Lightning Protection System Design Revised 5/28/14

Lightning Protection

Embed Size (px)

Citation preview

Page 1: Lightning Protection

Lightning Protection System Design

Revised 5/28/14

Page 2: Lightning Protection
Page 3: Lightning Protection

ERICO has met the standards and requirements of the Registered Continuing Education Providers

Program. Credit earned on completion of this program will be reported to RCEPP. A certificate of

completion will be issued to each participant. As such, it does not include content that may be

deemed or construed to be an approval or endorsement by NCEES or RCEPP.”

Page 4: Lightning Protection

At the end of this class you will be able to:

Understand the principle of lightning protection Understand what a lightning protection system is Understand how lightning is formed Identify the different ways to be struck by lightning Use and understand the Risk Assessment in NFPA® 780 Understand the various lightning protection codes Understand what surge protection is and how it is used Identify other types of lightning protection systems

NFPA is a registered trademark of National Fire Protection Association, Inc.

Learning Objectives

Page 5: Lightning Protection

Wearing jewelry, wearing shoes with metal cleats or carrying metal objects such as tripods, golf clubs, and umbrellas will attract lightning and make a person more susceptible to a strike.

Lightning Myths

Page 6: Lightning Protection

Lightning Video

Page 7: Lightning Protection

Lightning always strikes the tallest object

Lightning Myths

Page 8: Lightning Protection

Lightning strikes can occur either at the beginning or end of a storm

The average lightning strike is six miles long Lightning reaches 50,000 degrees Fahrenheit, fours times as hot

as the sun's surface Voltage in a cloud-to-ground strike is 100 million to 1 billion

volts Around the earth there are 100 lightning strikes per second, or

8,640,000 times a day There are approximately 100,000 thunderstorms in the U.S.

each year

Lightning Facts

Page 9: Lightning Protection

Injuries Due To Lightning

Page 10: Lightning Protection

TEXAS C/G Flash Density

TEXAS = 6 / KM² / YEAR = 16 / M² / YEAR ( 1 SQ. KILOMETER = 0.3861 SQ. MILES ) ( 1 SQ. MILE = 2.59 SQ. KILOMETERS )

TEXAS = 261,914 SQ. MILES FL. C / G FLASHES = < 4,190,624 FL. C/C FLASHES = < 37,715,616 FL. TOTAL FLASHES = < 41,906,240

Page 11: Lightning Protection

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

Page 12: Lightning Protection
Page 13: Lightning Protection
Page 14: Lightning Protection

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

+ + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + + + + + + - + - + - + - + - + - + - + - +

- - - - - - - - - - -

- -

+ + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + + + + + + - + - + - + - + - + - + - + - +

- - - - - - - - - - -

- -

Page 15: Lightning Protection
Page 16: Lightning Protection

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

+ + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + + + + + + - + - + - + - + - + - + - + - +

- - - - - - - - - - -

- -

+ + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + + + + + + - + - + - + - + - + - + - + - +

- - - - - - - - - - -

- -

- - + + + + + + + + + + + + - - - -

+ + + + +

Page 17: Lightning Protection
Page 18: Lightning Protection

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / /

+ + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + + + + + + - + - + - + - + - + - + - + - +

- - - - - - - - - - -

- - + + + + + + + + + + + + - - - -

- -+ + + + +

Page 19: Lightning Protection

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

Page 20: Lightning Protection
Page 21: Lightning Protection

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

Page 22: Lightning Protection

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

Page 23: Lightning Protection
Page 24: Lightning Protection

Positive Lightning

Page 25: Lightning Protection

Do Not Do This!

Page 26: Lightning Protection

Direct strike Side flash/splash Ground current/step potential Conduction through metal

Why people are struck by lightning

Page 27: Lightning Protection

Direct Strike

Most dangerous but fairly uncommon

Page 28: Lightning Protection
Page 29: Lightning Protection
Page 30: Lightning Protection

Side Flash/ Side Splash

Common for people standing under trees

Page 31: Lightning Protection
Page 32: Lightning Protection
Page 33: Lightning Protection

Ground Current/ Step Voltage

Fairly common

Page 34: Lightning Protection
Page 35: Lightning Protection
Page 36: Lightning Protection
Page 37: Lightning Protection

ConductionThrough metal wires or

surfaces

Fairly common especially indoors

Page 38: Lightning Protection
Page 39: Lightning Protection
Page 40: Lightning Protection
Page 41: Lightning Protection

Lightning Videos

Page 42: Lightning Protection

Is related to: The lightning threat. People’s behavior when thunderstorms are nearby.

The Risk Of Being Struck By Lightening

Page 43: Lightning Protection

Lightning Risk

Exposure To Risk

Thunderstorm Approaching

Thunderstorm Overhead

Thunderstorm Departing

Thunderstorm Overhead

Thunderstorm Departing

Low

High

Threat Casualties

Page 44: Lightning Protection

Reducing casualties: Before the storm

If the sky looks threatening, or if you hear thunder, GO TO A SAFE SHELTER IMMEDIATELY!

During the storm Avoid contact with phones, electrical equipment,

plumbing and stay away from doors and windows. After the storm

After the last rumble of thunder, wait 30 minutes before going back out side.

The Risk Of Being Struck By Lightening

Page 45: Lightning Protection

Safety Objective: To reduce the number of casualties by changing people’s

behavior around thunderstorms.

The Risk Of Being Struck By Lightening

Page 46: Lightning Protection

Lightning Risk

Exposure To Risk

Thunderstorm ApproachingThunderstorm Approaching

Thunderstorm Overhead

Thunderstorm Departing

Thunderstorm Overhead

Thunderstorm Departing

Low

High

Safety Objective

Page 47: Lightning Protection

Commercial/IndustrialNational Fire Protection Assoc. # 780Underwriters’ Laboratories # 96ALightning Protection Institute # 175

UtilityIEEE 998 – Direct Lightning Stroke Shielding for Substations.

Lightning Protection Codes

Page 48: Lightning Protection

What is a lightning protection system?

A lightning protection system is a passive means of preventing property damage from the effects of a lightning strike. It works by providing the electric charge produced by the clouds a path of least resistance to the ground. There are four main parts of a properly installed lightning protection system: air terminals, cable, copper clad ground rods, and surge suppressors.

The Principles Of Lightning Protection

Page 49: Lightning Protection

The Principles Of Lightning Protection

Page 50: Lightning Protection

Parts of a building that are most likely to be struck:

•Chimneys•Ventilators•Flagpoles•Towers•Water tanks•Deck railings•Dormers•Parapets•Edges and Corners

The Principles Of Lightning Protection

Page 51: Lightning Protection

Overview of Methods: - Cone of Protection or Protection Angle.

The Principles Of Lightning Protection

Page 52: Lightning Protection

Overview of Methods: - Cone of Protection or Protection Angle.

The Principles Of Lightning Protection

Page 53: Lightning Protection

Overview of Methods: - Rolling Sphere Method

•Incorporated in NFPA® 780 in 1980.•Originated - Electric power transmission industry.

•Based on the electrogeometric model:•Ip = (kA); ds = (m)

•ds = 10 Ip (.65)

•Typical peak current of 10kA•ds = 150’ R

The Principles Of Lightning Protection

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 54: Lightning Protection

Overview of Methods: - Rolling Sphere Method

150’ R – This is the distance at which the downward leader results in the initiation of an upward leader from the structure.

Peak currents below 5kA and 7kA are not common. 10kA peak current represents 91% of all lightning events.

The Principles Of Lightning Protection

Page 55: Lightning Protection

Overview of Methods: - Rolling Sphere Method

Soil vent Roof drain

*Plastic or metal soil vent

Air terminalCooling tower

Air terminal

Air terminal

*Soil vent*Roof drain

*Exhaust fan

*Ladder

Air handling unit

150’

radiu

s

The Principles Of Lightning Protection

Page 56: Lightning Protection

Overview of Methods: - Rolling Sphere Method

Advantages: Easy to apply, even to buildings with complicated shapes.

Limitations: It assigns an equal leader initiation ability to all contact points on the structure. So, it cannot distinguish between likely and unlikely contact points. Could strike the corner of the building rather than the vertical flat surface halfway down the side of the building.

The Principles Of Lightning Protection

Page 57: Lightning Protection

The Principles Of Lightning Protection

Air terminals placed on the structure do not substantially increase the probability of the structure being struck by lightning. If the downward leader is close to the structure, it will probably attach to that structure anyway.

Page 58: Lightning Protection

150’ radius sphere model can be calculated:

d = sqrt((h1(300-h1))) – sqrt((h2(300-h2)))

d = horizontal distance in feeth1 = height of the higher air terminal or protected roofh2 = height of the lower roof or object

Rolling Sphere Method

Page 59: Lightning Protection

Installations can be expensive Coverage area of any one air terminal is small Maintenance/Repair

Disadvantages of Conventional Lightning Protection Systems

Page 60: Lightning Protection

Appendix “L” of NFPA® 780 Not a part of the actual standard

Ae = LW + 6H(L + W) + PI()9H2

Nd = (Ng)(Ae)(C1)(10-6) Nc = (1.5 x 10-3) / C

Lightning Protection Risk Assessment

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 61: Lightning Protection

Equivalent Collective Area is defined as: Ae = LW + 6H(L + W) + PI()9H2

Ae refers to the ground area having the same yearly direct lightning flash probability as the structure

Expected Yearly Lightning Strike Frequency: Nd = (Ng)(Ae)(C1)(10-6)

Ng is the yearly number of flashes to ground per square kilometer (lightning flash density)

C1 is the environmental coefficient

Lightning Protection Risk Assessment

Page 62: Lightning Protection

C1 – Relative structure location C1 = .25 – Located within a space containing structures

or trees of the same height or taller within a distance of 3H

C1 = .5 – Surrounded by smaller structures within a distance of 3H

C1 = 1 – Isolated structure, no other structures located within a distance of 3H

C1 = 2 – Isolated structure on a hilltop

Lightning Protection Risk Assessment

Page 63: Lightning Protection

Tolerable Lightning Frequency: Nc = (1.5 x 10-3) / C Where C = (C2)(C3)(C4)(C5)

C2 – Structural Coefficient

Structure Metal Roof Non-Met. Roof Flammable RoofMetal .5 1.0 2.0Non-Metal 1.0 1.0 2.5Flammable 2.0 2.5 3.0

Lightning Protection Risk Assessment

Page 64: Lightning Protection

C3 – Structure Contents C3 = .5 – Low value and non-flammable C3 = 1 – Standard value and non-flammable C3 = 2 – High value, moderate flammability C3 = 3 – Exceptional value, flammable, computer or

electronics C3 = 4 – Exceptional value, irreplaceable curtural items

Lightning Protection Risk Assessment

Page 65: Lightning Protection

C4 – Structure Occupancy C4 = .5 – Unoccupied C4 = 1 – Normally occupied C4 = 3 – Difficult to evacuate or risk of panic

C5 – Lightning Consequence C5 = 1 – Continuity of services not req’d. No environmental

impact C5 = 5 – Continuity of services req’d. No environmental

impact C5 = 10 – Consequences to the environment

Lightning Protection Risk Assessment

Page 66: Lightning Protection

Ae = LW + 6H(L + W) + PI()9H2

Nd = (Ng)(Ae)(C1)(10-6) Nc = (1.5 x 10-3) / C

If Nd <= Nc; an LPS may be optional If Nd > Nc; an LPS should be installed

Lightning Protection Risk Assessment

Page 67: Lightning Protection

Spreadsheet Example

Lightning Protection Risk Assessment

Page 68: Lightning Protection

Owner Insurance Military Risk Assessment FL Building Code

Lightning Protection Risk Assessment

Page 69: Lightning Protection

First adopted in 1904

NFPA® 780-2014

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 70: Lightning Protection

Blunt/ Safety Tipped Parapet Air Terminal

Ridge Air Terminal with Typical Tapered Point

Adhesive Air Terminal with Safety Ball

A component of a lightning protection

system that is intended to intercept lightning

flashes.

Air Terminals/Strike Termination Devices

Page 71: Lightning Protection

Materials:

Copper

Nickel Plated Copper

Lead Coated Copper

Aluminum

Stainless Steel

BEWARE OF DISIMILAR METALS!!

Air Terminals/Strike Termination Devices

Page 72: Lightning Protection

Type of Air Terminal Parameter Copper Aluminum

Solid Diameter 3/8” 1/2”

Tubular Diameter 5/8” 5/8”

Tubular Wall Thickness Wall Thickness .033” .064”

Type of Air Terminal Parameter Copper Aluminum

Solid Diameter 1/2” 5/8”

Class I Material Requirements

Class II Material Requirements

Air Terminals/Strike Termination Devices

Page 73: Lightning Protection

Type of Conductor Parameter Copper Aluminum

Main Conductor, Cable Size – Each Strand 17 AWG 14 AWG

Weight per length 187#/1000’ 95#/1000’

Cross Sectional Area 57,400 cm 98,600 cm

Bonding Conductor, Cable Size – Each Strand 17 AWG 14 AWG

(solid or stranded) Cross Sectional Area 26,240 cm 41,100 cm

Bonding Cond. Solid Strip Thickness .051” .064

Width 1/2” 1/2”

Thickness .051” .064

Cross Sectional Area 57,400 cm 98,600 cm

Class I Material Requirements

Lightning Protection Cable

Page 74: Lightning Protection

Type of Conductor Parameter Copper Aluminum

Main Conductor, Cable Size – Each Strand 15 AWG 13 AWG

Weight per length 375#/1000’ 190#/1000’

Cross Sectional Area 115,000 cm 192,000 cm

Bonding Conductor, Cable Size – Each Strand 17 AWG 14 AWG

(solid or stranded) Cross Sectional Area 26,240 cm 41,100 cm

Bonding Cond. Solid Strip Thickness .051” .064”

Width 1/2” 1/2”

Thickness .064” .1026”

Cross Sectional Area 115,000 cm 192,000 cm

Class II Material Requirements

Lightning Protection Cable

Page 75: Lightning Protection

Protection of Ordinary Structures: GENERAL

• Structures not exceeding 75 feet – Class I• Structures exceeding 75 feet – Class II

• If a portion of the building exceeds 75 feet, then that portion of the building shall only have Class II material. The remaining building can have Class I material.

• The Class II material shall be extended to ground level and interconnected with the balance of the system.

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 76: Lightning Protection

Protection of Ordinary Structures: ROOF SLOPES

• Pitched roof shall be defined as:

• Having a span of 40 feet or less and a slope of 1/8 or greater.• Having a span of more than 40 feet and a slope of ¼ or greater.

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 77: Lightning Protection

Protection of Ordinary Structures: ROOF SLOPES

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 78: Lightning Protection

Protection of Ordinary Structures: AIR TERMINALS

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 79: Lightning Protection

Protection of Ordinary Structures: AIR TERMINALS

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 80: Lightning Protection

Protection of Ordinary Structures: AIR TERMINALS

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 81: Lightning Protection

Protection of Ordinary Structures: AIR TERMINALS

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 82: Lightning Protection

Protection of Ordinary Structures: CABLE BENDS

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 83: Lightning Protection

Protection of Ordinary Structures: DOWN LEADS

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 84: Lightning Protection

Protection of Ordinary Structures: GROUNDING

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 85: Lightning Protection

Apprenticeship School

Page 86: Lightning Protection

Apprenticeship School

Page 87: Lightning Protection

Apprenticeship School

Page 88: Lightning Protection

Apprenticeship School

Page 89: Lightning Protection

Apprenticeship School

Page 90: Lightning Protection

Apprenticeship School

Page 91: Lightning Protection

Apprenticeship School

Page 92: Lightning Protection

Apprenticeship School

Page 93: Lightning Protection

Apprenticeship School

Page 94: Lightning Protection

Apprenticeship School

Page 95: Lightning Protection

Apprenticeship School

Page 96: Lightning Protection

Surge Protection Devices

Page 97: Lightning Protection

Compliant SPD for UL Master Label

UL1449 Ed. 3 – In = 10ka

UL96A - In = 20ka

Page 98: Lightning Protection

Protection of Heavy Duty Stacks:

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 99: Lightning Protection

Mast and Overhead Ground Wires:

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 100: Lightning Protection

Mast and Overhead Ground Wires:

NFPA® 780-2011

NFPA is a registered trademark of National Fire Protection Association, Inc.

Page 101: Lightning Protection

Inspection and Maintenance of a lightning protection system:

•Annual visual inspections

•Thoroughly inspected every 5 years

Inspection and Maintenance

Page 102: Lightning Protection

National Fire Protection Assoc. # 780 Annex D

Underwriters’ Laboratories # 96A UL Master Label Letter of Findings

Lightning Protection Institute # 175 LPI Reconditioned Master Installation Certificate LPI Limited Scope Inspection

Maintenance of a LP System

Page 103: Lightning Protection
Page 104: Lightning Protection
Page 105: Lightning Protection
Page 106: Lightning Protection

Maintenance of a LP System

Page 107: Lightning Protection

Maintenance of a LP System

Page 108: Lightning Protection

Maintenance of a LP System

Page 109: Lightning Protection

Maintenance of a LP System

Page 110: Lightning Protection

Maintenance of a LP System

Page 111: Lightning Protection

IEEE 998 - 2012

Page 112: Lightning Protection

IEEE 998 - 2012

Page 113: Lightning Protection

IEEE 998 – 2012

Page 114: Lightning Protection

IEEE 998 – 2012

2 designs methods which have been used to protect substations from direct lightning strokes:

• Fixed Angles• Empirical curves

•CVM – Collection Volume Method

Page 115: Lightning Protection

IEEE 998 - 2012

Fixed Angle:

It was recognized that the area protected by a lightning rod was bound by a curved surface rather than a fixed plane.

More than likely the fixed angle was used as a convenience to determine the approximation of the boundaries against lightning strikes.

The angles used: approximately 30/45 degrees.

Page 116: Lightning Protection

IEEE 998 - 2012

Page 117: Lightning Protection

IEEE 998 - 2012

Page 118: Lightning Protection

Installations can be expensive Coverage area of any one mast is small Limited coverage by static wires/masts Risk of static wire failure

Disadvantages of Fixed Angle/Mast Sys.

Page 119: Lightning Protection

Collection Volume Method (CVM)

Page 120: Lightning Protection

Collection Volume Method (CVM)

Applied to 3D structures from original work of Dr A.J. Eriksson (1979, 1987)

The CVM is simply a physically-based, improved Electrogeometric Model.

Improved striking distance relationship:

ds = function (Ki, Ip)

where Ki is the field intensification factor near the prospective strike point (structure, structural feature or air terminal).

Page 121: Lightning Protection

Collection Volume Method (CVM)

S t r i k i n g D i s t a n c e

D o w n w a r d le a d e r

S t r i k in gd is ta n c e

R e s p o n d in gu p - le a d e r

G r o u n d

A

C

B

d Is p 1 0 0 6 5.

Page 122: Lightning Protection

Collection Volume Method (CVM)

Collection Volume Method

Downwardleader

Collectionvolume

Ground

AC

B

The CVM is a physically-based, improved version of the ElectrogeometricModel with added constraints to ensure the design is safe.

Key parameters: downleader Q or Ipeak

field intensification factor velocity ratio site altitude

1Striking distance

surface

Improved striking distance relationship: ds = function (Ki, Ip)

Velocity-derivedlimiting locus

2

- ratio of downward to upward leader velocity

- height of strike point (hence Ki)

Page 123: Lightning Protection

Collection Volume Method Application

(a) Key parameters downward leader charge or peak current field intensification

factor velocity ratio site altitude

(b) Example of CVM design output

Page 124: Lightning Protection

Application of the CVM to 3D Structures

Page 125: Lightning Protection

Application of the CVM to 3D Structures

Page 126: Lightning Protection

Application of the CVM to 3D Structures

Page 127: Lightning Protection

Strike Current (X)

Level of Protection (Y) Exceedance Probability

2.9 kA Level I – Very High 99%

5.4 kA Level II – High 97%

10.1 kA Level III – Medium 91%

15.7 kA Level IV - Low 84%

The protection zone provided by the air termination shall be such that it becomes the preferred strike point for all discharges exceeding a peak amplitude return strike current of “X” kA according to the statistical level “Y”.

Application of the CVM to 3D Structures

Page 128: Lightning Protection

For strikes below the specified kA level, some or all of these low-intensity strikes may not be captured by the system. This is an accepted part of the risk management principles that apply to all lightning protection systems.

Comparison of the Dynasphere protection levels vs. the EGM model striking distance computed for substations per First Energy’s LP guidelines.

Application of the CVM to 3D Structures

Page 129: Lightning Protection

Advantages

vs. static wire if strike bypasses from the side, CVM will intercept.

Larger protection area. Protect skater antenna and control house.

Dis-Advantages

Cannot get inspected by 3rd party (UL – LPI)

Application of the CVM to 3D Structures

Page 130: Lightning Protection

French Standard ESE Terminals

Controlled Leader Trigger System (CLT)

Other Types of Lightning Protection

Page 131: Lightning Protection

French Standard ESE Terminals

Other Types of Lightning Protection

Page 132: Lightning Protection

Designed to meet:NFC17-102

Available in three models : -

25 m/s40 m/s60 m/s

French Standard ESE Terminals

Page 133: Lightning Protection

T measured in Lab. Test defined by NFC17-102

Simple Linear Function of L = v * T

Protection Radius Rp proportional to the value of L

NFC17-102 Application

Page 134: Lightning Protection

NFC17-102 Application

Page 135: Lightning Protection

Thank you for your time!