129
Confidential for further publication Condensing Furnace Distributor Technical Training 1

ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

Embed Size (px)

Citation preview

Page 1: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

1

Condensing FurnaceDistributor

Technical Training

Page 2: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

2

Model Nomenclature System

Page 3: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

3

Model Nomenclature System

Page 4: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

4

Agenda

Product Line OverviewNew FeaturesInstallationAdjustmentServicing

Page 5: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

5

Overview

• 95.5 AFUE • 4-way multipoise

– 100 & 120 size– 140 size limited to Upflow & Horizontal

• Aluminized steel primary and stainless steel secondary heat exchangers

• Direct Vent or Non-Direct Venting

Page 6: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

6

New Features

• Lower height, now 35”• Standard widths

– 21” for 100 and 120 sizes – 24 ½” for 140 sizes

• Through-the-top venting• Multiple venting options• Internal Condensate system

Page 7: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

7

New Features

• Slide out blowers• Ease of access for control board• Two outer doors• Easy door attachments

– No sharp edges– Quarter-turn knobs and latches

Page 8: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

8

New Features

• Redesigned primary heat exchanger– More compact– No eyelets

• Updated tube-and-fin secondary– Better efficiency– Eliminated U-bend – Easier to service with

slide-out rails

Page 9: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

9

New Technologies

• True installation flexibility– Venting flexibility

• Vent pipes can exit cabinet in three different directions

– Low-profile horizontal drain trap position• Easy to re-position the drain trap• Fewer tubes to connect• Drain trap and tubes removed from the blower

compartment

Page 10: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

10

Casing

Page 11: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

11

Casing

Page 12: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

12

Casing

Page 13: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Casing

Combustion Air Opening

Gas Entry

Horizontal Drain Trap Opening

Vent or Combustion Air Opening

Condensate Drain K.O.

J Box K.O.

Return Air Opening

35”

Combustion Air Opening

Gas Entry

Vent or Combustion Air Opening

Horizontal Drain Trap Opening

Condensate Drain K.O.

J Box K.O.

Return Air Opening

13

Page 14: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

14

Outer Door Assembly

• Two piece door design• ¼ turn door knob attachment• Doors are gasketed

– Eliminates door rattling and leakage

– Vestibule is sealed• Door does NOT change with

furnace orientation– Logo rotates for upflow and

downflow positions

Page 15: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

15

Outer Door Assembly

• Vestibule functions as the burner compartment– Combustion air piped directly to the vestibule– Multiple locations to connect combustion air pipe

• Sealed burner box is not required• Simplifies set-up

Page 16: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

16

Upflow Return Air Connections

Page 17: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

17

Downflow Return Air Connections

Page 18: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

18

Horizontal Return Air Connections

Page 19: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

19

Upflow Venting

Page 20: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

20

100,000 BTUH & 120,000 BTUH Downflow Venting

Page 21: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

21

Horizontal Left Venting

Page 22: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

22

Horizontal Right Venting

Page 23: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

23

• Direct Vent– Concentric Vent– Field-fabricated 2-pipe

• Ventilated Combustion Air– Vent to outdoors– Combustion air from attic or crawlspace

• Single Pipe– Uses indoor air for combustion

Terminations

Page 24: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

24

Ventilated Combustion Air Option

The combustion air pipe for the Ventilated Combustion Air Option cannot be terminated in attics or crawlspaces that use ventilation fans designed to operate during the heating season. If ventilation fans are present in these areas, the combustion air pipe must terminate outdoors as a Direct Vent / 2-Pipe system.

Page 25: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

25

Indoor Air For Combustion Option

• Use a (minimum) 12-inch piece of PVC– Maximum of 5 feet

• Tight radius elbow– Face away for better sound

control• Secure pipe to adapter

– Pilot drill 1/8” hole– Install sheet metal screw– Seal with silicone

12” (min)

Page 26: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

26

Alternate Indoor Air For Combustion Connection

12” (min)

12” (min)

Page 27: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

27

Supply Air Flanges

• Flanges shipped flat– If flanges are not bent, nuisance

limit trips could occur• Bend flanges UP for upflow or

horizontal coil installations• Remove or bend flanges DOWN

for downflow coil installations– No downflow for 140,000 input

• Supply opening match current coil opening sizes

Page 28: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

28

Supply Air Flanges

Page 29: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

29

Return Air Connections• Upflow

– Either Side– Bottom– Any combination of Sides and Bottom

• Downflow (100,000 BTUH & 120,000 BTUH)– Bottom only (“bottom” as referenced to furnace in upflow position)

• Horizontal – Bottom– Side (side facing down only)

• Airflow above 1800 cfm may require both side/bottom return or bottom only return

• Remove closure panel for bottom return air

Page 30: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

30

Return Air Connections

Page 31: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

31

Gas Piping• Gas pipe can enter

from either side• Remove K/O on either

side gas entry• Install grommet in

casing• Flex lines must

connect outside of the casing per the NFGC

Sediment trap required per NFGC

Page 32: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

32

Optional Right Side Gas Entry

• No special fittings for left side entry

• Valve inlet is ½” NPT• Install Street Ell, 2” nipple and

90º elbow together• Install Street Ell into gas valve• Remove K/O from casing• Install gas pipe grommet in

casing– (Required For Direct Vent)

• Install gas line into elbow• Tighten gas line

Use backup wrench on gas valve!

Page 33: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

33

J-Box Installation

• J-box bracket and cover shipped in loose parts bag

• J-box can be relocated to opposite side

• Other electrical knock-outs are available

Page 34: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

34

J-Box Installation

• Remove 7/8” knockout in casing

• Install J-box bracket• Attach ground wire to

green ground screw• Install cover after all

other connections are made

• Other electrical knock-outs are available

Page 35: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

35

Typical Disconnect At Furnace

Power Cord Installation in Furnace J-Box (Where permitted)

NOTE: Power cords must be able to handle the electrical requirements listed in Table 6. Refer to power cord manufacturer’s listings.1. Remove 7/8” K.O. in casing.2. Attach J box bracket to casing.3. Route listed power cord through 7/8--in. (22 mm) diameter hole in casing.4. Attach power cord to J--Box bracket with a strain relief bushing or a connector approved for the type of cord used.5. Attach field ground wire to green ground screw on J-Box bracket.6. Connect line voltage leads as shown in wiring diagram7. Install cover to J--Box. Do not pinch wires between cover and bracket.

Page 36: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

36

Upflow

Page 37: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

37

Downflow - Trap UnconvertedPSC Inducer Models

Page 38: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

38

Downflow - Trap ConvertedPSC Inducer Models

Route tube through

Switch Tube to PortOn Collector Box

To 15 ib-in

Page 39: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

39

Horizontal Left - Trap UnconvertedPSC Inducer Models

Page 40: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

40

Horizontal Left - Trap ConvertedPSC Inducer Models

Route Pressure Switch

Page 41: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

41

Horizontal Right - Trap UnconvertedPSC Inducer Models

Page 42: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

42

Horizontal Right - Trap ConvertedPSC Inducer Models

Page 43: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

43

Horizontal Trap Grommet

• Required accessory for Direct Vent applications (only)

• Maintains a sealed vestibule

Page 44: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

44

Repositioning Vent Elbow

• Loosen the Vent Elbow Clamp. • Remove the Vent Elbow. • Re-install in the desired position. • Torque clamp 15 lb-in.

Page 45: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

45

Condensate Trap and Drain Elbow

• Clear trap– Shown for clarity

• Production Trap– White, Opaque front/Clear back

Page 46: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

46

Condensate Trap

Expanded View Outlet Relief Port Inlets Front View Back View

Mounting Screw Hole

Page 47: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

47

Right Side Drain

• Production trap will be opaque front/clear back• Connect field supplied CPVC fittings to drain tube• Clamp may be located inside casing• Connect condensate drain to code approved drain or condensate

pump approved for furnace condensate

Page 48: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

48

Right Side Drain

Page 49: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

49

Left Side Drain• Cut the tube as shown• Install formed end of

grommet in the left side of the casing

• Connect the elbow to the short end of Z pipe

• Slide clamps on elbow and pipe

• Route Z pipe behind inducer• The inducer can be removed

if necessary to install the Z pipe

Page 50: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

50

Left Side Drain

Page 51: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

51

Left Side Drain

Page 52: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

52

Vent Sizing

• New tables based on Maximum Equivalent length– Starts with a maximum length– Deduct for type of fitting used– No restriction on number of elbows

• Diameters up to 4 inches on larger sizes• Expanded exposed vent pipe tables

– Winter design down to -40 deg. F (C) – ½ inch insulation added

• Closed cell Armaflex type

Page 53: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

53

Maximum Equivalent Length Table

Page 54: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

54

Deductions Table and Example

Page 55: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

55

Vent Table Notes

1. Use only the vent pipe sizes shown for each furnace. It is NOT necessary to choose the smallest diameter pipe possible for venting.

2. NA – Not allowed. Pressure switch will not close, or flame disturbance may result.

3. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.

4. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.

5. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.

6. The minimum pipe length is 5 ft. (2 M) linear feet (meters) for all applications.7. Use 3–in. (76 m) diameter vent termination kit for installations requiring 4–in.

(102 mm) diameter pipe.

Page 56: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

56

Sizing The Vent Pipe

Page 57: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

57

Sizing The Vent Pipe

DRAFT COPY - ICP CONFIDENTIAL

Page 58: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

58

Vent Pipe Support

• Helps support vent pipe• Notches in coupling slide

over buttresses on adapter• Adds to unit serviceability

– Provides an optional disconnect point

Page 59: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

59

Combustion Air Adapter

• Attach to K.O. on casing– Any unused top or side K.O.

may be used • Connect 2” combustion air

pipe to casing• Gluing is not recommended

– Pilot drill 1/8” hole and secure with ½” #7 sheet metal screw

– Seal with silicone

Page 60: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

60

Comparing the Two Adapters(Both fit 2” PVC pipe)

Combustion Air Pipe Adapter

Vent Pipe Support

2 3/8”2”Internal pipe stop No pipe stop

Page 61: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

61

Vent Coupling & Adapter

• Coupling is notched• Provides for proper

orientation of coupling

• Notches slide over buttresses on adapter

Page 62: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

62

Vent Pipe Coupling & Combustion Air Pipe Adapter

Gaskets

Page 63: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

63

Continuous Vent PipeVent pipeInserts through coupling to vent elbow

Vent coupling w/clampsSlides over adapter

Vent coupling adapterAttaches to furnace casing

Vent pipePasses through adapter Inserts into Vent Elbow

360° Vent ElbowConnects to vent pipe

Page 64: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

64

Flush Mount Vent Pipe

Vent pipeInserts ½ way into coupling

Vent coupling w/clampsSlides over adapter

Vent coupling adapterAttaches to furnace casing

Vent pipe from inducerPasses through adapter Inserts ½ way into coupling

360° Vent coupling Vent pipe connects to coupling

Page 65: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

65

• Measure the vent pipe– Insert pipe through K.O and

adapter w/gasket installed– Insert pipe into vent elbow

• Slide adapter down on furnace casing– Mark the pipe at the top of the

adapter• Remove pipe from vent elbow

– Cut pipe square

Flush Mount Vent Pipe

Page 66: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

66

Optional Flush Mount Vent Pipe

• Clean and prime vent pipe• Pipe is inserted in vent elbow

– Clean and prime pipe

• Adapter with gasket is glued to vent pipe– Insert vent pipe into vent elbow– Apply cement to pipe and

adapter– Slide adapter over vent pipe

• If pipe is not glued to the adapter, the pipe will leak water!

Page 67: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

67

• Attach vent pipe adapter to furnace casing with screws

• Install vent coupling– Align notches in vent

coupling over stand-offs on vent pipe adapter

– Push down to seat coupling

• Seat coupling on adapter• Torque clamp 15 lb-in.

Optional Flush Mount Vent Pipe

Page 68: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

68

• Insert remaining vent pipe into coupling

• Torque clamp on coupling 15 lb-in.

• Torque clamp on vent elbow 15 lb-in.

Optional Flush Mount Vent Pipe

Page 69: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

69

Vent Through Casing Side

• Install adapter/gasket• Install coupling-

– Align notched and fully seat on vent pipe adapter

• Attach remaining vent pipe• Torque all clamps 15 lb-in.

Page 70: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

70

• Requires a (minimum) 12-inch pipe w/tight radius elbow• Pipe can be attached to any un-used 2-inch K.O.• Orient elbow or pipe away from front

– No combustion air disk required– Can be screened using ½” metal or plastic screening

Combustion Air Pipe (Non-Direct Vent)

12” 12”12”

Page 71: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

71

Single-Stage and Two-Stage PSC Inducer Assembly

360°Inducer outlet coupling

PSC inducer motor

Capacitor

Page 72: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

72

Single- and Two-StageInducer Assemblies

• Three unique sizes for each– PSC ball bearing motor– Provides optimum performance

• Adjustable vent coupling– Adjusts to 4 positions– Loosen the clamp, rotate the coupling, re-tighten the clamp

• Integral condensate drainage– No external hoses required

• Service replacement will be fully assembled

Page 73: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

73

Key Features Inducer Assembly

Drain outlets with gaskets

Mounting tabs

Inlet gasket

Flue gas inlet

Page 74: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

74

PSC Inducer Inlet ChokeFactory Installed

Inlet Choke Plate(when used)

Page 75: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

75

Integrated Inducer Vent/DrainFlue gases exit through the inner opening

The larger opening channels condensate from the vent through the inducer and out the drain openings in the back of the inducer.

Page 76: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

76

Vent Condensate DrainageFlue gases exit through the inner opening

The larger opening channels condensate from the vent through the inducer and out the drain openings in the back of the inducer.

DRAFT COPY - ICP CONFIDENTIAL

Page 77: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

77

Collector Box-Front View

Inducer drain openings

Inducer attachment points w/brass inserts (red circles)

Condensate trap gasket

Condensate trap gasket

Condensate trap openings for upflow and horizontal right

Condensate trap openings for downflow and horizontal left

Pressure Switch/Relief port

Outlet to inducer

Pressure Switch/Relief port

Page 78: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Single Stage Pressure Switches

• Single stage furnaces have 2 pressure switches– Housing Pressure Switch (HPS)

• Tapped into Inducer Housing• Connects electrically to the CPU of the furnace control board

– Collector Box Pressure Switch (LPS)• Tapped into Collector Box• Connects electrically to GVR via furnace control board

• The HPS has a lower set point than the LPS– HPS functions as a blocked vent switch– LPS functions as a blocked drain switch

Page 79: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Single Stage Pressure Switches

Page 80: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Single Stage Wiring Diagram

• Refer to the legend• HPS

– Inducer Housing Pressure Switch, SPST (N.O.)

• LPS– Collector Box Pressure

Switch, SPST (N.O.)

Page 81: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Single Stage Pressure Switches

Page 82: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Pressure Switch Settings

Single Stage Pressure Switches

Input Part Number Collector Box Pressure Switch Housing Pressure Switch

Max Make-IWC Nom Break-IWC Max Make-IWC Nom Break-IWC

100 &

120HK06NB030 0.45 0.30 +/- 0.05 0.45 0.30 +/- 0.05

140 HK06NB031 0.45 0.30 +/- 0.05 0.60 0.45 +/- 0.05

Page 83: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

83

Heat Exchanger AssemblyFront View

Page 84: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

84

Heat Exchanger AssemblyRear View

DRAFT COPY - ICP CONFIDENTIAL

Page 85: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

85

Primary Assembly

• Completely redesigned heat exchanger• Compact multi-pass design• Aluminized• Service replacement sold fully assembled to the Primary Cell Inlet Plate

Page 86: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

86

Condensing Heat Exchanger

• Fin and tube type design • Stainless steel tubes• Aluminum fins• Tubes are straight through• Turbulators are “locked” in each tube

Page 87: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

87

Burners, HSI and Flame Sensor

• One piece burner design for each size• Burners are “ganged” together• Eliminates burner misalignment

– Note igniter and flame sensor locations• Igniter mounts from the top of the burner assembly• Flame sensor mounts through tab on burner• Flame sensor is positioned underneath burner

– Igniter resistance at room temp• 40 to 70 ohms

– Flame sensing current• 4 to 6 micro amps DC

Page 88: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

88

Manifold Assembly Features(Top plate removed for clarity)

Manifold is the same type for all families

Four screws attach manifold here

Page 89: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

89

Burner Assembly

Igniter resistance is 40 to 70 ohms @ room temperature and is stable over the life of the igniter

Page 90: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

90

Burner Assembly

Page 91: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

91

Single-Stage Gas Valve - Features

Page 92: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

92

Blower Assemblies

• Improved blower rails• Forward-facing mounting

screws• Longer main harness

(not shown)– Blower can be removed

without harness removal• Forward-facing control

board

Mounting Screw Locations

Page 93: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

93

Torsion-Flex Blower Motors

• Mounting arms attached to motor• Isolated with rubber grommets

Page 94: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

94

Typical Blower Assembly (Expanded)

Page 95: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

95

There are 2 sets of holes in the blower so if one set gets stripped, the whole motor can be rotated to the other set of holes.

For example:

One or more of the screws were stripped in the blower marked with a blue circle.

Remove all 4 mounting screws, rotate the motor to the holes with the arrows and re-install the screws.

Motor Mounting Holes

Page 96: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

96

Remember!

• Either set of screw holes can be used to mount the blower as long as…– The same hole position is used for each

mounting arm– Do not use a left-side hole for one mounting

leg then a right side hole for another mounting leg.• This stresses the mounting arms and can

cause them to break

Page 97: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

97

Propane Conversion

• Regulator spring change required for all models• Low Gas Pressure Switch (LGPS) required for

ALL models• Burners will use “Mixing Screws”

– 1 screw is installed in each burner venturi– Provide better mixing of propane and combustion air– Includes drill bit to drill the correct size hole

Page 98: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

98

Converting The Gas Valve

Page 99: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

99

Spoiler Screw

Page 100: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

100

LGPS Installation– 14 3/16” casing– Or, vent passes across

vestibule– Install switch as shown

• Manifold removed• Add wires to switch• Install manifold

Page 101: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

101

Low Gas Pressure Switch Installation

Page 102: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

102

Low Gas Pressure Switch InstallationOptional Location

Page 103: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

103

Setup and Service

Page 104: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

104

Single-stage PSC

24vac Thermostat Connections

R, W, Y, G Inducer Pre/Post Purge 15 Sec/5 Sec

Heat On Delay 25 Sec EAC Yes

Heat Off Delay 90, 120, 150, 180 Hum 24 vac Q.C.

Cool On Delay 3 Sec Hum Method When Pressure Switch Closes

Cool Off Delay 90 Sec Blower Speeds Up to 4 speed taps at motor, 2 are controlled

Optional Cool Off Delay Cut J1 Jumper (non reversible)

Heat Airflow Selectable Heat

Component Self Test Yes Cool Airflow Selectable High Cool Only

Non-Volatile Memory Yes Continuous Fan Same as Heat

Control Board Features

Page 105: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

105

Single-Stage PSC ControlComponent Layout

Page 106: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

106

Optional 3-Second Cooling Off Delay

CUT J2 JUMPER TO REDUCE

90 SECOND COOLING OFF-DELAY TO 3 SECONDS

(NON-REVERSIBLE)

Page 107: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

107

Single-Stage PSC ControlFan Speed Selection

SELECT HEATING AND COOLING SPEEDS REQUIRED

CONTINUOUS FAN SPEED IS HEATING SPEED

STORE EXTRA SPEEDS ON SPARE 1 AND SPARE 2 TERMINALS

Page 108: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

108

Heating Off DelaySingle-Stage Control

2 PIN JUMPER: 1 TO 2 90 SECONDS 2 TO 3 120 SECONDS

3 TO 4 150 SECONDS 4 TO 5 180 SECONDS

90

150

120

180

Page 109: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

109

Single-Stage ControlComponent Self Test

To initiate the component last sequence, shut OFF the room thermostat or disconnect the “R” thermostat lead. Briefly short the TEST/TWIN terminal to the COM/24V terminal (Red Arrow)Once initiated the Status LED will flash the last Status Code and then turn ON the inducerThe inducer motor will run for the entire component test. The hot surface igniter, blower motor FAN speed (if equipped), blower motor Heat speed and blower motor COOL speed will be turned ON for 15 seconds each. Gas Valve and Humidifier will not be turned on.

Page 110: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Status CodesCode Description

Heartbeat NO PREVIOUS CODE • Stored status codes are erased automatically after 72 hours or as specified above.

2 PRESSURE SWITCH DID NOT OPEN. Check for: Obstructed pressure switch tubing, Pressure switch stuck closed.

3 PRESSURE SWITCH DID NOT CLOSE OR RE-OPENED. Check for: If LPS is open longer than 6 minutes, inducer shuts off for 18 minutes before re-try. If HPS remains open for 72 seconds after the gas valve closes (after 3 successive trials) the furnace control will lockout for 3 ½ hours before re-try

4 LIMIT CIRCUIT FAULT. Indicates a limit or flame rollout switch is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #7. If open less than 3 1/2 minutes status code #4 continues to flash until blower shuts off. Flame rollout switch requires manual reset. Check for: Dirty filter or restricted duct system-Improper limit switch or no limit gasket. Defective switch or connections- Improper gas input adjustment- Loose blower wheel

5 ABNORMAL FLAME PROVING SIGNAL, Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: Leaky gas valve; Stuck-open gas valve; Dirty flame sensor insulator

6 IGNITION PROVING FAULT -Control will try three more times before lockout #14 occurs. If flame signal lost during blower time limits. Thirty seconds after being turned ON or ten seconds during steady-state operation. Check for:- Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal) Manual valve shut-off- Control ground continuity- Gas valve defective fumed 'OFF'- Low inlet gas pressure-Defective hot surface igniter-Flame sensor must not be grounded-Green/yellow wire MUST be connected to furnace sheet metal.

110

Page 111: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

111

Code Description

7 LIMIT CIRCUIT LOCKOUT. Lockout occurs If a limit or flame rollout switch is open longer than 3 ½ minutes. Control will auto-reset in 3 hrs. Refer to Code 4.

8 GAS HEATING LOCKOUT • Control will NOT auto reset. Check for - Mis-wired gas valve -Defective control (valve relay)

9 POLARITY Line voltage (220 VAC) polarity reversed.

1 + 2 BLOWER ON AFTER POWER UP (115VAC or 24VAC)- Blower runs for 90 seconds, if unit is powered up during a call for heat (R to W/W1 closed) or (R to W/W1) opens during the blower on delay period.

6 + 1 IGNITION LOCKOUT Control will auto reset in 3 ½ hours. Refer to Code 6

OFF SECONDARY VOLTAGE FUSE IS OPEN • Check for - Short circuit in secondary voltage (24VAC) wiring.

On (solid) CONTROL CIRCUITRY LOCKOUT Auto reset after 72 minutes. Lockout due to: Gas Valve relay stuck open. Flame sense circuitry failure. Software check error. Reset power to clear lockout. Replace control if status code repeats.

Status Codes

Page 112: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

112

Sequence Of Operation

• NOTE: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire routed to gas valve and manifold bracket screw. Using the schematic diagram in Fig. 64, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.

• NOTE: If a power interruption occurs during a call for heat (W), the control will start a 108–sec blower–only ON period two sec after power is restored, if the thermostat is still calling for gas heating. The Green LED light will flash Code 1+2 during the 108–sec period, after which the LED will be flashing a heartbeat, as long as no faults are detected. After the 108–sec period, the furnace will respond to the thermostat normally.

Page 113: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

113

Page 114: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

114

ThermostatThermostat

Page 115: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

115

ThermostatThermostat

Page 116: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

116

ThermostatThermostat

Page 117: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

117

ThermostatThermostat

DRAFT COPY - ICP CONFIDENTIAL

Page 118: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

118DRAFT COPY - ICP CONFIDENTIAL

Page 119: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

119

Start-up

• Refer to the installation instructions for specific start-up details

• Start-up procedures are:– Verify installation is complete– Verify the correct orifices are installed– Prime the condensate trap– Purge the gas supply line– Check the inlet gas pressure

Page 120: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

120

Start-up Continued

• Start-up procedures (continued) are:– Adjust the manifold pressure– Set the temperature rise– Set the blower off delay– Set the cooling airflow– Check safety control operation– Review installation checklist

Page 121: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

Priming The Condensate Trap1. Remove upper and middle collector box drain plugs oppositeof the condensate trap.2. Connect field-supplied 5/8--in. (16 mm) ID tube with attached funnel to upper collector box drain connection.3. Pour one quart (liter) of water into funnel/tube. Water should run through collector box, overfill condensate trap,and flow into open field drain.4. Remove funnel; replace collector box drain plug.5. Connect field-supplied 5/8-in. (16 mm) ID tube to middle collector box drain port.6. Pour one quart (liter) of water into funnel/tube. Water should run through collector box, overfill condensate trap,and flow into open field drain.7. Remove funnel and tube from collector box and replace collectorbox drain plug.

Page 122: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

122

Start-up Continued• Start-up procedures are:

– Check the inlet gas pressure• Use a good quality fluid-filled manometer to measure

the inlet pressure at the gas valve• Set the furnace to call for heat

– Verify inlet gas pressure does not drop below minimum inlet pressure

» 4.5 IWC for Natural Gas» 12.0 for Propane

– Adjust the manifold pressure• Manifold/orifice tables are provided• Use a good quality fluid-filled manometer to measure

the manifold pressure at the gas valve– Adjust manifold pressure at the regulator of the gas valve

Page 123: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

123

Single-Stage Gas Valve - Features

Page 124: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

124

Start-up Continued• Start-up procedures (cont.) are:

– Set the temperature rise• Temperature rise shown on the unit rating plate• Run the furnace at steady state• Measure the temperature in the supply air and the return air

– Measure supply temperature away from the line of sight of the heat exchanger

• Subtract the return air temperature from the supply air temperature

• Change blower speed to increase or decrease the temperature rise

• Change blower speed at the heating relay on the furnace control board

– Ideal point is at the mid-point of the rise or slightly above the midpoint.

Page 125: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

125

Start-up Continued

• Start-up procedures (cont.) are:– Set the blower off delay

• Move the jumper on the control board to the desired off delay time

– Set the cooling airflow• Blower airflow tables are in the installation

instructions.– Typical cooling speed is high speed

• Change motor speeds at the cooling relay on the furnace control board

Page 126: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

126

Single-Stage PSC ControlComponent Layout

Page 127: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

127

Single-Stage PSC ControlFan Speed Selection

SELECT HEATING AND COOLING SPEEDS REQUIRED

CONTINUOUS FAN SPEED IS HEATING SPEED

STORE EXTRA SPEEDS ON SPARE 1 AND SPARE 2 TERMINALS

Page 128: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

128

Heating Off DelaySingle-Stage Control

2 PIN JUMPER: 1 TO 2 90 SECONDS 2 TO 3 120 SECONDS

3 TO 4 150 SECONDS 4 TO 5 180 SECONDS

90

150

120

180

Page 129: ICP Confidential Not for further publication Condensing Furnace Distributor Technical Training 1

ICP ConfidentialNot for further publication

129

Start-up Continued

• Start-up procedures (cont.) are:– Check safety control operation

• Pressure switch operation• Limit switch operation• Flame sensing circuit

– Review installation checklist