Upload
krsatish047
View
223
Download
0
Embed Size (px)
Citation preview
8/11/2019 Harmonics supression
1/38
HARMONIC SUPRESSION TECHNIQUES
IN POWER SYSTEM
PRESENTED BY :
KUMAR SATISH
ROLL NO.- 112224
01 SEPT 2014 NITW - EED 1
8/11/2019 Harmonics supression
2/38
PLAN OF PRESENTATION
1. DEFINITIONS
2. CATEGORIES OF POWER QUALITY VARIATIONS
3. HARMONIC DISTORTION SOURCES IN INDUSTRIAL POWER SYSTEMS
4. EFFECTS OF HARMONICS ON ELECTRICAL EQUIPMENT
5. HARMONIC STANDARDS
6. HARMONIC MITIGATING TECHNIQUES
7. DESIGN EXAMPLES
8. CONCLUSIONS
01 SEPT 2014 NITW - EED 2
8/11/2019 Harmonics supression
3/38
WHY HARMONIC ANALYSIS ?
When a voltage and/or current waveform is distorted, it causes abnormaloperating conditions in a power system such as:
Voltage Harmonics can cause additional heating in induction and synchronousmotors and generators.
Voltage Harmonics with high peak values can weaken insulation in cables,windings, and capacitors.
Voltage Harmonics can cause malfunction of different electronic components andcircuits that utilize the voltage waveform for synchronization or timing.
Current Harmonics in motor windings can create Electromagnetic Interference(EMI).
01 SEPT 2014 NITW - EED 3
8/11/2019 Harmonics supression
4/38
Current Harmonics flowing through cables can cause higher heating over and
above the heating that is created from the fundamental component.
Current Harmonics flowing through a transformer can cause higher heating overand above the heating that is created by the fundamental component.
Current Harmonics flowing through circuit breakers and switch-gear can increasetheir heating losses.
RESONANT CURRENTS which are created by current harmonics and the differentfiltering topologies of the power system can cause capacitor failures and/or fusefailures in the capacitor or other electrical equipment.
False tripping of circuit breakers ad protective relays.
01 SEPT 2014 NITW - EED 4
8/11/2019 Harmonics supression
5/38
01 SEPT 2014 NITW - EED 5
a) Current Source nonlinear load
Diode rectifier for ac drives,
electronic equipment, etc
HARMONIC SOURCES
Thyristor rectifier for dc drives,
heater drives, etc.
Per-phase equivalent circuit
of thyristor rectifier
b) Voltage source nonlinear load
Per-phase equivalent circuit
of diode rectifier
8/11/2019 Harmonics supression
6/38
01 SEPT 2014 NITW - EED 6
POWER QUALITY STANDARDS
IEEE 519-1992 STANDARDSTABLE I
CURRENT DISTORTION LIMITS FOR GENERAL DISTRIBUTION SYSTEMS
(120-69000 V)
Isc/IL
8/11/2019 Harmonics supression
7/3801 SEPT 2014 NITW - EED 7
TABLE II
LOW VOLTAGE SYSTEM CLASSIFICATION AND DISTORTION LIMITS
IEEE 519-1992 STANDARTS
Special
Applications
General
System
Dedicated
System
Notch Depth 10% 20% 50%
THD (Voltage) 3% 5% 10%
Notch Area
(AN)*
16,400 22,800 36,500
Source: IEEE Standard 519-1992.
Note: The value AN for another than 480Volt systems should be
multiplied by V/480 .The notch depth, the total voltage distortion factor (THD) and
the notch area limits are specified for line to line voltage.
In the above table, special applications include hospitals and
airports. A dedicated system is exclusively dedicated to converter load.
*In volt-microseconds at rated voltage and current.
8/11/2019 Harmonics supression
8/3801 SEPT 2014 NITW - EED 8
TABLE III
LIMITS OF THD%
IEEE 519-1992 STANDARDS
SYSTEM
Nominal Voltage
Special
Application
General
Systems
Dedicated
Systems120-600V 3.0 5.0 8.0
69KV and below - 5.0 -
8/11/2019 Harmonics supression
9/3801 SEPT 2014 NITW - EED 9
1) Parallel-passive filter for current-source nonlinear loads
TYPES OF FILTERS
Harmonic Sinc
Low Impedance
Cheapest
VA ratings = VT(Load Harmonic current + reactive current of the filter)
8/11/2019 Harmonics supression
10/3801 SEPT 2014 NITW - EED 10
2) Series-passive filter for voltage-source nonlinear loads
Harmonic damHigh-impedance
Cheapest
VA ratings = Load current (Fundamental drop across filter + Load Harmonic Voltage)
8/11/2019 Harmonics supression
11/3801 SEPT 2014 NITW - EED 11
3) Basic parallel-active filter for current source in nonlinear loads
8/11/2019 Harmonics supression
12/38
01 SEPT 2014 NITW - EED 12
4) Basic series-active filter for voltage-source in nonlinear loads
8/11/2019 Harmonics supression
13/38
01 SEPT 2014 NITW - EED 13
5) Parallel combination of parallel active and parallel passive
6) Series combination of series active and series passive
8/11/2019 Harmonics supression
14/38
01 SEPT 2014 NITW - EED 14
7) Hybrid of series active and parallel passive
8) Hybrid of parallel active and series passive
8/11/2019 Harmonics supression
15/38
01 SEPT 2014 NITW - EED 15
9) Series combination of parallel-passive and parallel-active
10) Parallel combination of series-passive and series-active
8/11/2019 Harmonics supression
16/38
01 SEPT 2014 NITW - EED 16
11) Combined system of series-active and parallel-active
12) Combined system of parallel-active and series-active
8/11/2019 Harmonics supression
17/38
POWER FACTOR CORRECTION ANDHARMONIC TREATMENTUSING TUNED FILTERS
- Basic configuration of a tuned 3-capacitor bank for power factor correction and
harmonic treatment.
01 SEPT 2014 NITW - EED 17
Simple and cheap filter
Prevents of current harmonic magnification
8/11/2019 Harmonics supression
18/38
01 SEPT 2014 NITW - EED 18
ACTIVE FILTERING
Parallel type Series type
8/11/2019 Harmonics supression
19/38
01 SEPT 2014 NITW - EED 19
-2500
-1500
-500
500
1500
2500
0 5 10 15 20 25 30 35 40
I
[A]
Time [ms]
0
5
10
15
20
25
30
2 5 8 11 14 17 20 23
[%I
1]
Harmonics
-5000
-2500
0
2500
5000
0 10 20 30 40
Time [ms]
IDynac
omp[A]
0%
5%
10%
15%
20%
25%
30%
35%
2 5 8 11 14 17 20 23
Harmonics
[%I1]
RESULTS OF ACTIVE FILTERING
Input current of a 6-pulse Rectifier driving a DC machine without any input filtering
Input current with Active Filtering
8/11/2019 Harmonics supression
20/38
01 SEPT 2014 NITW - EED 20
-1000
-500
0
500
1000
0 5 10 15 20 25 30 35 40
U
[V]
Time [ms]
0
2
4
6
8
10
12
14
2 5 8 11 14 17 20 23
[%U
1]
Harmonics
-1000
-500
0
500
1000
0 5 10 15 20 25 30 35 40
U[
V]
Time [ms]
0
2
4
6
8
10
12
14
2 5 8 11 14 17 20 23
[%U
]
Harmonics
Typical 6-pulse drive voltage waveform
Voltage source improvement with active filtering
8/11/2019 Harmonics supression
21/38
SHUNT ACTIVE FILTERS
By inserting a parallel active filter in a non-linear load location we can inject a
harmonic current component with the same amplitude as that of the load in to
the AC system.
01 SEPT 2014 NITW - EED 21
C
FL
Equivalent circuit
8/11/2019 Harmonics supression
22/38
01 SEPT 2014 NITW - EED 22
Low implementation cost. Do not create displacement power factor problems and utility loading.
Supply inductance LS, does not affect the harmonic compensation ofparallel active filter system.
Simple control circuit.
Can damp harmonic propagation in a distribution feeder or betweentwo distribution feeders.
Easy to connect in parallel a number of active filter modules in order toachieve higher power requirements.
Easy protection and inexpensive isolation switchgear.
Easy to be installed.
Provides immunity from ambient harmonic loads.
ADVANTAGES OF THE SHUNT OR PARALLEL
ACTIVE FILTER
8/11/2019 Harmonics supression
23/38
01 SEPT 2014 NITW - EED 23
SHUNT ACTIVE FILTER CONTROL
a) Shunt active filter control based on voltage detection
8/11/2019 Harmonics supression
24/38
01 SEPT 2014 NITW - EED 24
3- HYBRID ACTIVE-PASSIVE FILTER
Compensation of current harmonics and displacement power
factor can be achieved simultaneously.
8/11/2019 Harmonics supression
25/38
01 SEPT 2014 NITW - EED 25
HARMONIC DETECTION METHODS
i) Load current detection iAF= iLh
It is suitable for shunt active filters which are installed near
one or more non-linear loads.
ii) Supply current detection iAF= KSiSh
Is the most basic harmonic detection method for series
active filters acting as a voltage source vAF.
iii) Voltage detection
It is suitable for shunt active filters which are used as
Unified Power Quality Conditioners. This type of ActiveFilter is installed in primary power distribution systems. The
Unified Power Quality Conditioner consists of a series and a
shunt active filter.
8/11/2019 Harmonics supression
26/38
01 SEPT 2014 NITW - EED 26
HYBRID ACTIVE-PASSIVE FILTER
Single-phase equivalent circuit Single-phase equivalent circuit
for 5thHarmonic
8/11/2019 Harmonics supression
27/38
01 SEPT 2014 NITW - EED 27
HYBRID SERIES AND SHUNT
ACTIVE FILTER
At the Point of Common Coupling provides:
Harmonic current isolation between the sub transmission and the
distribution system (shunt A.F)
Voltage regulation (series A.F)
Voltage flicker/imbalance compensation (series A.F)
8/11/2019 Harmonics supression
28/38
HYBRID ACTIVE POWER FILTER USING FUZZYDIVIDING
FREQUENCY CONTROL METHOD> It shows great promise in reducingharmonics
> Improve the power factor with a relativelylow capacity active power filter
> Uses HAPF with injection circuit
01 SEPT 2014 NITW - EED 28
Configuration of the adaptive
8/11/2019 Harmonics supression
29/38
Configuration of the adaptivefuzzy dividing frequency
controller
01 SEPT 2014 NITW - EED 29
8/11/2019 Harmonics supression
30/38
Consists of two control
units:A generalized integrator control
unit
A fuzzy adjustor unit.
01 SEPT 2014 NITW - EED 30
8/11/2019 Harmonics supression
31/38
ADVANTAGE :The stability of the system is achieved by a proportional
controller, and the perfect dynamic state is received by thegeneralized integral controller. The fuzzy adjustor is set to adjust
the parameters of proportional control and generalized integralcontrol. Therefore, the proposed harmonic current trackingcontroller can decrease the tracking error of the harmonic
compensation current, and have better dynamic response androbustness
01 SEPT 2014 NITW - EED 31
8/11/2019 Harmonics supression
32/38
Block diagram of the fuzzy
adjustor unit.
01 SEPT 2014 NITW - EED 32
8/11/2019 Harmonics supression
33/38
Fuzzy AdjustorAdjust the parameters of proportional control gainand integral control gain , based on the error and
the change of error
Kp = Kp* + Kp
Ki = Ki* + Ki
01 SEPT 2014 NITW - EED 33
8/11/2019 Harmonics supression
34/38
Comparison without and
with IHAPFTHD pf
Without IHAPF 21.5% 0.69With IHAPF 1.9% 0.94
01 SEPT 2014 NITW - EED 34
8/11/2019 Harmonics supression
35/38
SELECTION OFAF S FOR SPECIFIC APPLICATION CONSIDERATIONS
AF Configuration with higher number of * is more preferredCompensation for
Specific Application
Active Filters
Active
Series
Active
Shunt
Hybrid of
Active Series
and Passive
Shunt
Hybrid of
Active Shunt
and Active
Series
Current Harmonics ** *** *
Reactive Power *** ** *
Load Balancing *
Neutral Current ** *
Voltage Harmonics *** ** *Voltage Regulation *** * ** *
Voltage Balancing *** ** *
Voltage Flicker ** *** *
Voltage Sag&Dips *** * ** *
01 SEPT 2014NITW - EED35
8/11/2019 Harmonics supression
36/38
CONCLUSIONS
Solid State Power Control results in harmonic pollution above the tolerable limits.
Harmonic Pollution increases industrial plant downtimes and power losses.
Harmonic measurements should be made in industrial power systems in order (a) aid in the design of capacitoror filter banks, (b) verify the design and installation of capacitor or filter banks, (c) verify compliance with utilityharmonic distortion requirements, and (d) investigate suspected harmonic problems.
Computer software programs such as PSPICE and SIMULINK can be used in order to obtain the harmonicbehavior of an industrial power plant.
The series LC passive filter with resonance frequency at 4.7 is the most popular filter.
The disadvantages of the the tuned LC filter is its dynamic response because it cannot predict the loadrequirements.
The most popular Active Filter is the parallel or shunt type.
Active Filter technology is slowly used in industrial plants with passive filters as a hybrid filter. These filters canbe used locally at the inputs of different nonlinear loads.
Active Filter Technology is well developed and many manufactures are fabricating Active filters with largecapacities.
A large number of Active Filters configurations are available to compensate harmonic current, reactive power,neutral current, unbalance current, and harmonics.
The active filters can predict the load requirements and consequently they exhibit very good dynamic response.
LC tuned filters can be used at PCC and the same time active filters can be used locally at the input of nonlinearloads.
01 SEPT 2014 NITW - EED 36
8/11/2019 Harmonics supression
37/38
REFERENCES
[1] IEEE Std. 519-1992, IEEE Recommended Practices and Requirements forHarmonic Control in Electric Power Systems, 1993.
[2] IEC Sub-Committee 77B report, Compatibility Levels in Industrial Plants forLow Frequency Conducted Disturbances, 1990.
[3] IEC Sub-Committee 77A report, Disturbances Caused by EquipmentConnected to the Public Low-Voltage Supply System Part 2 : Harmonics ,1990 (Revised Draft of IEC 555-2).
[4] UK Engineering Recommendation G.5/3: Limits for Harmonics in the UKElectricity Supply System, 1976.
[5] CIRGE WG 36.05 Report, Equipment producing harmonics and ConditionsGoverning their Connection to the Mains power Supply, Electra, No. 123,March 1989, pp. 20-37.
[6] Fuzzy adjustor unit IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1,JANUARY 2009
01 SEPT 2014 NITW - EED 37
8/11/2019 Harmonics supression
38/38
DEFINITIONS
[7] J. Arriilaga, D.A. Bradley, and P.S. Bodger, Power System Harmonics,New York:Wiley, 1985.
[8] N. Shepherd and P. Zand, Energy flow and power factor in nonsinusoidal circuits ,Cambridge University Press, 1979.
EFFECTS OF HARMONICS
[9] J.M. Bowyer, Three-Part Harmony: System Interactions Leading to a DivergentResonant System, IEEE Trans. on Industry Applications, Vol. 31, No. 6, Nov/Dec1995, pp. 1341-1349.
[10] R.D. Hondenson and P.J. Rose, Harmonics: the Effects on power Quality andTransformers ,IEEE Trans. on Industry Applications, Vol. 30, No.3, May/June 1994,pp. 528-532.
[11] J.S. Subjak and J. S. McQuilkin, Harmonics-Causes, effects, Measurements andAnalysis: An Update, IEEE Trans. on Industry Applications, Vol. 26, No. 6, Nov/Dec1990, pp. 103-1042.
[12] P.Y. Keskar, Specification of Variable Frequency Drive Systems to Meet the NewIEEE 51 Standard, IEEE Trans. on Industry Applications, Vol.32, No.2, March/April1996, pp. 393-402.