4
HFP100/HFP200 High Flow Vacuum Pump The HFP Series High Flow Vacuum Pump provides a continuous vacuum through the OptiNet communications backbone, and is offered with a bracket assembly, backup redundancy, and status notification options. The pump connects to the Sensor Suite (SST), which sequences air samples from the Air Data Routers (ADRs). Multiple areas can be monitored from the ADRs, and the routers can be networked as part of a larger distributed system. Includes • Factory set pressure relief valve. • 100' of 1/2" OD - 3/8"ID black polyethylene flame retardant tubing. Meets UL94V2 and UL1820. • Quick connect tubing fittings for easy installation. • Check-valve assembly to support the backup pump configuration. • Muffler assembly. • Vibration arresting rubber feet. • Electrical cord and plug. Options • 115 Vac/220 Vac options. • Bracket assembly for easy installation. • Backup pump and pump control module redundancy option and fault signaling features. FEATURES • Oilless operation • Permanently lubricated bearings • Long-life diaphragm • Balanced for smooth, low vibration operation • Redundancy and other failsafe options HFP100/HFP200 High Flow Vacuum Pump

HFP100/HFP200 High Flow Vacuum Pump - Aircuity · HFP100/HFP200 High Flow Vacuum Pump The HFP Series High Flow Vacuum Pump provides a continuous vacuum through the OptiNet communications

Embed Size (px)

Citation preview

HFP100/HFP200 High Flow Vacuum Pump

The HFP Series High Flow Vacuum Pump provides a continuous vacuum through

the OptiNet communications backbone, and is offered with a bracket assembly,

backup redundancy, and status notification options. The pump connects to

the Sensor Suite (SST), which sequences air samples from the Air Data Routers

(ADRs). Multiple areas can be monitored from the ADRs, and the routers can be

networked as part of a larger distributed system.

Includes• Factorysetpressurereliefvalve.

• 100'of1/2"OD-3/8"IDblackpolyethyleneflameretardanttubing.MeetsUL94V2andUL1820.

• Quickconnecttubingfittingsforeasyinstallation.

• Check-valveassemblytosupportthebackuppumpconfiguration.

• Mufflerassembly.

• Vibrationarrestingrubberfeet.

• Electricalcordandplug.

Options• 115Vac/220Vacoptions.

• Bracketassemblyforeasyinstallation.

• Backuppumpandpumpcontrolmoduleredundancyoptionandfaultsignalingfeatures.

FEATURES

• Oillessoperation

• Permanentlylubricatedbearings

• Long-lifediaphragm

• Balancedforsmooth,lowvibrationoperation

• Redundancyandotherfailsafeoptions

HFP100/HFP200 High Flow Vacuum Pump

www.aircuity.com HFP100/HFP200HighFlowVacuumPump Page2of4

BaseNumber

SeriesNumber101 Single115Vac,60HzPump102 Dual115Vac,60HzPumps201Single220Vac,50HzPump202 Dual220Vac,50HzPumps

PumpBracketBA2Includesabracketassemblytomountthepump,

outletsappropriateforthespecifiedpumpvoltage,andapumpinterconnectionkit.

PumpControlModuleOptionPCMIncludespumpcontrolmoduleforbackuppumpconfiguration. Requiresdualpumpselectioninseriesdesgination(102or202).BlankNopumpcontrolmodule.

HFPX-BA2-X

Pump Specifications

Model Number Voltage-Frequency HP VA Watts Net Wt. Per Pump Operating Environment

HFP101/102 115Vac,60Hz .125 450 191 14.5lbsperpump 41°–104°F(5°–40°C)

HFP201/202 220Vac,50Hz .125 420 171 14.5lbsperpump 41°–104°F(5°–40°C)

Regulatory Compliance

Ordering Guide

Page3of4 HFP100/HFP200HighFlowVacuumPump www.aircuity.com

Pump Bracket (BA2)

SpecificationsSize 24.187"Wx7.5"Hx7.25"DWeightapprox.12lbs.Mounting WallMountedContactor Energizing Power 4VA,approx.

ThePumpBracketprovidesastableplatformtomountbothaprimaryandbackuppump.The“BA2”,includesafactorymountedoutletandcontactorassemblydesignedtooperatewithaPumpControlModule(PCM),whenordered,toenablebackuppumpoperationwhenasustainedlossofvacuumisdetected.Initsdeenergizedstate,thecontactorappliesfieldwiredlinevoltage(115Vacor220Vac),basedonthespecifiedpumpvoltagetooneside(thetop)oftheduplexoutlettopowertheprimarypump.WhenalossofvacuumisdetectedbythePCM,itwillenergizethecontactorviaClass2–lowvoltagepowerwhich,inturndisconnectslinevoltagefromtheprimarypumpandappliesittothebackuppump,pluggedintothebottomsideoftheduplexoutlet.ThisisalatchedstatethatmustbemanuallyresetviathePCMresetfunction,orbycyclingpower.

WallMountBracket

CheckValves

SwitchedDuplexOutlet

PrimaryPumpBackupPump

EnclosureforPCMLowVoltageConnectionstoContactor

HFP102-BA2-PCM - shown above (PCM board not shown)

www.aircuity.com HFP100/HFP200HighFlowVacuumPump Page4of4

Pump Control Module Option (PCM)

SpecificationsSize 4.25"Wx4.00"HMounting MountsinsidetheSSTenclosureviaacard-guidebracketincludedwiththeoption.Power24Vac,±15%60HzPower Consumption 2.4VA,approx.Operating Environment40°–120°F(4.4°–49°C),0–90%RH(non-condensing)Regulatory Compliance

PumpControlModulePCBcontinuouslymonitorsvacuumlevelsprovidedbythepumpassemblyviaasensorelement.ItispoweredoffoftheSSTandprovidessignalingtotheSSTtosignifynormaloperation,alossofvacuum(belowafactorysetthreshold),ortheconditioninwhichthebackuppumphasbeenactivated.Whenalossofvacuumhasbeendetectedforasustaineddurationofabout1minutethePCMlatches24Vactoremotelyenergizethecontactorinthepumpbracketassembly(BA2)inordertoenablethebackuppump.Toreturnoperationtotheprimarypump,thePCMmustberesetviaitspush-buttonresetfunction,orbycyclingpower.OptiNetinturnhastheabilitytocommunicatethisconditiontotheKnowledgeCenterinordertopromptacallforservice.

Features• Provideslatchingcontroltoenablebackuppump.

• ContinuouslymonitorsvacuumlevelsatSST.

• Provideslocal0–10Vscaledgaugepressureoutputtoaidfielddiagnostics.

• LEDindicatorsclearlysignifypumpandvacuumstatus.

• Automatic/FixedModes.

• Test/ResetFunctionality.

• IsolatedForm-Ccontactstosignifylossofvacuumtoothersystems.RatedforClass2power(30VAmax).

SSTAssembly PCMMountedinCardGuideBracket

PumpControlModule

ConnectionstoPumpContactor

©2012Aircuity,Inc.Specificationsaresubjecttochangewithoutnotice.HFP100/HFP20009/2012

Part15ClassA

UL916AccessoryEnergyManagementEquipment