40
KIT # 826251 CURTAIN FIRE DAMPERS DFD/FD/OFD/ODFD/DFDR/FDR INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s) 452763 FD, DFD, SSFD & KFD Models 2–9 453946 FD & DFD 150X Models 10–17 462721 DFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR-XXX Models 18–22 461337 OFSD-XXX, ODFD-XXX, OFD-XXX and OSSFD-XXX Series 23–34 474015 Single Side Retaining Angle 35-37

INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Embed Size (px)

Citation preview

Page 1: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

KIT # 826251CURTAIN FIRE DAMPERS

DFD/FD/OFD/ODFD/DFDR/FDR

INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS

Instructions included in this booklet:

IOM # Description Page(s)

452763 FD, DFD, SSFD & KFD Models 2–9

453946 FD & DFD 150X Models 10–17

462721 DFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR-XXX Models 18–22

461337 OFSD-XXX, ODFD-XXX, OFD-XXX and OSSFD-XXX Series 23–34

474015 Single Side Retaining Angle 35-37

Page 2: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Installation, Operation and Maintenance Instructions

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.

“UL CLASSIFIED (see complete marking on product)”“UL CLASSIFIED to Canadian safety standards (see complete marking on product)” UL Standard 555 (Listing #R13317)

RECEIVING AND HANDLING

Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.

Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).

FD, DFD, SSFD, & KFD models are intended for installation in accordance with fire damper requirements established by:

National Fire Protection Association NFPA Standard 80, 90A, & 101

IBC International Building Code

CSFM California State Fire Marshal

Fire Damper Listing (#3225-0981:102)

New York City (BSA/MEA listing #260-91-M)

Document Number 452763FD, DFD, SSFD, SSDFD, & KFD Models

11/2 and 3 Hour Curtain Fire DampersVertical and Horizontal Mount

SAFETY WARNING:

Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.

WARRANTY

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.

These instructions apply to 11/2 and 3 hour rated fire dampers mounted (blades must be horizontal) in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. UL listing R13317, California State Fire Marshal listings 3225-0981:102, and New York City BSA/MEA listing 260-91-M apply to these dampers.Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling.

Installation SupplementsRefer to the appropriate Greenheck installation supplements for special requirements: • Close Indicator Switch • Concrete Floor with Steel Deck • Drive Slip Breakaway Connection • Fire Resistant Ventilated Duct Assembly • Firestop Material • Greenheck Test Switch • Grille Installation • Metal Stud in Shaftwall • Quick Connect Breakaway Connections • Sealant Supplement • Single Side Retaining Angle • Single 3-Sided Retaining Angle - Vertical Mount • Sleeve Extension • Support MullionsNote: Refer to Greenheck IOM, Part #461335, for CFSD

models to be installed in corridor ceiling applications.

Due to continuing research, Greenheck reserves the right to change specifications without notice.

®

2

Page 3: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Pre-Installation GuidelinesThe basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.

1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not activated. Never install a fire damper without the proper UL approved fusible link in place. If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary.

2) Lift or handle damper using sleeve or frame. Do not lift damper using blades.

3) Damper has label on outside of sleeve indicating a ‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing.

4) Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number.

5) Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned

installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design.

6) Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to:

a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray

7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design.

8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.

9) ACCESS: Suitable access (such that fusible links can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).

10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.

Table of ContentsPre-Installation Guidelines..............................................................................................................................................................3 Installation ...................................................................................................................................................................................3-9 • Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings............................................................3 • Sleeve Length and Wall Thickness .............................................................. ..............................................................4-5 • Duct to Sleeve Connections ......................................................................... .................................................................6 • Securing the Damper/Sleeve Assembly to Wall and Floor Openings ....................................................... .....................6 • Installing Multiple Damper Section Assemblies ............................................................................................................7 • Recommended Preparation of Openings in Wood and Metal Stud Walls ........................................................... ...........9 • Breakaway Connections .................................................................... .........................................................................7-8

1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS

Fire damper and sleeve assemblies expand during periods of intense heat. Therefore it is essential that openings in walls or floors be larger than the fire damper and sleeve assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are:

• Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per foot of damper width and 1/8 in. (3mm) per foot height with a minimum clearance of 1/4 in. (6mm) Recommended clearances, for width and/or height dimensions of:

1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm)

or less: 1 in. (25mm) clearance

3) More than 96 in. (2438mm): 1 1/2 in. (38mm) clearance

• Stainless steel fire dampers and stainless steel or galvanized sleeves: 3/16 in. (4.8mm) per foot of damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm). Recommended clearances, for width and/or height dimensions of:

1) 48 in. (1219mm) or less: 3/4 in. (19mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or

less: 1 1/2 in. (38mm) clearance 3) More than 96 in. (2438mm): 2 in. (51mm)

clearance These are total clearances (ignoring fastener heads)

and do not need to be equally spaced around the damper. Refer to Section 4 and Figure 6 for additional installation considerations.

3

Page 4: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Example: A 12 in. x 12 in. (305mm x 305mm) damper would re-quire a minimum clearance of 1/4 in. (6mm) on width and 1/4 in. (6mm) on height

A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height.

2. GAUGES AND LENGTHS OF FIRE DAMPER SLEEVES

All fire dampers must be installed in a steel sleeve of the required gauge and length. See Table 1 for required minimum sleeve gauges. Maximum sleeve thickness is 10 gauge (3.5mm). Sleeve inside dimensions must equal damper outside dimensions.

Sleeves shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side (see Figure 1). When an access door is incorporated as a part of sleeve, the sleeve may extend a maximum of 16 in. (406mm) beyond the wall or floor opening on the access door side.

Table 1: Minimum sleeve thickness for fire dampers.

Sleeve Gauge Duct Dimension

Type of Duct to Sleeve

Connection Permitted

14 ga. (0.075 in.) - 10 ga. (0.138

in.)[2mm - 3.5mm]

All duct sizesRigid or

Breakaway

16 ga. (0.060 in.)[1.5mm]

36 in. (914mm) max. width24 in. (610mm) max. width24 in. (610mm) diameter

Rigid or Breakaway

16 ga. (0.060 in.)[1.5mm]

All duct sizes

Breakaway only

18 ga. (0.048 in.)[1.2mm]

85 in. (2159mm) wide and over

20 ga. (0.036 in.)[0.9mm]

55 in. - 84 in. wide(1397mm - 2134mm)

22 ga. (.030 in.)[0.76mm]

31 in. - 54 in. wide(787mm - 1372mm)

24 ga. (0.024)[0.6mm]

13 in. - 30 in. wide(330mm - 762mm)

26 ga. (0.018 in.)[0.46mm]

12 in. wide and under(305mm)

Sleeve thickness must not be less than the gauge of the connecting duct.UL Standard 555 requires all ducts to terminate at fire damper sleeves.

Damper

1/4 in. minimumtotal clearance(See Section 1)

See Section 2

See Section 2

Wall or floor

Wall or floor

Wall or floor

Damper

Damper

Duct

Duct

Duct

Retaining Angles(See Section 4)

Sleeve(See Sections 2 & 3)

Sleeve

Sleeve

On types R & CR factoryfurnished duct collarqualifies as breakawayconneciton (See Section 5)

1 in. min. overlapFour sides

Mounting Angles(See Para. 4)

1/4 in. minimum total clearance(See Para. 1)

Retaining angle leg shall not exceed 7 in. (178mm)

Type C, CO, CR & R

Type B

Vertical mount without factory mounted sleeve

Type A

When dampers installed vertically, the blade stack must be on the top..

Figure 14

Page 5: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Horizontal mount with factory mounted sleeve

Wall or Floor

Retaining Angles(See Section 4)

Sleeve(see sections 2 & 3)

Duct

“K” side

Damper

See Section 2

See Section 2

Type A

Wall or Floor

Retaining Angles(See Section 4)

Sleeve(see sections 2 & 3)

Duct

“K” side

Damper

See Section 2

See Section 2

Type B

Wall or floor

On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5

Duct

Sleeve

Type C, CO, CR, & R

“K” side

When dampers installed horizontally, the ramp must be positioned up as

shown in above drawings.

1/4 in. minimumtotal clearance

Wall or Floor

Maximum 6 in.

Maximum 6 in.

Duct

Duct

Duct

Damper

Damper

Damper

Wall or Floor

Wall or Floor

Retaining Angles (See Section 3)

Type A

Type B

On types R, CO & CR factoryfurnished duct collarqualifies as breakaway connection.

Type C, CO, CR, & R

1/4 in. minimumtotal clearance

Wall or Floor

Maximum 6 in.

Maximum 6 in.

Duct

Duct

Duct

Damper

Damper

Damper

Wall or Floor

Wall or Floor

Retaining Angles (See Section 3)

Type A

Type B

On types R, CO & CR factoryfurnished duct collarqualifies as breakaway connection.

Type C, CO, CR, & R

1/4 in. minimumtotal clearance

Wall or Floor

Maximum 6 in.

Maximum 6 in.

Duct

Duct

Duct

Damper

Damper

Damper

Wall or Floor

Wall or Floor

Retaining Angles (See Section 3)

Type A

Type B

On types R, CO & CR factoryfurnished duct collarqualifies as breakaway connection.

Type C, CO, CR, & R

Vertical mount with factory mounted sleeve

Wall or floor

On types R & CR factory furnished duct collar quali-fies as breakaway connection, see Section 5

Duct

Sleeve

Type C, CO, CR, & R

“K” side

Sleeve(See Sections 2 & 3)

Duct

Retaining angles(See Section 4)

Type B

See Section 2

See Section 2

“K” side

Damper

Wall or Floor

Wall or Floor

Retaining Angles(See Section 4)

Sleeve(see sections 2 & 3)

Duct

“K” side

Damper

See Section 2

See Section 2

Type A

Horizontal mount without factory mounted sleeve

When dampers installed horizontally, the ramp must be positioned up as

shown in above drawings. When dampers installed vertically, the blade stack must be on the top.Figure 1

Type B2

Type B2

Wall or floor

Damper

Sleeve

Wall or floor

Damper

Sleeve

Type B2

Type B2

Wall or floor

Damper

Sleeve

Wall or floor

Damper

Sleeve

5

Page 6: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

3. ATTACHING FIRE DAMPERS TO SLEEVES Fire dampers must be attached to sleeves as shown in

Figure 3. All four sides of the damper frame must be attached to the sleeve with one row of attachments on each side of the blade channel. Attachments must be spaced a maximum of 6 in. (152mm) on centers and a maximum of 2 in. (51mm) from corners. A minimum of 4 attachments (2 on each side of the blade channel ) per side (16 per damper) are required. One of the methods of attachment shown below must be used.

• tack or spot welds• #10 sheet metal screws • 1/4 in. (6mm) bolts and nuts• 3/16 in. (4.7mm) steel pop rivets

4. SECURING FIRE DAMPER AND SLEEVES TO WALL AND FLOOR OPENINGS.

The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall or floor.

Fire damper and sleeve assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below: • Retaining angles for 11/2 hour rated dampers with a

width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm). (See Figure 4). Retaining angle legs may be reversed with leg of retaining angle with annular space of opening so angle and sleeve is flush against barrier.

• Retaining angles must be attached to the sleeve using the procedures and methods described in Section 3. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners.

• Retaining angles should not be fastened to the wall/floor material. The angles should only sandwich the wall/ floor and allow for damper/sleeve expansion during periods of intense heat.

For single retaining angle applications, see Single Side Retaining Angle Supplement (#474015).

No Connecting Duct or Transfer OpeningOpenings where duct does not attach on either side will not

require a breakaway connection. Transfer openings are typical of a non-ducted installation (see Figure 2).

• Sleeve may end flush with the rated wall/floor on both sides

• Refer to Section 4 for securing retaining angles to sleeves.

5. CONNECTING DUCTS TO FIRE DAMPER SLEEVE Any duct connection other than breakaway is considered

rigid. The connections shown on this page are considered breakaway. Factory furnished duct collars on type R and CR fire dampers are also considered breakaway (see Figure 1).

Figure 3: Field attachment of fire dampers to sleeves.

Attachments--Do not place attachments between blade channels

Blade Channel

2 in. Max.

6 in. Max.Attachments can be staggered or evenlyspaced.

NOTE: Attachments must not enter blade channel or they may cause interference with blade closure. Narrow Line and Ultra Thin dampers do not have flange for attachments and must be welded to sleeve.

Figure 2 Transfer opening or no connecting duct

Figure 4: Retaining angle installation.

Retaining Angle

Wall or Floor

Min. 1 in. overlay*

Duct

Sleeve

Retainingangle

Damper

2 in. Max.

2 in. Max.

6 in. Max.

6 in. Max.

6

Page 7: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Plain “S” Slip Hemmed “S” Slip Double “S” Slip

Inside Slip Joint Standing “S” Standing “S” (Alt.)

Standing “S” (Alt.) Standing “S” Standing “S” (Bar Reinforced) (Angle Reinforced)

DUCT-SLEEVE CONNECTIONSTraditional Breakaway Style Transverse JointsTransverse joints illustrated in Figure 5 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. • The breakaway connections shown to the right can be

applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket.

• Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm).

Drive Slip Joint

Figure 5: Traditional breakaway style transverse joints.

Table 2: Maximum section sizes and overall sizes for multiple section dampers (W x H).

Note: All dimensions shown are in inches (W x H).* Sizes listed is the damper size not transition size.

Damper Model MountingMaximum Single

Section Damper Sizes*Maximum Multi-Section

Damper Sizes*

FD-100 , FD-300, FD-310, SSFD-350 Vertical 48 X 48 (1219mm x 1219mm) -

FD-150 Vertical or Horizontal 48 X 48 (1219mm x 1219mm)96 x 48 (2438mm x 1219mm) or120 x 40 (3048mm x 1016mm)

FD-110 Vertical or Horizontal 48 x 48 (1219mm x 1219mm) 96 x 48 (2438mm x 1219mm)

SSFD-150Vertical 48 X 48 (1219mm x 1219mm)

96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm)

Horizontal 36 x 36 (914mm x 914mm) -

FD-350Vertical 48 x 48 (1219mm x 1219mm) -

Horizontal 40 x 40 (1016mm x 1016mm) 80 x 40 (2032mm x 1016mm)

KFD-150 Vertical or Horizontal 36 x 16 (914mm x 406mm)96 x 48 (2438mm x 1219mm) or120 x 40 (3048mm x 1016mm)

KFD-110 Vertical or Horizontal 36 x 16 (914mm x 406mm) 96 x 48 (2438mm x 1219mm)

SSKFD-150 Vertical 36 x 16 (914mm x 406mm)96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm)

KFD-350Vertical 36 x 16 (914mm x 406mm) -

Horizontal 36 x 16 (914mm x 406mm) 80 x 40 (2032mm x 1016mm)

SSKFD-350 Vertical 36 x 16 (914mm x 406mm) -

DFD-150, DFD-110

Vertical 36 x 36 (914mm x 914mm)72 x 48 (1828mm x 1219mm) or60 x 60 (1524mm x 1524mm) or

120 x 30 (3048mm x 762mm)

Horizontal24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm)

30 x 30 (762mm x 762mm) -

DFD-350

Vertical 36 x 36 (914mm x 914mm) -

Horizontal24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm)

30 x 30 (762mm x 762mm)

DFD-310Vertical 36 x 36 (914mm x 914mm) -

Horizontal 30 x 30 (762mm x 762mm) -

SSDFD-110, SSDFD-150. SSDFD-350 Vertical 30 x 30 (762mm x 762mm) -

6. MULTIPLE SECTION FIRE DAMPERS When multiple sections are shipped unassembled, installer shall fasten dampers together as described in Section 3.

Table 2 shows maximum sizes for multiple section dampers. Dampers that are two or more sections tall must be factory assembled.

7

Page 8: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Fire Damper Sleeve

Neoprene gasketbetween all angles

Flanged system angles

(Attach permanufacturer'sinstructions)

Duct

Do not bolt corners

6 in. long 1/16 in. max.thickness plastic cleats;12 in. c-c (min. 1 per side)

Manufactured Flanged System Breakaway ConnectionsFlanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 6.

Figure 6: Detail of manufactured flanged system breakaway connections.

Round and Oval Duct Breakaway ConnectionsRound ducts connected to factory supplied Type R or CR damper collars may use #10 sheet metal screws as follows: • Ducts 22 in. (559mm) wide (or dia.) and smaller may use

3 screws. • Ducts larger than 22 in. (559mm) wide (or dia.) may use

5 screws.NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision or DP1010 water base duct sealant by Design Polymetrics, Grey Pookie, or Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.

DuctSleeve

6 in.

Std. ClipLength

CLDuct

60 in. Duct4 Req’d.

48 in. Duct3 Req’d.

36 in. Duct3 Req’d.

24 in. Duct2 Req’d.

18 in. Duct &Smaller1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in. 6 in.9 in.

7 in.7 in.

5 in. 5 in.

5 in.5 in.

Proprietary Flange System Breakaway Connections(TDC by Lockformer, TDF by Engle)

TDC and TDF systems are approved as breakaway con-nections when installed as described in the SMACNA Duct Construction Standards. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure 7. Three-eighths in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces.

Figure 7: Detail of proprietary flanged system breakaway connections.

DuctSleeve

6 in.

Std. ClipLength

CLDuct

60 in. Duct4 Req’d.

48 in. Duct3 Req’d.

36 in. Duct3 Req’d.

24 in. Duct2 Req’d.

18 in. Duct &Smaller1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in. 6 in.9 in.

7 in.7 in.

5 in. 5 in.

5 in.5 in.

DUCT-SLEEVE CONNECTIONS cont...

Recommended Preparation of Openings in Wood and Metal Stud Walls

• Frame wall openings as shown in Figure 8 & 8A.• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see

Figure 8 & 8A).• Prepare opening between studs and sleeve assembly as shown (see. Figure 9).• All construction and fasteners must meet the requirements of the appropriate wall design. (See UL Fire Resistance

Directory)

Metal Stud Construction

Gypsum Wallboard

Retaining Angle

Stud or Runner

1in. (25mm) minimum

Damper Sleeve

In metal stud construction, exposed steel surfaces need not be covered with gypsumwallboard.

Wooden Stud Construction

Gypsum Wallboard

Stud or Runner

1in. (25mm) minimum

Retaining Angle

Damper Sleeve

In wood stud construction,gypsum wallboard must coverall wood stud surfaces.

Figure 9: Detail of retaining angles and gypsum board application for metal and wooden stud construction.

Metal Stud Construction

Gypsum Wallboard

Retaining Angle

Stud or Runner

1in. (25mm) minimum

Damper Sleeve

In metal stud construction, exposed steel surfaces need not be covered with gypsumwallboard.

Wooden Stud Construction

Gypsum Wallboard

Stud or Runner

1in. (25mm) minimum

Retaining Angle

Damper Sleeve

In wood stud construction,gypsum wallboard must coverall wood stud surfaces.

8

Page 9: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

12 in.

24 in. o.c.Maximum

24 in. o.c.Maximum

(metal studs)

24 in. o.c.Maximum

(metal studs)

16 in. o.c.Maximum

(wood studs)

16 in. o.c.Maximum

(wood studs)

Ceiling Runner

2 Panhead Screws

2 in. (51mm)

2 in. (51mm)

Floor Runner

Figure 8: Preparation detail for opening in stud wall.

Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.

Metal stud only

Figure 8A

Damper MaintenanceDampers shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections.Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract con-taminant’s such as dust.

Damper Trouble ShootingThe following is a cause and correction list for common concerns with the dampers.

Symptom Possible Cause Corrective Action

Damper does not fully open and/or fully close

Frame is 'racked' causing blades to bind on jamb

Adjust frame such that it is square and plumb

Screws in damper linkage Locate screws and remove

Contaminant's on damper Clean with a non-oil based solvent (see Damper Maintenance)

Link separated Heat Replace link

452763• DFD, FD, SSDFD Series Rev. 17, August 2013 Copyright 2013 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifica-tions without notice.Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

9

Page 10: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.

“UL CLASSIFIED (see complete marking on product)”“UL CLASSIFIED to Canadian safety standards (see complete marking on product)” UL Standard 555 (Listing #R13317)

RECEIVING AND HANDLINGUpon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.

Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F.

Document Number 453946

INSTALLATION SUPPLEMENTSRefer to the appropriate Greenheck installation supplements for special requirements:• Support Mullions• Shaftwall Supplement• Drywall Supplement• Grille Installation Supplement• Drive Slip Supplement• Sealant Supplement• Sleeve Extension Supplement• Single side Retaining Angles SupplementNote: Refer to Greenheck IOM, Part #461335, for

CFSD models to be installed in corridor ceiling applications.

Refer to Greenheck IOM, Part # 452763 for standard DFD and FD models.

FD & DFD 150X MODELS1 1⁄2 Hour

Curtain Fire DampersVertical or Horizontal Mount

FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standard 80, 90A, & 101 IBC International Building Codes CSFM California State Fire Marshal Fire Damper Listing (#3225-0981:102) New York City (BSA/MEA listing #260-91-M)

STAT

E OF CALIFORNIA

STATE

FIR E MAR S HALL

S E R V I C E

L I S T I N G

Installation, Operation and Maintenance Instructions

Due to continuing research, Greenheck reserves the right to change specifications without notice.

SAFETY WARNING:Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.

WARRANTYGreenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.

®

10

Page 11: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Pre-Installation GuidelinesThe basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.

1. Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. (Fusible link is standard control option. An electric link may have been provided.)

2. Lift or handle damper using sleeve or frame.3. Install damper accordingly to comply with manufacturer’s appropriate UL procedure file number.

4. Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening.

5. Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include, but are not limited to:

a. Mortar dustb. Drywall dustc. Firesafing materialsd. Wall texturee. Paint overspray

6. Damper should be sufficiently covered as to prevent overspray of spray-on insulating, wall texturing, or spray painting when performed within 5 feet of the damper. Excessive dirt or foreign material deposits can cause damper to bind and not operate properly.

7. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.

8. ACCESS: Suitable access (such that fusible links can be changed) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).

9. The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.

Table of Contents

Pre-Installation Guidelines .........................................................................................................................................11Installation ............................................................................................................................................................12-14 Breakaway Connections ............................................................................................................................................15Installation for Steel Stud Connection Option ..........................................................................................................16Damper Maintenance .................................................................................................................................................17Damper Troubleshooting ............................................................................................................................................17

11

Page 12: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Example: A 12 in. x 12 in. (305mm x 305mm) damper would require a minimum clearance of 1/4 in. (6mm).

A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height.

These instructions apply to 11/2 hour rated fire dampers mounted in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listing R13317, California State Fire Marshal listings 3225-981:102, and New York City BSA/MEA listing 260-91-M as they apply to these dampers.

Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling.

1. NO ADDITIONAL SLEEVES ARE REQUIRED The fire damper extended frame is an approved

sleeve and can be properly installed without the need for a supplemental field installed sleeve. Damper frame shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side.

2. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS

Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are:

• Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per linear foot of damper width and height with a minimum clearance of 1/4 in. (6mm) .Recommended clearances, for width and/or height dimensions of:

1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm)

or less: 1 in. (25mm) clearance 3) More than 96 in. (2438mm): 11/2 in. (38mm)

clearance

These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 3 and Figure 1 for additional installation considerations.

Installation - Failure to follow these instructions will void all warranties.

2 in. Max.

6 in. Max.

Sleeve

RetainingAngle

Damper

Duct

Min. 1 in.Overlap*

Wall orFloor

RetainingAngle

*only applicable for damper sizes above 36 in. x 36 in.

6 in. Max.

2 in. Max.

Figure 1: Retaining angle installation.

3. SECURING THE FIRE DAMPER TO WALL AND FLOOR OPENINGS

Fire damper assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below:

• Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm).

• Retaining angles must be attached to the damper using one or more of the following methods of attachment:

• tack or spot welds • #10 sheetmetal screws • 1/4 in. (6mm) bolts and nuts • 3/16 in. (4.7mm) steel pop rivets Attachments must be spaced a maximum of 6 in.

(152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners.

• Retaining angles should not be fastened to the wall/floor material. The angles should only sandwich the wall/floor and allow for damper expansion during periods of intense heat.

12

Page 13: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Table 1

Damper ModelMaximum Sizes for Single

Section Dampers* in. (mm)

FD-150X (H or V) 48 x 48 (1219 x 1219)

DFD-150X (V) 36 x 36 (914 x 914)

DFD-150X (H) 30 x 30 (762 x 762)

Note: V = Vertical mount & H = Horizontal

* Sizes are based on damper with no transitions.

Wall or Floor

Retaining Angles(See Section 4)

Sleeve(see sections 2 & 3)

Duct

“K” side

Damper

See Section 2

See Section 2

Type A

Dampe

See Section 2e

See Section 2

Wall or FloorW

Wall or Floor

Retaining Angles(See Section 4)

Sleeve(see sections 2 & 3)

Duct

“K” side

Damper

See Section 2

See Section 2

Type B

Wall or floor

On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5

Duct

Sleeve

Type C, CO, CR, & R

“K” side

Figure 3: Horizontal Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams.

When dampers installed horizontally, the ramp must be positioned up as shown in above drawings.

Figure 2: Vertical Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams.

1/4 in. minimumtotal clearance

Wall or Floor

Maximum 6 in.

Maximum 6 in.

Duct

Duct

Duct

Damper

Damper

Damper

Wall or Floor

Wall or Floor

Retaining Angles (See Section 3)

Type A

Type B

On types R & CR factoryfurnished duct collarqualifies as breakaway connection.

Type C, CO, CR, & R

1/4 in. minimumtotal clearance

Wall or Floor

Maximum 6 in.

Maximum 6 in.

Duct

Duct

Duct

Damper

Damper

Damper

Wall or Floor

Wall or Floor

Retaining Angles (See Section 3)

Type A

Type B

On types R & CR factoryfurnished duct collarqualifies as breakaway connection.

Type C, CO, CR, & R

1/4 in. minimumtotal clearance

Wall or Floor

Maximum 6 in.

Maximum 6 in.

Duct

Duct

Duct

Damper

Damper

Damper

Wall or Floor

Wall or Floor

Retaining Angles (See Section 3)

Type A

Type B

On types R & CR factoryfurnished duct collarqualifies as breakaway connection.

Type C, CO, CR, & R

4. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series extended frame dampers must be “breakaway” type connections. All

connections shown are considered breakaway. Factory furnished duct collars on types R & CR fire dampers are also considered breakaway(see Figure 2 & 3).

13

Page 14: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Metal Stud Construction

Wooden Stud Construction

In wood stud construction,gypsum wallboard must coverall wood stud surfaces.

Gypsum Wa llboard

Stud or Runner

RetainingAngl e

1 in. Min.

DamperSleeve

In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.

Gypsum Wallboard

Stud or Runner

RetainingAngle

1 in. Min.

DamperSleeve

Metal Stud Construction

Wooden Stud Construction

In wood stud construction,gypsum wallboard must coverall wood stud surfaces.

Gypsum Wa llboard

Stud or Runner

RetainingAngl e

1 in. Min.

DamperSleeve

In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.

Gypsum Wallboard

Stud or Runner

RetainingAngle

1 in. Min.

DamperSleeve

Recommended Preparation of Openings in Wood and Metal Stud Walls• Frame wall openings as shown in Figure 4 and 4A.

• Gypsum wall board must be fastened 12 in. on center to all stud and runner flanges surrounding opening (see Figure 4 and 4A).

• Prepare opening between studs and sleeve assembly as shown below (see Figure 5).

• All construction and fasteners must meet then requirements of the appropriate wall design. (See UL Fire Resistance Directory)

12 in.

24 in. o.c.Maximum

Floor Runner

Ceiling Runner24 in. o.c.Maximum

(metal studs)

24 in. o.c.Maximum

(metal studs)

16 in. o.c.Maximum

(wood studs)

16 in. o.c.Maximum

(wood studs)

2 in. (51mm)

2 in. (51mm)

2 Panhead Screws

Figure 4: Preparation detail for opening in stud wall.

Figure 5: Detail of retaining angles and gypsum board application for metal and wooden stud construction.

Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.

Metal stud only

Figure 4A

14

Page 15: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

DuctSleeve

6 in.

Std. ClipLength

CLDuct

60 in. Duct4 Req’d.

48 in. Duct3 Req’d.

36 in. Duct3 Req’d.

24 in. Duct2 Req’d.

18 in. Duct &Smaller1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in. 6 in.9 in.

7 in.7 in.

5 in. 5 in.

5 in.5 in.

Figure 8: Detail of proprietary flanged system breakaway connections.

Duct EndFlange

Corner Piece

3/8 in. bolt (optional)

Figure 9: Detail of bolted corner.

(TDC by Lockformer, TDF by Engle)TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Duct Construction Standards. Standard 6 in. metal clips may be used with spacing (see Figure 8). Three-eighth in. metal bolts and nuts may be used to fasten together corner pieces (see Figure 9).

Plain “S” Slip Hemmed “S” Slip Double “S” Slip

Inside Slip Joint Standing “S” Standing “S” (Alt.)

Standing “S” (Alt.) Standing “S” Standing “S” (Bar Reinforced) (Angle Reinforced)

Duct-Sleeve ConnectionsTraditional Breakaway Style Transverse JointsTransverse joints illustrated in Figure 6 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections.

• The breakaway connections shown to the right can be applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket.

• Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 in. (508mm).

Round and Oval Duct Breakaway ConnectionsRound or flat oval ducts connected to factory supplied Type R, CR, or CO damper collars may use #10 sheet metal screws as follows: • Ducts 22 in. (559mm) wide (or dia.) and smaller may

use 3 screws. • Ducts larger than 22 in. (559mm) wide (or dia.) may

use 5 screws.

Drive Slip Joint

Figure 6: Traditional breakaway style transverse joints.

NOTE: All breakaway connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal applied in accordance with SMACNA recommendations.

Figure 7: Detail of manufactured flanged system breakaway connections.

Do not bolt corners

Fire Damper Sleeve

(Attach per manufacturer’sinstructions)

Duct

Neoprene gasketbetween all angles

Flanged system angles

6 in. long 1/16 in. max.thickness plastic cleats;12 in. c-c (min. 1 per side)

Proprietary Flange System Breakaway Connections (Ductmate, Ward, Nexus)Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 7.

15

Page 16: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Top Cross-section ViewSide Cross-Section Viewof Damper in Wall

Retaining Bar

35

1

1

3

3

3

6

4

4 2

2

These instructions apply to 11/2 hour rated fire dampers mounted in steel stud walls. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listings R13317 and R13743, California State Fire Marshal listings 3225-981:102 and 3225-1241:101, and New York City BSA/MEA listing 260-91-M as they apply to these dampers.

Installation for Steel Stud Connection (SSC) Option

1. NO ADDITIONAL SLEEVES OR ANGLES ARE REQUIRED

The fire damper extended frame is an approved sleeve and the Steel Stud Connection (SSC) Option allows fastening of the fire damper sleeve directly to the wall's steel stud framing. Damper frame shall extend a maximum of 6 in. (152mm) beyond the wall opening on either side. Maximum size fire damper that may be installed using this SSC option is 36 in. W x 36 in. H (914mm x 914mm).

2. INSTALLATION Fire damper with SSC option must be in place before

the wall is constructed or it can be installed as the wall is being constructed. Wall opening is framed around the fire damper before sheet rock or other wall board material is applied to the steel studs. This installation provides appropriate protection for duct penetrations in fire resistant wall construction using steel studs with a fire resistance rating less than 3 hours. The following wall design numbers (as detailed in the UL Fire Resistance Directory) are appropriate for fire damper installations using this SSC option:

1 Hour Design: U405, U406, U422, U434, U448, U451, U456, U457, U465, U468, U469, U485, U494

11/2 Hour Design: U449, U452, U470, U471

2 Hour Design: U403, U411, U412, U421, U425, U428, U429, U443, U453, U474, U475, U477, U484, U491, U495

Item Description

1 FD150X fire damper with SSC option

2 Steel stud wall (see UL Fire Resistance Directory for spe-cific details)

3 Steel stud frame around opening in wall

4 Duct connection (see section 6)

5 Wallboard (see UL Fire Resistance Directory for specific details)

6 Fasteners (see UL Fire Resistance Directory and Section 5)

Top Cross-section ViewSide Cross-Section Viewof Damper in Wall

Retaining Bar

35

1

1

3

3

3

6

4

4 2

2

Top Cross-section ViewSide Cross-Section Viewof Damper in Wall

Retaining Bar

35

1

1

3

3

3

6

4

4 2

2

3. FRAMING OF WALL OPENING Form a wall opening 1/8 in. (3mm) to 1/4 in. (6mm)

larger than the OD of the fire damper's extended frame (sleeve) using the same metal studs and techniques required by the wall design per the UL Fire Resistance Directory. Open side of the steel stud channels shall face the fire damper and encompass the damper's retaining bar.

4. APPLY WALLBOARD AFTER DAMPER INSTALLATION

After damper is installed, wallboard shall be applied to steel stud framework in the manner required by the wall design per the UL Fire Resistance Directory listing. Around the damper perimeter use a minimum of 2 connections per side, spaced 12 in. (305mm) maximum and located a maximum of 2 in. (51mm) from each corner. No additional retaining angles are required to complete the installation.

5. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series

extended frame dampers must be “breakaway” type connections. All connections shown on page 5 & 6 are considered breakaway. Factory furnished duct collars on types R, CR, & CO fire dampers are also considered breakaway.

16

Page 17: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Damper MaintenanceDampers shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections.Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract contaminant’s such as dust.

Damper Trouble ShootingThe following is a cause and correction list for common concerns with the dampers.

Symptom Possible Cause Corrective Action

Damper does not fully open and/or fully close

Frame is 'racked' causing blades to bind on jamb

Adjust frame such that it is square and plumb

Screws in damper linkage Locate screws and remove

Contaminant's on damper Clean with a non-oil based solvent (see Damper Maintenance)

Link separated Heat Replace link

453946• DFD & FD 150X Series Rev. 15, August 2013 Copyright 2013 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifica-tions without notice.Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

17

Page 18: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

DOCUMENT NUMBER 462721DFDR-XXX, SEDFDR-XXX,

SSDFDR-XXX, FDR-XXX, and SSFDR-XXX MODELS

1 1⁄2 Hour Round Fire DampersVertical and Horizontal Mount

SAFETY WARNING:Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.

WARRANTYGreenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.

Due to continuing research, Greenheck reserves the right to change specifications without notice.

“UL CLASSIFIED (see complete marking on product)”“UL CLASSIFIED to Canadian safety standards (see complete marking on product)” UL Standard 555 (Classification #R13317)

DFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR-XXX Model Dampers are intended for installation in accordance with fire damper requirements established by:National Fire Protection Association NFPA Standards 80, 90A, 101 and 105IBC International Building CodesNew York City (MEA listing #260-91-M)California State Fire Marshal (CSFM)Fire Listing (3225-0981:0112)

RECEIVING AND HANDLINGUpon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.

Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (37°C).

INSTALLATION SUPPLEMENTSRefer to the appropriate Greenheck installation supplements for special requirements:

• Steel Deck Supplement

Installation, Operation and Maintenance Instructions

®

18

Page 19: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Pre-Installation GuidelinesThe basic intent of a proper installation is to secure the fire damper in the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.

Table of ContentsPre-Installation Guidelines .......................................................................................................19 Installation ...........................................................................................................................19-22 Maintenance .............................................................................................................................19Troubleshooting ........................................................................................................................19

These instructions apply to 1 1/2 hour rated fire dampers mounted (blades must be horizontal) in: 1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555. The installation of the damper and all duct

Installation - Failure to follow these instructions will void all warranties.

connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications R13317.

1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. Dampers will be supplied with a temperature responsive fusible link device. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place.

2) Lift or handle damper using the frame. Do not lift damper using blades.

3) Do not install screws into the main body area of the damper frame as screws may interfere with and prevent damper blade from opening and/or closing.

4) Damper must be installed into duct or opening free of distortion or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of round, racked, twisted or misaligned installations can cause torque requirements to exceed damper design.

5) Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: 1) Mortar dust 2) Drywall dust 3) Firesafing materials 4) Wall texture and 5) Paint overspray.

6) Damper should be sufficiently covered to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause torque requirements to exceed damper design.

7) Caulking is not allowed between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining plates and a field-applied sealant may be required for the damper sleeve and transitions to meet certain duct leakage standards.

8) ACCESS: Suitable access (such that fusible links can be maintained) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).

9) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.

19

Page 20: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

2 in.

TW

AIRFLOW

SLEEVE LENGTH

2 in.

6 in. max.6 in. max.

(OPTIONAL)RETAINER PLATE

DUCT CONNECTIONAREA

CLEARANCE FOREXPANSIONRETAINER PLATE

BLADE LATCHACCESS DOOR TO BE ONSAME SIDE AS BLADE LATCH

DUCT CONNECTIONAREA

DO NOT PLACE RETAINERPLATE IN THIS GROOVE

1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS

Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. The wall/floor opening must be a minimum of 7/8 in. (22mm) larger than the outside diameter of the damper. Refer to Section 4 for additional installation considerations.

Fig. 1

Installation - Continued

2. SLEEVE LENGTH AND WALL/FLOOR THICKNESS

Insert the damper assembly into the prepared opening, to appropriate depth (see Fig. 1).

Recommended maximum and minimum insertion depth can be exceeded as long as the CL of the damper blade remains within the plane of the wall/floor.

IMPORTANT SAFETY DANGER! To avoid causing death or serious bodily harm to building occupants, do not insert screws into the damper frame unless used for duct connection within 2 in. (51mm) of the frame end.

The sleeve may extend a maximum of 6 in. (152mm) beyond both sides of the wall or floor. Recommended standard sleeve lengths for various wall/floor thicknesses are:

3. DUCT TO SLEEVE CONNECTIONS Dampers are supplied with sleeves from the factory

4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS

Damper assemblies must be installed in wall/floor openings using a single retaining plate on either side of the wall/floor or by using a retaining plate on both sides of the wall/floor. The use of a second retaining plate is allowed, but is not necessary. A single retaining plate is provided with the dampers. A second retaining plate can be ordered as an option.

• The retaining plate(s) will open up for easy installation when the clamping screw is loosened. If necessary, remove the clamping screw and nut (see Fig. 2).

(IMPORTANT: The clamping mechanism should face away from the wall/floor). Retainer plate(s) are designed to mount flush to the wall/floor and hold the damper in the wall/floor opening.

• Place the damper and attached retainer plate into the wall/floor opening.

• If a second retaining plate is being used, secure it on the opposite side of the wall/floor

DO NOT POSITION RETAINER PLATE(S) IN FRAME GROOVE

• Verify position, blade orientation, and actuator clearance then tighten the retainer plate clamping screws. The retainer plate(s) must overlap the wall/floor opening a minimum of 1 inch (25mm). Secure the retainer plate(s) to the wall using appropriate fasteners (minimum #8 sheet metal screws) at the four corners of each retainer plate when two retainer plates are used and also within 3/4 in. (19mm) of the center of each plate when one retainer plate is used.

Wall/Floor Thickness

Dimension (Tw)Inches (mm)

Sleeve LengthDimension (L)Inches (mm)

Up to 61/2 (165) 13 5/8 (346)

61/2 - 81/2 (165 - 216) 15 5/8 (397)

81/2 - 101/2(216 - 267)

17 5/8 (448)

Sleeve Gauge(mm)

Duct DimensionMaximum

Inches (mm)

Type of Duct to Sleeve

Connection Permitted

10 ga. (3.5)

24 (610) Rigid or Break-

away14 ga. (2)

16 ga. (1.5)

20 ga. (1mm) 24 (610) Breakaway only

Sleeve thickness must not be less than the gauge of the connecting duct.

UL Standard 555 requires all ducts to terminate at fire damper sleeves.

and can be installed without the need for additional field installed sleeves.

Gauge of factory furnished sleeve determines the type of duct to sleeve connections required (see table below). Any duct connection other than the breakaway connections are considered rigid.

20

Page 21: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.

Metal stud only

12 in.

24 in. o.c.Maximum

Floor Runner

2 in .

Ceiling Runner

2 PanheadScrews

24 in. o.c.Maximum

(metal studs)

24 in. o.c.Maximum

(metal studs)

16 in. o.c.Maximum

(wood studs)

16 in. o.c.Maximum

(wood studs)

2 in .

Fig. 4

Round duct connections shall be attached with #8 sheet metal screws as follows: • Ducts 22 in. (559mm) dia. and smaller shall have

three screws.

• Ducts larger than 22 in. (559mm) dia. and up to including 24 in. dia. shall have five screws.

NOTE: All breakaway connections described may have duct sealant, PA2084T Duct Sealant Adhesive manufactured by Precision or DP1010 Water Base Duct Sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal® , or CL Ward S Seal applied in accordance with SMACNA recommendations.

6. Round Duct Connections

IN THIS GROOVE.RETAINER PLATEDO NOT PLACE

IN THIS GROOVE.

DO NOT PLACERETAINER PLATE

DAMPER FRAME

DAMPER FRAME

WOODSTUD

MIN1.00

STUDMETAL

1.00MIN

Fig. 3

5. Recommended Preparation of Openings in Wood and Metal Stud Walls

• Frame wall openings as shown below. (see Fig. 4 & 4A).

• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening. (see Fig. 4 & 4A).

• Prepare opening between studs and sleeve assembly as shown below (see Fig. 3).

• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes.

Opening + 2 in. Min.

Wall/Floor Opening= Nominal Size + 7/8 in. Min.

1.00 in. Typ.Fasteners

ClampingScrew

Nut

RetainingPlate Assembly

Clamping ScrewFig. 2

Fig. 4A

Opening + 2 in. Min.

Wall/Floor Opening= Nominal Size + 7/8 in. Min.

1.00 in. Typ.Fasteners

ClampingScrew

Nut

RetainingPlate Assembly

Clamping Screw

Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.

Metal stud only

21

Page 22: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Damper Maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.

Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.• Actuator manufacturer recommendations.

Damper TroubleshootingThe following is a possible cause and correction list for common concerns with the dampers.

DFDR-XXX Blade Orientation

Normal30° Off Horizontal(Maximum)

30° Off Horizontal(Maximum)

Axle

Axle

Axle30°

30°

Symptom Possible Cause Corrective Action

Damper does not fully open and/or fully close

Frame is out of round causing blades to interfere with frame

Adjust frame such that it is round

Screws interfere with blade Locate screws and remove

Contaminants on damper Clean with a non-oil based solvent (see Damper Maintenance)

Link separated Heat Replace link

462721• DFDR, FDR Series Rev. 9, August 2013 Copyright 2013 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

22

Page 23: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Document Number 461337 OFSD-XXX, ODFD-XXX,

OFD-XXX, and OSSFD-XXX Series11/2 Hour Combination Fire Smoke or Curtain Fire Dampers

Out of Wall or Out of Floor Vertical or Horizontal Mount

Installation, Operation, and Maintenance Instructions

OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX series dampers are intended for installation in accordance with combination fire smoke dampers requirements established by: NFPA National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B, 101, & 105 IBC International Building Codes New York City (MEA listing # 260-91-M) California State Fire Marshal Listing #3225-0981:103 & 3230-0981:104

“UL Classified (see complete marking on product)” “UL Classified to Canadian safety standards (see complete marking on product)” UL Standard 555 & 555S (Classification R13317)

Receiving and HandlingUpon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.

Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).

WarrantyGreenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.

Safety Warning:Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.

Electrical GuidelinesAll wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.

Due to continuing research, Greenheck reserves the right to change specifications without notice.

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.

Safety Caution!Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.

®

23

Page 24: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Pre-Installation Guidelines

The basic intent of a proper installation is to secure the fire or fire smoke damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.

1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place or has not activated. Never install a fire damper without the proper UL approved RRL in place. (RRL is standard control option. These electric links have a button for resetting.) If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary.

2) Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators.

3) Damper has label on outside of sleeve indicating a ‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing.

4) Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number.

5) Damper must be installed into duct or opening square and free of twist or other misalignment. Damper

must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design.

6) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to:

a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray

7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design.

8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.

9) ACCESS: Suitable access (such that RRL’s and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).

10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.

Table of ContentsPre-Installation Guidelines ................................................................................................................................ 24 Installation .....................................................................................................................................................24-34 • Clearances Requirements .............................................................................................................25-30 • Duct to Sleeve Connections ...................................... .........................................................................31 • Securing the Damper/Sleeve Assembly to Wall and Floor Openings ................... ......................31-32 • Actuator Connections ................................... ......................................................................................32 • Recommended Preparation of Openings in Wood and Metal Stud Walls ...................................32-33 • Breakaway Connections ...................................... .........................................................................33-34Maintenance ........................................................................................................................................................34Troubleshooting ...................................................................................................................................................34

These instructions apply to 11/2 hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry, block, wood or metal stud walls, or concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A (Installation of Air Conditioning and Ventilating Systems) and UL listing R13317.

Installation - Failure to follow these instructions will void all warranties.

24

Page 25: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE OFSD-XXX

Figure 1 shows two approved installations for combination fire smoke dampers: 1) “Through the grille access” and 2) installation in continuing duct. To provide “through the grille” access to the damper actuator, the damper is located toward the back of the sleeve and the actuator is installed between the damper and grille. Actuator and damper can be accessed and serviced by removing the grille. To provide access to the damper actuator for continuing ductwork, refer to the requirements of NFPA 90A.

Steel stud

Flange

Grille (Supplied by others)

Factory Supplied Thermal Blanket

Factory Supplied Thermal Blanket

7 1/2 in. Max.

7 1/2 in. Max.

Damper Damper

#10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly.

Masonry floor

“Duct Continues”Horizontal or Vertical Mount

Wooden Stud Construction

Gypsum Wallboard

Stud or Runner

Retaining Angle (Refer to section 4)

(Duct Terminates)

In wood stud construction, gypsum wallboard must coverall wood stud surfaces.

Grille (Supplied by others)

Factory Supplied Thermal Blanket

Fire damper or combination fire smoke damper

6 1/2 in. Max.

#10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and maximum of 2 in. from corners (minimum of 2 screws per side). Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly.

Figure 1: Installation configurations for ‘Out of Wall’ combination fire smoke dampers.

“Duct Terminates” Wood Stud“Duct Terminates” Metal Stud

Steel stud

Flange

Grille (Supplied by others)

Factory Supplied Thermal Blanket

Factory Supplied Thermal Blanket

7 1/2 in. Max.

7 1/2 in. Max.

Damper Damper

#10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly.

Masonry floor

Note: Both installations for vertical mount.

ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure 2 shows installations that are also approved for curtain fire dampers. For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A.

2. CLEARANCE REQUIREMENTS There is no minimum clearance requirement between

the wall/floor opening and the sleeve exterior (with thermal blanket attached). However, to facilitate installation, clearances between the wall/floor opening and the damper sleeve are recommended. although there is no maximum allowable clearance, the minimum overlap requirements between the wall/floor and the flange/retaining angle must be met. On grill mount installations the flange must overlap the wall/floor by 1/2 in. (13mm). On continuous duct installations, the retaining angles must overlap the wall/floor by 1 in. (25mm). Because no clearances are required between the wall/floor opening and the sleeve, dampers may not be installed in the plane of the wall using this installation method.

25

Page 26: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Figure 2

Steel Stud

Flange

FlangeFlange

Factory SuppliedThermal Blanket

7 1/2 in. (191mm)maximum

Concrete or Masonry

Wall

Wood Stud

Damper

Type A- Vertical Mount, Duct Terminates Flange Method

Type A- Vertical Mount, Duct Terminates Single Angle Method

Type A - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method

Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method

Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method

Flange

7 1/2 in. (191mm)max.Factory Supplied

Thermal Blanket

Masonry or Concrete Floor

Damper

7 1/2 in. (191mm)

max.

Factory Supplied Thermal Blanket

Retaining Angle

Alternate Retaining

AngleLocation

Concrete or Masonry Wall

Wood Stud

Steel StudDamper

7 1/2 in. (191mm)max.

Retaining Angle

Factory SuppliedThermal Blanket

Concrete or Masonry

Floor

Damper

Retaining Angle

Concrete or Masonry

Floor

Damper

7 1/2 in. (191mm)max.

Factory SuppliedThermal Blanket

26

Page 27: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Figure 2 cont...

Type A- Vertical Mount, Thru Duct with Two Retaining Angles

Type A- Vertical Mount, Thru Duct with Single Retaining Angle

Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles

Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle

Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles

Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle

RetainingAngle

RetainingAngle

7 1/2 in. (191mm)max.

Factory SuppliedThermal Blanket

Damper

Masonry or Concrete Wall

MetalStud

WoodStud

Masonry or Concrete Floor

7 1/2 in. (191mm)max.

RetainingAngle

Factory SuppliedThermal Blanket

Damper

RetainingAngle

7 1/2 in. (191mm)max.

RetainingAngle

RetainingAngle

Factory SuppliedThermal Blanket

Masonry or Concrete

Floor

Damper

Concrete or Masonry Wall

Wood Stud

7 1/2 in. (191mm)maximum

Factory SuppliedThermal Blanket

Retaining Angle

Alternate Retaining Angle Location

Damper

7 1/2 in. (191mm)maximum

Factory SuppliedThermal Blanket

Retaining Angle

Concrete or Masonry

Floor

Damper

7 1/2 in. (191mm)maximumFactory Supplied

Thermal Blanket

Retaining Angle

Concrete or Masonry Floor

27

Page 28: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Figure 2 cont....

Type B2- Vertical Mount, Duct Terminates Flange Method

Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method

Factory Supplied Thermal Blanket

7 1/2 in. (191mm)maximumDamper

Wood Stud

Masonry or Concrete

Flange

SteelStud

7 1/2 in. (191mm)maximum

Factory SuppliedThermal Blanket

Flange

Masonry or Concrete

Damper

Type B2- Vertical Mount, Thru Duct with Two Retaining Angles

Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles

Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles

Wood Stud

Masonry orConcrete

7 1/2 in.(191mm)Maximum

Retaining Angle

Retaining Angle

Damper

Factory SuppliedThermal Blanket

MetalStud

Damper

Masonry or Concrete

RetainingAngle

RetainingAngle

Factory SuppliedThermal Blanket

7 1/2 in. (191mm)maximum

7 1/2 in. (191mm)maximum

RetainingAngle

RetainingAngle

Damper

Masonry orConcrete

Factory SuppliedThermal Blanket

28

Page 29: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Figure 2 cont....

Type B2- Vertical Mount, Thru Duct with Single Retaining Angle

Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle

Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle

7 1/2 in. (191mm)maximum

Factory SuppliedThermal Blanket

Metal Stud

Damper

RetainingAngle

Alternate RetainingAngle Location

Concrete or Masonry

WoodStud

RetainingAngle

Factory SuppliedThermal Blanket

Damper

Concrete or Masonry

7 1/2 in. (191mm) maximum

Factory SuppliedThermal Blanket

Retaining Angle

Concrete orMasonry

7 1/2 in. (191mm)maximum

Damper

Type B2- Vertical Mount, Duct Terminates Single Angle Method

Type B2 - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method

Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method

7 1/2 in. (191mm)maximum

Retaining Angle

Alternate RetainingAngle Location

Concrete or Masonry

Factory SuppliedThermal Blanket

Damper

7 1/2 in. (191mm)maximum

Retaining Angle

Factory SuppliedThermal Blanket

Concrete or Masonry

Damper

7 1/2 in. (191mm)maximum

Factory SuppliedThermal Blanket

Damper

Concrete or Masonry

RetainingAngle

29

Page 30: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Figure 2 cont....

Type C2- Vertical Mount, Thru Duct with Two Retaining Angles

Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles

Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles

7 1/2 in. (191mm)maximum

Factory SuppliedThermal Blanket Retaining

Angle

RetainingAngle

Metal Stud

Wood Stud

Concrete or Masonry

Factory SuppliedThermal Blanket

RetainingAngle

RetainingAngle

Concrete or Masonry

7 1/2 in. (191mm)maximum

Damper

RetainingAngle

RetainingAngle

Factory SuppliedThermal Blanket

7 1/2 in. (191mm)maximum

Concrete or Masonry

Damper

Type C2- Vertical Mount, Duct Terminates Flange Method

Type C2 - Horizontal Mount Above Floor/Wall, Duct Terminates Flange Method

Type C2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method

7 1/2 in. (191mm)maximum

Factory SuppliedThermal Blanket

Flange

MetalStud

Concrete orMasonry

Wood Stud

Damper

Flange

Factory SuppliedThermal Blanket

Damper

7 1/2 in. (191mm)maximum

Concrete or Masonry

Flange

Factory SuppliedThermal Blanket

7 1/2 in. (191mm)maximum

Damper

Concrete or Masonry

30

Page 31: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Figure 2 cont....

Type C2- Vertical Mount, Thru Duct with Single Retaining Angle

Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle

Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle

7 1/2 in. (191mm)maximum

Factory Supplied Thermal Blanket

Wood Stud

Metal Stud

Alternate RetainingAngle Location

Concrete or Masonry

Factory SuppliedThermal Blanket

Retaining Angle 7 1/2 in. (191mm)

maximum

Damper

Concrete or Masonry

RetainingAngle

Factory SuppliedThermal Blanket

Damper

7 1/2 in. (191mm)maximum

Concrete or Masonry

3. DUCT TO SLEEVE CONNECTIONS Dampers are supplied with actuators (on applicable

models) and sleeves from the factory and can be installed without the need for additional field installed sleeves.

Sleeve gauges of 20-14 (.9mm - 2mm) are to be used. UL Standard 555 requires all ducts to terminate at fire damper sleeves. Sleeve thickness must not be less than the gauge of the connecting duct.

Duct to sleeve breakaway connections must be of the type described on page 33. Factory furnished round duct collars on type R and CR dampers are also considered to be breakaway connections and may be used.

Thermal Blanket(installed around entireoutside surface of sleeve)

Wall

Flange

Figure 3: Sleeved damper with Thermal Blanket (duct termination).

4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS.

Damper/sleeve assemblies must be installed in wall openings using flanges and sheet metal screws as illustrated and described below.

• Flange on front (grille end) of sleeve must be a minimum of 16 gauge (1.5mm) steel and have a 5⁄8 in. (16mm) minimum flange leg (refer to Figure 3). Using #10 (19mm) sheet metal screws, screw from inside of sleeve through the rear portion of the studs (as shown in Figure 1). Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). No retaining angles are required on the side of wall opposite from the grille.

• Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm)(see Figure 4).

31

Page 32: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Retaining Angle

Thermal Blanket(installed aroundentire outsidesurface of sleeve)

2 in. Max.6 in. Max.

6 in. Max.2 in. Max.

Wall

Figure 4: Sleeved damper with Thermal Blanket (duct continuation).

Note: Thermal blanket is riveted to the damper sleeve and the seam is taped with acrylic adhesive tape, FSK facing tape 152 5CWnt, manufactured by Venture Tape Company.

12 in.

24 in. o.c.Maximum

Floor Runner

Ceiling Runner24 in. o.c.Maximum

(metal studs)

24 in. o.c.Maximum

(metal studs)

16 in. o.c.Maximum

(wood studs)

16 in. o.c.Maximum

(wood studs)

2 in. (51mm)

2 in. (51mm)

2 Panhead Screws

Figure 5

5. ACTUATOR CONNECTIONS Electrical and/or pneumatic connections to damper

actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see Electrical Guidelines).

6 Recommended Preparation of Openings in Wood and Metal Stud Walls

• Frame wall openings as shown (see Figure 5 & 5A)

• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see Figure 5 & 5A).

• Prepare opening between studs and sleeve assembly as shown (Figure 6 & 7).

• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes.

4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS continued....

• Retaining angles must be attached to the sleeve using one or more of the following methods of attachment: • Tack or spot welds • #10 (19mm) sheet metal screws • 1⁄4 in. (6mm) bolts and nuts • 3⁄16 in. (4.7mm) steel pop rivets

Attachments must be spaced a minimum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners.

Caution! Do not tear the thermal blanket during installation.

Dampers are tested for correct operation and are square and straight before shipment from the factory. Dampers must be installed square and straight and must not be twisted or racked. Failure to install the damper square and straight may prevent the damper blades from operating open and closed.

Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.

Metal stud onlyFigure 5A32

Page 33: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Breakaway Connections

Traditional Breakaway Style Transverse JointsTransverse joints illustrated at right have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections.

• The breakaway connections shown (Figure 8) can be applied with maximum of two #10 (19mm) sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket.

• Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm) See Figure 7.

Round and Oval Duct Breakaway ConnectionsRound or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows:

• Ducts to 22 in. (558mm) wide (or dia.) and smaller shall have three screws.

• Ducts larger than 22 in. (558mm) wide (or dia.) up to and including 36 in. (914mm) wide (or dia.) shall have five screws.

NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.

Manufactured Flanged System Breakaway ConnectionsFlanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated (Figure 9).

Drive Slip Joint

Figure 7

Plain “S” Slip Hemmed “S” Slip Double “S” Slip

Inside Slip Joint Standing “S” Standing “S” (Alt.)

Standing “S” (Alt.) Standing “S” Standing “S” (Bar Reinforced) (Angle Reinforced)

Figure 8

Fire Damper Sleeve

Neoprene gasketbetween all angles

Flanged system angles

(Attach permanufacturer'sinstructions)

Duct

Do not bolt corners

6 in. long 1/16 in. max.thickness plastic cleats;12 in. c-c (min. 1 per side)

Figure 9

Proprietary Flange System Breakaway Connections (TDC by Lockformer, TDF by Engle)

TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF addendum to the SMACNA Duct Construction Standards except the corners may not be bolted. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure 10. 3/8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces (see Figure 11).

DuctSleeve

6 in.

Std. ClipLength

CLDuct

60 in. Duct4 Req’d.

48 in. Duct3 Req’d.

36 in. Duct3 Req’d.

24 in. Duct2 Req’d.

18 in. Duct &Smaller1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in. 6 in.

9 in.

7 in.7 in.

5 in. 5 in.

5 in.5 in.

Metal Stud Construction

Wooden Stud Construction

In wood stud construction,gypsum wallboard must coverall wood stud surfaces.

Gypsum Wallboard

Stud or Runner

RetainingAngle

1 in. Min.

DamperSleeve

In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.

Gypsum Wallboard

Stud or Runner

RetainingAngle

1 in. Min.

DamperSleeve

Figure 7

Metal Stud Construction

Wooden Stud Construction

In wood stud construction,gypsum wallboard must coverall wood stud surfaces.

Gypsum Wallboard

Stud or Runner

RetainingAngle

1 in. Min.

DamperSleeve

In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.

Gypsum Wallboard

Stud or Runner

RetainingAngle

1 in. Min.

DamperSleeve

Figure 6

33

Page 34: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Damper Troubleshooting

The following is a possible cause and correction list for common concerns with the dampers.

Symptom Possible Cause Corrective Action

Damper does not fully open and/or close

Frame is 'racked' causing blades to bind on jamb seals

Adjust frame such that it is square and plumb

Actuator linkage loose Close damper, disconnect power, adjust and tighten linkage

Defective motor Replace

Screws in damper linkage Damper installed too far into wall. Move out to line as designated on damper label

Contaminants on damper Clean with a non-oil based solvent (see Damper Maintenance)

RRL or TOR sensor tripped

Heat Push reset button located on backside of RRL or TOR

Damper does not operate

No power supplied to the actuator Add power supply

Damper MaintenanceDampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.

Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:

• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.

• Actuator manufacturer recommendations.

Duct EndFlange

Corner Piece

3/8 in. bolt (optional)

Figure 11

DuctSleeve

6 in.

Std. ClipLength

CLDuct

60 in. Duct4 Req’d.

48 in. Duct3 Req’d.

36 in. Duct3 Req’d.

24 in. Duct2 Req’d.

18 in. Duct &Smaller1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in. 6 in.

9 in.

7 in.7 in.

5 in. 5 in.

5 in.5 in.

Figure 10: Detail of proprietary flanged system breakaway connections.

461337• ODFD OFD Rev. 14, August 2013 Copyright 2013 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

34

Page 35: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Document number 474015 Single Side Retaining Angle

Refer to:‘Installation Instructions for FD, DFD, SSFD, & KFD Models’ (Part #452763) or‘Installation Instructions for FSD-XXX, DFD-XXX, SSFSD-XXX & CFSD-XXX Series Fire & Combination Fire Smoke Dampers’ (Part #461336)or‘Installation Instructions for FD & DFD 150X Series Curtain Fire Dampers’ (Part #453946) for additional details.

FD & DFD Series11/2 Hour Fire Dampers andFSD Series11/2 Hour Combination Fire Smoke Dampers

“UL CLASSIFIED (see complete marking on product)”“UL CLASSIFIED to Canadian safety standards (see complete marking on product)” Standards UL 555 & 555SClassifications Filed at UL under Listing #R13317

Single side retaining angleThese instructions apply to 11/2 hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry or block walls, metal stud walls, wood stud walls or concrete floors. Specific requirement in these instructions are mandatory. These instructions meet the requirements of NFPA 90A (Standard for the Installation of Air Conditioning and Ventilating Systems).

Vertical mount dampers up to a maximum size of 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), or 40 in. W x 100 in. H (1016mm x 2540mm) or horizontal mount dampers up to a maximum size of 144 in. W x 96 in. H (3658mm x 2438mm) may be installed as illustrated below. Larger damper assemblies require retaining angles on both sides of the partition.

Note: Model specific size limits can be found in the base installation instruction documents noted above.

1. Clearance Requirements

On vertical mount single side angle installations there are no minimum clearance requirements between the wall opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the damper sleeve are recommended.

On horizontal mount single side angle installations a minimum clearance is required between the outside of the damper sleeve and the floor opening of 1/8 in. per foot (3mm per .3m) of damper width and 1/8 in. per foot (3mm per .3m) height with a minimum clearance of 1/4 in. (6mm). The maximum overall clearance is 1 1/2 in. (38mm),

2. Securing the Damper/Sleeve Assembly to Wall/Floor OpeningRetaining angles must be attached to both the sleeve and the partition (see figures 1-8).

• Retaining angles for dampers with a width and height of 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for

Installation Instructions Supplement

dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 ga. (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 1 1/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by at least 1 in. (25mm).

For metal stud partitions only, the single-side mounting angle may be directly attached to the metal stud prior to the installation of the drywall.

• Retaining angles must be attached to the sleeve using one of the methods shown below:

• tack or spot welds • #10 sheet metal screws • 1/4 in. (6mm) nuts and bolts • Retaining angles must be attached to the

partition using one of the methods shown below:

• Drywall screws of a length such that the screw engages the steel stud/track by 1/2 in. (13mm) (steel framing).

®

35

Page 36: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

1/2 in. UL ClassifiedGypsum Wallboard (seeUL Rated Wall Designfor Additional Details)

2 1/2 in. Min.Stud or Runner

DamperSleeve

Angle Fastener(see Section 2)

1/2 in. UL ClassifiedGypsum Wallboard (seeUL Rated Wall Designfor Additional Details)

DamperSleeve

Angle Fastener(see Section 2)

2 1/2 in. Min.Metal Studor Runner

Figure 1: 1 Hour Wall Rating

Figure 3: 1 Hour Wall Rating

Damper Sleeve

Angle Fastener(See Section 2)

2 1/2 in. min.Stud or Runner

Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details)

Damper Sleeve

Angle Fastener(See Section 2)

2 1/2 in. min.Metal Studor Runner

Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details)

Figure 2: 2 Hour Wall Rating

Figure 4: 2 Hour Wall Rating

1/2 in. UL ClassifiedGypsum Wallboard (seeUL Rated Wall Designfor Additional Details)

2 1/2 in. Min.Stud or Runner

DamperSleeve

Angle Fastener(see Section 2)

Figure 6: 2 Hour Wall Rating

1/2 in. UL ClassifiedGypsum Wallboard (seeUL Rated Wall Designfor Additional Details)

2 1/2 in. Min.Stud or Runner

DamperSleeve

Angle Fastener(see Section 2)

Figure 5: 1 Hour Wall Rating

• Drywall screws of a length such that the screw engages the wood stud by 13/4 in. (44mm) (wood framing). • Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm). • A minimum of two connections per side are

required. Additional connections must be

2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont.......

made at a maximum of 12 in. (305mm) O.C. (on center) maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in. (152mm) O.C. (on center) for openings 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), and 40 in. W x 100 in. H (1016mm x 2540mm) or less.

36

Page 37: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Masonry orConcrete Floor

DamperSleeve

Angle Fastener(see Section 2)

Top Side

Figure 7: Masonry or Concrete Wall Figure 8: Concrete Floor

Copyright © 2013 Greenheck Corporation 474015 Single Side Retaining Angle Suppl Rev. 3 Jan 2013

Masonry orConcrete Wall

DamperSleeve

Angle Fastener(see Section 2)

2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont.......

Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm] maximum)

• Angle legs may be reversed and one leg inserted into the wall/floor opening. Retaining angles used in conjunction with grille installations must be a minimum of 20 gauge (1mm) steel and have a minimum of 5/8 in. x 1 in. (15mm x 25mm) 20 gauge (1mm) steel.

Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). See Figure 9 and Figure 10.

Note: Screws used to attach grille are allowed to penetrate reversed angle leg.

DamperSleeve

Angle Fastener(see Note 2)

Grille (suppliedby others)

#10 sheet metal screwsspaced 6 in. on centerand a maximum of 2 in.from the corners(minimum of 2 screws perside). Screw into studs soas to avoid spaceconflicts with the grille

1/2 in. UL ClassifiedGypsum Wallboard (seeUL Rated Wall Designfor Additional Details)

2 1/2 in. Min.Stud or Runner

Retaining Angle(See Section 2)

Figure 9: 1 Hour Wall Rating

DamperSleeve

Angle Fastener(see Note 2)

Grille (suppliedby others)

#10 sheet metal screwsspaced 6 in. on centerand a maximum of 2 in.from the corners(minimum of 2 screws perside). Screw into studs soas to avoid spaceconflicts with the grille

1/2 in. UL ClassifiedGypsum Wallboard (seeUL Rated Wall Designfor Additional Details)

2 1/2 in. Min.Stud or Runner Two layers of

Retaining Angle(See Section 2)

Figure 10: 2 Hour Wall Rating

Note: For horizontal installations, retaining angles must be mounted on top side of partition.

37

Page 38: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

DATE NOTES

38

Page 39: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

DATE NOTES

39

Page 40: INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN ... - · PDF fileINSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s)

Copyright ©2013 Greenheck Fan Corporation826251 Curtain Packet

August 2013