FEATURES Will work in conjunction with your current N2 system controls and devices Supports up to 256 N2 device connections Complete template library of all N2 devices N2 Device Discovery tool for fast implementation Built-in N2 and BACnet network diagnostic tools Each N2 device appears as an individual BACnet/ IP device Cost Effective Legacy Migration tool Small Industrial Form Factor Includes PC Based Configuration Tools S4O-BN2 Metasys ® N2 to BACnet/IP Connect Your Legacy N2 Systems to BACnet/IP The S4 Open router moves data between up to 256 N2 devices and a BACnet/IP system. The router is flexible enough to monitor data transparently along side your existing N2 master or it can be used to replace your legacy N2 controls with a BACnet/IP control system. Discovery Tools and Device Templates Make integration a Breeze! The S4 Open Router comes with a N2 device discovery tool and a complete list of predefined N2 device profiles. These templates along with a N2 auto detect feature makes integration of an entire N2 network into a project that takes a few hours, not a few days. Legacy Migration at a Pace You Define Let’s face it N2 has been put out to pasture. If you can still find replacement N2 components you have inevitably noticed the prices soaring as a few suppliers capitalize on a legacy monopoly. The beauty of the S4 Open router is that it is designed to help you transition to native BACnet devices at your pace. Eventually you’ll want all your devices to be BACnet enabled devices but having the power to control that transition can save an immense amount time, money and trouble. There is no need to retool an entire building in one disruptive and expensive sweep. The S4 Open router allows you to retool and upgrade to BACnet device replacements on a node by node basis. You can upgrade by department, building, device age or device importance. The point is the S4 Open Router lets you manage the transition and upgrade on your terms. A Gateway, A Philosophy, My Company “I remember my days as an engineer in the factory. I remember the pressure to keep the line running and product flowing. The endless headaches and stress that came every time I had to install a new gateway. If I never saw another hundred page manual or had to deal with fifty features I didn’t need it would be too soon. I knew there had to be a better way. That’s how Real Time Automation was formed. I found the best engineers and gave them one task. I asked them to make solutions so easy to use the hardest part would be opening the box. It has been twenty years now and we still strive for that same goal everyday.” John Rinaldi Real Time Automation, Inc. - www.rtaautomation.com - 1-800-249-1612 Real Time Automation Gateways In partnership with

In partnership with S4O-BN2 · Small Industrial Form Factor Includes PC Based Configuration Tools S4O-BN2 Metasys

  • Upload
    dangnhu

  • View
    215

  • Download
    2

Embed Size (px)

Citation preview

FEATURES

Will work in conjunction

with your current N2 system controls and devices

Supports up to 256 N2

device connections

Complete template

library of all N2 devices

N2 Device Discovery

tool for fast implementation

Built-in N2 and BACnet

network diagnostic tools

Each N2 device appears

as an individual BACnet/IP device

Cost Effective Legacy

Migration tool

Small Industrial Form

Factor

Includes PC Based

Configuration Tools

S4O-BN2

Metasys® N2 to BACnet/IP

Connect Your Legacy N2 Systems to BACnet/IP The S4 Open router moves data between up to 256 N2 devices and a BACnet/IP system. The router is flexible enough to monitor data transparently along side your existing N2 master or it can be used to replace your legacy N2 controls with a BACnet/IP control system.

Discovery Tools and Device Templates Make integration a Breeze! The S4 Open Router comes with a N2 device discovery tool and a complete list of predefined N2 device profiles. These templates along with a N2 auto detect feature makes integration of an entire N2 network into a project that takes a few hours, not a few days.

Legacy Migration at a Pace You Define Let’s face it N2 has been put out to pasture. If you can still find replacement N2 components you have inevitably noticed the prices soaring as a few suppliers capitalize on a legacy monopoly. The beauty of the S4 Open router is that it is designed to help you transition to native BACnet devices at your pace.

Eventually you’ll want all your devices to be BACnet enabled devices but having the power to control that transition can save an immense amount time, money and trouble. There is no need to retool an entire building in one disruptive and expensive sweep. The S4 Open router allows you to retool and upgrade to BACnet device replacements on a node by node basis. You can upgrade by department, building, device age or device importance. The point is the S4 Open Router lets you manage the transition and upgrade on your terms.

A Gateway, A Philosophy, My Company

“I remember my days as an engineer in the factory. I remember the pressure to keep the line running and product

flowing. The endless headaches and stress that came every time I had to install a new gateway. If I never saw

another hundred page manual or had to deal with fifty features I didn’t need it would be too soon. I knew there had

to be a better way. That’s how Real Time Automation was formed. I found the best engineers and gave them one

task. I asked them to make solutions so easy to use the hardest part would be opening the box. It has been twenty

years now and we still strive for that same goal everyday.”

John Rinaldi

Real Time Automation, Inc. - www.rtaautomation.com - 1-800-249-1612

Real Time Automation Gateways

In partnership with

www.rtaautomation.com

CATALOG # DESCRIPTION

S40-BN2-16 S4 Open: BACnet-N2 Router - 16 Devices

S40-BN2-32 S4 Open: BACnet-N2 Router - 32 Devices

S40-BN2-64 S4 Open: BACnet-N2 Router - 64 Devices

S40-BN2-128 S4 Open: BACnet-N2 Router - 128 Devices

S40-BN2-256 S4 Open: BACnet-N2 Router - 256 Devices

BACnet/IP FEATURES

BACnet/IP Operation Modes BACnet/IP Router, Clause 6, BBMD

Supported Object Types Device, Binary I/O & V, Analog I/O & V, Multi State I/O & V, Notification Class

Supported Service Codes Read & Read Multiple-B, Write & Write Multiple-B, COV & COV unsolicited-B, COVP, Views, Device Dynamic Binding-B, Dynamic Object Binding-B. *For complete list of supported service codes reference PICS

INCLUDED WITH S4 OPEN ROUTER

International DIN rail mounted 24VDC power supply N2 Device adapters

2 Year limited hardware warranty Adapter Cable for N30/NCM integration

1 Year Software Assurance Support subscription Full N2 Device template library

1 Year firmware upgrade subscription CD with Manual, utilities and trial software

ELECTRICAL/ENVIRONMENTAL

DC Input Voltage 10-30VDC, 1A @ 24VDC

Operating Temperature -10 C to 55 C

Certification RoHS-Compliant, UL, CE

ENCLOSURE / HARDWARE

Size 6.5”x4.2”x1.4”

Weight 7.6 oz

Enclosure Type Aluminum

Mounting Din rail or panel mount (included)

S4 OPEN ROUTER FEATURES & FUNCTIONS

Security Password protected UI

N2 Network Tool Diagnostic data that allows you to trouble shoot issues on your serial network and N2 nodes

Software Assurance Program

Year one included at no cost. Subsequent years can be purchased for 20% of routers purchase price.

S4 Open

Management

Console

Appliance discovery, setup, commissioning,

maintenance, and management all performed from

one convenient interface.

Implement BACnet Priority Array on N2

The router has the ability to force the Metasys supervi-sory controller to participate in the BACnet Priority Array

N2 FEATURES & PERFORMANCE

N2 Network Baud Rate 9600 half-duplex

Maximum N2 Devices Supported Up to 256 devices

Version Support N2 Open, VMA & System 91

Specifications

Real Time Automation, Inc. - www.rtaautomation.com - 1-800-249-1612

DIMENSIONS