  • I nsu la t ion

    Kingspan Cavity Closer & Kingspan Cavity Closer

    CI/Sfb

    Second Issue October 2011

    (31-9) Hn6 M2

    � Continuous insulation – maintains a continuous insulated cavity closer around window and door openings

    � Passes one–hour fire test with PVC window and up to 150 mm cavities

    � Passes half-hour fire test with PVC window and up to 300 mm cavities

    � Simplified construction – avoids the need for cut bricks, blocks or special reveal blocks

    � Reduced heat loss – avoids thermal bridging, condensation and mould growth

    � Weather resistant – forms an integral DPC

    � Flexible – can either be built in with frames or used to pre–form openings when frames are fitted later

    � Unaffected by air infiltration � Easy to handle and install � Non–deleterious material � Insulation core manufactured

    with a blowing agent that has zero ODP and low GWP

    Low Energy - Low Carbon Buildings

    INSULATED EXTRUSIONS FOR CLOSING WALL CAVITIES AT OPENINGS

  • 2

    Design Considerations

    Introduction

    Thermal Bridging – Basic Principles Thermal bridging occurs at openings in external walls when the cavities are closed with materials of poor insulating performance.

    Such thermal bridging can produce problems of condensation and mould growth at the reveals of these openings. Prolonged exposure to condensation will lead to the deterioration of plaster and paintwork.

    Typical Design Detail

    Heat Loss Paths Around a Typical Window Opening – Traditional Construction

    A Local Drop in the Surface Temperature Around Openings, or ‘Thermal Bridging’, Can Give Rise to Unsightly Mould Growth and Damage to Reveal Finishes.

    Window unit

    Masonry inner leaf

    Masonry outer leaf

    Kingspan Kooltherm®

    K8 Cavity Board

    Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm®

    Cavity Closer PLUS

    Kingspan Kooltherm® Cavity Closer is a PVC–U extrusion with a rigid thermoset insulation core, manufactured with a blowing agent that has zero Ozone Depletion Potential (ODP) and low Global Warming Potential (GWP). It is manufactured in thirteen sizes from 50–150 mm. Jointing clips extend the range further by allowing the Kingspan Kooltherm® Cavity Closer sections to be joined to suit cavity widths of up to 300 mm. It is suitable for use with timber, metal or PVC window frames and can also be supplied to order in curved sections.

    Kingspan Kooltherm® Cavity Closer provides a simple and efficient method of closing cavities around openings in cavity walls. Its rigid thermoset insulation core prevents thermal bridging, and its PVC–U J–section forms a positive damp proof barrier and key for the direct application of plaster. It effectively prevents condensation and mould growth, frequently associated with traditional methods of closing cavities.

    Kingspan Kooltherm® Cavity Closer PLUS is made to order, and comprises Kingspan Kooltherm® Cavity Closer sections, prefabricated into a U-shape, to match specified opening sizes.

    Kingspan Kooltherm® Cavity Closer PLUS is available for the same range of cavity widths as standard Kingspan Kooltherm®

    Cavity Closer and helps you to achieve accurate opening sizes.

    Specification Clause Kingspan Kooltherm® Cavity Closer should be described in specifications as:–

    The insulated cavity closer shall be Kingspan Kooltherm®

    Cavity Closer __*: comprising a one piece, rigid, J-section, PVC–U extrusion, with flange keys for direct plaster application, projecting fixing flange, and premium performance rigid thermoset insulation core. The insulation component of the product shall be manufactured with a blowing agent that has zero Ozone Depletion Potential (ODP) and low Global Warming Potential (GWP). The product shall be manufactured under a management system certified to BS / I.S. EN ISO 9001: 2008, BS / I.S. EN ISO 14001: 2004 and BS / I.S. OHSAS 18001: 2007; by Kingspan Insulation Limited; and installed in accordance with the instructions issued by them.

    *Insert product width.

    NBS Specifications NBS users should refer to clause: F30 180 (Standard and Intermediate) F30 18 (Minor works)

  • 3

    Accredited Construction Details Background Regulators have recognised the issue of thermal bridging around openings and the significant effect that it can have on both heat loss and building degradation. The route chosen to deal with this issue has been to produce a set of details which are deemed to be of an acceptable standard. These have been published in documents entitled “Accredited Construction Details” and “Accredited Construction Details (Scotland)”.

    Compliant Detail for Scotland Using Kingspan Kooltherm® Cavity Closer

    Compliant Detail for England & Wales Using Kingspan Kooltherm® Cavity Closer

    Temperatures and Heat Flows from Numerical Modelling of Compliant Detail for England & Wales

    Min. 30 mm overlap

    Temperatures and Heat Flows from Numerical Modelling of Compliant Detail for Scotland

    England & Wales A minimum thermal resistance path through the cavity closer of 0.45 m2.K/W and a minimum overlap of 30 mm between the window frame and the cavity closer are required by the Accredited Construction Details publication in order to gain compliance with the Approved Documents L in England & Wales. A 30 mm overlap between the window frame and the Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity Closer PLUS will exceed the minimum thermal resistance path of 0.45 m2.K/W.

    Scotland Accredited Construction Details (Scotland) shows only a check reveal for compliance with the Technical Handbooks in Scotland. There is no minimum thermal resistance path or overlap as this is not necessary with a check reveal.

  • 4

    Design Considerations

    Compliant Details An infinite variety of constructions can be formed with the use of Kingspan Kooltherm® Cavity Closer and Kingspan Kooltherm® Cavity Closer PLUS . The following details illustrate the design flexibility of Kingspan Kooltherm® Cavity Closer and Kingspan Kooltherm® Cavity Closer PLUS .

    All of the following details comply with the principles outlined in Accredited Construction Details or Accredited Construction Details (Scotland).

    Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity Closer PLUS at Reveal

    Masonry inner leaf

    Masonry outer leaf

    Kingspan Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity

    Closer® PLUS

    Frame Fitted Later

    Use of Jointing Clip in Wide CavityUse of Optional Fixing Tie

    Frame strap fixed to inner leaf

    Extra wide cavity

    DPC

    Two Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity

    Closer PLUS sections coupled together with

    100 mm sections of Jointing Clip at 300 mm centres

    Fixing ties engaging Kingspan Kooltherm®

    Cavity Closer or Kingspan Kooltherm®

    Cavity Closer PLUS and built in as work proceeds

    Plaster finish keyed to Kingspan Kooltherm®

    Cavity Closer or Kingspan Kooltherm®

    Cavity Closer PLUS

    Min. 30 mm overlap

    Min. 30 mm overlap

    Min. 30 mm overlap

    Min. 30 mm overlap

    Window unit

    It should be noted however that, although any detail can be used in England and Wales in exposure zones 1 and 2, only a check reveal can be used in England and Wales in exposure zones 3 and 4 and in Scotland (see page 5 left hand column for check reveal detail).

  • 5

    Use with Sub Cill & Check Reveal

    DPC

    Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity Closer PLUS at Head

    Masonry outer leaf

    Masonry inner leaf

    Window unit

    Kingspan Kooltherm® Cavity Closer or

    Kingspan Kooltherm® Cavity Closer PLUS

    Use at Cill with Flush Reveal & 30 mm Overlap

    Oversailing window board

    Masonry inner leaf

    Masonry outer leaf

    Window frame and cill

    Check Reveal

    Min. 30 mm overlap

    Min. 30 mm overlap

    Min. 30 mm overlap

    Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity Closer

    PLUS fixed to outer leaf

    Frame strap fixed to inner leaf

  • 6

    Selecting a Section � The width of cavity to be closed will decide the size of

    section, or combination of sections to be used.

    � Kingspan Kooltherm® Cavity Closer and Kingspan Kooltherm® Cavity Closer PLUS are normally fixed with their flange against the inner leaf as shown.

    Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity Closer PLUS with check reveal

    Kingspan Kooltherm® Cavity Closer or Kingspan Kooltherm® Cavity Closer PLUS with flush reveal

    Basic Installation Principles for New Walls � Kingspan Kooltherm® Cavity Closer and Kingspan

    Kooltherm® Cavity Closer PLUS can be built–in as work proceeds.

    � Kingspan Kooltherm® Cavity Closer fixing ties slot into the cavity side of the profile and key into the mortar bed of the outer masonry skin.

    NB Fixing ties can not be used when two sections are joined back to back.

    Sitework

    � An appropriate lintel and damp proof course is incorporated at the head.

    � Where an insulated lintel is used a head closer section will not be required and the jamb sections of closer will butt up against the lintel. If required, a Kingspan Kooltherm® Cavity Closer section can be used at the head where a separa