  • OCTOBER 2013 | NEW ZEALAND

    TechnicalSpecification

  • 5 FIXING HARDIEFLEX SHEET 65.1 General 6

    5.2 FastenerDurability 6

    5.3 Fastenersizeandlayout 6

    5.4 GunNailing 7

    5.5 Sheetlayout 7

    6 JOINTING 76.1 General 7

    6.2 VerticalJoint 7

    6.3 InternalCornerandExternalCorner 7

    6.4 HorizontalJoint 7

    7 FINISHING 77.1 Preparation 7

    7.2 Sealants 7

    7.3 Coating 7

    8 STORAGE AND HANDLING 7

    9 MAINTENANCE 8

    10 PRODUCT INFORMATION 810.1 ManufacturingandClassification 8

    10.2 Productmass 8

    10.3 Sheetsizes 8

    10.4 Durability 8

    11 SAFE WORKING PRACTICES 9

    12 ACCESSORIES 11

    13 DETAILS 13

    PRODUCT WARRANTY 39

    1 APPLICATION AND SCOPE 31.1 Application 3

    1.2 Scope 3

    1.3 Setails 3

    1.4 SpecificDesign 3

    2 DESIGN 32.1 Compliance 3

    2.2 Responsibility 3

    2.3 SiteandFoundation 3

    2.4 GroundClearances 3

    2.5 MoistureManagement 4

    2.6 Structure 4

    2.7 WindLoading 4

    2.8 StructuralBracing 4

    2.9 FireRatedWalls 4

    2.10 EnergyEfficiency 4

    3 FRAMING 43.1 General 5

    3.2 Dimensions 5

    3.3 TimberGrade 5

    3.4 Durability 5

    3.5 FrameConstruction 5

    3.6 Tolerances 5

    3.7 Curvedwalls 5

    4 PREPARATION 54.1 Buildingunderlay/HomeRABPrecladlining 5

    4.2 RigidAirBarrier 5

    4.3 VentStrip 5

    4.4 CavityBattens 5

    4.5 Flashings 6

    Contents

    WE VALUE YOUR FEEDBACKTocontinuewiththedevelopmentofourproductsandsystems,wevalueyourinput.Pleasesendanysuggestions,includingyourname,contactdetails,andrelevantsketchesto:

    Ask James Hardie [email protected]

  • James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 3

    1 Application and scope

    1.1 APPLICATIONHardieFlexSheetismanufacturedinNewZealandbyJamesHardiefromfibrecementwhichisacompositionofPortlandcement,groundsand,cellulosefibreandwater.HardieFlexSheetisapaneledlightweightwallcladdingsolutionforresidentialandlightcommercialbuildings.

    HardieFlexSheetisidealformanygeneralbuildingpurposessuchaswallcladding,widesoffits,porchesandgableendsetc.

    HardieFlexSheetisanaturalunsandedsheetandissuitableforapaintfinish.Avarietyofjointingmethodscanbeusedtoachievethedesiredlook.

    If you are a specifierOrotherresponsiblepartyforaprojectensurethattheinformationinthisdocumentisappropriatefortheapplicationyouareplanningandthatyouundertakespecificdesignanddetailingforareaswhichfalloutsidethescopeofthesespecifications.

    If you are an installer Ensurethatyoufollowthedesign,moisturemanagementandassociateddetailsandmaterialselectionprovidedbythedesigner.Allthedetailsprovidedinthisdocumentmustbereadinconjunctionwiththespecifiersspecification.

    Make sure your information is up to dateWhenspecifyingorinstallingJamesHardieproducts,ensureyouhavethecurrentmanual.Ifyourenotsureyoudo,oryouneedmoreinformation,visitwww.jameshardie.co.nzorAskJamesHardieon0800808868.

    1.2 SCOPEThescopeofthisspecificationisfortheuseofHardieFlexSheetlimitedtobuildingswhichfallwithinthescopelimitationsofNewZealandBuildingCode(NZBC)AcceptableSolutionE2/AS1paragraph1.1.ThismanualcoverstheuseofHardieFlexSheetforeitherconstructionmethodsi.e.directfixedorcavity,usedinexternalwallsoftimberframedbuildings.PleaserefertoE2/AS1forfurtherinformationregardingtheselectionofconstructionmethodsforcladdings.

    Thisdocumentisintendedforusebyarchitects,designersandspecifierswhomaybeinvolvedwiththespecificationofHardieFlexSheet.

    1.3 DETAILSVariousHardieFlexSheetdetailsareprovidedintheDetailssectionofthisdocument.ThisspecificationanddetailsinCADfilearealsoavailabletodownloadfromourwebsiteatwww.jameshardie.co.nz.

    1.4 SPECIFIC DESIGNForuseofHardieFlexSheetoutsidethescopeofthisdocument,thearchitect,designerorengineermustundertakespecificdesign.Foradviceondesignsoutsidethescopeofthisspecification,AskJamesHardieon0800808868.

    2 Design

    2.1 COMPLIANCEHardieFlexSheetcomplieswithsection9.7.2ofE2/AS1.InformationcontainedinthisdocumentisalignedwiththerequirementsofNZBCAcceptableSolutionE2/AS1.

    2.2 RESPONSIBILITYThespecifierorotherpartyresponsiblefortheprojectmustrunthroughariskmatrixanalysistodeterminewhichconstructionmethodistobeused.Thedesignermustalsoensurethatthefigurespublishedinthisspecificationareappropriatefortheintendedapplicationandthatadditionaldetailingisperformedforspecificdesignoranyareasthatfalloutsidethescopeofthisspecification.ThedesignersshouldensurethattheintentoftheirdesignmeetstherequirementsoftheNZBC.

    Alldimensionsshownareinmillimetersunlessnotedotherwise.AllNewZealandStandardsreferenceinthismanualarecurrenteditionandmustbecompliedwith.

    JamesHardieconductsstringentqualitycheckstoensurethatanyproductmanufacturedfallswithinourqualityspectrum.Itistheresponsibilityofthebuildertoensurethattheproductmeetsaestheticrequirementsbeforeinstallation.JamesHardiewillnotberesponsibleforrectifyingobviousaestheticsurfacevariationsfollowinginstallation.

    2.3 SITE AND FOUNDATIONThesiteonwhichthebuildingissituatedmustcomplywithNZBCAcceptableSolutionE1/AS1SurfaceWater.FoundationsdesignmustcomplywiththerequirementsofNZS3604TimberFramedBuildingsorbeasperspecificengineeringdesign.ThegradeofadjacentfinishedgroundmustslopeawayfromthebuildingtoavoidanypossibilityofwateraccumulationinaccordancewithNZBCrequirements.

    2.4 GROUND CLEARANCESTheclearancebetweenthebottomedgeofcladdingandpaved/unpavedgroundmustcomplywithsection9.1.3ofE2/AS1.Thefinishedfloorlevelmustalsocomplywiththeserequirements.Theseclearancesmustbemaintainedthroughoutthelifeofthebuilding.

    HardieFlexSheetsmustoverhangthebottomplateonaconcreteslabbyaminimumof50mmasrequiredbyNZS3604.

    HardieFlexSheetsmusthaveaminimumclearanceof100mmfrompavedgroundand175mmfromunpavedground.

    Ontheroofsanddeckstheminimumclearancemustbe50mm.

    Donotinstallexternalcladdingsuchthatitmayremainincontactwithwaterorground.RefertoFigures3and22.

  • 4 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    2.5 MOISTURE MANAGEMENTItistheresponsibilityofthespecifiertoidentifymoisturerelatedrisksassociatedwithanyparticularbuildingdesign.Wallconstructiondesignmusteffectivelymanagemoisture,consideringboththeinteriorandexteriorenvironmentsofthebuilding,particularlyinbuildingsthathaveahigherriskofwinddrivenrainpenetrationorthatareartificiallyheatedorcooled.

    WallsshallincludethoseprovisionsasrequiredbytheNZBCAcceptableSolutionE2/AS1ExternalMoisture.Inadditionallwallopenings,penetrations,junctions,connections,windowsills,headsandjambsmustincorporateappropriateflashingsforwaterproofing.Theothermaterials,componentsandinstallationmethodsusedtomanagemoistureinexternalwalls,mustcomplywiththerequirementsofrelevantstandardsandtheNZBC.ForfurtherinformationondesigningforweathertightnessrefertoBRANZLtdandtheDepartmentofBuildingandHousingupdatesonthefollowingwebsitesrespectively,www.branz.co.nzandwww.dbh.govt.nz.

    2.6 STRUCTURETimber-framedbuildingsmustbedesignedinaccordancewithNZS3604(TimberFramedBuildings).Whentheframingisprovidedasperthespecificengineeringdesign,theframingstiffnessmustbeequivalenttoormorethanthestiffnessrequirementsofNZS3604.

    2.7 WIND LOADINGHardieFlexSheetcladdingaresuitableforuseinallNewZealandwindzonesuptoandincludingEHasdefinedinNZS3604.Aspecificdesignisrequiredforallsituationswherethebuildingsfallinaspecificengineeringdesign(SED)windzone.

    2.8 STRUCTURAL BRACINGHardieFlexSheetcanbeusedtoachievestructuralbracingrequiredfortimberframedbuildingsdesignedandconstructedinaccordancewithNZS3604.TheHardieFlexSheetmustbeinstalledasperspecificbracingsystemdetailsthatareavailableseparately.HardieFlexSheetbracingsystemshavebeenindependentlytestedandassessedbyBRANZandaresuitableforbothconstructionmethodsi.e.directfixandcavity.RefertoJamesHardieBracingDesignManualfordetails.

    2.9 FIRE RATED WALLSHardieFlexSheetcladwallsusingdirectfixorcavityconstructionmethodcanachievefireratingsupto60/60/60whenthewallsareconstructedinaccordancewiththisliteratureandincludethefireratedsystemrequirementsasspecifiedinJamesHardieFireandAcousticDesignManual.RefertoFireandAcousticDesignManualforfurtherinformationaboutfireratedsystems.

    2.10 ENERGY EFFICIENCYExternalwallsconstructedusingHardieFlexSheet,bulkinsulation,wheretheareaofglazingis30%orlessofthetotalwallareaandconstructedasperthistechnicalspecificationcomplieswiththerequirementsforwallsinNZBCAcceptableSolutionH1/AS1(NZBCClauseH1EnergyEfficiency),ReplacementTable1.Tomeetthermalinsulationrequirementsfortheconstruction,thebulkinsulationasspecifiedinTable1mustbeused.ThisinsulationmaybesubstitutedwithinsulationshavinghigherR-values.Thethermalinsulationofawallgetsaffectedwhenthedepthofthetimberframingisincreasedordecreased.ThecalculationusedinTable1isbasedonatimberframingsize90x45mmandusinganinternalliningmaterialsuchasJamesHardieVillaboardLiningora10mmplasterboard.

    Table1Insulation capability

    Climate Zone

    Construction RValue Requirement

    Minimum RValue of Insulation Required

    1and2 1.9m2C/W #R2.0

    3 2.0m2C/W #R2.2

    TotalconstructionR-Valuedependsontheinsulationmaterialusedandtheframingratio.TheinsulationmaterialR-Valuesspecifiedinthistableareforstudsspacedat600mmc/candnogsspacedat800mmc/c.#ToachievehigherR-ValuesofconstructionthewallinsulationmaterialmustbereplacedwithaninsulationmaterialhavinghigherR-Valuestosuittherequirements.ForfurtherguidanceoninsulationrequirementrefertocurrenteditionofHouseInsulationGuidepublishedbyBRANZ.

  • 4 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 5

    3 Framing

    3.6 TOLERANCESInordertoachieveanacceptablewallfinish,itisimperativethatframingisstraightandtrue.

    FramingtolerancesmustcomplywiththerequirementsofNZS3604.Allframingshallbemadeflush.

    3.7 CURVED WALLSHardieFlexSheetcanbeusedinacurvedapplication.RefertoJamesHardietechnicalsupportforfurtherinformation.

    4 Preparation4.1 BUILDING UNDERLAY/HOMERAB

    PRECLAD LININGBuildingunderlayorHomeRABPreCladLiningmustbeprovidedaspertherequirementsofNZBCAcceptableSolutionE2/AS1ExternalMoistureandNZS3604.ThebuildingunderlaymustcomplywithTable23ofE2/AS1andAS/NZS4200.1.ThebuildingunderlaymustbefixedinaccordancewithE2/AS1,NZS3604andAS/NZS4200.2PliableBuildingMembranesandUnderlayInstallationstandardandtheunderlaymanufacturersrecommendations.

    Wallswhicharenotlinedontheinsidefacee.g.garagewallsorgableendsmustincludearigidsheathingoranairbarrierbehindthecladdingwhichcomplieswiththerequirementsofNZBCAcceptableSolutionE2/AS1Table23.HomeRABPreCladLiningissuitableforuseintheseapplications.ItmustbeinstalledinaccordancewithJamesHardieRigidAirBarriersInstallationManual.

    4.2 RIGID AIR BARRIERForEHwindzonesRABBoardmustbeusedinlieuofbuildingunderlays.RefertoJamesHardieRigidAirBarriersInstallationManualforinformationregardinginstallation.

    4.3 VENT STRIPTheJamesHardieuPVCcavityventstripmustbeinstalledatthebottomofallwallsconstructedusingthedrainedandventilatedcavityconstructionmethod.Itisimportantthattheopeningsintheventstriparekeptclearandunobstructedtoallowfreedrainageandventilationofcavities.JamesHardieuPVCventstriphasanopeningareaof1000mm2/mlength.

    4.4 CAVITY BATTENSBuildingswithariskscoreof7-20calculatedinaccordancewithNZBCAcceptableSolutionE2/AS1Table3,requireHardieFlexSheettobeinstalledonacavity.

    Thecavitybattensprovideairspacebetweentheframeandthesheetandareconsideredapackeronlyinthisspecification.

    3.1 GENERALThisHardieFlexSheettechnicalspecificationisonlysuitablefortimber-framedbuildings.Otherframingmaterialsoutsidethescopeofthisspecification.

    3.2 DIMENSIONSA45mm(nominal)minimumstudwidthisrequiredatallsheetedges.Elsewherea35mmwidestudmaybeused.

    3.3 TIMBER GRADEMinimumtimbergraderequirementsareNo.1FraminggradeasperNZS3631NewZealandTimberGradingRulesorequivalent.

    3.4 DURABILITYTheexternalframingmustbetreatedtoaminimumH1.2treatment.RefertoNZBCAcceptableSolutionB2/AS1Durabilityforfurtherinformationaboutthedurabilityrequirements.

    FortimbertreatmentandallowablemoisturecontentinformationrefertoNZS3602(TimberandWood-BasedProductsforuseinBuildings)andNZS3640(ChemicalPreservationofRoundSawnTimber)forminimumtimbertreatmentselectionandtreatmentrequirements.Alsorefertoframingmanufacturersliteratureforfurtherguidanceontimberselection.Framingmustbeprotectedfrommoistureatsitesinaccordancewiththerecommendationsoftheframingmanufacturer.

    NOTE:

    RefertoNZS3602forinformationabouttheallowablemoisturecontentintimber.

    3.5 FRAME CONSTRUCTIONTheframingmustfullysupportallsheetedges.Theframingmustberigidandnotrelyonthecladdingsheetforstability.

    Alltimberframingsizesandset-outmustcomplywithNZS3604andasspecifiedinthisspecification.Useoftimberframingmustbeinaccordancewithframingmanufacturersspecification.

    ForspecificengineeringdesignfortimberframingrefertoNZS3603andAS/NZS1170.

    3.5.1 Direct Fix Construction MethodFordirectfixedconstructionmethodthefollowingframingisrequired:

    Studsprovidedat600mmcentresmaximumand Nogs/dwangsprovidedat1200mmcentresmaximum.

    3.5.2 Cavity Construction MethodForcavityconstructionmethodthefollowingframingisrequired:

    Whenstudsarespacedat600mmcentresmaximumthenthenogs/dwangsmustbeprovidedat800mmcentresmaximum.

    Whenstudsarespacedat400mmcentresthenthenogs/dwangsmaybeprovidedat1200mmcentres.

    Anextrastudisrequiredininternalcorners.

  • 6 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    ThetimberbattensmustbeminimumH3.1treatedinaccordancewithNZS3640(Chemicalpreservationofroughandsawntimber)tocomplywiththedurabilityrequirementsofB2/AS1.

    Cavitybattensmustcomplywithfollowingrequirements:

    beminimum18mmthick. beminimumaswideasthewidthofstuds. whenstudsareat600mmcentresbattenstobeprovidedat300mmcentres.

    befixedbythecladdingfixingstothemainframingthroughthebuildingunderlay.

    untilcladdingsarefixedthebattensonlyneedtobetackedtotheframing.

    NOTE:

    Battenfixingisrequiredtemporarilytokeepthemstraightonthewallduringconstruction.

    Nointermediatebattenbetweenstudsisrequired:

    whenstudsarespacedatmaximum400mmcentresand whenrigidsheathingsinsteadofbuildingunderlaysareused.NOTE:

    100mmlongcavitypackersmustbeusedwhererequiredtosupportfixingsinthiscircumstance.

    Battensmustbefixedwith40x2.8mmHardieFlexnailsat800mmcentresmaximum.

    4.5 FLASHINGSAllwallopenings,penetrations,intersections,connections,windowsills,headsandjambsmustbeflashedpriortosheetinstallation.PleaserefertomoisturemanagementrequirementsinClause2.5.

    Thebuildingunderlaymustbeappropriatelyincorporatedwithpenetrationandjunctionflashings.Materialsmustbelappedinsuchawaythatwatertracksdowntotheexterioronthefaceofbuildingunderlay.JamesHardiewillassumenoresponsibilityforwaterinfiltrationwithinthewallduetopoorinstallationofflashingsorbuildingunderlays.TheselectedflashingmaterialsmustcomplywiththedurabilityrequirementsoftheNZBCAcceptableSolutionE2/AS1.

    5 Fixing HardieFlex Sheet

    5.1 GENERALHardieFlexSheetsmustbekeptdryandundercoverwhilstinstorageorduringinstallation.FramingmoisturecontentsmustnotexceedthemaximumlimitspecifiedinNZS3602priortosheetinstallation.Everyendeavourmustbemadetokeepframingdryoncesheetfixingcommences.

    Allsheetedgesmustbesealedpriortoinstallation.Thesheetedgesmustalsobesealedaroundwindow/dooropeningsandotherpenetrationse.g.meterboxesetc.

    5.2 FASTENER DURABILITYFastenersmustmeettheminimumdurabilityrequirementsoftheNZBC.NZS3604specifiestherequirementsforfixingmaterialtobeusedinrelationtoexposureconditionsandaresummarisedinTable2.

    Table2Exposure conditions and nail selection prescribed by NZS 3604

    Nail Material

    ZoneD* ZoneCoutsideseasprayzoneandZoneBandGeothermalhotspots

    BracingAllzones

    Grade316Stainless

    Hot-dippedgalvanisedor316stainless

    Grade316stainless

    * (Zone C areas where local knowledge dictates that increased durability is required, appropriate selection shall be made) Microclimate conditions as detailed in NZS 3604, paragraph 4.2.4 require SED.

    AlsorefertotheNZBCAcceptableSolutionE2/AS1Table20and21forinformationregardingtheselectionofsuitablefixingmaterialsandtheircompatibilitywithothermaterials.

    5.3 FASTENER SIZE AND LAYOUTHardieFlexSheetmustbefixedtoframingusingthefixingsasspecifiedinTable3andinaccordancewiththefollowingrequirements:

    Nailsmusthaveaminimumclearanceof12mmfromsheetedgesandaminimumof75mmverticallyand150mmhorizontallyfromsheetcorners.

    Nailsmustfinishflushwithsheetsurface.

    Table3Sheet fixingDirect to stud fixing

    40x2.8mmHardieFlexnails

    Fixsheetat200mmcentresatallsheetedgesaswellasallintermediateframing.

    Cavity construction up to and including VH wind zones

    60x3.15mmHardieFlexnails

    Fix sheet at 200mm centres at all studs and at 150mm centres at top plate and bottom plate.

    Cavity construction on buildings with EH wind zone or with uls design wind pressure of up to 2.5kPa

    60x3.15mmHardieFlexnails

    Fix sheet at 150mm centres at all sheet edges as well as all intermediate framing.

    WhenusingrigidairbarrierlikeHomeRABPreCladLiningorRABBoard,thecladdingfixingnailsmustbeincreasedinlengthequaltothethicknessoftherigidairbarrier.

    NOTE:

    Specialfixingarrangementsarerequiredforbracingandfire-resistanceratedwallsystems.FormoreinformationAskJamesHardieon0800808868.

  • 6 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 7

    5.4 GUN NAILINGHardieFlexSheetscanbefixedusingnailguns.Thegunnailsusedmusthaveafullroundheadtoprovidetherequiredholdingpower.Thelengthandgaugeofnailsmustataminimumbeasspecifiedinthisdocument.Checkwithnailgunmanufacturerformoreinformation.

    NOTE:

    DonotuseDHeadnails.Donotusegunnailingforbracingapplications.

    5.5 SHEET LAYOUT Allsheetedgesmustbesupportedbytheframing. HardieFlexSheetmustbefixedvertically.

    6 Jointing6.1 GENERALHardieFlexSheetscanbejointedinanumberofwaystoachievedifferentpanelisedlookofthewalls.

    6.2 VERTICAL JOINTHardieFlexSheetscouldhavethefollowingtypesofverticaljoints.

    uPVCHardiejointerJoint,refertoFigure4and23 TimberBattenJoint,refertoFigure5and24 FlexibleSealantJoint,refertoFigure6and25

    6.3 INTERNAL CORNER AND EXTERNAL CORNER

    HardieFlexSheetcouldhavethefollowingtypesofinternalandexternalcorners.

    uPVCJointer,refertoFigure7,8,26,27and34 TimberBattenJoint,refertoFigure9,10,28and29 FlexibleSealantJoint,refertoFigure11,12,30and31

    6.4 HORIZONTAL JOINTAtfloorjoistlevelsahorizontaljointmustbeprovidedtoaccommodatethemovementresultingfromtimberjoistshrinkageandsettlement.

    ForHardieFlexSheetsuseaJamesHardieuPVChmouldtoformahorizontaljointorapurposemademetalZflashingcouldalsobeusedtoformahorizontaljoint.

    7 Finishing

    7.1 PREPARATIONPaintingofHardieFlexSheetsisrequiredinordertomeetthedurabilityrequirementsoftheNZBCandproductwarranties.HardieFlexSheetsmustbedryandfreefromdirtbeforepainting.Coatingmustbecompletedwithin3monthsofsheetinstallation.

    WhenusinguPVCflashings,thelightreflectivevalueofthecolourusedmustbemorethan40%asrequiredunderE2/AS1.Darkcolourscauseexcessivemovementanddeterioratethecladdingperformance.

    7.2 SEALANTS AllsealantsmustmeettherelevantrequirementsoftheNZBC.Applicationanduseofsealantsmustcomplywithmanufacturersinstructions.Checkwithsealantmanufacturerpriortocoatingoversealants.Somesealantmanufacturersdonotrecommendcoatingovertheirproduct.

    7.3 COATING UseonlyqualityexteriorpaintscomplyingwithAS3730.Manufacturersspecificationfortheselectedpaintmustbefollowed.Notethatsomepaintsrequireundercoatbeforeapplyingthefinishcoat.Priortocoating,thesurfaceshouldbeexaminedtoensureitisclean,dryandfreeofanydustorcontaminants.WhenusinguPVCflashings,thelightreflectivevalue(LRV)forthecolourmustnotbelessthan40%.

    PaintswithalowLRVwillabsorbmoresolarheatandcouldcausethecomponentsusedinthewalltoexpandorcontract.Thiscombinedwithglossypaintsandwettimberusedatconstructionstage,couldleadtoincreasedchancesoffastenerreadthroughasiscommonwithanyotherbuildingmaterial.

    Enamelbasedpaintscanbeused,utilisingathree-coatsystem.Refertothepaintmanufacturerfordetailsbeforecommencingthecoatingwork.

    Paintmustnotbeappliedwhenthetemperatureisbelow10C.

    8 Storage and handling

    HardieFlexSheetsmustbelaidflatonasmoothlevelsurface.Edgesandcornersmustbeprotectedfromchipping.Toensureoptimumperformance,storepanelsundercoverandkeepdrypriortofixing.Ifthesheetsbecomewet,allowthemtodrythoroughlybeforefixing.Donotcarrysheetsontheflat,carryintheverticalpositiontoavoidexcessivebending.

  • 8 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    10.3 SHEET SIZES AvailablesizesofHardieFlexSheetsarespecifiedinTable4.

    Table4Sheet sizes HardieFlex Sheets 6mm and 7.5mmThickness (mm)

    Width (mm)

    Length (mm)

    1800 2400 2700 3000

    6 900 3

    6 1200 3 3 3 3

    7.5 1200 3 3 3

    10.4 DURABILITYHardieFlexSheets,wheninstalledandmaintainedasperthetechnicalspecification,willmeetthedurabilityrequirementsforcladdingsasrequiredintheNZBCApprovedDocumentB2Durability.

    10.4.1 Resistance to moisture/rottingHardieFlexSheetsdemonstrateresistancetopermanentmoistureinduceddeterioration(rotting)andhaspassedthefollowingtestsinaccordancewithAS/NZS2908.2:

    WaterPermeability(Clause8.2.2) WarmWater(Clause8.2.4) HeatRain(Clause6.5) SoakDry(Clause8.2.5)

    10.4.2 Resistance to fireHardieFlexSheetisclassifiedasNon-CombustibleMaterialwhichissuitableforuseasexternalcladdingandcomplieswiththeprovisionsofClauseCProtectionFromFirecompliancedocumentofNZBC.

    10.4.3 Alpine regionsInregionssubjecttofreeze/thawconditions,HardieFlexSheetmustnotbeindirectcontactwithsnoworicebuildupforextendedperiods,e.g.externalwallsinalpineregionsmustbeprotectedwheresnowdriftsoverwinterisexpected.

    TheHardieFlexSheethasbeentestedinaccordancewithAS/NZS2908.2Clause8.2.3.

    9 Maintenance

    ItistheresponsibilityofthespecifiertodeterminenormalmaintenancerequiredtocomplywiththeNZBCAcceptableSolutionB2/AS1.Theextentandnatureofmaintenancewilldependonthegeographicallocationandexposureofthebuilding.Asaguide,itisrecommendedthatbasicnormalmaintenancetasksshallincludebutnotbelimitedto:

    Washingdownexteriorsurfacesevery6-12months* Re-applyingofexteriorprotectivefinishesifnecessary** Maintainingtheexteriorenvelopeandconnectionsincludingjoints,penetrations,flashingsandsealantsthatmayprovideameansofmoistureentrybeyondtheexteriorcladding

    Cleaningoutgutters,blockedpipesandoverflowsasrequired Pruningbackvegetationthatisclosetoortouchingthebuilding.

    * Do not use a water blaster to wash down the cladding.** Refer to paint manufacturer for washing down and recoating requirements related to paint performance.

    10 Product information

    10.1 MANUFACTURING AND CLASSIFICATION

    HardieFlexSheetsareacellulosefibrereinforcedcementbuildingproduct.ThebasiccompositionisPortlandcement,groundsand,cellulosefibreandwater.ThesheetsareeasilyidentifiedbythenameHardieFlexprintedatregularintervalsonthebackfaceofsheet.

    HardieFlexSheetsaremanufacturedtoAS/NZS2908.2Cellulose-CementProductsPart2:FlatSheets(ISO8336FibreCementFlatSheets)standardsinNewZealand.JamesHardieNewZealandisanISO9001Telarccertifiedmanufacturer.HardieFlexSheetsareclassifiedTypeA,Category3inaccordancewithAS/NZS2908.2Cellulose-CementProducts.

    ForSafetyDataSheets(SDS)visitwww.jameshardie.co.nzorAskJamesHardieon0800808868.

    10.2 PRODUCT MASS HardieFlexSheetsaremanufacturedintwothickness.The6.0mmthicksheethasaMassof8.6kg/m2atEMCandthe7.5mmthicksheethasaMassof10.8kg/m2atEMC.

    HardieFlexSheetsaredefinedasaLightWeightWallCladding(notexceeding30kg/m2)asperNZS3604.

  • 8 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 9

    11 Safe working practices

    WARNING DO NOT BREATHE DUST AND CUT ONLY IN WELL VENTILATED AREAJamesHardieproductscontainsand,asourceofrespirablecrystallinesilicawhichisconsideredbysomeinternationalauthoritiestobeacauseofcancerfromsomeoccupationalsources.Breathingexcessiveamountsofrespirablesilicadustcanalsocauseadisablingandpotentiallyfatallungdiseasecalledsilicosis,andhasbeenlinkedwithotherdiseases.Somestudiessuggestsmokingmayincreasetheserisks.Duringinstallationorhandling:(1)workinoutdoorareaswithampleventilation;(2)minimisedustwhencuttingbyusingeitherScoreandSnapknife,fibrecementshearsor,wherenotfeasible,useaHardieBladeSawBladeanddust-reducingcircularsawattachedtoaHEPAvacuum;(3)warnothersintheimmediateareatoavoidbreathingdust;(4)wearaproperly-fitted,approveddustmaskorrespirator(e.g.P1orP2)inaccordancewithapplicablegovernmentregulationsandmanufacturerinstructionstofurtherlimitrespirablesilicaexposures.Duringclean-up,useHEPAvacuumsorwetcleanupmethods-neverdrysweep.Forfurtherinformation,refertoourinstallationinstructionsandSafetyDataSheetsavailableatwww.jameshardie.co.nz.

    FAILURE TO ADHERE TO OUR WARNINGS, SAFETY DATA SHEETS, AND INSTALLATION INSTRUCTIONS MAY LEAD TO SERIOUS PERSONAL INJURY OR DEATH.

    James Hardie recommended safe working practices

    CUTTING OUTDOORS

    1.Positioncuttingstationsothatwindwillblowdustawayfromuserorothersinworkingarea.

    2.Useoneofthefollowingmethodsbasedontherequiredcuttingrate:

    BEST

    Scoreandsnap Handguillotine Fibreshear

    BETTER

    DustreducingcircularsawequippedwithHardieBladeSawBladeandHEPAvacuumextraction.

    GOOD

    DustreducingcircularsawequippedwithHardieBladeSawBlade

    CUTTINGINDOORS

    Cutonlyusingscoreandsnap,handguillotineorfibreshears(manual,electricorpneumatic).

    Positioncuttingstationinwell-ventilatedarea

    Drilling/othermachining

    WhendrillingormachiningyoushouldalwayswearaP1orP2dustmaskandwarnothersintheimmediatearea.

    IMPORTANTNOTES

    1.Formaximumprotection(lowestrespirabledustproduction),JamesHardierecommendsalwaysusingBest-levelcuttingmethodswherefeasible

    2.NEVERuseapowersawindoors3.NEVERuseacircularsawbladethatdoesnotcarrythe

    HardieBladelogo4.NEVERdrysweepUsewetsuppressionorHEPA

    Vacuum5.NEVERusegrinders6.ALWAYSfollowtoolmanufacturerssafetyrecommendations

    P1orP2respiratorscanbeusedinconjunctionwithabovecuttingpracticestofurtherreducedustexposures.Additionalexposureinformationisavailableatwww.jameshardie.co.nztohelpyoudeterminethemostappropriatecuttingmethodforyourjobrequirements.Ifconcernstillexistsaboutexposurelevelsoryoudonotcomplywiththeabovepractices,youshouldalwaysconsultaqualifiedindustrialhygienistorcontactJamesHardieforfurtherinformation.

  • 10 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Working instructionsRefertorecommendedSafeWorkingPracticesbeforestartinganycuttingormachiningofproduct.

    Score and SnapScoreandSnapisafastandefficientmethodofcuttingtheproductusingspecialtungstentippedScoreandSnapknife.

    Preferablyscoreonthefacesideoftheproduct.Scoreagainstastraightedgeandrepeattheactiontoobtainadequatedepthforcleanbreaknormally1/3ofsheetthickness.Snapupwardstoachievebreak.Smoothanyroughedgeswitharasp.

    Hand GuillotineMakeguillotinecutontheoff-cutsideoflinetoallowforthethicknessoftheblade.

    Fibreshear Heavy Duty Anelectricallypowered,fast,cleanandeffortlesswayofcuttingJamesHardiebuildingproducts,especiallyaroundcurvessuchasarchways.MakeFibreshearcutontheoff-cutsideofthelinetoallowforthethicknessoftheshear.

    HardieBlade Saw BladeTheHardieBladeSawBladeusedwithadust-reducingsawandHEPAvacuumextractionallowsforfast,cleancuttingofJamesHardiefibrecementproducts.Adust-reducingsawusesadustdeflectororadustcollectorconnectedtoavacuumsystem.Whensawing,clampastraight-edgetothesheetasaguideandrunthesawbaseplatealongthestraightedgewhenmakingthecut.

    Hole FormingFor smooth clean cut circular holes: Markthecentreoftheholeonthesheet. Pre-drillapilothole. Usingthepilotholeasaguide,cuttheholetotheappropriatediameterwithaholesawfittedtoaheavydutyelectricdrill.

    For irregular holes: Smallrectangularorcircularholescanbecutbydrillingaseriesofsmallholesaroundtheperimeteroftheholethentappingoutthewastepiecefromthesheetface.

    Tapcarefullytoavoiddamagetosheets,ensuringthatthesheetedgesareproperlysupported.

    Storage and handlingAllJamesHardiebuildingproductsshouldbestoredtoavoiddamage,withedgesandcornersofthesheetsprotectedfromchipping.JamesHardiebuildingproductsmustbeinstalledinadrystateandbeprotectedfromrainduringtransportandstorage.Theproductmustbelaidflatundercoveronasmoothlevelsurfaceclearofthegroundtoavoidexposuretowaterormoisture,etc.

    QualityJamesHardieconductsstringentqualitycheckstoensurethatanyproductmanufacturedfallswithinourqualityspectrum.Itistheresponsibilityofthebuildertoensurethattheproductmeetsaestheticrequirementsbeforeinstallation.JamesHardiewillnotberesponsibleforrectifyingobviousaestheticsurfacevariationsfollowinginstallation.

  • 10 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 11

    Accessories/tools supplied by James Hardie

    6mm HardieFlex Sheet

    Accessory Code Size (mm) Material/appearance

    6mmCappingMould 2400 3000

    300539300540

    2400long3000long

    uPVC/Bonecolour

    6mmHorizontalFlashing 302254 3000long uPVC/Bonecolour

    6mmHardiejointer 2400 3000

    300730300734

    2400long3000long uPVC/Bonecolour

    6mm and 7.5mm HardieFlex Sheets

    Accessory Code Size (mm) Material/appearance

    VentStrip 302490 3000long uPVC

    HorizontalFlashingJointer 301921 100long uPVC/Bonecolour

    6mmHorizontalFlashing 302254 3000long uPVC/Bonecolour

    6mmHardiejointer 2400 3000

    300730300734

    2400long3000long

    uPVC/Bonecolour

    CornerFlashingJointer301920 50x50 uPVC/Bonecolour

    Inseal32591.5mmthick 50mm 80mm

    300767300769

    50mroll50mroll

    BlackCompressibleFoam

    HardieFlexNail-5kg

    30278260x3.15mmx6.8mmheadsize 316StainlessSteel

    HardieFlexNail-5kg 302784

    60x3.15mmx6.8mmheadsize HotDipGalvanised

    HardieBladeSawBlade 300660 4tooth184mm DiamondTipped

    CornerUnderflashing50mmx50mm

    303745 3000long uPVC/Bonecolour

    2pieceInternalCorner 305756 3000long uPVC/Bonecolour

    2pieceExternalCorner 305755 3000long uPVC/Bonecolour

    12 Accessories

  • 12 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Accessories not supplied by James Hardie

    JamesHardierecommendsthefollowingproductsforuseinconjunctionwithitsHardieFlexSheets.JamesHardiedoesnotsupplytheseproducts.Pleasecontactcomponentmanufacturerforinformationontheirwarrantiesandfurtherinformationontheirproducts.

    Accessory Size (mm) Material/appearance

    HardieFlexnail/FibreCementnail 40x2.8mm 316StainlessSteel

    HardieFlexnail/FibreCementnail 40x2.8mm HotDipGalvanised

    HardieFlexnail/FibreCementnail 60x3.15mm 316StainlessSteel

    HardieFlexnail/FibreCementnail 60x3.15mm HotDipGalvanised

    SikaflexAT-Facadeorsimilar Tube

    PEFrodSikaBoomorsimilar

    Polyethylenefoam

    FlashingtapeTyvek,Protectowraporsimilar

    Proprietarytapetoadheretobuildingunderlay

    Inseal3109SealingStrip 19mm x 10mm x 12m Black Compressible Foam

    FlashingtoTable20E2/AS1 ReferFigure13 Flashingfabricator

    ScoringKnife TungstenCarbide

    Accessories/Tools supplied by James Hardie

    7.5mm HardieFlex Sheet

    Accessory Code Size (mm) Material/appearance

    7.5mmHardiejointer 2400 3000

    300731 300735

    2400long3000long

    uPVC/Bonecolour

    7.5mmCappingMould 300541 3000long uPVC/Bonecolour

    7.5mmHorizontalFlashing 302256 3000long uPVC/Bonecolour

  • 12 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 13

    13 Details

    VariousdetailsoutlinedinthefollowingtableareavailableonPages13to38.

    Table7Details

    Description Direct fixed Cavity construction

    Figure Page Figure Page

    Framing Figure1 14 Figure19 25

    SheetFixing Figure2 15 Figure21 27

    ConcreteFoundationDetail Figure3 16 Figure22 28

    VerticaluPVCJoint Figure4 16 Figure23 29

    TimberBattenJoint Figure5 17 Figure24 29

    VerticalSealantJoint Figure6 17 Figure25 29

    InternaluPVCCornerJoint Figure7 18 Figure26 30

    ExternaluPVCCornerJoint Figure8 18 Figure27 30

    InternalTimberBattenCorner Figure9 19 Figure28 31

    ExternalTimberBattenCorner Figure10 19 Figure29 31

    InternalSealantJointCorner Figure11 20 Figure30 32

    ExternalSealantJointCorner Figure12 20 Figure31 32

    HorizontalControlJoint Figure13 21 Figure33 34

    SoffitDetail Figure14 22 Figure32 33

    hMouldJointer Figure15 22

    WindowSill Figure16 23 Figure35 35

    WindowHead Figure17 24 Figure36 36

    WindowJamb Figure18 24 Figure37 36

    CavityBattenFixing Figure20 26

    CornertohMouldJoint Figure34 35

    OnePieceApronFlashingJoint Figure38 37

    ParapetFlashing Figure39 37

    PipePenetration Figure40 38

  • 14 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure1:Directfixframing

  • 14 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 15

    Figure2:Directfixsheetfixing

  • 16 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure3:Directfixconcretefoundationdetail

    Figure4:DirectfixverticaluPVCjoint

  • 16 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 17

    Figure5:Directfixverticaltimberbattenjoint

    Figure6:Directfixverticalsealantjoint

  • 18 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure7:DirectfixinternaluPVCcornerjoint

    Figure8:DirectfixexternaluPVCcornerjoint

  • 18 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 19

    Figure9:Directfixinternaltimberbattencorner

    Figure10:Directfixexternaltimberbattencorner

  • 20 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure11:Directfixinternalsealantjointcorner

    Figure12:Directfixexternalsealantjointcorner

  • 20 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 21

    Figure13:Directfixhorizontalcontroljoint

  • 22 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure14:Directfixsoffitdetail

    Figure15:hmouldjointer

  • 22 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 23

    Figure16:Directfixwindowsill

  • 24 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure18:Directfixwindowjamb

    Figure17:Directfixwindowhead

  • 24 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 25

    Figure19:Cavityfixframing

  • 26 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure20:Cavitybattenfixing

  • 26 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 27

    Figure21:Cavitysheetfixing

  • 28 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure22:Cavityconcretefoundationdetail

  • 28 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 29

    Figure25:Cavityverticalsealantjoint

    Figure23:CavityverticaluPVCjoint

    Figure24:Cavityverticaltimberbattenjoint

  • 30 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure26:CavityinternaluPVCcornerjoint

    Figure27:CavityexternaluPVCcornerjoint

  • 30 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 31

    Figure28:Cavityinternaltimberbattencorner

    Figure29:Cavityexternaltimberbattencorner

  • 32 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure30:Cavityinternalsealantjointcorner

    Figure31:Cavityexternalsealantjointcorner

  • 32 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 33

    Figure32:Cavitysoffitdetail

  • 34 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure33:Cavityhorizontalcontroljoint

  • 34 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 35

    Figure35:Cavitywindowsill

    Figure34:Cavitycornertohmouldjoint

  • 36 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure37:Cavitywindowjamb

    Figure36:Cavitywindowhead

  • 36 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand 37

    Figure38:Cavityonepieceapronflashingjoint

    Figure39:Cavityparapetflashing

  • 38 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Figure40:Cavitypipepenetration

  • 38 James Hardie HardieFlex Sheet Technical Specification October 2013 New Zealand

    Product WarrantyOctober 2013JamesHardieNewZealand(JamesHardie)warrantsforaperiodof15yearsfromthedateofpurchasethattheHardieFlexSheet(theProduct),willbefreefromdefectsduetodefectivefactoryworkmanshipormaterialsand,subjecttocompliancewiththeconditionsbelow,willberesistanttocracking,rotting,fireanddamagefromtermiteattackstotheextentsetoutinJamesHardiesrelevantpublishedliteraturecurrentatthetimeofinstallation.JamesHardiewarrantsforaperiodof15yearsfromthedateofpurchasethattheaccessoriessuppliedbyJamesHardiewillbefreefromdefectsduetodefectivefactoryworkmanshipormaterials.

    NothinginthisdocumentshallexcludeormodifyanylegalrightsacustomermayhaveundertheConsumerGuaranteesActorotherwisewhichcannotbeexcludedormodifiedatlaw.

    CONDITIONS OF WARRANTY: Thewarrantyisstrictlysubjecttothefollowingconditions:

    a) JamesHardiewillnotbeliableforbreachofwarrantyunlesstheclaimantprovidesproofofpurchaseandmakesawrittenclaimeitherwithin30daysafterthedefectwouldhavebecomereasonablyapparentor,ifthedefectwasreasonablyapparentpriortoinstallation,thentheclaimmustbemadepriortoinstallation.

    b) Thiswarrantyisnottransferable.

    c) TheProductmustbeinstalledandmaintainedstrictlyinaccordancewiththerelevantJamesHardieliteraturecurrentatthetimeofinstallationandmustbeinstalledinconjunctionwiththecomponentsorproductsspecifiedintheliterature.Further,allotherproducts,includingcoatingandjointingsystems,appliedtoorusedinconjunctionwiththeProductmustbeappliedorinstalledandmaintainedstrictlyinaccordancewiththerelevantmanufacturersinstructionsandgoodtradepractice.

    d) TheprojectmustbedesignedandconstructedinstrictcompliancewithallrelevantprovisionsofthecurrentNewZealandBuildingCode(NZBC),regulationsandstandards.

    e) Theclaimantssoleremedyforbreachofwarrantyis(atJamesHardiesoption)thatJamesHardiewilleithersupplyreplacementproduct,rectifytheaffectedproductorpayforthecostofthereplacementorrectificationoftheaffectedproduct.

    f) JamesHardiewillnotbeliableforanylossesordamages(whetherdirectorindirect)includingpropertydamageorpersonalinjury,consequentialloss,economiclossorlossofprofits,arisingincontractornegligenceorhowsoeverarising.WithoutlimitingtheforegoingJamesHardiewillnotbeliableforanyclaims,damagesordefectsarisingfromorinanywayattributabletopoorworkmanship,poordesignordetailing,settlementorstructuralmovementand/ormovementofmaterialstowhichtheProductisattached,incorrectdesignofthestructure,actsofGodincludingbutnotlimitedtoearthquakes,cyclones,floodsorothersevereweatherconditionsorunusualclimaticconditions,efflorescenceorperformanceofpaint/coatingsappliedtotheProduct,normalwearandtear,growthofmould,mildew,fungi,bacteria,oranyorganismonanyProductsurfaceorProduct(whetherontheexposedorunexposedsurfaces).

    g) Allwarranties,conditions,liabilitiesandobligationsotherthanthosespecifiedinthiswarrantyareexcludedtothefullestextentallowedbylaw.

    h) Ifmeetingaclaimunderthiswarrantyinvolvesre-coatingofProducts,theremaybeslightcolourdifferencesbetweentheoriginalandreplacementProductsduetotheeffectsofweatheringandvariationsinmaterialsovertime.

    DISCLAIMER: TherecommendationsinJamesHardiesliteraturearebasedongoodbuildingpractice,butarenotanexhaustivestatementofallrelevantinformationandaresubjecttoconditions(c),(d),(f)and(g)above.JamesHardiehastestedtheperformanceoftheHardieFlexSheetwheninstalledinaccordancewiththeHardieFlexSheettechnicalspecification,inaccordancewiththestandardsandverificationmethodsrequiredbytheNZBCandthosetestresultsdemonstratetheproductcomplieswiththeperformancecriteriaestablishedbytheNZBC.However,asthesuccessfulperformanceoftherelevantsystemdependsonnumerousfactorsoutsidethecontrolofJamesHardie(e.g.qualityofworkmanshipanddesign)JamesHardieshallnotbeliablefortherecommendationsmadeinitsliteratureandtheperformanceoftherelevantsystem,includingitssuitabilityforanypurposeorabilitytosatisfytherelevantprovisionsoftheNZBC,regulationsandstandards,asitistheresponsibilityofthebuildingdesignertoensurethatthedetailsandrecommendationsprovidedintherelevantJamesHardieinstallationmanualaresuitablefortheintendedprojectandthatspecificdesignisconductedwhereappropriate.

    CopyrightOctober2013.JamesHardieNewZealand.TManddenotesaTrademarkorRegisteredMarkownedbyJamesHardieTechnologyLimited.

  • CopyrightOctober2013.JamesHardieNewZealand.TManddenotesaTrademarkorRegisteredMarkownedbyJamesHardieTechnologyLimited.