28
OPERATION AND MAINTENANCE MANUAL CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266 (NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0 LIST OF CONTENTS SECTION TITLE Special Emergency Instruction 1. Introduction 2. Systems Description & Operation A. Automatic Sprinkler System B. Fire Hose Reel System C. Portable Fire Extinguisher D. Fire Alarm System E. Fireman Intercom System F. CO2 Fire Extinguishing System 3. Systems Testing, Service & Maintenance A. Automatic Sprinkler System B. Fire Hose Reel System C. Portable Fire Extinguisher D. Fire Alarm System E. Fireman Intercom System F. CO2 Fire Extinguishing System 4 Equipment Catalogs 1

FPS O&M City Mall Version 1.0

Embed Size (px)

Citation preview

Page 1: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

LIST OF CONTENTS

SECTION TITLE

Special Emergency Instruction

1. Introduction

2. Systems Description & Operation

A. Automatic Sprinkler System

B. Fire Hose Reel System

C. Portable Fire Extinguisher

D. Fire Alarm System

E. Fireman Intercom System

F. CO2 Fire Extinguishing System

3. Systems Testing, Service & Maintenance

A. Automatic Sprinkler System

B. Fire Hose Reel System

C. Portable Fire Extinguisher

D. Fire Alarm System

E. Fireman Intercom System

F. CO2 Fire Extinguishing System

4 Equipment Catalogs

1

Page 2: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

SPECIAL: EMERGENCY INSTRUCTIONS

IN CASE OF FIRE

a) When the Fire Alarm bell rings, note the zone light “On”.

b) Locate the affected area from the Mimic Diagram.

c) Investigate the affected area.

d) Inform the duty officer who is in-charge.

e) Contact the Fire Brigade if necessary. Tel: 944

f) DO NOT switch off panel or reset the alarm bells before investigating the 'Fire' affected zone.

g) When situation is back to normal, refer to instruction manual housed in the cabinet for resetting system.

JIKA BERLAKU KEBAKARAN

a) Bila loceng kebakaran berbunyi, lihat lampu daerah mana yang bernyala.

b) Lihat bahagian manakah yang terlibat dari gambar.

c) Siasat bahagian tersebut.

d) Beritahu kepada `Pegawai' yang tertanggung-jawab.

e) Kalau keadaan memaksa beritahu kepada Bomba. Tel : 994

f) JANGAN tutupkan suis panel atau memulihkan system sebelum tamat siasatan.

2

Page 3: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Introduction

1. INTRODUCTION

The City Mall is protected with the following Fire Protection System.

1. Automatic Sprinkler System.

2. Fire Hose Reel System

3. Portable Fire Extinguisher.

4. Fire Alarm System.

5. Fireman Intercom System.

6. CO2 Fire Extinguishing System.

A. AUTOMATIC SPRINKLER SYSTEM

An Automatic Sprinkler installation is a device contrived for the detection and by the application of water,

extinguisher a fore in its initial stages. It is designed to carry out those functions automatically and its operation

simultaneously causes an alarm bell to sound.

The method of its application is by the action of the Sprinkler head inserted into the system of pipework fitted

throughout the building.

At normal temperatures, the sprinkler glass bulb contains the fluid in both liquid and gaseous phase. As heat is

applied, the liquid expands forcing it to push out against the bulb, causing the glass to shatter, opening the water way

and allowing the deflector to distribute the discharging water.

The necessary features of a satisfactory sprinkler head are briefly as follows :

i. The reliability of operation at its rated operating temperature.

ii. Complete and instantaneous release of the valve and operating parts.

iii. Provision of an even distribution of water over an adequate area.

iv. Simplicity and robustness.

B. FIRE HOSE REEL SYSTEM

Hose Reel provides one of the most effective non-automatic means of extinguishing a fire in its early stage or

containing a large fire pending the arrival of the the fire brigade. It is able to scope with larger fire than portable

extinguisher, and is simple and convenient to handle. The floor distance coverage using Hose Reel usually ranging

from 100 ft. The water pressure is 30 psi at which pressure of 30 ft. jet is produced. In principle, Hose Reel are

strategically located in a building. They are normally housed in cabinets with a graphic board symbol 'HOSE REEL'

conspicuously displayed.

C. PORTABLE EXTINGUISHERS INSTALLATION

Portable Fire Extinguishers is useful when initial Fire-Fighting is called. Various type of Fire Extinguishers are

available for different purposes. Among all Dry Powder extinguisher is commonly used as it is effective for class A

(carbonaceous), B (flammable liquid) and C (flammable gas ) fires. CO2 Fire Extinguishers are used to kill fires

involving flammable liquids and gases. It is non-conductive and therefore particularly effective against fires in

electrical plant and equipment.

3

Page 4: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Introduction

D. FIRE ALARM SYSTEM

This system mainly consists of detectors, control panel battery and charger. Audible and visual alarm and electrical

power supply which will automatically raise an alarm in the event of the fire, and simultaneously transmit an alarm

signal to the fire control station.

Generally the location of the breakglass manual call point together with 6" Alarm Bell are installed at the passage

way leading to lobby and corridor of the building. The Smoke Detectors are located in the lift lobby area, lift motor

room and air handling unit room. Heat Detectors are normally installed in places where Smoke Detectors are

discouraged e.g. Diesel Generator room and workshop.

An alarm can be activated in the following way:

1. The breaking of manual call point glass

2. The activation of Smoke Detectors or Heat Detectors or both by the presence of fumes smoke created by

combustion.

3. The activation of Heat Detectors due to the accumulation of predetermined heat level in the environment of

burning fires.

4. The activation of the sprinkler system flow Switch.

E. FIREMAN INTERCOM SYSTEM

This system consists of a Master Handset in the main panel control room which is linked to other remote handsets

located at every floor of the building. The purpose of this system is to enable the Fireman to communicate at

different floor level and control station while fighting a fire within the building.

F. CO2 FIRE EXTINGUISHING SYSTEM

CO2 (carbon dioxide) is an odourless and colourless gas. The particular characteristics of this gas make it the

cleanest fire extinguishing method known to date. Carbon dioxide is electrically non-conductive. It is neither caustic,

corrosive nor contaminating. It evaporates without any chemical influence and leaves no residues. The extinguishing

effect is based on the fact that the oxygen content of the air is reduced, thus, choking the fire. This system is installed

in the substation.

4

Page 5: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

3. SYSTEMS DESCRIPTION & OPERATION

A. AUTOMATIC SPRINKLER SYSTEM

This automatic sprinkler system is designed / installed in accordance with the Rules and Regulations of the Uniform

Building By-Laws 1976, Rules of the loss Prevention Council for Automatic Sprinkler Installation BS 5306 Part 2

1990 and subsequents and Jabatan Perkhidmatan Bomba Malaysia.

SPRINKLER PUMPSETS SCHEDULE

LocationPumpsets Pump Description Model Model/ Water Flow Rate

Fire Pump Room Electric (Duty) Pump: EBSRAY

Engine: TECO

STREAMLINE 80-20

OH3- 30M

Fire Pump Room Electric (Standby) Pump: EBSRAY

Engine: TECO

STREAMLINE 80-20

OH3- 30M

Fire Pump Room Electric (Jockey) Pump: EBARA

Motor: EBARA

CVM AM/12

10iGPM/150FT

SPRINKLER SYSTEM PRESSURES SWITCH SETTING

SPRINKLER PUMPSETS CUT-1N PRESSURE CUT-OUT PRESSURE

JOCKEY PUMP 65 psi 90 psi

DUTY PUMP 50 psi Manual

STANDBY PUMP 40 psi Manual

5

Page 6: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

SPRINKLER PUMP PANEL OPERATION MANUAL

1) Pump On "Auto"-AC/ Operated

a. Turn pump isolator to "ON" position,

b. Select AUTO/MANUAL switch to "AUTO” position.

c. Pump will operate when pressure drop below cut-in pressure.

d. Depress 'STOP' button to stop the pump.

2) Pump On 'Manual-AC/Operated

a. Turn pump isolator knob to 'ON' position.

b. Select AUTO/MANUAL switch to "MANUAL" position.

c. Push 'START' button to operate pump.

d. Push 'STOP' button to stop the pump.

SPRINKLER SYSTEM OPERATION MANUAL

1)Notice In Case Of Fire

a. When sprinkler alarm gong rings check all sprinkler heads.

b. Locate the area affected.

c. Investigate the affected area.

d. Contact the Fire Brigade if necessary.

e. Inform the duty officer-in-charge.

f. Do not switch off the sprinkler Control Panel before investigation.

g. Do not close any valve.

h. When situation is back to normal refer to the instruction in Schedule of outline or Preventive

Service and Maintenance Manual and Pump Operation Manual.

2)Notice After A Fire

a. Ensure that the fire is completely extinguished before closing main stop valve.

b. Open drain valve to drain away remaining water in the pipework.

c. Replace affected sprinkler heads with the same type and temperature rating.

d. Open main stop valve and drain valve.

e. Start the pump via start-push button on the pump starter panel.

f. Pressure will again rise in the system and when the test gauge shows a steady maximum reading.

g. Switch the AUTO/MANUAL SWITCH TO "AUTO" position.

6

Page 7: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

B. FIRE HOSE REEL SYSTEM

This system has been installed, tested and commissioned according to the specification of the Local Fire Authorities.

The Hose Reel system covers the whole building and is installed along the sideway of the building.

This system comprises of the following:

a) Two sets of electric pumpsets.

b) Hose Reel.

c) Shut-off Nozzle

1. HOSE REEL

The Hose Reel is of the swing type. Each Reel is complete with 1" x 50 ft. long non-link rubber hose. The

Hose Reel is finished in black colour which can be easily identified.

2. SHUT-OFF NOZZLE

The shut-off nozzle assembly is constructed from a non-corrosive resistant material conforming to BS336.

3. SYSTEM OPERATION

Opening of any of the Hose Reel nozzle results in a pressure drop in the system. This, in turn, starts the

electric duty pumpset. Should the duty pumpset fails to start, a further pressure drop will operate the

standby pumpset.

Care should be taken to ensure that no Hose Reel can be permitted to be operated for any other purposes. Should the

Hose Reel be used freely, the duty electric pumpset will start and stop frequently thereby increasing maintenance

costs, not to mention the frequent false alarms.

HOSEREEL PUMPSETS SCHEDULE

Location Pump Description Model Water Flow Rate

Fire Pump Room Electric (Duty) Pump: EBARA

Engine: MARELLI

30IGPM

Fire Pump Room Electric (Standby) Pump: EBARA

Engine: MARELLI

30IGPM

HOSEREEL SYSTEM PRESSURES SWITCH SETTING

HOSEREEL PUMPSETS CUT-IN PRESSURE CUT-OUT PRESSURE

DUTY PUMP 70 psi 90 psi

STANDBY PUMP 50 psi 70 psi

7

Page 8: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

Generally, the hose reel serves as an initial general fire fighting aid. In order for the user to operate the system

efficiently, the following instructions should be followed :

a. Turn on stop valve to release nozzle.

b. Run out hose.

c. Turn on water at nozzle.

d. Hose Reel should be fully charged with water before winding it into the Drum.

OPERATION OF HOSE REEL STARTER PANEL

GENERAL INFORMATION

The basic function of the Fire Pump Starter Panel for electric motor driven fire pumpsets is to automatically start &

run the motor upon a drop in pressure in the water line.

When water pressure drops below a level which is preset on the internal pressure switch. the pressure switch will

open. The preset pressure switch will trigger the starter panel to start the duty pumpset. Should the duty pumpset

fails to start, a further pressure drop will operate the standby pump. At any time, only one pumpset shall operate. To

stop the pumpset, place the selector switch to 'OFF' position and press the red button 'STOP'. Therefore, the selector

switch must always be restored to 'AUTO' position.

FUNCTION

Equipment is provided in the starter panel to provide the following functions.

AUTOMATIC STARTING FROM Drop in water line pressure.

CONTROL SWITCH A (3) THREE position switch is provided marked 'AUTO—OFF-

MANUAL', to enable motor selection.

DUTY HOSE REEL PUMP

'AUTO OPERATION'

Select A-O-M selector switch to 'AUTO' position. When the pressure in the

water pipelines drops to the preset pressure, the pressure switch will cut in

and the pump will run for a preset time. After the preset time (0-60 sec) if

the pressure increases, the pressure switch will cut off and pump will stop.

DUTY HOSE REEL PUMP

`MANUAL OPERATION'

Select A-0-M selector switch to 'MANUAL' position. Depress the start push

button, the run light will switch on and pump will run. Depress the stop

push button, the pump will stop. During operation, if the pump is

overloaded, the thermal overload relay will trip and the pump will stop. The

trip light will then switch on.

STANDBY HOSE REEL PUMP

'AUTO OPERATION'

Same as Duty Hose Reel Pumpset.

STANDBY HOSE REEL PUMP

'MANUAL OPERATION'

Same as Duty Hose Reel Pumpset.

Note : The standby Hose Reel pump will operate automatically only when the duty pump is 'OFF' or fail to start.

8

Page 9: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

C) PORTABLE FIRE EXTINGUISHERS INSTALLATION

a) ABC Dry Powder Extinguisher

This extinguisher is free flowing powder with a composition based on ammonium phosphate and

ammonium sulphates with special additive to improve fluidity and storage.

When discharge, the heat from the fire is greatly reduced. Firstly, because a cloud of powder provides an

effective heat-shield. Secondly, there is an immediately knockdown of the flames. Hence, the flames are

suffocated and any embers are extinguished by a layer of melted powder.

b) CO2 Dry Powder Extinguisher

Carbon Dioxide gas is an efficient Fire Extinguishing agent which offers unique properties to user. The

colourless and odourless gas is heavier than air and works by smothering the flames and reducing the

oxygen content of the air around the fire.

Carbon Dioxide is the ideal agent for use on Class B (flammable liquids) and Class C (flammable gas) fire.

It is non-conductive and therefore particularly effective against fires in electrical plant and equipment.

Carbon Dioxide Extinguisher are used throughout industry as a protection against complex industrial fires

where dangerous chemicals and gases are involved. Carbon Dioxide does not deteriorate with storage or

freeze in the container.

After use carbon dioxide disperses without leaving any contamination or corrosive residue but if used in a

confined area normal ventilation procedure should be followed.

D) FIRE ALARM SYSTEM

Statistic proves that more and more fire are being detected too late for the fire fighting action to be innate in

time. It is the function of the fire alarm system to detect a fire, if possible in its incipient stage and

automatically alert an emergency service to isolate the source of a fire by means of fire protection and local

extinguishing facility.

Quick and reliable automatic alerting depends on the detection element of the automatic fire detectors. To

ensure the proper functioning of fire detectors, the response criterion must be based on the expected

characteristic of an incipient fire.

a) Alarm and Detector

The installation of alarms and detectors-alarm bells of 6" Ø size and operated on 24V DC supply is

such that the system can be actuated by either automatic means or manual means. For automatic actuation,

breakglass or smashing glass callpoint are included. The alarm bell is an audible device which sound in the

event of a fire.

b) Manual Call Point (Breakglass)

'Breakglass' is a device in which a piece of glass needs to be broken or smashed before an alarm can be

initiated in the event of a fire.

9

Page 10: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

(E) FIREMAN INTERCOMMUNICATION SYSTEM MAINTENANCE

Minimum Maintenance required. It is a closed supervisory type of system. Therefore, whenever fault occurred

automatic self detection will sound the buzzer with light indication.

F) CO2 FIRE EXTINGUISHING SYSTEM

The Genset Room, MSB Room, Transformer Room & Switchgear Room are protected with CO2 Extinguishing

System.

CO2 (carbon dioxide) is an odourless and colourless gas. The particular characteristics of this gas make it the

cleanest fire extinguishing method known to date. Carbon dioxide is electrically non-conductive. It is neither caustic,

corrosive nor contaminating. It evaporates without any chemical influence and leaves no residues. The extinguishing

effect is based on the fact that the oxygen content of the air is reduced, thus choking the fire. The liquified gas is

stored in high pressure gas cylinder. This cylinder is equipped with an electrical Solenoid actuator control from CO2

control panel. This actuator open the cylinder valve and the CO2 is discharge into the common manifold as well as

into the control piping from which the desired number of follow-up cylinders are pneumatically opened. The CO2

nozzles are open at all times.

10

Page 11: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

INSTRUCTION MANUAL FOR AUTOMATIC CO2 PROTECTION SYSTEM

A. DESIGN SPECIFICATION

1. The installation is designed for extinguishing of fire involving electrical / electronic equipment

hazards and complied to the requirements of Malaysian Fire Protection Association.

2. The quantity of extinguishing agent is carefully predetermined to ensure the fastest possible

extinction of any fire in the protected area.

3. The protected area is provided with normally 50% @ 70 °F concentration of agent in the space of

protected area.

4. Normally a time delay of 25-30 seconds is set for discharge of gas after both two detector zones

receive alarm.

5. The system comprises the following features : -

a) CO2 containers charged with the required quantity of gas.

b) Automatic electric solenoid actuator, manual keyswitch box and manual pull box.

c) Automatic detectors, Alarm bells, Flashing lights & by pass switch.

d) CO2 control panel with 24V Dry Cell batteries and charger.

e) Discharge nozzles, piping and conduit wiring.

f) Discharge warning signboard.

6. The system is installed with 2.27 KG pilot cylinder used to activate all the slave cylinder when the

pilot cylinder is actuated.

B. SYSTEM OPERATION

The installation is operated from automatic mode using smoke/heat detectors under dual mode operation

and manual mode using electric keyswitch. The system is operated by an input voltage of 240V AC 50Hz

supplied to a power charger module within the panel. The AC voltage is transformed and rectified to 24V

DC. A set of Dry Cell batteries is provided as secondary supply in case of AC failure. These batteries will

automatically and instantaneously be switched into use as soon as the mains supply fails. Such a failure is

shown both visually and audibly at the panel. The batteries is trickled charged during normal operating

conditions. The hazard area is protected by two detectors i.e. one smoke and one heat detector. When one of

these detectors receive an alarm condition, a visual and audible warning bell will be given at the control

panel. In order to discharge the extinguishing agent automatically, both detectors must receive alarm

condition. This mode of operation is called 'Double Knock' system with a time delay of 30 seconds preset in

the control panel to discharge the extinguishing agent. This obviates the possibility of false discharge due to

one detector operating.

The facility to discharge the CO2 agent manually is also been provided via manual keyswitch. Also, in the

event of total failure of the control panel, the CO2 agent can still be discharged through mechanical manual

pull station by double action breakglass and follow by pulling the level. The detectors are continuously

supervised by zone supervisory module of the panel for line fault. Any break of wires, the module will both

visually and audibly inform by a fault lamp and buzzer.

11

Page 12: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

C. SYSTEM CONTROL PANEL

The CO2 control panel is located normally beside the hazard area is complete with the following facilities: -

a) Alarm zoning facility

b) Master reset switch

c) Facilities for test alarm and test fault

d) Voltmeter and Ammeter to provide visual condition on batteries.

e) Lamp test and battery test facility

f) 'AC ON', 'DC ON' and 'CHARGER ON' indicator

g) Audible and visual fault alarm

h) Audible and visual isolation switch

i) Alarm, fault and isolation indicator

j) Audible and visual 'AC FAIL', 'BATTERY FAIL' and 'CHARGER FAIL' warning by buzzer and

indicator

k) CO2 DISCHARGE' indicator is also provide

l) 'C02 ISOLATE', 'BELL ISOLATE' and 'BUZZER ISOLATE' facility

m) Remote indication to fire alarm panel include CO2 discharge and 'AC FAIL' indication

n) Audible alarm bell warning

The audible warning and indicators are used to indicate the operations and conditions of the system. The

alarm is provided to give a warning of a discharge or pending to discharge of extinguishing agent where a

hazard to personnel may exist.

The audible buzzer indicating, failure of supervised devices or equipment are provided with prompt and

indication of any failure to warn the personnel that the system is not in proper and require immediate

rectification.

D. ATTENDING FIRE ALARM

In case of fire alarm, quickly evacuate hazard area and close the doors. The CO2 gas can be released by

smashing the glass of manual keyswitch and to turn it in clockwise position. In case of false alarm or minor

fire hazards, which can be easily extinguished by using portable lire extinguisher, quickly run to CO2

control panel and switch the C02 isolate switch to 'Isolate CO2' so as to prevent the CO2 from discharging,.

E. RESET FIRE ALARM

1. Ventilate the affected area to disperse all smoke or heat that would reinitiate the fire alarm system.

2. Replace the broken glass of manual keyswitch.

3. Depress the master reset switch.

12

Page 13: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

F. FUNCTION OF CO2 PANEL

MAINS ON When the “MAINS ON” switch is on, the LED indicator will light.

“CHARGER ON” and “DC ON” will also on.

DC ON This indicator is on all the time whenever there is supply (either AC or Battery

Supply).

ALARM

RESET

The “ALARM RESET” push-button switch is incorporated for

resetting the alarm condition and set the system back to normal.

BATTERY

FAIL

“BATTERY FAIL” indicator will light and the buzzer sounds when

the battery fuse is removed or in fuse condition.

TEST LED To check that all the LED's are good, switch on the “TEST LED” switch and all

the LED's will light and buzzer sounds restore switch back to normal.

CHARGER

FAIL

“CHARGER FAIL” indicator will light and the buzzer sounds when there is no

AC supply.

MAINS FAIL “MAINS FAIL” indicator will light and the buzzer sounds when either one of

the following conditions exists :(i) The AC Supply is switched off, (ii) AC Fuse

has been removed or in fused condition.

BUZZER

SILENCE

When the Bell switch inside the CO2 panel is switched to “OFF” position, the

“BUZZER SILENCE” green indicator will light, indicating that the buzzer has

been cut-off.

BELL

SILENCE

When the Bell Silence switch inside the CO2 panel is switched to “OFF”

position, the “BELL SILENCE” green indicator will light and the buzzer

sounds. All the bells will not sound. This allow test alarm to carry out without

causing any inconvenience to the public.

BELL LINE

OPEN

When the bell is removed or disconnected, "BELL LINE OPEN" indicator will

light and the buzzer sound.

VOLTAGE The Voltmeter will indicate the system's voltage, it should be 25V.

CURRENT The Ammeter will indicate the system's current consumption.

13

Page 14: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

ZONE INDICATIONS AND CONTROL

ALARM When alarm signal from sensors is received, the two red LED alarm light for

that particular zone will flash. Further alarm signal for the adjacent zone will

cause the adjacent zone indicator to flash again. Since the signal is latched, the

indication will remain until the signal is cleared and the panel “RESET”.

FAULT When the external zone detector wiring is open or the end-of-line resistor is

removed, this yellow indicator will light and buzzer sounds. The “Fault”

indicator will automatically clear when the fault condition is cleared.

ISOLATE This green indicator will light and buzzer sounds when the rotary switch is set to

“ISOLATE” (ISO) position. This will cause the flashing “ALARM” indicator to

become steady and the bells to stop ringing.

T/F (TEST

FAULT)

When the rotary switch is set to “FAULT” (T/F) position, it simulated an open

circuit on the detected line. The yellow “FAULT” indicator of that particular

zone will light and buzzer sound. The “FAULT” will automatically clear when

the rotary switch is turn to “NORMAL” (NOR) position.

T/A (TEST

ALARM)

Alarm condition can be tested from the panel by turning the rotary switch to

“ALARM” position. That particular zone's ALARM indicator will flash and it

will remain flashing until the rotary switch turns back to “NORMAL” (NOR)

position and depressing the “MASTER RESET” switch once. Be careful, by

activating two zones simultaneously, will cause the system to activate &

discharge of CO2 agent.

Note:

● Under normal condition, the “Bell Silence” and “Buzzer Silence” switches outside the CO2 panel should

not be “OFF”.

● When doing Test Alarm, always isolate the CO2 Gas or disconnect Electrical Actuator wire at the CO2

panel. This is to avoid accidentally discharging the gas.

14

Page 15: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Description &Operation

SPECIFICATION

AC INPUT VOLTAGE 230v +/-10% 50Hz Single Phase

STANDBY BATTERY 24V DC Rechargeable Type

CHARGER OUTPUT

VOLTAGE

28V DC (with short circuit protection)

SYSTEM VOLTAGE 25V DC (with short circuit protection)

END-OF-LINE

RESISTOR

22 K Ohm

OUTPUT TO BELL 24V DC

TRIPPING OUTPUT

(EG. EXHAUST FAN

TRIP)

24V DC

CURTAIN TRIP Zone 1 & Zone 2 Alarm, 24V DC will be sent to trip the curtain.

BELL INTERMITTENT Zone 1 alarm, bell intermittent ringing.

Zone 2 alarm, bell intermittent ringing.

Zone 1 & 2 alarm, bell ringing continuously.

NUMBER OF SENSOR

PER ZONE

An indefinite number of sensors can be connected to any one zone

of the Fire Alarm System. Sensors must be opened and provide a

short circuit contact on alarm condition.

CO2 DISCHARGE

OUTPUT

24V DC when actuated.

DETECTOR LINE Two terminals are provided for each zone. At the last detector of

each zone and end-of-line resistor of 22 K is connected.

MASTER BELL This is the output of Master Bell. An end-of-line resistor of 4.7K is

connected at the bell.

RED & GREEN This is the 24V output to the external red (Alarm) and green

(Normal) indicating light.

CO2 DISCHARGE This is the 24V output to discharge the CO2 gas.

MASTER PANEL Voltage free contact signal to the Master Panel.

A.C FAIL Voltage free contact signal to the Master Panel.

EXHAUST FAN This is the 24V output to trip the exhaust fan. (External 24VDC

relay has to be install by others in the fan Control Panel).

CAUTION (A) Do not attempt to adjust the variable resistor on the printed

circuit board as they are factory calibrated.

(B) When inserting the printed circuit boards, make sure that they

are plugged in properly in the correct place.

15

Page 16: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

3. SYSTEMS TESTING, SERVICE & MAINTENANCE

A. AUTOMATIC SPRINKLER SYSTEM

This automatic sprinkler system is designed / installed in accordance with the Rules and Regulations of the Uniform

Building By-Laws 1976, Rules of the loss Prevention Council for Automatic Sprinkler Installation BS 5306 Part 2

1990 and subsequents and Jabatan Perkhidmatan Bomba Malaysia.

SYSTEM OPERATION AND CONTROL

This automatic sprinkler system is using a deluge system with wet pilot actuation utilizes the deluge valve in

conjunction with open sprinkler nozzles. The system piping contains no water under normal conditions. Water is

held back by the deluge valve. With "wet pilot” actuation, a network of ½” or ¾" piping with closed ½" orifice

sprinklers is spaced throughout the area of coverage. This "pilot" piping is under water pressure and is connected to

the "wet pilot" (basic) trim of the deluge valve. When the "wet pilot” piping is pressurized / filled with water, the

diaphragm chamber of the deluge valve is also pressurized. This pressure in the diaphragm chamber is exerted to a

piston which forces the clapper lever against the clapper, holding it closed. When a fire activates a pilot sprinkler

detector, water pressure is released through the pilot sprinkler faster than it can be restored due to the restricted

orifice located at the inlet of the diaphragm chamber. This drop in pressure in the diaphragm chamber releases the

lever, allowing the valve to trip. Water enters the system piping and discharges from all of the sprinklers.

It is possible to isolate the sprinkler system via the insolation Rate value.

16

Page 17: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

SCHEDULE OF ROUTINE OR PREVENTIVE SERVICE AND MAINTENANCE

Item Description Service Interval

1. Sprinkler

a. Check the sprinkler heads and sprinkler spanner are on hand. Every 6 months

2. Piping

a. Check and clean strainers Every 6 months

b. Check to ensure that supply non-return valve are correctly sealed Every 3 months

c. Check all drain pipes Every 3 months

d. To inspect the turbine motor & clean the filter or the water motor gong Every 6 months

e. To check the jet is not blocked & remove any sediment present in the Chamber Every 6 months

f. Check for the correct operation of external alarm motor & gong Every month

g. Check and oil the alarm water motor & gong Every 6 months

h. Examine all pipework and sprinklers in corrosive atmosphere & clean, repaint and

replace as required

Every 3 years

i. Flush all system pipework Every 3 years

j. Check all stop valve glands for leaks & tighten or replace packing Every month

k. Overhaul stop, alarm, back-pressure valve. Replace all damage parts if necessary Every 3 years

l. Check all stop valve secured open or closed position as appropriate Every month

m. Check all stop valve working freely Every 3 years

n. Check all alarm and back pressure valve Every 3 years

3. Pumps

a. Check pump glands for leakage Every month

b. Check pump & motor breakings for excessive noise, wear & temperature

c. Check lubrication & alignment

d. The electric pump shall be under full load conditions & the load current per phase

checked for variation from original test readings

Every month

e. Testing of pumps & installation valves as per requirement Every month

17

Page 18: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

Item Description Service Interval

4. Automatic Control

a. Check & test control wiring Every 12 months

b. Check correct operation of the pressure switch Every month

c. Check electric pump starter operation to ensure that the starting sequence is

completed & the pump fully operational within 30 seconds

Every 12 months

d. The internal mechanism of all pressure switches i.e. mercury switched. Contact

assemblies shall be physically checked to ensure that all components are free of

corrosion securely mounted & in working conditions

Every 3 years

5. Electrical

a. Check all change-over switches Every month

b. Check operation of all selector switches & all automatic devices & adjust

accordingly

Every month

c. Check wiring connection to pump control panel and that fire line is adequately

supported & in good condition

Every month

d. Check circuit breaker and/or fuses protecting pump motor circuits, to ensure that

this equipment is of the correct type & rating as originally installed

Every month

e. Circuit below the alarm switch and control circuit Every month

f. With electrical equipment isolated from all supplies, the motor starter should be

cleaned & the condition of all heavy current-carrying contacts checked. Any item

showing signs of wear or corrosion shall be immediately repaired or replaced.

Every 12 months

g. Check all bulbs meters and switches on the panel Every month

18

Page 19: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

ELECTRIC MOTOR SERVICING

A - replace supply conductor by one of larger cross-section.

B – extend breaks in motor operation, or reduce the number of actuations.

C – connect the motor correctly.

D – detect and remove the break.

E – detect and remove short-circuit in widings, re-wind the motor.

F – detect and remove the mechanical damage.

G – detect and remove the Inter-turn short-circuit or the short-circuit to casing (if any).

H - set the overload thermal release correctly.

I - inspect the bearings and replace, if required.

J - make a new and coupled.

K - replace the bearings.

L - correct the foundation and correct the motor positioning.

M - remove excess of grease.

N - clean the motor up.

P — reduce load or select adequate starter.

Q - rings to be cleaned, re-turned, re-grounded.

19

Page 20: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

B. FIRE HOSE REEL SYSTEM

VISUAL INSPECTION

1. Check all hoses fully charged with water-monthly.

2. Check swivel joint of drum of leakage and ease of movement-monthly

3. Check all stop valves in fully 'open'-weekly.

4. Check for air lock in the system and rectify accordingly.

TESTING PROCEDURES

The Hose Reel system is pressurized by means of pumpsets. Opening of the Hose Reel nozzle result in a

pressure drop in the system. This in turn starts the electric Pumpset.

In order for the user to operate the system efficiently, the following step must be followed:

1. Turn on stop valve to release nozzle.

2. Run out hose.

3. Turn on water at nozzle.

4. Hose should be fully charged with water before it into the Drum.

Each Hose Reel has a minimum flow rate of 6 igpm at 13 psi. Normally 2 sets of Hose Reel are tested at

one time for this specified duty.

A test valve is connected to each of the Hose Reel system in the pump room. Testing of pumpset operation

sequences can be carried out as follow:

1. Operating the test valve slowly and note the system pressure drops.

2. Check the electric Pumpset cut in pressure against the pressure switch setting.

3. Drop the system pressure further until Pumpset cut in.

4. Check the standby Pumpset cut in pressure against the pressure switch setting.

5. Check cut out pressure by closing the test valve while duty or standby pumpset is running.

At any time, only one pumpset shall operate. To stop the pumpset. place the selector switch to "OFF"

position and then press the red button "STOP'. Thereafter the selector switch must always be restored to

'AUTO' position.

20

Page 21: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

C. PORTABLE EXTINGUISHERS

The purpose of well planned and well executed maintenance program is to enable the maximum probability

of an extinguisher.

a)Properly operate between the time intervals established for maintenance examination in the environment

to which it is exposed.

b)Will not constitute a potential hazard to person in its vicinity or to operate or recharge extinguisher.

Frequency of extinguisher inspection should be on the need of the area in which extinguishers are located.

The monthly inspection should be more frequent if any of the following exists:-

1. High frequency of fire in the past.

2. Severe hazards.

3. Susceptibility to tampering, vandalism or malicious mischief.

4. Possibility of or experience with, theft of extinguisher.

5. Possibility of visible or physical obstructions.

6. Exposure to abnormal temperature or corrosive atmosphere.

7. Characteristics of extinguisher, such as susceptibility to leakage.

INSPECTION PROCEDURE

1. The extinguisher shall be in its designated place.

2. The operation instruction on the extinguisher nameplate should be legible and face outwards.

3. Any seal or tamper indicator, that were broken or missing should be replaced.

4. Any obvious physical damage, corrosion leakage or clogged nozzle should be noted.

5. When an inspection reveals that tampering has occurred or that it has damaged, leaked over or

under charged obvious corrosion should be subject to applicable maintenance procedures.

Extinguisher that is out of service should be replaced by spare extinguisher having the same classification

and capacity.

21

Page 22: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

D) FIRE ALARM INDICATING PANEL TESTING AND MAINTENANCE PROCEDURES

WHAT TO DO WHEN THERE IS AN ALARM

1. When there is alarm, rush to the main panel and see which indicator is on.

2. Rush to that particular area to check which alarm comes from and check that area to see if there is fire or

false alarm.

3. If there is a fire, please leave the alarm on till the Fire Brigade arrives, meanwhile you can call for help and

fight for fire by using the system installed.

4. If this is a false alarm, isolate the corresponding isolating switch and then reset to silence the alarm.

5. Main panel should also be reset.

6. When the alarm is off, ring Fire Brigade about the false alarm.

7. Investigate the cause of false alarm.

8. When you are sure all the breakglass & detectors are in their original position, put the isolator back to its

original position.

Testing

The fire alarm system should be tested at least once a month.

Procedure

1. Ring up Fire Brigade if the system is connected to them.

2. Send a man to the main panel and take down which area the indicator is on during testing.

3. Send another man to any area chosen to actuate alarm by unscrewing breakglass point

momentarily until an alarm is heard and then screw back the breakglass, or release the detector

element until an alarm is heard and then put back the detector element.

4. The alarm will be on even if the breakglass or detector is put back.

5. Reset the alarm by pressing a reset button in the main panel.

6. The main at the main panel should also press a button as soon as the area indicator in the main

panel is off.

7. These procedures can be repeated on other areas.

8. When the testing is completed, ring Fire Brigade again to inform them the test is over.

22

Page 23: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

Maintenance

General Introduction

The indicating panel is available for use in open or closed circuit system, and in either case continually

supervise external wiring to associate alarm initiating devices and alarm sounders.

Control and indicating panel allows the system to be tailored to meet particular requirements by the

addition of standard modules.

Panel interconnection diagram is supplied with each panel and shows panel interconnections and also

typical external wiring to bells, detectors, remote indicators, etc.

NOTE

When installation is completed, the system must be checked by qualified personnel before power is

supplied.

The following text and illustrations explain the operation of a representative control. Though individual

system may differ, all standard features are describe in this publication.

Normal Condition

"Power On" LED illuminated. Should the "Power On" becomes extinguished at any time, this will indicate

a failure of the power supply to the panel or a failure of the LED itself.

Alarm Condition

When an alarm initiating device is operated, the following signal will be given by the control panel.

1. The external alarm sounders will operate.

2. The built in supervisory buzzer will operate.

3. The red LED associated with the zone in which the alarm originated will light.

4. Any ancillary equipment required to be operated for an alarm in that zone will operate e.g. fire

station link. Fan shutdown staircase pressurization, door closed, etc.

23

Page 24: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

Alarm Control

a) Fault Buzzer Switch

Operation of this switch silences the external sounders leaving the supervisory buzzer and LED in

operation.

b) General Alarm Switch (Bell Cut off Switch)

This switch is used to convert a local alarm warning in the zone of the alarm to a general alarm

warning throughout the premises.

c) Reset Switch

Operation of this switch resets the control panel after an alarm providing that the alarm initiating

device has been restored to normal.

NOTE

In case of smoke detectors or ionisation type detectors it is important to ensure that all smoke or

product of combustion are purged from the detector before the "Reset Alarm" switch is operated.

d) Trouble Condition

When any one of variety of faults occurs, signals given by the control panel, either singly or

combination, assist in tracing the nature of the fault. These indications are as follow:-

System Trouble Lamp

When the "System Trouble” lamp only is illuminated together with the audible warning from the

built-in supervisory buzzer, it signifies trouble within the panel.

Battery Test

To assist anticipation possible battery deterioration, a battery test facility is provided. If operation

of the "Test Battery" voltage switch produces a battery trouble indication, an inspection of the

battery should be carried out.

e) Possible Causes

1. Open or short circuit on warning to alarm sounders.

2. Low insulations resistance between system wiring and earth.

3. Main supply to charger disconnected or charger faulty.

4. Condition of battery requires investigating.

NOTE All above visual warning indications are accompanied by an audible warning from the built-in supervisory buzzer.

24

Page 25: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

PART A-DAILY MAINTENANCE

A-1 Before carrying out any test, check the following:-

a) 'AC ON' indicator healthy (LED illuminated)

b) 'System DC ON' indicator healthy (LED illuminated).

c) Charged ON indicator healthy (LED illuminated).

d) Voltmeter-reads approx. 26V (battery on watch).

e) Ammeter-reads in Ma (subject to system's standby battery maintaining current).

f) No internal buzzer sounding.

A-2 Check other indication LED, they should not be lighted.

A-3 Visually check every zone functional test switch, they should be at "Normal" (NOR) position.

A-4 Lamp Test

To check that LED indicators are healthy for servicing, press on the 'LED Test' button switch (a non-locking switch)

and all the bulbs will light up at the same time bring in the fault buzzer to sound. Check all LED on the panel to

make sure that they are healthy.

PART B-MONTHLY MAINTENANCE

B-1 Before carrying out any test, it will be necessary to contact the local Fire Brigade where the call line is connected

prior to the transmitting of fire call to warn them of the simulated fire condition to be tested and the location you are

testing.

B-2 Inform all personnel in the premises about the testing through the person-in-charge.

B-3 Check the installation using PART A DAILY maintenance procedure. If the system is checked normal, then proceed

with the test below.

B-4 Alarm Test

1) To check fire alarm function : simulated fire condition by operating the manual call points or the automatic

detectors in all fire zone at random.

2) Alarm condition can also be tested at the panel by depressing the red coloured push button switch once.

3) When an alarm condition is created in a zone, the appropriate alarm zone indicator at the panel light up

flashing. Simultaneously bringing all alarm bells to ring.

4) While testing the alarm zone, check all alarm bells in the premises to ensure they are healthy for emergency

service.

5) After the alarm test, RESET the whole system by depressing the"MASTER RESET" button once.

B-5 Fault Test

1) Zone fault can be created by removing the end of the line resistor at every and loop of signalling devices zone

e.g. smoke/heat detector and manual glass call point.

2) Zone fault can also be tested at the panel by depressing the black coloured push button switch once.

3) When fault is created in a zone, the appropriate zone fault indicator at the panel lights up. Simultaneously

bring in a fault warning buzzer to sound and a 'Common Fault' Indication light to show there is a fault in this

alarm system.

4) Release the push button switch, the "Fault" will automatically clear.

B-6 LED Indicator Check

It is advisable to check all LED again after these test procedures. Check with lamp test switch.

When an LED under supervision fails, this will bring in the 'Lamp Fault' indication lamp to illuminate and activate

the fault buzzer in action.

After completing all the test, close the protective cover (door) and lock to avoid unnecessary attempt to the fire alarm

installation.

Inform the fire Brigade Station Authority and the Building Personnel in-Charge that the system is back to normal

operation. Record all your testing in 'Record Book'.

25

Page 26: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

Testing,Services&Maintenance

E) FIREMAN INTERCOM SYSTEM

MODES OF OPERATION

The fireman intercom system installed supports several modes of operation. They are as follow:-

A. MASTER TO SLAVE COMMUNICATION

Any remote handset is addressed by the operator at Master control Panel via selector switches. A call to any

remote handset can be made simply by the following procedure.

1. Lift up the master handset.

2. Press the selector switch that correspond to the remote handset to be called.

3. The respective 'call' LED will then be flashing.

4. The buzzer at the remote handset will sound continuously and the LED at the remote.

5. When the remote handset is lifted, the CALL LED lights steadily and the buzzer stops sounding.

6. Communication between master and slave handset is then established.

7. Once conversation ends and the handset is put back in position the processor will cut off the line

automatically.

B. SLAVE TO MASTER COMMUNICATION

To call the Master Station.

1. Lift up remote handset.

2. Call is automatically registered at the master control panel by the flashing of the respective call

LED and the sounding of the buzzer.

3. Lift up the master handset and press the selector switch that corresponds to the flashing LED.

4. The LED will light steadily and the line is established.

5. Once conversation ends and the handset is put back in passion, the processor will cut off the line

automatically and everything is back to normal.

C. SLAVE TO SLAVE COMMUNICATION

Any communication between two slaves handsets must be patched by the master handset. Just perform

operation B and request the operator to perform GROUPCALL on the other Slave handset.

To GROUPCALL:

1. Press the GROUPCALL selector switch followed by the selector switch that corresponds to the

slave handsets.

2. The LED will be flashing and remote handset buzzer sounds.

3. Once the remote handset is lifted, the communication is established.

D. CONFERENCE LINE

By similar operation as in C, a conference line of not more than 5 handset can be achieved. After

GROUPCALL has been used, it must be cancelled by CANCEL command. TO CANCEL:Press the

CANCEL selector switch.

26

Page 27: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

Testing,Services&Maintenance

F) CO2 FIRE EXTINGUISHING SYSTEM

TESTING, SERVICE & MAINTENANCE

The C02 cylinder to be installed is calculated to cover the volume of the protected space. The room is under

surveillance of the Heat/Smoke Detection devices which work on a double knob basic.

Only with the activation of the two zones, would the CO2 gas be discharged.

If only zone one activates, 'ALARM' would be indicated and the bell will ring. When zone two activates the

CO2 agent will be discharged after 25-30 seconds (preset timing) through the balanced distribution piping

and nozzles.

In the case when the Heat/Smoke detectors is not functioning, use the manual electric keyswitch which is

enclosed in the metal box installed below the CO2 panel to actuate the CO2 gas or through mechanical

manual pull station by double action breakglass and followed by pulling the level to discharge CO2 agent.

DAILY MAINTENANCE

WARNING:Precise execution of each step is necessary to avoid discharge of the gas and to prevent danger to

personnel.

A-1 Safety requirement : Arrangements must be made to ensure rapid and safe evacuation of any area into

which CO2 agent may be discharge accidentally.

A-2 Before carrying out any test, check the system supervising lamps : A.C on indicator, D.C on indicator,

and charger on indicator. Other indicators are off.

A-3 Lamp test; to check that bulbs are healthy for servicing, depress the lamp Test Switch (Non-locking

type), this will light up all the bulbs of the indicators, simultaneously bring in the fault warning device

for sound check.

A-4 Visually check the flashing light, the 'GREEN' light must be on.

A-5 Visually check the manual release mechanical device and electrical actuator.

A-6 Nozzle of proper type in place and properly arm.

MONTHLY MAINTENANCE

B-1 Repeat daily check.

B-2 Check all the wires are in place and intact.

B-3 Check for mechanical damage or tampering.

B-4 Check that nozzle blow-off cap if required are in place.

B-5 Piping securely bracketed or hung.

B-6 All pipes and tubing connecting are tight.

B-7 Check all components supporting hardware and tighten or repair as required.

B-8 Visually check all components for evidence of physical abuse and take whatever action that is

indicated. Replace the components if in doubt of its ability to perform properly.

27

Page 28: FPS O&M City Mall Version 1.0

OPERATION AND MAINTENANCE MANUALCITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266

(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0

TEST ACTIVATION OF CO2 FIRE EXTINGUISHING

1. Check the system with DAILY MAINTENANCE. If the system checked normal, then proceed with the

following test procedure.

2. Disconnect the electrical actuator wire at the CO2 panel.

3. Automatic detector gas release : Activate a detector in accordance with procedures recommended. This will

bring in an alert alarm bell sounding (one second on : one second off), and zone alarm indicator lit up

flashing.

4. Activate another detector in the next zone, this will operate the alarm lamp to pulsate and the' Fire

confirmation' circuit and discharge time start to operate and fire extinguishing gas is discharged after the

preset time and an evacuate alarm is given in the area.

Note : Factory present time for this system is 30 sec.

5. Check the gas discharge LED Bulb is lit up and the gas discharge flashing warning lamp (RED COLOUR)

is ON and the blanket tripped.

6. Return detector / alarm control system to normal supervisory operation.

7. Remote manual key operated gas release : Open the remote key switch box cover.

8. Discharge flashing lamp (RED COLOUR) will light and warning signaling device will operate, also

actuating end terminals to enclose the protected area (Blanked etc.) and fire extinguishing gas will be

discharged immediately. Check the gas discharge LED Bulb operated.

28