MELEX MCCB, MMP, MAGNETIC CONTACTOR,CIRCUIT PROTECTOR, MCB, RCCB, POWER METER,ECOMONITOR, ECO-WEBSERVER

Contents

INDEX

1 MOLDED CASE CIRCUIT BREAKERS

1) Melex 1

2) WS-V 2 – 6

3) Earth Leakage Circuit Breaker 7 – 10

4) Japan Series 8 – 20

2 MOTOR CIRCUIT BREAKERS 21

3 MAGNETIC CONTACTOR 22 – 23

4 CIRCUIT PROTECTORS 24 – 27

5 MCB / RCCB / ISOLATOR 28

6 POWER METER 29

7 ECO MONITOR PLUS 30

8 ECO WEBSERVER 31

1

1-1 Molded Case Circuit Breakers — Melex

Specifications

2

1-2 Molded Case Circuit Breakers — WS-V

14

2

NF-C (Economy class)

Frame (A) 30 50 60 63 100 125Model NF30-CS NF63-CV NF125-CV

Image

Rated current In (A)Rated ambient temperture 40°C (45°C for marine use) 3 5 10 15 20 30 3 4 (5) 6 10 (15) 16

20 25 (30) 32 40 50 (60) 63 50 (60) 63(75) 80 100 125

Number of poles 2 3 2 3 2 3 2 3 2 3 2 3Rated insulation voltage Ui (V) 500 600 600 600 600 600

Rated

short

-circu

it brea

king c

apac

ities (

kA)

IEC 60947-2EN 60947-2(Icu/Ics)

AC

690V − − − − − −500V − 2.5/2.5 2.5/2.5 2.5/2.5 7.5/4 7.5/4440V − 2.5/2.5 2.5/2.5 2.5/2.5 10/5 10/5415V 1.5/1.5 2.5/2.5 2.5/2.5 2.5/2.5 10/5 10/5400V 1.5/1.5 5/5 5/5 5/5 10/5 10/5380V 1.5/1.5 5/5 5/5 5/5 10/5 10/5230V 2.5/2 (240V) 7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15200V 2.5/2 (240V) 7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15

DC 250V − 2.5/2.5 (*7) 2.5/2.5 (*7) 2.5/2.5 (*7) 7.5/4 (*4) 7.5/4 (*4)Rated impulse withstand voltage Uimp (kV) 4 8 8 8 8 8

Current (*1) AC AC/DC compatible AC/DC compatible AC/DC compatible AC/DC compatible AC/DC compatibleSuitability for isolation − Compatible Compatible Compatible Compatible CompatibleReverse connection − Possible Possible Possible Possible Possible

Number ofoperating cycles

Without current 10,000 10,000 10,000 10,000 10,000 10,000With current (440VAC) 6,000 (AC415V) 6,000 6,000 6,000 6,000 6,000

Utilization category A A A A A APollution degree 2 3 3 3 3 3

EMC environment condition (environment A or B) N/A N/A N/A N/A N/A N/A

Overa

lldim

ensio

ns (m

m) a

b

cac a 45 67.5 50 75 50 75 50 75 60 90 60 90

b 96 130 130 130 130 130c 52 68 68 68 68 68

ca 67 90 90 90 90 90Mass of front-face type (kg) 0.25 0.35 0.45 0.65 0.5 0.7 0.5 0.7 0.6 0.9 0.6 0.9

Instal

lation

and

conn

ectio

ns Front connection (F) Page �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminalSolderless (BOX) terminal (SL)

94− − − − � �

Rear (B) �Round stud (assembled in) �Round stud �Round stud �Round stud �Bar stud �Bar stud Plug-in (PM) − � � � � �

Cas

sette

-typ

e ac

cess

orie

s

Alarm switch (AL)

104

� (*5) � (*6) � (*6) � (*6) � (*6) �(*6)Auxiliary switch (AX) �(*5) � (*6) � (*6) � (*6) � (*6) �(*6)Shunt trip (SHT) − � (*6) � (*6) � (*6) � (*6) �(*6)Undervoltage trip (UVT) − � (*6) � (*6) � (*6) � (*6) �(*6)With lead-wire terminal block (SLT) 116 � � � � � �

Pre-alarm (PAL) 118 − − − − − −

Ext

erna

l acc

esso

ries

EnclosureClosed (S)

132� � � � � �

Dustproof (I) − � � � � �

Waterproof (W) − − � − � − � − � − �

Electrical operation device (NFM) 135 − − − − − � − �

Mechanicalinterlock (MI) (*10)

Panel mounting131

− � � � � �

Breaker mounting − � � � � �

Handle lockdevice

LC129

� � � � � �

HL � � � � � �

HL-S − � � � � �

Externaloperating handle

(F)119

− � � � � �

(V) − � � � � �

Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 123 � � � � � �

Rear stud (B-ST)96

− � � � � �

Plug-in (PM) − � � � � �

IEC 35mm rail mounting adapters 139 � � � � − −CE marking TÜV approval Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration

CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in processMarine use approval (NK, LR, ABS, GL) � (NK, LR, ABS) � � � � �

Automatic tripping device Hydraulic magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magneticTrip button − (*2) Equipped Equipped Equipped Equipped Equipped

Page of Characteristics and dimensions 142 144 146

1D

etai

led

Spe

cific

atio

ns

2 Molded Case Circuit BreakersDetailedSpecifications 1

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 It is attached with the alarm switch. *3 In case of a current rating of 100A, it does not specify NK rating. *4 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products.

If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively. *5 The standard lead drawing is performd laterally. Load drawing is also available. *6 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame

(excluding UVT). *7 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right. *8 Place an order of other models in conjunction with the circuit breaker. *9 Solid state relay output is option. Please specify if other output is necessary.

(Standard type is thus SLT equipped). *10 Not isolation compatible, excluding 400 to 800A frame.

Line

3-poleLoad

Line

4-poleLoad

3

1-2 Molded Case Circuit Breakers — WS-V

16

2

1D

etai

led

Spe

cific

atio

ns

NF-S (Standard class)

Frame (A) 30 32 50 60 63Model NF32-SV NF63-SV

Image

Rated current In (A)Rated ambient temperture 40°C (45°C for marine use)

3 4 (5) 6 1015 16 20 25 (30) 32 3 4 (5) 6 10 (15) 16

20 25 (30) 32 40 50 (60) 63

Number of poles 2 3 2 3 2 3 4 2 3 4 2 3 4Rated insulation voltage Ui (V) 600 600 600 600 600

Rated

short

-circu

it brea

king c

apac

ities (

kA)

IEC 60947-2EN 60947-2(Icu/Ics)

AC

690V − − − − −500V 2.5/2.5 2.5/2.5 7.5/7.5 7.5/7.5 7.5/7.5440V 2.5/2.5 2.5/2.5 7.5/7.5 7.5/7.5 7.5/7.5415V 2.5/2.5 2.5/2.5 7.5/7.5 7.5/7.5 7.5/7.5400V 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5380V 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5230V 7.5/7.5 7.5/7.5 15/15 15/15 15/15200V 7.5/7.5 7.5/7.5 15/15 15/15 15/15

DC 250V 2.5/2.5 (*5) 2.5/2.5 (*5) 7.5/7.5 (*5) 7.5/7.5 (*5) 7.5/7.5 (*5)Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8

Current (*1) AC/DC compatible AC/DC compatible AC/DC compatible AC/DC compatible AC/DC compatibleSuitability for isolation Compatible Compatible Compatible Compatible CompatibleReverse connection Possible Possible Possible Possible Possible

Number ofoperating cycles

Without current 10,000 10,000 10,000 15,000 15,000With current (440VAC) 6,000 6,000 6,000 8,000 8,000

Utilization category A A A A APollution degree 3 3 3 3 3

EMC environment condition (environment A or B) N/A N/A N/A N/A N/A

Overa

lldim

ensio

ns (m

m) a

b

cac a 50 75 50 75 50 75 100 50 75 100 50 75 100

b 130 130 130 130 130c 68 68 68 68 68

ca 90 90 90 90 90Mass of front-face type (kg) 0.45 0.65 0.45 0.65 0.5 0.7 0.9 0.55 0.75 1.0 0.55 0.75 1.0

Instal

lation

and

conn

ectio

ns Front connection (F) Page �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminalSolderless (BOX) terminal (SL)

94− − − − −

Rear (B) �Bar stud �Round stud �Round stud �Round stud �Round stud Plug-in (PM) � � � � �

Cas

sette

-typ

e ac

cess

orie

s

Alarm switch (AL)

104

� (*4) � (*4) � (*4) � � (*4) � � (*4) �

Auxiliary switch (AX) � (*4) � (*4) � (*4) � � (*4) � � (*4) �

Shunt trip (SHT) � (*4) � (*4) � (*4) � � (*4) � � (*4) �

Undervoltage trip (UVT) � (*4) � (*4) � (*4) � � (*4) � � (*4) �

With lead-wire terminal block (SLT) 116 � � � � � � � �

Pre-alarm (PAL) 118 − − − − −

Ext

erna

l acc

esso

ries

EnclosureClosed (S)

132� � � − � − � −

Dustproof (I) � � � − � − � −Waterproof (W) − � − � − � − − � − − � −

Electrical operation device (NFM) 135 − − − − −Mechanical

interlock (MI) (*7)Panel mounting

131� � � � � � � �

Breaker mounting � � � − � − � −

Handle lockdevice

LC129

� � � � �

HL � � � � �

HL-S � � � � �

Externaloperating handle

(F)119

� � � � �

(V) � � � � �

Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 123 � � � � � � � �

Rear stud (B-ST)96

� � � � �

Plug-in (PM) � � � � � � � �

IEC 35mm rail mounting adapters 139 � � � − � − � −CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration

CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in processMarine use approval (NK, LR, ABS, GL) � � � − � − � −

Automatic tripping device Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magneticTrip button Equipped Equipped Equipped Equipped Equipped

Page of Characteristics and dimensions 144 144

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 In case of a current rating of 100A, it does not specify NK rating. *3 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products.

If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively.(In case of NF250-SV, three and four poles can be used for up to 500 and 600VDC)

*4 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT).

*5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right. *6 Place an order of other models in conjunction with the circuit breaker. *7 Not isolation compatible. excluding 400 to 800A frame.

Line

3-poleLoad

Line

4-poleLoad

2 Molded Case Circuit BreakersDetailedSpecifications 1

4

17

2

1D

etai

led

Spe

cific

atio

ns

NF-S (Standard class)

100 125 125 125 160 225 250NF125-SV NF125-SGV NF125-SEV NF160-SGV NF250-SV

(15) 16 20 (30) 32 4050 (60) 63 (75) 80 100 125 16-20 20-25 25-32 32-40 35-50

45-63 56-80 70-100 90-125 16-32 32-63 63-125 125-160 (100) 125 150 160175 200 225 (*2) 250

2 3 4 2 3 4 2 3 4 3 4 2 3 4 2 3 4 2 3 4690 690 690 690 690 690 6908/8 8/8 8/8 8/8 8/8 8/8 8/8

18/18 18/18 30/30 30/30 30/30 30/30 30/3025/25 25/25 36/36 36/36 36/36 36/36 36/3630/30 30/30 36/36 36/36 36/36 36/36 36/3630/30 30/30 36/36 36/36 36/36 36/36 36/3630/30 30/30 36/36 36/36 36/36 36/36 36/3650/50 50/50 85/85 85/85 85/85 85/85 85/8550/50 50/50 85/85 85/85 85/85 85/85 85/85

40/40 (*3) 40/40 (*3) 20/20 (300V) (*3) − 20/20 (300V) (*3) 20/20 (300V) (*3) 20/20 (300V) (*3)8 8 8 8 8 8 8

AC/DC compatible AC/DC compatible AC/DC compatible AC AC/DC compatible AC/DC compatible (*1) AC/DC compatible (*1)Compatible Compatible Compatible Compatible Compatible Compatible Compatible

Possible Possible Possible Possible Possible Possible Possible25,000 25,000 50,000 25,000 40,000 25,000 25,00010,000 10,000 30,000 10,000 15,000 10,000 10,000

A A A A A A A3 3 3 3 3 3 3

N/A N/A N/A A N/A N/A N/A60 90 120 60 90 120 105 140 105 140 105 140 105 140 105 140

130 130 165 165 165 165 16568 68 68 68 68 68 6890 90 92 92 92 92 92

0.7 1.0 1.3 0.7 1.0 1.3 1.4 1.6 2.0 1.7 2.2 1.4 1.6 2.0 1.4 1.6 2.0 1.4 1.6 2.0�Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal

� � � � � � � � � � �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud � � � � � � � � � � � �

� (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) �

� (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) �

� (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) �

� (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) � � (*4) �

� � � � � � � � � � � �

− − − � − − −� − � − � − � − � − � − � −� − � − � − � − � − � − � −

− � − − � − � − � − � − � − � −− � − � � � � � �

� � � � � � � � � � � �

� − � − � � − � � − � −� � � � � � �

� � � � � � �

� � � � � � �

� � � � � � �

− � � − � � � � � �

� � � � � � � � � � � �

� � � � � � � � � � � �

� � � � � � � � � � � �

− − − − − − −Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration TÜV approval Self-declaration TÜV approval Self-declaration

Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process� − � − � (LR, ABS, GL) − � (LR, ABS, GL) − � (LR, ABS, GL) − � − � −

Thermal-magnetic Thermal-magnetic Thermal-magnetic Electronic (effective value detection) Thermal-magnetic Thermal-magnetic Thermal-magneticEquipped Equipped Equipped Equipped Equipped Equipped Equipped

146 154 156 154 150

Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specifi ed in the shaded cells.

2 Detailed Specifications 1Molded Case Circuit Breakers

5

1-2 Molded Case Circuit Breakers — WS-V

20

2

1D

etai

led

Spe

cific

atio

ns

NF-L / NF-H / NF-R (High-performance class)

Frame (A) 50 60 63 100 125 125 125 125Model NF63-HV NF125-HV NF125-LGV NF125-HGV NF125-RGV

Image

Rated current In (A)Rated ambient temperture 40°C (45°C for marine use)

10 15 16 20 25 30 32 40 50 60 (63) 15 16 20 30 32 40

50 60 63 75 80 100 125 16-20 20-25 25-32 32-40 35-5045-63 56-80 70-100 90-125

16-20 20-25 25-32 32-40 35-5045-63 56-80 70-100 90-125

16-20 20-25 25-32 32-40 40-5050-63 63-80 80-100 100-125

Number of poles 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3Rated insulation voltage Ui (V) 690 690 690 690 690 690 690 690

Rated

short

-circu

it brea

king c

apac

ities (

kA)

IEC 60947-2EN 60947-2(Icu/Ics)

AC

690V 2.5/2.5 2.5/2.5 2.5/2.5 10/8 10/8 8/8 10/8 –500V 7.5/7.5 7.5/7.5 7.5/7.5 30/23 30/23 36/36 50/38 –440V 10/8 10/8 10/8 50/38 50/38 50/50 65/65 125/125415V 10/8 10/8 10/8 50/38 50/38 50/50 70/70 150/150400V 10/8 10/8 10/8 50/38 50/38 50/50 75/75 150/150380V 10/8 10/8 10/8 50/38 50/38 50/50 75/75 150/150230V 25/19 25/19 25/19 100/75 100/75 90/90 100/100 150/150200V 25/19 25/19 25/19 100/75 100/75 90/90 100/100 150/150

DC 250V 7.5/7.5 (*5) 7.5/7.5 (*5) 7.5/7.5 (*5) − − 20/20 (300V) (*2) 40/40 (300V) (*2) −Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8 8 8 8

Current AC/DC compatible (*1) AC/DC compatible (*1) AC/DC compatible (*1) AC AC AC/DC compatible AC/DC compatible ACSuitability for isolation Compatible Compatible Compatible Compatible Compatible Compatible Compatible CompatibleReverse connection Possible Possible Possible Possible Possible Possible Possible Possible

Number ofoperating cycles

Without current 15,000 15,000 15,000 25,000 25,000 50,000 50,000 50,000With current (440VAC) 8,000 8,000 8,000 10,000 10,000 30,000 30,000 30,000

Utilization category A A A A A A A APollution degree 3 3 3 3 3 3 3 3

EMC environment condition (environment A or B) N/A N/A N/A N/A N/A N/A N/A N/A

Overa

lldim

ensio

ns (m

m) a

b

cac a 50 75 100 50 75 100 50 75 100 90 120 90 120 105 140 105 140 105

b 130 130 130 130 130 165 165 165c 68 68 68 68 68 68 68 68ca 90 90 90 90 90 92 92 92

Mass of front-face type (kg) 0.5 0.7 0.9 0.55 0.75 1.0 0.55 0.75 1.0 0.8 1.0 1.3 0.8 1.0 1.3 1.4 1.6 2.0 1.4 1.6 2.0 1.5 1.8

Instal

lation

and

conn

ectio

ns Front connection (F) Page �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal � � �Screw terminalSolderless (BOX) terminal (SL)

94� � � � � � � �

Rear (B) �Round stud �Round stud �Round stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud Plug-in (PM) � � � � � � � � � �

Cas

sette

-typ

e ac

cess

orie

s

Alarm switch (AL)

104

� (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3)Auxiliary switch (AX) � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3)Shunt trip (SHT) � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3)Undervoltage trip (UVT) � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3) � � (*3)With lead-wire terminal block (SLT) 116 � � � � � � � � � � � � �

Pre-alarm (PAL) 118 − − − − − − − −

Ext

erna

l acc

esso

ries

EnclosureClosed (S)

132� − � − � − � − � − � − − −

Dustproof (I) � − � − � − � − � − � − � − −Waterproof (W) − � − − � − − � − � − � − � − � − −

Electrical operation device (NFM) 135 − − − � � � � �

Mechanicalinterlock (MI) (*4)

Panel mounting131

� � � � � � � � � � � � �

Breaker mounting � − � − � − � − � − � � �

Handle lockdevice

LC129

� � � � � � � �

HL � � � � � � � �

HL-S � � � � � � � �

Externaloperating handle

(F)119

� � � � � � � �

(V) � � � � � � � �

Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 123 � � � � � � � � � � � � �

Rear stud (B-ST)96

� � � � � � � � � � � −Plug-in (PM) � � � � � � � � � � � � � � �

IEC 35mm rail mounting adapters 139 � − � − � − − − − − −CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration

CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in processMarine use approval (NK, LR, ABS, GL) � − � − � − � − � − � (LR, ABS, GL) − � (LR, ABS, GL) − � (LR, ABS, GL)

Automatic tripping device Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magneticTrip button Equipped Equipped Equipped Equipped Equipped Equipped Equipped Equipped

Page of Characteristics and dimensions 144 146 154 154 154

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products.

If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively. *3 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame

(excluding UVT). *4 Not isolation compatible, excluding 400 to 800A frame. *5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products.

Not available for use with connection as shown on the right.

Line

3-poleLoad

Line

4-poleLoad

Available soon

2 Molded Case Circuit BreakersDetailedSpecifications 1

6

22

2

1D

etai

led

Spe

cific

atio

ns

Frame (A) 250 400 630 800Model NF250-HEV NF400-HEW NF400-REW NF630-HEW NF630-REW NF800-HEW NF800-REW

Image

Rated current In (A)Rated ambient temperture 40°C (45°C for marine use) 80-160 125-250 Adjustable 200 225

250 300 350 400Adjustable 200 225 250 300 350 400

Adjustable 300 350400 500 600 630

Adjustable 300 350400 500 600 630

Adjustable 400 450500 600 700 800

Adjustable 400 450500 600 700 800

Number of poles 3 4 3 4 3 3 4 3 3 4 3Rated insulation voltage Ui (V) 690 690 690 690 690 690 690

Rated

short

-circu

it brea

king c

apac

ities (

kA)

IEC 60947-2EN 60947-2(Icu/Ics)

AC

690V 10/8 35/18 − 35/18 − 15/15 −500V 50/38 50/50 70/35 50/50 70/35 50/50 70/35440V 65/65 65/65 125/63 65/65 125/63 65/65 125/63415V 70/70 70/70 125/63 70/70 125/63 70/70 125/63400V 75/75 70/70 125/63 70/70 125/63 70/70 125/63380V 75/75 70/70 125/63 70/70 125/63 70/70 125/63230V 100/100 100/100 150/75 100/100 150/75 100/100 150/75200V 100/100 100/100 150/75 100/100 150/75 100/100 150/75

DC 250V − − − − − − −Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8 8 8

Current AC AC AC AC AC AC ACSuitability for isolation Compatible Compatible Compatible Compatible Compatible Compatible CompatibleReverse connection Possible Possible Possible Possible Possible Possible Possible

Number ofoperating cycles

Without current 25,000 6,000 6,000 6,000 6,000 4,000 4,000With current (440VAC) 10,000 1,000 1,000 1,000 1,000 500 500

Utilization category A B B B B B BRated short time with stand current Icu (kA) at 0.25s − 5 5 7.6 7.6 9.6 9.6

Pollution degree 3 3 3 3 3 3 3EMC environment condition (environment A or B) A A A A A A A

Overa

lldim

ensio

ns (m

m) a

b

cac a 105 140 140 185 140 140 185 140 210 280 210

b 165 257 257 257 257 275 275c 68 103 103 103 103 103 103ca 92 155 155 155 155 155 155

Mass of front-face type (kg) 1.7 2.2 6.0 7.6 6.0 6.5 8.3 6.0 10.9 14.2 10.9

Instal

lation

and

conn

ectio

ns Front connection (F) Page �Screw terminal �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminalSolderless (BOX) terminal (SL)

94� � � � � � � � � � �

Rear (B) �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud Plug-in (PM) � � � � � � � � � � �

Cas

sette

-typ

e ac

cess

orie

s

Alarm switch (AL)

104

� (*1) � � (*1) � � (*1) � (*1) � � (*1) � (*1) � � (*1)Auxiliary switch (AX) � (*1) � � (*1) � � (*1) � (*1) � � (*1) � (*1) � � (*1)Shunt trip (SHT) � (*1) � � (*1) � � (*1) � (*1) � � (*1) � (*1) � � (*1)Undervoltage trip (UVT) � (*1) � � � � � � � � � �

With lead-wire terminal block (SLT) 116 � � � � � � � � � � �

Pre-alarm (PAL) 118 � � (*2) � (*2) � (*2) � (*2) � (*2) � (*2)

Ext

erna

l acc

esso

ries

EnclosureClosed (S)

132− − − − − − −

Dustproof (I) � − − − − − − −Waterproof (W) � − − − − − − −

Electrical operation device (NFM) 135 � � (*3) � (*3) � (*3) � (*3) � (*3) � (*3)Mechanical

interlock (MI) (*4)Panel mounting

131� � � � � � � � � � �

Breaker mounting � − � − � � − � � − �

Handle lockdevice

LC129

� − − − − − −HL � � � � � � �

HL-S � � � � � � �

Externaloperating handle

(F)119

� � � � � � �

(V) � � � � � � �

Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 123 � � � � � � � � � �

Rear stud (B-ST)96

� � � � � � � � � �

Plug-in (PM) � � � � � � � � �

IEC 35mm rail mounting adapters 139 − − − − − − −CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration

CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in processMarine use approval (NK, LR, ABS, GL) � (LR, ABS, GL) − � − � � − � � − �

Automatic tripping device Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection)Trip button Equipped Equipped Equipped Equipped Equipped Equipped Equipped

Page of Characteristics and dimensions 156 160 160 166 166 168 168

NF-H / NF-R (High-performance class)

Notes: *1 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT).

*2 Solid state relay output is option. Please specify if other output is necessary. (Standard type is thus SLT equipped).

*3 Place an order of other models in conjunction with the circuit breaker. *4 Not isolation compatible, excluding 400 to 800A frame.

Line

3-poleLoad

Line

4-poleLoad

2 Molded Case Circuit BreakersDetailedSpecifications 1

7

1-3 Earth Leakage Circuit Breakers

26

2

2D

etai

led

Spe

cific

atio

ns

NV-S (Standard class) Harmonic Surge Ready Frame (A) 30 32 50 60 63 100 125 125

Model NV32-SV NV63-SV NV125-SV NV125-SEV

Image

Rated current In (A)Rated ambient temperture 40°C

(5) 6 10 (15) 16 20 25 (30) (32) (5) (10) (15) 16 20

25 (30) 32 40 50 (60) 63 (15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 (*3) 125 63-125

Number of poles 3 3 3 3 3 3 4 3 4 3 4

Phase line (*1) 3f3W, 1f3W,1f2W

3f3W, 1f3W,1f2W

3f3W, 1f3W,1f2W

3f3W, 1f3W,1f2W

3f3W, 1f3W,1f2W

3f3W,1f3W,1f2W

3f4W3f3W,1f3W,1f2W

3f4W 3f3W, 1f2W 3f4W

Rated operational voltage Ue (V) (*2) AC 100-440 100-440 100-440 100-440 100-440 100-440 200-440 100-440 200-440 100-440

Hig

h-sp

eed

type

Rated current sensitivity (mA) 30,100/200/500selectable

30,100/200/500selectable

30,100/200/500selectable

30,100/200/500selectable

30,100/200/500selectable

30,100/200/500selectable

30,100/200/500selectable

(30),100/200/500selectable

Max. operating time (s)at IΔn 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1at 5IΔn 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04

Tim

e-de

lay

type

Rated current sensitivity (mA) − − − − − (100/200/500selectable) (100/200/500selectable) (100/200/500selectable)Max. operating time (s) (*4) − − − − − (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable)Internal non-operating (s) (or more) − − − − − (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0)

Earth leakage indication system Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button)

Rated

short

-circu

itbre

aking

capa

cities

(kA)

IEC 60947-2EN 60947-2(Icu/Ics)

AC

440V 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 25/25 25/25 36/36415V 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 30/30 30/30 36/36400V 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 30/30 30/30 36/36230V 10/10 10/10 15/15 15/15 15/15 50/50 50/50 85/85200V 10/10 10/10 15/15 15/15 15/15 50/50 50/50 85/85100V 10/10 10/10 15/15 15/15 15/15 50/50 − 50/50 − 85/85

Rated impulse withstand voltage Uimp (kV) 6 6 6 6 6 6 6 6Current AC AC AC AC AC AC AC AC

Suitability for isolation Compatible Compatible Compatible Compatible Compatible Compatible Compatible CompatibleReverse connection (below 230VAC) Possible Possible Possible Possible Possible Possible Possible Possible

Number ofoperating cycles

Without current 10,000 10,000 15,000 15,000 15,000 25,000 25,000 25,000With current 6,000 6,000 8,000 8,000 8,000 10,000 10,000 10,000

Utilization category A A A A A A A ARated short time withstand current Icu (kA) at 0.25s − − − − − − − −

Pollution degree 2 2 2 2 2 2 2 2EMC environment condition (environment A or B) A A A A A A A A

Overa

lldim

ensio

ns (m

m) a

b

cac a 75 75 75 75 75 90 120 90 120 105 140

b 130 130 130 130 130 130 130 165c 68 68 68 68 68 68 68 68ca 90 90 90 90 90 90 90 92

Mass of front-face type (kg) 0.75 0.75 0.75 0.8 0.8 1.1 1.4 1.1 1.4 1.9 2.5

Instal

lation

and

conn

ectio

ns Front connection (F) Page �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminal �

Solderless (BOX) terminal (SL)94

− − − − − − − −Rear (B) �Round stud �Round stud �Round stud �Round stud �Round stud �Bar stud �Bar stud �Bar stud Plug-in (PM) − − − − − − − −

Cas

sette

-typ

e ac

cess

orie

s

Alarm switch (AL)

104

� (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � � (*5) � � (*5) �

Auxiliary switch (AX) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � � (*5) � � (*5) �

Shunt trip (SHT) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � � (*5) � � (*5) �

Undervoltage trip (UVT) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � � (*5) � � (*5) �

Earth leakage alarm switch (EAL) − − − − − − − −With lead-wire terminal block (SLT) 116 � � � � � � � � � �

Test button module (TBM) 117 � (*6) � (*6) � (*6) � (*6) � (*6) � (*6) � (*6) � (*6)

Ext

erna

l acc

esso

ries

EnclosureClosed (S)

132− − − − − − − � −

Dustproof (I) − − − − − − − � −Waterproof (W) − − − − − − − � −

Electrical operation device (NFM) 135 − − − − − � � �

Mechanicalinterlock (MI) (*8)

Panel mounting131

� � � � � � � � � �

Breaker mounting � � � � � � − � − � −

Handle lockdevice

LC129

� � � � � � � �

HL � � � � � � � �

HL-S � � � � � � � �

Externaloperating handle

(F)119

� � � � � � � �

(V) � � � � � � � �

Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 123 � � � � � � � �

Rear stud (B-ST)96

� � � � � � � �

Plug-in (PM) − − − − − − − −IEC 35mm rail mounting adapters 139 � � � � � − − −

CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declarationCCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognized

Marine use approval (NK, LR, ABS, GL) − − − − − − − −Automatic tripping device Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Electronic (effective value detection)

Trip button Equipped Equipped Equipped Equipped Equipped Equipped Equipped EquippedPage of Characteristics and dimensions 182 182 184 188

Notes: *1 If using a 3-pole earth leakage cirsuit breaker as a 1-pole 2-phase device, connect the left and right poles and not the central pole. When wiring to single-phase 3-wire, connect the neutral line to the central pole.

*2 In case of time delay type, rated voltage is 200-440VAC. *3 In case of time delay type, rated current is prodused with 20 amp. or less. *4 When the operating time are 0.45, 1.0 and 2.0 seconds, the Earth Leakage circuit

breaker operates between 0.15 and 0.45 seconds, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively.

*5 Cassette type accessories are fi eld mountable type. It can respend to adhesion attachment of a breaker as standard below 250A frame. (excluding UVT.)

*6 Standard type is SLT equipped. *7 Place an order of other models in conjunction with the circuit breaker. *8 Not isolation compatible, excluding 400 to 800A frame. *9 AC100V does not acquire the CCC certifi cation.

2 Earth Leakage Circuit BreakersDetailedSpecifications 2

8

24

2

NV-C (Economy class) Harmonic Surge Ready Frame (A) 50 60 63 100 125

Model NV63-CV NV125-CV

Image

Rated current In (A)Rated ambient temperture 40°C

(5) (10) (15) 16 20 25 (30) 32 40 50 (60) 63 (60) 63 (75) 80 100 125

Number of poles 2 3 2 3 2 3 3 3

Phase line (*1) 1f2W 3f3W, 1f3W,1f2W 1f2W 3f3W, 1f3W,

1f2W 1f2W 3f3W, 1f3W,1f2W 3f3W, 1f3W, 1f2W 3f3W, 1f3W, 1f2W

Rated operational voltage Ue (V) (*2) AC 100-240 100-440 100-240 100-440 100-240 100-440 100-440 100-440

Hig

h-sp

eed

type

Rated current sensitivity (mA) 30 30,100/200/500selectable 30 30,100/200/500

selectable 30 30,100/200/500selectable

30,100/200/500selectable

30,100/200/500selectable

Max. operating time (s)at IΔn 0.1 0.1 0.1 0.1 0.1at 5IΔn 0.04 0.04 0.04 0.04 0.04

Tim

e-de

lay

type

Rated current sensitivity (mA) − − − (100/200/500 selectable) (100/200/500 selectable)Max. operating time (s) (*3) − − − (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable)Internal non-operating (s) (or more) − − − (0.1/0.5/1.0) (0.1/0.5/1.0)

Earth leakage indication system Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button)

Rated

short

-circu

itbre

aking

capa

cities

(kA)

IEC 60947-2EN 60947-2(Icu/Ics)

AC

440V − 2.5/2.5 − 2.5/2.5 − 2.5/2.5 10/5 10/5415V − 2.5/2.5 − 2.5/2.5 − 2.5/2.5 10/5 10/5400V − 5/5 − 5/5 − 5/5 10/5 10/5230V 7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15200V 7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15100V 7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15

Rated impulse withstand voltage Uimp (kV) 6 6 6 6 6Current AC AC AC AC AC

Suitability for isolation Compatible Compatible Compatible Compatible CompatibleReverse connection (below 230VAC) Possible Possible Possible Possible Possible

Number ofoperating cycles

Without current 10,000 10,000 10,000 10,000 10,000With current 6,000 6,000 6,000 6,000 6,000

Utilization category A A A A APollution degree 2 2 2 2 2

EMC environment condition (environment A or B) A A A A A

Overa

lldim

ensio

ns (m

m) a

b

cac a 75 75 75 90 90

b 130 130 130 130 130c 68 68 68 68 68

ca 90 90 90 90 90Mass of front-face type (kg) 0.7 0.75 0.7 0.75 0.7 0.75 1.0 1.0

Instal

lation

and

conn

ectio

ns Front connection (F) Page �Screw terminal �Screw terminal �Screw terminal �Screw terminal �Screw terminalSolderless (BOX) terminal (SL)

94− − − − −

Rear (B) �Round stud �Round stud �Round stud �Bar stud �Bar stud Plug-in (PM) − − − − −

Cas

sette

-typ

e ac

cess

orie

s

Alarm switch (AL)

104

� (*4) � (*4) � (*4) � (*4) � (*4)Auxiliary switch (AX) � (*4) � (*4) � (*4) � (*4) � (*4)Shunt trip (SHT) � (*4) � (*4) � (*4) � (*4) � (*4)Undervoltage trip (UVT) � (*4) � (*4) � (*4) � (*4) � (*4)Earth leakage alarm switch (EAL) − − − − −With lead-wire terminal block (SLT) 116 � � � � �

Test button module (TBM) 117 � (*5) � (*5) � (*5) � (*5) � (*5)

Ext

erna

l acc

esso

ries

EnclosureClosed (S)

132− − − − −

Dustproof (I) − − − − −Waterproof (W) − − − − −

Electrical operation device (NFM) 135 − − − � �

Mechanicalinterlock (MI) (*7)

Panel mounting131

� � � � �

Breaker mounting � � � � �

Handle lockdevice

LC129

� � � � �

HL � � � � �

HL-S � � � � �

Externaloperating handle

(F)119

� � � � �

(V) � � � � �

Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 123 � � � � �

Rear stud (B-ST)96

� � � � �

Plug-in (PM) − − − − −IEC 35mm rail mounting adapters 139 � � � − −

CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declarationCCC recognition − Recognition in process − Recognition in process − Recognition in process Recognition in process Recognition in process

Marine use approval (NK, LR, ABS, GL) − − − − −Automatic tripping device Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic

Trip button Equipped Equipped Equipped Equipped EquippedPage of Characteristics and dimensions 182 184

2D

etai

led

Spe

cific

atio

ns

Notes: *1 If using a 3-pole earth leakage circuit breaker as a 1-pole 2-phase device, connect the left and right poles and not the central pole. When wiring to single-phase 3-wire, connect the neutral line to the central pole.

*2 In case of time delay type, rated voltage is 200-440VAC. *3 When the operating time are 0.45, 1.0 and 2.0 seconds, the Earth Leakage circuit

breaker operates between 0.15 and 0.45 seconds, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively.

*4 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT).

*5 Standard type is SLT equipped.

*6 Place an order of other models in conjunction with the circuit breaker. *7 Not isolation compatible, excluding 400 to 630A frame. *8 AC100V does not acquire the CCC certifi cation.

2 Earth Leakage Circuit BreakersDetailedSpecifications 2

9

1-3 Earth Leakage Circuit Breakers

25

2

NV-C (Economy class) Harmonic Surge Ready 225 250 400 600 630

NV250-CV NV400-CW NV630-CW

125 150 175 200 225 250 250 300 350 400 500 600 (630)

3 3 3 3 3

3f3W, 1f3W, 1f2W 3f3W, 1f3W, 1f2W 3f3W, 1f3W, 1f2W 3f3W, 1f3W, 1f2W 3f3W, 1f3W, 1f2W

100-440 100-440 100-440 200-440 200-44030,100/200/500

selectable30,100/200/500

selectable(30),100/200/500

selectable − −

0.1 0.1 0.1 − −0.04 0.04 0.04 − −

(100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable)(0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable)

(0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0)Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button)

15/12 15/12 25/13 36/18 36/1825/19 25/19 36/18 36/18 36/1825/19 25/19 36/18 36/18 36/1836/27 36/27 50/25 50/25 50/2536/27 36/27 50/25 50/25 50/2536/27 36/27 50/25 − −

6 6 8 8 8AC AC AC AC AC

Compatible Compatible Compatible Compatible CompatiblePossible Possible Possible Possible Possible

8,000 8,000 6,000 6,000 6,0004,000 4,000 1,000 1,000 1,000

A A A A A2 2 3 3 3A A A A A

105 105 140 140 140165 165 257 257 25768 68 103 103 10392 92 134 155 1551.7 1.7 6.1 6.9 6.9

�Screw terminal �Screw terminal �Busbar terminal �Busbar terminal �Busbar terminal− − − − −

�Bar stud �Bar stud �Bar stud �Bar stud �Bar stud − − − − −

� (*4) � (*4) � (*4) � (*4) � (*4)� (*4) � (*4) � (*4) � (*4) � (*4)� (*4) � (*4) � (*4) � (*4) � (*4)� (*4) � (*4) � � �

− − − − −� � � � �

� (*5) � (*5) � (*5) � (*5) � (*5)− − − − −− − − − −− − − − −� � � (*6) � (*6) � (*6)� � � � �

� � � � �

� � − − �

� � � � �

� � � � �

� � � � �

� � � � �

� � � � �

� � � � �

− − − − −− − − − −

TÜV approval TÜV approval Self-declaration Self-declaration Self-declarationRecognition in process Recognition in process Recognition in process Recognition in process Recognition in process

− − − − −Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic

Equipped Equipped Equipped Equipped Equipped186 190 194

2D

etai

led

Spe

cific

atio

ns

Remarks: 1. Products with rated current parenthesized are produced when an order is placed.

2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block.

3. The circuit breaker has the rated short-circuit breaking capacity specifi ed in the shaded cells.

4. Rated operational voltage Applicable circuit voltage Available voltage range100-240V 100/110/200/220/230/240V 85-264V100-440V 100/110/200/220/240/254/265/380/400/415/440V 85-484V200-440V 200/220/240/254/265/380/400/415/440V 160-484V

2 Detailed Specifications 2Earth Leakage Circuit Breakers

10

27

2

2D

etai

led

Spe

cific

atio

ns

NV-S (Standard class) Harmonic Surge Ready 225 250 250 400 400 600 630 630 800

NV250-SV NV250-SEV NV400-SW NV400-SEW NV630-SW NV630-SEW NV800-SEW

125 150 175200 225 250 125-125 250 300 350 400 Adjustable 200 225

250 300 350 400 500 600 (630) Adjustable 300 350400 500 600 630

Adjustable 400 450 500 600 700 800

3 3 3 3 3 4 3 3 3 4 3

3f3W, 1f3W,1f2W

3f3W, 1f3W,1f2W 3f3W, 1f2W 3f3W, 1f3W,

1f2W

3f3W, 1f3W, 1f2W

3f4W 3f3W, 1f3W,1f2W

3f3W, 1f3W,1f2W

3f3W, 1f3W, 1f2W

3f4W 3f3W, 1f3W,1f2W

100-440 100-440 100-440 100-440 100-440 200-440 200-440 100-440 200-440(30),100/200/500

selectable(30),100/200/500

selectable(30),100/200/500

selectable(30),100/200/500

selectable(30),100/200/500

selectable − − − −

0.1 0.1 0.1 0.1 0.1 − − − −0.04 0.04 0.04 0.04 0.04 − − − −

(100/200/500selectable) (100/200/500selectable) (100/200/500selectable) (100/200/500selectable) (100/200/500selectable) 100/200/500selectable 100/200/500selectable (100/200/500selectable) 100/200/500selectable(0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) 0.45/1.0/2.0selectable 0.45/1.0/2.0selectable (0.45/1.0/2.0selectable) 0.45/1.0/2.0selectable

(0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) 0.1/0.5/1.0 0.1/0.5/1.0 (0.1/0.5/1.0) 0.1/0.5/1.0Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button)

36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 42/4236/36 36/36 36/36 45/45 50/50 50/50 50/50 50/50 50/5036/36 36/36 36/36 45/45 50/50 50/50 50/50 50/50 50/5085/85 85/85 85/85 85/85 85/85 85/85 85/85 85/85 85/8585/85 85/85 85/85 85/85 85/85 85/85 85/85 85/85 85/8585/85 85/85 85/85 85/85 85/85 − − 85/85 −

6 6 6 8 8 8 8 8 8AC AC AC AC AC AC AC AC AC

Compatible Compatible Compatible Compatible Compatible Compatible Compatible Compatible CompatiblePossible Possible Possible Possible Possible Possible Possible Possible Possible25,000 25,000 25,000 6,000 6,000 6,000 6,000 6,000 4,00010,000 10,000 10,000 1,000 1,000 1,000 1,000 1,000 500

A A A A B A A B A− − − − 5 − − 7.6 9.62 2 2 3 3 3 3 3 3A A A A A A A A A

105 105 105 140 140 185 140 140 140 185 210165 165 165 257 257 257 257 257 27568 68 68 103 103 103 103 103 10392 92 92 155 155 155 155 155 1551.9 1.9 1.9 6.4 6.2 8.2 6.9 6.9 7.1 8.9 15.3

�Screw terminal �Screw terminal � �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminal �Busbar terminal− − − − − − − − −

�Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud �Bar stud − − − − − − − − −

� (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5)� (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5)� (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5) � (*5)� (*5) � (*5) � (*5) � � � � � �

− − − − − − − − −� � � � � � � � �

� (*6) � (*6) � (*6) � (*6) � (*6) � (*6) � (*6) � (*6) � (*6)− − � − − − − − −− − � − � − − − � − −− − � − � − − − � − −� � � � (*7) � (*7) � (*7) � (*7) � (*7) � (*7)� � � � � � � � �

� � � � � � � � �

� � � − − − − − −� � � � � � � � �

� � � � � � � � �

� � � � � � � � �

� � � � � � � � �

� � � � � � � � �

� � � � � � � � �

− − − − � − − � −− − − − − − − − −

TÜV approval TÜV approval Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declarationRecognition in process Recognition in process Recognized Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process

− − − − − − − − −Thermal-magnetic Thermal-magnetic Electronic (effective value detection) Thermal-magnetic Electronic (effective value detection) Thermal-magnetic Thermal-magnetic Electronic (effective value detection) Electronic (effective value detection)

Equipped Equipped Equipped Equipped Equipped Equipped Equipped Equipped Equipped186 188 190 192 194 196 198

Remarks: 1. Products with rated current parenthesized are produced when an order is placed.

2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block.

3. The circuit breaker has the rated short-circuit breaking capacity specifi ed in the shaded cells.

4. Rated operational voltage Applicable circuit voltage Available voltage range100-440V 100/110/200/220/240/254/265/380/400/415/440V 85-484V200-440V 200/220/240/254/265/380/400/415/440V 160-484V

2 Detailed Specifications 2Earth Leakage Circuit Breakers

11

Molded Cage Circuit Breakers — Japan Series1-4

1φ2W 3φ3W1φ2W 1φ2W 3φ3W

1φ2W 1φ2W3φ3W1φ2W1φ3W

2 3 2 3 2 3 2 3 2 3 2 3

2 4 6.3 816

0.3 0.4 0.6 0.81.2 1.4 2 2.54 7.1 8 12 1625 32 45

-1.4 2.5 46.3 7.116 25 3245

AC(V)DC(V)

AC 240VDC 60V

400V230V

DC 60V

415V240V230V

DC 60V

415V200V

DC 65V

200V100V

a 40 60 40 60 50 75 40 60 40 60 50 75bc

ca0.14 0.12 0.16 0.22 0.25 0.37 0.16 0.22 0.18 0.24 0.3 0.43

(LC)(HL)

Small terminal cover (TC-S)Large terminal cover (TC-L)

(RTC)

Notes: *1 If using a 3-pole earth leakage circuit breaker as a 1-pole 2-phase device, *7 UL(cURus) is certified. CCC・TUV is not certified. connect the left and right poles and not the central pole. When wiring to single- *8 UL(cURus) ・CCC・TUV is not certified. phase 3-wire, connect the neutral line to the central pole. *9 only alarm switch(excluding NF30-FAU,NF50-FAU SHT+AL)*2 0.1 for UL1053 *10 Rated current sensitivity 30mA/50mA is available for motor protection rated current*3 Rated shor-circuit breaking capacity of product which is 5A of rated current is 1.5kA.*4 Rated shor-circuit breaking capacity of product which is 5A of rated current is 1.5/1kA .*5 Standard type is SLT equipped.*6 Lead wires come from load side of the breaker as standard. Lead wires come from lateral   side of the breaker is also available as an option.

Remarks: (1) breaking capacity of indicate to breaker. (2)

30 50 100

-

5030NF30-FAU NF50-FAU NF50-FHU NF100-FHU

- - - - 30 30 30 50 100

NV30-FAU NV50-FAU NV50-FHU NV100-FHU

Circuit Breakers for control panel(FAU/FHU series)

Rated current In(A)Rated ambient temperture 40℃

10050503010050Molded Case Circuit Breakers Earth Leakage Circuit Breakers(Harmonic Surge Ready)

Frame(A)

3

3 5 10 1520 30 40 50 60 75 100 5 10 15 20

30 40 50

5 10 15 2030 40 50

5 10 15 2030

Phase line(*1)

Number of poles

For motor protection Rated current(*13)

Model

Image

3φ3W1φ2W1φ3W

- - - -

60 75 1005 10 15 2030 40 50

5 10 15 2030

3

- - - -

Rated current sensitivity I△n mA

Earth leakage indication system

High-speed type Max. operating time(s) at 5I△1n(*2)

Pickup current , UL 1053 -

- - - -

75% of I△n 75% of I△n 75% of I△n- - - 75% of I△n0.04 0.04 0.04 0.04

Mechanical type(button) Mechanical type(button) Mechanical type(button) Mechanical type(button)

GB 14048.2(Icu/Ics)

IEC 60947-2EN 60947-2

(Icu/Ics)

UL1077CSA C22.2

No.235

Rat

ed s

hort-

circ

uit

Bre

akng

Cap

aciti

es(k

A)

240 24060 60

2.5(*3)2.5(*3)

Rated insullation voltage(V)

AC

AC

Rated voltageAC(V)Jis C 8201-2-2Ann.1 Ann.2

(Icu/Ics

Jis C 8201-2-1Ann.1 Ann.2

(Icu/Ics)

Rated voltage

AC

Rated insullation voltage(V)

Rated insullation voltage(V)

AC

- - - - - -240 240 240 240 240 240

500 500 AC230V(rated voltage) AC230V(rated voltage) AC240V(rated voltage) AC240V(rated voltage)

5 5

250- - - - - -

250

51.5 1.5

5 2.5(*3) 2.5(*3)

- -2.5/1(*4) 2.5/1(*4) 5/2 5/2 - - 5/2 5/2

- - 1.5/1 - - -

- -250 250 500 500 AC230V(rated voltage) AC230V(rated voltage) AC240V(rated voltage) AC240V(rated voltage)

1.5/1 1.5/1 - - - -

- -- - 5/2 5/2 - - 5/2 5/2- - 1.5/1 - - -

- -1.5/1 1.5/1 - - - - - -

2.5/1(*4) 2.5/1(*4) - - 2.5/1(*4) 2.5/1(*4)

- -- - 1.5/1 - - - - -

250 250 500 500 - -

- -1.5/1 1.5/1 - - - - - -

2.5/1(*4) 2.5/1(*4) 5/2 5/2 - -

100-200 100-200- - - - 2.5/1(*4) 2.5/1(*4) 5/2 5/2- - - - 100-200 100-200

5/2 5/2Rated impluse withstand voltage Uimp(kV) 2.5 2.5 4 4 2.5 2.5 4

- - - - 2.5/1(*4) 2.5/1(*4)4

Current AC/DC compatible AC/DC compatible AC AC AC AC AC AC- - -

Ove

rall

dim

entio

ns(

mm

)

7597.56076

Suitability for isolation - - - - -

76 7657 57 60 57 57 60

75

Screw terminal Screw terminal Screw terminal Screw terminal Screw terminal Screw terminal

Mass kg 0.51 0.57

Screw terminal Screw terminal● ● ● ● ● ● ● ●Installation

Reverse connection - - - - - -

6073.5 73.5 76 73.5 73.5

72 72 96 72 72 96 97.5

- -

● ●

● ●

● ●

Alarm switch(AL)Auxiliary switch(AX)

Shunt trip(SHT)- -

● ●

● ●

●(*5) ●(*6)●(*5) ●(*6)●(*5) ●(*6)

●(*8) ●(*8)

--

●(*5) ●(*6)●(*5) ●(*6)

- -

●(*8)- -

- -

● ●

- -

● ●

- -

● ● ● ●● ●

- -

●(*8) ●(*8)

TUV approvalCE marking TUV approval TUV approval TUV approval TUV approval TUV approval●

-

● ●

-Front plate connection terminal cover

Ext

erm

inal

acc

esso

ries

●(*7) ●(*7)●(*7) ●(*7)

●(*8) ●(*8)- -

●(*7)

Recognized Recognized Recognized Recognized Recognized Recognized

Connection

TUV approval TUV approval

●(*7)●(*7) ●(*7)

● ●

●(*8) ●(*8)●(*8) ●(*8)

● ●

●(*8)

Handle lock devise

Test lead wire(TBL)Optional accessories

- - -

With lead-wire terminal block(SLT)

Front connectionIEC 35mm rail

Trip button -(*9) -(*9) -(*9) -(*9) -

RecognizedAutomatic tripping device Termal-magnetic Termal-magnetic Termal-magnetic Termal-magneticHydrautic magnetic Hydrautic magnetic Hydrautic magnetic Hydrautic magnetic

CCC recognition Recognized

12

2 3 2 3 2 3 2 3 2 3 2 3 2 3

690V500V440V415V400V380V230V200V250V125V415V400V380V230V250V125V

a 36 54 36 54 36 54 36 54 36 54

b

c

ca

0.3 0.4 0.3 0.4 0.3 0.4 0.3 0.4 0.3 0.4 0.75 0.85 0.75 0.85

Remarks: (1) breaking capacity of      indicate to breaker. (2)Producs with rated current parenthesized are produced when an order is placed.

Recognized RecognizedTUV approval

cass

ete

type

-ac

cess

sorie

s

Auxiliary switch(AX)Alarm switch(AL)

Shunt trip(SHT)Undervoltage trip(UVT)With lead-wire terminal block(SLT)

Recognized RecognizedCE marking TUV approval TUV approval TUV approval TUV approval

- - - -

- -Marine use approval(NK, LR, ABS, GL) - - - - -

Rear stud(B-ST)

IEC 35mm rail mounting adaptersPlug-in (PM)

Ext

erna

l a

cces

sorie

s

Enclosure

Electrical operation device(NFM)Mechanicalinterlock(MI)

Panel mountingBreaker mounting

Handle lockdevice

TUV approval TUV approvalCCC recognition Recognized Recognized Recognized

Rat

ed s

hort-

circ

uit

Bre

akng

Cap

aciti

es(k

A)

GB 14048.2(Icu/Ics)

Utilization categoryPollution degree

EMC environment condition(environment A or B)

Number of operating cycles

Without currentWith current(440VAC)

AC

DC(*2)

JIS C 8201-2-1 Ann.1JIS C 8201-2-1 Ann.2

IEC 60947-2EN 60947-2

(Icu/Ics)

AC

DC(*2)

Rated impluse withstand voltage Uimp(kV)

Termal-magneticTrip button equipped equipped equipped equipped equipped equipped equipped

Automatic tripping device Termal-magnetic Termal-magnetic Termal-magnetic Termal-magnetic Termal-magnetic Termal-magnetic

-- -

- - - - - -

● ●

- - - -● ● ● ●

- - -

●(*3)

● ● ● ● ● ●(*3) ●(*3)

●(*3) ●(*3)

●(*3) ●(*3) ●(*3) ●(*3) ●(*3) ●(*3)

●(*3)

●(*3)

●(*3) ●(*3) ●(*3) ●(*3)

●(*3) ●(*3) ●(*3) ●(*3)

Mass of front-face type kg

● ● ● ●

68

90 90 90 90 90 90 90

Front connection(F)

Inst

alla

tion

and

conn

ectio

n

Solderless(BOX) terminal(SL)

Rear(B)

Plug-in(PM)

68 68 68 68 68 68

● ● ●

N/A N/A N/A N/A N/A N/A

100 130 130

Reverse connection - - - - - Possible Possible

Ove

rall

dim

entio

ns(m

m) 75

3

100 100 100 100

3 3 3 3 3 3

75

N/A

AC/DC compatible AC/DC compatible AC/DC compatible

Suitability for isolation compatible compatible compatible compatible compatibleCurrent(*1) AC/DC compatible AC/DC compatible AC/DC compatible AC/DC compatible

compatible compatible

A AA A A A A

15,000 15,0006,000 6,000 6,000 6,000 6,000 8,000 8,00010,000 10,000 10,000 10,00010,000

25/25 25/257.5/7.5 7.5/7.5 15/15 15/15 15/15 50/50 50/50

5/5 5/5 10/8 10/8 10/8

25/255/5 5/5 10/8 10/8 10/8 25/25 25/255/5 5/5 10/8 10/8 10/8 25/25

50/50 50/507.5/7.5 7.5/7.5 15/15 15/15 15/15

25/257.5/7.5 7.5/7.5 15/15 15/15 15/15 50/50 50/50

25/25 25/255/5 5/5 10/8 10/8 10/8 25/25

25/25 25/255/5 5/5 10/8 10/8 10/85/5 5/5 10/8 10/8 10/8

- - - -

63 15 20 30 40 5060 75 100 125

10/102.5/2.5 2.5/2.5 7.5/6 7.5/6 7.5/6 20/20 20/20

- - -- - - - - 10/10

Number of polesRated insulation voltage Uimp(kV) 440 440 440 440 440 600 600

Rated current In(A)Rated ambient temperture 40℃ 3 5 10 15 20 30 32 (3) (5) 10 15 20

30 40 50 60

Model NF32-SVF NF63-SVF NF125-SVF

Image

NF-S(Standard class)

Frame(A) 30 32 50 60 63 100 125

standard equopped standard equopped standard equopped standard equopped standard equopped standard equopped standard equopped

-- - - - - - -- - - - - -

● ● ● ● ●Terminal cover(TC-L,TC-S,TTC,BTC,PTC)● ● ● ● ●

LCHLHL-S

● ●

- - - - - - -

● ●

● ● ● ● ● ● ●

● ● ● ● ●

Waterpoof(W)Dustproof(I)

- - - - -

-- - - - - - -- -

Closed(S)

- - - - - - -

- -

- - - - - - -

- - - - -

●(*3) ●(*3)

- - - -10/10 15/15 15/1510/10 10/10 10/10 10/10

6 6 6 6 6 8 8

-10/10 10/10 10/10 10/10 10/10 15/15 15/15

- - - - - -

- - -

13

1-4 Molded Cage Circuit Breakers — Japan Series

2 3 2 3 2 3 2 3 2 3

690V500V440V415V400V380V230V200V250V125V415V400V380V230V250V125V

a 36 54 36 54 36 54 50 75 50 75

b

c

ca

0.3 0.4 0.3 0.4 0.3 0.4 0.55 0.8 0.55 0.8

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatibe with both AC and DC*2 Use two poles for three-pole product.*3 The cassette type design makes it easy for customer to install.

NF-C(Economy class)

NF63-CVF NF125-CVF

Trip button equipped equipped equipped equipped equippedAutomatic tripping device Termal-magnetic Termal-magnetic Termal-magnetic Termal-magnetic Termal-magnetic

Marine use approval(NK, LR, ABS, GL) - - - - -CCC recognition Recognized Recognized Recognized Recognized Recognized

CE marking TUV approval TUV approval TUV approval TUV approval TUV approvalIEC 35mm rail mounting adapters standard equopped standard equopped standard equopped standard equopped standard equoppedPlug-in (PM) - - - - -Rear stud(B-ST) - - - - -Terminal cover(TC-L,TC-S,TTC,BTC,PTC) ● ● ● ● ●

● ● ● ●

HL ● ● ● ● ●

- -

Handle lockdevice

LC ● ● ● ● ●

-breaker mounting - - - - -

Mechanicalinterlock(MI)

Panel mounting - - - -

HL-S ●

Dustproof(I) - - - - -

Ext

erna

l a

cces

sorie

s

EnclosureClosed(S) - - - - -

Electrical operation device(NFM) - - - - -Waterpoof(W) - - -

●(*3)

With lead-wire terminal block(SLT) ● ● ● ● ●

Shunt trip(SHT) ●(*3) ●(*3) ●(*3) ●(*3) ●(*3)

cass

ete

type

-ac

cess

sorie

s

Alarm switch(AL) ●(*3) ●(*3) ●(*3) ●(*3)

Undervoltage trip(UVT) ● ● ● ●(*3)

- -

●(*3)

Auxiliary switch(AX) ●(*3) ●(*3) ●(*3) ●(*3) ●(*3)

Solderless(BOX) terminal(SL) - - - - -

Mass of front-face type kg

Inst

alla

tion

and

conn

ectio

n

Front connection(F) ● ● ● ● ●

Plug-in(PM) - - - - -

Rear(B) - - -

Ove

rall

dim

entio

ns(m

m)

100 100 100 130 130

EMC environment condition(environment A or B) N/A N/A N/A N/A N/A

90 90 90 90 90

68 68 68 68 68

Pollution degree 3 3 3 3 3Utilization category A A A A A

10,000With current(440VAC) 6,000 6,000 6,000 6,000 6,000

Number of operating cycles

Without current 10,000 10,000 10,000 10,000Reverse connection - - - Possible Possible

Suitability for isolation compatible compatible compatible compatible compatible

DC(*2)- - - 7.5/4 7.5/4

Current(*1) AC AC AC AC/DC compatible AC/DC compatibleRated impluse withstand voltage Uimp(kV) 6 6 6 8 6

GB 14048.2(Icu/Ics)

AC

- - -

5/5 5/5 5/5 10/5

5/5 5/5 5/5 10/5

7.5/47.5/4

- - - 7.5/4 7.5/4DC(*2) - - - 7.5/4 7.5/4

10/57.5/7.5 7.5/7.5 7.5/7.5 10/5 10/5

10/55/5 5/5 5/5 10/5 10/5

7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/157.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15

5/5 5/5 5/5 10/5 10/55/5 5/5 5/5 10/5 10/5

-- - - 7.5/4 7.5/4

600

Rat

ed s

hort-

circ

uit

Bre

akng

Cap

aciti

es(k

A)

JIS C 8201-2-1 Ann.1JIS C 8201-2-1 Ann.2

IEC 60947-2EN 60947-2

(Icu/Ics)

AC

- - - -

5/5 5/5 5/5 10/5 10/52.5/2.5 2.5/2.5 2.5/2.5 10/5 10/5

Number of polesRated insulation voltage Uimp(kV) 440 440 440 600

Rated current In(A)Rated ambient temperture 40℃

(3) (5) 10 15 2030 40 50 60 (63) 60 75 100 125

Model

Image

Frame(A) 50 60 63 100 125

14

100 125

15 20 30 (40) 5060 75 100 125

2 3 2 3 2 3 2 3 2 3 3 3

1φ2W 1φ2W,3φ3W1φ3W 1φ2W 1φ2W,3φ3W

1φ3W 1φ2W 1φ2W,3φ3W1φ3W 1φ2W 1φ2W,3φ3W

1φ3W 1φ2W 1φ2W,3φ3W1φ3W

1φ2W,3φ3W1φ3W

1φ2W,3φ3W1φ3W

AC 100-240 100-440 100-240 100-440 100-240 100-440 100-240 100-440 100-240 100-440 100-440 100-440

(mA) 30 30 100(200) (500) 30 30 100

(200) (500) 30 30 100(200) (500) 30 30 100

(200) (500) 30 30 100(200) (500)

30,100/200/500selectable

30,100/200/500selectable

at L△n 0.1 0.1

at 5l△n 0.04 0.04

(mA) (100/200/500) selectable

(100/200/500) selectable

(*4) (0.45/10./2.0 selectable)

(0.45/10./2.0 selectable)

(0.1/0.5/1.0) (0.1/0.5/1.0)Mechanical type

(button)Mechanical type

(button)440V - 2.5/2.5 - 2.5/2.5 - 7.5/6 - 7.5/6 - 7.5/6 20/20 20/20415V - 5/5 - 5/5 - 10/8 - 10/8 - 10/8 25/25 25/25400V - 5/5 - 5/5 - 10/8 - 10/8 - 10/8 25/25 25/25230V 50/50 50/50200V 50/50 50/50100V 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 15/15 15/15 15/15 15/15 50/50 50/50415V - 5/5 - 5/5 - 10/8 - 10/8 - 10/8 25/25 25/25400V - 5/5 - 5/5 - 10/8 - 10/8 - 10/8 25/25 25/25380V - 5/5 - 5/5 - 10/8 - 10/8 - 10/8 25/25 25/25230V 50/50 50/50

4 6 4 6 4 6 4 6 4 6 6 6AC AC

compatible compatiblepossible possible10,000 10,000

6,000(AC240V) 6,000 6,000(AC240V) 6,000 6,000(AC240V) 6,000 6,000(AC240V) 6,000 6,000(AC240V) 6,000 8,000 8,000A A2 2A A

a 36 54 36 54 36 54 36 54 36 54 75 75

b 130 130

c 68 68

ca 90 90

0.4 0.5 0.4 0.5 0.4 0.5 0.4 0.5 0.4 0.5 0.95 0.95

● ●

- -

- -

- -

- ●(*6) - ●(*6) - ●(*6) - ●(*6) - ●(*6) ●(*6) ●(*6)- ●(*6) - ●(*6) - ●(*6) - ●(*6) - ●(*6) ●(*6) ●(*6)- ●(*6) - ●(*6) - ●(*6) - ●(*6) - ●(*6) ●(*6) ●(*6)- ● - ● - ● - ● - ● ●(*6) ●

- -- ● - ● - ● - ● - ● ● ●

Test button module(TBM) ●(*7) ●(*7)- -- -- -- -- -- -

● ●

● ●

● ●

● ●

- -- -

standard equipped standard equippedTUV approval TUV approval

Recognized Recognized- -

Termal-magnetic Termal-magneticequipped equipped

Notes: *1 If using a 3-pole earth leakage circuit breaker as a 1-pole 2-phase device, *5 breaking capacity of 2P AC240V is same as 230V. connect the left and right poles and not the central pole. When wiring to single- *6 The cassette type design makes it easy for customer to install. phase 3-wire, connect the neutral line to the central pole. *7 Standard type is SLT equipped.*2 In case of time delay type, rated voltage is 200-440V.*3 In case of time delay tyoe, products can be produced more than 20A of rated current.*4 When the operating time are 0.45, 1.0 and 2.0 seconds, the Earth leakage circuit breaker operates between 0.15 and 0.45 seconds, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively.

standard equoppedTUV approval

Recognized-

Termal-magneticequipped

--

----

-

-

-

-

●(*7)

68

90

15/15

ACcompatible

-10,000

--

A

Visible color(Indication window)

15/1515/15

15/1515/15

2A

100

-

-

-

-

●(*7)

-

TUV approvalRecognized

-

-

2A

100

68

90

15/15

ACcompatible

-10,000

A

-

-

0.10.04

-

NV63-SVF

-

-Visible color

(Indication window)

Termal-magneticequipped

(63)

0.10.04

--

standard equopped

-----

Automatic tripping device Termal-magnetic Termal-magnetic Termal-magneticTrip button equipped equipped equipped

CCC recognition Recognized Recognized RecognizedMarine use approval(NK, LR, ABS, GL) - - -

IEC 35mm rail mounting adapters standard equopped standard equopped standard equoppedCE marking TUV approval TUV approval TUV approval

Rear stud(B-ST) - - -Plug-in (PM) - - -

- - -

● ● ●

Terminal cover(TC-L,TC-S,TTC,BTC,PTC) ● ● ●

Handle lockdevice

LC ● ● ●

HL ● ● ●

HL-S

Waterpoof(W) - - -Electrical operation device(NFM) - - -

Ext

erna

l a

cces

sorie

s

EnclosureClosed(S) - - -Dustproof(I) - - -

Mechanicalinterlock(MI)

Panel mounting - - -breaker mounting

- - -With lead-wire terminal block(SLT)

●(*7) ●(*7) ●(*7)

cass

ete

type

-ac

cess

sorie

s

Alarm switch(AL)Auxiliary switch(AX)Shunt trip(SHT)Undervoltage trip(UVT)Earth leakage alarm switch(EAL)

- - -

Plug-in(PM) - - -Inst

alla

tion

and

conn

ectio

n

Front connection(F) ● ● ●

Solderless(BOX) terminal(SL) - - -

Rear(B)

68 68

90 90 90

Mass of front-face type kg

EMC environment condition(environment A or B) A A A

Ove

rall

dim

entio

ns(m

m)

100 100 100

68

Utilization category A A APollution degree 2 2 2

Reverse connection(below 230VAC) - - -Number of

operating cyclesWithout current 10,000 10,000 10,000

With current(440VAC)

Rated impluse withstand voltage Uimp(kV)Current AC AC AC

Suitability for isolation compatible compatible compatible

GB 14048.2Icu/Ics) (*8) AC

7.5/7.5 7.5/7.5 15/15

Rat

ed s

hort-

circ

uit

Bre

akng

Cap

aciti

es(k

A) JIS C 8201-2-1 Ann.1

JIS C 8201-2-1 Ann.2IEC 60947-2 2nd.ed

(Icu/Ics) (*5)

AC7.5/7.5 7.5/7.5 15/157.5/7.5 7.5/7.5 15/15

- - -

Earth leakage indication system Visible color(Indication window)

Visible color(Indication window)

Visible color(Indication window)

Tim

e-de

lay

Type

Rated current sensitivity - - -

Max. operating tme(s) - - -

Internal non-operating(s) (or more)

0.1 0.1 0.10.04 0.04 0.04

Number of poles

Phase line(*1)

Rated operational voltage Ue(V) (*2)

Hig

h-sp

eed

Type

Rated current sensitivity

Max. operating tme(s)

Image

Rated current In(A)Rated ambient temperture 40℃ (5) (10) 15 20 30 (32) (5) (10) 15 20 30

45 50

NV-S(standard class) Harmonic Surge Ready

Frame(A) 30 32 50Model NV125-SVFNV32-SVF

60

60

63

15

1-4 Molded Cage Circuit Breakers — Japan Series

100 125

60 75 100 125

2 3 2 3 2 3 3 3

1φ2W 1φ2W,3φ3W1φ3W 1φ2W 1φ2W,3φ3W

1φ3W 1φ2W 1φ2W,3φ3W1φ3W

1φ2W,3φ3W1φ3W

1φ2W,3φ3W1φ3W

AC 100-240 100-440 100-240 100-440 100-240 100-440 100-440 100-440

(mA) 30 30 100(200) (500) 30 30 100

(200) (500) 30 30 100(200) (500)

30,100/200/500selectable

30,100/200/500selectable

at L△n 0.1 0.1at 5l△n 0.04 0.04

(mA) (100/200/500) selectable (100/200/500) selectable(*4) (0.45/10./2.0 selectable) (0.45/10./2.0 selectable)

(0.1/0.5/1.0) (0.1/0.5/1.0)Mechanical type

(button)Mechanical type

(button)440V - 2.5/2.5 - 2.5/2.5 - 2.5/2.5 10/5 10/5415V - 5/5 - 5/5 - 5/5 10/5 10/5400V - 5/5 - 5/5 - 5/5 10/5 10/5230V 30/15 30/15200V 30/15 30/15100V 30/15 30/15415V - 5/5 - 5/5 - 5/5 10/5 10/5400V - 5/5 - 5/5 - 5/5 10/5 10/5380V - 5/5 - 5/5 - 5/5 10/5 10/5230V 30/15 30/15

4 6 4 6 4 6 6 6AC AC

compatible compatiblepossible possible10,000 10,000

6,000(AC240V) 6,000 6,000(AC240V) 6,000 6,000(AC240V) 6,000 6,000 6,000A A2 2A A

a 36 54 36 54 36 54 75 75

b 130 130

c 68 68

ca 90 90

0.4 0.5 0.4 0.5 0.4 0.5 0.9 0.9

● ●

- -

- -

- -

- ●(*6) - ●(*6) - ●(*6) ●(*6) ●(*6)- ●(*6) - ●(*6) - ●(*6) ●(*6) ●(*6)- ●(*6) - ●(*6) - ●(*6) ●(*6) ●(*6)- ● - ● - ● ●(*6) ●(*6)

- -- ● - ● - ● ● ●

Test button module(TBM) ●(*7) ●(*7)- -- -- -- -- -- -

● ●

● ●

● ●

● ●

- -- -

standard equipped standard equippedTUV approval TUV approval

Recognized Recognized- -

Termal-magnetic Termal-magneticequipped equipped

Notes: *1 If using a 3-pole earth leakage circuit breaker as a 1-pole 2-phase device, *7 Standard type is SLT equipped. connect the left and right poles and not the central pole. When wiring to single- phase 3-wire, connect the neutral line to the central pole.*2 In case of time delay type, rated voltage is 200-440V.*3 In case of time delay tyoe, products can be produced more than 20A of rated current.*4 When the operating time are 0.45, 1.0 and 2.0 seconds, the Earth leakage circuit breaker operates between 0.15 and 0.45 seconds, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively.*5 breaking capacity of 2P AC240V is same as 230V.*6 The cassette type design makes it easy for customer to install.

- -

●(*7)

Visible color(Indication window)

Visible color(Indication window)

Visible color(Indication window)

Plug-in(PM) - - -

- - -

Rear(B) - -

Earth leakage indication system

-

Inst

alla

tion

and

conn

ectio

n

Front connection(F) ● ● ●

-

Trip button equipped

CCC recognition Recognized

Plug-in (PM) -

HL ●

breaker mounting -

Dustproof(I) -

With lead-wire terminal block(SLT)

Undervoltage trip(UVT)

Auxiliary switch(AX)Alarm switch(AL)

Shunt trip(SHT)

Earth leakage alarm switch(EAL)

cass

ete

type

-ac

cess

sorie

s

Mass of front-face type kg

-

equipped equippedAutomatic tripping device Termal-magnetic Termal-magnetic Termal-magnetic

Marine use approval(NK, LR, ABS, GL) - - -Recognized Recognized

CE marking TUV approval TUV approval TUV approvalIEC 35mm rail mounting adapters standard equopped standard equopped standard equopped

- -Rear stud(B-ST) - - -Terminal cover(TC-L,TC-S,TTC,BTC,PTC) ● ● ●

-

● ●Handle lockdevice

LC ● ● ●

HL-S ● ● ●

- -

●(*7) ●(*7)

Ext

erna

l a

cces

sorie

s

EnclosureClosed(S) - - -

Waterpoof(W) - - -

- -Mechanicalinterlock(MI)

Panel mounting - - -Electrical operation device(NFM) - -

Solderless(BOX) terminal(SL)

68 68 68Ove

rall

dim

entio

ns(m

m)

100 100 100

90 90 90

EMC environment condition(environment A or B) A A APollution degree 2 2 2

Utilization category A A AWith current(440VAC)

Number of operating cycles

Without current 10,000 10,000 10,000Reverse connection(below 230VAC) - - -

Suitability for isolation compatible compatible compatibleCurrent AC AC AC

Rated impluse withstand voltage Uimp(kV)

Rat

ed s

hort-

circ

uit

Bre

akng

Cap

aciti

es(k

A)

GB 14048.2Icu/Ics) (*8) AC

7.5/7.5 7.5/7.5 7.5/7.5

7.5/7.5 7.5/7.5 7.5/7.5

7.5/7.5 7.5/7.5 7.5/7.57.5/7.5 7.5/7.5 7.5/7.5

JIS C 8201-2-1 Ann.1JIS C 8201-2-1 Ann.2IEC 60947-2 2nd.ed

(Icu/Ics) (*5)

AC

NV125-CVF

Image

NV-C(Economy class) Harmonic Surge Ready

Frame(A) 50 60 63

Number of poles

Phase line(*1)

Rated current In(A)Rated ambient temperture 40℃ (5) (10) 15 20 30 40 50 60 (63)

Model NV63-CVF

-------Rated current sensitivity

Rated operational voltage Ue(V) (*2)

Hig

h-sp

eed

Type

Tim

e-de

lay

Type

0.040.040.04Max. operating tme(s)

Rated current sensitivity

0.1 0.1 0.1

Max. operating tme(s)Internal non-operating(s) (or more)

-

16

(0.5) (1) (1.5)(2) (3) 4 5(6) (7) (8) 1013 15 20 2530 (35) 40 50

1 2 3 2 3 2 3 2 3 2 3AC(V)DC(V) 60

600/Y/347V480V

480Y/277V240V 5120V 10

DC 60V 10

690V500V440V415V400V -380V230V 10/7.5250V125V 10/7.5

AC/DC

a 18 36 54 36 54 50 75 50 75 50 75

b

c

ca

0.15 0.3 0.45 0.3 0.45 0.55 0.8 0.5 0.75 0.55 0.8

Screw terminal(AMP/N)

Solderless terminal(SL)

Bar(BAR)

HLHL-S

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatibe with both AC and DC*2 The standard structure conforms to IP20(finger protection)*3 Rated ambient temperature for NF50-SVFU, NF100-CVFU, NF100-SRU, NF100-HRU is specified at 40℃ also by IEC*4 The circuit breaker with busbar teeminal have insullation barriers.*5 Isolation function is not available.*6 Circuit breaker for power supply solderless load screw terminal(SL/AMP-N) are available. In this case , a busbar terminal is not provided on the load side.*7 breaking capacity of ( ) is for below 15A of rated current.*8 optional parts.*9 These cassette type circuit breaker can be installed by the customer. They can be installed with their side faces in close contact(except NF50-SVFU and UVT)

UL 489CSA C22.2 No.5-02

JIS C 8201-2-1 Ann.1IEC 60947-2EN60947-2

(Icu/Ics)

Hnadle lock device

Large terminal cover(TC-L)

- -35/18(25/13) (*7) 50/25(25/13) (*7)

-

AC

10/510/5

-10/7.5

-10/7.5 15/8

10/515/8

50(25) (*9)

-

10/510/5

Ratedvoltage -

AC

-10 14

18/9(10/5) (*7)- 7.5/4 10/5 15/8 25/13(15/8) (*7)

500- - - -

Rated insulation voltageUi(V)

-- - - -

14

Trip button - equipped equipped equipped equippedAutomatic tripping device Termal-magnetic Termal-magnetic Termal-magnetic Termal-magnetic Termal-magnetic

Recognized RecognizedCE marking TUV approval TUV approval TUV approval TUV approval TUV approval

IEC 35mm rail mounting adapters - - - - -

CCC recognition Recognized Recognized Recognized

Ext

erm

nal

acc

esso

ries

Small terminal cover(TC-S) - - - - -

- ● ● ● ●

● ● ● ● ●

● ● ● ● ●

●(*4,6) ●(*6) ●(*6)

-

●(*9) ●(*9)With lead-wire terminal block(SLT) - ● ● ● ●

Shunt trip(SHT) ●(*8) ●(*9) ●(*9) ●(*9) ●(*9)

●(*9)Auxiliary switch(AX) ●(*8) ●(*9) ●(*9) ●(*9) ●(*9)

cass

ete

type

-ac

cess

sorie

s

Alarm switch(AL) ●(*8) ●(*9) ●(*9) ●(*9)

Undervoltage trip(UVT) - ● ●(*9)

Mass of front-face type kg

Inst

alla

tion

and

conn

ectio

n ● ● ● ● ●

70 90 90 96 102

- ●(*4) ● ●

- - ● ● ●

Fron

t(F)

- -

44 68 68 68 74Ove

rall

dim

entio

ns(m

m)

124 120 150 120 120

EMC environment condition(environment A or B) N/A N/A N/A N/A N/APollution degree 3 3 3 3 3

Utilization category A A A A A

10,000With current(440VAC) 6,000 6,000 6,000 6,000 6,000

Number of operating cycles

Without current 10,000 10,000 10,000 10,000Reverse connection possible - possible possible possible

Suitability for isolation compatible compatible compatible compatible compatible

-

10/5

DC(*2)

- - - - -

Current(*1) AC AC AC ACRated impluse withstand voltage Uimp(kV) 6 6 8 8 8

AC 25/13(15/8) (*7)25/13(15/8) (*7)

15/815/8

35(25) (*9)

-440 440 600 500

-

480- - - -

- - - - -- - - - 18(10) (*9)

- - -

- - 7.5/4 10/5

- - -

UL 489 Listed Mold Case Circuit Breakers

Frame(A)NF50-SMU NF50-SVFU

50 100NF100-CVFU NF100-SRU NF100-HRU

Power supply solderless load bar(SL/BAR)

(1) (2) 3 5 10 15 20 (25) 3040 50 60 (70) 75 (80) (90)

100

Model

Image

0.5 1 (1.5) 2 3 4 5(6) 7 (8) 10 13 15 20(25) 30 (35) (40) 50

Rat

ed s

hort-

circ

uit

Bre

akng

Cap

aciti

es(k

A)

240 240 240 240Number of poles

Rated current In(A)Rated ambient temperture 40℃(IEC 30℃) (*3)

(3) 5 10 1520 30 40 50

60 (70) 75(80) (90) 100

(1) (2) 3 5 10 15 20 (25) 3040 50 60 (70) 75 (80) (90)

100

- - - -

17

1-4 Molded Cage Circuit Breakers — Japan Series

NV100-CVFU NV100-HRU

60 (70) 75(80) (90) 100

5 10 15 20(25) 30 40 50

5 10 15 20 (25) 30 40 50

60 (70) 75 (80) (90) 100

5 10 15 20 (25) 30 40 5060 (75) (80) (90) 100

2 3 3 2 3 31φ2W 1φ2W,3φ3W 1φ2W,3φ3W 1φ2W 1φ2W,3φ3W 1φ2W,3φ3W

120-240 120-240-480

100-240 100-440 100-440 100-230-400-440

(mA) 30 50 30 50 10030 100

100・200・500selecable

30 5030 50

100・300・500selecable

30,100/200/500selectable

75% of l△n 75% of l△n

0.04 0.04

Mechanical type(button)

Mechanical type(button)

480V - 18(10) (*5)240V 14 50(25) (*5)120V 14 50(25) (*5)440V - 7.5/4 10/5 25/13(15/8) (*5)400V - 10/5 10/5 25/13(15/8) (*5)230V 15/8(*10) 15/8 15/8 50/25(25/13) (*5)100V 15/8 15/8 15/8 50/25(25/13) (*5)415V - 10/5 10/5 25/13(15/8) (*5)380V - 10/5 10/5 25/13(15/8) (*5)230V 15/8 50/25(25/13) (*5) (*8)

4 6 6 8compatible compatible

possible - possible possibleA A2 2A A

a 36 54 75 50 75 75

b 150 120

c 68 74

ca 90 102

0.4 0.5 0.9 0.55 0.85 0.95

● ●

● ●

●(*4) ●

●(4,6) ●(*6)- ●(*9) ●(*9) ●(*9)

- ●(*9) ●(*9) ●(*9)

- ●(*9) ●(*9) ●(*9)

- ● ●(*9) ●(*9)

- ● ● ●

●(*11) -

● ●

● ●

● ●

-(*2) ●(*2)standard equipped standard equipped

TUV approval TUV approvalRecognized Recognized

Termal-magnetic Termal-magneticequipped equipped

Notes: *1 If using a 3-pole earth leakage circuit breaker as a 1-pole 2-phase device, connect the left and right poles and not the central pole.*2 The standard structure conforms to IP20(finger protection)*3 0.1 for UL 1053.*4 The circuit breaker with busbar teeminal have insullation barriers.*5 breaking capacity of ( ) is for below 15A of rated current.*6 Circuit breaker for power supply solderless load screw terminal(SL/AMP-N) are available. In this case , a busbar terminal is not provided on the load side.*7 In case AC100V , not comply CCC recognition*8 In case AC 100V , comply CCC recognition.*9 These cassette type circuit breaker can be installed by the customer. They can be installed with their side faces in close contact(except NV50-SVFU and UVT)*10 breaking capacity of JIS C 8201-2 Ann.1 AC240V is same as 230V*11 Standard type is SLT equipped.* 12 Isolation function is not available and no TUV approval.

Rated current In(A)Rated ambient temperture 40℃

(5) (10) 15 20 30 40 50

UL 489 Listed Earth Leakage Circuit Breakers(Harmonic Surge Ready)

Frame(A) 50Model NV50-SVFU

Number of polesPhase line(*1)

Hig

h-sp

eed

Type

Rated voltage AC V

UL 489IEC 60947-2EN 60947-2

JIS C 8201-2-2 Ann1

Max. operating tme(s) at 5l△n (*4)

Image

Earth leakage indication system Visible color(Indication window)

120-240

Rated current sensitivity L△n

Mechanical type(button)

AC14

- -

75% of l△n 75% of l△n

0.04 0.04

Pickup current, UL 1053

35/18(25/13) (*5)

AC15/8 35/18(25/13) (*5)(*8)

AC

Rat

ed s

hort-

circ

uit

Bre

akng

Cap

aciti

es(k

A)

-

35/18(25/13) (*5)

14 35(25) (*5)

GB 14048.2Icu/Ics) (*7)

JIS C 8201-2-2 Ann.1IEC 60947-2EN 60947-2

(Icu/Ics)

UL 489CSA C22.2 No.5-02

-

--

●(*11) -cass

ete

type

-acc

esss

orie

s

Auxiliary switch(AX)

Alarm switch(AL)

Test button module(TBM)

With lead-wire terminal block(SLT)

Undervoltage trip(UVT)

Shunt trip(SHT)

CE marking TUV approval TUV approvalstandard equipped standard equipped

● ●

-(*2) ●(*2)Ext

erna

l a

cces

sorie

s Hnadle lock device

Large terminal cover(TC-L)Small terminal cover(TC-S)IEC 35mm rail mounting adapters

HL ● ●

HL-S ● ●

Automatic tripping device Termal-magnetic Hydrautic magneticTrip button equipped equipped

CCC recognition Recognized Recognized

120-240

100-230

100NV100-SRU

35(25) (*5)

●(*9)

●(*9)

●(*9)

- ●

- ●(*6)

● ●

- ●

68

90 96

A A

120 120

●(*9)

8

Fron

t(F)

Screw terminal(AMP/N)

Solderless terminal(SL)

Bar(BAR)

Mass of front-face type kg

EMC environment condition(environment A or B)

Ove

rall

dim

entio

ns(m

m)

68

Utilization category A APollution degree

Power supply solderless load bar(SL/BAR)Inst

alla

tion

and

conn

ectio

n

2 2

Reverse connection(below 230VAC) -

Rated impluse withstand voltage Uimp(kV)Suitability for isolation compatible compatible

18

NFB NV

For rightpole

AL-03SVAL-03SVRS

AX-03SVAX-03SVRS

ALAX-03SVALAX-03SVRS

SHTA240-03SVRSHTA440-03SVRSHTD100-03SVRSHTA240-03SVRSSHTA440-03SVRSSHTD100-03SVRS

-

For left pole

NV32-SVFNV63-CVFNV63-SVF

For left pole

For rightpole

AL-03SVUAL-03SVURS

AX-03SVUAX-03SVURS

ALAX-03SVUALAX-03SVURS

SHTA240-03SVURSHTA440-03SVURSHTD100-03SVURSHTA240-03SVURSSHTA440-03SVURSSHTD100-03SVURS

-

For left pole

NV50-SVFU For left pole

NF32-SV,NF63-CV,NF63-SV,NF63-HV,NF63-HRV,NF125-CVF,NF125-SVF,NF125-CV,NF125-SV,NF125-HV,NF125-SEV,NF125-HEV,NF125-RV,NF125-UV,NF250-CV,NF250-SV,NF250-HV,NF250-SEV,NF250-HEV,NF250-RV,NF250-UV,

For rightpole

AL-05SVAL-05SVRS

AX-05SVAX-05SVRS

ALAX-05SVALAX-05SVRS

SHTA240-05SVRSHTA550-05SVRSHTD125-05SVRSHTA240-05SVRSSHTA550-05SVRSSHTD125-05SVRS

UVTNAD130-05SVR UVTSAD130-05SVRUVTNA250-05SVR UVTSA250-SVRUVTNA480-05SVR UVTSA480-SVRUVTNAD130-05SVRS UVTSAD130-05SVRSUVTNA250-05SVRS UVTSA250-SVRSUVTNA480-05SVRS UVTSA480-SVRS

NV32-SV,NV63-CV,NV63-SV,NV63-HV,NV125-SVF,NV125-SVF,NV125-CV,NV125-SV,NV125-HV,NV125-SEV,NV125-HEV,NV250-CV,NV250-SV,NV250-HV,NV250-SEV,NV250-HEV

For left pole

AL-05SVAL-05SVLS

AX-05SVAX-05SVLS

ALAX-05SVALAX-05SVLS

SHTA240-05SVLSHTA550-05SVLSHTD125-05SVLSHTA240-05SVLSSHTA550-05SVLSSHTD125-05SVLS

UVTNAD130-05SVL UVTSAD130-05SVLUVTNA250-05SVL UVTSA250-SVLUVTNA480-05SVL UVTSA480-SVLUVTNAD130-05SVLS UVTSAD130-05SVLSUVTNA250-05SVLS UVTSA250-SVLSUVTNA480-05SVLS UVTSA480-SVLS

For rightpole

AL-05SVUAL-05SVURS

AX-05SVUAX-05SVURS

ALALX05SVUALAX-05SVURS

SHTA240-05SVURSHTA550-05SVURSHTD125-05SVURSHTA240-05SVURSSHTA550-05SVURSSHTD125-06SVURS

UVTNAD130-05SVUR UVTSAD130-05SVURUVTNA250-05SVUR UVTSA250-05SVURUVTNA480-05SVUR UVTSA480-05SVURUVTNAD130-05SVURS UVTSAD130-05SVURSUVTNA250-05SVURS UVTSA250-05SVURSUVTNA480-05SVURS UVTSA480-05SVURS

For left pole

NV100-CVFUNV125-SVU/HVUNV250-SVU/HVU

For left pole

For rightpole

AL-05SRUAL-05SRURS

AX-05SRUAX-05SRURS

ALAX-05SRUALAX-05SRURS

SHTA240-05SRURSHTA550-05SRURSHTD125-05SRURSHTA240-05SRURSSHTA550-05SRURSSHTD125-05SRURS

-

For left pole

NV100-SRUNV100-HRU

For left pole

For rightpole(2 or 3pole)

-AX-4SWAX-4SWRSAX2-4SWRS

-SHT-4SWSHT-4SWRS -

For rightpole(4 pole)

- - -SHT-4SWRFSSHT-8SWRFS -

For left pole(2,3 or 4pole)

NV400-CW,NV400-SW,NV400-SEW,NV400-HEW,NV400-REWNV630-CW,NV630-SW,NV630-SEW,NV630-HEW,NV800-SEW,NV800-HEW

For left pole(2,3 or 4pole)

Remarks: 1.For the possibility of installation of accessories and the installation pole , please refer general catalogue.

AL-03SVAL-03SVLS -

NF50-SVFU

NF32-SVFNF63-CVFNF63-SVF

SHTA240-03SVLSHTA440-03SVLSHTD100-03SVLSHTA240-03SVLSSHTA440-03SVLSSHTD100-03SVLS

ALAX-03SVALAX-03SVLS

AX-03SVAX-03SVLS

Internal accessories

Installationpole AL AX AL+AX SHT UVTN or UVTS

Model

SHTA240-03SVULSHTA440-03SVULSHTD100-03SVULSHTA240-03SVULSSHTA440-03SVULSSHTD100-03SVULS

ALAX-03SVUALAX-03SVLRS

AX-03SVUAX-03SVULS

AL-03SVUAL-03SVULS

-

NF100-CVFUNF125-SVU/HVUNF250-SVU/HVU

UVTNAD130-05SVUL UVTSAD130-05SVULUVTNA250-05SVUL UVTSA250-05SVULUVTNA480-05SVUL UVTSA480-05SVULUVTNAD130-05SVULS UVTSAD130-05SVULSUVTNA250-05SVULS UVTSA250-05SVULSUVTNA480-05SVULS UVTSA480-05SVULS

SHTA240-05SVULSHTA550-05SVULSHTD125-05SVULSHTA240-05SVULSSHTA550-05SVULSSHTD125-06SVULS

ALALX05SVUALAX-05SVULS

AX-05SVUAX-05SVULS

AL-05SVUAL-05SVULS

NF100-SRUNF100-HRU

UVTNA110-05SRULSUVTNA127-05SRULSUVTNA220-05SRULSUVTNA240-05SRULSUVTND024-05SRULSUVTND110-05SRULS

SHTA110-05SRULSSHTA127-05SRULSSHTA220-05SRULSSHTA240-05SRULSSHTD024-05SRULSSHTD110-05SRULS

ALAX-05SRUALAX-05SRULS

AX-05SRUAX-05SRULS

AL-05SRUAL-05SRULS

NF400-CW,NF400-SW,NF400-SEW,NF400-HEW,NF400-REW,NF400-UEW,NF630-CW,NF630-SW,NF630-SEW,NF630-HEW,NF630-REW,NF800-CEW,NF800-SEW,NF800-HEW,NF800-REW,NF800-UEW

-SHT-4SWSHT-4SWLS

ALAX-4SWLALAX-4SWLS

AX-4SWLAX-4SWLS

AX2-4SWLS

AL-4SWLAL-4SWLSAL2-4SWLS

Motor Circuit Breakers2

19

MOTOR CIRCUIT BREAKERS

Specifications

14 15

Usage Environment

Operating Characteristic Curve

Optional Unit

Product name Model SpecificationNumber Description Applied model

UT-MAX

UT-MAXLL(for subtle load)

UT-MAL

UT-MALLL(for subtle load)

UT-EP3

UT-2B4

UT-3B4

UT-2B5

UT-3B5

UT-CV3

UT-TU

UT-MT20

UT-MT32

UT-BT20

UT-BT32

UT-RT10

UT-RT20

UT-RT32

1a1b1a1b1a1b1a1b

45mmTwin type45mm

Triple type58mmTwin type58mm

Triple type MMP-T32

Contact of the unit operates in conjunction with ON/OFF operation of MMP-T32.

Contact of the unit operates in conjunction with the trip operation of MMP-T32.

A unit to supply power to two or three MMP-T32.

A set of the blocks for mechanically connecting two mounting base units.

A plate to install the combination starter with MMP-T32 and Magnetic Contactor combined. Rail mounting and screw mounting are available.

A unit to connect the large size electric wire to MMP-T32.

Power supply-side terminal cover to respond to UL60947-4-1A, Type E/FThis kit consists of terminal adapter, terminal cover and 3 screws.This unit has a feature that the red lamp is lit only when the device is tripped due to short-circuit.This unit is required for application to UL60947-4-1A, Type E/F.

Auxiliary contact unit (to be internally installed)

Alarm contact unit (to be internally installed)

3 phase feed-in terminal

Bus bar

Line side terminal adapter kit

Short-circuit indicator unit

Connection conductor unit

Mounting base unit

Jointing block unit

List of Options

①② ④

●Option combination Diagram

(1) Ambient temperature : -10°C to 40°C (Applied to the outside of

the control panel) Average daily atmospheric temperature: 35°C (Max.), Average yearly atmospheric temperature: 25°C (Max.)(2) Maximum temperature of the

inside of the control panel : 55°C (Yearly average temperature of the inside of the control panel should be 40°C or less.) Please note that the operating characteristic may vary with the ambient temperature.(3) Ambient temperature : 45% to 85%RH However, dew condensation and freezing should be avoided.(4) Height above sea level : 2000m or less(5) Vibration : 10 to 55Hz, 19.6m/s2 or less(6) Impact : 49m/s2 or less(7) Atmosphere : Inclusion of dust, smoke, corrosive gas, moisture, salt content and the like in the atmosphere should be

avoided as much as possible. Please note that continuing to use the device in a closed condition for a long period may cause contact failure. Never use the device under an atmosphere that contains flammable gas.(8) Storage temperature/

Relative humidity : -30°C to 65°C 45% to 85%RH However, dew condensation and freezing should be avoided. The storage temperature is ambient temperature during transportation or storage and should be within the

usage temperature when starting to use the device.* As for handling, temperature adjustment, and closely-attached installation, please read the Instruction Manual.

A unit to connect and link the MMP-T32 and Magnetic Contactor electrically and mechanically.

Three-phase cold start

The momentary release characteristic is 1040% to 1560% of the maximum set current.

Three-phase hot start

0.01

0.1

1

10

100

1000

10000

100000

100 1000 10000

Op

erat

ing

tim

e(s)

Multiple of rated current (%)

MOTOR CIRCUIT BREAKERS

Specifications

12 13

MMP-T32BCMMP-T32

Model Heater nominal

32A▲

●How to Order

Auxiliary contact unit UT-MAX ▲ 1a

Type name Contact arrangement

●How to Order the Options

UT-MAX ▲ 1bAlarm contact unit UT-MAL ▲ 1a UT-MAL ▲ 1b

Short-circuit indicator unit UT-TU

Frame A

Number of poles

Rated current In [A]

Rated insulation voltage Ui [V]Rated impulse withstand voltage Uimp [kV]

3

MMP-T3232

0.1 to 32

6906

MMP-T32BC*1

Handle shape Tumbler handle

Trip class (JIS C8201-4-1, IEC60947-4-1)

Trip display

JIS C8201-2-1 Ann.1IEC60947-2

Mechanical [times]

Cat.A

AC-3

Type name

200 to 69050/60

JIS C8201-2-1Ann.1

Weight [g]

Test trip function

Electrical [times]

JIS C8201-4-1IEC60947-4-1

IEC60947-2

0.1 - 0.16

0.25 - 0.4 0.4 - 0.63 0.63 - 1 1 - 1.6 1.6 - 2.5 2.5 - 4 4 - 6.3 5.5 - 8 7 - 10 9 - 13 12 - 18 18 - 25 24 - 32

0.16 - 0.250.16

0.40.63

11.62.54

6.381013182532

0.25

200/240V 400/415V 440/460V 500V 600/690V

Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

100

100100100100100100100100100100100100100

100100

100100100100100100100100100100

505050

100

383838

100

100100100100100100100

100100

100100100100100100100

100

505050353535

383838272727

323232888

4242101010

42

44

666

4

886

33

555

3

665

100

100100100100

100

1013 × Maximum Ie

100,000100,000

YesYesYes

UT-TU

Auxiliary contact unitAlarm contact unitShort-circuit indicator unit

Standard JIS C8201-2-1 Ann.1, JIS 8201-4-1, EN60947-2, EN60947-4-1, IEC60947-2, IEC60947-4-1, GB14048.2

*1: MMP-T32BC type is based on the specification of wiring streamlining terminal.*2: UL-compliant rated working current is described on a different page.

330

Key points

45mm

MMP-T32

Test trip function

Applicable Standards■ International Standards

IEC60947-2, 60947-4-1 UL60947-4-1A, CSA C22.2 No.60947-4-1 TUV approval CE CCC■ Domestic Standards in Japan

JIS C8201-2-1 Ann.1, 8201-4-1 Electric Applicable Safety Law (Electric articles other than specified)

Specification List

A round solderless terminal is applicable.

At time of your order, please specify your desired products as shown below.(A space should be inserted in the ▲-marked position. )

Current setting range

Rated operational voltage Ue [V.]Rated frequency [Hz]

Rated short-circuit breaking capacity[kA]

Rated current Ie [A]*2

Heater designation

Selectivity categoryUtilization category

Instantaneous release current

Phase loss sensitive

Durability

UT-MAX (1a or 1b) AC-12: 125V/5A, 250V/3AUT-MAL (1a or 1b) DC-12: 125V/0.4A, 250V/0.2A

Wiring-supporting BC terminal (Option)

Adjustment dial settable to full load current Optional short-circuit indicator

unit can be added speeding up fault diagnosis.

Integrated finger protection provides convenient safety

Breaker type operating handle with off-lock hole.

The compact breaker design also allows Auxiliary contact unit (AX) and alarm contact unit (AL).

20

MOTOR CIRCUIT BREAKERS

Specifications

14 15

Usage Environment

Operating Characteristic Curve

Optional Unit

Product name Model SpecificationNumber Description Applied model

UT-MAX

UT-MAXLL(for subtle load)

UT-MAL

UT-MALLL(for subtle load)

UT-EP3

UT-2B4

UT-3B4

UT-2B5

UT-3B5

UT-CV3

UT-TU

UT-MT20

UT-MT32

UT-BT20

UT-BT32

UT-RT10

UT-RT20

UT-RT32

1a1b1a1b1a1b1a1b

45mmTwin type45mm

Triple type58mmTwin type58mm

Triple type MMP-T32

Contact of the unit operates in conjunction with ON/OFF operation of MMP-T32.

Contact of the unit operates in conjunction with the trip operation of MMP-T32.

A unit to supply power to two or three MMP-T32.

A set of the blocks for mechanically connecting two mounting base units.

A plate to install the combination starter with MMP-T32 and Magnetic Contactor combined. Rail mounting and screw mounting are available.

A unit to connect the large size electric wire to MMP-T32.

Power supply-side terminal cover to respond to UL60947-4-1A, Type E/FThis kit consists of terminal adapter, terminal cover and 3 screws.This unit has a feature that the red lamp is lit only when the device is tripped due to short-circuit.This unit is required for application to UL60947-4-1A, Type E/F.

Auxiliary contact unit (to be internally installed)

Alarm contact unit (to be internally installed)

3 phase feed-in terminal

Bus bar

Line side terminal adapter kit

Short-circuit indicator unit

Connection conductor unit

Mounting base unit

Jointing block unit

List of Options

①② ④

●Option combination Diagram

(1) Ambient temperature : -10°C to 40°C (Applied to the outside of

the control panel) Average daily atmospheric temperature: 35°C (Max.), Average yearly atmospheric temperature: 25°C (Max.)(2) Maximum temperature of the

inside of the control panel : 55°C (Yearly average temperature of the inside of the control panel should be 40°C or less.) Please note that the operating characteristic may vary with the ambient temperature.(3) Ambient temperature : 45% to 85%RH However, dew condensation and freezing should be avoided.(4) Height above sea level : 2000m or less(5) Vibration : 10 to 55Hz, 19.6m/s2 or less(6) Impact : 49m/s2 or less(7) Atmosphere : Inclusion of dust, smoke, corrosive gas, moisture, salt content and the like in the atmosphere should be

avoided as much as possible. Please note that continuing to use the device in a closed condition for a long period may cause contact failure. Never use the device under an atmosphere that contains flammable gas.(8) Storage temperature/

Relative humidity : -30°C to 65°C 45% to 85%RH However, dew condensation and freezing should be avoided. The storage temperature is ambient temperature during transportation or storage and should be within the

usage temperature when starting to use the device.* As for handling, temperature adjustment, and closely-attached installation, please read the Instruction Manual.

A unit to connect and link the MMP-T32 and Magnetic Contactor electrically and mechanically.

Three-phase cold start

The momentary release characteristic is 1040% to 1560% of the maximum set current.

Three-phase hot start

0.01

0.1

1

10

100

1000

10000

100000

100 1000 10000

Op

erat

ing

tim

e(s)

Multiple of rated current (%)

MOTOR CIRCUIT BREAKERS

Specifications

12 13

MMP-T32BCMMP-T32

Model Heater nominal

32A▲

●How to Order

Auxiliary contact unit UT-MAX ▲ 1a

Type name Contact arrangement

●How to Order the Options

UT-MAX ▲ 1bAlarm contact unit UT-MAL ▲ 1a UT-MAL ▲ 1b

Short-circuit indicator unit UT-TU

Frame A

Number of poles

Rated current In [A]

Rated insulation voltage Ui [V]Rated impulse withstand voltage Uimp [kV]

3

MMP-T3232

0.1 to 32

6906

MMP-T32BC*1

Handle shape Tumbler handle

Trip class (JIS C8201-4-1, IEC60947-4-1)

Trip display

JIS C8201-2-1 Ann.1IEC60947-2

Mechanical [times]

Cat.A

AC-3

Type name

200 to 69050/60

JIS C8201-2-1Ann.1

Weight [g]

Test trip function

Electrical [times]

JIS C8201-4-1IEC60947-4-1

IEC60947-2

0.1 - 0.16

0.25 - 0.4 0.4 - 0.63 0.63 - 1 1 - 1.6 1.6 - 2.5 2.5 - 4 4 - 6.3 5.5 - 8 7 - 10 9 - 13 12 - 18 18 - 25 24 - 32

0.16 - 0.250.16

0.40.63

11.62.54

6.381013182532

0.25

200/240V 400/415V 440/460V 500V 600/690V

Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

100

100100100100100100100100100100100100100

100100

100100100100100100100100100100

505050

100

383838

100

100100100100100100100

100100

100100100100100100100

100

505050353535

383838272727

323232888

4242101010

42

44

666

4

886

33

555

3

665

100

100100100100

100

1013 × Maximum Ie

100,000100,000

YesYesYes

UT-TU

Auxiliary contact unitAlarm contact unitShort-circuit indicator unit

Standard JIS C8201-2-1 Ann.1, JIS 8201-4-1, EN60947-2, EN60947-4-1, IEC60947-2, IEC60947-4-1, GB14048.2

*1: MMP-T32BC type is based on the specification of wiring streamlining terminal.*2: UL-compliant rated working current is described on a different page.

330

Key points

45mm

MMP-T32

Test trip function

Applicable Standards■ International Standards

IEC60947-2, 60947-4-1 UL60947-4-1A, CSA C22.2 No.60947-4-1 TUV approval CE CCC■ Domestic Standards in Japan

JIS C8201-2-1 Ann.1, 8201-4-1 Electric Applicable Safety Law (Electric articles other than specified)

Specification List

A round solderless terminal is applicable.

At time of your order, please specify your desired products as shown below.(A space should be inserted in the ▲-marked position. )

Current setting range

Rated operational voltage Ue [V.]Rated frequency [Hz]

Rated short-circuit breaking capacity[kA]

Rated current Ie [A]*2

Heater designation

Selectivity categoryUtilization category

Instantaneous release current

Phase loss sensitive

Durability

UT-MAX (1a or 1b) AC-12: 125V/5A, 250V/3AUT-MAL (1a or 1b) DC-12: 125V/0.4A, 250V/0.2A

Wiring-supporting BC terminal (Option)

Adjustment dial settable to full load current Optional short-circuit indicator

unit can be added speeding up fault diagnosis.

Integrated finger protection provides convenient safety

Breaker type operating handle with off-lock hole.

The compact breaker design also allows Auxiliary contact unit (AX) and alarm contact unit (AL).

21

3 Magnetic Contactor

Frame T10 T12 T20 T21 T25 T32 T35 T50 T65 T80 T100Applicable standard JIS C8201-4-1,IEC60947-4-1,EN60947-4-1,GB14048.4 JIS C8201-4-1,IEC60947-4-1,

EN60947-4-1,GB14048.4

Mod

el n

ame

Magnetic Contactors(Without Thermal Overload Relays, Open type)

Non-Reversing S-T10 S-T12 S-T20 S-T21 S-T25 S-T32 S-T35 S-T50 S-T65 S-T80 S-T100Reversing S-2×T10 S-2×T12 S-2×T20 S-2×T21 S-2×T25 S-2×T32 S-2×T35 S-2×T50 S-2×T65 S-2×T80 S-2×T100

Magnetic Starters(With standard 2-element, With Thermal Overload Relays)

EnclosedNon-Reversing MS-T10 MS-T12 ー MS-T21 MS-2×T25 ー MS-T35 MS-T50 MS-T65 MS-T80 MS-T100Reversing ー MS-2×T21 MS-T25 ー MS-2XT35 MS-2XT50 MS-2XT65 MS-2XT80 MS-2XT100

Open typeNon-Reversing MSO-T10 MSO-T12 MSO-T20 MSO-T21 MSO-T25 ー MSO-T35 MSO-T50 MSO-T65 MSO-T80 MSO-T100Reversing MSO-2×T10 MSO-2×T12 MSO-2×T20 MSO-2×T21 MSO-2×T25 ー MSO-2×T35 MSO-2×T50 MSO-2×T65 MSO-2×T80 MSO-2×T100

Combined Thermal Overload Relays TH-T18 TH-T25 TH-T25 ー TH-T25/T50 TH-T25/T50 TH-T65 TH-T65/T100 TH-T65/T100Magnetic Starters(With 3-element type Thermal Overload Relays)

Open typeNon-Reversing MSO-T10KP MSO-T12KP MSO-T20KP MSO-T21KP MSO-T25KP ー MSO-T35KP MSO-T50KP MSO-T65KP MSO-T80KP MSO-T100KPReversing MSO-2×T10KP MSO-2×T12KP MSO-2×T20KP MSO-2×T21KP MSO-2×T25KP ー MSO-2×T35KP MSO-2×T50KP MSO-2×T65KP MSO-2×T80KP MSO-2×T100KP

Combined Thermal Overload Relays TH-T18KP TH-T25KP TH-T25KP ー TH-T25/T50KP TH-T25/T50KP TH-T65KP TH-T65/T100KP TH-T65/T100KP

Mai

n co

ntac

t rat

ing

Rated insulation voltage [V] 690 690Rated impulse withstand voltage [kV] 6 6Rated frequency [Hz] 50/60 50/60Pollution degree 3 3

Rated operational current / powerCategory AC-3 (Note 1)(Three-phase squirrel-cage motor load standard responsibility) (Note 2) [kW/A]

220 to 240VAC 2.5/11 [2.2/11] 3.5/13 [2.7/13] 4.5/18 [3.7/18] 5.5/25 [4/20] 7.5/30(26) [5.5/26] 7.5/32 [7.5/32] 11/40 [7.5/35] 15/55 [11/50] 18.5/65 [15/65] 22/85 [19/80] 30/105 [22/100]380 to 440VAC 4/9 [2.7/7] 5.5/12 [4/9] 7.5/18 [7.5/18] 11/23 [7.5/20] 15/30(26) [11/25] 15/32 [15/32] 18.5/40 [15/32] 22/48 [22/48] 30/65 [30/65] 45/85 [37/80] 55/105 [45/93]

500VAC 4/7 [2.7/6] 5.5/9 [5.5/9] 7.5/17 [7.5/17] 11/17 [7.5/17] 15/24 [11/20] 15/24 [11/20] 18.5/32 [15/26] 25/38 [22/38] 37/60 [30/45] 45/75 [45/75] 55/85 [45/75]690VAC 4/5 5.5/7 7.5/9 7.5/9 11/12 11/12 15/17 22/26 30/38 45/52 55/65

Rated operational current / powerCategory AC-4(Three-phase squirrel-cage motor load inching responsibility) [kW/A]

220 to 240VAC 1.5/8 2.2/11 3.7/18 4.5/20 5.5/26 5.5/26 7.5/35 11/50 15/65 19/80380 to 440VAC 2.2/6 4/9 5.5/13 7.5/17 11/24 11/24 15/32 22/47 30/62 37/75

500VAC 2.7/6 5.5/9 5.5/10 7.5/12 7.5/13 11/17 15/24 22/38 30/45 37/55

Rated operational current / powerCategory AC-1 (Resistance, heater load)

100 to 240VAC 20 32 32 60 80 100 120 150380 to 440VAC 11 13 32 32 60 80 100 120 150

Conventional free air thermal current Ith [A] 20 32 32 60 80 100 120 150Minimum applicable load level 48V 200mA 48V 200mA

Aux

iliar

y co

ntac

t rat

ing

Con

tact

ar

rang

emen

t

Standard accessoryNon-Reversing 1a 1a1b 2a2b 2a2b ー 2a2b 2a2b 2a2b 2a2b 2a2bReversing (Note 4, Note 6) 1a×2+2b 1a1b×2+2b 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2

Special accessoryNon-Reversing 1b 2a ー ー ー ー ー ー ーReversing (Note 4, Note 6) 1b×2+2b 2a×2+2b ー ー ー ー ー ー ー

Max. number of additional options(Note 5)

Front clip-on

Non-Reversing 1 1 ーReversing 2 2 ー 2 ー

Side clip-on

Non-Reversing 2 2Reversing 2 2 ー 2

Rated operational current(Category AC-15 : Alternating current coil load)

120VAC 6 6240VAC 3 3

Rated operational current (Category DC-13 : Direct current coil load)

24VDC 3 3110VDC 0.6 0.6

Conventional free air thermal current Ith [A] 10 10Minimum applicable load level 20V 3mA 20V 3mA

Per

form

ance

Mechanical durability [ten thousand times] 1000 1000 500

Electrical durability[ten thousand times]

Category AC-3 200(Note 9) 200 100Category AC-4 3(Note 9) 3 (Note 9)Category AC-1 50 50

Switching frequency [time/hour]Category AC-3 1800 1800 1200Category AC-4 300 300Category AC-1 1200 1200 600

Chara

cteris

tic

Coil consumption (Note 7)Inrush [VA] 45 75 75 55 110 110 115 115 210Sealed [VA] 7 7 7 4.5 10 10 20 20 23

Power consumption (Note 7) [W] 2.2 2.4 2.4 1.8 3.8 3.8 2.2 2.2 2.8

Out

side

di

men

sion

s

Magnetic Contactors (without Thermal Overload Relays)(Width x Height x Depth) [mm]

Non-Reversing 36×75×78 43×75×78 63×81×81 63×81×81 43×81×81 75×89×91 88×106×106 88×106×106 100×124×127Reversing 82×85×78 97×85×78 136×81×81 136×81×81 96×81×111 160×114×97 216×115×112 216×115×112 270×140×137

Open type Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 45×115×79 63×128×82 63×128×82 ー 75×157.5×91 90×158×106 90×174.5×106 100×196×127Reversing 90×125×79 97×125×79 136×138×82 136×138×82 ー 160×179×97 216×169×112 216×185.5×112 270×213×137

Enclosed Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 76×165×97.5 ー 104×176×110 ー 135×231×126 160×282×145 190×317×163Reversing ー ー 220×192×115 ー 300×247×130 320×282×140 410×347×154

IEC 35mm rail mounting Possible (excluding Enclosed Magnetic Starters) Possible (excluding Enclosed Magnetic Starters) ー

Specification List Table

●Magnetic Starters/Magnetic Contactors (AC operated)

Note 1: The figure in the square brackets indicates the rated current shown on the rating plate of the product at which the category AC-3 opening/closing durability is 2,000,000 times (1,000,000 times for the T20 380V). Refer to the electric durability curve for the life performance.

Note 2: The content within ( ) of rated capacity and rated operational current is applied to the Magnetic Contactor.Note 3: The T10 to T50 types can be manufactured with a coil surge absorber-mounted type (□-□SA type). The UT-SA21 type can be mounted.Note 4: +2b of T10 and T12 auxiliary contact arrangements in Reversing type represents b contact built in the UT-ML11 interlock unit.Note 5: The main unit and auxiliary contact block must be prepared separately and additionally mounted by the user.Note 6: For auxiliary contact arrangement in Reversing type, X2 is displayed as combined auxiliary contact arrangement of two Magnetic Contactors. Please specify the contact arrangement for which

two main units are combined must be designated. <Designation example> In case of 1b x 2 + 2b: 2BNote 7: Operational coil input and coil consumption are average values in case of applying 220V60Hz to AC200V coil.Note 8: Refer to pages 36 for the mountable options.Note 9: 1,000,000 times for T20 AC-3 Class 380V or higher, and 15,000 times for AC-4 Class. 15,000 times for T35 to T100 AC-4 Class 380V or higher.

S o l v e T o g e t h e rSelection and Application

18

Frame T10 T12 T20 T21 T25 T32 T35 T50 T65 T80 T100Applicable standard JIS C8201-4-1,IEC60947-4-1,EN60947-4-1,GB14048.4 JIS C8201-4-1,IEC60947-4-1,

EN60947-4-1,GB14048.4

Mod

el n

ame

Magnetic Contactors(Without Thermal Overload Relays, Open type)

Non-Reversing S-T10 S-T12 S-T20 S-T21 S-T25 S-T32 S-T35 S-T50 S-T65 S-T80 S-T100Reversing S-2×T10 S-2×T12 S-2×T20 S-2×T21 S-2×T25 S-2×T32 S-2×T35 S-2×T50 S-2×T65 S-2×T80 S-2×T100

Magnetic Starters(With standard 2-element, With Thermal Overload Relays)

EnclosedNon-Reversing MS-T10 MS-T12 ー MS-T21 MS-2×T25 ー MS-T35 MS-T50 MS-T65 MS-T80 MS-T100Reversing ー MS-2×T21 MS-T25 ー MS-2XT35 MS-2XT50 MS-2XT65 MS-2XT80 MS-2XT100

Open typeNon-Reversing MSO-T10 MSO-T12 MSO-T20 MSO-T21 MSO-T25 ー MSO-T35 MSO-T50 MSO-T65 MSO-T80 MSO-T100Reversing MSO-2×T10 MSO-2×T12 MSO-2×T20 MSO-2×T21 MSO-2×T25 ー MSO-2×T35 MSO-2×T50 MSO-2×T65 MSO-2×T80 MSO-2×T100

Combined Thermal Overload Relays TH-T18 TH-T25 TH-T25 ー TH-T25/T50 TH-T25/T50 TH-T65 TH-T65/T100 TH-T65/T100Magnetic Starters(With 3-element type Thermal Overload Relays)

Open typeNon-Reversing MSO-T10KP MSO-T12KP MSO-T20KP MSO-T21KP MSO-T25KP ー MSO-T35KP MSO-T50KP MSO-T65KP MSO-T80KP MSO-T100KPReversing MSO-2×T10KP MSO-2×T12KP MSO-2×T20KP MSO-2×T21KP MSO-2×T25KP ー MSO-2×T35KP MSO-2×T50KP MSO-2×T65KP MSO-2×T80KP MSO-2×T100KP

Combined Thermal Overload Relays TH-T18KP TH-T25KP TH-T25KP ー TH-T25/T50KP TH-T25/T50KP TH-T65KP TH-T65/T100KP TH-T65/T100KP

Mai

n co

ntac

t rat

ing

Rated insulation voltage [V] 690 690Rated impulse withstand voltage [kV] 6 6Rated frequency [Hz] 50/60 50/60Pollution degree 3 3

Rated operational current / powerCategory AC-3 (Note 1)(Three-phase squirrel-cage motor load standard responsibility) (Note 2) [kW/A]

220 to 240VAC 2.5/11 [2.2/11] 3.5/13 [2.7/13] 4.5/18 [3.7/18] 5.5/25 [4/20] 7.5/30(26) [5.5/26] 7.5/32 [7.5/32] 11/40 [7.5/35] 15/55 [11/50] 18.5/65 [15/65] 22/85 [19/80] 30/105 [22/100]380 to 440VAC 4/9 [2.7/7] 5.5/12 [4/9] 7.5/18 [7.5/18] 11/23 [7.5/20] 15/30(26) [11/25] 15/32 [15/32] 18.5/40 [15/32] 22/48 [22/48] 30/65 [30/65] 45/85 [37/80] 55/105 [45/93]

500VAC 4/7 [2.7/6] 5.5/9 [5.5/9] 7.5/17 [7.5/17] 11/17 [7.5/17] 15/24 [11/20] 15/24 [11/20] 18.5/32 [15/26] 25/38 [22/38] 37/60 [30/45] 45/75 [45/75] 55/85 [45/75]690VAC 4/5 5.5/7 7.5/9 7.5/9 11/12 11/12 15/17 22/26 30/38 45/52 55/65

Rated operational current / powerCategory AC-4(Three-phase squirrel-cage motor load inching responsibility) [kW/A]

220 to 240VAC 1.5/8 2.2/11 3.7/18 4.5/20 5.5/26 5.5/26 7.5/35 11/50 15/65 19/80380 to 440VAC 2.2/6 4/9 5.5/13 7.5/17 11/24 11/24 15/32 22/47 30/62 37/75

500VAC 2.7/6 5.5/9 5.5/10 7.5/12 7.5/13 11/17 15/24 22/38 30/45 37/55

Rated operational current / powerCategory AC-1 (Resistance, heater load)

100 to 240VAC 20 32 32 60 80 100 120 150380 to 440VAC 11 13 32 32 60 80 100 120 150

Conventional free air thermal current Ith [A] 20 32 32 60 80 100 120 150Minimum applicable load level 48V 200mA 48V 200mA

Aux

iliar

y co

ntac

t rat

ing

Con

tact

ar

rang

emen

t

Standard accessoryNon-Reversing 1a 1a1b 2a2b 2a2b ー 2a2b 2a2b 2a2b 2a2b 2a2bReversing (Note 4, Note 6) 1a×2+2b 1a1b×2+2b 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2

Special accessoryNon-Reversing 1b 2a ー ー ー ー ー ー ーReversing (Note 4, Note 6) 1b×2+2b 2a×2+2b ー ー ー ー ー ー ー

Max. number of additional options(Note 5)

Front clip-on

Non-Reversing 1 1 ーReversing 2 2 ー 2 ー

Side clip-on

Non-Reversing 2 2Reversing 2 2 ー 2

Rated operational current(Category AC-15 : Alternating current coil load)

120VAC 6 6240VAC 3 3

Rated operational current (Category DC-13 : Direct current coil load)

24VDC 3 3110VDC 0.6 0.6

Conventional free air thermal current Ith [A] 10 10Minimum applicable load level 20V 3mA 20V 3mA

Per

form

ance

Mechanical durability [ten thousand times] 1000 1000 500

Electrical durability[ten thousand times]

Category AC-3 200(Note 9) 200 100Category AC-4 3(Note 9) 3 (Note 9)Category AC-1 50 50

Switching frequency [time/hour]Category AC-3 1800 1800 1200Category AC-4 300 300Category AC-1 1200 1200 600

Chara

cteris

tic

Coil consumption (Note 7)Inrush [VA] 45 75 75 55 110 110 115 115 210Sealed [VA] 7 7 7 4.5 10 10 20 20 23

Power consumption (Note 7) [W] 2.2 2.4 2.4 1.8 3.8 3.8 2.2 2.2 2.8

Out

side

di

men

sion

s

Magnetic Contactors (without Thermal Overload Relays)(Width x Height x Depth) [mm]

Non-Reversing 36×75×78 43×75×78 63×81×81 63×81×81 43×81×81 75×89×91 88×106×106 88×106×106 100×124×127Reversing 82×85×78 97×85×78 136×81×81 136×81×81 96×81×111 160×114×97 216×115×112 216×115×112 270×140×137

Open type Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 45×115×79 63×128×82 63×128×82 ー 75×157.5×91 90×158×106 90×174.5×106 100×196×127Reversing 90×125×79 97×125×79 136×138×82 136×138×82 ー 160×179×97 216×169×112 216×185.5×112 270×213×137

Enclosed Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 76×165×97.5 ー 104×176×110 ー 135×231×126 160×282×145 190×317×163Reversing ー ー 220×192×115 ー 300×247×130 320×282×140 410×347×154

IEC 35mm rail mounting Possible (excluding Enclosed Magnetic Starters) Possible (excluding Enclosed Magnetic Starters) ー

Specification List Table

S o l v e T o g e t h e r

MS-

T Se

ries

Intro

duct

ion

Sele

ctio

n an

d Ap

plic

atio

nAp

plicati

on to

Therm

al Over

load R

elays

Pro

duct

Intr

oduc

tion

Ove

rsea

s S

tand

ard

Type

Cod

esO

rder

Pro

cedu

reO

utlin

e D

raw

ing

War

rant

y an

d S

afet

y

19

22

Frame T10 T12 T20 T21 T25 T32 T35 T50 T65 T80 T100Applicable standard JIS C8201-4-1,IEC60947-4-1,EN60947-4-1,GB14048.4 JIS C8201-4-1,IEC60947-4-1,

EN60947-4-1,GB14048.4

Mod

el n

ame

Magnetic Contactors(Without Thermal Overload Relays, Open type)

Non-Reversing S-T10 S-T12 S-T20 S-T21 S-T25 S-T32 S-T35 S-T50 S-T65 S-T80 S-T100Reversing S-2×T10 S-2×T12 S-2×T20 S-2×T21 S-2×T25 S-2×T32 S-2×T35 S-2×T50 S-2×T65 S-2×T80 S-2×T100

Magnetic Starters(With standard 2-element, With Thermal Overload Relays)

EnclosedNon-Reversing MS-T10 MS-T12 ー MS-T21 MS-2×T25 ー MS-T35 MS-T50 MS-T65 MS-T80 MS-T100Reversing ー MS-2×T21 MS-T25 ー MS-2XT35 MS-2XT50 MS-2XT65 MS-2XT80 MS-2XT100

Open typeNon-Reversing MSO-T10 MSO-T12 MSO-T20 MSO-T21 MSO-T25 ー MSO-T35 MSO-T50 MSO-T65 MSO-T80 MSO-T100Reversing MSO-2×T10 MSO-2×T12 MSO-2×T20 MSO-2×T21 MSO-2×T25 ー MSO-2×T35 MSO-2×T50 MSO-2×T65 MSO-2×T80 MSO-2×T100

Combined Thermal Overload Relays TH-T18 TH-T25 TH-T25 ー TH-T25/T50 TH-T25/T50 TH-T65 TH-T65/T100 TH-T65/T100Magnetic Starters(With 3-element type Thermal Overload Relays)

Open typeNon-Reversing MSO-T10KP MSO-T12KP MSO-T20KP MSO-T21KP MSO-T25KP ー MSO-T35KP MSO-T50KP MSO-T65KP MSO-T80KP MSO-T100KPReversing MSO-2×T10KP MSO-2×T12KP MSO-2×T20KP MSO-2×T21KP MSO-2×T25KP ー MSO-2×T35KP MSO-2×T50KP MSO-2×T65KP MSO-2×T80KP MSO-2×T100KP

Combined Thermal Overload Relays TH-T18KP TH-T25KP TH-T25KP ー TH-T25/T50KP TH-T25/T50KP TH-T65KP TH-T65/T100KP TH-T65/T100KP

Mai

n co

ntac

t rat

ing

Rated insulation voltage [V] 690 690Rated impulse withstand voltage [kV] 6 6Rated frequency [Hz] 50/60 50/60Pollution degree 3 3

Rated operational current / powerCategory AC-3 (Note 1)(Three-phase squirrel-cage motor load standard responsibility) (Note 2) [kW/A]

220 to 240VAC 2.5/11 [2.2/11] 3.5/13 [2.7/13] 4.5/18 [3.7/18] 5.5/25 [4/20] 7.5/30(26) [5.5/26] 7.5/32 [7.5/32] 11/40 [7.5/35] 15/55 [11/50] 18.5/65 [15/65] 22/85 [19/80] 30/105 [22/100]380 to 440VAC 4/9 [2.7/7] 5.5/12 [4/9] 7.5/18 [7.5/18] 11/23 [7.5/20] 15/30(26) [11/25] 15/32 [15/32] 18.5/40 [15/32] 22/48 [22/48] 30/65 [30/65] 45/85 [37/80] 55/105 [45/93]

500VAC 4/7 [2.7/6] 5.5/9 [5.5/9] 7.5/17 [7.5/17] 11/17 [7.5/17] 15/24 [11/20] 15/24 [11/20] 18.5/32 [15/26] 25/38 [22/38] 37/60 [30/45] 45/75 [45/75] 55/85 [45/75]690VAC 4/5 5.5/7 7.5/9 7.5/9 11/12 11/12 15/17 22/26 30/38 45/52 55/65

Rated operational current / powerCategory AC-4(Three-phase squirrel-cage motor load inching responsibility) [kW/A]

220 to 240VAC 1.5/8 2.2/11 3.7/18 4.5/20 5.5/26 5.5/26 7.5/35 11/50 15/65 19/80380 to 440VAC 2.2/6 4/9 5.5/13 7.5/17 11/24 11/24 15/32 22/47 30/62 37/75

500VAC 2.7/6 5.5/9 5.5/10 7.5/12 7.5/13 11/17 15/24 22/38 30/45 37/55

Rated operational current / powerCategory AC-1 (Resistance, heater load)

100 to 240VAC 20 32 32 60 80 100 120 150380 to 440VAC 11 13 32 32 60 80 100 120 150

Conventional free air thermal current Ith [A] 20 32 32 60 80 100 120 150Minimum applicable load level 48V 200mA 48V 200mA

Aux

iliar

y co

ntac

t rat

ing

Con

tact

ar

rang

emen

t

Standard accessoryNon-Reversing 1a 1a1b 2a2b 2a2b ー 2a2b 2a2b 2a2b 2a2b 2a2bReversing (Note 4, Note 6) 1a×2+2b 1a1b×2+2b 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2

Special accessoryNon-Reversing 1b 2a ー ー ー ー ー ー ーReversing (Note 4, Note 6) 1b×2+2b 2a×2+2b ー ー ー ー ー ー ー

Max. number of additional options(Note 5)

Front clip-on

Non-Reversing 1 1 ーReversing 2 2 ー 2 ー

Side clip-on

Non-Reversing 2 2Reversing 2 2 ー 2

Rated operational current(Category AC-15 : Alternating current coil load)

120VAC 6 6240VAC 3 3

Rated operational current (Category DC-13 : Direct current coil load)

24VDC 3 3110VDC 0.6 0.6

Conventional free air thermal current Ith [A] 10 10Minimum applicable load level 20V 3mA 20V 3mA

Per

form

ance

Mechanical durability [ten thousand times] 1000 1000 500

Electrical durability[ten thousand times]

Category AC-3 200(Note 9) 200 100Category AC-4 3(Note 9) 3 (Note 9)Category AC-1 50 50

Switching frequency [time/hour]Category AC-3 1800 1800 1200Category AC-4 300 300Category AC-1 1200 1200 600

Chara

cteris

tic

Coil consumption (Note 7)Inrush [VA] 45 75 75 55 110 110 115 115 210Sealed [VA] 7 7 7 4.5 10 10 20 20 23

Power consumption (Note 7) [W] 2.2 2.4 2.4 1.8 3.8 3.8 2.2 2.2 2.8

Out

side

di

men

sion

s

Magnetic Contactors (without Thermal Overload Relays)(Width x Height x Depth) [mm]

Non-Reversing 36×75×78 43×75×78 63×81×81 63×81×81 43×81×81 75×89×91 88×106×106 88×106×106 100×124×127Reversing 82×85×78 97×85×78 136×81×81 136×81×81 96×81×111 160×114×97 216×115×112 216×115×112 270×140×137

Open type Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 45×115×79 63×128×82 63×128×82 ー 75×157.5×91 90×158×106 90×174.5×106 100×196×127Reversing 90×125×79 97×125×79 136×138×82 136×138×82 ー 160×179×97 216×169×112 216×185.5×112 270×213×137

Enclosed Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 76×165×97.5 ー 104×176×110 ー 135×231×126 160×282×145 190×317×163Reversing ー ー 220×192×115 ー 300×247×130 320×282×140 410×347×154

IEC 35mm rail mounting Possible (excluding Enclosed Magnetic Starters) Possible (excluding Enclosed Magnetic Starters) ー

Specification List Table

●Magnetic Starters/Magnetic Contactors (AC operated)

Note 1: The figure in the square brackets indicates the rated current shown on the rating plate of the product at which the category AC-3 opening/closing durability is 2,000,000 times (1,000,000 times for the T20 380V). Refer to the electric durability curve for the life performance.

Note 2: The content within ( ) of rated capacity and rated operational current is applied to the Magnetic Contactor.Note 3: The T10 to T50 types can be manufactured with a coil surge absorber-mounted type (□-□SA type). The UT-SA21 type can be mounted.Note 4: +2b of T10 and T12 auxiliary contact arrangements in Reversing type represents b contact built in the UT-ML11 interlock unit.Note 5: The main unit and auxiliary contact block must be prepared separately and additionally mounted by the user.Note 6: For auxiliary contact arrangement in Reversing type, X2 is displayed as combined auxiliary contact arrangement of two Magnetic Contactors. Please specify the contact arrangement for which

two main units are combined must be designated. <Designation example> In case of 1b x 2 + 2b: 2BNote 7: Operational coil input and coil consumption are average values in case of applying 220V60Hz to AC200V coil.Note 8: Refer to pages 36 for the mountable options.Note 9: 1,000,000 times for T20 AC-3 Class 380V or higher, and 15,000 times for AC-4 Class. 15,000 times for T35 to T100 AC-4 Class 380V or higher.

S o l v e T o g e t h e rSelection and Application

18

Frame T10 T12 T20 T21 T25 T32 T35 T50 T65 T80 T100Applicable standard JIS C8201-4-1,IEC60947-4-1,EN60947-4-1,GB14048.4 JIS C8201-4-1,IEC60947-4-1,

EN60947-4-1,GB14048.4

Mod

el n

ame

Magnetic Contactors(Without Thermal Overload Relays, Open type)

Non-Reversing S-T10 S-T12 S-T20 S-T21 S-T25 S-T32 S-T35 S-T50 S-T65 S-T80 S-T100Reversing S-2×T10 S-2×T12 S-2×T20 S-2×T21 S-2×T25 S-2×T32 S-2×T35 S-2×T50 S-2×T65 S-2×T80 S-2×T100

Magnetic Starters(With standard 2-element, With Thermal Overload Relays)

EnclosedNon-Reversing MS-T10 MS-T12 ー MS-T21 MS-2×T25 ー MS-T35 MS-T50 MS-T65 MS-T80 MS-T100Reversing ー MS-2×T21 MS-T25 ー MS-2XT35 MS-2XT50 MS-2XT65 MS-2XT80 MS-2XT100

Open typeNon-Reversing MSO-T10 MSO-T12 MSO-T20 MSO-T21 MSO-T25 ー MSO-T35 MSO-T50 MSO-T65 MSO-T80 MSO-T100Reversing MSO-2×T10 MSO-2×T12 MSO-2×T20 MSO-2×T21 MSO-2×T25 ー MSO-2×T35 MSO-2×T50 MSO-2×T65 MSO-2×T80 MSO-2×T100

Combined Thermal Overload Relays TH-T18 TH-T25 TH-T25 ー TH-T25/T50 TH-T25/T50 TH-T65 TH-T65/T100 TH-T65/T100Magnetic Starters(With 3-element type Thermal Overload Relays)

Open typeNon-Reversing MSO-T10KP MSO-T12KP MSO-T20KP MSO-T21KP MSO-T25KP ー MSO-T35KP MSO-T50KP MSO-T65KP MSO-T80KP MSO-T100KPReversing MSO-2×T10KP MSO-2×T12KP MSO-2×T20KP MSO-2×T21KP MSO-2×T25KP ー MSO-2×T35KP MSO-2×T50KP MSO-2×T65KP MSO-2×T80KP MSO-2×T100KP

Combined Thermal Overload Relays TH-T18KP TH-T25KP TH-T25KP ー TH-T25/T50KP TH-T25/T50KP TH-T65KP TH-T65/T100KP TH-T65/T100KP

Mai

n co

ntac

t rat

ing

Rated insulation voltage [V] 690 690Rated impulse withstand voltage [kV] 6 6Rated frequency [Hz] 50/60 50/60Pollution degree 3 3

Rated operational current / powerCategory AC-3 (Note 1)(Three-phase squirrel-cage motor load standard responsibility) (Note 2) [kW/A]

220 to 240VAC 2.5/11 [2.2/11] 3.5/13 [2.7/13] 4.5/18 [3.7/18] 5.5/25 [4/20] 7.5/30(26) [5.5/26] 7.5/32 [7.5/32] 11/40 [7.5/35] 15/55 [11/50] 18.5/65 [15/65] 22/85 [19/80] 30/105 [22/100]380 to 440VAC 4/9 [2.7/7] 5.5/12 [4/9] 7.5/18 [7.5/18] 11/23 [7.5/20] 15/30(26) [11/25] 15/32 [15/32] 18.5/40 [15/32] 22/48 [22/48] 30/65 [30/65] 45/85 [37/80] 55/105 [45/93]

500VAC 4/7 [2.7/6] 5.5/9 [5.5/9] 7.5/17 [7.5/17] 11/17 [7.5/17] 15/24 [11/20] 15/24 [11/20] 18.5/32 [15/26] 25/38 [22/38] 37/60 [30/45] 45/75 [45/75] 55/85 [45/75]690VAC 4/5 5.5/7 7.5/9 7.5/9 11/12 11/12 15/17 22/26 30/38 45/52 55/65

Rated operational current / powerCategory AC-4(Three-phase squirrel-cage motor load inching responsibility) [kW/A]

220 to 240VAC 1.5/8 2.2/11 3.7/18 4.5/20 5.5/26 5.5/26 7.5/35 11/50 15/65 19/80380 to 440VAC 2.2/6 4/9 5.5/13 7.5/17 11/24 11/24 15/32 22/47 30/62 37/75

500VAC 2.7/6 5.5/9 5.5/10 7.5/12 7.5/13 11/17 15/24 22/38 30/45 37/55

Rated operational current / powerCategory AC-1 (Resistance, heater load)

100 to 240VAC 20 32 32 60 80 100 120 150380 to 440VAC 11 13 32 32 60 80 100 120 150

Conventional free air thermal current Ith [A] 20 32 32 60 80 100 120 150Minimum applicable load level 48V 200mA 48V 200mA

Aux

iliar

y co

ntac

t rat

ing

Con

tact

ar

rang

emen

t

Standard accessoryNon-Reversing 1a 1a1b 2a2b 2a2b ー 2a2b 2a2b 2a2b 2a2b 2a2bReversing (Note 4, Note 6) 1a×2+2b 1a1b×2+2b 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2 2a2b×2

Special accessoryNon-Reversing 1b 2a ー ー ー ー ー ー ーReversing (Note 4, Note 6) 1b×2+2b 2a×2+2b ー ー ー ー ー ー ー

Max. number of additional options(Note 5)

Front clip-on

Non-Reversing 1 1 ーReversing 2 2 ー 2 ー

Side clip-on

Non-Reversing 2 2Reversing 2 2 ー 2

Rated operational current(Category AC-15 : Alternating current coil load)

120VAC 6 6240VAC 3 3

Rated operational current (Category DC-13 : Direct current coil load)

24VDC 3 3110VDC 0.6 0.6

Conventional free air thermal current Ith [A] 10 10Minimum applicable load level 20V 3mA 20V 3mA

Per

form

ance

Mechanical durability [ten thousand times] 1000 1000 500

Electrical durability[ten thousand times]

Category AC-3 200(Note 9) 200 100Category AC-4 3(Note 9) 3 (Note 9)Category AC-1 50 50

Switching frequency [time/hour]Category AC-3 1800 1800 1200Category AC-4 300 300Category AC-1 1200 1200 600

Chara

cteris

tic

Coil consumption (Note 7)Inrush [VA] 45 75 75 55 110 110 115 115 210Sealed [VA] 7 7 7 4.5 10 10 20 20 23

Power consumption (Note 7) [W] 2.2 2.4 2.4 1.8 3.8 3.8 2.2 2.2 2.8

Out

side

di

men

sion

s

Magnetic Contactors (without Thermal Overload Relays)(Width x Height x Depth) [mm]

Non-Reversing 36×75×78 43×75×78 63×81×81 63×81×81 43×81×81 75×89×91 88×106×106 88×106×106 100×124×127Reversing 82×85×78 97×85×78 136×81×81 136×81×81 96×81×111 160×114×97 216×115×112 216×115×112 270×140×137

Open type Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 45×115×79 63×128×82 63×128×82 ー 75×157.5×91 90×158×106 90×174.5×106 100×196×127Reversing 90×125×79 97×125×79 136×138×82 136×138×82 ー 160×179×97 216×169×112 216×185.5×112 270×213×137

Enclosed Magnetic Starters(Width x Height x Depth) [mm]

Non-Reversing 76×165×97.5 ー 104×176×110 ー 135×231×126 160×282×145 190×317×163Reversing ー ー 220×192×115 ー 300×247×130 320×282×140 410×347×154

IEC 35mm rail mounting Possible (excluding Enclosed Magnetic Starters) Possible (excluding Enclosed Magnetic Starters) ー

Specification List Table

S o l v e T o g e t h e r

MS-

T Se

ries

Intro

duct

ion

Sele

ctio

n an

d Ap

plic

atio

nAp

plicati

on to

Therm

al Over

load R

elays

Pro

duct

Intr

oduc

tion

Ove

rsea

s S

tand

ard

Type

Cod

esO

rder

Pro

cedu

reO

utlin

e D

raw

ing

War

rant

y an

d S

afet

y

19

23

3 Magnetic Contactor

Appearance

T50Frame T100T65

Model name

Applicable standard

Use conditionAmbient temperature [°C]

Frequency [Hz]

For Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mounting

with2-elements

D

HW

with 3-elements

Heater designation (adjustable range of stabilized current)[A]

(Rated operational voltage : 550V maximum)

Rated insulation voltage [V]Rated impulse withstand voltage [kV]Pollution degree

Power consumption [VA/element] at minimum/maximum stabilizationTerminal screw size

Terminal screw size

Contact arrangementConventional free air thermal current Ith [A]

24VAC120VAC240VAC550VAC24VDC110VDC220VDC

TH-□SRTH-□KPSRTH-□FSTH-□FSKP

Compatible with terminalElectric wire size [mm2]

Crimp lug size

Compatible with terminalElectric wire size [mm2]

Crimp lug size

RatingOperational

Current[A]

Minimum applicable load level

Trip classOperating characteristic curve description page

Vibration resistance (vibration resistance malfunction performance)Trip-free

Reset methodOperation indication (lever indication)

Manual trip check

Appli

ed pr

oduc

tsM

ain

circ

uit s

peci

ficat

ions

Note 1: The ambient temperature compensator is mounted on all types.Note 2: ◎ indicates standard equipment.

IEC60947-4-1,EN60947-4-1,JIS C8201-4-1,GB14048.4-10 to +40 (Standard: 20°C; maximum temperature on the board: 55°C)

0(DC) to 40069063

10 to 55Hz 19.6m/s2

29 (24 to 34)35 (30 to 40)42 (34 to 50)

15 (12 to 18)22 (18 to 26)29 (24 to 34)35 (30 to 40)42 (34 to 50)54 (43 to 65)

TH-T50-

TH-T50KP-

74.3×72×83.5-0.2-

TH-T65

TH-T65KP

89×57×83.5

0.26

TH-T100-

TH-T100KP-

89×73.5×83.5-

0.32-

1.6/3.2M5

φ5.5 to 145.5-5 to 14-5

1a1b5

2(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)

0.3(0.3) / 0.3(0.3)1(0.3)

0.2(0.2)0.1(0.1)20V 5mA

M3.5φ1.6, 1.25 to 21.25-3.5 to 2-3.5

10A

◎Manual/Automatic switchable

◎◎

○(TH-T50SR)○(TH-T50KPSR)

△(TH-T50FS)△(TH-T50FSKP)

2.4/5.5M6-

5.5-6 to 22-61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S415 to 42A:10 54A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T65SR)○(TH-T65KPSR)

△(TH-T65FS)△(TH-T65FSKP)

67 (54 to 80)82 (65 to 100)

2.5/6.0M6-

14-6 to 22-6、38-S61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S467A:10 82A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T100SR)○(TH-T100KPSR)△(TH-T100FS)

△(TH-T100FSKP)

Outside dimensions [mm]W×H×D

Product weight[kg]

Category AC-15 AC operated Magnetic Contactors

Coil opening and closinga contact/b contactThe value in brackets indicates the rating for automatic reset.

Category DC-13 DC operated Magnetic Contactors

Coil opening and closingThe value in brackets indicates the rating for automatic reset.

Ope

ratio

n ci

rcui

t (co

ntac

t) sp

ecifi

catio

ns

Thermal Overload Relays

Char

acte

ristic

s/Fu

nctio

ns

Model list

Page 27

With saturable reactorWith 3-element (2E) thermal saturable reactor2-element quick-acting characteristics thermalWith 3-element (2E) thermal quick-acting characteristics

0.8 / 1.8M3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5, 5.5-S3

1a1b2

2(0.5) / 2(0.5)2(0.5) / 2(0.5)1(0.5) / 1(0.5)

0.3(0.3) / 0.3(0.3)0.5(0.3)0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎◎

Model list

Appearance

T18Frame T25

Model name

Applicable standard

Use conditionAmbient temperature [°C]

Frequency [Hz]

For Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mounting

Outside dimensions [mm]W×H×D

Product weight[kg]D

HW

Heater designation (adjustable range of stabilized current)[A]

(Rated operational voltage : 550V maximum)

Rated insulation voltage [V]Rated impulse withstand voltage [kV]Pollution degree

IEC60947-4-1,EN60947-4-1,JIS C8201-4-1,GB14048.4-10 to +40 (Standard: 20°C; maximum temperature on the board: 55°C)

0(DC) to 40069063

0.12 (0.1 to 0.16)

0.17 (0.14 to 0.22)

0.24 (0.2 to 0.32)

0.35 (0.28 to 0.42)

0.5 (0.4 to 0.6)

0.7 (0.55 to 0.85)

0.9 (0.7 to 1.1)

1.3 (1 to 1.6)

1.7 (1.4 to 2)

0.24 (0.2 to 0.32)

0.35 (0.28 to 0.42)

0.5 (0.4 to 0.6)

0.7 (0.55 to 0.85)

0.9 (0.7 to 1.1)

1.3 (1 to 1.6)

1.7 (1.4 to 2)

2.1 (1.7 to 2.5)

2.1 (1.7 to 2.5)

2.5 (2 to 3)

3.6 (2.8 to 4.4)

5 (4 to 6)

6.6 (5.2 to 8)

9 (7 to 11)

11 (9 to 13)

15 (12 to 18)

2.5 (2 to 3)

3.6 (2.8 to 4.4)

5 (4 to 6)

6.6 (5.2 to 8)

9 (7 to 11)

11 (9 to 13)

15 (12 to 18)

22 (18 to 26)

TH-T18–

TH-T18KP–

45×55×76.5–

0.11–

TH-T25

TH-T25KP

63×51×79

0.16

Power consumption [VA/element] at minimum/maximum stabilizationTerminal screw size

Terminal screw size

Contact arrangementConventional free air thermal current Ith [A]

24VAC120VAC240VAC550VAC24VDC110VDC220VDC

TH-□SRTH-□KPSRTH-□FSTH-□FSKP

Compatible with terminalElectric wire size [mm2]Crimp lug size

Compatible with terminalElectric wire size [mm2]

10 to 55 Hz, 19.6 m/s2

10APage 27

Crimp lug size

RatingOperational

Current[A]

Minimum applicable load level

Trip classOperating characteristic curve description page

Vibration resistance (vibration resistance malfunction performance)Trip-free

Reset methodOperation indication (lever indication)

Manual trip checkWith saturable reactor

With 3-element (2E) thermal saturable reactor2-element quick-acting characteristics thermalWith 3-element (2E) thermal quick-acting characteristicsAp

plied

prod

ucts

0.8 / 1.8M3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5, 5.5-S3

1a1b2

2(0.5) / 2(0.5)2(0.5) / 2(0.5)1(0.5) / 1(0.5)

0.3(0.3) / 0.3(0.3)0.5(0.3)0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎Manual/Automatic switchable

◎◎○○○○

1.5 / 3.0M4

φ1.6 to 2.6, 1.25 to 61.25-4 to 5.5-4

1a1b5

2(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)

0.3(0.3) / 0.3(0.3)1(0.3)

0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎Manual/Automatic switchable

◎◎○○○○

Note 1: The ambient temperature compensator is mounted on all types.Note 2: ◎ indicates standard equipment.

Specification List

with 2-elements

with 3-elements

Category AC-15 AC operated Magnetic Contactors

Coil opening and closinga contact/b contact

Category DC-13 DC operated Magnetic Contactors

Coil opening and closing

Char

acte

ristic

s/Fu

nctio

nsO

pera

tion

circ

uit (

cont

act)

spec

ifica

tions

Mai

n ci

rcui

t spe

cific

atio

ns

The value in brackets indicates the rating for automatic reset.

The value in brackets indicates the rating for automatic reset.

S o l v e T o g e t h e rApplication to Thermal Overload Relays

24

Appearance

T50Frame T100T65

Model name

Applicable standard

Use conditionAmbient temperature [°C]

Frequency [Hz]

For Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mounting

with2-elements

D

HW

with 3-elements

Heater designation (adjustable range of stabilized current)[A]

(Rated operational voltage : 550V maximum)

Rated insulation voltage [V]Rated impulse withstand voltage [kV]Pollution degree

Power consumption [VA/element] at minimum/maximum stabilizationTerminal screw size

Terminal screw size

Contact arrangementConventional free air thermal current Ith [A]

24VAC120VAC240VAC550VAC24VDC110VDC220VDC

TH-□SRTH-□KPSRTH-□FSTH-□FSKP

Compatible with terminalElectric wire size [mm2]

Crimp lug size

Compatible with terminalElectric wire size [mm2]

Crimp lug size

RatingOperational

Current[A]

Minimum applicable load level

Trip classOperating characteristic curve description page

Vibration resistance (vibration resistance malfunction performance)Trip-free

Reset methodOperation indication (lever indication)

Manual trip check

Appli

ed pr

oduc

tsM

ain

circ

uit s

peci

ficat

ions

Note 1: The ambient temperature compensator is mounted on all types.Note 2: ◎ indicates standard equipment.

IEC60947-4-1,EN60947-4-1,JIS C8201-4-1,GB14048.4-10 to +40 (Standard: 20°C; maximum temperature on the board: 55°C)

0(DC) to 40069063

10 to 55Hz 19.6m/s2

29 (24 to 34)35 (30 to 40)42 (34 to 50)

15 (12 to 18)22 (18 to 26)29 (24 to 34)35 (30 to 40)42 (34 to 50)54 (43 to 65)

TH-T50-

TH-T50KP-

74.3×72×83.5-0.2-

TH-T65

TH-T65KP

89×57×83.5

0.26

TH-T100-

TH-T100KP-

89×73.5×83.5-

0.32-

1.6/3.2M5

φ5.5 to 145.5-5 to 14-5

1a1b5

2(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)

0.3(0.3) / 0.3(0.3)1(0.3)

0.2(0.2)0.1(0.1)20V 5mA

M3.5φ1.6, 1.25 to 21.25-3.5 to 2-3.5

10A

◎Manual/Automatic switchable

◎◎

○(TH-T50SR)○(TH-T50KPSR)

△(TH-T50FS)△(TH-T50FSKP)

2.4/5.5M6-

5.5-6 to 22-61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S415 to 42A:10 54A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T65SR)○(TH-T65KPSR)

△(TH-T65FS)△(TH-T65FSKP)

67 (54 to 80)82 (65 to 100)

2.5/6.0M6-

14-6 to 22-6、38-S61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S467A:10 82A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T100SR)○(TH-T100KPSR)△(TH-T100FS)

△(TH-T100FSKP)

Outside dimensions [mm]W×H×D

Product weight[kg]

Category AC-15 AC operated Magnetic Contactors

Coil opening and closinga contact/b contactThe value in brackets indicates the rating for automatic reset.

Category DC-13 DC operated Magnetic Contactors

Coil opening and closingThe value in brackets indicates the rating for automatic reset.

Ope

ratio

n ci

rcui

t (co

ntac

t) sp

ecifi

catio

ns

Thermal Overload Relays

Char

acte

ristic

s/Fu

nctio

ns

Model list

Page 27

With saturable reactorWith 3-element (2E) thermal saturable reactor2-element quick-acting characteristics thermalWith 3-element (2E) thermal quick-acting characteristics

0.8 / 1.8M3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5, 5.5-S3

1a1b2

2(0.5) / 2(0.5)2(0.5) / 2(0.5)1(0.5) / 1(0.5)

0.3(0.3) / 0.3(0.3)0.5(0.3)0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎◎

S o l v e T o g e t h e r

MS-

T Se

ries

Intro

duct

ion

Sele

ctio

n an

d Ap

plic

atio

nAp

plicati

on to

Therm

al Over

load R

elays

Pro

duct

Intr

oduc

tion

Ove

rsea

s S

tand

ard

Type

Cod

esO

rder

Pro

cedu

reO

utlin

e D

raw

ing

War

rant

y an

d S

afet

y

25

24

Appearance

T50Frame T100T65

Model name

Applicable standard

Use conditionAmbient temperature [°C]

Frequency [Hz]

For Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mounting

with2-elements

D

HW

with 3-elements

Heater designation (adjustable range of stabilized current)[A]

(Rated operational voltage : 550V maximum)

Rated insulation voltage [V]Rated impulse withstand voltage [kV]Pollution degree

Power consumption [VA/element] at minimum/maximum stabilizationTerminal screw size

Terminal screw size

Contact arrangementConventional free air thermal current Ith [A]

24VAC120VAC240VAC550VAC24VDC110VDC220VDC

TH-□SRTH-□KPSRTH-□FSTH-□FSKP

Compatible with terminalElectric wire size [mm2]

Crimp lug size

Compatible with terminalElectric wire size [mm2]

Crimp lug size

RatingOperational

Current[A]

Minimum applicable load level

Trip classOperating characteristic curve description page

Vibration resistance (vibration resistance malfunction performance)Trip-free

Reset methodOperation indication (lever indication)

Manual trip check

Appli

ed pr

oduc

tsM

ain

circ

uit s

peci

ficat

ions

Note 1: The ambient temperature compensator is mounted on all types.Note 2: ◎ indicates standard equipment.

IEC60947-4-1,EN60947-4-1,JIS C8201-4-1,GB14048.4-10 to +40 (Standard: 20°C; maximum temperature on the board: 55°C)

0(DC) to 40069063

10 to 55Hz 19.6m/s2

29 (24 to 34)35 (30 to 40)42 (34 to 50)

15 (12 to 18)22 (18 to 26)29 (24 to 34)35 (30 to 40)42 (34 to 50)54 (43 to 65)

TH-T50-

TH-T50KP-

74.3×72×83.5-0.2-

TH-T65

TH-T65KP

89×57×83.5

0.26

TH-T100-

TH-T100KP-

89×73.5×83.5-

0.32-

1.6/3.2M5

φ5.5 to 145.5-5 to 14-5

1a1b5

2(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)

0.3(0.3) / 0.3(0.3)1(0.3)

0.2(0.2)0.1(0.1)20V 5mA

M3.5φ1.6, 1.25 to 21.25-3.5 to 2-3.5

10A

◎Manual/Automatic switchable

◎◎

○(TH-T50SR)○(TH-T50KPSR)

△(TH-T50FS)△(TH-T50FSKP)

2.4/5.5M6-

5.5-6 to 22-61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S415 to 42A:10 54A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T65SR)○(TH-T65KPSR)

△(TH-T65FS)△(TH-T65FSKP)

67 (54 to 80)82 (65 to 100)

2.5/6.0M6-

14-6 to 22-6、38-S61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S467A:10 82A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T100SR)○(TH-T100KPSR)△(TH-T100FS)

△(TH-T100FSKP)

Outside dimensions [mm]W×H×D

Product weight[kg]

Category AC-15 AC operated Magnetic Contactors

Coil opening and closinga contact/b contactThe value in brackets indicates the rating for automatic reset.

Category DC-13 DC operated Magnetic Contactors

Coil opening and closingThe value in brackets indicates the rating for automatic reset.

Ope

ratio

n ci

rcui

t (co

ntac

t) sp

ecifi

catio

ns

Thermal Overload Relays

Char

acte

ristic

s/Fu

nctio

ns

Model list

Page 27

With saturable reactorWith 3-element (2E) thermal saturable reactor2-element quick-acting characteristics thermalWith 3-element (2E) thermal quick-acting characteristics

0.8 / 1.8M3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5, 5.5-S3

1a1b2

2(0.5) / 2(0.5)2(0.5) / 2(0.5)1(0.5) / 1(0.5)

0.3(0.3) / 0.3(0.3)0.5(0.3)0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎◎

Model list

Appearance

T18Frame T25

Model name

Applicable standard

Use conditionAmbient temperature [°C]

Frequency [Hz]

For Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mounting

Outside dimensions [mm]W×H×D

Product weight[kg]D

HW

Heater designation (adjustable range of stabilized current)[A]

(Rated operational voltage : 550V maximum)

Rated insulation voltage [V]Rated impulse withstand voltage [kV]Pollution degree

IEC60947-4-1,EN60947-4-1,JIS C8201-4-1,GB14048.4-10 to +40 (Standard: 20°C; maximum temperature on the board: 55°C)

0(DC) to 40069063

0.12 (0.1 to 0.16)

0.17 (0.14 to 0.22)

0.24 (0.2 to 0.32)

0.35 (0.28 to 0.42)

0.5 (0.4 to 0.6)

0.7 (0.55 to 0.85)

0.9 (0.7 to 1.1)

1.3 (1 to 1.6)

1.7 (1.4 to 2)

0.24 (0.2 to 0.32)

0.35 (0.28 to 0.42)

0.5 (0.4 to 0.6)

0.7 (0.55 to 0.85)

0.9 (0.7 to 1.1)

1.3 (1 to 1.6)

1.7 (1.4 to 2)

2.1 (1.7 to 2.5)

2.1 (1.7 to 2.5)

2.5 (2 to 3)

3.6 (2.8 to 4.4)

5 (4 to 6)

6.6 (5.2 to 8)

9 (7 to 11)

11 (9 to 13)

15 (12 to 18)

2.5 (2 to 3)

3.6 (2.8 to 4.4)

5 (4 to 6)

6.6 (5.2 to 8)

9 (7 to 11)

11 (9 to 13)

15 (12 to 18)

22 (18 to 26)

TH-T18–

TH-T18KP–

45×55×76.5–

0.11–

TH-T25

TH-T25KP

63×51×79

0.16

Power consumption [VA/element] at minimum/maximum stabilizationTerminal screw size

Terminal screw size

Contact arrangementConventional free air thermal current Ith [A]

24VAC120VAC240VAC550VAC24VDC

110VDC220VDC

TH-□SRTH-□KPSRTH-□FSTH-□FSKP

Compatible with terminalElectric wire size [mm2]Crimp lug size

Compatible with terminalElectric wire size [mm2]

10 to 55 Hz, 19.6 m/s2

10APage 27

Crimp lug size

RatingOperational

Current[A]

Minimum applicable load level

Trip classOperating characteristic curve description page

Vibration resistance (vibration resistance malfunction performance)Trip-free

Reset methodOperation indication (lever indication)

Manual trip checkWith saturable reactor

With 3-element (2E) thermal saturable reactor2-element quick-acting characteristics thermalWith 3-element (2E) thermal quick-acting characteristicsAp

plied

prod

ucts

0.8 / 1.8M3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5, 5.5-S3

1a1b2

2(0.5) / 2(0.5)2(0.5) / 2(0.5)1(0.5) / 1(0.5)

0.3(0.3) / 0.3(0.3)0.5(0.3)0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎Manual/Automatic switchable

◎◎○○○○

1.5 / 3.0M4

φ1.6 to 2.6, 1.25 to 61.25-4 to 5.5-4

1a1b5

2(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)

0.3(0.3) / 0.3(0.3)1(0.3)

0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎Manual/Automatic switchable

◎◎○○○○

Note 1: The ambient temperature compensator is mounted on all types.Note 2: ◎ indicates standard equipment.

Specification List

with 2-elements

with 3-elements

Category AC-15 AC operated Magnetic Contactors

Coil opening and closinga contact/b contact

Category DC-13 DC operated Magnetic Contactors

Coil opening and closing

Char

acte

ristic

s/Fu

nctio

nsO

pera

tion

circ

uit (

cont

act)

spec

ifica

tions

Mai

n ci

rcui

t spe

cific

atio

ns

The value in brackets indicates the rating for automatic reset.

The value in brackets indicates the rating for automatic reset.

S o l v e T o g e t h e rApplication to Thermal Overload Relays

24

Appearance

T50Frame T100T65

Model name

Applicable standard

Use conditionAmbient temperature [°C]

Frequency [Hz]

For Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mountingFor Magnetic StartersFor independent mounting

with2-elements

D

HW

with 3-elements

Heater designation (adjustable range of stabilized current)[A]

(Rated operational voltage : 550V maximum)

Rated insulation voltage [V]Rated impulse withstand voltage [kV]Pollution degree

Power consumption [VA/element] at minimum/maximum stabilizationTerminal screw size

Terminal screw size

Contact arrangementConventional free air thermal current Ith [A]

24VAC120VAC240VAC550VAC24VDC110VDC220VDC

TH-□SRTH-□KPSRTH-□FSTH-□FSKP

Compatible with terminalElectric wire size [mm2]

Crimp lug size

Compatible with terminalElectric wire size [mm2]

Crimp lug size

RatingOperational

Current[A]

Minimum applicable load level

Trip classOperating characteristic curve description page

Vibration resistance (vibration resistance malfunction performance)Trip-free

Reset methodOperation indication (lever indication)

Manual trip check

Appli

ed pr

oduc

tsM

ain

circ

uit s

peci

ficat

ions

Note 1: The ambient temperature compensator is mounted on all types.Note 2: ◎ indicates standard equipment.

IEC60947-4-1,EN60947-4-1,JIS C8201-4-1,GB14048.4-10 to +40 (Standard: 20°C; maximum temperature on the board: 55°C)

0(DC) to 40069063

10 to 55Hz 19.6m/s2

29 (24 to 34)35 (30 to 40)42 (34 to 50)

15 (12 to 18)22 (18 to 26)29 (24 to 34)35 (30 to 40)42 (34 to 50)54 (43 to 65)

TH-T50-

TH-T50KP-

74.3×72×83.5-0.2-

TH-T65

TH-T65KP

89×57×83.5

0.26

TH-T100-

TH-T100KP-

89×73.5×83.5-

0.32-

1.6/3.2M5

φ5.5 to 145.5-5 to 14-5

1a1b5

2(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)

0.3(0.3) / 0.3(0.3)1(0.3)

0.2(0.2)0.1(0.1)20V 5mA

M3.5φ1.6, 1.25 to 21.25-3.5 to 2-3.5

10A

◎Manual/Automatic switchable

◎◎

○(TH-T50SR)○(TH-T50KPSR)

△(TH-T50FS)△(TH-T50FSKP)

2.4/5.5M6-

5.5-6 to 22-61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S415 to 42A:10 54A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T65SR)○(TH-T65KPSR)

△(TH-T65FS)△(TH-T65FSKP)

67 (54 to 80)82 (65 to 100)

2.5/6.0M6-

14-6 to 22-6、38-S61a1b

52(0.5) / 3(0.5)2(0.5) / 3(0.5)1(0.5) / 2(0.5)0.5(0.5) / 1(0.5)

1(0.3)0.2(0.2)0.1(0.1)20V 5mA

M4φ1.6, 1.25 to 2

1.25-4 to 2-4, 5.5-S467A:10 82A:10A

◎Manual/Automatic switchable

◎◎

○(TH-T100SR)○(TH-T100KPSR)△(TH-T100FS)

△(TH-T100FSKP)

Outside dimensions [mm]W×H×D

Product weight[kg]

Category AC-15 AC operated Magnetic Contactors

Coil opening and closinga contact/b contactThe value in brackets indicates the rating for automatic reset.

Category DC-13 DC operated Magnetic Contactors

Coil opening and closingThe value in brackets indicates the rating for automatic reset.

Ope

ratio

n ci

rcui

t (co

ntac

t) sp

ecifi

catio

ns

Thermal Overload Relays

Char

acte

ristic

s/Fu

nctio

ns

Model list

Page 27

With saturable reactorWith 3-element (2E) thermal saturable reactor2-element quick-acting characteristics thermalWith 3-element (2E) thermal quick-acting characteristics

0.8 / 1.8M3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5, 5.5-S3

1a1b2

2(0.5) / 2(0.5)2(0.5) / 2(0.5)1(0.5) / 1(0.5)

0.3(0.3) / 0.3(0.3)0.5(0.3)0.2(0.2)0.1(0.1)

20V 5mAM3.5

φ1.6, 0.75 to 2.51.25-3.5 to 2-3.5

◎◎

S o l v e T o g e t h e r

MS-

T Se

ries

Intro

duct

ion

Sele

ctio

n an

d Ap

plic

atio

nAp

plicati

on to

Therm

al Over

load R

elays

Pro

duct

Intr

oduc

tion

Ove

rsea

s S

tand

ard

Type

Cod

esO

rder

Pro

cedu

reO

utlin

e D

raw

ing

War

rant

y an

d S

afet

y

25

25

4 Circuit Protectors

51

2

Frame (A) 30

Model CP30-BA CP-S

Image

Number of poles 1 2 3 1 2 3

Rated insulation voltage Ui (V) 250 250

Rated impulse withstand voltage Uimp (kV) 2.5 2.5

Rated current (A) 0.1 0.25 0.3 0.5 1 2 3 5 7 10 15 20 30 0.05 0.1 0.25 0.3 0.5 0.75 1 2 2.5 3 5 7 7.5 10 15 20 25 30

Rated short-circuit capacity (kA)

UL 1077CSA C22.2 No.235 (*11)

Rated voltage (V)AC (V) 250 250 –

DC (V) 65 125 – 65 –

AC 2.5kA at 250V 1.5kA at 250V –

DC 2.5kA at 65V 2.5kA at 125V – 1kA at 65V –

IEC 60934EN 60934(Icn)

Rated insulation voltage Ui (V) 250 250

AC 250 1.5kA at 230V2.5kA at 120V

DC 2.5kA at 60V 2.5kA at 120V – 1kA at 60V 1kA at 120V(1kA at 60V) (*7) 1kA at 60V

EN 60947-2IEC 60947-2(Icu/Ics)

Rated insulation voltage Ui (V) 250 –

AC 2.5/2.5kA at 230V –

DC 2.5/2.5kA at 60V 2.5/2.5kA at 120V – –

AC-DC common use � – (*1) – (*8)

Reverse connection � –

Rated short time current(for switch only type) –

AC250V 50/60Hz 1500A 0.02sAC125V 50/60Hz 2500A 0.02sDC65V 1000A 0.02sDC125V 1000A 0.02s

Rated ambient temperature (°C) 40 (T40) 25 (T25)

Operating characteristics Instantaneous type (I); Medium type (M), (MD);Slow type (S), (SD); Fast type (F) (*2)

Instantaneous type (I); Medium type (M), (MD);Slow type (S), (SD); Fast type (F) (FD)

Mode of tripping

Instantaneous type (I): magnetic only [MO] Instantaneous type (I): magnetic only [MO]

Medium type (M), (MD)Slow type (S), (SD) : hydraulic-magnetic [HM]Fast type (F)

Medium type (M), (MD)Slow type (S), (SD) : hydraulic-magnetic [HM]Fast type (F), (FD)

Method of operation S-type (IEC 60934)

Trip-free behaviour Trip-free (IEC 60934)

Mass (kg) 0.08 0.16 0.23 0.06 0.12 0.18

Accessories

Retractable small terminal cover (TC-S) �Standard IP20 (front, terminal covers closed) [Certifi ed of TUV] –

Inertial delay (ID) � (Medium, Slow type: AC only) � (Medium, Slow, Fast type: AC only)

Alarm switch (AL) � (1c) � (1c) (*7)

Auxiliary switch (AX) � (1c) � (1c)

Shunt trip (SHT) � (for relay type) (*3) � (for parallel and relay type: AC only)

Large terminal cover (TC-L) � (*6) –

Flushpanel mounting brackets (FP) � –

Back facing wiring termnal (BT) � (*4), (*6) –

Lock cover (LC) – � –

Accessory terminal cover (TC) � (*6) –

ConnectionMain body 20A or less : Screw terminal M4

30A : Screw termnal M5Male tub terminal 6.3mm (#250)

[Screw terminal M4 (series type only)]

Alarm switch / Auxiliary switch Screw terminal M3.5 Male tub terminal 2.8mm (#110)

Main body mounting method Srface, IEC rail mountingFlush panel mounting (option) Panel mounting

International standard UL(cURus), CCC (*5) UL(UR) (*9), (*10) –

CE Marking EN 60934 : TUV approvalEN 60947-2 : Self-declaration (*5) EN 60934 : TUV approval (*10)

Operating characteris is Medium type (M) only. The rated current, 0.3A, 2A, 3A and 7A are not applied.

Notes: *1 The 3-pole products are for AC use only. *2 Contact us for operating characteristics other than those mentioned above. *3 In poles equipped with a shunt tripping mechanism, the overcurrent tripping element is not operative (switched shunt tripping). *4 For back-face wiring terminals, specify if it will be used with 30A, or 20A or less. *5 UL(cURus), CCC, and CE Marking are displayed on standard products. *6 It is recognition of UL(cURus), CCC, and TUV. *7 In case of DC use, only DC65V is available. *8 Specify if for DC use when ordering. *9 Specify when ordering. (In case of CP-S UL, type name is CP-SU.) *10 Connection is male tub terminal only. *11 CP30-BA only.

Remarks: 1. Products for non-standard conditions are special order. (Low temperature, 1st and 2nd-degree moisture fungal treatment, corrosion-resistant) 2. Although a buzzing sound may occur when an instantaneous type becomes 80% or more of the rated current for AC use, performance is not effected. Please take this point into

consideration when selecting units for use in quiet environments. 3. Please use in environments free of high temperatures, humidity, dust, corrosive gas, vibration, and impact.

Also, do not use it in a circuit with inrush current or harmonics. Problems may result.

7D

etai

led

Spe

cific

atio

ns

2 Circuit ProtectorsDetailedSpecifications 7

26

5 MCB / RCCB / IsolatorDIN SeriesDIN Series

5

MCB

Type BHW-T10

Image

No. of poles [P] 1 1+N∗1 2 3 3+N∗1 4 1 1+N∗1 2 3 3+N∗1 4

Instantaneous tripping Type B∗2 Type C, D∗2

Rated insulation voltage Ui [V] 660 660

Rated current In [A]at ambient temperature 30:

6, 10, 16, 20, 25,32, 40, 50, 63

0.5, 1, 2, 3, 4, 5,6, 10, 16, 20, 25,

32, 40, 50, 63

Rated short- circuit capacity [kA]

IEC/EN 60898-1(Icn)

AC

240V 10 10

240/415V 10 – 10 10 – 10

415V – 10 – 10

Energy limiting class∗3 Class 3

Number of operating cycles

Without current 4,000

With current 4,000

Dimensions[mm]

a 18 36 54 72 18 36 54 72

b 92.6

c 44

ca Max. 73.5

Type of overcurrent release Thermal-magnetic

Mounting IEC 35mm rail

Applicable wire size 1 to 25mm2

Mass [kg] 0.13 0.25 0.26 0.39 0.51 0.52 0.13 0.25 0.26 0.39 0.51 0.52

Accessories (optional)∗4Auxiliary switch (AX) s

Shunt trip (SHT) s

Terminal connection Solderless

Based on standard IEC/EN 60898-1

CE marking s

Specifications

∗4: Factory fitted∗5: In case of installing breakers side by side, reduce the

passing current to under 80% of the rated current.

∗1: N pole is a switched neutral pole (without overcurrent release device).∗2: Type B: (3 In <, 5 In), Type C: (5 In <, 10 In), Type D: (10 In <, 20 In)∗3: Except for Type D

RCCB

Type BVW-T

Image

No. of poles [P] 2(1+N)∗1 4(3+N)∗1

Rated current In [A]at ambient temperature 30: 16, 25, 32, 40, 63

Rated voltage [VAC] 240 415

Rated current sensitivity I∆n [mA] 30, 100, 300

Max. operating time at 5 I∆n [s] 0.04

Pulsating current sensitivity Type AC

Dimensions[mm]

a 36 72

b 90

c 44

ca 74

Rated making and breaking capacity Im [A] 500(In 16, 25, 32, 40A), 630(In 63A)

Rated conditional short-circuit current Inc [kA] 6

Rated residual making and breaking capacity I∆m [A] 500(In 16, 25, 32, 40A), 630(In 63A)

Rated conditional residual short-circuit current I∆C [kA] 6

Number of operating cycles

Without current 4,000∗2

With current 2,000

Type of overcurrent release –

Mounting IEC 35mm rail

Applicable wire size 1 to 25mm2

Mass [kg] 0.22 0.44

Terminal connection Solderless

Based on standard IEC/EN 61008-1

CE marking s

∗1: N pole is a switched neutral pole (without overcurrent release device).∗2: In case of ampere rating 32, 40 and 63A, the number of operating

cycles is 3,000.

Isolating switch

Type KBW-T

Image

No. of poles [P] 1 2 3 4 2 3 4

Utilization category AC-22A AC-22A

Rated current In [A]at ambient temperature 30: 25, 40, 63 80, 100, 125

Rated voltage [VAC] 240 240/415 240/415

Short time withstand current Icw [A] 12×In, 1s 12×In, 1s

Short-circuit making capacity Icm [A] 12×In 12×In

Rated impulse withstand voltage Uimp [kV] 6 6

Pollution degree 2 2

Dimensions[mm]

a 18 36 54 72 36 54 72

b 92.6 92.6

c 44 44

ca Max. 73.5 Max. 73.5

Number of operating cycles

Without current 10,000 10,0008,000(125A)

With current 1,500 1,5001,000(125A)

Mounting IEC 35mm rail IEC 35mm rail

Applicable wire size 1 to 25mm2 16 to 50mm2

Mass [kg] 0.12 0.22 0.33 0.47 0.2 0.3 0.4

Terminal connection Solderless Solderless

Based on standard IEC/EN 60947-3 IEC/EN 60947-3

CE marking s s

aca

c

b aca

c

b

aca

c

b

27

6 Power Meter

April 2016 No.M012

NewProductNews

MITSUBISHI ELECTRONIC MULTI-MEASURING INSTRUMENTMODEL

ME96SS Version“A”

Upgraded version of ME96SS Series of electronic multi-measuring instrument will be launched. New ME96SS Series (Version A) are improved measurement function and network support. It allows more effective and energy-saving monitoring systems with upgraded items.Key Items- Improved measurement accuracy of economy model to support active

energy class 0.5S.- Line-up MODBUS®TCP communication unit and support Ethernet

communication.- Line-up logging unit for data backup.

Data logging support (optional plug-in module: ME-0000BU-SS96)Special Feature#

Line-up the option unit that can hold the data during a communication impossible period.

SD memory card (EMU4-SD2GB)*1

The data of multiple logging units can be managed with one SD memory card.

CSV file data

*1 Make sure to use the SD memory card manufactured by Mitsubishi Electric Corporation (Model EMU4-SD2GB). Using the other types of the SD memory card may cause the trouble such as data destruction of the memory card or system failure.

Economy model Standard model High-spec model

Before improvement After improvement Before improvement After improvement Before improvement After improvement

Model ME96SSE-MB ME96SSEA-MB ME96SSR-MB ME96SSRA-MB ME96SSH-MB ME96SSHA-MB

Mea

sure

men

t ite

ms

and

accu

racy

Active energy Class1 Class0.5S Class1 Class0.5S Class0.5S Class0.5S

Reactive energy – – Class2 Class1S Class2 Class1S

Power factor ±2.0% ±0.5% ±2.0% ±0.5% ±1.0% ±0.2%

Harmonic –±2.0%THD

±2.0%(Up to 13th)

±1.0%(Up to 19th)

±2.0%(Up to 31st)

±1.0%(Up to 31st)

Demand – A (thermal) A (thermal)A (thermal),

W, var, VA (rolling)A (thermal),W (rolling)

A (thermal),W, var, VA (rolling)

Line-up MODBUS®TCP communication unit that can be used in Ethernet environment in addition to the current MODBUS®RTU (RS-485) communication and CC-Link communication units.

MODBUS®TCP communication support (optional plug-in module: ME-0000MT-SS96)Special Feature@

SWITCH/HUBEthernet

PLC

Product Outline External Appearance

Improved measurement accuracy of active energy, reactive energy and power factor. And also expanded measurement range of harmonic, demand and others.

Measuring function improvementSpecial Feature!

Launch Date April 2016

April 2016 No.M012

NewProductNews

MITSUBISHI ELECTRONIC MULTI-MEASURING INSTRUMENTMODEL

ME96SS Version“A”

Upgraded version of ME96SS Series of electronic multi-measuring instrument will be launched. New ME96SS Series (Version A) are improved measurement function and network support. It allows more effective and energy-saving monitoring systems with upgraded items.Key Items- Improved measurement accuracy of economy model to support active

energy class 0.5S.- Line-up MODBUS®TCP communication unit and support Ethernet

communication.- Line-up logging unit for data backup.

Data logging support (optional plug-in module: ME-0000BU-SS96)Special Feature#

Line-up the option unit that can hold the data during a communication impossible period.

SD memory card (EMU4-SD2GB)*1

The data of multiple logging units can be managed with one SD memory card.

CSV file data

*1 Make sure to use the SD memory card manufactured by Mitsubishi Electric Corporation (Model EMU4-SD2GB). Using the other types of the SD memory card may cause the trouble such as data destruction of the memory card or system failure.

Economy model Standard model High-spec model

Before improvement After improvement Before improvement After improvement Before improvement After improvement

Model ME96SSE-MB ME96SSEA-MB ME96SSR-MB ME96SSRA-MB ME96SSH-MB ME96SSHA-MB

Mea

sure

men

t ite

ms

and

accu

racy

Active energy Class1 Class0.5S Class1 Class0.5S Class0.5S Class0.5S

Reactive energy – – Class2 Class1S Class2 Class1S

Power factor ±2.0% ±0.5% ±2.0% ±0.5% ±1.0% ±0.2%

Harmonic –±2.0%THD

±2.0%(Up to 13th)

±1.0%(Up to 19th)

±2.0%(Up to 31st)

±1.0%(Up to 31st)

Demand – A (thermal) A (thermal)A (thermal),

W, var, VA (rolling)A (thermal),W (rolling)

A (thermal),W, var, VA (rolling)

Line-up MODBUS®TCP communication unit that can be used in Ethernet environment in addition to the current MODBUS®RTU (RS-485) communication and CC-Link communication units.

MODBUS®TCP communication support (optional plug-in module: ME-0000MT-SS96)Special Feature@

SWITCH/HUBEthernet

PLC

Product Outline External Appearance

Improved measurement accuracy of active energy, reactive energy and power factor. And also expanded measurement range of harmonic, demand and others.

Measuring function improvementSpecial Feature!

Launch Date April 2016

www.MitsubishiElectric.com

New publication, effective March 2016.Specifications are subject to change without notice.

This pamphlet is made of recycled paper.M012 1603[IP]

For Safety : Please read the instruction manual carefully before using the products in this catalog. Wiring and connection must be done by the person have a specialized knowledge of electric construction and wiring.

SpecificationsType ME96SSHA-MB, ME96SSRA-MB, ME96SSEA-MB

Phase wire system 3-PHASE 4-WIRE, 3-PHASE 3-WIRE (3CT, 2CT) 1-PHASE 3-WIRE, 1-PHASE 2-WIRE (common)

Rating

Current AC5A, AC1A (common)

Voltage3-PHASE 4-WIRE: max AC277/480V 3-PHASE 3-WIRE: (DELTA) max AC220V, (STAR) max AC440V1-PHASE 3-WIRE: max AC220/440V 1-PHASE 2-WIRE: (DELTA) max AC220V, (STAR) max AC440V

Frequency 50-60Hz (common)

Item Measurement Item ME96SSHA-MB ME96SSRA-MB ME96SSEA-MB

Mea

sure

men

t ele

men

ts

Current (A) A1, A2, A3, AN, AAVG

±0.1% ±0.2% ±0.5%Current Demand (DA) DA1, DA2, DA3, DAN, DAAVG

Voltage (V) V12, V23, V31, VAVG (L-L), V1N, V2N, V3N, VAVG (L-N)

Active Power (W) W1, W2, W3, ΣW

±0.2% ±0.5%

±0.5%

Reactive Power (var) var1, var2, var3, Σvar –

Apparent Power (VA) VA1, VA2, VA3, ΣVA –

Power Factor (PF) PF1, PF2, PF3, ΣPF ±0.2% ±0.5% ±0.5%

Frequency (Hz) Hz ±0.1% ±0.1% ±0.2%

Active Energy (Wh) Imported, Exported class0.5S (IEC62053-22) class0.5S (IEC62053-22) class0.5S (IEC62053-22)

Reactive Energy (varh) Imported Lag, Imported Lead, Exported Lag, Exported Lead class1S (IEC62053-24) class1S (IEC62053-24) –

Apparent Energy (VAh) Imported + Exported ±2.0% ±2.0% –

Harmonic current (HI) Only odd number±1.0% (1 to 31st) ±1.0% (1 to 19th) ±2.0% (THD only)

Harmonic voltage (HV) Only odd number

Rolling Demand (DW) Rolling Block, Fixing Block ±0.2% ±0.5% –

Rolling Demand (Dvar) Rolling Block, Fixing Block ±1.0% ±1.0% –

Rolling Demand (DVA) Rolling Block, Fixing Block ±1.0% ±1.0% –

Periodic Active Energy (Wh) Periodic Active Energy 1, Periodic Active Energy 2 class0.5S (IEC62053-22) class0.5S (IEC62053-22) –

Operation time (h) Operation time 1, Operation time 2 (Reference) (Reference) (Reference)

Communication Specification MODBUS®RTU communication

Accessible optional plug-in module(only ME96SSHA-MB, ME96SSRA-MB)

ME-4210-SS96 4-Analog output, 2-Pulse output, 1-Digital input

ME-0040C-SS96 CC-Link communication, 4-Digital input

ME-0052-SS96 5-Digital input, 2-Digital output

ME-0000BU-SS96 SD CARD

ME-0000MT-SS96 MODBUS®TCP communication

Auxiliary power AC100-240V (±15%), DC100-240V (-30% +15%)

Weight 0.5kg

Dimension 96 (H) × 96 (W) × 90 (D)

Attachment Method Embedding attachment

Operating temperature/humidity -5 to +55°C (average temperature: 35°C or less per day), 0 to 85%RH, non condensing

Storage temperature/humidity -25 to +75°C (average temperature: 35°C or less per day), 0 to 85%RH, non condensing

Optional part (For ME-0000BU-SS96) SD memory card (EMU4-SD2GB)*1

Dimensions & Wiring Diagrams

3P4W circuitMODBUS® RTU communication

CC-Link communication

Analog output

Pluse output

Alarm output

92 +0.5 0

92+

0.5

0

Panel Hole DimensionsAttachible to a panel of thicness 1.6mm to 4.0mm

95.8(COVER)

95.8

(CO

VE

R)

91.6(PANEL CUT)

91.6

(PA

NE

L C

UT

)

20.7

90.2

(110

.9)

uvuvuv

UV

UV

UV

kKL

321

Load

0

(+)(−)

KL

KL

l k

l k

l

321

Load

0

ProtectiveEarthing

ProtectiveEarthing

C2

+C1C1+C2

+C3C3P1P2P3PN

SG

T/R+T/R−

MAMB

SLDTer e e

w

q(+)(−)

w

q

MODBUS® RTUCommunication

MODBUS® RTUCommunication

kKL

l kKL l k

KL l

C2

+C1C1+C2

+C3C3P1P2P3PN

C2

+C1C1+C2

+C3C3P1P2P3PN

SG

T/R+T/R−

MAMB

SLDTer

qAuxiliary power supply 100-240VAC or 100-240VDCwFuse : 0.5AeSome MODBUS® RTU equipment dosen't have SG. In this case, the wiring between SG is unnecessary. *1 For a low voltage circuit, grounding of the secondary sides of VT and CT is unnecessary.*2 Do not connect to NC terminal.

SLD

ME-4210-SS96

DC24V

Analog output CH1

Analog output CH2

Analog output CH3

Analog output CH4

Pulse output1/ Alarm output1

Pulse output2/ Alarm output2

{{{{{{{

Digital inputMAMB

CH1+CH1-CH2+CH2-CH3+CH3-CH4+

C2B/COM2C2A/A2

CH4-

DI+

C1A/A1C1B/COM1

DI-

ME96SSRA-MB

ME96SSHA-MB

ME-0040C-SS96

ME96SSRA-MB

ME96SSHA-MB

ME96SSRA-MB

ME96SSHA-MB

T/R+T/R−SGTer

C2

+C1C1+C2

+C3C3P1P2P3PN

C2

+C1C1+C2

+C3C3P1P2P3PN

C2

+C1C1+C2

+C3C3P1P2P3PN

C2

+C1C1+C2

+C3C3P1P2P3PN

SLD

MAMB

T/R+T/R−SGTer

SLD

MAMB

T/R+T/R−SGTer

SLD

MAMB

T/R+T/R−SGTer

SLD

MAMB

T/R+T/R−SGTer

DI COM

DC24V

DADBDGSLDFG

DGDB

SLD

DADI1DI2DI3DI4

Digital input 1Digital input 2Digital input 3Digital input 4

{{{{

Digital input 1

{

Digital input 2

{

Digital input 3

{

Digital input 4

{

Digital input 5

{

{

Digital output 1

{

Digital output 2

ProtectiveBonding

ProtectiveEarthing

CC-LinkCommunication

CC-LinkCommunication

DI, DO

DI1+DI1-DI2+DI2-DI3+DI3-DI4+DI4-DI5+DI5-DO1+DO1-DO2+DO2-

DC24VME-0052-SS96

ME96SSRA-MB

ME96SSHA-MB

DI1-,DI2-,DI3-,DI4-,DI5-, are connected inside.

MODBUS® TCP communication

SD CARD

SDCARD

ProtectiveEarthing

ME-0000BU-SS96

ME96SSRA-MB

ME96SSHA-MB ME-0000MT-SS96

ProtectiveEarthing

ETHERNET

*1 Make sure to use the SD memory card manufactured by Mitsubishi Electric Corporation (Model EMU4-SD2GB). Using the other types of the SD memory card may cause the trouble such as data destruction of the memory card or system failure.

MITSUBISHI ELECTRIC CORPORATIONFUKUYAMA WORKS1-8, Midorimachi Fukuyama-city Hiroshima-pref., JapanPhone+81-84-926-8142

28

7 Eco Monitor Plus

8

Equipment has been operating at high operating rates for more than 10 years, so failure may occur anytime unexpectedly.

①Capable of measuring even extremely low levels of leakage current.

< Measurement of leakage current >

< Measurement of load current >

②Monitoring of equipment insulation degradation using Ior system

Alarm output + Current upper-/lower-limit monitoringUsing the contact output and current upper-/lower-limit monitoring function, the EcoMonitorPlus can detect abnormalities of production equipment before a problem actually occurs.

Production equipment

Insulation monitor unit (EMU4-LG1-MB)Leakage current resolution: 0.01 mA⇒Capable of measuring leakage current in equipment groups, such as motors.

Alarm output

Since leakage current (Io)is affected by the Ioc of the whole equipment, the Ior measurement is effective for insulation deterioration diagnosis.■Method of leakage current measurement(Io and Ior measurements)

When Ioc is low

When Ioc is high

Ioc fluctuates on equipment with long wiring distance or inverter devices and filters.

Ior : Leakage current (resistive leakage current) which flows due to degraded insulationIoc: Leakage current (leakage current from electrostatic capacity) which flows even if the insulation condition is soundIo : Composite leakage current of Ior and Ioc (composition of vectors)

Ioc IorIorIo Ioc

TrCapacitor Resistance

{Ioc Io

IorIoc Io Io’

Ior Ior’

Amount of chance due to insulation deterioration=

Ioc Io Io’

Ior Ior’

Amount of change in Io

Amount of change in Ior <

Amount of change in Io

Amount of change in Ior

EMU4-HM1-MB

Want to use the EcoMonitorPlus for purposes other than energy saving!

Pro

duct Lineup

FeaturesS

pecificatio

nsN

ames of P

arts andE

xternal viewE

xternal viewC

onnectio

n C

onfig

urations

Sim

plified Com

parison of EcoM

onitor Prod

Application example

Monitoring of leakage current and load current

ProblemHeat seizure occurred in the motor for equipment due to electrical leakage.

Line stopped operating, resulting in a decline of production efficiency.Repair of the motor costs several million yen!

SolutionUsing the basic unit and extension unit to set the threshold values

for electric leakage and load current, preventive maintenance/repair can be conducted before an equipment problem occurs so

that unexpected equipment shutdown can be prevented.

Motor

Split-type current sensor

Basic unit Extension unit

Control panel

GOT for visualization of load/

leakage current.

Output an alarm when the threshold

is exceeded.

What EcoMonitorPlus can do

It measures leakage current and load current for predictive monitoring of

problems due to insulation degradation or aged deterioration of motor, thus helping

prevent unexpected equipment failure.Reduction of equipment

repair expenses and improvement of production efficiency.

■Monitoring of load/leakage current in emulsification/dispersion/dissolution equipment of beverage production line.

3. Specifications

9

Pro

duc

t Li

neup

Feat

ures

Sp

ecifi

catio

nsN

ames

of P

arts

and

Ext

erna

l vie

wE

xter

nal v

iew

Co

nnec

tion

Co

nfig

urat

ions

S

impl

ified

Com

paris

on o

f Ec

oMon

itor P

rod

Item

Voltage circuit

Current circuit

Frequency

Instrument ratings

External input

specification

External output

specification

Power interruption

backup

Model

Phase wire system Single-phase 2-wire/single-phase 3-wire, 3-phase 3-wire/ three-phase 4-wire common

Single-phase 2-wire/3-phase 3-wire

Single-phase 3-wire

110V, 220V, 440V AC common (*11)110V AC (between wires 1 and 2, and wires 2 and 3),

220V AC (between wires 1 and 3)220V AC (between wires 1 and 2, and wires 2 and 3),

440V AC (between wires 1 and 3)

ーーー

ーー

ーーーーー

ー ー

ーInput signal format

Rated input voltage/current

Output signal format

Auxiliary power rating

Data update cycle Leakage current: 2 sec, resistive leakage current: 2 sec

Contact output of alarm generating statusSelect monitoring target from below.

Monitoring of current demand upper limit, monitoring of current demand lower limit

Monitoring of N-phase current demand upper limitMonitoring of line voltage upper limitMonitoring of line voltage lower limit

Monitoring of phase voltage upper limitMonitoring of phase voltage lower limit

Monitoring of power demand upper limit, monitoring of power demand lower limitMonitoring of power factor upper limit, monitoring of power factor lower limit

Monitoring of pulse conversion value upper limitMonitoring of current imbalance rate upper limitMonitoring of voltage imbalance rate upper limit

100msecNon-voltage a contact, 1 input (Select function from below)

Contact/pulse inputMonitoring of contact and measurement of

electric energy during operation (when contact is ON)

Counting of input pulse (count: 0 to 999,999)

5V DC, 7 mA

Alarm/pulse outputContact output of alarm generating status

Select monitoring target from belowLeakage current first stage alarm

Leakage current second stage alarmResistance leakage current first stage alarm

Resistance leakage current second stage alarmLimit alarm of number of first stage alarm

occurrences of leakage currentLimit alarm of number of second stage alarm

occurrences of leakage currentLimit alarm of number of first stage alarm occurrences of resistance leakage current

Limit alarm of number of second stage alarm occurrences of resistance leakage current

Alarm

35V DC 75 mA, 24V AC 75 mA (Power factor = 1)

Non-voltage a contact, 1 output (Select function from below)

Main unit tolerances (*5)

No. of measurement circuits

Consumption VA

3-phase 4-wire

110V AC:2.0VA AC220V:3.0VA

Alarm output

Contact input

Pulse input

Rated switching voltage/current

Recorded item

Plus output

Setting values, electric energy (consumption, regenerative), reactive electric energy, periodic electric energy, operating time, pulse count value, pulse conversion value, electric energy

conversion value, maximum value, minimum value (Stored in the nonvolatile memory)Compatible standard EMC: EN-61326-1:2013, Safety: EN-61010-1:2010

Operating temperature range -5℃to +55℃ (ave. daily temp. of 35℃ or lower)Operating humidity range 30% to 85%RH (no condensation)

Storage temperature range -10℃ to +60℃ (ave. daily temp. of 35℃ or lower)Altitude

Commercial-frequency withstand voltage

2,000 m or lower

Insulation resistance At the same locations as above: 10 MΩ or more (500V DC)Auxiliary power/

voltage input terminal

Input/output terminal

Current input

Between all current/voltage inputs and all auxiliary power terminals: 2,000V AC for 1 min

Pulse output of electric energySelect pulse unit from below.

0.001/0.01/0.1/1/10/100/1000/10000/100000(kWh/pulse)*6

Function

Function

Insulation Monitor ModelEMU4-LG1-MB

Specification

Measurement items

■Basic Unit

Between all current/voltage inputs, auxiliary power terminals and all contact/pulse inputs, pulse/alarm outputs, communication terminals: 2,000V AC for 1 min

A WG26-14 (single wire/stranded wires)(Single wire: φ0.41 to φ1.62 mm, Stranded wires: 0.13 to 2.0 mm2)

Single wire: AWG24-17, Stranded wires: AWG20-26 (*9)(Single wire: φ0.5 toφ1.2 mm, Stranded wires: 0.5 to 1.3 mm2)

WeightExternal dimensions (unit: mm) 37.5 (W) x 90 (H) x 94 (D) mm (excluding protruding parts)

0.2 kg

AWG26-16 (single wire/stranded wires)(Single wire: φ0.41 to φ1.29 mm, Stranded wires: 0.13 to 1.3 mm2)

Single-phase 2-wire/single-phase 3-wire, 3-phase 3-wire common

110V, 220V AC common (*1)

Energy Measuring Standard ModelEMU4-BM1-MB

Single-phase 2-wire/single-phase 3-wire, 3-phase 3-wire/ three-phase 4-wire common110V, 220V, 440V AC common (*2)

Energy Measuring High Performance ModelEMU4-HM1-MB

Minimum: 63.5V/110V AC, Maximum: 277V/480V AC (*3) Minimum: 63.5V/110V AC, Maximum: 277V/480V AC(*12)50A, 100A, 250A, 400A, 600A

(Dedicated split-type current sensor is used. All values indicate primary current values of current sensor.)5A

(Dedicated 5A current sensor is used. Current transformer (CT) is used in two-step configuration together with the 5A current sensor in order to allow a maximum primary current value setting of 30,000A) (*4)

1A(Mitsubishi ZCT is used. Primary current value of ZCT is indicated.)

110V AC (between wires 1 and 2, and wires 2 and 3), 220V AC (between wires 1 and 3)

110V AC (between wires 1 and 2, and wires 2 and 3), 220V AC (between wires 1 and 3)

220V AC (between wires 1 and 2, and wires 2 and 3), 440V AC (between wires 1 and 3)

50/60Hz (automatic frequency selection)100V – 240V AC (+10%, -15%) 50/60Hz

1 circuitFor each phase: 0.1VA (110V AC), 0.2VA (220V AC), 0.4VA (440V AC)

1 circuit

For each phase: 0.1VA (current sensor primary side)For each phase: 0.1VA (110V AC), 0.2VA (220V AC), 0.4VA (440V AC)

1 circuitFor each phase: 0.1VA (110V AC), 0.2VA (220V AC)

Current circuitVoltage circuit

Auxiliary power circuit (*10)

Current, voltage, power, reactive power, apparent power, frequency: ±1.0% (relative to rated input)

Power factor: ±3.0%Electric energy: ±2.0%(in 5 to 100%

range of rated values; power factor = 1)Reactive electric energy: ±2.5%

(in 10 to 100% range of rated values; power factor = 0)

Current, voltage, power, reactive power, apparent power, frequency: ±1.0% (relative to rated input)

Power factor: ±3.0%Electric energy: ±2.0%(in 5 to 100%

range of rated values; power factor = 1)Reactive electric energy: ±2.5% (in 10 to 100%

range of rated values; power factor = 0)Harmonic current, harmonic voltage: ±2.5%

Low sensitivity modeLeakage current Io, resistive leakage current Ior: ±2.5%

(relative to 10 to 100% of rating)Leakage current Io, resistive leakage current Ior: ±2.5 mA

(relative to 10% of rating or lower)High sensitivity mode

Leakage current Io, resistive leakage current Ior: ±2.5 mA

Current, demanded current, voltage, power, demanded power, reactive power, power factor, frequency, electric energy (regenerative, consumption), reactive electric energy(*7), current imbalance rate, voltage imbalance rate, operating time

Apparent power, periodic electric energy, harmonic current, harmonic voltage, pulse count value, pulse conversion value, electric energy conversion value

Leakage current, demanded leakage current, resistance leakage current(*8), demanded resistance leakage current(*8),

resistance leakage current difference conversion value(*8)

Between all terminals (excluding communication circuit and frame GND terminal) and external casing: 2,000V AC for 1 min

Energy Measuring Unit

Compatible wire

Operating environment

* 1 110V and 220V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 11,000V, and secondary voltage can be set between 1 and 220V). For details, see the instruction manual.

* 2 110V, 220V and 440V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 6,600V, and secondary voltage can be set between 1 and 220V). For details, see the instruction manual.

* 3 63.5V/110V – 277V/480V can be connected directly. An externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 6,600V, and secondary voltage can be set between 1 and 220V). For details, see the instruction manual.

* 4 The settable primary current when using the 5A current sensor is as follows:5A、6A、7.5A、8A、10A、12A、15A、20A、25A、30A、40A、50A、60A、75A、80A、100A、120A、150A、200A、250A、300A、400A、500A、600A、750A、800A、1000A、1200A、1500A、1600A、2000A、2500A、3000A、4000A、5000A、6000A、7500A、8000A、10000A、12000A、20000A、25000A、30000A(CT primary side can be set freely up to 30,000A. However, CT secondary side is fixed at 5A.)

* 5 Refer to the specifications of options (split-type current sensor, 5A current sensor) on page 13 for the current sensor error rates.* 6 Refer to the instruction manual for the detail on the setting of pulse unit.* 7 Measurements are conducted based on a setting other than 2-circuit measurement mode with single-phase 2-wire setting.* 8 It measures only in the case of Single-phase 2-wire, Single-phase 3-wire, 3-phase 3-wire. * 9 Recommended bar terminal: Nichihu TGV TC-1.25-11T.*10 Connected with optional units, it increases AC110V:4.5VA, AC220V:5.0VA.

Connected with display units, it increases AC110V:1.5VA, AC220V:2.0VA.*11 110V, 220V and 440V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (maximum:600V AC). For details, see the instruction manual.*12 63.5V/110V – 277V/480V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (maximum:600V AC). For details, see the instruction manual.

・Setting values・Number of alarm occurrences

・Maximum value(Stored in the nonuvolatile memory)

29

8 Eco WebServer

MDU Breaker

Ecomonitor

Power Meter

Eco Webserver

What’s e&eco-F@ctory?

Solution which enables visualization of production and energy saving to reduce production cost and energy cost

Mitsubishi Electric visualises activities to improve productivity with standard data management, and strongly supports energy conservation activity.

“Measurement/diagnosis”, “measures”, and “management” are assessed as a total life cycle, while each abundant results and know-how are linked to achieve an effect.

Energy-saving solution of e-F@ctory will be used for future management strategy more effectively.

Effect of “visible management” introduction• Compliance with Energy Conservation Law/ execution of enhanced enforcement

• Optimization of energy usage by FEMS (Factory Energy Management System)

• “Visualization” of energy-saving effect

• Permeation of energy-saving activity to organization

• Promotion of operational restructuring/ productivity improvement

Modbus RS485 & CC-Link

Communication available