    Air System Sizing Summary for 1.CHILDREN PLAYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 1.CHILDREN PLAY

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1905.2 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 13.3 Tons  Total coil load 159.1 MBH  Sensible coil load 125.7 MBH  Coil CFM at Jul 1500 6748 CFM  Max block CFM 6748 CFM  Sum of peak zone CFM 6748 CFM  Sensible heat ratio 0.790

      ft²/Ton 143.7

      BTU/(hr-ft²) 83.5

      Water flow @ 10.0 °F rise 31.83 gpm

    Load occurs at Jul 1500

    OA DB / WB 107.0 / 75.0 °FEntering DB / WB 77.2 / 66.5 °FLeaving DB / WB 59.9 / 58.9 °FCoil ADP 58.0 °FBypass Factor 0.100Resulting RH 66 %Design supply temp. 58.0 °FZone T-stat Check 0 of 1 OKMax zone temperature deviation 0.1 °F

    Central Heating Coil Sizing Data  Max coil load 23.7 MBH  Coil CFM at Des Htg 6748 CFM  Max coil CFM 6748 CFM  Water flow @ 20.0 °F drop 2.37 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 12.4

    Ent. DB / Lvg DB 68.3 / 71.6 °F

    Supply Fan Sizing Data  Actual max CFM 6748 CFM  Standard CFM 6744 CFM  Actual max CFM/ft² 3.54 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 795 CFM  CFM/ft² 0.42 CFM/ft²

    CFM/person 11.20 CFM/person

    Hourly Analysis Program v4.80 Page 1 of 78

  • 8/18/2019 Load Calculation System Design Report

    2/78

    Zone Sizing Summary for 1.CHILDREN PLAYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 1.CHILDREN PLAY

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1905.2 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 99.1 6748 6748 Jul 1400 9.7 1905.2 3.54

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      1.CHILDREN PLAY 1 99.1 Jul 1400 6748 9.7 1905.2 3.54

    Hourly Analysis Program v4.80 Page 2 of 78

  • 8/18/2019 Load Calculation System Design Report

    3/78

    Air System Design Load Summary for 1.CHILDREN PLAYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 107.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 97 ft² 1437 - 97 ft² - -

    Wall Transmission 1657 ft² 5139 - 1657 ft² 2331 -

    Roof Transmission 1905 ft² 40602 - 1905 ft² 6879 -

    Window Transmission 97 ft² 1046 - 97 ft² 518 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 312 ft² 557 - 312 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1912 W 6522 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 4000 W 13648 - 0 0 -

    People 71 20955 32294 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 8991 1615 0% 0 0

    >> Total Zone Loads - 98897 33908 - 9729 0

    Zone Conditioning - 96710 33908 - 9704 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 6748 CFM 0 - 6748 CFM 0 -

    Ventilation Load 795 CFM 29005 -572 795 CFM 13950 0

    Supply Fan Load 6748 CFM 0 - 6748 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 125714 33336 - 23654 0

    Central Cooling Coil - 125714 33344 - 0 0

    Central Heating Coil - 0 - - 23654 ->> Total Conditioning - 125714 33344 - 23654 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 3 of 78

  • 8/18/2019 Load Calculation System Design Report

    4/78

    Zone Design Load Summary for 1.CHILDREN PLAYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 97 ft² 1119 - 97 ft² - -

    Wall Transmission 1657 ft² 5107 - 1657 ft² 2331 -

    Roof Transmission 1905 ft² 41128 - 1905 ft² 6879 -

    Window Transmission 97 ft² 1028 - 97 ft² 518 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 312 ft² 551 - 312 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1912 W 6522 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 4000 W 13648 - 0 0 -

    People 71 20955 32294 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 9006 1615 0% 0 0

    >> Total Zone Loads - 99063 33908 - 9729 0

    Hourly Analysis Program v4.80 Page 4 of 7

  • 8/18/2019 Load Calculation System Design Report

    5/78

    System Psychrometrics for 1.CHILDREN PLAYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    July DESIGN COOLING DAY, 1500

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 107.0 0.01129 795 400 29005 -572

    Vent - Return Mixing Outlet 77.2 0.01143 6748 1880 - -

    Central Cooling Coil Outlet 59.9 0.01038 6748 1880 125714 33344

    Central Heating Coil Outlet 59.9 0.01038 6748 1880 0 -

    Supply Fan Outlet 59.9 0.01038 6748 1880 0 -

    Cold Supply Duct Outlet 59.9 0.01038 6748 1880 - -

    Zone Air - 73.2 0.01144 6748 2077 96710 33908

    Return Plenum Outlet 73.2 0.01144 6748 2077 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 98897 Cooling 96710 73.2 6748 2077 0 0

    Hourly Analysis Program v4.80 Page 5 of 7

  • 8/18/2019 Load Calculation System Design Report

    6/78

    System Psychrometrics for 1.CHILDREN PLAYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 795 400 -13950 0

    Vent - Return Mixing Outlet 68.3 0.00441 6748 469 - -

    Central Cooling Coil Outlet 68.3 0.00441 6748 469 0 0

    Central Heating Coil Outlet 71.6 0.00441 6748 469 23654 -

    Supply Fan Outlet 71.6 0.00441 6748 469 0 -

    Cold Supply Duct Outlet 71.6 0.00441 6748 469 - -

    Zone Air - 70.3 0.00441 6748 478 -9704 0

    Return Plenum Outlet 70.3 0.00441 6748 478 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -9729 Deadband -9704 70.3 6748 478 0 0

    Hourly Analysis Program v4.80 Page 6 of 7

  • 8/18/2019 Load Calculation System Design Report

    7/78

    Air System Sizing Summary for 2.ENTRANCE LOBBYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 2.ENTRANCE LOBBY

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1659.8 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 5.1 Tons  Total coil load 61.8 MBH  Sensible coil load 57.8 MBH  Coil CFM at Aug 1400 3603 CFM  Max block CFM 3603 CFM  Sum of peak zone CFM 3603 CFM  Sensible heat ratio 0.936

      ft²/Ton 322.3

      BTU/(hr-ft²) 37.2

      Water flow @ 10.0 °F rise 12.36 gpm

    Load occurs at Aug 1400

    OA DB / WB 106.5 / 74.9 °FEntering DB / WB 74.4 / 64.2 °FLeaving DB / WB 59.5 / 58.5 °FCoil ADP 57.9 °FBypass Factor 0.100Resulting RH 61 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 9.4 MBH  Coil CFM at Des Htg 3603 CFM  Max coil CFM 3603 CFM  Water flow @ 20.0 °F drop 0.94 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 5.7

    Ent. DB / Lvg DB 69.2 / 71.6 °F

    Supply Fan Sizing Data  Actual max CFM 3603 CFM  Standard CFM 3601 CFM  Actual max CFM/ft² 2.17 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 180 CFM  CFM/ft² 0.11 CFM/ft²

    CFM/person 11.98 CFM/person

    Hourly Analysis Program v4.80 Page 7 of 7

  • 8/18/2019 Load Calculation System Design Report

    8/78

    Zone Sizing Summary for 2.ENTRANCE LOBBYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 2.ENTRANCE LOBBY

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1659.8 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 52.9 3603 3603 Jul 1400 6.3 1659.8 2.17

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      2.ENTRANCE LOBBY 1 52.9 Jul 1400 3603 6.3 1659.8 2.17

    Hourly Analysis Program v4.80 Page 8 of 7

  • 8/18/2019 Load Calculation System Design Report

    9/78

    Air System Design Load Summary for 2.ENTRANCE LOBBYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 201 ft² 583 - 201 ft² 283 -

    Roof Transmission 1660 ft² 35278 - 1660 ft² 5993 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 1528 ft² 2699 - 1528 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1542 W 5261 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 15 3675 3076 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 4750 154 0% 0 0

    >> Total Zone Loads - 52246 3230 - 6276 0

    Zone Conditioning - 51272 3230 - 6282 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 3603 CFM 0 - 3603 CFM 0 -

    Ventilation Load 180 CFM 6551 734 180 CFM 3101 0

    Supply Fan Load 3603 CFM 0 - 3603 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 57823 3964 - 9383 0

    Central Cooling Coil - 57823 3969 - 0 0

    Central Heating Coil - 0 - - 9383 ->> Total Conditioning - 57823 3969 - 9383 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 9 of 78

  • 8/18/2019 Load Calculation System Design Report

    10/78

    Zone Design Load Summary for 2.ENTRANCE LOBBYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 201 ft² 619 - 201 ft² 283 -

    Roof Transmission 1660 ft² 35830 - 1660 ft² 5993 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 1528 ft² 2699 - 1528 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1542 W 5261 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 15 3675 3076 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 4808 154 0% 0 0

    >> Total Zone Loads - 52892 3230 - 6276 0

    Hourly Analysis Program v4.80 Page 10 of 78

  • 8/18/2019 Load Calculation System Design Report

    11/78

    System Psychrometrics for 2.ENTRANCE LOBBYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    August DESIGN COOLING DAY, 1400

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 106.5 0.01129 180 400 6551 734

    Vent - Return Mixing Outlet 74.4 0.01047 3603 1153 - -

    Central Cooling Coil Outlet 59.5 0.01024 3603 1153 57823 3969

    Central Heating Coil Outlet 59.5 0.01024 3603 1153 0 -

    Supply Fan Outlet 59.5 0.01024 3603 1153 0 -

    Cold Supply Duct Outlet 59.5 0.01024 3603 1153 - -

    Zone Air - 72.7 0.01043 3603 1193 51272 3230

    Return Plenum Outlet 72.7 0.01043 3603 1193 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 52246 Cooling 51272 72.7 3603 1193 0 0

    Hourly Analysis Program v4.80 Page 11 of 78

  • 8/18/2019 Load Calculation System Design Report

    12/78

    System Psychrometrics for 2.ENTRANCE LOBBYProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 180 400 -3101 0

    Vent - Return Mixing Outlet 69.2 0.00441 3603 586 - -

    Central Cooling Coil Outlet 69.2 0.00441 3603 586 0 0

    Central Heating Coil Outlet 71.6 0.00441 3603 586 9383 -

    Supply Fan Outlet 71.6 0.00441 3603 586 0 -

    Cold Supply Duct Outlet 71.6 0.00441 3603 586 - -

    Zone Air - 70.0 0.00441 3603 595 -6282 0

    Return Plenum Outlet 70.0 0.00441 3603 595 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -6276 Deadband -6282 70.0 3603 595 0 0

    Hourly Analysis Program v4.80 Page 12 of 78

  • 8/18/2019 Load Calculation System Design Report

    13/78

    Air System Sizing Summary for 2.PRAY AREA MENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 2.PRAY AREA MEN

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 547.9 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 6.4 Tons  Total coil load 76.6 MBH  Sensible coil load 49.4 MBH  Coil CFM at Jun 1500 2505 CFM  Max block CFM 2505 CFM  Sum of peak zone CFM 2505 CFM  Sensible heat ratio 0.644

      ft²/Ton 85.8

      BTU/(hr-ft²) 139.9

      Water flow @ 10.0 °F rise 15.34 gpm

    Load occurs at Jun 1500

    OA DB / WB 106.0 / 75.0 °FEntering DB / WB 77.3 / 67.9 °FLeaving DB / WB 59.1 / 58.2 °FCoil ADP 57.0 °FBypass Factor 0.100Resulting RH 74 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 8.8 MBH  Coil CFM at Des Htg 2505 CFM  Max coil CFM 2505 CFM  Water flow @ 20.0 °F drop 0.88 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 16.1

    Ent. DB / Lvg DB 67.8 / 71.1 °F

    Supply Fan Sizing Data  Actual max CFM 2505 CFM  Standard CFM 2504 CFM  Actual max CFM/ft² 4.57 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 356 CFM  CFM/ft² 0.65 CFM/ft²

    CFM/person 5.83 CFM/person

    Hourly Analysis Program v4.80 Page 13 of 78

  • 8/18/2019 Load Calculation System Design Report

    14/78

    Zone Sizing Summary for 2.PRAY AREA MENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 2.PRAY AREA MEN

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 547.9 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 36.8 2505 2505 Jul 1400 2.3 547.9 4.57

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      3.PRAY AREA MEN 1 36.8 Jul 1400 2505 2.3 547.9 4.57

    Hourly Analysis Program v4.80 Page 14 of 78

  • 8/18/2019 Load Calculation System Design Report

    15/78

    Air System Design Load Summary for 2.PRAY AREA MENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 249 ft² 770 - 249 ft² 350 -

    Roof Transmission 548 ft² 11600 - 548 ft² 1978 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 614 ft² 1075 - 614 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 509 W 1737 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 61 18004 27745 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 3319 1387 0% 0 0

    >> Total Zone Loads - 36505 29132 - 2328 0

    Zone Conditioning - 36516 29132 - 2630 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 2505 CFM 0 - 2505 CFM 0 -

    Ventilation Load 356 CFM 12839 -1847 356 CFM 6197 0

    Supply Fan Load 2505 CFM 0 - 2505 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 49355 27286 - 8826 0

    Central Cooling Coil - 49355 27287 - 0 0

    Central Heating Coil - 0 - - 8826 ->> Total Conditioning - 49355 27287 - 8826 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 15 of 78

  • 8/18/2019 Load Calculation System Design Report

    16/78

    Zone Design Load Summary for 2.PRAY AREA MENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 249 ft² 779 - 249 ft² 350 -

    Roof Transmission 548 ft² 11827 - 548 ft² 1978 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 614 ft² 1084 - 614 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 509 W 1737 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 61 18004 27745 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 3343 1387 0% 0 0

    >> Total Zone Loads - 36773 29132 - 2328 0

    Hourly Analysis Program v4.80 Page 16 of 78

  • 8/18/2019 Load Calculation System Design Report

    17/78

    System Psychrometrics for 2.PRAY AREA MENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    June DESIGN COOLING DAY, 1500

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 106.0 0.01152 356 400 12839 -1847

    Vent - Return Mixing Outlet 77.3 0.01246 2505 3223 - -

    Central Cooling Coil Outlet 59.1 0.01016 2505 3223 49355 27287

    Central Heating Coil Outlet 59.1 0.01016 2505 3223 0 -

    Supply Fan Outlet 59.1 0.01016 2505 3223 0 -

    Cold Supply Duct Outlet 59.1 0.01016 2505 3223 - -

    Zone Air - 72.6 0.01262 2505 3690 36516 29132

    Return Plenum Outlet 72.6 0.01262 2505 3690 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 36505 Cooling 36516 72.6 2505 3690 0 0

    Hourly Analysis Program v4.80 Page 17 of 78

  • 8/18/2019 Load Calculation System Design Report

    18/78

    System Psychrometrics for 2.PRAY AREA MENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 356 400 -6197 0

    Vent - Return Mixing Outlet 67.8 0.00441 2505 455 - -

    Central Cooling Coil Outlet 67.8 0.00441 2505 455 0 0

    Central Heating Coil Outlet 71.1 0.00441 2505 455 8826 -

    Supply Fan Outlet 71.1 0.00441 2505 455 0 -

    Cold Supply Duct Outlet 71.1 0.00441 2505 455 - -

    Zone Air - 70.1 0.00441 2505 464 -2630 0

    Return Plenum Outlet 70.1 0.00441 2505 464 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -2328 Deadband -2630 70.1 2505 464 0 0

    Hourly Analysis Program v4.80 Page 18 of 78

  • 8/18/2019 Load Calculation System Design Report

    19/78

    Air System Sizing Summary for 4.ADMIN OFFICE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 4.ADMIN OFFICE 1

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1604.9 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 6.1 Tons  Total coil load 73.2 MBH  Sensible coil load 71.1 MBH  Coil CFM at Jun 1500 4600 CFM  Max block CFM 4600 CFM  Sum of peak zone CFM 4600 CFM  Sensible heat ratio 0.971

      ft²/Ton 263.1

      BTU/(hr-ft²) 45.6

      Water flow @ 10.0 °F rise 14.65 gpm

    Load occurs at Jun 1500

    OA DB / WB 106.0 / 75.0 °FEntering DB / WB 73.7 / 63.7 °FLeaving DB / WB 59.4 / 58.5 °FCoil ADP 57.8 °FBypass Factor 0.100Resulting RH 60 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 12.3 MBH  Coil CFM at Des Htg 4600 CFM  Max coil CFM 4600 CFM  Water flow @ 20.0 °F drop 1.23 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 7.7

    Ent. DB / Lvg DB 69.4 / 71.9 °F

    Supply Fan Sizing Data  Actual max CFM 4600 CFM  Standard CFM 4597 CFM  Actual max CFM/ft² 2.87 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 134 CFM  CFM/ft² 0.08 CFM/ft²

    CFM/person 22.39 CFM/person

    Hourly Analysis Program v4.80 Page 19 of 78

  • 8/18/2019 Load Calculation System Design Report

    20/78

    Zone Sizing Summary for 4.ADMIN OFFICE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 4.ADMIN OFFICE 1

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1604.9 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 67.5 4600 4600 Jun 1500 10.2 1604.9 2.87

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      4.ADMIN OFFICE 1 1 67.5 Jun 1500 4600 10.2 1604.9 2.87

    Hourly Analysis Program v4.80 Page 20 of 78

  • 8/18/2019 Load Calculation System Design Report

    21/78

    Air System Design Load Summary for 4.ADMIN OFFICE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 517 ft² 8237 - 517 ft² - -

    Wall Transmission 1178 ft² 3607 - 1178 ft² 1657 -

    Roof Transmission 1605 ft² 33978 - 1605 ft² 5795 -

    Window Transmission 517 ft² 5405 - 517 ft² 2763 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 108 ft² 189 - 108 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1491 W 5087 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 1000 W 3412 - 0 0 -

    People 6 1470 1230 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 6138 62 0% 0 0

    >> Total Zone Loads - 67523 1292 - 10215 0

    Zone Conditioning - 66277 1292 - 10005 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 4600 CFM 0 - 4600 CFM 0 -

    Ventilation Load 134 CFM 4818 795 134 CFM 2307 2

    Supply Fan Load 4600 CFM 0 - 4600 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 71095 2086 - 12312 2

    Central Cooling Coil - 71095 2092 - 0 0

    Central Heating Coil - 0 - - 12312 ->> Total Conditioning - 71095 2092 - 12312 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 21 of 78

  • 8/18/2019 Load Calculation System Design Report

    22/78

    Zone Design Load Summary for 4.ADMIN OFFICE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 517 ft² 8237 - 517 ft² - -

    Wall Transmission 1178 ft² 3607 - 1178 ft² 1657 -

    Roof Transmission 1605 ft² 33978 - 1605 ft² 5795 -

    Window Transmission 517 ft² 5405 - 517 ft² 2763 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 108 ft² 189 - 108 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1491 W 5087 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 1000 W 3412 - 0 0 -

    People 6 1470 1230 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 6138 62 0% 0 0

    >> Total Zone Loads - 67523 1292 - 10215 0

    Hourly Analysis Program v4.80 Page 22 of 78

  • 8/18/2019 Load Calculation System Design Report

    23/78

    System Psychrometrics for 4.ADMIN OFFICE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    June DESIGN COOLING DAY, 1500

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 106.0 0.01152 134 400 4818 795

    Vent - Return Mixing Outlet 73.7 0.01031 4600 804 - -

    Central Cooling Coil Outlet 59.4 0.01022 4600 804 71095 2092

    Central Heating Coil Outlet 59.4 0.01022 4600 804 0 -

    Supply Fan Outlet 59.4 0.01022 4600 804 0 -

    Cold Supply Duct Outlet 59.4 0.01022 4600 804 - -

    Zone Air - 72.8 0.01027 4600 816 66277 1292

    Return Plenum Outlet 72.8 0.01027 4600 816 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 67523 Cooling 66277 72.8 4600 816 0 0

    Hourly Analysis Program v4.80 Page 23 of 78

  • 8/18/2019 Load Calculation System Design Report

    24/78

    System Psychrometrics for 4.ADMIN OFFICE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 134 400 -2307 -2

    Vent - Return Mixing Outlet 69.4 0.00441 4600 725 - -

    Central Cooling Coil Outlet 69.4 0.00441 4600 725 0 0

    Central Heating Coil Outlet 71.9 0.00441 4600 725 12312 -

    Supply Fan Outlet 71.9 0.00441 4600 725 0 -

    Cold Supply Duct Outlet 71.9 0.00441 4600 725 - -

    Zone Air - 69.9 0.00441 4600 735 -10005 0

    Return Plenum Outlet 69.9 0.00441 4600 735 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -10215 Heating -10005 69.9 4600 735 0 0

    Hourly Analysis Program v4.80 Page 24 of 78

  • 8/18/2019 Load Calculation System Design Report

    25/78

    Air System Sizing Summary for 5.BACK OFFICEProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 5.BACK OFFICE

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1043.0 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 3.5 Tons  Total coil load 41.8 MBH  Sensible coil load 39.3 MBH  Coil CFM at Jul 1500 2395 CFM  Max block CFM 2395 CFM  Sum of peak zone CFM 2395 CFM  Sensible heat ratio 0.940

      ft²/Ton 299.1

      BTU/(hr-ft²) 40.1

      Water flow @ 10.0 °F rise 8.37 gpm

    Load occurs at Jul 1500

    OA DB / WB 107.0 / 75.0 °FEntering DB / WB 74.8 / 64.3 °FLeaving DB / WB 59.6 / 58.6 °FCoil ADP 57.9 °FBypass Factor 0.100Resulting RH 61 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 7.3 MBH  Coil CFM at Des Htg 2395 CFM  Max coil CFM 2395 CFM  Water flow @ 20.0 °F drop 0.73 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 7.0

    Ent. DB / Lvg DB 69.1 / 71.9 °F

    Supply Fan Sizing Data  Actual max CFM 2395 CFM  Standard CFM 2393 CFM  Actual max CFM/ft² 2.30 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 140 CFM  CFM/ft² 0.13 CFM/ft²

    CFM/person 15.51 CFM/person

    Hourly Analysis Program v4.80 Page 25 of 78

  • 8/18/2019 Load Calculation System Design Report

    26/78

    Zone Sizing Summary for 5.BACK OFFICEProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 5.BACK OFFICE

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1043.0 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 35.2 2395 2395 Jul 1400 4.8 1043.0 2.30

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      5.BACK OFFICE 1 35.2 Jul 1400 2395 4.8 1043.0 2.30

    Hourly Analysis Program v4.80 Page 26 of 78

  • 8/18/2019 Load Calculation System Design Report

    27/78

    Air System Design Load Summary for 5.BACK OFFICEProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 107.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 756 ft² 2371 - 756 ft² 1063 -

    Roof Transmission 1043 ft² 22228 - 1043 ft² 3766 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 904 ft² 1612 - 904 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 969 W 3306 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 9 2205 1845 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 3172 92 0% 0 0

    >> Total Zone Loads - 34894 1937 - 4830 0

    Zone Conditioning - 34169 1937 - 4841 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 2395 CFM 0 - 2395 CFM 0 -

    Ventilation Load 140 CFM 5158 583 140 CFM 2413 0

    Supply Fan Load 2395 CFM 0 - 2395 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 39328 2521 - 7255 0

    Central Cooling Coil - 39328 2522 - 0 0

    Central Heating Coil - 0 - - 7255 ->> Total Conditioning - 39328 2522 - 7255 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 27 of 78

  • 8/18/2019 Load Calculation System Design Report

    28/78

    Zone Design Load Summary for 5.BACK OFFICEProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 756 ft² 2334 - 756 ft² 1063 -

    Roof Transmission 1043 ft² 22516 - 1043 ft² 3766 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 904 ft² 1597 - 904 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 969 W 3306 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 9 2205 1845 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 3196 92 0% 0 0

    >> Total Zone Loads - 35153 1937 - 4830 0

    Hourly Analysis Program v4.80 Page 28 of 78

  • 8/18/2019 Load Calculation System Design Report

    29/78

    System Psychrometrics for 5.BACK OFFICEProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    July DESIGN COOLING DAY, 1500

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 107.0 0.01129 140 400 5158 583

    Vent - Return Mixing Outlet 74.8 0.01046 2395 969 - -

    Central Cooling Coil Outlet 59.6 0.01024 2395 969 39328 2522

    Central Heating Coil Outlet 59.6 0.01024 2395 969 0 -

    Supply Fan Outlet 59.6 0.01024 2395 969 0 -

    Cold Supply Duct Outlet 59.6 0.01024 2395 969 - -

    Zone Air - 72.8 0.01041 2395 1004 34169 1937

    Return Plenum Outlet 72.8 0.01041 2395 1004 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 34894 Cooling 34169 72.8 2395 1004 0 0

    Hourly Analysis Program v4.80 Page 29 of 78

  • 8/18/2019 Load Calculation System Design Report

    30/78

    System Psychrometrics for 5.BACK OFFICEProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 140 400 -2413 0

    Vent - Return Mixing Outlet 69.1 0.00441 2395 553 - -

    Central Cooling Coil Outlet 69.1 0.00441 2395 553 0 0

    Central Heating Coil Outlet 71.9 0.00441 2395 553 7255 -

    Supply Fan Outlet 71.9 0.00441 2395 553 0 -

    Cold Supply Duct Outlet 71.9 0.00441 2395 553 - -

    Zone Air - 70.0 0.00441 2395 562 -4841 0

    Return Plenum Outlet 70.0 0.00441 2395 562 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -4830 Deadband -4841 70.0 2395 562 0 0

    Hourly Analysis Program v4.80 Page 30 of 78

  • 8/18/2019 Load Calculation System Design Report

    31/78

    Air System Sizing Summary for 6.PRAY AREA WOMENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 6.PRAY AREA WOMEN

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 406.9 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 4.0 Tons  Total coil load 47.9 MBH  Sensible coil load 38.3 MBH  Coil CFM at Aug 1500 1990 CFM  Max block CFM 1990 CFM  Sum of peak zone CFM 1990 CFM  Sensible heat ratio 0.799

      ft²/Ton 101.9

      BTU/(hr-ft²) 117.8

      Water flow @ 10.0 °F rise 9.59 gpm

    Load occurs at Aug 1500

    OA DB / WB 107.0 / 75.0 °FEntering DB / WB 77.7 / 66.5 °FLeaving DB / WB 59.8 / 58.8 °FCoil ADP 57.9 °FBypass Factor 0.100Resulting RH 65 %Design supply temp. 58.0 °FZone T-stat Check 0 of 1 OKMax zone temperature deviation 0.1 °F

    Central Heating Coil Sizing Data  Max coil load 8.0 MBH  Coil CFM at Des Htg 1990 CFM  Max coil CFM 1990 CFM  Water flow @ 20.0 °F drop 0.80 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 19.6

    Ent. DB / Lvg DB 67.8 / 71.5 °F

    Supply Fan Sizing Data  Actual max CFM 1990 CFM  Standard CFM 1989 CFM  Actual max CFM/ft² 4.89 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 264 CFM  CFM/ft² 0.65 CFM/ft²

    CFM/person 5.87 CFM/person

    Hourly Analysis Program v4.80 Page 31 of 78

  • 8/18/2019 Load Calculation System Design Report

    32/78

    Zone Sizing Summary for 6.PRAY AREA WOMENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 6.PRAY AREA WOMEN

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 406.9 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 29.2 1990 1990 Aug 1500 3.4 406.9 4.89

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      6.PRAY AREA WOMEN 1 29.2 Aug 1500 1990 3.4 406.9 4.89

    Hourly Analysis Program v4.80 Page 32 of 78

  • 8/18/2019 Load Calculation System Design Report

    33/78

    Air System Design Load Summary for 6.PRAY AREA WOMENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 107.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 1381 ft² 4635 - 1381 ft² 1944 -

    Roof Transmission 407 ft² 8493 - 407 ft² 1469 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 624 ft² 1113 - 624 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 378 W 1290 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 45 11025 9225 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 2656 461 0% 0 0

    >> Total Zone Loads - 29212 9686 - 3413 0

    Zone Conditioning - 28667 9686 - 3453 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 1990 CFM 0 - 1990 CFM 0 -

    Ventilation Load 264 CFM 9642 -79 264 CFM 4527 0

    Supply Fan Load 1990 CFM 0 - 1990 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 38309 9607 - 7980 0

    Central Cooling Coil - 38309 9608 - 0 0

    Central Heating Coil - 0 - - 7980 ->> Total Conditioning - 38309 9608 - 7980 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 33 of 78

  • 8/18/2019 Load Calculation System Design Report

    34/78

    Zone Design Load Summary for 6.PRAY AREA WOMENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 107.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 1381 ft² 4635 - 1381 ft² 1944 -

    Roof Transmission 407 ft² 8493 - 407 ft² 1469 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 624 ft² 1113 - 624 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 378 W 1290 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 45 11025 9225 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 2656 461 0% 0 0

    >> Total Zone Loads - 29212 9686 - 3413 0

    Hourly Analysis Program v4.80 Page 34 of 78

  • 8/18/2019 Load Calculation System Design Report

    35/78

    System Psychrometrics for 6.PRAY AREA WOMENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    August DESIGN COOLING DAY, 1500

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 107.0 0.01129 264 400 9642 -79

    Vent - Return Mixing Outlet 77.7 0.01135 1990 2093 - -

    Central Cooling Coil Outlet 59.8 0.01033 1990 2093 38309 9608

    Central Heating Coil Outlet 59.8 0.01033 1990 2093 0 -

    Supply Fan Outlet 59.8 0.01033 1990 2093 0 -

    Cold Supply Duct Outlet 59.8 0.01033 1990 2093 - -

    Zone Air - 73.2 0.01135 1990 2352 28667 9686

    Return Plenum Outlet 73.2 0.01135 1990 2352 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 29212 Cooling 28667 73.2 1990 2352 0 0

    Hourly Analysis Program v4.80 Page 35 of 78

  • 8/18/2019 Load Calculation System Design Report

    36/78

    System Psychrometrics for 6.PRAY AREA WOMENProject Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 264 400 -4527 0

    Vent - Return Mixing Outlet 67.8 0.00441 1990 463 - -

    Central Cooling Coil Outlet 67.8 0.00441 1990 463 0 0

    Central Heating Coil Outlet 71.5 0.00441 1990 463 7980 -

    Supply Fan Outlet 71.5 0.00441 1990 463 0 -

    Cold Supply Duct Outlet 71.5 0.00441 1990 463 - -

    Zone Air - 69.9 0.00441 1990 472 -3453 0

    Return Plenum Outlet 69.9 0.00441 1990 472 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -3413 Heating -3453 69.9 1990 472 0 0

    Hourly Analysis Program v4.80 Page 36 of 78

  • 8/18/2019 Load Calculation System Design Report

    37/78

    Air System Sizing Summary for 7.ADMIN OFFICE 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 7.ADMIN OFFICE 2

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1304.6 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 4.4 Tons  Total coil load 53.0 MBH  Sensible coil load 51.1 MBH  Coil CFM at Jun 1400 3331 CFM  Max block CFM 3331 CFM  Sum of peak zone CFM 3331 CFM  Sensible heat ratio 0.964

      ft²/Ton 295.6

      BTU/(hr-ft²) 40.6

      Water flow @ 10.0 °F rise 10.60 gpm

    Load occurs at Jun 1400

    OA DB / WB 105.5 / 74.9 °FEntering DB / WB 73.9 / 63.9 °FLeaving DB / WB 59.7 / 58.7 °FCoil ADP 58.1 °FBypass Factor 0.100Resulting RH 60 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 9.3 MBH  Coil CFM at Des Htg 3331 CFM  Max coil CFM 3331 CFM  Water flow @ 20.0 °F drop 0.93 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 7.1

    Ent. DB / Lvg DB 69.6 / 72.1 °F

    Supply Fan Sizing Data  Actual max CFM 3331 CFM  Standard CFM 3329 CFM  Actual max CFM/ft² 2.55 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 109 CFM  CFM/ft² 0.08 CFM/ft²

    CFM/person 18.19 CFM/person

    Hourly Analysis Program v4.80 Page 37 of 78

  • 8/18/2019 Load Calculation System Design Report

    38/78

    Zone Sizing Summary for 7.ADMIN OFFICE 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 7.ADMIN OFFICE 2

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 1304.6 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 48.9 3331 3331 Jul 1500 7.3 1304.6 2.55

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      7.ADMIN OFFICE 1 48.9 Jul 1500 3331 7.3 1304.6 2.55

    Hourly Analysis Program v4.80 Page 38 of 78

  • 8/18/2019 Load Calculation System Design Report

    39/78

    Air System Design Load Summary for 7.ADMIN OFFICE 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 105.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 237 ft² 2986 - 237 ft² - -

    Wall Transmission 958 ft² 2996 - 958 ft² 1348 -

    Roof Transmission 1305 ft² 28047 - 1305 ft² 4710 -

    Window Transmission 237 ft² 2432 - 237 ft² 1266 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 118 ft² 206 - 118 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1212 W 4135 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 500 W 1706 - 0 0 -

    People 6 1470 1230 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 4398 62 0% 0 0

    >> Total Zone Loads - 48376 1292 - 7325 0

    Zone Conditioning - 47237 1292 - 7373 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 3331 CFM 0 - 3331 CFM 0 -

    Ventilation Load 109 CFM 3850 586 109 CFM 1894 1

    Supply Fan Load 3331 CFM 0 - 3331 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 51087 1878 - 9268 1

    Central Cooling Coil - 51087 1881 - 0 0

    Central Heating Coil - 0 - - 9268 ->> Total Conditioning - 51087 1881 - 9268 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 39 of 78

  • 8/18/2019 Load Calculation System Design Report

    40/78

    Zone Design Load Summary for 7.ADMIN OFFICE 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 107.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 237 ft² 3513 - 237 ft² - -

    Wall Transmission 958 ft² 3053 - 958 ft² 1348 -

    Roof Transmission 1305 ft² 27802 - 1305 ft² 4710 -

    Window Transmission 237 ft² 2557 - 237 ft² 1266 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 118 ft² 211 - 118 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 1212 W 4135 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 500 W 1706 - 0 0 -

    People 6 1470 1230 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 4445 62 0% 0 0

    >> Total Zone Loads - 48893 1292 - 7325 0

    Hourly Analysis Program v4.80 Page 40 of 78

  • 8/18/2019 Load Calculation System Design Report

    41/78

    System Psychrometrics for 7.ADMIN OFFICE 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    June DESIGN COOLING DAY, 1400

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 105.5 0.01152 109 400 3850 586

    Vent - Return Mixing Outlet 73.9 0.01043 3331 808 - -

    Central Cooling Coil Outlet 59.7 0.01031 3331 808 51087 1881

    Central Heating Coil Outlet 59.7 0.01031 3331 808 0 -

    Supply Fan Outlet 59.7 0.01031 3331 808 0 -

    Cold Supply Duct Outlet 59.7 0.01031 3331 808 - -

    Zone Air - 72.8 0.01039 3331 822 47237 1292

    Return Plenum Outlet 72.8 0.01039 3331 822 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 48376 Cooling 47237 72.8 3331 822 0 0

    Hourly Analysis Program v4.80 Page 41 of 78

  • 8/18/2019 Load Calculation System Design Report

    42/78

    System Psychrometrics for 7.ADMIN OFFICE 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 109 400 -1894 -1

    Vent - Return Mixing Outlet 69.6 0.00441 3331 687 - -

    Central Cooling Coil Outlet 69.6 0.00441 3331 687 0 0

    Central Heating Coil Outlet 72.1 0.00441 3331 687 9268 -

    Supply Fan Outlet 72.1 0.00441 3331 687 0 -

    Cold Supply Duct Outlet 72.1 0.00441 3331 687 - -

    Zone Air - 70.1 0.00441 3331 696 -7373 0

    Return Plenum Outlet 70.1 0.00441 3331 696 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -7325 Deadband -7373 70.1 3331 696 0 0

    Hourly Analysis Program v4.80 Page 42 of 78

  • 8/18/2019 Load Calculation System Design Report

    43/78

    Air System Sizing Summary for 81.STORAGE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 81.STORAGE 1

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 587.7 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 1.4 Tons  Total coil load 16.3 MBH  Sensible coil load 15.8 MBH  Coil CFM at Jun 1400 1011 CFM  Max block CFM 1011 CFM  Sum of peak zone CFM 1011 CFM  Sensible heat ratio 0.972

      ft²/Ton 433.7

      BTU/(hr-ft²) 27.7

      Water flow @ 10.0 °F rise 3.25 gpm

    Load occurs at Jun 1400

    OA DB / WB 105.5 / 74.9 °FEntering DB / WB 74.0 / 63.8 °FLeaving DB / WB 59.5 / 58.5 °FCoil ADP 57.9 °FBypass Factor 0.100Resulting RH 60 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 3.2 MBH  Coil CFM at Des Htg 1011 CFM  Max coil CFM 1011 CFM  Water flow @ 20.0 °F drop 0.32 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 5.5

    Ent. DB / Lvg DB 69.2 / 72.1 °F

    Supply Fan Sizing Data  Actual max CFM 1011 CFM  Standard CFM 1010 CFM  Actual max CFM/ft² 1.72 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 40 CFM  CFM/ft² 0.07 CFM/ft²

    CFM/person 40.05 CFM/person

    Hourly Analysis Program v4.80 Page 43 of 78

  • 8/18/2019 Load Calculation System Design Report

    44/78

    Zone Sizing Summary for 81.STORAGE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 81.STORAGE 1

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 587.7 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 14.8 1011 1011 Jul 1400 2.5 587.7 1.72

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      81.STORAGE 1 1 14.8 Jul 1400 1011 2.5 587.7 1.72

    Hourly Analysis Program v4.80 Page 44 of 78

  • 8/18/2019 Load Calculation System Design Report

    45/78

    Air System Design Load Summary for 81.STORAGE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 105.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 759 ft² 2235 - 759 ft² 1068 -

    Roof Transmission 393 ft² 8446 - 393 ft² 1419 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 323 ft² 560 - 323 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 546 W 1863 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 1 245 205 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 1335 10 0% 0 0

    >> Total Zone Loads - 14685 215 - 2487 0

    Zone Conditioning - 14388 215 - 2531 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 1011 CFM 0 - 1011 CFM 0 -

    Ventilation Load 40 CFM 1418 237 40 CFM 683 0

    Supply Fan Load 1011 CFM 0 - 1011 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 15806 452 - 3214 0

    Central Cooling Coil - 15806 454 - 0 0

    Central Heating Coil - 0 - - 3214 ->> Total Conditioning - 15806 454 - 3214 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 45 of 78

  • 8/18/2019 Load Calculation System Design Report

    46/78

    Zone Design Load Summary for 81.STORAGE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG

    COOLING OA DB / WB 106.5 °F / 74.9 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

    Wall Transmission 759 ft² 2332 - 759 ft² 1068 -

    Roof Transmission 393 ft² 8481 - 393 ft² 1419 -

    Window Transmission 0 ft² 0 - 0 ft² 0 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 323 ft² 570 - 323 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 546 W 1863 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 0 W 0 - 0 0 -

    People 1 245 205 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 1349 10 0% 0 0

    >> Total Zone Loads - 14841 215 - 2487 0

    Hourly Analysis Program v4.80 Page 46 of 78

  • 8/18/2019 Load Calculation System Design Report

    47/78

    System Psychrometrics for 81.STORAGE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    June DESIGN COOLING DAY, 1400

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 105.5 0.01152 40 400 1418 237

    Vent - Return Mixing Outlet 74.0 0.01032 1011 796 - -

    Central Cooling Coil Outlet 59.5 0.01023 1011 796 15806 454

    Central Heating Coil Outlet 59.5 0.01023 1011 796 0 -

    Supply Fan Outlet 59.5 0.01023 1011 796 0 -

    Cold Supply Duct Outlet 59.5 0.01023 1011 796 - -

    Zone Air - 72.7 0.01027 1011 812 14388 215

    Return Plenum Outlet 72.7 0.01027 1011 812 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 14685 Cooling 14388 72.7 1011 812 0 0

    Hourly Analysis Program v4.80 Page 47 of 78

  • 8/18/2019 Load Calculation System Design Report

    48/78

    System Psychrometrics for 81.STORAGE 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 40 400 -683 0

    Vent - Return Mixing Outlet 69.2 0.00441 1011 637 - -

    Central Cooling Coil Outlet 69.2 0.00441 1011 637 0 0

    Central Heating Coil Outlet 72.1 0.00441 1011 637 3214 -

    Supply Fan Outlet 72.1 0.00441 1011 637 0 -

    Cold Supply Duct Outlet 72.1 0.00441 1011 637 - -

    Zone Air - 69.8 0.00441 1011 646 -2531 0

    Return Plenum Outlet 69.8 0.00441 1011 646 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -2487 Heating -2531 69.8 1011 646 0 0

    Hourly Analysis Program v4.80 Page 48 of 78

  • 8/18/2019 Load Calculation System Design Report

    49/78

    Air System Sizing Summary for 82.SHOPPING AREA PART 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 82.SHOPPING AREA PART 1

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 5929.8 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 24.3 Tons  Total coil load 291.6 MBH  Sensible coil load 249.2 MBH  Coil CFM at Aug 1500 11957 CFM  Max block CFM 11957 CFM  Sum of peak zone CFM 11957 CFM  Sensible heat ratio 0.855

      ft²/Ton 244.0

      BTU/(hr-ft²) 49.2

      Water flow @ 10.0 °F rise 58.35 gpm

    Load occurs at Aug 1500

    OA DB / WB 107.0 / 75.0 °FEntering DB / WB 78.4 / 65.8 °FLeaving DB / WB 59.1 / 57.9 °FCoil ADP 56.9 °FBypass Factor 0.100Resulting RH 62 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 53.5 MBH  Coil CFM at Des Htg 11957 CFM  Max coil CFM 11957 CFM  Water flow @ 20.0 °F drop 5.35 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 9.0

    Ent. DB / Lvg DB 67.3 / 71.4 °F

    Supply Fan Sizing Data  Actual max CFM 11957 CFM  Standard CFM 11950 CFM  Actual max CFM/ft² 2.02 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 2031 CFM  CFM/ft² 0.34 CFM/ft²

    CFM/person 12.31 CFM/person

    Hourly Analysis Program v4.80 Page 49 of 78

  • 8/18/2019 Load Calculation System Design Report

    50/78

    Zone Sizing Summary for 82.SHOPPING AREA PART 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 82.SHOPPING AREA PART 1

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 5929.8 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Zone Sizing Data

    Maximum Maximum Zone

    Cooling Design Minimum Heating Floor  

    Sensible Airflow Airflow Time of Load Area Zone

    Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²

    Zone 1 175.5 11957 11957 Jul 1500 18.5 5929.8 2.02

    Zone Terminal Sizing Data

    No Zone Terminal Sizing Data required for this system.

    Space Loads and Airflows

    Cooling Time Air Heating Floor  

    Zone Name / Sensible of Flow Load Area Space

      Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²

    Zone 1 

      82. SHOPING AREA PART 1 1 175.5 Jul 1500 11957 18.5 5929.8 2.02

    Hourly Analysis Program v4.80 Page 50 of 78

  • 8/18/2019 Load Calculation System Design Report

    51/78

    Air System Design Load Summary for 82.SHOPPING AREA PART 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 107.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 377 ft² 7268 - 377 ft² - -

    Wall Transmission 2370 ft² 7308 - 2370 ft² 3336 -

    Roof Transmission 3635 ft² 75877 - 3635 ft² 13125 -

    Window Transmission 377 ft² 4067 - 377 ft² 2014 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 527 ft² 941 - 527 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 5509 W 18796 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 1000 W 3412 - 0 0 -

    People 165 40424 33825 0 0 0

    Infiltration - 0 0 - 0 0

    Miscellaneous - 0 0 - 0 0Safety Factor 10% / 5% 15809 1691 0% 0 0

    >> Total Zone Loads - 173903 35516 - 18475 0

    Zone Conditioning - 173570 35516 - 18476 0

    Plenum Wall Load 0% 0 - 0 0 -

    Plenum Roof Load 0% 0 - 0 0 -

    Plenum Lighting Load 0% 0 - 0 0 -

    Return Fan Load 11957 CFM 0 - 11957 CFM 0 -

    Ventilation Load 2031 CFM 75603 6885 2031 CFM 35032 0

    Supply Fan Load 11957 CFM 0 - 11957 CFM 0 -

    Space Fan Coil Fans - 0 - - 0 -

    Duct Heat Gain / Loss 0% 0 - 0% 0 -

    >> Total System Loads - 249174 42401 - 53508 0

    Central Cooling Coil - 249174 42410 - 0 0

    Central Heating Coil - 0 - - 53509 ->> Total Conditioning - 249174 42410 - 53509 0

    Key: Positive values are clg loads Positive values are htg loads

    Negative values are htg loads Negative values are clg loads

    Hourly Analysis Program v4.80 Page 51 of 78

  • 8/18/2019 Load Calculation System Design Report

    52/78

    Zone Design Load Summary for 82.SHOPPING AREA PART 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Zone 1 DESIGN COOLING DESIGN HEATING

    COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

    COOLING OA DB / WB 107.0 °F / 75.0 °F HEATING OA DB / WB 54.0 °F / 45.3 °F

    OCCUPIED T-STAT 71.6 °F OCCUPIED T-STAT 70.0 °F

    Sensible Latent Sensible Latent

    ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

    Window & Skylight Solar Loads 377 ft² 7147 - 377 ft² - -

    Wall Transmission 2370 ft² 7310 - 2370 ft² 3336 -

    Roof Transmission 3635 ft² 77466 - 3635 ft² 13125 -

    Window Transmission 377 ft² 4067 - 377 ft² 2014 -

    Skylight Transmission 0 ft² 0 - 0 ft² 0 -

    Door Loads 0 ft² 0 - 0 ft² 0 -

    Floor Transmission 0 ft² 0 - 0 ft² 0 -

    Partitions 527 ft² 941 - 527 ft² 0 -

    Ceiling 0 ft² 0 - 0 ft² 0 -

    Overhead Lighting 5509 W 18796 - 0 0 -

    Task Lighting 0 W 0 - 0 0 -

    Electric Equipment 1000 W 3412 - 0 0 -

    People 165 40424 33825 0 0 0

    Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0

    Safety Factor 10% / 5% 15956 1691 0% 0 0

    >> Total Zone Loads - 175519 35516 - 18475 0

    Hourly Analysis Program v4.80 Page 52 of 78

  • 8/18/2019 Load Calculation System Design Report

    53/78

    System Psychrometrics for 82.SHOPPING AREA PART 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    August DESIGN COOLING DAY, 1500

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 107.0 0.01129 2031 400 75603 6885

    Vent - Return Mixing Outlet 78.4 0.01070 11957 1165 - -

    Central Cooling Coil Outlet 59.1 0.00995 11957 1165 249174 42410

    Central Heating Coil Outlet 59.1 0.00995 11957 1165 0 -

    Supply Fan Outlet 59.1 0.00995 11957 1165 0 -

    Cold Supply Duct Outlet 59.1 0.00995 11957 1165 - -

    Zone Air - 72.5 0.01058 11957 1322 173570 35516

    Return Plenum Outlet 72.5 0.01058 11957 1322 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 173903 Cooling 173570 72.5 11957 1322 0 0

    Hourly Analysis Program v4.80 Page 53 of 78

  • 8/18/2019 Load Calculation System Design Report

    54/78

    System Psychrometrics for 82.SHOPPING AREA PART 1Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    WINTER DESIGN HEATING

    TABLE 1: SYSTEM DATA

    Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat

    Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 54.0 0.00441 2031 400 -35032 0

    Vent - Return Mixing Outlet 67.3 0.00441 11957 443 - -

    Central Cooling Coil Outlet 67.3 0.00441 11957 443 0 0

    Central Heating Coil Outlet 71.4 0.00441 11957 443 53509 -

    Supply Fan Outlet 71.4 0.00441 11957 443 0 -

    Cold Supply Duct Outlet 71.4 0.00441 11957 443 - -

    Zone Air - 70.0 0.00441 11957 452 -18476 0

    Return Plenum Outlet 70.0 0.00441 11957 452 0 -

       Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)   Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4743.9 BTU/(hr-CFM)  Site Altitude = 16.0 ft 

    TABLE 2: ZONE DATA

    Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating

    Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)

    Zone 1 -18475 Deadband -18476 70.0 11957 452 0 0

    Hourly Analysis Program v4.80 Page 54 of 78

  • 8/18/2019 Load Calculation System Design Report

    55/78

    Air System Sizing Summary for 83.SHOPPING AREA PART 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 83.SHOPPING AREA PART 2

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 6152.7 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calculation Months Jan to Dec

      Sizing Data Calculated

    Zone CFM Sizing Sum of space airflow rates

    Space CFM Sizing Individual peak space loads

    Central Cooling Coil Sizing Data  Total coil load 23.7 Tons  Total coil load 284.5 MBH  Sensible coil load 240.7 MBH  Coil CFM at Jul 1600 11138 CFM  Max block CFM 11138 CFM  Sum of peak zone CFM 11138 CFM  Sensible heat ratio 0.846

      ft²/Ton 259.6

      BTU/(hr-ft²) 46.2

      Water flow @ 10.0 °F rise 56.92 gpm

    Load occurs at Jul 1600

    OA DB / WB 106.5 / 74.9 °FEntering DB / WB 79.0 / 66.1 °FLeaving DB / WB 59.0 / 57.8 °FCoil ADP 56.8 °FBypass Factor 0.100Resulting RH 62 %Design supply temp. 58.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F

    Central Heating Coil Sizing Data  Max coil load 60.7 MBH  Coil CFM at Des Htg 11138 CFM  Max coil CFM 11138 CFM  Water flow @ 20.0 °F drop 6.07 gpm

    Load occurs at Des Htg

    BTU/(hr-ft²) 9.9

    Ent. DB / Lvg DB 66.9 / 71.9 °F

    Supply Fan Sizing Data  Actual max CFM 11138 CFM  Standard CFM 11132 CFM  Actual max CFM/ft² 1.81 CFM/ft²

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air Data  Design airflow CFM 2107 CFM  CFM/ft² 0.34 CFM/ft²

    CFM/person 12.29 CFM/person

    Hourly Analysis Program v4.80 Page 55 of 78

  • 8/18/2019 Load Calculation System Design Report

    56/78

    Zone Sizing Summary for 83.SHOPPING AREA PART 2Project Name: SHARJAH SHOPPING MALL 04/05/2016Prepared by: Oman Technical 11:06AM

    Air System Information  Air System Name 83.SHOPPING AREA PART 2

      Equipment Class UNDEF

      Air System Type SZCAV

    Number of zones 1

    Floor Area 6152.7 ft²Location Sharjah, United Arab Emirates

    Sizing Calculation Information  Calcula