1 IEEE/NFPA Arc Flash Phenomena Collaborative Research Project Wei-Jen Lee, Ph.D., P.E. Tammy Gammon, Ph.D. Project Management Team Ben Johnson Sue Vogel Steering Committee Chair January 27, 2011

IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

1

IEEE/NFPA Arc Flash Phenomena Collaborative

Research ProjectWei-Jen Lee, Ph.D., P.E. Tammy Gammon, Ph.D.

Project Management Team

Ben Johnson Sue VogelSteering Committee Chair

January 27, 2011

Page 2: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Introduction

On average, approximately 5 to 10 arc flash incidents or events occur on the job every day in the United States.

Though electrical incidents represent a relatively small percentage of all work-related incidents, they are disproportionately fatal and, in the case of burns, may result in extended hospitalization and rehabilitation.

2

Page 3: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Introduction

IEEE 1584 and NFPA 70E have been developed to protect the safety of workers.

Several areas of arc flash phenomena need further research and testing validation.

IEEE and NFPA formed the Arc Flash Collaborative Research Project to support research and additional testing to increase the understanding of issues related to arc flash phenomena.

3

Page 4: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Introduction

The identified areas include but are not limited to: – Heat and Thermal Effects– Blast Pressure– Sound– Luminance (Light) measurement

This report highlights the activities of this collaborative research project.

4

Page 5: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Selection of the Testing Labs

A total of four high power test/laboratory facilities have been “pre-qualified” through both written response and site visits. (Three labs are independent test laboratories and the one lab belongs to a corporate sponsor.)

These test laboratories are third-party certified for quality assurance.

All labs have qualified personnel, experience with arc flash testing, and adequate facilities.

5

Page 6: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Selection of the Testing Labs

The initial phase of pre-qualification was concluded in August 2008. In February 2010, another independent test laboratory, S&C, was identified and pre-qualified through a similar process.

These test laboratories were invited to submit technical and cost proposals for RFQs issued on behalf of the arc flash collaborative research project.

6

Page 7: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Phase I Testing

The first round of “scouting” tests referred to as “Phase 1 Testing” was designed to check the following among test labs using identical test protocols and arrangement:

– Instrumentation functionality and sensitivity– Overall measurement accuracy– Repeatability of experiments – Consistency of test results

7

Page 8: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Phase I Testing

The test parameters are:– System Voltage: 480V, 3-phase and 1-phase, 60-Hz,

Solidly Grounded and Ungrounded System. – RMS Bolted Fault Current: 5 and 20kA.– Electrode: 19mm (3/4”) cylindrical hard drawn Copper.– Electrode Orientations: Vertical and Horizontal.– Electrode Gap Widths: 10mm and 25mm (approx. 1 in)– Arc Duration (60Hz Base): 6 cycles (0.1 sec) and 12

cycles (0.2sec).– Configurations: Open Air, Cubic Box (3-Ph), Faraday

cage (1-Ph), Electrodes Terminated in Barrier (1 lab).

8

Page 9: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Phase I Testing

Test performed (Two tests per configuration)

9

3P-VCB-12-5-10-UB 3P-VCB-6-5-10-UB 3P-VOA-12-5-10

3P-VCB-12-5-10-B 3P-VCB-6-5-10-B 3P-VOA-12-5-25

3P-VCB-12-5-25-UB 3P-VCB-6-5-25-UB 3P-VOA-12-20-10

3P-VCB-12-5-25-B 3P-VCB-6-5-25-B 3P-VOA-12-20-25

3P-VCB-12-20-10-UB 3P-VCB-6-20-10-UB

3P-VCB-12-20-10-B 3P-VCB-6-20-10-B

3P-VCB-12-20-25-UB 3P-VCB-6-20-25-UB

3P-VCB-12-20-25-B 3P-VCB-6-20-25-B

3P-HCB-12-20-10-UB 3P-HOA-12-5-10 1P-VFC-12-5-10

3P-HCB-12-20-10-B 3P-HOA-12-5-25 1P-VFC-12-5-25

3P-HCB-12-20-25-UB 3P-HOA-12-20-10 1P-VFC-6-20-10

3P-HCB-12-20-25-B 3P-HOA-12-20-25 1P-VFC-12-20-25

Page 10: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

480V Phase I Testing – 244 Tests

Number of Tests by type (~50% each: 6,12 cycle)

10

Bolted Fault:Gap width:

~5kA10mm

~5kA25mm

~20kA10mm

~20kA25mm

HOA 7 3 8 5HCB-B 4 5 8HCB-UB 7 14 13VOA 2 12 12VCB-B 9 4 16 18VCB-UB 12 5 20 18VCB-Barrier 9 8 8 9Faraday,1ph 2 2 2 2

Page 11: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Observations From Phase I Testing

Important Factors for the Test– Bolted fault current level.– Duration of the arc.– Voltage level.– Electrode Orientation/Configuration (VCB, VCB-

Barrier, HCB, VOA, HOA).– Gap width between electrodes.– Calorimeter arrangement and measurement locations.– Distance between electrode and back panel*.– Dimensions of the metal enclosure**.

11

Page 12: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Design of Phase II Testing

Cover installations between (208V) 480V and 13.8kV.

Compile/Analyze Phase I 480V testing results. Perform extensive tests on 600V, 2.4kV/4.16kV,

and 13.8kV. Perform select tests on 208V and 7.2kV.

12

Page 13: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Design of Phase II Testing

Based upon engineering practice, select appropriate sized metal enclosure for Phase II testing. Other dimensions will be checked later (selective testing).

Based upon engineering practice, select appropriate distance between electrode and back panel for Phase II testing. Other distances will be check later (selective testing).

13

Page 14: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Design of Phase II Testing

Measure IE at three different distances. Measure the sound levels at 3 meters and 5 meters

for ANSI S1.4 peak. Measure pressure at three different distances (Same

as IE measurement). Perform luminance (light) measurement at 3 meters

and 5 meters.

14

Page 15: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Design of Phase II Testing

Gaps between electrodes and over surface.– For medium voltage, the design is based upon the

requirement of BIL (Basic Impulse Level).– The breakdown voltage in the dry air is around 30

kV/inch.– Laboratory testing shows that the breakdown voltage is

around 15 kV/inch.

15

Page 16: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Design of Phase II Testing

Gaps between electrodes and over surface.– Design parameters for gap between electrodes and

electrodes to the back panel.

16

Voltage(kV)

BIL(kV)

Minimum Gap (inch)

Maximum Gap (inch)

Over Surface Phase-to-ground (inch)

0 – 0.125 0.5 0.750.126 – 0.250 0.75 1.00.251 – 0.600 1.0 2.0 4.0

2.4 60 1.5 4.5 4.04.16 (5) 60 1.5 4.5 4.0

7.2 75 2.5 4.5 4.0 13.8 95 3.0 6.0 7.0

Page 17: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Design of Phase II Testing

Other Parameters.

17

Voltage(kV)

Maximum Ibf(kA)

Distance to the Back Panel (inch)

Box Size (inch)

0 – 0.1250.126 – 0.2500.251 – 0.600 100 4 20x20x20

2.4 63 4 26x26x264.16 (5) 63 4 26x26x26

7.2 63 4 26x26x2613.8 63 7 36x36x36

Page 18: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Design of Phase II Testing

List of 4160V Testing (270 Tests).

18

Bolted Fault Current (KA)

Duration(cycles)

Gap(inch)

Distance to Back Panel (inch)

Measure Distance

(inch)

VCB VCB-Barr

HCB Measure Distance

(inch)

VOA HOA

20/40/63 6 1.5/3.0/4.5 4 24 1 1 1 18 1 120/40/63 12 1.5/3.0/4.5 4 24 1 1 1 18 1 120/40/63 6 1.5/3.0/4.5 4 33 1 1 1 27 1 120/40/63 12 1.5/3.0/4.5 4 33 1 1 1 27 1 120/40/63 6 1.5/3.0/4.5 4 42 1 1 1 36 1 120/40/63 12 1.5/3.0/4.5 4 42 1 1 1 36 1 1

Page 19: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Voltage and Current– Voltage and current are measured near the electrodes.– The sampling rate is between 10K and 20K samples per

second.– Arc power and energy are calculated from V·I samples.

19

Page 20: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Voltage and Current– Bonded or Un-bonded.

20

Neutral Current

-15000

-10000

-5000

0

5000

10000

1 113 225 337 449 561 673 785 897 1009 1121 1233

Sample (0.1ms/sample)

Cur

rent

(A)

VCB-6-17.2-10-G

VCB-6-17.2-10-UG

Page 21: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Voltage and Current– Arc Power, MW (480V Testing)

21

Ibf kA

3Ph, VCB

3Ph, HCB, HOA

3Ph, VOA

1Ph, VFC

3Ph ~Psc

Lower Bolted-Fault Currents Kinectrics 5.9 – 6.3 1.7 – 2.0 0.4 – 0.6 4.9 Ferraz 5.2 1.3 – 1.5 1.8 – 1.9 4.3 KEMA 5.0 – 5.1 2.0 1.8 – 1.9 0.4 – 0.5 4.2 Higher Bolted-Fault Currents Kinectrics 17.2 – 17.6 4.0 – 4.8 4.4 – 5.4 5.1 – 5.6 1.8 14.3 Ferraz 19.8 – 20.1 5.2 – 6.4 6.9 16.6 KEMA 20.6 – 21.7 3.6 – 6.9 4.8 – 7.3 4.9 – 6.7 2.6 17.1

Page 22: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Incident Energy– ASTM 1959 Slug Calorimeters.

22

Page 23: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Incident Energy– ASTM 1959 Slug Calorimeters.

23

Page 24: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Incident Energy– Gardon Gauge Calorimeters.

24

Page 25: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Incident Energy– Different size of thermocouples.

25

Page 26: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Transient Response of Heat Measurement

26

-0.10

0.10.20.30.40.50.60.70.80.9

1

-1 -0.5 0 0.5 1 1.5 2 2.5

Cal/c

m^2

Second

Response of Calorimeters

Calorimeter 1

Calorimeter 2

Calorimeter 3

Calorimeter 4

Calorimeter 5

Calorimeter 5

Response of Calorimeters

-15

-10

-5

0

5

10

15

-1 -0.5 0 0.5 1 1.5 2 2.5

Second

Cal/c

m^2

Calorimeter 1

Calorimeter 2

Calorimeter 3

Calorimeter 4

Calorimeter 5

Calorimeter 5

-4000

-2000

0

2000

4000

3 3.1 3.2 3.3 3.4

Deg

rees

Cel

cius

Time (seconds)

Aug '09 HCB-12-20-25-UB-2, Tarc ~ 206 ms Cal 1 -

Cal 2 -

Page 27: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Incident Energy– Cooper Barrier

Test.

27

0

2

4

6

8

5kA-10-4"

5kA-10-10"

5kA-25-4"

5kA-25-10"

20kA-10-4"

20kA-10-10"

20kA-25-4"

20kA-25-10"

Inci

dent

Ene

rgy,

cal

/cm

2

09/2009 Cooper, Middle & Bottom Calorimeters, 12-Cycle

Middle Rows - Blue SymbolsBottom Rows - Red, Orange

0

2

4

6

8

5kA-10-4"

5kA-10-10"

5kA-25-4"

5kA-25-10"

20kA-10-4"

20kA-10-10"

20kA-25-4"

20kA-25-10"

Inci

dent

Ene

rgy,

cal

/cm

2

Sept. 2009 Barrier Tests, Avg. Calorimeter Msmts., 12-Cycles

Top Middle Bottom

Page 28: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Pressure Measurement– Pressure Transducer (100” from arc flash)

28

-0.8-0.7-0.6-0.5-0.4-0.3-0.2-0.1

00.10.20.3

0 50 100 150 200 250

PSI

ms

Pressure

Pressure

Page 29: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Pressure Measurement– Consecutive frames of high speed video

Frame-by-frame of 1000 fps, video recording (VCB-12cyc-20kA-25mm)

Hot air moves around 3” to 4” between 2 consecutive frames

– Wind Speed = 170 ~ 227 miles/hr– Pressure = 74~132 psf = 0.5~0.9 psi*– Person facing incoming force will receive

110 ~ 200 lbs force at the initial blast (impact on 1ft. x 1.5 ft.).

– Due to the air temperature and its contents, the actual pressure may be different.

29

Page 30: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Pressure Measurement– Pendulum (VCB-12-20-25)

Preliminary analysis reveals that average pressure is around 0.6 to 0.8 psi.

30

Page 31: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Pressure Measurement– Pressure Transducer (Honeywell 19C030PG2K)

Preliminary analysis reveals that peak pressure may reach 0.93 psi (VCB-12-20-12.5-27). This is similar to the previous estimation.

Need more tests

31 -0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1

1.2

1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61

Arc flash starting point

Page 32: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Pressure Measurement– Pressure Transducer (Honeywell 19C030PG2K)

A testbed is built to check the output of the pressure sensor.

32

Page 33: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Sound Level Measurement– Different sound level measurement devices are used in

different tests.– The measurement complies with ANSI S1.4.– Since the whole event is less than 200ms, Weighted C

peak (50 μs) is recorded– Sound levels are affected by:

Size and shape of testing labs. The magnitude of short circuit current.

– Correlation between sound level and arc duration is small.33

Page 34: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Sound Level Measurement– According to OSHA, exposure to impulsive or impact

noise should not exceed 140 dB peak sound pressure level. At 115 dB, OSHA’s permissible noise exposure is 15 minutes or less daily. (OSHA Table G-16)

– Initial measurements indicate that hearing protection is recommended for protection against impulsive noise.

34

Page 35: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Sound Level Measurement– 4160V arc flash test results (2 meters and 3 meters from

the arc flash)

35

135

140

145

150

155

160

HCB

-20

HCB

-40

HCB

-63

HO

A-2

0H

OA

-40

HO

A-6

3VC

B-20

VCB-

40VC

B-63

VCB-

BA-2

0VC

B-BA

-40

VCB-

BA-6

3VO

A-2

0VO

A-4

0VO

A-6

3

Average Intensity of Sound

Mic 1 12 Cycle

Mic 2 12 Cycle

Mic 1 6 Cycle

Mic 2 6 Cycle

Page 36: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Luminance (Light) Measurement – SFH 5711 High Accuracy Ambient Light Sensor is used

for light level measurement.– This device is designed to match human eye sensitivity

(Vλ).

36

Page 37: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Luminance (Light) Measurement – Neutral density filters are used to attenuate the light

intensity.

37

Page 38: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Luminance (Light) Measurement – Response of the light sensor.

38

Light Intensity (VOA-63-12-1.5)

-0.1

0

0.1

0.2

0.3

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4

Time (sec)

Vo

lts

Series1

Page 39: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Data Measurement and Analysis

Luminance (Light) Measurement – Luminance level. (A bright summer day will have a midday ground

level illumination in the order of 100,000 lux)

39

Light Intensity

05

101520253035404550

VOA-20-12-1.5-36

VOA-20-6-1.5-27

VOA-20-12-1.5-27

VOA-40-6-1.5-36

VOA-40-12-1.5-36

VOA-40-6-1.5-27

VOA-40-12-1.5-27

VOA-63-6-1.5-36

VOA-63-12-1.5-36

VOA-63-6-1.5-27

VOA-63-12-1.5-27

Mill

ion

Lux

Page 40: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Video Recording and Data Acquisition System

Video Recording System – Some laboratories offer high speed video recording

system.– Video provides valuable information for the research team

to observe the arc flash activities.– Research team has also acquired Casio F1 high speed

video camera to observe other arc flash phenomena.

40

Page 41: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Recording and Data Acquisition System

Video Recording System– We are able to record the arc flash up to 1200FPS.

41

Page 42: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Recording and Data Acquisition System

Video Recording System– IR filter is used to observe the arc flash behind the smoke.

42

Page 43: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Recording and Data Acquisition System

Data Acquisition System– Some laboratories have data acquisition system for

voltage, current, slug calorimeters, light, and pressure measurement and data recording.

– In some case, the laboratory can only provide the recording equipment for voltage and current.

– Research team has designed and built data acquisition system for heat flux, pressure, and light measurements.

43

Page 44: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Recording and Data Acquisition System

Data Acquisition System– Current DAQ has the following set-up and capabilities:

Two Dewetron - DEWE 43V. 8 analog inputs per module. 204.8K samples/second simultaneous sampling. USB extender is used to extend USB signal transfer up to 300 feet

through Cat 5 cable.

44

Page 45: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Recording and Data Acquisition System

Data Acquisition System– Unfortunately, the system was damaged during January

2011 testing at Cooper Bussmann lab.– While trying to fix the system, research team is building

second DAQ system using cRio from National Instruments.

– The unit is IP addressable. It can communicate with host computer through internet or direct Cat 5 crossover cable.

45

Page 46: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Recording and Data Acquisition System

Data Acquisition System– Configuration of new DAQ system.

46Analog Devices7B-47-K

NI cRio: 16 Differential AI16 TTL Compatible DI/O

Slug calorimeters and Pressure sensors

Cat. 5Connection

Page 47: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Complication on Data Analysis

Arc Flash on Back of Box

47

Page 48: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Complication on Data Analysis

48

0.1675 sec

0.1717 sec

0.1783 sec

0.1858 sec

0.0 sec

0.00417 sec

0.00583 sec

0.2058 sec

0.2108 sec

0.2117 sec

Page 49: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Complication on Data Analysis

Other event: Arc Flash on Top of Box

49

Page 50: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Complication on Data Analysis

Arc flash happens at different location

50

Page 51: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Complication on Data Analysis

Equipment damage

51

Page 52: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Conclusion and Discussion

In addition to heat flux, research team is exploring other arc flash related hazards.

Research team adjusts/re-designs testing set-up continuously to obtain critical information for model verification and development.

The results of this collaborative project will provide information to improve electrical safety standards, predict the hazards associated with arc flash, and provide practical safeguards for employees in the workplace. 52

Page 53: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash

Conclusion and Discussion

The Arc Flash Project is one of the most important projects that has been carried out by IEEE and NFPA. The results will affect the safety of lives.

53

Page 54: IEEE/NFPA Arc Flash Phenomena Collaborative Research Project · Several areas of arc flash phenomena need further research and testing validation. IEEE and NFPA formed the Arc Flash