the duct. With partial grout, the stress wave may reach or fail to reach one or both of the top or bottom surface of the duct. To enable

Figure 2. The two drawings of the PZT patch: (a) Top view; (b) Front view.

Sensors 2016, 16, 1343 4 of 13

(a) (b)

Figure 2. The two drawings of the PZT patch: (a) Top view; (b) Front view.

(a) (b)

Figure 3. Schematic of PZT patch with compressive mode: (a) 3D view; (b) Front view.

2.2. Smart Aggregates

For the sake of protecting a fragile PZT patch which could work in concrete, a smart aggregate (SA) was designed by sandwiching a waterproofed PZT patch with two marble protections. A Bayonet Neill-Concelman (BNC) connector is made at the end of the wires to connect the SA with the sensing instrument. The structure of a SA including the schematic and the photo is shown in Figure 4. Benefiting from the extraordinary physical properties of marble material, SAs can be safely embedded in a concrete structure, and perform long-term structural health monitoring. Several applications of SAs in structural health monitoring have been reported in recent years [23,31].

(a)

(b)

Figure 4. The structure of a smart aggregator: (a) Schematic; (b) A photo of SA with a BNC connector.

3. Detection Principles

3.1. Active Sensing Approach

In this research, an active sensing approach using PZT transducers is developed to monitor the grouting compactness in post-tensioning tendon duct. The schematic principle is shown in Figure 5. The SA in the post-tensioning tendon duct functions as an actuator to generate stress waves. If the duct is 100% filled with the grout, the stress wave will propagate to reach both the top and bottom surfaces of the tendon duct via the grout. However, without the presence of any grout or cement, the stress wave will fail to reach either the top or the bottom surfaces of the duct. With partial grout, the stress wave may reach or fail to reach one or both of the top or bottom surface of the duct. To enable

Figure 3. Schematic of PZT patch with compressive mode: (a) 3D view; (b) Front view.

2.2. Smart Aggregates

For the sake of protecting a fragile PZT patch which could work in concrete, a smart aggregate(SA) was designed by sandwiching a waterproofed PZT patch with two marble protections. A BayonetNeill-Concelman (BNC) connector is made at the end of the wires to connect the SA with the sensinginstrument. The structure of a SA including the schematic and the photo is shown in Figure 4.Benefiting from the extraordinary physical properties of marble material, SAs can be safely embeddedin a concrete structure, and perform long-term structural health monitoring. Several applications ofSAs in structural health monitoring have been reported in recent years [23,31].

Sensors 2016, 16, 1343 4 of 13

(a) (b)

Figure 2. The two drawings of the PZT patch: (a) Top view; (b) Front view.

(a) (b)

Figure 3. Schematic of PZT patch with compressive mode: (a) 3D view; (b) Front view.

2.2. Smart Aggregates

For the sake of protecting a fragile PZT patch which could work in concrete, a smart aggregate (SA) was designed by sandwiching a waterproofed PZT patch with two marble protections. A Bayonet Neill-Concelman (BNC) connector is made at the end of the wires to connect the SA with the sensing instrument. The structure of a SA including the schematic and the photo is shown in Figure 4. Benefiting from the extraordinary physical properties of marble material, SAs can be safely embedded in a concrete structure, and perform long-term structural health monitoring. Several applications of SAs in structural health monitoring have been reported in recent years [23,31].

(a)

(b)

Figure 4. The structure of a smart aggregator: (a) Schematic; (b) A photo of SA with a BNC connector.

3. Detection Principles

3.1. Active Sensing Approach

In this research, an active sensing approach using PZT transducers is developed to monitor the grouting compactness in post-tensioning tendon duct. The schematic principle is shown in Figure 5. The SA in the post-tensioning tendon duct functions as an actuator to generate stress waves. If the duct is 100% filled with the grout, the stress wave will propagate to reach both the top and bottom surfaces of the tendon duct via the grout. However, without the presence of any grout or cement, the stress wave will fail to reach either the top or the bottom surfaces of the duct. With partial grout, the stress wave may reach or fail to reach one or both of the top or bottom surface of the duct. To enable

Figure 4. The structure of a smart aggregator: (a) Schematic; (b) A photo of SA with a BNC connector.

3. Detection Principles

3.1. Active Sensing Approach

In this research, an active sensing approach using PZT transducers is developed to monitor thegrouting compactness in post-tensioning tendon duct. The schematic principle is shown in Figure 5.The SA in the post-tensioning tendon duct functions as an actuator to generate stress waves. If theduct is 100% filled with the grout, the stress wave will propagate to reach both the top and bottomsurfaces of the tendon duct via the grout. However, without the presence of any grout or cement, thestress wave will fail to reach either the top or the bottom surfaces of the duct. With partial grout, thestress wave may reach or fail to reach one or both of the top or bottom surface of the duct. To enable

Page 5: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 5 of 13

the monitoring of the grouting compactness, two PZT sensors mounted on the outside surface of thetendon duct are used as sensors to detect the wave response. As seen in Figure 5, four different groutstages were simulated: empty, half grouting, 90% grouting, and full grouting. In order to simulatethese four situations in one specimen, the grout was poured to reach each stage in an increment offive days. When the tendon duct is empty, there is no medium to allow the waves to travel from theSA to reach one of the PZT sensors. As the grout level increases towards approximately 50%, thereis enough grout to allow the passage of the waves to reach from the SA to the bottom PZT sensor.At this point, however, the top PZT sensor still does not receive much signal, except for negligibleamounts that may propagate through the newly poured grout to the walls of the tendon duct. The topPZT sensor will continue to receive small increases in the signal strength until the grout fully fills thetendon duct, whereupon the top PZT sensor can receive the signals generated by the SA through thepoured grout. Therefore, in effect, two milestones can be inferred from the PZT sensors. In the firstmilestone, only the bottom PZT sensor receives the SA signal, indicating that the duct is filled by 50%grout. To reach the second milestone, both the top and bottom PZT sensors receive the signal withhigh strength, finally indicating that the tendon duct has been 100% filled with grout.

Sensors 2016, 16, 1343 5 of 13

the monitoring of the grouting compactness, two PZT sensors mounted on the outside surface of the tendon duct are used as sensors to detect the wave response. As seen in Figure 5, four different grout stages were simulated: empty, half grouting, 90% grouting, and full grouting. In order to simulate these four situations in one specimen, the grout was poured to reach each stage in an increment of five days. When the tendon duct is empty, there is no medium to allow the waves to travel from the SA to reach one of the PZT sensors. As the grout level increases towards approximately 50%, there is enough grout to allow the passage of the waves to reach from the SA to the bottom PZT sensor. At this point, however, the top PZT sensor still does not receive much signal, except for negligible amounts that may propagate through the newly poured grout to the walls of the tendon duct. The top PZT sensor will continue to receive small increases in the signal strength until the grout fully fills the tendon duct, whereupon the top PZT sensor can receive the signals generated by the SA through the poured grout. Therefore, in effect, two milestones can be inferred from the PZT sensors. In the first milestone, only the bottom PZT sensor receives the SA signal, indicating that the duct is filled by 50% grout. To reach the second milestone, both the top and bottom PZT sensors receive the signal with high strength, finally indicating that the tendon duct has been 100% filled with grout.

(a) (b)

(c) (d)

Figure 5. Principle of active sensing approach in monitoring of grouting compactness: (a) Empty duct; (b) Half grouting; (c) 90% grouting; (d) Full grouting.

3.2. Wavelet Packet-Based Energy Analysis

To evaluate the energy of the stress wave received by PZT sensors, the wavelet packet-based analysis is applied to provide the computed energy values of the signal received by PZT sensors. In the wavelet packet-based analysis, the sensor signal X can be decomposed by n-level wavelet packet decomposition into 2n frequency bands. Xj can be expressed in Equation (1).

Xj = [Xj,1, Xj,2, …, Xj,m] (1)

where j is the frequency band (j = 1 … 2n), and m is the amount of sampling data. The energy Ej of the decomposed signal is defined in Equation (2).

Ej = ||Xj||2 = Xj,12 + Xj,22 + ··· Xj,m2 (2)

Figure 5. Principle of active sensing approach in monitoring of grouting compactness: (a) Empty duct;(b) Half grouting; (c) 90% grouting; (d) Full grouting.

3.2. Wavelet Packet-Based Energy Analysis

To evaluate the energy of the stress wave received by PZT sensors, the wavelet packet-basedanalysis is applied to provide the computed energy values of the signal received by PZT sensors.In the wavelet packet-based analysis, the sensor signal X can be decomposed by n-level wavelet packetdecomposition into 2n frequency bands. Xj can be expressed in Equation (1).

Xj = [Xj,1, Xj,2, . . . , Xj,m] (1)

where j is the frequency band (j = 1 . . . 2n), and m is the amount of sampling data.The energy Ej of the decomposed signal is defined in Equation (2).

Ej = ||Xj||2 = Xj,12 + Xj,2

2 + ···Xj,m2 (2)

Page 6: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 6 of 13

The total energy E of the signal can be computed as the summation of all the decomposed signalenergy, which is given as,

E =2n

∑j=1

Ej (3)

The energy level given by Equation (3) offers a quantitative measure of the energy of the stresswave that propagates from the SA actuator to the PZT sensors.

4. Experimental Setup and Procedures

4.1. Specimen Fabrication

Figure 6 gives the CAD model, dimensions, and the sensor location for the test specimen. OneSA was bonded to the tendon using epoxy and installed in the pre-determined location in the tendonduct, as shown in Figure 6a. Three waterproofed PZT sensors, including one sensor (PZT 1) mountedon the bottom outside surface and the other two sensors (PZT 2, PZT 3) mounted on the top outsidesurface, were used as sensors to detect stress wave, as shown in Figure 7a. The length, width, andheight of the concrete specimen are all 254 mm. The diameter and thickness of the tendon duct are70 mm and 5 mm, respectively. Detailed locations of the SA and PZT sensors are shown in Figure 6b.The test specimen used two types of binding materials i.e., concrete mix and cement, as shown inFigure 7a. The concrete mix is a 27.6 MPa blend of portland cement, sand, and gravel. The cementused for grouting in this research is a multipurpose construction material with underlayment, casting,anchoring, industrial grouting, and concrete repair. A PVC pipe was utilized as the grouting tube. Twoplastic plates were attached on both sides of the tendon duct to prevent the leakage of grout from theduct during the grouting process, as shown in Figure 7.

Sensors 2016, 16, 1343 6 of 13

The total energy E of the signal can be computed as the summation of all the decomposed signal energy, which is given as,

E = ∑ E (3)

The energy level given by Equation (3) offers a quantitative measure of the energy of the stress wave that propagates from the SA actuator to the PZT sensors.

4. Experimental Setup and Procedures

4.1. Specimen Fabrication

Figure 6 gives the CAD model, dimensions, and the sensor location for the test specimen. One SA was bonded to the tendon using epoxy and installed in the pre-determined location in the tendon duct, as shown in Figure 6a. Three waterproofed PZT sensors, including one sensor (PZT 1) mounted on the bottom outside surface and the other two sensors (PZT 2, PZT 3) mounted on the top outside surface, were used as sensors to detect stress wave, as shown in Figure 7a. The length, width, and height of the concrete specimen are all 254 mm. The diameter and thickness of the tendon duct are 70 mm and 5 mm, respectively. Detailed locations of the SA and PZT sensors are shown in Figure 6b. The test specimen used two types of binding materials i.e., concrete mix and cement, as shown in Figure 7a. The concrete mix is a 27.6 MPa blend of portland cement, sand, and gravel. The cement used for grouting in this research is a multipurpose construction material with underlayment, casting, anchoring, industrial grouting, and concrete repair. A PVC pipe was utilized as the grouting tube. Two plastic plates were attached on both sides of the tendon duct to prevent the leakage of grout from the duct during the grouting process, as shown in Figure 7.

(a) (b)

Figure 6. Test specimen: (a) the CAD model; (b) Schematic of the test specimen.

(a) (b)

Figure 7. Fabricated specimen: (a) Ungrouted specimen; (b) Grouted specimen.

Figure 6. Test specimen: (a) the CAD model; (b) Schematic of the test specimen.

Sensors 2016, 16, 1343 6 of 13

The total energy E of the signal can be computed as the summation of all the decomposed signal energy, which is given as,

E = ∑ E (3)

The energy level given by Equation (3) offers a quantitative measure of the energy of the stress wave that propagates from the SA actuator to the PZT sensors.

4. Experimental Setup and Procedures

4.1. Specimen Fabrication

Figure 6 gives the CAD model, dimensions, and the sensor location for the test specimen. One SA was bonded to the tendon using epoxy and installed in the pre-determined location in the tendon duct, as shown in Figure 6a. Three waterproofed PZT sensors, including one sensor (PZT 1) mounted on the bottom outside surface and the other two sensors (PZT 2, PZT 3) mounted on the top outside surface, were used as sensors to detect stress wave, as shown in Figure 7a. The length, width, and height of the concrete specimen are all 254 mm. The diameter and thickness of the tendon duct are 70 mm and 5 mm, respectively. Detailed locations of the SA and PZT sensors are shown in Figure 6b. The test specimen used two types of binding materials i.e., concrete mix and cement, as shown in Figure 7a. The concrete mix is a 27.6 MPa blend of portland cement, sand, and gravel. The cement used for grouting in this research is a multipurpose construction material with underlayment, casting, anchoring, industrial grouting, and concrete repair. A PVC pipe was utilized as the grouting tube. Two plastic plates were attached on both sides of the tendon duct to prevent the leakage of grout from the duct during the grouting process, as shown in Figure 7.

(a) (b)

Figure 6. Test specimen: (a) the CAD model; (b) Schematic of the test specimen.

(a) (b)

Figure 7. Fabricated specimen: (a) Ungrouted specimen; (b) Grouted specimen.

Figure 7. Fabricated specimen: (a) Ungrouted specimen; (b) Grouted specimen.

Page 7: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 7 of 13

4.2. Experimental Setup

The experimental setup, including the test specimen, a data acquisition system (NI-USB 6331),and a supporting laptop, is shown in Figure 8. The data acquisition board was used to generate thesignal to the SA and collected the signal response from the PZT sensors.

Sensors 2016, 16, 1343 7 of 13

4.2. Experimental Setup

The experimental setup, including the test specimen, a data acquisition system (NI-USB 6331), and a supporting laptop, is shown in Figure 8. The data acquisition board was used to generate the signal to the SA and collected the signal response from the PZT sensors.

Figure 8. Experimental setup.

4.3. Experimental Procedures

The grouting process began 2 days after the concrete was cast. The pre-mixed cement was carefully poured through the grouting tube. The percentage of the grouting process was controlled by measuring the height of the cement level in the duct from the transparent plastic plate. The grout pouring was performed in four progressive stages: no grout (empty duct), half grouting, 90% grouting, and full grouting, as shown in Figure 9. In each stage, the grout was allowed to cure for 5 days and the proposed method was applied to monitor the status of the grout progress, before moving to the next stage. During the monitoring process, a repeated swept sine wave was applied to the PZT-based SA to generate a stress wave. Meanwhile, the signal response of each mounted PZT sensor was recorded. The frequency range of the swept sine wave is from 100 Hz to 150 kHz. The amplitude and the period of the swept sine wave is 10 V and 1 s, respectively. The sampling frequency of each channel is 2 MHz.

Figure 9. Specimen in four different grout stages.

Figure 8. Experimental setup.

4.3. Experimental Procedures

The grouting process began 2 days after the concrete was cast. The pre-mixed cement wascarefully poured through the grouting tube. The percentage of the grouting process was controlledby measuring the height of the cement level in the duct from the transparent plastic plate. The groutpouring was performed in four progressive stages: no grout (empty duct), half grouting, 90% grouting,and full grouting, as shown in Figure 9. In each stage, the grout was allowed to cure for 5 days and theproposed method was applied to monitor the status of the grout progress, before moving to the nextstage. During the monitoring process, a repeated swept sine wave was applied to the PZT-based SA togenerate a stress wave. Meanwhile, the signal response of each mounted PZT sensor was recorded.The frequency range of the swept sine wave is from 100 Hz to 150 kHz. The amplitude and the periodof the swept sine wave is 10 V and 1 s, respectively. The sampling frequency of each channel is 2 MHz.

Sensors 2016, 16, 1343 7 of 13

4.2. Experimental Setup

The experimental setup, including the test specimen, a data acquisition system (NI-USB 6331), and a supporting laptop, is shown in Figure 8. The data acquisition board was used to generate the signal to the SA and collected the signal response from the PZT sensors.

Figure 8. Experimental setup.

4.3. Experimental Procedures

The grouting process began 2 days after the concrete was cast. The pre-mixed cement was carefully poured through the grouting tube. The percentage of the grouting process was controlled by measuring the height of the cement level in the duct from the transparent plastic plate. The grout pouring was performed in four progressive stages: no grout (empty duct), half grouting, 90% grouting, and full grouting, as shown in Figure 9. In each stage, the grout was allowed to cure for 5 days and the proposed method was applied to monitor the status of the grout progress, before moving to the next stage. During the monitoring process, a repeated swept sine wave was applied to the PZT-based SA to generate a stress wave. Meanwhile, the signal response of each mounted PZT sensor was recorded. The frequency range of the swept sine wave is from 100 Hz to 150 kHz. The amplitude and the period of the swept sine wave is 10 V and 1 s, respectively. The sampling frequency of each channel is 2 MHz.

Figure 9. Specimen in four different grout stages.

Figure 9. Specimen in four different grout stages.

Page 8: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 8 of 13

5. Test Results and Discussions

5.1. Time Domain Analysis

The signals received by the distributed PZT sensors corresponding to one period of the excitationsignal in all the investigated stages are shown in Figures 10–12. Each figure shows the sensor signalsfrom one of the four different grouting stages, including empty tube, half grouting, 90% grouting, andfull grouting. Sensor PZT 1 mounted on the bottom surface of the tendon duct cannot detect any signalfrom the SA if the tendon duct is empty. The reason is that there is no medium/grout between theactuator SA and sensor PZT 1 and therefore the stress wave propagation is prevented. When the groutlevel increases to approximately 50%, the grout, as a conduit between the SA and PZT, allows the stresswave to propagate. Therefore, the PZT 1 sensor starts to receive a meaningful signal and the receivedsignal remains in the two following stages. For PZT 2 and PZT 3 mounted on the top surface of thetendon duct, not much signal can be detected before the full grout stage, except for negligible amountsthat may propagate through the newly poured grout to the walls of the tendon duct. When the groutcompletely fills in the tendon duct, the stress wave can propagate to the top side of the tendon duct.In this case, PZT 2 and PZT 3 start to receive significant signal from the SA.

Sensors 2016, 16, 1343 8 of 13

5. Test Results and Discussions

5.1. Time Domain Analysis

The signals received by the distributed PZT sensors corresponding to one period of the excitation signal in all the investigated stages are shown in Figures 10–12. Each figure shows the sensor signals from one of the four different grouting stages, including empty tube, half grouting, 90% grouting, and full grouting. Sensor PZT 1 mounted on the bottom surface of the tendon duct cannot detect any signal from the SA if the tendon duct is empty. The reason is that there is no medium/grout between the actuator SA and sensor PZT 1 and therefore the stress wave propagation is prevented. When the grout level increases to approximately 50%, the grout, as a conduit between the SA and PZT, allows the stress wave to propagate. Therefore, the PZT 1 sensor starts to receive a meaningful signal and the received signal remains in the two following stages. For PZT 2 and PZT 3 mounted on the top surface of the tendon duct, not much signal can be detected before the full grout stage, except for negligible amounts that may propagate through the newly poured grout to the walls of the tendon duct. When the grout completely fills in the tendon duct, the stress wave can propagate to the top side of the tendon duct. In this case, PZT 2 and PZT 3 start to receive significant signal from the SA.

Figure 10. Time-domain signal of PZT 1 sensor in different grout stages.

Figure 11. Time-domain signal of PZT 2 sensor in different grout stages.

Figure 10. Time-domain signal of PZT 1 sensor in different grout stages.

Sensors 2016, 16, 1343 8 of 13

5. Test Results and Discussions

5.1. Time Domain Analysis

The signals received by the distributed PZT sensors corresponding to one period of the excitation signal in all the investigated stages are shown in Figures 10–12. Each figure shows the sensor signals from one of the four different grouting stages, including empty tube, half grouting, 90% grouting, and full grouting. Sensor PZT 1 mounted on the bottom surface of the tendon duct cannot detect any signal from the SA if the tendon duct is empty. The reason is that there is no medium/grout between the actuator SA and sensor PZT 1 and therefore the stress wave propagation is prevented. When the grout level increases to approximately 50%, the grout, as a conduit between the SA and PZT, allows the stress wave to propagate. Therefore, the PZT 1 sensor starts to receive a meaningful signal and the received signal remains in the two following stages. For PZT 2 and PZT 3 mounted on the top surface of the tendon duct, not much signal can be detected before the full grout stage, except for negligible amounts that may propagate through the newly poured grout to the walls of the tendon duct. When the grout completely fills in the tendon duct, the stress wave can propagate to the top side of the tendon duct. In this case, PZT 2 and PZT 3 start to receive significant signal from the SA.

Figure 10. Time-domain signal of PZT 1 sensor in different grout stages.

Figure 11. Time-domain signal of PZT 2 sensor in different grout stages. Figure 11. Time-domain signal of PZT 2 sensor in different grout stages.

Page 9: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 9 of 13Sensors 2016, 16, 1343 9 of 13

Figure 12. Time-domain signal of PZT 3 sensor in different grout stages.

5.2. Wavelet Packet-Based Energy Analysis

In order to directly detect the grout situation, the energy of the received signal was computed using the wavelet packet-based energy analysis and the results are shown in Figure 13–15. Figure 13 shows the energy levels of PZT 1 in all four different stages of grout pouring. Please note that the SA, as an actuator to generate the stress wave, is placed in the middle of the duct and PZT 1, as a sensor to detect any possible stress wave, is bonded on the bottom surface of the duct. When the tendon duct was empty, there was no medium/grout between the SA and PZT 1, and it is clear that the PZT 1’s energy level was zero, as shown in Figure 13. When the grout level approached approximately 50%, PZT 1 began to receive the stress wave signal and the computed energy rapidly increased from the empty stage and half grouting stage, as revealed in Figure 13. As the grouting reached 90%, Figure 13 shows that the energy level of PZT 1 further increases. We also note that the energy levels for 90% and 100% are almost the same in Figure 13, which can be easily explained by the fact that paths for the stress wave to propagate from the SA to PZT 1 are almost identical for both 90% and 100% grouting stages.

For both PZT 2 and PZT 3, which are located on the top surface of the tendon duct, there is no medium/grout between the SA and PZT 2 or PZT 3 during the empty duct, 50% grouting, and 90% grouting stages, therefore the energy levels of both PZT 2 and PZT 3 are very low for these three stages, as shown in Figures 14 and 15. As the grouting level reaches 100%, a complete stress wave propagation path is formed between the SA and PZT 2 or PZT 3, and hence there is a significant increase of the energy level of signals from both PZT 2 and PZT 3, as shown in Figures 14 and 15.

Figure 13. Wavelet packet-based energy analysis of PZT 1 located on the bottom surface.

Figure 12. Time-domain signal of PZT 3 sensor in different grout stages.

5.2. Wavelet Packet-Based Energy Analysis

In order to directly detect the grout situation, the energy of the received signal was computedusing the wavelet packet-based energy analysis and the results are shown in Figures 13–15. Figure 13shows the energy levels of PZT 1 in all four different stages of grout pouring. Please note that the SA,as an actuator to generate the stress wave, is placed in the middle of the duct and PZT 1, as a sensor todetect any possible stress wave, is bonded on the bottom surface of the duct. When the tendon ductwas empty, there was no medium/grout between the SA and PZT 1, and it is clear that the PZT 1’senergy level was zero, as shown in Figure 13. When the grout level approached approximately 50%,PZT 1 began to receive the stress wave signal and the computed energy rapidly increased from theempty stage and half grouting stage, as revealed in Figure 13. As the grouting reached 90%, Figure 13shows that the energy level of PZT 1 further increases. We also note that the energy levels for 90% and100% are almost the same in Figure 13, which can be easily explained by the fact that paths for the stresswave to propagate from the SA to PZT 1 are almost identical for both 90% and 100% grouting stages.

Sensors 2016, 16, 1343 9 of 13

Figure 12. Time-domain signal of PZT 3 sensor in different grout stages.

5.2. Wavelet Packet-Based Energy Analysis

In order to directly detect the grout situation, the energy of the received signal was computed using the wavelet packet-based energy analysis and the results are shown in Figure 13–15. Figure 13 shows the energy levels of PZT 1 in all four different stages of grout pouring. Please note that the SA, as an actuator to generate the stress wave, is placed in the middle of the duct and PZT 1, as a sensor to detect any possible stress wave, is bonded on the bottom surface of the duct. When the tendon duct was empty, there was no medium/grout between the SA and PZT 1, and it is clear that the PZT 1’s energy level was zero, as shown in Figure 13. When the grout level approached approximately 50%, PZT 1 began to receive the stress wave signal and the computed energy rapidly increased from the empty stage and half grouting stage, as revealed in Figure 13. As the grouting reached 90%, Figure 13 shows that the energy level of PZT 1 further increases. We also note that the energy levels for 90% and 100% are almost the same in Figure 13, which can be easily explained by the fact that paths for the stress wave to propagate from the SA to PZT 1 are almost identical for both 90% and 100% grouting stages.

For both PZT 2 and PZT 3, which are located on the top surface of the tendon duct, there is no medium/grout between the SA and PZT 2 or PZT 3 during the empty duct, 50% grouting, and 90% grouting stages, therefore the energy levels of both PZT 2 and PZT 3 are very low for these three stages, as shown in Figures 14 and 15. As the grouting level reaches 100%, a complete stress wave propagation path is formed between the SA and PZT 2 or PZT 3, and hence there is a significant increase of the energy level of signals from both PZT 2 and PZT 3, as shown in Figures 14 and 15.

Figure 13. Wavelet packet-based energy analysis of PZT 1 located on the bottom surface. Figure 13. Wavelet packet-based energy analysis of PZT 1 located on the bottom surface.

Page 10: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 10 of 13Sensors 2016, 16, 1343 10 of 13

Figure 14. Wavelet packet-based energy analysis of PZT 2 located on the top surface.

Figure 15. Wavelet packet-based energy analysis of PZT 3 located on the top surface.

It is clear from Figures 13–15 that the case of a strong signal from the sensor on the bottom surface and a weak signal from the top surface indicates the first milestone, i.e., 50% grouting, is achieved. The strong signals with high energy levels from the sensors bonded on both top and bottom surfaces of the tendon duct indicate that the second milestone, i.e., the 100% grouting, is achieved. In summary, by observing the sensor responses and associated energy levels, we can monitor the grouting compactness in the tendon duct in real time. In addition, the sensor responses can clearly reveal the two important milestones of 50% and 100% grouting condition.

5.3. Discussion

In this study, the grouting compactness in the post-tensioning tendon duct was successfully monitored in real time by using the proposed PZT based active sensing approach. Two important milestones including 50% and 100% grouting conditions can be clearly confirmed by the appearance of the strong signal received by PZT sensors. It should be noted that the amplitude of the received signal may further change with the cement hardening process since the mechanical properties of the wave propagation medium change with time. Studying the change of the sensor signal amplitude may be another interesting topic when monitoring the cement hydration progress in tendon duct, and may be considered a future work. Since the proposed method is limited to monitoring the local grouting compactness of the duct, several sets of actuators and sensors must be deployed to evaluate the general grouting compactness of large-scale structures in the practical applications. In addition,

Figure 14. Wavelet packet-based energy analysis of PZT 2 located on the top surface.

Sensors 2016, 16, 1343 10 of 13

Figure 14. Wavelet packet-based energy analysis of PZT 2 located on the top surface.

Figure 15. Wavelet packet-based energy analysis of PZT 3 located on the top surface.

It is clear from Figures 13–15 that the case of a strong signal from the sensor on the bottom surface and a weak signal from the top surface indicates the first milestone, i.e., 50% grouting, is achieved. The strong signals with high energy levels from the sensors bonded on both top and bottom surfaces of the tendon duct indicate that the second milestone, i.e., the 100% grouting, is achieved. In summary, by observing the sensor responses and associated energy levels, we can monitor the grouting compactness in the tendon duct in real time. In addition, the sensor responses can clearly reveal the two important milestones of 50% and 100% grouting condition.

5.3. Discussion

In this study, the grouting compactness in the post-tensioning tendon duct was successfully monitored in real time by using the proposed PZT based active sensing approach. Two important milestones including 50% and 100% grouting conditions can be clearly confirmed by the appearance of the strong signal received by PZT sensors. It should be noted that the amplitude of the received signal may further change with the cement hardening process since the mechanical properties of the wave propagation medium change with time. Studying the change of the sensor signal amplitude may be another interesting topic when monitoring the cement hydration progress in tendon duct, and may be considered a future work. Since the proposed method is limited to monitoring the local grouting compactness of the duct, several sets of actuators and sensors must be deployed to evaluate the general grouting compactness of large-scale structures in the practical applications. In addition,

Figure 15. Wavelet packet-based energy analysis of PZT 3 located on the top surface.

For both PZT 2 and PZT 3, which are located on the top surface of the tendon duct, there is nomedium/grout between the SA and PZT 2 or PZT 3 during the empty duct, 50% grouting, and 90%grouting stages, therefore the energy levels of both PZT 2 and PZT 3 are very low for these three stages,as shown in Figures 14 and 15. As the grouting level reaches 100%, a complete stress wave propagationpath is formed between the SA and PZT 2 or PZT 3, and hence there is a significant increase of theenergy level of signals from both PZT 2 and PZT 3, as shown in Figures 14 and 15.

It is clear from Figures 13–15 that the case of a strong signal from the sensor on the bottomsurface and a weak signal from the top surface indicates the first milestone, i.e., 50% grouting,is achieved. The strong signals with high energy levels from the sensors bonded on both top and bottomsurfaces of the tendon duct indicate that the second milestone, i.e., the 100% grouting, is achieved.In summary, by observing the sensor responses and associated energy levels, we can monitor thegrouting compactness in the tendon duct in real time. In addition, the sensor responses can clearlyreveal the two important milestones of 50% and 100% grouting condition.

5.3. Discussion

In this study, the grouting compactness in the post-tensioning tendon duct was successfullymonitored in real time by using the proposed PZT based active sensing approach. Two importantmilestones including 50% and 100% grouting conditions can be clearly confirmed by the appearance ofthe strong signal received by PZT sensors. It should be noted that the amplitude of the received signal

Page 11: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 11 of 13

may further change with the cement hardening process since the mechanical properties of the wavepropagation medium change with time. Studying the change of the sensor signal amplitude may beanother interesting topic when monitoring the cement hydration progress in tendon duct, and maybe considered a future work. Since the proposed method is limited to monitoring the local groutingcompactness of the duct, several sets of actuators and sensors must be deployed to evaluate the generalgrouting compactness of large-scale structures in the practical applications. In addition, isolation andprotection of the surface mounted PZT patches especially in harsh environments must be considered.

6. Conclusions

A practical problem associated with reinforced concrete structures with post-tensioning is thepartially filled or empty tendon duct, which may reduce structural integrity and service life, and evencause accidents. This paper proposes a real-time method to monitor the grouting compactness of apost-tensioning tendon duct for reinforced concrete structures. The proposed method employs a stresswave-based active sensing approach with piezoceramic transducers. In the proposed method, one PZTbased smart aggregate (SA), which was bonded on the tendon, was utilized as an actuator to generatethe stress wave. Meanwhile, waterproofed PZT patches mounted on the top and bottom surfaces(outside) of the tendon duct were used as sensors to detect the stress wave. Grout in the tendon ductfunctions as the wave propagation medium which allows the propagation of the stress wave. If theduct is 100% filled with the grout, the stress wave generated by the SA will propagate to reach boththe top and bottom surfaces of the tendon duct via the grout. However, without any grout, the stresswave will fail to reach either the top or the bottom of the duct. In addition, wavelet packet-basedenergy analysis was adopted in this research to compute the total signal energy received by PZTsensors. In this research, four different grout stages, including empty duct, half grouting, 90% grouting,and full grouting, were experimentally studied. Experimental results clearly demonstrate that thecase of strong signals with high energy levels from the sensors bonded on both top and bottomsurfaces of the tendon duct indicate the achievement of the milestone of the 100% grouting condition.In summary, by observing the sensor responses and associated energy levels, we can monitor thegrouting compactness in the tendon duct in real time.

Acknowledgments: The authors are grateful for the partial financial support received from the Major State BasicResearch Development Program of China (973 Program, grant number 2015CB057704), the National NatureScience Foundation of China [Grant No. 51208061, 51278084, 51478080, and 51421064 (Creative Group)], theHunan Province Innovation Open Fund Project of China [Grant No. 12K077], and Changsha University of Scienceand Technology Civil Engineering Innovation Project of China [Grant No. 15ZDXK11].

Author Contributions: Tianyong Jiang designed and performed the experiments, analyzed the data, and helpedwrite the manuscript. Qingzhao Kong developed the concept, helped collect the data, analyzed the data, and wrotemost part of the paper. Wenxi Wang helped design and perform the experiments, and helped analyzed the data.Linsheng Huo fabricated the transducers and provided the corresponding sensing technologies. Gangbing Songdeveloped the concept, designed the experiments, and made critical revision of the manuscript.

Conflicts of Interest: The authors declare no conflict of interest.

References

1. Yang, T.; Yi, W.; Lu, G.; Huang, H.L. Experimental study of nondestructive testing for grouting quality inprestressed concrete T-beam. J. Vib. Eng. 2006, 19, 411–415.

2. Yamada, M.; Ohtsu, M. Case studies on ungrouted tendon-duct in prestressed concrete models by SIBIE.Constr. Build. Mater. 2010, 24, 2376–2380. [CrossRef]

3. Yaman, F.; Weiland, T. Inhomogeneity reconstructions in tendon ducts via boundary integral equations.NDT E Int. 2014, 68, 66–72.

4. Muldoon, R.; Chalker, A.; Forde, M.C.; Ohtsu, M.; Kunisue, F. Indentifying voids in plastic ducts inpost-tensioning prestressed concrete members by resonant frenquency of impact-echo, SIBIE and tomography.Constr. Build. Mater. 2007, 21, 527–537. [CrossRef]

Page 12: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 12 of 13

5. Wang, F.; Zhang, F. Experimental research on detection of duct grouting quality of prestressed corrugatedpipe with ultrasonic. Bridge Tunn. Constr. Mach. 2015, 2, 73–77.

6. Krause, M.; Mielentz, F.; Milman, B.; Müller, W.; Schmitz, V.; Wiggenhauser, H. Ultrasonic imaging ofconcrete members using an array system. NDT E Int. 2001, 34, 403–108.

7. Schickert, M.; Krause, M.; Müller, W. Ultrasonic imaging of concrete elements using reconstruction bysynthetic aperture focusing technique. J. Mater. Civ. Eng. 2003, 15, 235–246. [CrossRef]

8. Maierhofer, C. Non-destructive evaluation of concrete infrastructure with ground penetrating radar. J. Mater.Civ. Eng. 2003, 15, 287–297. [CrossRef]

9. Bungey, J.H.; Millard, S.G.; Shaw, M.R. Radar assessment of post-tensioned concrete. In Proceedings of the7th Internetional Conference on Structural Faults and Repair, Edinburgh, UK, 8 July 1997.

10. Yang, Y.; Hu, Y.; Lu, Y. Sensitivity of PZT impedance sensors for damage detection of concrete structures.Sensors 2008, 8, 327–346. [CrossRef]

11. Xu, B.; Wang, Y.; Dyke, S.J.; Huang, T. Cracking monitoring of RC joints under cyclic loadings based onwavelet packet analysis on embedded PZT measurements. In Proceedings of the 14th ASCE InternationalConference on Engineering, Science, Construction and Operations in Challenging Environments, St. Louis,MO, USA, 27–29 October 2014.

12. Wang, T.; Song, G.; Wang, Z.; Li, Y. Proof-of-concept Study of Monitoring Bolt Connection Status using aPiezoelectric based Active Sensing Method. Smart Mater. Struct. 2013, 22, 087001. [CrossRef]

13. Sevillano, E.; Sun, R.; Perera, R. Damage Detection Based on Power Dissipation Measured with PZT Sensorsthrough the Combination of Electro-Mechanical Impedances and Guided Waves. Sensors 2016, 16, 639.[CrossRef] [PubMed]

14. Karayannis, C.G.; Voutetaki, M.E.; Chalioris, C.E.; Providakis, C.P.; Angeli, G.M. Detection of flexural damagestages for RC beams using piezoelectric sensors (PZT). Smart Struct. Syst. 2015, 15, 997–1018. [CrossRef]

15. Karayannis, C.G.; Chalioris, C.E.; Angeli, G.M.; Papadopoulos, N.A.; Favvata, M.J.; Providakis, C.P.Experimental damage evaluation of reinforced concrete steel bars using piezoelectric sensors.Constr. Build. Mater. 2016, 105, 227–244. [CrossRef]

16. Voutetaki, M.E.; Papadopoulos, N.A.; Angeli, G.M.; Providakis, C.P. Investigation of a new experimentalmethod for damage assessment of RC beams failing in shear using piezoelectric transducers. Eng. Struct.2016, 114, 226–240. [CrossRef]

17. Providakis, C.P.; Stefanaki, K.D.; Voutetaki, M.E.; Tsompanakis, Y.; Stavroulaki, M. Damage detection inconcrete structures using a simultaneously activated multi-mode PZT active sensing system: numericalmodelling. Struct. Infrastruct. Eng. 2014, 10, 1451–1468. [CrossRef]

18. Lim, Y.Y.; Kwong, K.Z.; Liew, W.Y.H.; Soh, C.K. Non-destructive concrete strength evaluation using smartpiezoelectric transducer–a comparative study. Smart Mater. Struct. 2016, 25, 085021. [CrossRef]

19. Chalioris, C.E.; Karayannis, C.G.; Angeli, G.M.; Papadopoulo, N.A.; Favvata, M.J.; Providakis, C.P.Applications of smart piezoelectric materials in a wireless admittance monitoring system (WiAMS) toStructures–Tests in RC elements. Case Stud. Constr. Mater. 2016, 5, 1–18. [CrossRef]

20. Song, G.; Olmi, C.; Gu, H. An overheight vehicle-bridge collision monitoring system using piezoelectrictransducer. Smart Mater. Struct. 2007, 16, 462–468. [CrossRef]

21. Song, G.; Gu, H.; Mo, Y.L.; Hsu, T.; Dhonde, H. Concrete structural health monitoring using embeddedpiezoceramic transducers. Smart Mater. Struct. 2007, 16, 959–968. [CrossRef]

22. Song, G.; Gu, H.; Mo, Y.L. Smart aggregate: multi-functional sensors for concrete structures–a tutorial andreview. Smart Mater. Struct. 2008, 17, 033001. [CrossRef]

23. Xu, B.; Li, B.; Song, G. Active debonding detection for large rectangular CFSTs based on wavelet packetenergy spectrum with piezoceramics. ASCE J. Struct. Eng. 2013, 139, 1435–1443. [CrossRef]

24. Xu, B.; Zhang, T.; Song, G.; Gu, H. Active interface debonding detection of a concrete-filled steel tube withPZT techniques using wavelet packet analysis. Mech. Syst. Signal Process. 2013, 36, 7–17. [CrossRef]

25. Wu, F.; Chang, F.K. Debond detection using embedded piezoelectric elements in reinforced concretestructure–part I: Experiment. Struct. Health Monit. 2006, 5, 5–15. [CrossRef]

26. Wu, F.; Chang, F.K. Debond detection using embedded piezoelectric elements in reinforced concretestructure–part II: Analysis and Algorithm. Struct. Health Monit. 2006, 5, 17–28. [CrossRef]

27. Qin, F.; Kong, Q.; Li, M.; Mo, Y.; Song, G. Bond slip detection of steel plate and concrete beams using smartaggregates. Smart Mater. Struct. 2015, 24, 1–13. [CrossRef]

Page 13: Monitoring of Grouting Compactness in a Post-Tensioning ... · series of standard concrete beams with plastic P-T (post-tensioning) tendon ducts at the University of Edinburgh using

Sensors 2016, 16, 1343 13 of 13

28. Chalioris, C.E.; Papadopoulos, N.A.; Angeli, G.M.; Karayannis, C.G.; Liolios, A.A.; Providakis, C.P. Damageevaluation in shear-critical reinforced concrete beam using piezoelectric transducers as smart aggregates.Open Eng. 2015, 1, 373–384. [CrossRef]

29. Gu, H.; Song, G.; Dhonde, H.; Mo, Y.L.; Yan, S. Concrete early-age strength monitoring using embeddedpiezoelectric transducers. Smart Mater. Struct. 2006, 15, 1837–1845. [CrossRef]

30. Du, G.; Kong, Q.; Lai, T.; Song, G. Feasibility Study on Crack Detection of Pipelines Using PiezoceramicTransducers. Int. J. Distrib. Sens. Netw. 2013, 2013, 631715. [CrossRef]

31. Kong, Q.; Wang, R.; Song, G.; Yang, Z.; Still, B. Monitoring the Soil Freeze-Thaw Process UsingPiezoceramic-Based Smart Aggregate. J. Cold Reg. Eng. 2014, 28, 06014001. [CrossRef]

© 2016 by the authors; licensee MDPI, Basel, Switzerland. This article is an open accessarticle distributed under the terms and conditions of the Creative Commons Attribution(CC-BY) license (http://creativecommons.org/licenses/by/4.0/).