ABS
ABSOLUTE
AD
ACCESS DOOR
ADJ
ADJUSTABLE
AFF
ABOVE FINISHED FLOOR
BHP
BRAKE HORSEPOWER
CONC
CONCRETE
CONN
CONNECTION
CONT
CONTINUATION
D
DRAIN
DIA
DIAMETER
DN
DOWN
DWG
DRAWING
EAT
ENTERING AIR TEMPERATURE
EF
EXHAUST FAN
ENT
ENTERING
ESP
EXTERNAL STATIC PRESSURE
EUH
ELECTRIC UNIT HEATER
F
FAHRENHEIT
FLEX
FLEXIBLE
FPM
FEET PER MINUTE
GAL
GALLONS
GPM
GALLONS PER MINUTE
HD
HEAD
HP
HORSEPOWER
L
LOUVER
LAT
LEAVING AIR TEMPERATURE
MAX
MAXIMUM
MIN
MINIMUM
N.T.S.
NOT TO SCALE
NG
NATURAL GAS
PD
PRESSURE DROP
RPBP
REDUCED PRESSURE BACKFLOW PREVENTER
SP
STATIC PRESSURE
SPEC
SPECIFICATION
STANDARD
STD
TEMP
TEMPERATURE
T STAT
THERMOSTAT
TYP
TYPICAL
V
VOLT
W
WATT
WG
WATER GAUGE
SYMBOLDESCRIPTION
EF
FFE
FINISH FLOOR ELEVATION
CP-1
CONTROL PANEL WITH DESIGNATION
AFG
ABOVE FINISH GRADE
EXHAUST FAN
DUCT OFFSET UPUP
DN DUCT OFFSET DOWN
FD
FIRE DAMPER
1. ALL SHEET METAL PLENUMS SHALL BE WRAPPED WITH DUCTWRAP. SUPPLY AIR DUCTWORK UPSTREAM
OF MECHANICAL WINTERIZATION DAMPERS SHALL BE WRAPPED WITH DUCTWRAP. SEE SPECIFICATION
FOR ADDITIONAL INSULATION REQUIREMENTS.
2. ALL DUCTWORK IS SHOWN AS FREE AREA INSIDE DIMENSIONS.
3. USE SPIN-INS WITH SCOOP AND VOLUME DAMPER, FOR ROUND TAKE OFF'S FROM SQUARE DUCT.
4. ALLOW FOR FIELD MEASURED OFFSETS OR TRANSITIONS, ELBOWS ETC.
5. FLEX DUCT SHALL NOT BE USED.
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE
CONDITIONS. IT IS INTENDED THAT A COMPLETE SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT,
APPURTENANCES, AND CONTROLS, COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL PARAMETERS
GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY CONFORMED WITH. ANY ITEMS AND LABOR REQUIRED
FOR A COMPLETE SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, AND THESE
CONTRACT DOCUMENTS SHALL BE FURNISHED WITHOUT OCCURING ANY ADDITIONAL COST TO THE OWNER.
CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE PREPARING
SHOP DRAWINGS.
2. COORDINATE EQUIPMENT AND PIPING WITH ALL OTHER DISCIPLINES AND TRADES. MAKE ALL OFFSETS AND
TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER.
3. COORDINATE THE EXACT LOCATION AND SIZE OF ALL ROOF, WALL, AND SLAB PENETRATIONS WITH THE
ARCHITECTURAL DRAWINGS.
4. MOUNT THERMOSTATS WHERE INDICATED ON PLANS, 4'-0" A.F.F. UNLESS NOTED OTHERWISE.
5. ELECTRICAL CONTRACTOR TO VERIFY CONTROL VOLTAGES WITH EQUIPMENT AND PROVIDE ACCORDINGLY.
6. FINAL CLOSEOUT SHALL INCLUDE A TWO WEEK HVAC ENDURANCE TEST.
MECHANICAL GENERAL NOTES:
DUCTWORK NOTES:
ALL SYMBOLS WHICH APPEAR WITHIN THE
LEGEND MAY NOT APPLY TO THIS PROJECT.
THIS LEGEND IS FOR REFERENCE ONLY.
ELBOW, TURNED UP
BUTTERFLY VALVE
ANCHOR, INTERMEDIATE
ELBOW, TURNED DOWN
NOTE:
T
BALL VALVE
GATE VALVE
TEE
DUCT SIZE, FIRST FIGURE IS SIDE SHOWN12x20
LOUVER AND SCREEN
GRILLE OR REGISTER, SIDEWALL
SUPPLY AIR FLOW
CONNECTION, TOP
CONNECTION, BOTTOM
CAP
DUCT TRANSITION
DUCT SECTION, POSITIVE PRESSURE
DUCT SECTION, NEGATIVE PRESSURE
TURNING VANES
NEW DUCTWORK
ALL DUCT TAPS SHALL BE PER SMACNA STANDARDS LATEST EDITION.
THERMOSTAT
MECHANICAL ABBREVIATIONSMECHANICAL LEGEND
MMOTORIZED DAMPER
CO
CO SENSOR2
2
MMASTER EMERGENCY SHUTDOWN SWITCH
RS/RL
REFRIGERANT SUCTION/LIQUID
MB
MAN BARS
SB
SECURITY BARS
AIR QUANTITY DELIVERED
BY DEVICE IN CFM
AIR TERMINAL TAG
AIR TERMINAL MARK AS
INDICATED IN SCHEDULE
250CDA
BD
BALANCING DAMPER
CW
DOMESTIC COLD WATER
SAN
SANITARY SEWER
WATER HAMMER ARRESTOR
M-001
ME
CH
AN
IC
AL
SY
MB
OLS
A
ND
AB
BR
EV
IA
TIO
NS
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.tetratech.com
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
4/20/2020 2:04:08 P
M - \\T
T.LO
CA
L\IE
R\P
RO
JE
CT
S\S
EA
TT
LE
\163931\200-163931-18001\C
AD
\S
HE
ET
FILE
S\M
-001-S
YM
BO
LS
.D
WG
- O
ST
RO
WS
KI, JE
SS
IC
A
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Copyright: T
etra T
ech
200-163931-18001
WE
LL #2 R
ELO
CA
TIO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
IL
WA
UK
IE
15350 S
W S
equoia P
kw
y, S
te 220
Portland, O
R 97224
Tel 503.684.9097
6/30/2021
40x48
32
x3
2
8X6
L-1
L-2
EF-1
EUH-1
EUH-1
SF-2
M
SF-1
SUPPORT UNIT HEATER
FROM WALL. MOUNT LOWER
THAN BOTTOM OF FILTER
BOX TO NOT INTERFERE
WITH FILTER ACCESS.
1
2
" CW
CONNECT
1
2
" CW TO
PRE-LUBRICATION
CONNECTION.
FD-2
4" SAN
4" SAN
BELOW FLOOR
4" SAN
CONNECT TO SEWER LINE.
COORDINATE INVERT WITH
CIVIL DESIGN.
FD-2
2" VENT UP TO VENT
THROUGH ROOF
BF
P
WALL CLEANOUT
1
2
2
4
T
5
FD-1
3
BACKWATER VALVE WITH
VALVE ACCESS PANEL.
WATER HAMMER
ARRESTOR
M-101
WE
LL
B
UIL
DIN
G
FL
OO
R P
LA
N
ME
CH
AN
IC
AL
FLOOR PLAN1
_
SCALE: 1/2"=1'-0"
N
2'1' 4'0
SCALE: 1/2" = 1'-0"
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.tetratech.com
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
4/17/2020 4:16:35 P
M - \\T
T.LO
CA
L\IE
R\P
RO
JE
CT
S\S
EA
TT
LE
\163931\200-163931-18001\C
AD
\S
HE
ET
FILE
S\M
101-W
ELLB
LD
G-P
LA
N.D
WG
- O
ST
RO
WS
KI, JE
SS
IC
A
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Copyright: T
etra T
ech
200-163931-18001
WE
LL #2 R
ELO
CA
TIO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
ILW
AU
KIE
15350 S
W S
equoia P
kw
y, S
te 220
Portland, O
R 97224
Tel 503.684.9097
WELL PUMP AND PIPING SHOWN FOR REFERENCE. SEE
PROCESS DRAWINGS FIG 6-2.
COORDINATE LOUVER LOCATIONS WITH ARCHITECTURAL
DRAWINGS.
PROVIDE FLOOR DRAINS AS SPECIFIED IN SECTION
221319.13 SANITARY DRAINS.
REDUCED PRESSURE BACKFLOW PREVENTER TO
PROTECT POTABLE WATER SUPPLY. REFER TO DETAIL ON
M-501. WATER LINE IS TAPPED OFF METERED WATER LINE
SERVING ADJACENT BUILDINGS.
MOUNT THERMOSTAT 48" ABOVE FLOOR AND SPACED OFF
THE MASONRY WALL AS SHOWN IN THE THERMOSTAT
MOUNTING DETAIL ON M-501.
KEYED NOTES:
1
2
3
4
5
6/30/2021
FAN SCHEDULE
TAG SERVICE TYPE DRIVE CFM
ESP
(TSP)
(IN. WG)
RPM HP VOLTS/PH/HZ
FLA
(AMPS)
WEIGHT
(LBS)
DIMENSIONS
W / H / D
(IN)
BASIS OF DESIGN MAKE
AND MODEL
NOTES
SF-1 SUPPLY FAN INLINE CENTRIFUGAL DIRECT 3000 0.7 1285 1 115/1/60 150 26 / 26 / 51 GREENHECK SQ-160-VG2, 3, 4, 5, 6
SF-2 VENTILATION SUPPLY FAN INLINE CENTRIFUGAL DIRECT 100 0.12 950 3/10 115/1/60 0.62 16 9 / 13 / 11 GREENHECK CSP-A1101, 3, 5
EF-1 EXHAUST FAN WALL PROPELLER DIRECT 3000 0.4 1750
1
2
115/1/60 9.8 80 32 / 32 / 37 GREENHECK AER-E24C-304-A3, 4, 5, 6, 7
FACTORY OPTIONS AND ACCESSORIES
1. INTEGRAL BACKDRAFT DAMPER.
2. FILTER BOX W/ 1" MERV 7 PAPER FILTERS.
3. DISCONNECT SWITCH.
4. HANGING SPRING ISOLATION KIT.
5. OSHA FAN GUARD.
6. MOTORIZED DAMPER.
7. WALL HOUSING.
ELECTRIC HEATER SCHEDULE
TAG DESCRIPTION SERVICE
PHYSICAL
DESCRIPTION
KW V/PH/HZ CFM
EAT
°F
LAT
°F
BASIS OF
DESIGN MAKE
AND MODEL
NOTES
EUH-1
ELECTRIC UNIT
HEATER
SPACE HEATING16
1
2
" X 16" X 9", 40 LB5 240/1/60 310 45 96 REZNOR EGEB
MOUNT IN VERTICAL
ORIENTATION FROM WALL.
PROVIDE WIRED
THERMOSTAT.
LOUVER SCHEDULE
TAG SERVICE DIRECTION CFM WIDTH" X HEIGHT" DEPTH
FREE
AREA
(FT²)
VELOCITY
(FPM)
DESIGN
PRESSURE DROP
(IN WC)
FINISH
BASIS OF DESIGN
MAKE AND MODEL
NOTES
L-1SF-1,2
INTAKE 3000 40" X 48" 6" 6.2 480 0.05
ALUMINIMUM, (2) COATS 70%
KYNAR 500/HYLAR 5000, AAMA
2605 - DRY FILM THICKNESS 1.2
MIL - COLOR PER ARCHITECT
GREENHECK EHH-601
AMCA-500L WIND DRIVEN RAIN RESISTANT, PROVIDE
BIRD SCREEN
L-2 EF-1 EXHAUST 3000 32" x 32" 4" 2.8 1070 0.21 GREENHECK EHH-401
AMCA-500L WIND DRIVEN RAIN RESISTANT, PROVIDE
BIRD SCREEN
M
M
M
BO - OA DAMPER OPEN/CLOSE
BO - FAN START/STOP
THERMOSTAT
AI - SPACE TEMPERATURE
AI - SPACE TEMPERATURE SETPOINT
BI - ON/OFF/AUTO
M
CONSTANT VENTILATION AND COOLING - SEQUENCE OF OPERATIONS
GENERAL: SUPPLY FAN ONE (SF-1) AND EXHAUST FAN ONE (EF-1) RUN CONSTANTLY WHEN THE SPACE TEMPERATURE IS AT OR ABOVE 85° F (ADJUSTABLE). THERE SHALL BE A 5° DEAD
BAND IN FAN OPERATION SO THAT THE FANS TURN OFF AT 80° F. THE FANS WILL SUPPLY THE ROOM WITH OUTSIDE AIR TO KEEP IT AT MOST 5° ABOVE THE OUTDOOR TEMPERATURE.
THIS WILL ALSO PROVIDE VENTILATION.
WHEN THE SPACE TEMPERATURE IS BELOW 85° F, SUPPLY FAN TWO (SF-2) WILL RUN CONSTANTLY TO PROVIDE VENTILATION TO THE SPACE. THE ELECTRIC UNIT HEATERS WILL RUN TO
MAINTAIN THE SPACE AT 45° F.
MECHANICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY CONTROL DEVICES TO EXECUTE THIS SEQUENCE OF OPERATION. CONTROL DEVICES SHALL BE WIRED BY ELECTRICAL
CONTRACTOR.
RUN CONDITIONS:
SPACE TEMPERATURE 45°< AND > 80° F:
OA DAMPER SHALL CLOSE.
EA DAMPER SHALL CLOSE.
FAN SF-2 SHALL START.
EUH'S SHALL CYCLE ON-OFF TO MAINTAIN SET POINT OF 45°F (ADJUSTABLE).
SPACE TEMPERATURE > 85° F
OA DAMPER SHALL OPEN.
EA DAMPER SHALL OPEN.
FANS SF-1 AND EF-1 SHALL START.
IF SPACE TEMPERATURE FALLS BELOW 80° F, SF-1 AND EF-1 SHALL STOP AND DAMPERS SHALL CLOSE.
SF-1
L-1 EF-1
L-2
BO - EA DAMPER OPEN/CLOSE
BO - FAN START/STOP
M
SF-2
BO - FAN START/STOP
EUH-1
PROTECTIVE SCREEN FAN
GUARD W/HINGED BACK
(NOT REQ'D FOR FANS
HAVING COMBINATION
SCREEN/MOTOR MOUNT)
BLOCK WALL
BY LOUVER MFR.
EXT. ALUM. SILL
FIXED LOUVER
EXHAUST DAMPER
METAL FRAME
SCREEN
LINTEL
BFP
FLOOR
BALL VALVE. TYPICAL
REDUCED BACKFLOW PREVENTER.
SEE SECTION 221119 - DOMESTIC
WATER PIPING SPECIALTIES
PROVIDE AIR GAP FITTING WITH
INDIRECT DRAIN TO FUNNEL ON
FLOOR SINK.
PRESSURE GAUGE
WITH COCK.
REDUCED PRESSURE
BACKFLOW PREVENTER DETAIL
NOT TO SCALE
2
WALL EXHAUST FAN
W/ DAMPER AND FIXED LOUVER
NOT TO SCALE
3
THERMOSTAT
8" X 8" PLYWOOD
STRUT RACKING
MASONRY WALL
THERMOSTAT MOUNTING DETAIL
NOT TO SCALE
1
M-501
ME
CH
AN
IC
AL
SC
HE
DU
LE
S
AN
D D
ET
AILS
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.te
tra
te
ch
.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
4/1
7/2
02
0 4
:1
8:0
5 P
M - \\T
T.L
OC
AL
\IE
R\P
RO
JE
CT
S\S
EA
TT
LE
\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\M
-5
01
-S
CH
ED
UL
ES
.D
WG
- O
ST
RO
WS
KI, JE
SS
IC
A
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra
T
ech
200-163931-18001
WE
LL
#
2 R
EL
OC
AT
IO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
IL
WA
UK
IE
15
35
0 S
W S
eq
uo
ia
P
kw
y, S
te
2
20
Po
rtla
nd
, O
R 9
72
24
Te
l 5
03
.6
84
.9
09
7
6/30/2021
LIGHTING
TB
ATS
X
XX
SCHEMATICSINGLE LINE DIAGRAM
TVSSTRANSIENT VOLTAGE SURGE
SUPRESSOR
VFD VARIABLE FREQUENCY DRIVE
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
DISCONNECT SWITCH
VALVE MOTOR AND ACTUATOR
SSS SOLID STATE STARTER
SSTSOLID STATE TRIP
CLOSED
NORMALLYNORMALLY
OPEN
O/L'S
TD
ETM
M
CONTACT
TIMED CONTACT, CONTACT ACTION
RETARDED ON ENERGIZATION (ON
DELAY)
TIMED CONTACT, CONTACT ACTION
RETARDED ON DE-ENERGIZATION
(OFF DELAY)
LEVEL SWITCH
PRESSURE SWITCH
PUSH BUTTON SINGLE CIRCUIT
LIMIT SWITCH
TEMPERATURE SWITCH
MOTOR OVERLOAD DEVICE
CONTACTS
MOTOR OVERLOAD DEVICE
PILOT LIGHT
R= RED, W= WHITE, G= GREEN, A=
AMBER
CONTROL RELAY
TIME DELAY RELAY. TIME DELAY ON
ENERGIZATION
TIME DELAY RELAY. TIME DELAY ON
DE-ENERGIZATION
STARTER COIL
SOLENOID OPERATED VALVE
ELAPSED TIME METER
FUSE
CONTROL POWER TRANSFORMER
GROUND
MOTOR SPACE HEATER
1TR1TR
1TR1TR
A
CR
TD
TDAE
TDAD
DISCONNECT SWITCH
PANELBOARD, 120/240VAC
CONDUIT BENDS AWAY FROM
OBSERVER
CONDUIT BENDS TOWARD
OBSERVER
GROUNDING CONDUCTOR 30"
BELOW GRADE
CONDUIT EXPOSED
G
SPST LIGHTING SWITCH WITH
SWITCHING CONTROL ZONE
INDICATED AS "a".
JUNCTION BOX
3-WAY SWITCH
4-WAY SWITCH
J
S
3
S
4
S
G
20
75KW
75
VS
F
(3)
(3)
POWER FACTOR
CORRECTION CAPACITOR
FUSE, RATING
DISCONNECT SWITCH "F" INDICATES
FUSED, SEE PLANS FOR RATING
COMBINATION STARTER AND
DISCONNECT SWITCH
GENERAL
M-MAGNETIC MOTOR STARTER,
C-GENERAL USE CONTACTOR
(NUMBER INDICATED NEMA SIZE)
2
EXISTING WORK TO BE REMOVED
MOTOR RATED SWITCH WITH
OVERLOAD PROTECTION AND
LOCKABLE HASP
4' SURFACE OR PENDANT-MOUNT
LINEAR LIGHTING FIXTURE.
GROUND WIRE WITH CADWELD
CONNECTION PIGTAILED 18" ABOVE
FINISHED FLOOR
2L1-1,3
PANEL AND CIRCUIT (EXAMPLE:
PANEL 2L1, CIRCUITS 1 AND 3)
CIRCUIT BREAKER 200A, 3-POLE
SHOWN
200/3
ST
CLOSE
AUTO
OPEN
PUSHBUTTON, N.O. SHOWN,
LETTERS INDICATE: A-AUTO,
DN-DOWN, FWD-FORWARD, H-HAND,
LOS-LOCK OUT STOP, O-OFF,
REV-REVERSE, ST-START, SP-STOP,
T-TEST
SELECTOR SWITCH, "A" POSITION
SHOWN. ARROW, WHEN USED,
INDICATES SPRING RETURN, X'S
AND O'S TO RIGHT OF CONTACTS,
WHEN USED, INDICATE CONTACT
DEVELOPMENT.
SPEED SWITCH, N.C. SHOWN.
CONTACT CLOSES AT PRESET
SPEED.
CALLOUT - LIGHTING FIXTURE TYPE
AND WATTAGE SEE SCHEDULE
BUS W/ CONNECTIONS
G - GROUND, N - NEUTRAL
DRAW-OUT TYPE EQUIPMENT
GENERATOR
GROUND OR EARTH CONNECTION
HEATER
THERMAL OVERLOAD
CONDUCTOR CONNECTION
WATT-HOUR METER
MOTOR W/ HORSEPOWER
INDICATED, 75HP SHOWN
RECEPTACLE - SPECIAL NEMA TYPE
AS INDICATED.
METER PHASE SELECTOR SWITCH,
VS - VOLTMETER, AS - AMMETER
TRANSFER SWITCH
POWER TRANSFORMER
CURRENT TRANSFORMER, (3)
INDICATES QUANTITY
POTENTIAL TRANSFORMER (3)
INDICATES QUANTITY
ENCLOSURE WIRING
FIELD WIRING
DEVICE A.C. SIGNALS
DEVICE D.C. SIGNALS
MCC A.C. SIGNALS
MCC D.C. SIGNALS
CONTROL PANEL A.C. SIGNALS
CONTROL PANEL D.C. SIGNALS
PHOTOELECTRIC CONTROL UNIT.
WALL MOUNTED
LIGHTING FIXTURE, OUTDOOR POLE
MOUNT
EMERGENCY BATTERY LIGHT DUAL
S
M
RECEPTACLE - DUPLEX
TERMINAL BOX
DEVICE CONNECTION
MOTOR - HP INDICATED
GENERATOR
PUSH BUTTON
GROUND ROD W/ INSPECTION WELL
EQUIPMENT CONNECTION
CONDUIT STUB
CONDUIT CONCEALED BELOW
GRADE OR FINISHED FLOOR
G
G
TRANSFORMER
AUTOMATIC TRANSFER SWITCH
NEUTRAL CONDUCTOR
GROUND CONDUCTOR
HOMERUN/CONDUIT
PHASE/SWITCHLEG CONDUCTOR
GROUND WIRE WITH CADWELD
CONNECTION
DUCT BANK, CONCRETE ENCASED,
STEEL REINFORCED
DUCT BANK, CONCRETE ENCASED
WATTHOUR/DEMAND METER
DEM
KWH
BUS CONNECTION
L6-30R
PANEL BOARD
WALL-MOUNT LIGHT - EXTERIOR
EXIT SIGN - SINGLE FACE BACK
WALL MOUNTED
a
RECEPTACLE - SPECIAL NEMA TYPE
AS INDICATED.L5-20R
RECEPTACLE MODIFIER SUBSCRIPTS:
GFCI - GROUND FAULT CIRCUIT INTERRUPTER,
GFPE - GROUND FAULT PROTECTION OF
EQUIPMENT,
WP - WEATHERPROOF COVER, WHILE IN USE
AFCI - ARC-FAULT CIRCUIT INTERRUPTER
GFI
DISCONNECT SWITCH
REACTOR OR INDUCTOR
A
HTR-1
LI
101
GENERAL
LIGHT LINE INDICATES EXISTING
ELECTRICAL OR EXISTING
EQUIPMENT. LIGHT LINE MAY ALSO
BE USED FOR DETAIL DRAWING
CLARITY.
HEAVY LINE INDICATES NEW WORK
KEY NOTE
CALLOUT - INSTRUMENT
CALLOUT - EQUIPMENT
CALLOUT - CONDUIT
(CONT'D)
GROUND ROD W/O INSPECTION
WELL
INDUCTIVE REACTOR
A, AMP AMPERE
AF AMPERE FUSE
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERES INTERRUPTING CURRENT
AIL AMBER INDICATING LIGHT
AL ALUMINUM
AS AMPERE SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BLDG BUILDING
BP BY-PASS CONTACTOR
C CONDUIT
CB CIRCUIT BREAKER
CDR CONDUCTOR
CKT CIRCUIT
CNTL CONTROL
CO CONDUIT ONLY
COMPT COMPARTMENT
CONTD CONTINUED
CR CONTROL RELAY
CT CURRENT TRANSFORMER
CU COPPER
DB DUCT BANK
DET DETAIL
DIAG DIAGRAM
DISC DISCONNECT
DP DISTRIBUTION PANEL
DWG(S) DRAWING(S)
EL ELEVATION
ELEV ELEVATOR
EMER EMERGENCY
EPR ETHYLENE-PROPLYENE RUBBER
EQUIP EQUIPMENT
ETM ELAPSED TIME METER
FDR FEEDER
FV FRONT VIEW
GEN GENERATOR
GCFI GROUND-FAULT CIRCUIT INTERRUPTER
GRI GROUND FAULT INTERRUPTING
GFP GROUND-FAULT PROTECTION OF
EQUIPMENT
GIL GREEN INDICATING LIGHTING
GND GROUND
GRC GALVANIZED RIGID CONDUIT
ABBREVIATIONS
ABBREVIATIONS (CONT'D)
HH HANDHOLE
HOA HAND-OFF-AUTO
HTR HEATER
HZ HERTZ
I/O INPUT/OUTPUT
IC ISOLATION CONTACATOR
IG ISOLATED GROUND
INST INSTANTANEOUS
INTLK INTERLOCK
IPB ILLUMINATED PUSHBUTTON
J JUNCTION BOX
KCMIL THOUSAND CIRCUILAR MILS
KV KILOVOLTS
KVA KILOVOLT-AMPERES
KVAR KILOVARS
KW KILOWATTS
KWH KILOWATT HOUR
LS LEVEL SWITCH
LSH LEVEL SWITCH HIGH
LT LEVEL TRANSMITTER
LTFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT
LTG LIGHTING
LV LOW VOLTAGE
mA MILLIAMPERES
MAN MANUAL
MCC MOTOR CONTROL CENTER
MH MANHOLE
MPZ MINI POWER ZONE
MTR, M MOTOR
MTS MANUAL TRANSFER SWITCH
mV MILLIVOLTS
NA NON-AUTO
NC NORMALLY CLOSED
NF NON-FUSED
NO NORMALLY OPEN
NP NAMEPLATE
NTS NOT TO SCALE
OL OVERLOAD
PC PHOTOELECTRIC CELL
PH, Ø PHASE
PNL PANEL
PR SHIELDED PAIR
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
REF REFERENCE
REC RECEPTACLE
RIL RED INDICATING LIGHT
RTD RESISTANCE TEMPERATURE DETECTOR
S, SEC SECOND
SEL SELECTOR
SER SERVICE ENTRANCE RATED
SPEC SPECIFICATION
SS STAINLESS STEEL
SSS SOLID STATE SOFT START
STA STATION
SW SWITCH
SWBD SWTICHBOARD
SWGR SWITCHGEAR
TB TERMINAL BOX, TERMINAL BLOCK
TOA TEST-OFF-AUTOI
TSP TWISTED SHIELDED PAIR
TST TWISTED SHIELDED TRIAD
TYP TYPICAL
UP UTILITY POWER
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
W WIRE, WATTS
W/ WITH
W/O WITHOUT
WIL WHITE INDICATING LIGHTING
WP WEATHERPROOF
XFMR TRANSFORMER
XLP CROSS-LINKED POLYETHYLENE
XP EXPLOSION-PROOF
ZS POSITION SWITCH
WH
SERVICE ENTRANCE
PANEL
A
UTILITY
FLEXIBLE CORD OR CABLE
FLEXIBLE CONDUIT
1
HANDHOLEHH
PULLBOX
MANHOLE (SEE LAYOUT DETAILS)MH01
XX ASW
XX AFU
FUSED SWITCH
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.te
tra
te
ch
.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
5/1
/2
02
0 1
2:5
2:3
7 P
M - \\T
TS
00
7F
S2
\IE
W\P
RO
JE
CT
S\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\E
-0
01
-E
LE
CT
RIC
AL
S
YM
BO
LS
A
ND
A
BB
RE
VIA
TIO
NS
.D
WG
- F
OR
TY
GIN
, K
IR
IL
L
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra
T
ech
200-163931-18001
WE
LL
#
2 R
EL
OC
AT
IO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
ILW
AU
KIE
15
35
0 S
W S
eq
uo
ia
P
kw
y, S
te
2
20
Po
rtla
nd
, O
R 9
72
24
Te
l 5
03
.6
84
.9
09
7
O:\P
ro
je
cts\S
ea
ttle
\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\M
od
elF
ile
s\Im
ag
es\M
ilw
au
kie
-L
og
o-G
ra
ysca
le
-3
00
.jp
g
E-001
EL
EC
TR
IC
AL
S
YM
BO
LS
AN
D A
BB
RE
VIA
TIO
NS
KAF
JAR
R
E
G
I
S
T
E
R
E
D
PRO
F
E
S
S
I
O
N
A
L
E
C
I
R
.A
N
H
O
J
E
N
G
I N
E
E
R
M
A
Y
9,
2
0
1
7
OREGON
48239PE
EXPIRES: 12/31/2020
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
xx
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
xx
x
x
x
xx
xx
xx
xx
x
x
x
SE
40T
H A
VE
.
FIRE
STATION
WELL #3
WATER
TREATMENT
FACILITY
1.5 MG
CONCRETE
RESERVOIR
WELL #2
BLDG.
PUBLIC
WORKS
BLDG.
PUBLIC
WORKS
BLDG.
CONCRETE
DRIVEWAY
J
J
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.te
tra
te
ch
.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
5/1
/2
02
0 1
2:5
3:1
2 P
M - \\T
TS
00
7F
S2
\IE
W\P
RO
JE
CT
S\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\E
-1
00
-E
LE
CT
RIC
AL
S
IT
E P
LA
N.D
WG
- F
OR
TY
GIN
, K
IR
IL
L
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra
T
ech
200-163931-18001
WE
LL
#
2 R
EL
OC
AT
IO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
ILW
AU
KIE
15
35
0 S
W S
eq
uo
ia
P
kw
y, S
te
2
20
Po
rtla
nd
, O
R 9
72
24
Te
l 5
03
.6
84
.9
09
7
O:\P
ro
je
cts\S
ea
ttle
\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\M
od
elF
ile
s\Im
ag
es\M
ilw
au
kie
-L
og
o-G
ra
ysca
le
-3
00
.jp
g
E-100
EL
EC
TR
IC
AL
S
IT
E P
LA
N
KAF
JAR
20'10' 40'0
SCALE: 1" = 20'
ELECTRICAL SITE PLAN1
_
SCALE: 1"=20'"
N
1
E-101
SE HARVEY ST.
PAVEMENT EDGE
KEYED NOTES:
COORDINATE CONDUIT ENTRANCE BETWEEN ROLL UP DOOR AND
PEDESTRIAN DOOR LOCATIONS.
REPLACE EXISTING MANUAL TRANSFER SWITCH. EXTEND CONDUIT AS
NEEDED FOR MTS.
PROVIDE CONDUIT AND WIRING BETWEEN THE MTS AND THE LOCAL
PROCESS PANEL. 4#16 FOR MONITORING SOURCE AVAILABILITY, 6#16 FOR
MONITORING MTS STATE.
PROVIDE CONDUIT AND WIRING BETWEEN MTS AND THE ON-BOARD
GENERATOR CONTROLS. FOR REMOTE START.
PROVIDE CONDUCTORS BETWEEN MTS AND GENERATOR DISCONNECT.
PROVIDE CONDUCTORS BETWEEN MTS AND BUS GUTTER.
PROVIDE CONDUCTORS BETWEEN MTS AND MAIN SERVICE DISCONNECT
(CIRCUIT BREAKER).
PROVIDE SPARE CONDUITS FROM FLUSH WITH FLOOR IN WELL #2
BUILDING TO PUBLIC WORKS WELL BUILDING. PROVIDE LB FITTING TO
STUB AND CAP SPARE CONDUITS INTO PUBLIC WORKS BUILDING.
2
E-501
2
E-500
2
E-500
3/4"-10#16+#12G
3/4"-2#16+#12G
NOTES:
1. FIELD VERIFY LOCATIONS OF EXISTING EQUIPMENT AND ROUTING
DISTANCES IN WELL #2 BUILDING.
BUS GUTTER
MTS
GENERATOR
DISCONNECT
MAIN SERVICE
CIRCUIT BEAKER
2
E-101
3
E-101
3
1
2
3
4
5
6
7
6
2
7
4
5
R
E
G
I
S
T
E
R
E
D
PRO
F
E
S
S
I
O
N
A
L
E
C
I
R
.A
N
H
O
J
E
N
G
I N
E
E
R
M
A
Y
9,
2
0
1
7
OREGON
48239PE
EXPIRES: 12/31/2020
(2) 2 "C
(2) 1"C
8
1
8
8
40x48
32x32
8X6
M
VFDTERMINAL CABINET
1/2
GF
CI
1
3/10
TO EXISTING BUS GUTTER
IN WELL #2 BUILDING
SEE SHEET E-100
2#10,1#10N+#12G
2#10,1#10N, 1#12G
75
2#1,1#8G
MPZ-9
5, 7
1, 3
2, 4
6
10,12
MPZ-15,17
SAND SEPARATOR
PURGE VALVE
CONTROLLER
REMOVABLE
ROOF
S
M
S
M
S
M
3#4, #8G
EUH-2
EF-1
SF-2
EUH-1
MPZ
J
SF-1
6#12,1#12G
2#12+G
2#12+G
3#4,#8G
MAGNETIC
FLOW METER
3/4"C, 2#12,1#12G
8
15
GF
CI
J
17
J
J
14
14
30/2P
30/2P
2#12+G
LIT-1
MINI POWER ZONE
JUNCTION BOX
VFD
TERMINAL
CABINET
TO EXISTING
WELL #2
BUILDING.
DISCONNECT
EUH-2MPZ
VFDTERMINAL CABINET
SAND SEPARATOR
PURGE VALVE
CONTROLLER
SAND SEPARATOR
PURGE VALVE
TO EXISTING PLANT
CONTROL PANEL
1"C-12#16,1#12G
1"C-SPARE
1"C-12#16
REMOVABLE
ROOF
MPZ
LEVEL
TRANSDUCER,
TERMINAL BOX AND
DISPLAY (LIT-1)
3/4"C-TSP#16
1"C-SENSOR
CABLE
MAGNETIC
FLOW METER
3/4"C-TSP#16
S
VFDTERMINAL CABINET
13
11
13
11
A
40
G G G
(TYP)
B
25
11
11
J
L5-20RL5-20R
11
REMOVABLE
ROOF
GG
MPZ
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.te
tra
te
ch
.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
5/1
/2
02
0 1
2:5
3:1
8 P
M - \\T
TS
00
7F
S2
\IE
W\P
RO
JE
CT
S\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\E
-1
01
-W
EL
L B
UIL
DIN
G E
LE
CT
RIC
AL
P
LA
N.D
WG
- F
OR
TY
GIN
, K
IR
IL
L
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra
T
ech
200-163931-18001
WE
LL
#
2 R
EL
OC
AT
IO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
ILW
AU
KIE
15
35
0 S
W S
eq
uo
ia
P
kw
y, S
te
2
20
Po
rtla
nd
, O
R 9
72
24
Te
l 5
03
.6
84
.9
09
7
O:\P
ro
je
cts\S
ea
ttle
\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\M
od
elF
ile
s\Im
ag
es\M
ilw
au
kie
-L
og
o-G
ra
ysca
le
-3
00
.jp
g
E-101
WE
LL
B
UIL
DIN
G
EL
EC
TR
IC
AL
P
LA
N
KAF
JAR
4'2' 8'0
SCALE: 1/4" = 1'-0"
WELL BUILDING POWER PLAN1
_
SCALE: 1/4"=1'-0"
N
WELL BUILDING POWER PANEL SECTION4
_
SCALE: 1/4"=1'-0"
WELL BUILDING CONTROL PLAN3
_
SCALE: 1/4"=1'-0"
N
WELL BUILDING LIGHTING AND GROUNDING PLAN2
_
SCALE: 1/4"=1'-0"
N
3
E-501
1
E-501
KEYED NOTES:
1. ALL CONDUITS WITHIN THE WELL BUILDING SHALL BE SURFACE
MOUNTED GRC.
2. BELOW GRADE PVC CONDUIT, WITH GRS ELBOWS & RISERS TO ABOVE
FINISHED FLOOR.
1 1
2
E-500
2
E-500
1
E-100
2
R
E
G
I
S
T
E
R
E
D
PRO
F
E
S
S
I
O
N
A
L
E
C
I
R
.A
N
H
O
J
E
N
G
I N
E
E
R
M
A
Y
9,
2
0
1
7
OREGON
48239PE
EXPIRES: 12/31/2020
4
KEYED NOTES:
PROVIDE SINGLE RECEPTACLE WITH MATCHING PLUG. LOCATE
RECEPTACLE ABOVE BOTTOM CORD OF TRUSS. RECEPTACLE WILL ALLOW
FOR REMOVAL OF LIGHT FIXTURES WHEN ROOF IS REMOVED.
TAP FOR VFD AND MPZ MADE IN JUNCTION BOX.
PROVIDE CONDUIT STUB UP TO MAGNETIC FLOW METER. TRANSITION TO
LIQUID TIGHT FLEX CONDUIT AT MAGNETIC FLOW METER.
TERMINATE SPARE CONDUIT FLUSH AT FLOOR W/ COUPLING AND BRASS
PLUG BELOW TERMINAL CABINET.
TERMINATE SPARE CONDUIT FLUSH AT FLOOR W/ COUPLING AND BRASS
PLUG BELOW JUNCTION BOX.
PROVIDE A JUNCTION BOX WITH 120VAC POWER FOR MOTORIZED
DAMPER. COORDINATE MOTORIZED DAMPER CONNECTION WITH SHEET
M-501.
COORDINATE WITH MECHANICAL, WHICH IS SUPPLYING THE LEVEL
TRANSDUCER AND SUPPORTING POWER SUPPLY, TERMINAL BOX, AND
DISPLAY MODULE. SEE SECTIONS 33 21 00 FOR ADDITIONAL INFORMATION.
1
2
3
4
3
45
5
5
6
6
6
(TYP)
7
7
4
E-101
EXISTING WELL 2 BUILDING PUMP CONTROL EQUIPMENT DEMO1
_
SCALE: NONE
WELL# 2 SOFT START
PLANT CONTROL
PANEL
EXISTING WELL 2 BUILDING MODIFICATIONS2
_
SCALE: NONE
MANUAL TRANSFER
SWITCH
TO MAIN BREAKER
TO GENERATOR
ROOM DISCONNECT
TO BUS GUTTER
BUS GUTTER
4
4
4
4
3
1
PLANT CONTROL
PANEL
TO MAIN BREAKER
TO GENERATOR
ROOM DISCONNECT
BUS GUTTER
4
4
3
2
TO NEW WELL#2 BUILDING
PROVIDE MANUAL
TRANSFER SWITCH
PROVIDE DISCONNECT TO
NEW WELL#2 BUILDING
SEE E-100 FOR CONDUIT
SIZE AND CONTENTS
PLANT CONTROL PANEL
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.te
tra
te
ch
.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
5/1
/2
02
0 1
2:5
3:4
8 P
M - \\T
TS
00
7F
S2
\IE
W\P
RO
JE
CT
S\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\E
-5
00
-E
LE
CT
RIC
AL
D
ET
AIL
S.D
WG
- F
OR
TY
GIN
, K
IR
IL
L
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra
T
ech
200-163931-18001
WE
LL
#
2 R
EL
OC
AT
IO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
ILW
AU
KIE
15
35
0 S
W S
eq
uo
ia
P
kw
y, S
te
2
20
Po
rtla
nd
, O
R 9
72
24
Te
l 5
03
.6
84
.9
09
7
E-500
EL
EC
TR
IC
AL
D
ET
AIL
S
KAF
JAR
KEYED NOTES:
REMOVE SOFT START AND EXTEND CONTROL CIRCUIT TO NEW WELL#2
BUILDING AND VFD.
PROVIDE FUSED DISCONNECT AND CIRCUIT TO NEW WELL#2 BUILDING.
EXTEND CONTROL CONDUCTORS TO NEW WELL#2 BUILDING TERMINATION
CABINET.
REPLACE EXISTING MANUAL TRANSFER SWITCH. REPLACE CONDUCTORS
BETWEEN MTS AND GENERATOR ROOM. REPLACE CONDUCTORS
BETWEEN MTS AND BUS GUTTER. REPLACE CONDUCTORS BETWEEN MTS
AND MAIN SERVICE CIRCUIT BREAKER. SEE SHEET E-600 FOR SIZING.
MODIFY PORTIONS OF EXISTING RACEWAY AS REQUIRED FOR INTERFACE
WITH NEW EQUIPMENT.
1
2
3
4
R
E
G
I
S
T
E
R
E
D
PRO
F
E
S
S
I
O
N
A
L
E
C
I
R
.A
N
H
O
J
E
N
G
I N
E
E
R
M
A
Y
9,
2
0
1
7
OREGON
48239PE
EXPIRES: 12/31/2020
TERMINAL
CABINET
LOCKABLE HANDLEHINGED COVER
24 TERMINAL
BLOCKS
DIN RAIL
TO EXISTING
WELL 2 PLANT
CONTROL
PANEL
TERMINAL CABINET COVER TERMINAL CABINET INTERIOR
12" X 12" NEMA 12 BOX
TO WELL 2
VFD IN NEW
WELL#2
BUILDING
TO WELL 2
VFD IN NEW
WELL#2
BUILDING
TO EXISTING
WELL 2 PLANT
CONTROL
PANEL
NAMEPLATE
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.te
tra
te
ch
.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
5/1
/2
02
0 1
2:5
4:1
6 P
M - \\T
TS
00
7F
S2
\IE
W\P
RO
JE
CT
S\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\E
-5
01
-C
ON
TR
OL
P
AN
EL
D
ET
AIL
.D
WG
- F
OR
TY
GIN
, K
IR
IL
L
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra
T
ech
200-163931-18001
WE
LL
#
2 R
EL
OC
AT
IO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
ILW
AU
KIE
15
35
0 S
W S
eq
uo
ia
P
kw
y, S
te
2
20
Po
rtla
nd
, O
R 9
72
24
Te
l 5
03
.6
84
.9
09
7
E-501
TE
RM
IN
AL
C
AB
IN
ET
KAF
JAR
R
E
G
I
S
T
E
R
E
D
PRO
F
E
S
S
I
O
N
A
L
E
C
I
R
.A
N
H
O
J
E
N
G
I N
E
E
R
M
A
Y
9,
2
0
1
7
OREGON
48239PE
EXPIRES: 12/31/2020
REMOVABLE ROD CLAMP
3/4" COPPER-CLAD STEEL
SECTIONAL GROUND ROD
(10' LENGTH MINIMUM)
GROUND ROD WITH
INSPECTION WELL DETAIL1
_
SCALE: NONE
12" DIAMETER CONCRETE
INSPECTION WELL WITH CAST
IRON COVER
FINISHED GRADE BACKFILL AND SUB-SURFACE
3" MIN FINE
SAND (TYP)
SELECT NATIVE MATERIAL
PASSING NO. 8 SEEVE OR
SAND (TYP)
TYPICAL DUCT-BANK
FEATURES2
_
SCALE: NONE
1. PROVIDE 24" MINIMUM COVER FOR
BRANCH CIRCUITS AND CONTROL
CONDUIT.
2. PROVIDE SCHED-80 PVC FOR
CONDUITS.
3. RISER AND SWEEPS SHALL BE GRC
GRC 24" LR-ELBOWS.
4. ALL BACKFILL COMPACTED TO 95% OR
GREATER.
NOTES:
12"
12" MIN
TERMINAL CABINET DETAIL3
_
SCALE: NONE
DETECTABLE
WARNING TAPE
3" MIN
SAWCUT PRIOR TO EXCAVATION,
RESTORE FINISHES UPON
COMPLETION OF WORK. SEE CIVIL.
PG-E
400/3
300AT
(SER)
400/3
200 ASW
200AFU
400 ASW
255 AFU
WH
22
PANEL
B
PANEL
A
20
TRANSFER
PUMP 2
20
TRANSFER
PUMP 1
50
WELL
PUMP #2
ETM
SSS
HOA
BUS GUTTER
WELL
PUMP #2
VFD
75
200/3
WH
MH
PANEL
A
60
WELL
PUMP #3
SSS
HOA
ETM
WH
150/3
MTS# 3MTS# 2
MTS# 1
400A-3P
WIREWAY
MCC
15KVA
480:120/
240VAC
X
CL2
PUMP
X
BLOWER
1
BLOWER
2
X X
BLOWER
3
X
PUMP
1
X
PUMP
2
X
PUMP
3
X
SUMP
PUMP
15KVA
480:120/
240VAC
DIST
DP
100A
SSSSSS SSS
30/3
20AF
PGE #
31021677
WIREWAY
PGE #
31043398
WH
PGE #
31009777
PGE #
31002672
PANEL
A
PANEL
D
PANEL
B
SPARE
120/240
STANDBY
EXISTING WELL #2 BUILDING
PAD-MOUNTED UTILITY
TRANSFORMER
480/277V SECONDARY
OLD FIREHOUSE BUILDINGEXISTING WELL #3 BUILDING TREATMENT BUILDING (BLDG 3800)
3
(3) #250MCM, #4G
(3) #250MCM, G
(3) #3/0+#6G
STANDBY
GENSET
250KW/313KVA
480/277V
MTS# 1
400A-3P
(3) #250MCM, G
NEW WELL #2 BUILDING
(3) #3/0
(3) #250MCM,
#4G
100/2
2"C, (3) 3/0AWG, #6G
G
NEW WELL #2 BUILDING
G
G
#4G
JUNCTION BOX
WATER
PIPE
BUILDING
STEEL
25KVA
480V:120/240V
MPZ
480V, 3-PH, 3-W
GROUND
RODS
200 ASW
200AFU
2"C, (3) 3/0AWG, #6G
2"C, SPARE
100 ASW
45 AFU
100 ASW
45 AFU
100 ASW
45 AFU
1-1/4" C,
(2)#2AWG,
#8G
1-1/2" C, (3)
#1AWG,#6G
225/3
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.tetra
tech.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
5/1
/2
02
0 1
:3
9:59
P
M - \\T
TS
007F
S2\IE
W\P
RO
JE
CT
S\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\E
-6
00
-E
LE
CT
RIC
AL O
NE
LIN
E D
IA
GR
AM
.D
WG
- F
OR
TY
GIN
, K
IR
ILL
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra T
ech
200-163931-18001
WE
LL
#2 R
ELO
CA
TIO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
IL
WA
UK
IE
15
350
S
W S
equo
ia
P
kw
y, S
te 22
0
Portland, O
R 972
24
Tel 503.68
4.9
097
E-600
EL
EC
TR
IC
AL
ON
EL
IN
E D
IA
GR
AM
KAF
JAR
NOTES:
1. ONELINE OF EXISTING SITE CONDITIONS BASED OFF OF BEST
AVAILABLE INFORMATION, FIELD OBSERVATION, AND EXISTING SITE
DRAWINGS.
KEYED NOTES:
SWITCH LOCATED IN EXISTING WELL#2 BUILDING. PROVIDE RK-5 FUSES.
NEW WELL PUMP AND MOTOR.
PROVIDE CIRCUIT BREAKER AS RECOMMENDED BY THE MANUFACTURER,
SIZE SHOWN IS ESTIMATED SIZE. UPDATE RECORD DOCUMENTS DURING
CLOSE OUT OF PROJECT.
PROVIDE "SERVICE DISCONNECT" LABELS.
PROVIDE GROUND CONNECTION TO MPZ XO TERMINAL. (DERIVED SOURCE)
VERIFY AVAILABLE SHORT CIRCUIT CURRENT AT MTS#1 AND PROVIDE
EQUIPMENT WITH A RATING TO WITHSTAND AND/OR OPERATE UNDER THE
AVAILABLE FAULT CURRENTS.
1
2
2
R
E
G
I
S
T
E
R
E
D
PR
O
F
E
S
S
I
O
N
A
L
E
C
I
R
.
A
N
H
O
J
E
N
G
I N
E
E
R
M
A
Y
9,
2
0
1
7
OREGON
48239PE
EXPIRES: 12/31/2020
1
3
3
4
4
5
4
5
6
6
6
6
6
Checked By:
Drawn By:
Project No.:
Designed By:
ww
w.te
tra
te
ch
.co
m
MA
RK
DA
TE
DE
SC
RIP
TIO
NB
Y
5/1
/2
02
0 1
2:5
5:4
6 P
M - \\T
TS
00
7F
S2
\IE
W\P
RO
JE
CT
S\1
63
93
1\2
00
-1
63
93
1-1
80
01
\C
AD
\S
HE
ET
FIL
ES
\E
-6
02
-E
LE
CT
RIC
AL
S
CH
ED
UL
E.D
WG
- F
OR
TY
GIN
, K
IR
IL
L
1
A
B
C
D
E
F
2 3 4 5 6 7
Bar Measures 1 inch
Co
pyrig
ht: T
etra
T
ech
200-163931-18001
WE
LL
#
2 R
EL
OC
AT
IO
N
AN
D C
ON
ST
RU
CT
IO
N
CIT
Y O
F M
ILW
AU
KIE
15
35
0 S
W S
eq
uo
ia
P
kw
y, S
te
2
20
Po
rtla
nd
, O
R 9
72
24
Te
l 5
03
.6
84
.9
09
7
E-601
EL
EC
TR
IC
AL
SC
HE
DU
LE
KAF
JAR
KEYED NOTES:
EXISTING BUILDING LOAD BASED OFF OF CALCULATION USING THE
12-MONTH UTILITY MAX-DEMAND.