GRUNDFOS DATA BOOKLET

Fire NBF, Fire NKFGrundfos fire systems

Fire systems with electrically and diesel-powered pumps

according to EN 12845 and EN 12259-12

Page 2: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

2

Contents

Performance rangeNKF, ordinay hazard (OH) 4

NBF, NKF, high hazard 5

Product descriptionIntroduction 6

EN standards 6

Fire NBF and NKF pumps 6

Identification 7

Fire system 7

Bare shaft pump 7

Pump characteristics 8

Electric motor 8

Diesel engine 8

Power rating 8

Controller 9

Other system components 9

Compressor 9

Scope of delivery 9

Commissioning 9

Curve chartsHow to read the curve charts 10

OH1 dry or alternate, OH2 wet or pre-action 11

OH2 dry or alternate, OH3 wet or pre-action 14

OH3 dry or alternate, OH4 wet or pre-action 17

High hazard 20

Page 3: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

3

Fire NBF, Fire NKFPerformance range

Precalculated pumps

NBF and NKF pumps for Ordinary Hazard (OH)

classes.

(2-pole, 2950 to 3000 rpm)

Hazard class

Sprinkler height, height above the control valve set

[m]

Pump type

Nominal data Characteristics

Pressure[bar (m)]

Flow rate

[l/min (m3/h)]

Pressure[bar (m)]

Flow rate

[l/min (m3/h)]

Pressure[bar (m)]

Flow rate

[l/min (m3/h)]

OH1: wet or pre-action

0 < h 15 NKF 65-1601.2

(12.2)900(54)

2.2(22.4)

540(32.4)

2.5(25.5)

375(22.5)

15 < h 30

NKF 65-200

1.9(19.4)

1150(69)

3.7(37.7)

540(32.4)

4.0(40.8)

375(22.5)

30 < h 452.7

(27.5)1360(81.6)

5.2(53.0)

540(32.4)

5.5(56.1)

375(22.5)

OH1: dry or alternateOH2: wet or pre-action

0 < h 15 NKF 65-1601.4

(14.3)1750(105)

2.5(25.5)

1000(60.0)

2.9(29.6)

725(43.5)

15 < h 30

NKF 65-200

2.0(20.4)

2050(123)

4.0(40.8)

1000(60.0)

4.4(44.9)

725(43.5)

30 < h 452.6

(26.5)2350(141)

5.5(56.1)

1000(60.0)

5.9(60.1)

725(43.5)

OH2: dry or alternateOH3 wet or pre-action

0 < h 15 NKF 65-1601.4

(14.3)2250(135)

2.9(29.6)

1350(81.0)

3.2(32.6)

1100(66)

15 < h 30 NKF 80-2002.0

(20.4)2700(162)

4.4(44.9)

1350(81.0)

4.7(47.9)

1100(66)

30 < h 45 NKF 80-2502.6

(26.5)3100(186)

5.9(60.1)

1350(81.0)

6.2(63.2)

1100(66)

Page 4: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

4

Performance range Fire NBF, Fire NKF

Calculated pumps

NBF and NKF pump for Ordinary Hazard (OH) and High

Hazard (HH) classes.

(2-pole, 2950 to 3000 rpm)

TM

04

66

16 0

61

0

10

15

20

30

40

50

60

80

100

150

200

300

400

500

600

Q [m³/h]

10

12

20

30

40

50

60

70

80

90

100

120

[m]

H

NBF/NKF

2 pole, 50 Hz

2950/3000 rpm

65-160

40-250

32-200

125-250

100-200

80-250

80-200

65-200

50-200

Page 5: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

5

Fire NBF, Fire NKFProduct description

Introduction

Grundfos Fire NBF and Fire NKF fire systems are

typically used in fire-fighting applications for supplying

water to fire hose reels, fire hydrants or sprinkler

systems.

This data booklet covers fire systems with electric and

diesel-powered NBF and NKF end-suction pumps.

Designations

Fire NBF is an NBF end-suction pump with motor or

engine mounted on a common base frame.

Fire NKF is an NKF end-suction pump with coupling

and motor or engine mounted on a common base

frame.

The fire system can be incorporated into a fire-fighting

system.

EN standardsThe products in this data booklet have been built to

comply with EN standards on water-based fire-fighting

systems, described in the following documents:

• EN 12845: Fixed fire-fighting systems. Automatic

sprinkler systems. Design, installation and

maintenance

• EN 12259-12: Fixed fire-fighting systems. Pumps

for sprinkler and water spray systems.

Fire NBF and NKF pumps

Grundfos NBF and NKF pumps according to EN 12845

and EN 12259-12 are designed for the distribution of

water in stationary sprinkler systems using water spray.

They are operated in case of fire and during tests.

Materials

Requirements to pump materials according to

EN 12845 and EN 12259-12:

• Impeller and wear rings must be made of bronze.

• Wet parts such as shaft, washers and nuts must be

made of stainless steel.

• Castings must be made of cast iron.

Page 6: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

6

Product description Fire NBF, Fire NKF

Identification

Fire system

Example of nameplate

Fig. 1 Example of nameplate

Type key for fire system

Bare shaft pump

Example of nameplate

Fig. 2 Example of nameplate

Type key for pumpTM

04

644

1 0

31

0

Example Fire NK F 80 -250 /270 E F X D B A B

Fire: Fire systems

Pump typeNBNK

F: Pump approved for fire-fighting

Nominal diameter of discharge port[mm]

Pump housing size[mm]

Actual impeller diameter[mm]

DriverD: Diesel engineE: Electric motor, 50 Hz

Approval of pumpG: EN

Approval of fire systemX: No approval

Pipe connectionsD: DIN

Control panel B:For mounting on base frameW:For wall mountingX:No panel

Shaft sealA: BAQE

CouplingA: Standard (NKF)B: Spacer (NKF)

Type:

part No.

serial No.

Main Supply:

impeller diameter:

Made in Germany P1 0640

Fire NKF 80-250/270-E-F-X-D-B-A-B

96157421

123456789

65542145624565

65542145624565

3X400V 50Hz

270

min2940n:55 kWP2:kg346G:55IP

Q: H: 112 m150 m /h3-1

TM

04

64

42

03

10

Example NKF 65 -200 /219 AH -F -B -BAQE -G

Type range:NBFNKF

Nominal diameter of discharge port [mm]

Nominal impeller diameter [mm]

Actual impeller diameter [mm]

Code for pump version:A = NBFAH = NKF

Code for pipework connection:F = DIN flange

Code for materials:B = EN-GJL-250 with bronze impeller

Code for mechanical shaft seal and rubber pump parts

Approval of pump:G = EN

-G

Page 7: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

7

Product description Fire NBF, Fire NKF

Pump characteristicsEN 12845 and EN 12259-12 require stable QH

characteristics. The total head declines continuously

with increasing flow rate.

Fig. 3

Specific duty requirementsAn orifice plate can be included where the maximum

flow from the pump is critical (for determining the stored

water capacities). The effect of an orifice plate is to

throttle the pump curve and provide a steeper fall-off in

performance. This does, however, result in power

losses through loss of pump efficiency.

Impellers can be trimmed to provide a tailor-made

pump curve. This means that the closed-valve

pressure, power demand and potential maximum flow

rate from the pump are optimised to suit specific duty

requirements.

Performance curves of pumps used in precalculated

systems for hazard class OH1, OH2 and OH3 can be

seen on page 10 to 18. The pump impeller has been

trimmed and an orifice plate used to match the design

data requirements for the specific hazard class.

Electric motorThe electric motor is an MG or MMG motor complying

with local standards for electric motors. As from 16 July

2011, the motors used in Europe will be IE2 = EFF 1

motors.

Fig. 4 Fire NKF: An NKF end-suction pump with electric

motor and controller mounted on a base frame

Insulation class: F.

Enclosure class: IP55.

Diesel engineThe diesel engine can operate continuously at full load

at site elevation with rated output in accordance with

ISO 3046-1:1986. The pump is at full operational speed

within 15 seconds; the engine is capable of starting at

a room temperature of 5 °C.

Fig. 5 Fire NKF: An NKF end-suction pump with diesel

engine and controller mounted on a base frame

Each complete engine and pump unit is tested on the

manufacturers test bed for at least 1.5 hours at rated

flow rate. A supplier test is prepared, and the result

recorded on the test certificate.

TM

04

60

75

48

09

0 10 20 30 40 50 60 70 80 90 100 110 120

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

[m]

H

0 200 400 600 800 1000 1200 1400 1600 1800 2000

Q [l/min]

NBF/NKF 50-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø170

ø194

ø207

ø219

15 kW

22 kW

18.5 kW

11 kW

0 10 20 30 40 50 60 70 80 90 100 110 120

Q [m³/h]

0

4

8

12

16

20

24

[kW]

P2

0

10

20

NPSH

[m]

ø170 (NPSH)

ø219 (NPSH)

ø170

ø194

ø207

ø219

GrA

17

19

TM

04

01

91

Page 8: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

8

Product description Fire NBF, Fire NKF

Power ratingTo ensure that the motor (electric motor or diesel

engine) is capable of operating the pump at any time, to

ensure water supply, EN 12845 and EN 12259-12

stipulate an excess capacity of motor power.

According to EN 12845 and EN 12259-12, the motor

power is found at 16 m NPSH. The example below

show a required motor size of 22 kW.

Fig. 6 Required and stipulated power

ControllerGrundfos offers a complete, factory-assembled

controller in a steel plate cabinet, suitable for wall

mounting or free-standing.

The controller complies with the standard EN 12845.

The controller for pumps with electric motor can be

mounted on the wall or on the base frame.

The controller for diesel-powered pumps is always

mounted on the base frame.

Functions

The starting signal for the fire pump is given via two

redundant pressure switches. The fire pump can only

be switched off manually.

The control of the fire pump has been arranged in such

a way that motor failures, for example due to heating,

do not cause the fire pump to stop, but only in fault

indications and/or a potential-free signal to a

superordinate fault centre.

Other system components

Jockey pumps

Grundfos CR pumps are used as jockey pumps,

maintaining the water level in the pressure tank. Under

normal conditions, the jockey pump is activated by the

low-level switch in the pressure tank as a result of small

leakages in the pipe systems filled with water. The

jockey pump operates until it is deactivated by the high-

level switch. The jockey pump can also be activated in

case one or more sprinklers are open, in order to

maintain the water level in the pressure tank.

CompressorThe compressor can be operated manually or

automatically by using the selector switch.

During automatic operation, the compressor is

controlled by an external pressure switch, for example

connected to the pressure tank.

The compressor can be manually switched on and off

by means of the respective buttons.

Scope of delivery

A complete Fire NBF and Fire NKF unit assembled and

supplied from factory normally comprises these

elements:

• a pump and motor mounted on a common base

plate/frame

• a standard coupling protected by a coupling guard

(NKF).

Fire NBF and Fire NKF pumps can be ordered with or

without a controller according to EN 12845.

Commissioning

The installer should commission the complete fire set

before handing it over to the plant manager on site.

Many potential issues of the complete fire system must

be tested before commissioning to ensure a

satisfactory system performance and identify any

damage during installation.

Key components should be checked according to the

descriptions in the respective installation and operating

instructions. In addition, EN (12845) stipulates that fire

system tests should be carried out, for example:

• pressure test of sprinkler circuits

• values of all measuring devices (air pressure, water

level, etc.) to the system

• water flow to fire pumps

• test of alarm system and interface to municipal fire

department.

The installer should supply the plant manager with the

following documents:

• Installation certificate, stating that the fire system

has been installed according to EN (12845)

requirements.

• A complete set of installation and operating

instructions and system drawings with specification

of all components for the plant manager and the

owner of the system.

TM

04

64

92

05

10

0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [m³/h]

0

4

8

12

16

20

24

[kW]

P2

0

4

8

12

16

20

NPSH

[m]

ø170

ø194

ø207

ø219

ø170 (Min. NPSH)

ø219 (Max. NPSH)

P2 required

Page 9: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

9

Fire NBF, Fire NKFCurve charts

How to read the curve charts

TM

04 6

07

3 4

80

9

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

[m]

H

0 500 1000 1500 2000 2500 3000 3500 4000 4500

Q [l/min]

NBF/NKF 80-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø188

ø202

ø213

ø222

37 kW

55 kW

45 kW

30 kW

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300

Q [m³/h]

0

10

20

30

40

50

[kW]

P2

0

10

20

NPSH

[m]

ø188 (NPSH)

ø222 (NPSH)

ø188

ø202

ø213

ø222

Pump type and frequency of motor

Impeller size

Total pump head:H = Htotal

The power curve indicates pump input power [P2]. P2 is found at 16 m NPSH.

The NPSH curves are according to the minimum and maximum impeller diameter.

QH curve for the individual pump

This line indicates the limit of the individual pump performance.

Page 10: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

10

Performance curves

OH1 wet or pre-action

NKF 65-160

The performance envelope indicates the overall approved range for pump model NKF 65-160 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 15 m requirements of OH1 wet or pre-action.

TM

04

652

9 0

510

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-160

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø152

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

2

4

6

8

10

12

[kW]

P2

2

4

6

8

NPSH

[m]

ø152

ø152 (NPSH)

Precalculated pumpsOH1 wet or pre-action

15 m

Page 11: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

11

NKF 65-200

The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 30 m requirements of OH1 wet or pre-action.

TM

04 6

53

0 0

51

0

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø182

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

4

8

12

16

20

[kW]

P2

2

4

6

8

NPSH

[m]

ø182

ø182 (NPSH)

Precalculated pumpsOH1 wet or pre-action

30 m

Performance curves

Page 12: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

12

NKF 65-200

The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 45 m requirements of OH1 wet or pre-action.

TM

04

65

37

051

0

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø210

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

4

8

12

16

20

24

28

[kW]

P2

2

4

6

8

NPSH

[m]

ø210

ø210 (NPSH)

Precalculated pumpsOH1 wet or pre-action

45 m

Performance curves

Page 13: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

13

Performance curves

OH1 dry or alternate, OH2 wet or pre-action

NKF 65-160

The performance envelope indicates the overall approved range for pump model NKF 65-160 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 15 m requirements of OH1 dry and alternate, and OH2 wet or pre-action.

TM

04

65

35 0

51

0

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

4

8

12

16

20

24

28

32

36

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-160

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø163

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

2

4

6

8

10

12

14

[kW]

P2

2

4

6

8

NPSH

[m]

ø163

ø163 (NPSH)

Precalculated pumpsOH1 dry or alternate

OH2 wet or pre-action15 m

Page 14: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

14

NKF 65-200

The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 30 m requirements of OH1 dry and alternate, and OH2 wet or pre-action.

TM

04 6

53

8 1

61

0

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø188

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

4

8

12

16

20

[kW]

P2

2

4

6

8

NPSH

[m]

ø188

ø188 (NPSH)

Precalculated pumpsOH1 dry or alternate

OH2 wet or pre-action30 m

Performance curves

Page 15: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

15

NKF 65-200

The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 45 m requirements of OH1 dry and alternate, and OH2 wet or pre-action.

TM

04

65

39

05

10

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø215

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

4

8

12

16

20

24

28

[kW]

P2

2

4

6

8

NPSH

[m]

ø215

ø215 (NPSH)

Precalculated pumpsOH1 dry or alternate

OH2 wet or pre-action45 m

Performance curves

Page 16: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

16

Performance curves

OH2 dry or alternate, OH3 wet or pre-action

NKF 65-160

The performance envelope indicates the overall approved range for pump model NKF 65-160 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 15 m requirements of OH2 dry and alternate, and OH3 wet or pre-action.

TM

04

653

6 0

51

0

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-160

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø171

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

2

4

6

8

10

12

14

16

[kW]

P2

2

4

6

8

NPSH

[m]

ø171

ø171 (NPSH)

Precalculated pumpsOH2 dry or alternate

OH3 wet or pre-action15 m

Page 17: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

17

NKF 80-200

The performance envelope indicates the overall approved range for pump model NKF 80-200 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 30 m requirements of OH2 dry and alternate, and OH3 wet or pre-action.

TM

04 6

53

1 0

51

0

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

[m]

H

0 500 1000 1500 2000 2500 3000 3500 4000 4500

Q [l/min]

NKF 80-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø205

0 20 40 60 80 100 120 140 160 180 200 220 240

Q [m³/h]

0

5

10

15

20

25

30

35

[kW]

P2

3

4

5

6

7

NPSH

[m]

ø205

ø205 (NPSH)

Precalculated pumpsOH2 dry or alternate

OH3 wet or pre-action30 m

Performance curves

Page 18: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

18

NKF 80-250

The performance envelope indicates the overall approved range for pump model NKF 80-250 and includes an

allowance for the minimum bypass flow rate of 30 l/min.

The design data refers to specific 45 m requirements of OH2 dry and alternate, and OH3 wet or pre-action.

TM

04 6

53

2 0

51

0

0 20 40 60 80 100 120 140 160 180 200 220 240 260

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

[m]

H

0 500 1000 1500 2000 2500 3000 3500 4000

Q [l/min]

NKF 80-250

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø227

0 20 40 60 80 100 120 140 160 180 200 220 240 260

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

[kW]

P2

3

4

5

6

7

NPSH

[m]

ø227

ø227 (NPSH)

Precalculated pumpsOH2 dry or alternate

OH3 wet or pre-action45 m

Performance curves

Page 19: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

19

Performance curves

Calculated pumps

NBF, NKF 32-200

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04 6

48

1 0

41

0

0 5 10 15 20 25 30 35 40

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

[m]

H

0 100 200 300 400 500 600 700

Q [l/min]

NBF/NKF 32-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø190

ø176

ø206

ø219

11 kW

4 kW

5.5 kW

7.5 kW

0 5 10 15 20 25 30 35 40 45

Q [m³/h]

0

2

4

6

8

10

[kW]

P2

0

2

4

NPSH

[m]

ø219 (NPSH)

ø176

ø206

ø219

ø190

NBF, NKF 32-200Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 206 219 11 (2930 rpm)

Contact Grundfos> 190 206 7.5 (2900 rpm)

> 176 190 5.5 (2900 rpm)

= 176 4 (2890 rpm)

Calculated pumpsNBF, NKF 32-200

Page 20: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

20

NBF, NKF 40-250

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04

64

82 0

41

0

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85

Q [m³/h]

0

10

20

30

40

50

60

70

80

90

100

110

[m]

H

0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

Q [l/min]

NBF/NKF 40-250

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

/210

/230

/238

/250

/260

30 kW

15 kW

18.5 kW

22 kW

11 kW

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85

Q [m³/h]

0

4

8

12

16

20

24

[kW]

P2

0

4

8

12

16

NPSH

[m]

/210

/230

/238

/250

/260

NPSH

NBF, NKF 40-250Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 255 260 30 (2960 rpm) Contact Grundfos

> 245 255 22 (2950 rpm) 26

> 230 245 18.5 (2940 rpm) 19

> 211 230 15 (2940 rpm)Contact Grundfos

= 211 11 (2930 rpm)

Calculated pumpsNBF, NKF 40-250

Performance curves

Page 21: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

21

NBF, NKF 50-200

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04

607

5 4

80

9

0 10 20 30 40 50 60 70 80 90 100 110 120

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

[m]

H

0 200 400 600 800 1000 1200 1400 1600 1800 2000

Q [l/min]

NBF/NKF 50-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø170

ø194

ø207

ø219

15 kW

22 kW

18.5 kW

11 kW

0 10 20 30 40 50 60 70 80 90 100 110 120

Q [m³/h]

0

4

8

12

16

20

24

[kW]

P2

0

10

20

NPSH

[m]

ø170 (NPSH)

ø219 (NPSH)

ø170

ø194

ø207

ø219

NBF, NKF 50-200Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 207 219 22 (2950 rpm) 26

> 194 207 18.5 (2940 rpm) 19

> 170 194 15 (2940 rpm)Contact Grundfos

= 170 11 (2930 rpm)

Calculated pumpsNBF, NKF 50-200

Performance curves

Page 22: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

22

NBF, NKF 65-160

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04

716

7 1

71

0

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NKF 65-160

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø152

ø163

ø171

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

2

4

6

8

10

12

14

16

[kW]

P2

2

4

6

8

NPSH

[m]

ø171

ø163

ø152

ø152 (NPSH)

ø171 (NPSH)

NBF, NKF 65-160Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 163 171 15 (2940 rpm)

Contact Grundfos> 152 163 11 (2930 rpm)

= 152 7.5 (2900 rpm)

Calculated pumpsNBF, NKF 65-160

Performance curvesPerformance curves

Page 23: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

23

NBF, NKF 65-200

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04

60

72

48

09

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

[m]

H

0 500 1000 1500 2000 2500

Q [l/min]

NBF/NKF 65-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø170

ø186

ø195

ø214

ø219

37 kW

18.5 kW

22 kW

30 kW

15 kW

0 20 40 60 80 100 120 140 160

Q [m³/h]

0

5

10

15

20

25

30

35

[kW]

P2

0

10

20

NPSH

[m]

ø170 (NPSH) ø219 (NPSH)

ø170

ø186

ø195

ø214

ø219

NBF, NKF 65-200Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 215 219 37 (2960 rpm)Contact Grundfos

> 195 215 30 (2960 rpm)

> 186 195 22 (2950 rpm) 26

> 170 186 18.5 (2940 rpm) 19

= 170 15 (2940 rpm) Contact Grundfos

Performance curves Calculated pumpsNBF, NKF 65-200

Page 24: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

24

NBF, NKF 80-200

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04

60

73

48

09

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

[m]

H

0 500 1000 1500 2000 2500 3000 3500 4000 4500

Q [l/min]

NBF/NKF 80-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø188

ø202

ø213

ø222

37 kW

55 kW

45 kW

30 kW

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300

Q [m³/h]

0

10

20

30

40

50

[kW]

P2

0

10

20

NPSH

[m]

ø188 (NPSH)

ø222 (NPSH)

ø188

ø202

ø213

ø222

NBF, NKF 80-200Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 213 222 55 (2960 rpm) Contact Grundfos

> 202 213 45 (2980 rpm) 48

> 188 202 37 (2960 rpm)Contact Grundfos

= 188 30 (2960 rpm)

Calculated pumpsNBF, NKF 80-200

Performance curves

Page 25: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

25

NBF, NKF 80-250

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04

607

4 4

80

9

0 40 80 120 160 200 240 280 320

Q [m³/h]

0

10

20

30

40

50

60

70

80

90

100

110

120

[m]

H

0 1000 2000 3000 4000 5000

Q [l/min]

NBF/NKF 80-250

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø216

ø233

ø255

ø270

55 kW

90 kW

75 kW

45 kW

0 40 80 120 160 200 240 280 320

Q [m³/h]

0

10

20

30

40

50

60

70

80

90

[kW]

P2

0

5

10

15

20

NPSH

[m]

ø216 (NPSH)

ø270 (NPSH)

ø216

ø233

ø255

ø270

NBF, NKF 80-250Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 255 270 90 (2980 rpm) 96

> 233 255 75 (2970 rpm)Contact Grundfos

> 216 233 55 (2960 rpm)

= 216 45 (2980 rpm) 48

Calculated pumpsNBF, NKF 80-250

Performance curves

Page 26: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

26

NBF, NKF 100-200

Circulation flow = 2 % of rated flow rate.

The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values

in table below.

TM

04

60

69

48

09

0 50 100 150 200 250 300 350 400

Q [m³/h]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

[m]

H

0 1000 2000 3000 4000 5000 6000 7000

Q [l/min]

NBF/NKF 100-200

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

2950/3000 rpm

ø209

ø215

ø219

75 kW

45 kW

55 kW

0 50 100 150 200 250 300 350 400

Q [m³/h]

0

10

20

30

40

50

60

70

[kW]

P2

0

4

8

12

16

NPSH

[m]

ø209

ø215

ø219

ø209 (NPSH) ø219 (NPSH)

NBF, NKF 100-200Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 215 219 75 (2970 rpm)Contact Grundfos

> 209 215 55 (2960 rpm)

= 209 45 (2980 rpm) 48

Calculated pumpsNBF, NKF 100-200

Performance curves

Page 27: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

27

NBF, NKF 125-250

Circulation flow = 2 % of rated flow rate.

The full lines show the performance curves of electrically powered pumps.

The dotted lines show the performance curves of diesel-powered pumps.

TM

04

60

70

48

09

0 50 100 150 200 250 300 350 400 450 500 550 600

Q [m³/h]

0

10

20

30

40

50

60

70

80

90

100

110

[m]

H

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000

Q [l/min]

NKF 125-250

ISO 9906 Annex A

2-pole, 50 Hz

EN12845/EN12259-12

ø242

ø250

ø262

ø265

ø237

ø245

ø255

ø269

200 kW

110 kW

132 kW

160 kW

0 50 100 150 200 250 300 350 400 450 500 550 600

Q [m³/h]

0

20

40

60

80

100

120

140

160

180

[kW]

P2

0

4

8

12

16

NPSH

[m]

ø237

ø245

ø255

ø269

ø237 (NPSH)

ø269 (NPSH)

NBF, NKF 125-250Impeller sizes

P2 [kW] NBF, NKF 125-250Impeller sizes

P2 [kW]

Electric motor Diesel engine

> 255 269 200 (2990 rpm) > 262 265 184

> 245 255 160 (2990 rpm) > 250 262 178

> 237 245 132 (2990 rpm) > 242 250 147

237 110 (2990 rpm) 242 119

Calculated pumpsNBF, NKF 125-250

Performance curves

Page 28: Fire NBF, Fire NKF - filbo.eu - Fire NBF, Fire NKF.pdfGRUNDFOS DATA BOOKLET Fire NBF, Fire NKF Grundfos fire systems ... 3X400V 50Hz 270 P2: 55 kW n: ... Performance curves of pumps

www.grundfos.com

97641687 0410GB

Being responsible is our foundation

Thinking ahead makes it possible

Innovation is the essence