Itron Metering Pocket Guide i

This document contains trade secrets and confidential information of Itron, Inc., which are not to be divulged to third parties and may not be reproduced or transmitted in whole or part, in any form or by any means, electronic or mechanical for any purpose, without the express written permission of Itron, Inc. All rights to designs or inventions disclosed herein, including the right to manufacture, are reserved to Itron, Inc.

The information contained in this document is subject to change without notice. Itron, Inc. reserves the right to change the product specifications at any time without incurring any obligations.

CENTRON, FULCRUM, QUANTUM, VECTRON, SENTINEL, and PC-PRO+ are registered trademarks of Itron, Inc.

Page 3: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide ii

This Metering Pocket Guide is intended as a quick reference for currently produced CENTRON®, CENTRON Polyphase and SENTINEL® meter functions. It does not encompass all of the functionality of these meters. For more details, see the appropriate Technical Reference Guide:

Technical Reference Guide Stock Number

CENTRON Meter Technical Reference Guide 100299GM-xx

CENTRON Polyphase Meter Technical Reference Guide 100690GM-xx

SENTINEL Meter Technical Reference Guide 100300GM-xx

CENTRON II C12.19 Residential Meter Technical Reference Guide TDC-0989-xx

Where xx = the latest revision.

Page 4: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide iii

Table of Contents

Meter Product Page

Software Matrix 1

CENTRON Meter Pocket Guide 9

CENTRON Polyphase Meter Pocket Guide 41

SENTINEL Meter Pocket Guide 81

Page 5: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide iv

Page 6: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 1

Software Matrix

Device

Devices Supported by Software Product (as of June 2011)

PC-P

RO

+ (1

6 B

it)

3.5

– 3.

5.3

PC

-PR

O+

Adv

ance

d 9.

70

PC

-PR

O+

Vie

ws

9.70

Sho

p-P

ro 9

.70

HH

-PR

O 8

.0

Fiel

d-P

ro 9

.70

Ener

gyA

udit

4.30

100 Series Yes No No No No No No

200 Series Yes Yes(1) Yes(R) Yes Yes Yes No

CENTRON Yes Yes Yes(R) Yes Yes Yes No (1): Initialize with imported programs (R): Read Only

Page 7: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 2

Device

Devices Supported by Software Product (as of June 2011)

PC-P

RO

+ (1

6 B

it)

3.5

– 3.

5.3

PC-P

RO

+ A

dvan

ced

9.70

PC-P

RO

+ Vi

ews

9.70

Shop

-Pro

9.7

0

HH

-PR

O 8

.0

Fiel

d-Pr

o 9.

70

Ener

gyA

udit

4.30

CENTRON C12.19 (1) No Yes Yes(R) Yes Yes Yes No

CENTRON II C12.19(2) No Yes No No No Yes No

CENTRON V&I No Yes Yes(R) Yes Yes Yes No

DATA STAR® Yes No No No No No No

FULCRUM® SL320 Yes Yes(3) Yes(R) Yes No No Yes(R) (1): Refer to PIL EL-P09-682 for more details about PC-PRO+ Advanced 9.60 (2): Requires PL-PRO Advanced 9.70 or higher (3): Initialize with imported programs (R): Read Only

Page 8: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 3

Device

Devices Supported by Software Product (as of June 2011)

PC-P

RO

+ (1

6 B

it)

3.5

– 3.

5.3

PC-P

RO

+ A

dvan

ced

9.70

PC-P

RO

+ Vi

ews

9.70

Shop

-Pro

9.7

0

HH

-PR

O 8

.0

Fiel

d-Pr

o 9.

70

Ener

gyA

udit

4.30

FULCRUM® SQ400 Yes Yes(R) Yes(R) Yes(R) No No Yes(R)

QUANTUM® Yes Yes(R) Yes(R) Yes(R) No No Yes(R)

QUANTUM Q1000 No Yes Yes(R) Yes No No Yes(R)

SENTINEL® No Yes Yes(R) Yes Yes Yes Yes(R)

VECTRON® Yes Yes(*) Yes(R) Yes Yes Yes Yes(R) (*): No PRO-READ or Factory exports available for VECTRON (R): Read Only

Page 9: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 4

Operating System

Software Qualified on Operating Systems (as of June 2011)

PC-P

RO

+ (1

6 B

it)

3.5

– 3.

5.3

PC-P

RO

+ A

dvan

ced

9.70

PC-P

RO

+ Vi

ews

9.70

Shop

-Pro

9.7

0

HH

-PR

O 8

.0

Fiel

d-Pr

o 9.

70

Ener

gyA

udit

4.30

DOS® 6.22 No No No No No No No

Windows® 3.1 No No No No No No No

Windows NT 3.51 No No No No No No No

Windows NT 4.0 SP6.0+ Yes(**) No No No No No Yes

Windows 95 Yes Yes No No No Yes No (**): For PC-PRO+® 3.5 - 3.53 to function properly, Microsoft® Security Patch MS04-012 (KB828741)

must be installed

Page 10: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 5

Operating System

Software Qualified on Operating Systems (as of June 2011)

PC-P

RO

+ (1

6 B

it)

3.5

– 3.

5.3

PC-P

RO

+ A

dvan

ced

9.70

PC-P

RO

+ Vi

ews

9.70

Shop

-Pro

9.7

0

HH

-PR

O 8

.0

Fiel

d-Pr

o 9.

70

Ener

gyA

udit

4.30

Windows 98 SE No No No No No No No

Windows Me No No No No No No No

Windows 2000 Professional No Yes Yes Yes Yes Yes Yes

Windows XP Professional SP2 (32 bit) No Yes Yes Yes Yes Yes Yes

Windows XP Professional SP2 (64 bit) No Yes No No No Yes No

Page 11: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 6

Operating System

Software Qualified on Operating Systems (as of June 2011)

PC-P

RO

+ (1

6 B

it)

3.5

– 3.

5.3

PC-P

RO

+ A

dvan

ced

9.70

PC-P

RO

+ Vi

ews

9.70

Shop

-Pro

9.7

0

HH

-PR

O 8

.0

Fiel

d-Pr

o 9.

70

Ener

gyA

udit

4.30

Windows Vista Professional (32 bit) No Yes Yes Yes Yes Yes No

Windows Vista Professional (64 bit) No Yes No No No Yes No

Windows 7 (32 bit) No Yes Yes Yes Yes Yes No

Windows 7 (64 bit) No Yes No No No Yes No

Page 12: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 7

Notes:

Page 13: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron
Page 14: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 9

CENTRON Meter

Page 15: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 10

CENTRON Meter Forms Available Metrology Class Number of

Elements Number of

Wires Voltage Test

Amps

1Sa 100 1 2 120 15

2S 200 1.5 3 240 30

320 1.5 3 240 50

3S 20 1 2 240 2.5

20 1 2 120 2.5

4S 20 2 3 240 2.5

12S Network 200 2 3 120 30

25S 200 2 3 120 30 a "S" = Socket Base

Page 16: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 11

CENTRON Type Codes 1st Generation

CRegister Functionality

= kWh onlyC = CellNetD = DemandL = Load ProfileR = R300T = TOUX = Metrology only

Example :

1 SProduct Family

C = CENTRON

Metrology Generation1 = 1st Generation

Base StyleS = SocketA = A- base

R 2 = 2 ERTsR 3 = 3 ERTs

C1SLR2 = CENTRON C12.19 Load Profile Meter equipped with 2 ERTs

Page 17: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 12

CENTRON Type Codes 2nd Generation

C

System = kWh onlyC = CellNetD = DemandL = Load ProfileR = R300T = TOUX = Metrology only

2 SProduct FamilyC = CENTRON

Metrology Generation

1 = 1st Generation (pulse)

Base StyleS = SocketA = A-base

= Standard

2 = nd Generation(blurt)

2

N

Optional= Singlephase

P = PolyphaseN = Network

Option Module Type

O

O = OpenWay

PD

P PLAN

Meter Type = StandardD = DisconnectR = Cell Relay, GPRS, Ethernet, GPRS+ EthernetX = Third Part Comm

=

Page 18: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 13

CENTRON Label Description

Page 19: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 14

CENTRON C12.19 Meter Indicators

Page 20: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 15

CENTRON C12.19 D/T/L Meter LCD Display The CENTRON C12.19 D/T/L meter features a versatile ANSI C12.10 compliant, 104 segment liquid crystal display (LCD). The LCD module may be programmed with the following digit and multiplier settings: 4x1, 4x10, or 5x1. A nine-digit LCD, with a variety of annunciators, is provided on these multifunction personality modules.

Page 21: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 16

Static Indicators Indicator Description

888 888888 Nine digits (7 segments each) for display of alphanumeric information

EOI End of Interval—(Registers - Dmd)

VA, VB, VC Indicators for phase voltage (not applicable in C12.19 meters) are present during segment check

Watt Disk Emulator - scrolls right for positive; scrolls left for negative

120 240 277 480 Nominal Voltage Indicator (not applicable in C12.19 meters) are present during segment check

Scr Loc Scroll Lock (indicates temporary scroll lock of a display item)

SEL nor, SEL Alt Selection of Normal or Alternate sequence

Page 22: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 17

Static Indicators Indicator Description

nor diSP Entry into Normal Mode.

TEST Entry into Test Mode.

Note: The indicators shown in the table above actually display in a digital readout font; some characters may display as upper case. The Watt Disk Emulator does not appear for segment check.

Page 23: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 18

CENTRON C12.19 D/T/L Meter Load Indicators

The watt disk emulator can represent the delivered or received power as follows:

Segment Progression for Delivered Power

Segment Progression for Received Power

Where Kh = 1 Wh per pulse

Page 24: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 19

Demand Reset Button There are two methods of triggering a demand reset. When the Demand Reset Button is pressed, a demand reset is immediately performed. A demand reset can also be done using the system programming software communicating directly with the meter when logged on.

The following actions occur with a demand reset: 888 888888 is displayed on the LCD. The demand registers are processed and reset. The Demand Reset Count is incremented. A self read “snapshot” occurs. The meter can be programmed with a demand reset lockout time. This is the minimum time required to pass between demand resets configurable from 0 to 255 minutes. If a demand reset is attempted before this amount of time elapses since the last demand reset, the meter will not reset demands. This lockout time does not apply to software initiated demand resets. Also, if the Demand Reset Button has been programmed to be disabled, the meter will not perform a demand reset when the button is pushed.

Page 25: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 20

Three-Button Reset WARNING! Performing this function clears: Billing Data Meter Program Security Codes To perform a three-button reset: 1 Remove power from the meter. 2 Remove the outer cover from the meter. 3 Simultaneously hold down the Test Button and the Demand Reset Button, while holding a magnet at the

nine o'clock position on the meter. Note: The Test Button, Demand Reset Button, and magnet position are shown on CENTRON C12.19 Meter Indicators (on page 14). On older C1SD/T/L meters, the magnetic switch is located at the 10 o'clock position.

4 While holding the buttons and magnet in place apply power to the meter. Once you see "3BReset" or "nordiSP" on the display, release both buttons and remove the magnet.

The three-button reset is complete.

Page 26: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 21

Magnetic Switch The magnetic switch allows for manual switching between display modes as well as scroll lock of display items. To activate the magnetic switch, hold the magnet to the Magnetic Switch (see "CENTRON C12.19 Meter Indicators" on page 14). Older C1SD/T/L meters have a magnetic switch at the 10 o'clock position.

To switch between different display modes, hold the magnet in place for 5 seconds. The meter display will show one of the following:

selnor

selAlt

When the display shows the mode you want, remove the magnet. To activate the scroll lock, hold and release the magnet. “ScrLoc” will appear on the meter display. Apply and release the magnet again to step through the selected meter display.

Page 27: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 22

Test Mode Button The Test Mode button is located at the 3 o'clock position on the meter register under the meter outer cover. Pressing the button activates Test Mode. Pressing the button again will exit Test Mode and activate the Normal display.

Note: If the TEST button has been programmed to be disabled, the meter will not enter Test Mode when the button is pressed.

Page 28: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 23

Display Modes Normal Display Mode

The Normal Display Mode is the default display when the meter is energized and when the meter is in Normal Operating Mode.

Alternate Display Mode

The Alternate Display Mode is functionally identical to the Normal Mode. The meter itself still operates under normal measurement, but the display sequence can be programmed to show a different set of displayable items from those in the Normal Display Mode. While in Alternate Display Mode, the letters “ALT” appear on the LCD to designate activation of the Alternate Display Mode. Upon completion of the Mode Timeout period, the meter automatically returns to the Normal Display Mode.

Page 29: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 24

Test Display Mode

The Test Mode can be accessed from either the Normal or Alternate Mode by removing the meter cover and pressing the Test button. To activate this mode with a programming device, refer to the appropriate software user’s manual. The Test Mode annunciator, “TEST” is displayed while the CENTRON meter is in Test Mode. In Test Mode, normal metering stops and Test Mode registration begins.

Display Mode Timeout

When the display is put into display modes other than Normal display (Alternate, Scroll Lock, or Test display modes), the meter will return to normal operation after a programmable Mode Timeout expires. The Mode Timeout can be configured from 1 to 255 minutes using the meter programming software.

Page 30: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 25

Three Ways to Test 1. Test using infrared pickup

• Place sensor on light pipe (top of meter) • Program test board according to table.

Refer to the CENTRON Test Board Parameters table.

• Remember: Kh = 1.0

2. Test using pulse detector • Place sensor on light pipe • Use x1 light for light loads and x10 light

for heavy loads 3. Test using disk emulator on LCD

• Each change of state of disk emulator is equal to 1 Wh

• Direction of disk emulator shows power flow direction (forward or reverse)

Page 31: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 26

CENTRON Pulse Detector Converts infrared pulse to visible light. Gives quick indication of load.

Page 32: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 27

CENTRON Test Board Parameters Recommended # of pulses for CENTRON on Test Board

1S, 2S CL200 3S, 4S CL20 12S/25S, 2S CL320

FL 10 7 15

LL 10 6 7

PF 10 7 12

Page 33: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 28

Programming Tips R300CD/CD3 For complete details refer to CENTRON R300CD/CD3 Quick Install Guide document.

Note: These instructions are given assuming a CENTRON (C12.19) program is open in PC-PRO+ Advanced. 1 Energy and Demand measurements need to be selected from the Quantity Selections menu in Program

Editor. 2 Quantities desired for transmission can be selected from the drop down menu in the RF Configuration

component. NOTE: If IDM is enabled, then register1 must be a non-net energy.

3 Logon to the meter: Program Editor/ Communications/Logon/ Set Serial Baud Rate to 9600.

Page 34: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 29

Error Codes (Applicable Only to C12.19 C1SD, C1ST, & C1SL) Non-Fatal Errors

Non-fatal errors can be programmed to scroll during one second display off-time or lock on the meter display. If multiple non-fatal errors occur, the meter will display a combined error message. For non-fatal errors, RF transmission can be controlled via PC-PRO+ Advanced software.

Low Battery Error

Error Code Possible Cause(s) Err 1----- • Battery Voltage Low

• Battery Not Connected Properly

Recommended Action

Once a low battery is detected, the daily battery voltage tests will be halted and a battery present test will be run every second. A low battery continues to function; however, its reliability decreases over time. As long as the meter is not powered down with a dead or missing battery, the meter will continue to function as normal. If the meter is powered down with a dead or missing battery, then, when power is restored, the meter's clock will be off by the duration of the outage, and Load Profile and TOU will be halted.

Page 35: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 30

Time-of-Use (TOU) Error

Error Code Possible Cause(s) Err --3--- • Current Season is not programmed

• Current Year is not programmed • TOU halted due to power down with dead or missing battery

Recommended Action This is tested at power-up, at midnight crossings, at season changes, upon reconfigures and upon set clocks. Depending on the cause of the error, it can be cleared with a corrective reconfigure or with a set clock with a good battery present.

Page 36: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 31

Reverse Power Error

Error Code Possible Cause(s) Err ---4-- The configured reverse power threshold has been reached.

Recommended Action Reverse power is tested every second and an accumulator for it is maintained. If power is delivered during the second, then the accumulator is cleared. If power is received during the second, then the accumulator is incremented. If the accumulator reaches the configured reverse power threshold, then the error is triggered. A Demand Reset will clear this error.

Page 37: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 32

Clock/Load Profile Error

Error Code Possible Cause(s) Err ----5- Clock or Load Profile error detected.

Recommended Action This is tested upon power-up. A set clock with a good battery present will clear this error. Be sure to read the Load Profile data prior to setting the clock to clear the error. The dead battery will cause some invalid intervals at the end of the data. When the error is cleared, Load Profile will be restarted from the beginning to purge the bad data.

Page 38: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 33

Full Scale Overflow Error

Error Code Possible Cause(s) Err -----6 The calculated W delivered demand at an EOI exceeded the configured full

scale value. Recommended Action

This error is checked upon every Demand EOI, set clock, demand reset, enter Test Mode, and power-up. If the meter is configured for Max W Del, then that value is compared to the programmed threshold. The fullscale overflow error displays after the interval during which the overflow occurred. The maximum demand register continues to accumulate and display kW as long as the format limitations are not exceeded. If a full scale overflow occurs, check the installation to ensure that the current capacity of the meter has not been exceeded. A full scale overflow error in no way affects the existing billing data. This error will clear when a demand reset is performed.

Page 39: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 34

Fatal Errors

Fatal errors cause the display to lock on the error code because of the possibility that billing data may have been corrupted or that the meter may not be operating correctly. If multiple fatal errors occur, the one with the lowest number will be the error code that locks on the display.

The CENTRON C12.19 meter will check for fatal errors: when a meter reconfigure is performed. when power is initially energized and upon future power restoration. while performing key operations. Fatal errors are cleared when they are corrected by the factory and the meter is reprogrammed.

Page 40: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 35

MCU Flash Error

Error Code Possible Cause(s) FAtError1 The meter has detected a problem with the program memory.

Recommended Action If this error occurs, program the meter and check for proper operation. If the error continues to exist, return the meter to the factory for repair.

RAM Error

Error Code Possible Cause(s) FAtError2 The meter has detected a problem with the RAM.

Recommended Action If the meter detects a RAM problem, return the meter to the factory for repair.

Page 41: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 36

Data Flash Error

Error Code Possible Cause(s) FAtError3 The meter has detected a problem with the data flash.

Recommended Action If this error occurs, program the meter and check for proper operation. If the error continues to exist, return the meter to the factory for repair.

Page 42: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 37

Front End Processor Error

Error Code Possible Cause(s) FATError4 A problem has occurred with the metrology portion of the meter.

Recommended Action Return the meter for repair.

Power Down Error

Error Code Possible Cause(s) FATError5 A problem has occurred while saving billing data at time of a power outage.

Recommended Action The billing data has been corrupted. Factory Reset the meter, reprogram the meter and check for proper operation, including several power cycles. If the error continues to exist, return the meter for repair.

Page 43: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 38

File System Error

Error Code Possible Cause(s) FATError6 A problem has occurred with the file system.

Recommended Action Return the meter for repair.

Operating System Error

Error Code Possible Cause(s) FATError7 A problem has occurred with the operating system.

Recommended Action Return the meter for repair.

Page 44: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 39

Error Codes (Applicable Only to C1S & C1SR) Fatal errors happen when an unsuccessful writing to or reading from EEPROM memory occurs or it could also be a metrology error. All metering and RF functions are halted. The LCD will display the word Error on the area normally used for energy accumulation and the module will have to be returned to the factory for repair.

Page 45: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 40

Notes:

Page 46: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 41

CENTRON Polyphase Meter

Page 47: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 42

CENTRON Polyphase Meter Forms Available Socket Meter Forms

Metrology Class Number of Elements

Number of Wires

Voltage Test Amps

9S(8S) 20 3 4 120-480 2.5

9S(8S)/36S 20 3 4 120-480 2.5

11S 20 3 4 120-480 2.5

12S 200 2 3 120-480 30

12S 320 2 3 120-480 50

16S(14S, 15S, 17S)

200 3 4 120-480 30

16S(14S, 15S, 17S)

320 3 4 120-480 50

45S(5S) 20 3 3 120-480 2.5

Page 48: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 43

A-base Meter Forms

Metrology Class Number of Elements

Number of Wires

Voltage Test Amps

10A(9A) 20 3 4 120-480 2.5

16A(14A, 15A, 17A) 150 3 4 120-480 30

45A(5A) 20 2 3 120-480 2.5

46A(6A) 20 2.5 4 120-480 2.5

Page 49: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 44

CENTRON Polyphase Type Codes

Code Description

C Product Family: C = CENTRON

P Metrology Type: P = Polyphase

1 Metrology Generation: 1 = 1st Generation

S Base Style: S = Socket; A = A-base

_ Register Functionality: Blank = kWh Only; D = Demand; L = Load Profile; R = R300; T = TOU; X = Metrology Only

_ If R300 CD/CD3: R2 = 2 ERTs; R3 = 3 ERTs

Note: R300: 1 ERT (type 07) with IDM (24) and PON/PRN. R2: 2 ERTs (type 04) with no IDM. R3: 3 ERTs (type 08) with IDM (24).

Page 50: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 45

CENTRON Polyphase Type Code Examples:

CP1SD = CENTRON Polyphase Meter with Demand

CP1ST = CENTRON Polyphase Meter with Demand and TOU

CP1SL = CENTRON Polyphase Meter with Demand, TOU and Load Profile

Page 51: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 46

CENTRON Polyphase Label Description

Page 52: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 47

CENTRON Polyphase - Three Ways to Test 1. Test using infrared pickup

• Place sensor on light pipe (top of meter) • Program test board according to table in CENTRON

Polyphase Technical Reference Guide. CP1S, CP1SR: CL20 Kh = 1.0 CL200/CL320 Kh = 10.0 CP1SD/T/L: Kh = Programmable

2. Test using pulse detector (Part Number 442444-001) • Place sensor on light pipe • Use x1 light for light loads and x10 light for heavy loads

3. Test using disk emulator on LCD • Each change of state of disk emulator is equal to the Kh

values shown in item 1 above. • Direction of disk emulator shows power flow direction

(forward or reverse)

Page 53: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 48

CENTRON Polyphase Pulse Detector (Part Number 442444-001) Converts infrared pulse to visible light. Gives quick indication of load.

Page 54: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 49

Zero Resetter (CP1S and CP1SR ONLY) ZRO-C2A/C2B Part Number 441710-005 Handheld device used for resetting kWh and R300

meters Shows current energy reading and tamper counters CP1S - Resets kWh to 0 CP1SR - Resets kWh to 0 and clears tamper registers Must be used with NO power applied to meter

Page 55: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 50

Error Codes (Applicable Only to C1S & C1SR) Fatal errors happen when an unsuccessful writing to or reading from EEPROM memory occurs or it could also be a metrology error. All metering and RF functions are halted. The LCD will display the word Error on the area normally used for energy accumulation and the module will have to be returned to the factory for repair.

Multiple Custom Schedule (MCS) Functionality With the Multiple Custom Schedules (MCS) option, CENTRON C&I Demand Mobile AMR (Polyphase) meters have the ability to store up to 25 billing cycles. Users can select one of these billing cycles by a combination of magnet and Demand Reset button. The MCS option is MeterKey enabled and factory programming for MCS meters is available. PC-PRO+ Advanced 7.3 and later enables CENTRON C&I Demand Mobile AMR (Polyphase) meters to program up to 25 custom billing cycles.

Selecting a MCS schedule

The following procedure describes how to select a schedule that has been programmed into the meter: 1 Start with the meter in Normal Display mode. 2 Hold an Itron magnet to the magnetic switch. After 4 seconds the meter will begin scrolling through

display mode options. "SEL SCHED" will appear in the list if the MeterKey bit is set.

Page 56: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 51

3 Remove the magnet while this option is being displayed. This will launch the "Custom Schedule Selection Mode".

4 The display will show "cs _ _" 5 Select the first digit of the schedule number. The first digit will scroll through the valid options 0 1, and 2.

Each number will display for 1 second before switching to the next number. When the desired number is displayed, push the Demand Reset button to select that number.

6 The screen will read "cs #_" (where # is the number selected in the previous step). 7 Select the second digit of the schedule number. The second digit will scroll through the possible second

numbers -- 1 - 9 if first digits is a 0, 0 - 9 if first digit is a 1, and 0 - 5 if first digit is a 2. When the desired number is displayed, push the Demand Reset button to select that number. If the selected schedule is not valid, then "no SCHEd" will display for 4 seconds. After that you will

be returned to step 4.

If the schedule is valid, the Custom Schedule ID of the schedule will flash on the LCD (for example, "cs 22"). Press the Demand Reset button to confirm the schedule. The meter will copy over the new schedule, show "Success" on the display, and then return to Normal Display. If you you do not want that schedule, swipe the magnet and you will be returned to step 4.

Page 57: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 52

CENTRON Polyphase Display Note: The following sections apply to the CP1SD/T/L R2/R3 meters only.

Indicator Description

Load Emulator (-> for Wh delivered, <- for Wh received).

888 888888 Nine digits (7 segments each) for display of alphanumeric information.

VA, VB, VC Indicators for phase voltages being present.

Page 58: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 53

Indicator Description

Reactive Load Indicator: No arrow for unity PF

for PF lagging for PF leading

120 240 277 480 Nominal Voltage Indicator (one value appears at a time).

EOI End of Interval (Registers - Dmd).

Scr Loc Scroll Lock (indicates temporary scroll lock of a display item).

SEL nor, SEL Alt, SEL tooL Selection of Normal, Alternate, or Toolbox display sequence.

nor diSP Entry into Normal Mode.

TEST Entry into Test Mode.

ALT TEST Entry into Test Alternate Mode.

Page 59: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 54

CENTRON Polyphase Power Flow and Load Emulation Power Flow (V&I) D/T/L

The CENTRON Polyphase meter can be configured to provide instant power flow feedback. The Load Emulator and Reactive Load indicator identify in real time which quadrant of the power circle the power is flowing through.

Page 60: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 55

Load Emulator

The Load Emulator simulates mechanical disk revolution by scrolling to the right when power is delivered. The quantity represented by the Load Emulator is determined by the register programmed on the meter’s LED. Also, the speed of the Load Emulator is proportional to the pulse constant (Kh) programmed for the LED. Kh accumulates with each segment change as shown in the graphic below.

Page 61: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 56

Page 62: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 57

CENTRON Polyphase Power Circle Quadrants The following power circle diagram shows the quadrants for watts and vars delivered and received.

Page 63: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 58

CENTRON Polyphase Annunciators Phase-Voltage Indication Annunciators

The CENTRON Polyphase meter is equipped with three LCD voltage indicator annunciators. They are located in the lower left portion of the LCD display. Illuminated annunciators (VA, VB, and VC) indicate active voltage for these respective phases.

Nominal Voltage Indication Annunciator

The CENTRON Polyphase meter is equipped with a nominal voltage indication annunciator. This annunciator indicates the voltage value to which the nominal voltage is nearest. Nominal voltage indication values are 120, 240, 277, and 480.

Test Mode Annunciator

The CENTRON Polyphase meter is equipped with a Test Mode LCD annunciator. Located in the upper right portion of the display, this annunciator is present when Test Mode or Test Alternate Mode is activated. The word “TEST” appears on the display during Test Mode activation. The words “ALT” and “TEST” appear on the display during Test Alternate Mode activation. The “TEST” annunciator will also appear when the meter is in Toolbox Mode.

Page 64: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 59

CENTRON Polyphase Demand Reset Button There are two methods of triggering a demand reset. When the Demand Reset Button is pressed, a demand reset is immediately performed. A demand reset can also be done using the system programming software communicating directly with the meter when logged on.

The following actions occur with a demand reset: 888 888888 is displayed on the LCD. The demand registers are processed and reset. The Demand Reset Count is incremented. A self read “snapshot” occurs. The meter can be programmed with a demand reset lockout time. This is the minimum time required to pass between demand resets configurable from 0 to 255 minutes. If a demand reset is attempted before this amount of time elapses since the last demand reset, the meter will not reset demands. This lockout time does not apply to software initiated demand resets. Also, if the Demand Reset Button has been programmed to be disabled, the meter will not perform a manual demand reset.

Page 65: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 60

CENTRON Polyphase Three-Button Reset WARNING! Performing this function clears: Billing Data Meter Program Security Codes To perform a three-button reset: 1 Remove power from the meter. 2 Remove the outer cover from the meter. 3 Simultaneously hold down the Test Button and the Demand Reset Button, while holding a magnet at the

nine o'clock position on the meter. Note: The Test Button, Demand Reset Button, and magnet position are shown on CENTRON Polyphase Meter Indicators.

4 While holding the switches and magnet in place apply power to the meter. Once you see all segments flashing on the display, release both buttons and remove the magnet.

5 The three-button reset is complete. Note: If you do not see all segments flashing, repeat steps 1, 3 and 4.

Page 66: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 61

CENTRON Polyphase Magnetic Switch The magnetic switch allows for manual switching between display modes as well as scroll lock of display items. To activate the magnetic switch, hold the magnet to the 9:00 position.

To switch between different display modes, hold the magnet in place for 5 seconds. The meter display will show one of the following:

selnor

selAlt

seltool

When the display shows the mode you want, remove the magnet. To activate the scroll lock, hold and release the magnet. “ScrLoc” will appear on the meter display. Apply and release the magnet again to step through the selected meter display.

Page 67: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 62

CENTRON Polyphase Test Mode Button The Test Mode button is located at the 3 o'clock position on the register of the meter under the meter cover. Pressing the button activates Test Mode. Pressing the button a second time activates Test Alternate Mode, enabling the user to test a different energy quantity with the IR LED. Pressing the button a third time will exit Test Mode and activate the Normal display.

Note: If the TEST button has been programmed to be disabled, the meter will not enter Test Mode when the button is pressed.

Page 68: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 63

CENTRON Polyphase Display Modes Normal Display Mode

The Normal Display Mode is the default display when the meter is energized and when the meter is in Normal Operating Mode.

Alternate Display Mode

The Alternate Display Mode is functionally identical to the Normal Mode. The meter itself still operates under normal measurement, but the display sequence can be programmed to show a different set of displayable items from those in the Normal Display Mode. While in Alternate Display Mode, the letters “ALT” appear on the LCD to designate activation of the Alternate Display Mode. Upon completion of the Mode Timeout period, the meter automatically returns to the Normal Display Mode.

Toolbox Display Mode

Toolbox Display Mode is identical to Normal Mode except that the list of displayable items is a fixed list dependent on the service type. You can enter the Toolbox Mode from either Normal or Alternate Mode. While in Toolbox Mode, a flashing “TEST” appears on the right side of the display. Once activated, the Toolbox Mode scrolls through the list of per phase items and diagnostic counters.

Page 69: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 64

Display Modes (continued)

Test Display Mode

The Test Mode can be accessed from either the Normal, Alternate, or Toolbox Mode by removing the meter cover and pressing the Test button. To activate this mode with a programming device, refer to the appropriate software user’s manual. The Test Mode annunciator, “TEST” is displayed while the CENTRON Polyphase meter is in Test Mode. While the meter is in Test Mode, normal metering stops and Test Mode registration begins.

Test Alternate Display Mode

Test Alternate Mode is functionally identical to Test Mode. To enter Test Alternate Mode, press the Test switch twice. The meter will return to Normal Mode at the completion of Mode Timeout.

Display Mode Timeout

When the display is put into display modes other than Normal display (Alternate, Toolbox, Scroll Lock, Test, or Test Alternate display modes), the meter will return to normal operation after a programmable Mode Timeout expires. The Mode Timeout can be configured from 1 to 255 minutes using the meter programming software.

Page 70: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 65

CENTRON Polyphase Main I/O & Supplemental I/O Module Color Coding 2KYZ, 1LC Boards

Yellow

Form ALow Current / High CurrentSolid-State Contact

NOCommon

OrangeWhite

Form CKYZ Output #1

Black

Red

Y

Z

K

Form CKYZ Output #2

White/Yellow

Black/White

Red/White

Y

Z

K

Page 71: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 66

CENTRON Polyphase SiteScan™ System and Installation Diagnostic Checks SiteScan Diagnostic #1 Polarity, Cross-Phase & Energy Flow Check

SiteScan Diagnostic #2 Phase Voltage Deviation Check

SiteScan Diagnostic #3 Inactive Phase Current Check

SiteScan Diagnostic #4 Phase Angle Displacement Check

Each error check is performed upon initial power-up, upon programming, upon restoration of power after an outage, and as specified in the field descriptions below. The error display is removed when the error condition no longer exists.

It is very important to note that the meter will continue to operate normally while any of the diagnostic errors are being displayed. The system and installation diagnostic checks will only report that there may be a problem with the meter or site. They have no effect on metering or on any operations performed by the CENTRON Polyphase meter.

Page 72: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 67

If enabled, all the diagnostic checks will continually check for errors every five seconds. The CENTRON Polyphase meter will not check for diagnostic errors under any of the following conditions: When single-phase series conditions occur (Test Bench) When the meter is in Test Mode When the diagnostic(s) have been disabled by the programming software When the meter has triggered a Non-Fatal 9 Error Note: Once the condition causing the error is corrected, the meter must pass two consecutive checks before the diagnostic error is cleared from the display. The CENTRON Polyphase meter checks every five seconds for configured diagnostics. A diagnostic error must exist for 15 seconds (3 checks) to be logged as an error. The error condition must be clear for 25 seconds (5 checks) before the error condition is removed on the meter display or in the SiteScan view while online with a meter.

Page 73: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 68

CENTRON Polyphase Non-Fatal Errors The options for displaying Non-Fatal Errors are the same as those for displaying Diagnostic errors. If one or more non-fatal errors from the 1 to 6 set are to be scrolled at the same time as one or more non-fatal errors from the 7 to 10 set, then the meter will alternate between the two sets between each display item.

Low Battery Error

Error Code Possible Cause(s) Err 1----- Battery Voltage Low.

Recommended Action Once a low battery is detected, the daily battery voltage tests will be halted and a battery present test will be run every second. As long as the battery is good and the meter does not lose power, the meter will remain a Clock meter and the one-second battery present tests will continue. If the battery dies and a power outage occurs, when power is restored, the meter will become a Demand-Only meter. If a dead battery is detected upon restoration of power, this error code will display. TOU and load profile functions will be disabled. TOU registers and Load Profile Channels will not accumulate after an outage with a dead battery. If a dead battery level error occurs during normal operation, TOU and load profile will continue to operate until an outage occurs.

Page 74: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 69

Loss of Phase Error

Error Code Possible Cause(s) Err -2---- The voltage on one of the phases dropped below 96 volts.

Recommended Action SiteScan check. It runs every 5 seconds and must fail twice successively to be recorded. A Demand Reset after the voltage returns will clear this error.

Time-of-Use (TOU) Error

Error Code Possible Cause(s)

Err --3--- A problem was detected in the Time-of-Use Schedule.

Recommended Action

This error indicates that there is a problem between the configuration data and the state of the meter. When this error occurs it may be logged to a History Log. A TOU non-fatal error can be cleared in several ways depending on what caused the condition:

• On a reconfigure, if Calendar (and possibly TOU) configuration data is removed. • On a reconfigure that corrects the calendar and/or TOU configuration data. • On a set clock with correct Calendar and possibly TOU configuration data.

Page 75: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 70

Reverse Power Flow Error

Error Code Possible Cause(s) Err ---4-- Reverse Power was detected on one or more phases.

Recommended Action Reverse power is tested every second and an accumulator for it is maintained. If power is delivered during the second, then the accumulator is cleared. If power is received during the second, then the accumulator is incremented. If the accumulator reaches the configured reverse power threshold, then the error is triggered. A Demand Reset will clear this error.

Page 76: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 71

Load Profile Error

Error Code Possible Cause(s) Err ----5- Clock not set, missing or dead battery.

Recommended Action This error indicates that the meter has Load Profile configuration data, but either the clock has never been set or the battery is dead or missing. This error may be detected upon a power-up, a reconfigure, or a set clock. This error may be cleared as follows:

• On a reconfigure, if Load Profile configuration data is removed. • On a set clock.

Page 77: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 72

Register Full Scale Exceeded

Error Code Possible Cause(s)

Err -----6 Programmed Full Scale Value Exceeded.

Recommended Action

This error is checked upon every Demand EOI, set clock, demand reset, enter Test Mode, and power-up. If the meter is configured for Max W Del, then that value is compared to the programmed threshold. The full scale overflow error displays after the interval during which the overflow occurred. The maximum demand register continues to accumulate and display kW as long as the format limitations are not exceeded. If a full scale overflow occurs, check the installation to ensure that the current capacity of the meter has not been exceeded. A full scale overflow in no way affects the existing billing data. This error will clear when a demand reset is performed.

Error Code: Err 7----- Reserved Error Code: Err -8---- Reserved

Page 78: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 73

SiteScan Error

Error Code Possible Cause(s) Err --9--- Meter not in a recognized service for the meter type.

Recommended Action Verify site wiring. This error may be cleared:

• On a reconfigure, if the SiteScan Override Service Type is changed to correct service. • On a power-up, if the SiteScan Auto-Service Sense detects correct meter service.

Note: The check for this error will not start until SiteScan power-up delay time has passed. If this error is present, then SiteScan diagnostics are disabled. If SiteScan is configured to override service type in the meter program, then this test shall not be performed.

Note: If multiple non-fatal errors occur, the meter will display a combined error message. For example, if a Low Battery and a Loss of Phase exist, the LCD display will show Err 12----. If one of the errors was programmed to lock and the other to scroll, the display will lock on the combined error message.

Page 79: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 74

CENTRON Polyphase Fatal Errors Fatal errors cause the display to lock on the error code because of the possibility that billing data may have been corrupted or that the meter may not be operating correctly. If multiple fatal errors occur, the one with the lowest number will be the error code that locks on the display.

The CENTRON Polyphase meter will check for fatal errors: when a meter reconfigure is performed. when power is initially energized and upon future power restoration. Fatal errors are cleared when they are corrected by the factory and the meter is reprogrammed.

MCU Flash Error

Error Code Possible Cause(s) FAtError1 The meter has detected a problem with the program memory.

Recommended Action If this error occurs, program the meter and check for proper operation. If the error continues to exist, return the meter to the factory for repair.

Page 80: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 75

RAM Error

Error Code Possible Cause(s) FAtError2 The meter has detected a problem with the RAM.

Recommended Action If the meter detects a RAM problem, return the meter to the factory for repair.

Data Flash Error

Error Code Possible Cause(s) FAtError3 The meter has detected a problem with the data flash.

Recommended Action If this error occurs, program the meter and check for proper operation. If the error continues to exist, return the meter to the factory for repair.

Page 81: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 76

Metrology Communication Error

Error Code Possible Cause(s) FAtError4 Meter processor communication failure.

Recommended Action Normally, any Fatal Error will cause the meter to stop all metering operations. However, a Metrology Communication Error is displayed as a Fatal Error, but will not shut down the meter. This error occurs when communications are interrupted between the meter processors. The error is registered, but the processors continue to attempt to communicate with each other. If communication between the processors resumes, the meter continues to operate; however, all register values are suspect due to lost data during the period when metering was interrupted. As with all Fatal Errors, the meter should be returned to the factory for repair.

Page 82: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 77

Power Down Error

Error Code Possible Cause(s)

FAtError5 Power Down Error.

Recommended Action

If this error occurs, program the meter and check for proper operation through two complete power down and power up sequences. If the error continues to exist, return the meter to the factory for repair.

File System Error

Error Code Possible Cause(s) FAtError6 The meter has detected a problem with the file system.

Recommended Action If the meter detects this problem, return the meter to the factory for repair.

Page 83: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 78

Operating System Error

Error Code Possible Cause(s) FAtError7 The meter has detected a problem with the operating system.

Recommended Action

If the meter detects this problem, return the meter to the factory for repair.

Page 84: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 79

CENTRON Polyphase Error Codes (Applicable Only to CP1S & CP1SR) The following additional error conditions apply to the CP1S and CP1SR meters:

Phase A (B, C) voltage out of tolerance

CP1S and CP1SR meters will flash the individual voltage icon (Va, Vb, or Vc) for each of the individual voltages if they are out of tolerance. Once the individual voltage is below a threshold voltage amount, the individual voltage icon is turned off and no longer appears on the display.

Power up with Phase A, B, and C voltage equal 0 degrees

This is a test setup message. The meter displays "noSEr" on the CP1SR standard display.

Page 85: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 80

Notes:

Page 86: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 81

SENTINEL Meter

Page 87: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 82

SENTINEL Meter Forms Available Socket Meter Forms

Metrology Class Number of Elements

Number of Wires

Voltage Test Amps

2Sa 200 1.5 3 120-480 30

2S 320 1.5 3 120-480 50

3S 20 1 3 120-480 2.5

4S 20 1 3 120-480 2.5

9S(8S)c 20 3 4 120-480 2.5

9S(8S)/46Sb c 20 3 4 120-480 2.5

a The meter must have register multiplier. Reference PIL EL-P04-451. b Must be ordered at meter order time; cannot be upgraded later in the field. c The KYZ spades option must be specified on the SENTINEL Specification form on the Mounting/Form

Type tab.

Page 88: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 83

Socket Meter Forms (continued)

Metrology Class Number of Elements

Number of Wires

Voltage Test Amps

12S 200 2 3 120-277 30

12S 320 2 3 120-277 50

16S(14S, 15S, 17S) 200 3 4 120-480 30

16S(14S, 15S, 17S) 320 3 4 120-480 50

45S(5S) 20 2 3 120-480 2.5

46S(6S) 20 2.5 4 120-480 2.5

56S(66S, 26S)d 20 2 3 120-480 2.5

66S(26S) 20 2 4 120-480 2.5

d Requires Firmware Version 5.00 or higher.

Page 89: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 84

A-base Meter Forms

Metrology Class Number of Elements

Number of Wires

Voltage Test Amps

10A(9A) 20 3 4 120-480 2.5

16A(14A, 15A, 17A) 150 3 4 120-480 30

45A(5A) 20 2 3 120-480 2.5

46A(6A) 20 2.5 4 120-480 2.5

48A(8A) 20 2 4 120-480 2.5

Page 90: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 85

Switchboard Ready Meter Forms

Metrology Class Number of Elements

Number of Wires

Voltage Test Amps

9F(8F)c 20 3 4 120-480 2.5

45F(5F) 20 2 3 120-480 2.5

46F(6F)c 20 2.5 4 120-480 2.5

c The KYZ spades option must be specified on the SENTINEL Specification form on the Mounting/Form Type tab.

Page 91: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 86

SENTINEL Type Codes

Code Description

S Manufacturer: S = Itron

S Product: S = SENTINEL

4 Meter Form / Wiring Type: 1 = 1 phase [Form 2, 3, & 4] 2 = 3 phase, 3W, 2 element [Form 12] 3 = 3 phase, 3W, 2 element [Form 45(5), 56 (26, 66)]

4 = 3 phase, 4W, 3 element [Form 9(8), 9(8,46)a, 10, 16(14/15/17), 48] 5 = 3 phase, 4W, 2½ element [Form 46(6)] 6 = 3 phase, 4W, Delta

S Base Style: S = Socket; A = A-base; F = Switchboard Ready™

a Must be ordered at meter order time; cannot be upgraded later in the field.

Page 92: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 87

SENTINEL Type Codes (continued) Code Description

4 Measurement Level: 0 = Level 0 Wh (energy only) 1 = Level 1 (Wh, PF) 2 = Level 2 (Wh, PF, + Varh, or VAh, or Qh)

3 = Level 3 (Wh, PF, Varh, VAh, Qh, Per phase V&A) 4 = Level 4 (Wh, PF, 4Q Varh, VAh, Qh, Per phase V&A, Power Quality (VQ/Harmonics)a ,Bi-directional Measurement)

L Meter Options: D = Demand; T = Time-of-Use; L = Load Profile a Supported in Firmware revision 5.0 or above meters.

Page 93: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 88

Display

Indicator Description

Load Emulator (-> for Wh delivered, <- for Wh received).

888 888888 Nine digits (7 segments each) for display of alphanumeric information.

VA, VB, VC Indicators for phase voltages being present.

Reactive Load Indicator: No arrow for unity PF

for PF lagging for PF leading

120 240 277 480 Nominal Voltage Indicator (one value appears at a time).

Page 94: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 89

Indicator Description EOI End of Interval (Registers - Dmd).

Scr Loc Scroll Lock (indicates temporary scroll lock of a display item).

SEL nor, SEL Alt, SEL tooL Selection of Normal, Alternate, or Toolbox display sequence.

nor diSP Entry into Normal Mode.

TEST Entry into Test Mode.

ALT TEST Entry into Test Alternate Mode.

Page 95: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 90

Display Messages Display Message Description

Indicates that the meter is in Loader Mode and is waiting for firmware download to begin via the RS-232/485, Modem, or optical ports.

Indicates that the meter is in Loader Mode and is communicating with the option board (RS-232/485, Modem) port.

Indicates that the meter is in Loader Mode and is communicating with the Optical port.

Indicates that a firmware download has been initiated. The display shows a memory address. The address will change while the download is occurring.

Page 96: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 91

Display Message Description

Indicates that a reconfigure was not successfully performed, possibly due to power lost during reconfiguration. The PC-PRO+ Advanced software may lock up when this occurs. To unlock the software:

1. Open the Windows Task Manager. 2. On the Applications tab, end the “Program Editor” task. 3. On the Processes tab, end the “resource manager” process. 4. Restart PC-PRO+ Advanced and re-initiate the reconfigure.

Indicates that the PC-PRO+ Advanced program’s “Display Configuration” is configured to display an item that is not supported by the firmware in the meter. To resolve this issue, either go to PC-PRO+ Advanced program’s “Display Configuration” and delete the item from the display list, or install a newer version of firmware in the meter.

Page 97: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 92

Power Flow and Load Emulation Power Flow

The SENTINEL meter can be configured to provide instant power flow feedback. The Load Emulator and Reactive Load indicator identify in real time which quadrant of the power circle the power is flowing through.

Page 98: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 93

Load Emulator

The Load Emulator simulates mechanical disk revolution by scrolling to the right when power is delivered. The quantity represented by the Load Emulator is determined by the register programmed on the meter’s LED. Also, the speed of the Load Emulator is proportional to the pulse constant (Kh) programmed for the LED. Kh accumulates with each segment change as shown in the graphic below.

Page 99: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 94

Note: For Firmware Version 5.0 meters (and above), several new uni-directional quantities are available. When these quantities are programmed to LED, both the LED and the load emulator will function for delivered and received quantities.

Page 100: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 95

Power Circle Quadrants The following power circle diagram shows the quadrants for watts and vars delivered and received.

Page 101: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 96

Annunciators Phase-Voltage Indication Annunciators

The SENTINEL meter is equipped with three LCD voltage indicator annunciators. They are located in the lower left portion of the LCD display. Illuminated annunciators (VA, VB, and VC) indicate active voltage for these respective phases. Depending on how the user configures the meter, a loss of voltage may be indicated with either a missing or flashing annunciator.

Nominal Voltage Indication Annunciator

The SENTINEL meter is equipped with a nominal voltage indication annunciator. This annunciator indicates the voltage value to which the nominal voltage is nearest. Nominal voltage indication values are 120, 240, 277, and 480.

Test Mode Annunciator

The SENTINEL meter is equipped with a Test Mode LCD annunciator. Located in the lower left portion of the display, this annunciator is present when Test Mode or Test Alternate Mode is activated. The word “TEST” appears on the display during Test Mode activation. The words “ALT” and “TEST” appear on the display during Test Alternate Mode activation. The “TEST” annunciator will also appear when the meter is in Toolbox Mode.

Page 102: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 97

Demand Reset Button There are two methods of triggering a demand reset. When the Demand Reset Button is pressed, a demand reset is immediately performed. A demand reset can also be done using the system programming software communicating directly with the meter when logged on.

The following actions occur with a demand reset: 888 888888 is displayed on the LCD. The demand registers are processed and reset. The Demand Reset Count is incremented. A self read “snapshot” occurs (if programmed). The meter can be programmed with a demand reset lockout time. This is the minimum time required to pass between demand resets configurable from 0 to 255 minutes. If a demand reset is attempted before this amount of time elapses since the last demand reset, the meter will not reset demands. This lockout time does not apply to software initiated demand resets. Also, if the Demand Reset Button has been programmed to be disabled, the meter will not perform a demand reset when the button is pushed.

Page 103: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 98

Three-Button Reset WARNING! Performing this function clears: Billing Data Meter Program Security Codes To perform a three-button reset: 1 Remove power from the meter. 2 Remove the outer cover from the meter. 3 Remove battery if present. 4 Simultaneously hold down the Test Button and the Demand Reset Button, while holding a magnet at the

magnet icon located at 7 o'clock on the meter cover. Note: For the Test Button and the Demand Reset Button locations see SENTINEL Meter (on page 81); a magnet picture on the meter’s outer cover shows you the location to apply the magnet.

5 While holding the switches and magnet in place apply power to the meter. Once you see “3b rESEt” on the display, release both buttons and remove the magnet. Note: If you do not see “3b rESEt” on the display, you will need to follow steps 1, 4, and 5 again.

6 The three-button reset is complete.

Page 104: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 99

Magnetic Switch The magnetic switch allows for manual switching between display modes as well as scroll lock of display items. To activate the magnetic switch, hold the magnet to the location shown (magnet icon embedded in cover).

To switch between different display modes, hold the magnet in place for 5 seconds. The meter display will show one of the following:

selnor

selAlt

seltool

When the display shows the mode you want, remove the magnet. To activate the scroll lock, hold and release the magnet. “ScrLoc” will appear on the meter display. Apply and release the magnet again to step through the selected meter display.

Page 105: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 100

Test Mode Button The Test Mode button is located in the lower center of the meter nameplate under the meter cover. Pressing the button activates Test Mode. Pressing the button a second time activates Test Alternate Mode, enabling the user to test a different energy quantity with the IR LED. Pressing the button a third time will exit Test Mode and activate the Normal display.

Note: If the TEST button has been programmed to be disabled, the meter will not enter Test Mode when the button is pressed.

Page 106: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 101

Display Modes Normal Display Mode

The Normal Display Mode is the default display when the meter is energized and when the meter is in Normal Operating Mode.

Alternate Display Mode

The Alternate Display Mode is functionally identical to the Normal Mode. The meter itself still operates under normal measurement, but the display sequence can be programmed to show a different set of displayable items from those in the Normal Display Mode. While in Alternate Display Mode, the letters “ALT” appear on the LCD to designate activation of the Alternate Display Mode. Upon completion of the Mode Timeout period, the meter automatically returns to the Normal Display Mode.

Toolbox Display Mode

Toolbox Display Mode is identical to Normal Mode except that the list of displayable items is a fixed list dependent on the service type. You can enter the Toolbox Mode from either Normal or Alternate Mode. While in Toolbox Mode, a flashing “TEST” appears on the left side of the display. Once activated, the Toolbox Mode scrolls through the list of per phase items and diagnostic counters.

Page 107: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 102

Display Modes (continued)

Test Display Mode

The Test Mode can be accessed from either the Normal, Alternate, or Toolbox Mode by removing the meter cover and pressing the Test button. To activate this mode with a programming device, refer to the appropriate software user’s manual. The Test Mode annunciator, “TEST” is displayed while the SENTINEL meter is in Test Mode. While the meter is in Test Mode, normal metering stops and Test Mode registration begins.

Test Alternate Display Mode

Test Alternate Mode is functionally identical to Test Mode. To enter Test Alternate Mode, press the Test switch twice. The meter will return to Normal Mode at the completion of Mode Timeout.

Display Mode Timeout

When the display is put into display modes other than Normal display (Alternate, Toolbox, Scroll Lock, Test, or Test Alternate display modes), the meter will return to normal operation after a programmable Mode Timeout expires. The Mode Timeout can be configured from 1 to 255 minutes using the meter programming software.

Page 108: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 103

SENTINEL Main I/O & Supplemental I/O Module Color Coding 1KYZ, 1LC Boards

Yellow

Form ALow Current / High CurrentSolid-State Contact

NO

Common

Orange

White

Form CKYZ Output #1

Black

Red

Y

Z

K

Page 109: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 104

SENTINEL Main I/O & Supplemental I/O Module Color Coding 2KYZ, 1LC Boards

Yellow

Form ALow Current / High CurrentSolid-State Contact

NOCommon

OrangeWhite

Form CKYZ Output #1

Black

Red

Y

Z

K

Form CKYZ Output #2

White/Yellow

Black/White

Red/White

Y

Z

K

Page 110: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 105

SENTINEL Main I/O & Supplemental I/O Module Color Coding 4KYZ, 1LC Boards

K

YZ

Form CKYZ Output #1

YellowBlackRed

Form CKYZ Output #3

BrownBlueViolet

YZK

Form CKYZ Output #4

Brown/WhiteBlue/WhiteViolet/White

YZK

Form ALow Current / High CurrentSolid-State Contact

NOCommon

OrangeWhiteForm C

KYZ Output #2Black/WhiteRed/White

YZK

White/Yellow

Page 111: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 106

SENTINEL Main I/O & Supplemental I/O Module Color Coding 2KYZ, 1LC, 2 KY Inputs Boards

Form CKYZ Output #1

Yellow

Black

Red

Form CKYZ Output #2

White/Yellow

Black/White

Red/White

Y

Z

KY

Z

KForm ALow Current / High CurrentSolid-State Contact

NOCommon

OrangeWhite

POSGND

YK

White/Orange

White/BlackForm AKY Input #1

POSGND

Y

K

White/VioletWhite/Blue

Form AKY Input #2

Page 112: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 107

SENTINEL Main I/O & Supplemental I/O Module Color Coding 4KYZ, 1LC, 2 KY Inputs Boards

2

Form ALow Current / High CurrentSolid- State Contact

NOCommon

OrangeWhite

POSGND

YK

White/ OrangeWhite/ Black

Form AKY Input #1

POSGND

White/ VioletWhite/Blue

Form AKY Input #2

Y

K

YZK

Form CKYZ Output #1

YellowBlackRed

Form CKYZ Output #

White/YellowBlack/ WhiteRed/ White

Form CKYZ Output #3

BrownBlueViolet

Form CKYZ Output #4

Brown/ WhiteBlue/ WhiteViolet/ White

YZK

YZK

YZK

Page 113: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 108

RS-232/RS-485 DB-25 Pinouts - Port 1 Pin # Description Signal Color

1

2 Transmit Data / Transmit Data (Z) TXD1 / Z1 GRY

3 Receive Data / Receive Data (B) RXD1 / B1 GRN/YEL

4 Request to Send / Transmit Data (Y) RTS1 / Y1 RED/GRN

5 Clear to Send / Receive Data (A) CTS1 / A1 WHT/GRY

6

7 Ground / Shield GND1 /Shield1 WHT/BLK/ORN

8 K1 Input K1 In WHT/BLK

9 Y1 Input Y1 In WHT/ORG

10 Y1 Output Y1 YEL

11 K1 Output K1 RED

Page 114: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 109

Pin # Description Signal Color 12 Z1 Output Z1 BLK

13 Y2 Output Y2 YEL/WHT

14 K2 Output K2 RED/WHT

15 Z2 Output Z2 BLK/WHT

16 Y3 Output Y3 BRN

17 K3 Output K3 VIO

18 Z3 Output Z3 BLU

19 Y4 Output Y4 BRN/WHT

20 K4 Output K4 VIO/WHT

21 Z4 Output Z4 BLU/WHT

22 K1 Output K1 Out WHT

Page 115: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 110

Pin # Description Signal Color 23 Y1 Output Y1 Out ORG

24 K2 Input K2 In WHT/BLU

25 Y2 Input Y2 In WHT/VIO

To use RS-485 2-wire communication on Port 1, twist the following pairs of wires together: Received Data (A1) & Transmit Data (Y1) Receive Data (B1) & Transmit Data (Z1)

RS-232/RS-485 DB-9 Pinouts - Port 2 (if present) Pin # Description Signal Color

1

2 Receive Data / Receive Data (B) RXD2 / B2 WHT/BLK/GRY

3 Transmit Data / Transmit Data (Z) TXD2 / Z2 GRY/WHT

4

Page 116: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 111

Pin # Description Signal Color 5 Ground / Shield GND2 /Shield2 WHT/BLK/BRN

6

7 Request to Send / Transmit Data (Y) RTS2 / Y2 BLK/GRN

8 Clear to Send / Receive Data (A) CTS2 / A2 RED/YEL

9

To use RS-485 2-wire communication on Port 2, twist the following pairs of wires together: Received Data (A2) & Transmit Data (Y2) Receive Data (B2) & Transmit Data (Z2)

Page 117: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 112

SiteScan™ System and Installation Diagnostic Checks SiteScan Diagnostic #1 (diA1) Polarity, Cross-Phase & Energy Flow Check SiteScan Diagnostic #2 (diA2) Phase Voltage Deviation Check SiteScan Diagnostic #3 (diA3) Inactive Phase Current Check SiteScan Diagnostic #4 (diA4) Phase Angle Displacement Check SiteScan Diagnostic #5 (diA5) Current Waveform Distortion Check SiteScan Diagnostic #6a (diA6) Harmonic Distortion Check

a SiteScan Diagnostic #6 is controlled by the Power Quality MeterKey, which is an optional feature for meters with Firmware Version 5.00 and higher.

Each error check is performed upon initial power-up, upon programming, upon restoration of power after an outage, and as specified in the field descriptions below. The error display is removed when the error condition no longer exists.

It is very important to note that the meter will continue to operate normally while any of the diagnostic errors are being displayed. The system and installation diagnostic checks will only report that there may be a problem with the meter or site. They have no effect on metering or on any operations performed by the SENTINEL meter.

Page 118: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 113

If enabled, all the diagnostic checks will continually check for errors every five seconds. The SENTINEL meter will not check for diagnostic errors under any of the following conditions: When single-phase series conditions occur (Test Bench) When the meter is in Test Mode When the diagnostic(s) have been disabled by the programming software When the meter has triggered a Non-Fatal 9 Error Note: Once the condition causing the error is corrected, the meter must pass two consecutive checks before the diagnostic error is cleared from the display. The SENTINEL meter checks every five seconds for configured diagnostics. A diagnostic error must exist for 15 seconds (3 checks) to be logged as an error. The error condition must be clear for 10 seconds (2 checks) before the error condition is removed on the meter display or in the SiteScan view while online with a meter.

Page 119: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 114

Non-Fatal Errors The options for displaying Non-Fatal Errors are the same as those for displaying Diagnostic errors. If one or more non-fatal errors from the 1 to 6 set are to be scrolled at the same time as one or more non-fatal errors from the 7 to 10 set, then the meter will alternate between the two sets between each display item.

Low Battery Error

Error Code Possible Cause(s) Err 1----- Battery Voltage Low.

Battery Connector Not Connected Properly. Recommended Action

Once a low battery is detected, the daily battery voltage tests will be halted and a battery present test will be run every second. As long as the battery is good and the meter does not lose power, the meter will remain a Clock meter and the one-second battery present tests will continue. If the battery dies or is removed and a power outage occurs, when power is restored, the meter will become a Demand-Only meter. -- Continued on next page -- If a dead battery is detected upon restoration of power, this error code will display until the battery is replaced. TOU and load profile functions will be disabled until the battery is replaced and the time is set. TOU (rates A, B, C, D, E, F, G) registers and Load Profile Channels will not accumulate after an outage with a dead battery. If a dead battery level error occurs during normal operation, TOU and load profile will continue to operate until an outage occurs.

Page 120: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 115

Loss of Phase Error

Error Code Possible Cause(s) Err -2---- The voltage on one of the phases dropped below the voltage

threshold.

Single-phase Power Supply Threshold: 96 volts. Three Phase Power Supply Threshold: 45 volts.

Recommended Action SiteScan check. It runs every 5 seconds and must fail twice successively to be recorded. A Demand Reset after the voltage returns will clear this error.

Page 121: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 116

Time-of-Use (TOU) Error

Error Code Possible Cause(s)

Err --3--- A problem was detected in the Time-of-Use Schedule.

Recommended Action

This error indicates that there is a problem between the configuration data and the state of the meter. When this error occurs it may be logged to a History Log. A TOU non-fatal error can be cleared in several ways depending on what caused the condition:

• On a reconfigure, if Calendar (and possibly TOU) configuration data is removed. • On a reconfigure that corrects the calendar and/or TOU configuration data. • On a set clock with a battery present and with correct Calendar and possibly TOU

configuration data.

Page 122: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 117

Reverse Power Flow Error

Error Code Possible Cause(s) Err ---4-- Reverse Power was detected on one or more phases.

Recommended Action Firmware Versions prior to 3.21: Reverse power is tested every second and must fail three times successively to be recorded. Each phase is individually checked for reverse current. The reverse direction error will clear when a demand reset is performed. Firmware Version 3.21: Reverse power is tested every second and must fail three times successively to be recorded. Reverse power is tested on the phases only if the aggregate is in the reverse. The reverse direction error will clear when a demand reset is performed. Firmware Version 5.0 or above: Reverse power is tested every second and an accumulator is maintained. If power is delivered during the second, then the accumulator is cleared. If power is received during the second, then the accumulator is incremented. If the accumulator reaches the configured reverse power Wh threshold configured in the meter's program, then this error is triggered. The reverse direction error will clear when a demand reset is performed.

Page 123: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 118

Load Profile Error

Error Code Possible Cause(s) Err ----5- Clock not set, missing or dead battery.

Recommended Action This error indicates that the meter has Load Profile configuration data, but either the clock has never been set or the battery is dead or missing. This error may be detected upon a power-up, a reconfigure, or a set clock. This error may be cleared as follows:

• On a reconfigure, if Load Profile configuration data is removed. • On a set clock with a battery present.

Page 124: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 119

Register Full Scale Exceeded

Error Code Possible Cause(s)

Err -----6 Programmed Full Scale Value Exceeded.

Recommended Action

This error is checked upon every Demand EOI, set clock, demand reset, enter Test Mode, and power-up. If the meter is configured for Max W Del, then that value is compared to the programmed threshold. The full scale overflow error displays after the interval during which the overflow occurred. The maximum demand register continues to accumulate and display kW as long as the format limitations are not exceeded. If a full scale overflow occurs, check the installation to ensure that the current capacity of the meter has not been exceeded. A full scale overflow in no way affects the existing billing data. This error will clear when a demand reset is performed.

Error Code: Err 7----- Reserved Error Code: Err -8---- Reserved

Page 125: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 120

SiteScan Error

Note: Supported in Firmware Version 3.21 and above. Error Code Possible Cause(s)

Err --9--- Meter not in a recognized service for the meter type. Recommended Action

Verify site wiring. This error may be cleared:

• On a reconfigure, if the SiteScan Override Service Type is changed to correct service. • On a power-up, if the SiteScan Auto-Service Sense detects correct meter service.

Note: The check for this error will not start until SiteScan power-up delay time has passed. If this error is present, then SiteScan diagnostics are disabled. If SiteScan is configured to override service type in the meter program, then this test shall not be performed.

Note: If multiple non-fatal errors occur, the meter will display a combined error message. For example, if a Low Battery and a Loss of Phase exist, the LCD display will show Err 12----. If one of the errors was programmed to lock and the other to scroll, the display will lock on the combined error message.

Page 126: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 121

Fatal Errors Fatal errors cause the display to lock on the error code because of the possibility that billing data may have been corrupted or that the meter may not be operating correctly. If multiple fatal errors occur, the one with the lowest number will be the error code that locks on the display.

The SENTINEL meter will check for fatal errors: when a meter reconfigure is performed. when power is initially energized and upon future power restoration. while performing key operations. Fatal errors are cleared when they are corrected by the factory and the meter is reprogrammed.

MCU Flash Error

Error Code Possible Cause(s) FAtError1 The meter has detected a problem with the program memory.

Recommended Action If this error occurs, program the meter and check for proper operation. If the error continues to exist, return the meter to the factory for repair.

Page 127: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 122

RAM Error

Error Code Possible Cause(s) FAtError2 The meter has detected a problem with the RAM.

Recommended Action If the meter detects a RAM problem, return the meter to the factory for repair.

DATA FLASH Error

Error Code Possible Cause(s) FAtError3 The meter has detected a problem with the data flash.

Recommended Action If this error occurs, program the meter and check for proper operation. If the error continues to exist, return the meter to the factory for repair.

Page 128: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 123

Metrology Communication Error

Error Code Possible Cause(s) FAtError4 Meter processor communication failure.

Recommended Action Normally, any Fatal Error will cause the meter to stop all metering operations. However, a Metrology Communication Error is displayed as a Fatal Error, but will not shut down the meter. This error occurs when communications are interrupted between the meter processors. The error is registered, but the processors continue to attempt to communicate with each other. If communication between the processors resumes, the meter continues to operate; however, all register values are suspect due to lost data during the period when metering was interrupted. As with all Fatal Errors, the meter should be returned to the factory for repair.

Page 129: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 124

Power Down Error

Error Code Possible Cause(s)

FAtError5 Power Down Error.

Recommended Action

If this error occurs, program the meter and check for proper operation through two complete power down and power up sequences. If the error continues to exist, return the meter to the factory for repair.

File System Error

Error Code Possible Cause(s) FAtError6 The meter has detected a problem with the file system.

Recommended Action If the meter detects this problem, return the meter to the factory for repair.

Page 130: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 125

Operating System Error

Error Code Possible Cause(s) FAtError7 The meter has detected a problem with the operating system.

Recommended Action

If the meter detects this problem, return the meter to the factory for repair.

Page 131: Itron Metering Pocket Guide i - Cooper Electric Supply - Pocket... · Itron Metering Pocket Guide i ... QUANTUM Q1000 . No . ... Itron Metering Pocket Guide 9 CENTRON Meter . Itron

Itron Metering Pocket Guide 100279MP-08

Itron, Inc. Corporate Headquarters 2111 North Molter Road Liberty Lake, WA 99019 Itron, Inc. Oconee Electricity Metering 313-B North Highway 11 West Union, SC 29696 http://www.itron.com Copyright© 2004-2011 Itron, Inc All rights reserved.

Itron Support Phone Number (877) 487-6602

Itron Support Email Address

[email protected]

Itron Access Website http://access.itron.com