Fireproofing Testing Today and The Future
Luke Woods Principal Engineer Fire Resistance and Containment – UL
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Luke Woods
• Mechanical (BS) and Fire Protection Engineer (MS)
• Principal Engineer for Fire Resistance and Containment
• 7 years with UL
• Formerly employed by fireproofing product manufacturer
• Experience with testing, standards, building codes, construction
• Membership of NFPA, SFPE, ISO, ASTM
• Other association participation – Firestops, Fire Doors, Fire Dampers
etc.
3
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Who is UL?
• Accredited 3rd party testing and certification laboratory.
• Standards development organization (SDO).
• Research
• Quality assurance.
• Market surveillance.
• Training/consultants.
• Know by test and state the facts.
4
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL Facts and Figures
• Founded in 1894
• 131 global laboratories.
• Over 10,000 employees.
• 1,490 current standards.
• Over 100 countries with UL customers.
• Over 20,000 types of products evaluated.
• 22 Billion UL Marks on products.
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Relevant Firestop Standards
6
Standard Type Standard Reference
Fire Tests of Building Construction and Materials
UL 263 (ASTM E119, ULC-S101, ISO 834, BS 476)
Rapid Rise Fire Test of Protection Materials for Structural Steel UL 1709 (ASTM E1529)
Jet Fire ISO 22899
Durability of SFRM’s UL 2431
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL 263
• Fourteenth edition. First edition 1929.
• Standard t-T curve
• Loading requirements – where required.
• Standard hose stream – where required.
• Standard conditions of acceptance
• Report of standard information.
• Reference by building codes and local jurisdictions
• UL Categories CHPX, CDWZ, BYBU
7
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
CAN ULC S101
• Fourth edition. First edition 1982.
• Standard t-T curve
• Loading requirements – Limit States Design Method
• Standard hose stream – where required.
• Standard conditions of acceptance
• Report of standard information.
• Reference by building codes and local jurisdictions
• UL Category CHPX7/C, CDWZ7
8
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL 1709
• Fourth Edition. First Published in 1989.
• More intense fire and energy exposure.
• Environmental exposure criteria.
• Limited scope to columns.
• Used for onshore petrochemical and industrial steelwork protection.
• Ongoing updates.
9
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL 2431
• Evaluates SFRM and IFRM fire
performance after impact,
vibration and environmental
exposure.
• Recent revision and adoption.
• Looking to become Certification
requirements for SFRM and IFRM.
10
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Jet Fire – ISO 22899
• Simulates fire from pressurized
piping or tanking network
commonly found in oil refineries.
• Projects a 240-300 kW/m2 heat
flux sonic gas jet fire exposure.
UL 1709 heat flux is approximately
190-220 kW/m2 .
11
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Full Scale Panel/Wall Furnace
Dimensions
13 feet tall
15 feet wide
Specifications
Pre-mix gas burners
Computer automated
Positive and negative pressure tests in addition to various t-T curves.
Adjacent hose stream station.
12
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Column Furnace
Dimensions
Width – 10 ft.
Height – 10 ft.
Depth – 8 ft.
Specifications
UL 263 and UL 1709 testing
Full and short sections
Non loaded chamber
Manually controlled
13
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Full Scale Floor Furnace
Dimensions
14 feet long
17 feet wide
Specifications
Premixed gas burners
Fully automated.
Designed to hit various t-T curves.
Used for testing floor, roof, short columns.
14
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Large Scale Floor Furnace
15
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Small scale panel/wall furnace
Dimensions
52 inches wide
62 inches tall
Specifications
Positive and Neutral Pressure capable.
Standard t-T exposure curve
16
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Small Scale Floor Furnace
Dimensions
4 feet wide
4 feet long
2 feet deep
Dimensions
Fully automated.
Used for both UL and ULC testing.
17
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Data Acceptance Program
Remote testing capabilities.
Extends UL’s breadth.
Broadens means for UL Certification.
Global resources.
18
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL 263 Time (t) – Temperature (T) Curve
0
500
1000
1500
2000
2500
0 60 120 180 240 300 360 420 480
Tem
pera
ture
(°F)
Time (s)
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL 1709 Time (t) – Temperature (T) Curve
0
500
1000
1500
2000
2500
0 60 120 180 240 300 360 420 480
Tem
pera
ture
(°F)
Time (s)
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL 263/1709 Time-Temperature Comparison
0
500
1000
1500
2000
2500
0 60 120 180 240 300 360 420 480
Tem
pera
ture
(°F)
Time (s)
UL 263 UL 1709
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Comparison of UL 263 to UL 1709
UL 263 – 14th ed. (1st ed. 1929) UL 1709 – 4th ed. (1st ed. 1989) Models wood fueled fire Models oil fueled fire
T-t Curve – 1000°F at 5 min T-t Curve – 2000°F at 5 min Columns, Walls, Floors, Roofs, Beams Columns Only
No calibration requirements Calibration required Optional environmental exposures Mandatory environmental exposures
Same TC layout Same C o A - 1000°F average and 1200°F maximum
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Conditions of Acceptance
Sustain the imposed load
Max Deflection
Max Deflection Rate
No Passage of Flame
Openings or Ignition of Cotton Waste
250°F + Ambient Temperature Rise
Beam Temperatures
Withstand Hose Stream (Walls)
Floor or Roof
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Thermocouple Locations
24
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Conditions of Acceptance – UL 263
Ability to support the implied loading for the duration of the endurance test. Beams includes max. deflection and max. rate of deflection.
Prevent thermal transmission to < 325 F on the unexposed side of the
assembly for the duration of the endurance test. Limit steel temperatures from reaching 1100/1300°F average/max
individual for beams. Limit steel temperatures from reaching 1000/1200°F average/max
individual for unloaded columns. Withstand hose stream (where required).
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Full Scale Column Specimens – UL 263 and UL 1709
Structural Tube Wide Flange
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Conditions of Acceptance – UL 263 and 1709
Full Scale
6.1 The transmission of heat through the protection material during the period of fire exposure for which Classification is desired shall not raise the average temperature at any of the four levels of the steel column above 1000°F (538°C) and no thermocouple shall indicate a temperature greater than 1200°F (649°C).
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Small Scale Specimens
6 x 6 in. tubes.
3/16 in. wall.
2 ft. tall.
8 x 8 x ¼ in. plates.
Plates at each end.
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Conditions of Acceptance – UL 1709
Small Scale
Subjected to Simulated Environments
Comparative fire test conducted to determine relative performance
10.1 The average temperature of the test samples shall not exceed 1000°F (538°C) and no thermocouple shall indicate a temperature greater than 1200°F (649°C) within a time equal to three quarters of the control sample.
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Hose Stream Test
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Hose Stream
31
• Measures assembly durability from impact. • Mandated by code and test standard. • Not required for all fire tests or fire ratings (e.g. Europe)
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Hose Stream Requirements
UL 263
• Mandatory for walls rated over 60 minutes.
ASTM E2226
• Exclusive method
• Requires turn OFF assembly
32
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
SFRM and IFRM Ratings
Fire Resistance Restrained Assembly Restrained Beam Unrestrained Assembly Unrestrained Beam Column Walls (Loadbearing and non-loadbearing)
Environmental Ratings
Interior General Purpose Interior Conditioned Space Exterior
33
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL 2341 Environmental Conditions
Simulated Environment Exposure to:
• Aging • High Humidity • Salt Spray • Industrial Atmosphere • Wet/Freeze/Thaw Cycle
34
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Environmental Effects
Cracking
Erosion
Delamination
UV Decomposition
Chipping
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Durability and Environmental Evaluation – UL 2431
Exposure to impact, vibration and environmental condition. Conduct fire test, either UL 263 or UL 1709. Individual sample set shall be w/in 90% EPT of control sample. Multiple sample set average shall be w/in 85% EPT of control sample.
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL Certification Process
Witness Production of test material • Provides traceability between production and test preparation Witnessed sample preparation and application • Ensures the correct sample is prepared
Consistent thickness readings during preparation and before testing
Fire Test
Environmental Exposure Test
Evaluation of Data Package
Final Certification
Online Certification Database Updated
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL Fire Resistive Design
Includes:
Rating
Construction
Certified Components
Generic Components
Special Instructions
Future?
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Recent Activity
UL Industry Annual Meeting - Task groups established and routinely meet. - Task groups for UL 1709, Alternate Formulations, Topcoat
Certification Attachments statement in UL FR Directory Loading information – Further explanation for WSD vs. LSDM Multi-Temperature Analysis Revisions to UL 1709 Revision to UL Environmental Program (UL 2431)
39
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
Multi Temperature Analysis
Provides SFRM or IFRM thicknesses for a specific temperature and time.
Not to replace current Certification criteria.
Only to be used for performance based design approaches.
40
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
The Future
• What do FP contractors need? • Testing of attachments? • Testing of connections between
beams and columns? • Routine retests? • New standards? • Updated UL FRD? • More participation with UL
activities: − Standards Development − Industry Meetings − Education Seminars
41
COPYRIGHT © 2013 UL LLC. ALL RIGHTS RESERVED. THIS DOCUMENT MAY NOT BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION OF UNDERWRITERS LABORATORIES INC.
UL Resources
UL.com (link)
UL fire resistance directory (link)
Code correlation database (link)
Architectural services (link)
UL TSA/FSA Newsletters
UL Fire Wizard (link)
UL (+1.877.854.3577)
42