24
engineering guide FH Fan-Coil Units Low-Profile, Horizontal

FH Fan-Coil Units Low-Profile, Horizontal - Engineering ...FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908) coils, PHYsical daTa coils Johnson Controls offers hot water,

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  • engineering guide

    FH Fan-Coil Units Low-Profile, Horizontal

  • 2 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Construction Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Standard and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Coils, Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Fan Performance Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Motor, Fan and Sound Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Table of conTenTs

    noTes:• JohnsonControlsoffersWeb-Select®,theindustry’sfirstweb-basedratingandselectionprogramforcom-

    plete unit, coil and sound selection. See your representative for more information. • Somedrawingsarenotshowninthiscatalog.• Alldatahereinissubjecttochangewithoutnotice.• Drawingsnotforinstallationpurposes;refertoIOMmanual.• ETLReportNumber539840.• CityofNewYorkMaterialandEquipmentAcceptance(MEA)FileNumbers: -FHFandFHP:MEA53-98-E -FHX:MEA53-98-EVol.II.

  • Johnson Controls 3

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    feaTures and benefiTs

    HigH Performance

    Johnson Controls FH Series horizontal low profile fan coilunitsaredesignedtomaximizeflexibilityofselec-tion and installation.

    The units are also designed to exceed the stringentquality standards of the institutional market, whileremainingcostcompetitiveinthelightcommercialseg-mentofthemarket.

    Johnson Controls horizontal fan coil units set the new standardsforquality,flexibility,andcompetitivepricing.

    design fleXibiliTY

    Theextensivevarietyofstandardoptionsavailableonthe FH Series units are where you find the versatility to fitanyHVACsystemdesigner’sneeds.

    Optionsinclude:rearorbottomductedreturn,foilfacedor elastomeric closed cell foam insulation, solid or tele-scopingbottompanels forunit recessing, singlewallstainlesssteeldrainpans,electricheatwithsinglepointpowerconnection.AllelectricheatunitsarelistedwithETLasanassemblyandcarrythecETLlabel.

    AllunitscomplywiththelatesteditionofARIStandard440 for testingand rating fancoilunits,arecertified,anddisplaytheARIsymbol.

    High Efficiency motors, fan relays, disconnects andfusingmeaneasiercoordinationbetweenmechanicaland electrical trades.

    Coil options allow for three or four row chilled water or DXcoolingcoils.Oneortworowhotwaterorstandardsteam coilsmay be placed in the preheat or reheatposition.

    Silentsolidstaterelaysareavailableforfanandelectricheat control in sound sensitive environments.

    conVenienT insTallaTion

    All FH Series fan coil units are shipped completelyassembled, reducing field installation timeand labor.

    Allunitsare thoroughly inspectedand testedprior to shipment, eliminating potential problems at startup.Motorwiringisbroughttoajunctionboxontheoutsideoftheunitcasing,reducingelectricalhook-uptime.

    Plenumunitsarefieldreversibleforeitherrearorbot-tom return without special adapters, tools or additional parts.

    AllFHSeriesfancoilunitshavetheoptionofahingedcoverelectricalenclosureinthebottomoftheunit.Theexpansivecompartmentallowsforeasyaccess toallelectricalcomponents,terminalblocksandwiring.

    Factory furnished valve packages assure proper fit,operation and performance.

    Forfasttrackjobs,theFHSeriesfancoil isavailableonQuickShipwith5,10or15dayleadtimes.

    QualiTY ProducT

    ConcealedModelFHSeriesfancoilunitsarebuiltfromgalvanizedsteel.ThismetalsurpassestheASTM125hour salt spray test for corrosion and rust. ExposedModelFHXcabinetry ispowdercoatedgalvannealedsteel.

    Standardinsulationis1/2inchthickfiberglass,complyingwithUL181andNFPA90A.Optionalfoilfacedorelas-tomericclosedcellfoaminsulationmaybespecified.

    Allunits,withorwithoutelectricheat,arecETLlistedandlabeled.AllwiringisincompliancewithNEC,assur-ingsafetyandqualityfortheowner.

    FHSeriesfancoilunitshavearemovablefanassembly.Theentirefanassemblycanberemovedfromtheunitandservicedeasilyonaworkbench.

  • 4 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    consTrucTion feaTures

    model fHPFHSeriesfancoilshavemanystandardandoptionalfeatureswhichareuniquetotheindustry

    (seepage6foracompletelisting).

    model fHXHorizontalExposedCabinet

    model fHfHorizontal Free Return

    11/2"ductcollarallowsquickfieldconnectionofductwork

    ETLandARI440listedandlabeled

    Optionalhingedcoverelectrical enclosure allowseasybottomaccess to all electrical components

    Optional secondary drain

    connection for added security

    (not shown)

    Singlewallgalvanizedorstainless steel (optional) drain pans are positively sloped to drain connec-tions

    Drainpanscanbeeasily removed for cleaning,andreversedfor opposite side drain connections

    ChilledwaterorDXcoolingcoils up to 4 rows

    Hotwaterheatingcoilsorsteam coils up to 2 rows canbemountedinthepre-heat or reheat position

    Bottomaccesstobothenteringandleavingsidesofallcoilsforcleaning

    Maximum6totalrowsofcoilcombined

    Optional electric resistanceheatisETLlistedasanassemblyfor safety compliance

    Entireelectricheatassemblycanberemovedfromthebottomforservicing

    Galvanizedsteelcasingwithstanding 125hoursaltspraytestperASTMB-117

    1/2"thickfiberglassinsulation (standard), or foil faced or

    elastomeric closed cell foam insulation (optional)

    Integralfilterrackwith1" filterandintegralrear

    ducted (shown) or bottomreturnon all plenum units

    Permanentlylubricated,three tap, PSC fan

    motorsdesignedforquietandefficient

    operation

    Singlepointpower connection on all units

    with electric heat

    Removablefanboardforcomplete bottomorrearaccessandservicing

  • Johnson Controls 5

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    elecTrical enclosureThebottomhingedelectricalenclosureprovidesaccesstoaspaciouselectricalcompartment.Thiscompartmenthouses all electric heat and control components. Terminal strips are furnished for simple power andcontrol wiring connections. Multiple knockouts allowwiringentriesfromeithersideofthecompartment.

    filTersOneinchthrowawayfiltersaretightfittingtopreventairbypass.Filtersareeasilyremovablefromthebottomthroughtheaccesspanelorplenum.

    coilsAllfancoilsareavailablein2or4pipeconfigurations.Theheatingcoilmaybeplacedinthereheatorpreheatposition. On concealedmodels, heating and coolingcoils are available with right, left or opposite side connections.

    drain PanStandarddrainpansareexternallyinsulated,singlewallgalvanizedsteelwithanoptionforstainlesssteel.Drainpans are available with secondary drain connection.On concealed models, the FH Series drain pan is eas-ilyremovableforcleaningorreversingconnections.

    TelescoPing boTTom PanelThetelescopingbottompanelallowsforfullyrecessingtheunitwhilepermittingserviceaccessintotheceilingplenum.Thearchitecturalceilingpanelisfinishedwithadurablepowdercoatpaint.

    fan decKThe fan assembly is easily removed without disconnectingtheductworkforserviceaccesstomotorsandblowersat,orawayfromtheunit.

    consTrucTion feaTures

    models fHf/fHP/fHX

  • 6 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    sTandard and oPTional feaTures

    sTandard feaTures

    ConstructionAll Units• ARI440certifiedandlabeled• Galvanizedsteelconstruction• 1/2"thickfiberglassinsulation• 11/2"ductdischargecollar• FourpointhangermountingbracketsPlenum units•Integralfilterrackwith1"throwawayfilter•Integralrearductedreturn-fieldreversible tobottomreturnExposed units•Stampedlouversupplyandreturnairgrilles• Durablepowdercoatpaint• 18gaugebottompanelconstruction

    Coils• Cooling-3or4rowchilledwaterorDX,heatpumpcom-patible

    • Heating-1or2rowhotwaterorsteam–reheatorpre-heat position

    • 6totalrowsofcoolingandheatingcoilsmaximum• 1/2"O.D.seamlesscoppertubes• 0.016"tubewallthickness• Highefficiencyaluminumfinsurfaceforoptimizingheat

    transfer, pressure drop and carryover• Leftorrighthand,sameoroppositeside connections• Accesstoenteringandleavingairsidesfor cleaning

    • Removableforservice• Manualairvents

    Drain Pans• Singlewall,galvanizedsteel,externallyinsulated–fireretardantandantimicrobial

    • Positivelyslopedtodrainconnection• Removable,fieldreversible• 7/8"O.D.primarydrainconnection

    Fan Assemblies• Forwardlycurved,DWDIcentrifugaltype• 115volt,singlephase,threetapPSCmotors• Quickdisconnectmotorconnections• Removablefan/motordeckforservice

    Electrical• cETLlistedforsafetycompliance• Electricaljunctionboxforfieldwiringterminations• Terminalblockforfieldconnections

    Electric Heat• ETLlistedasanassemblyforsafetycompliance• Integralelectricheatassemblywithremovable

    elements for easy service• Automaticresetprimaryandback-upsecondary

    thermal limits• Singlepointpowerconnection• Bottomhingedelectricalenclosure

    oPTional feaTures

    ConstructionAll units• Foilfacedfiberglassinsulation• ElastomericclosedcellfoaminsulationPlenum units• Bottomreturn• 1"pleatedfilters(MERV6)• Spare1"throwawayfilters• TelescopingBottomPanelsExposed units• 1"pleatedfilters(MERV6)•Doubledeflectiondischargegrille• Ductedsupplyand/orreturn

    Coils• Automaticairvents• Stainlesssteelcoilcasings• 0.025"tubewall(standardonsteam)

    Drain Pans• Stainlesssteelconstructionwithexternalinsulation• 5/8"O.D.secondarydrainconnection• Auxiliarydrippans,galvanizedorstainlesssteel

    Fan Assemblies• 208-230,220&277volt,singlephase,threetapPSC

    motors

    Electrical• Bottomhingedcoverelectricalenclosure• SCRfanspeedcontroller• Fanrelaypackages• Silentsolidstatefanrelays• Toggledisconnectswitch• Condensateoverflowswitch(drainpan)• Mainfusing• Unitandremotemountedthreespeedfanswitches

    Electric Heat• Manualresetsecondarythermallimits• Doorinterlockingdisconnectswitches• Mainfusing• Silentrelay/contactors

    Piping Packages• Factoryassembled–shippedlooseforfieldinstallation• 1/2"and3/4",2wayand3waynormallyclosed,two

    position electric motorized valves• Isolationballvalveswithmemorystop• Fixedandadjustableflowcontroldevices• UnionsandP/Tports•Floatingpointmodulatingcontrolvalves•Highpressureclose-offactuators (1/2"=50PSIG;3/4"=25PSIG)

    Thermostats• Remotemountedanalog,digitaldisplayor programmable

    • 2and4pipecontrolsequences• Automaticandmanualchangeover• Integralthreespeedfanswitches

  • Johnson Controls 7

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    coils, PHYsical daTa

    coilsJohnsonControlsoffershotwater,chilledwater,directexpansion(DX),andstandardsteamcoilsforspecificappli-cation with all FHSeriesFanCoilUnits.Stricton-siteinspectionbefore,during,andafterinstallationguaranteesthehighestqualityandperformanceavailable.

    sTandard feaTures• Cooling-3or4rowchilledwaterorDX• Heating-1,2,3or4rowhotwateror,1or2rowsteam• 6totalrowsofcoolingandheatingcoilsmaximum• 1/2"O.D.seamlesscoppertubes• 0.016"tubewallthickness• Highefficiencyaluminumfinsurfaceforoptimizingheattrans-

    fer, pressure drop and carryover• Leftorrighthand,sameoroppositesideconnections• Manualairvents

    oPTional feaTures• Automaticairvents• Stainlesssteelcoilcasings• 0.025"tubewallthickness

    (standard on steam coils)• DXcoilsareheatpumpcompatible

    JohnsonControlsoffersWeb-Select™, the industry’s firstweb-based fancoil ratingandselectionprogramforcomplete unit, coil and sound selection. See your representative for more information.

    UNIT SIZE

    COIL FACE AREA

    MODEL FHX MODEL FHPRETURN AIR

    GRILLE FREE AREA

    SUPPLY AIR GRILLE

    FREE AREA

    FILTER FACE AREA

    NOMINAL FILTER SIZES

    FILTER FACE AREA

    NOMINAL FILTER SIZES

    20 1.04 [.09] 0.47 [.04] 0.40 [.04] 1.77 [.16]30x8.5x1

    [762x216x25]1.18 [.11]

    20x8.5x1[508x216x25]

    25 1.35 [.13] 0.58 [.05] 0.50 [.05] 2.36 [.22](2)20x8.5x1[508x216x25]

    1.54 [.14]

    26x8.5x1[660x216x25]

    30 1.56 [.14] 0.68 [.06] 0.56 [.05] 2.36 [.22](2)20x8.5x1[508x216x25]

    1.77 [.16]

    30x8.5x1[762x216x25]

    40 2.08 [.19] 0.81 [.08] 0.80 [.07] 2.95 [.27](1)20,(1)30x8.5x1[508,762x216x25]

    2.36 [.22]

    (2)20x8.5x1[508x216x25]

    50 2.60 [.24] 1.01 [.09] 0.96 [.09] 3.54 [.33](2)30x8.5x1[762x216x25]

    2.95 [.27]

    (1)20,(1)30x8.5x1[508,762x216x25]

    60 3.13 [.29] 1.15 [.11] 1.20 [.11] 4.13 [.38](2)20,(1)30x8.5x1[508,762x216x25]

    3.54 [.33]

    (2)30x8.5x1[762x216x25]

    NOTES:1.Faceandfreeareasareinsquarefeet[squaremeters].2. Filter sizes are in inches [millimeters].3.ReturnAirGrilleFreeAreaappliestoFHXandTelescopingBottomPanelreturngrilles.4. SupplyAirGrilleFreeAreaappliestoFHXsupplygrilleandminimumfreeareaallowableforasupplygrillesuppliedby

    others.

  • 8 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    PHYsical daTa

    ari sTandard raTings

    MODEL / SIZECOIL AIRFLOW

    CFM(Dry Flow)

    COOLING CAPACITY WATER POWER

    INPUT(WATTS)Rows FPI QT(BTUH)

    QS(BTUH)

    Flow Rate(GPM)

    WPDft-wg

    FHF 20FHF 25FHF 30FHF 40FHF 50FHF 60

    333333

    101010101010

    33045064080011401590

    80001150013200185002400034000

    590085009900143001930026500

    1.82.63.24.25.47.6

    1.63.47.63.77.414.6

    81138152263402489

    FHF 20FHF 25FHF 30FHF 40FHF 50FHF 60

    444444

    101010101010

    32043061078010401510

    85001160015900222002850041400

    6000860010400166002250031300

    1.82.63.94.96.49.2

    3.16.610.97.212.927.1

    77135151261380466

    FHP 20FHP 25FHP 30FHP 40FHP 50FHP 60

    333333

    101010101010

    27042054077010101460

    69001090011900181002230032300

    530081008100139001820025600

    1.62.52.84.15.07.2

    1.23.16.13.57.113.3

    81132152263372489

    FHP 20FHP 25FHP 30FHP 40FHP 50FHP 60

    444444

    101010101010

    2604105207409701370

    88001090015100213002720038600

    6000810010300159002140028400

    1.62.53.54.86.18.6

    2.56.010.06.911.923.8

    77130151261361466

    FHX 20FHX 25FHX 30FHX 40FHX 50FHX 60

    333333

    101010101010

    2403104506508201130

    6300890010400163001950027500

    480065007100124001570021500

    1.52.02.53.74.46.1

    1.12.24.92.95.610.0

    75127135245337402

    FHX 20FHX 25FHX 30FHX 40FHX 50FHX 60

    444444

    101010101010

    2403004406307801040

    6300870012800189002340031900

    470063008300140001830024200

    1.52.03.14.25.37.1

    2.14.07.95.59.116.8

    65125130235321383

    NOTE:Basedon80°FDBand67°FWBEAT,45°FEWT,10°Ftemperaturerise,highfanspeed.MotortypeisPSCandmotorvoltageis115/1/60.Airflowunderdrycoilconditions.ModelsFHXtestedat0.0"externalstaticpressure.ModelsFHFandFHPtestedat0.05"externalstaticpressure.

  • Johnson Controls 9

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    PHYsical daTa

    NOTE:Unitweightdataisinpounds[kilograms].

    uniT WeigHT daTa

    COMPONENTUNIT SIZE

    20 25 30 40 50 60FHF BASE UNIT 40 [18] 51 [23] 59 [27] 69 [31] 91 [41] 111 [50]FHP BASE UNIT 45 [20] 56 [25] 65 [30] 80 [36] 103 [47] 123 [56]FHX BASE UNIT 119 [54] 138 [63] 155 [70] 181 [82] 220 [100] 257 [117]

    COILROWS

    1 ROW - DRY 8 [4] 10 [5] 11 [5] 13 [6] 15 [7] 18 [8]1 ROW - WET 10 [5] 12 [5] 13 [6] 15 [7] 18 [8] 21 [10]2 ROW - DRY 11 [5] 13 [6] 15 [7] 18 [8] 22 [10] 26 [12]2 ROW - WET 14 [6] 16 [7] 18 [8] 22 [10] 27 [12] 32 [15]3 ROW - DRY 14 [6] 17 [8] 19 [9] 24 [11] 29 [13] 34 [15]3 ROW - WET 17 [8] 21 [10] 24 [11] 30 [14] 36 [16] 42 [19]4 ROW - DRY 17 [8] 20 [9] 23 [10] 29 [13] 36 [16] 42 [19]4 ROW - WET 21 [10] 25 [11] 29 [13] 36 [16] 45 [20] 53 [24]

    HeaTing caPaciTYUNIT TYPE UNIT SIZE NOMINAL CFM

    1 ROW 2 ROWQS (MBH) GPM WPD QS (MBH) GPM WPD

    FHPFHF

    20 250 8.6 0.4 0.2 15.7 0.8 0.925 400 15.0 0.6 0.6 21.0 1.1 3.130 500 16.1 0.8 0.6 29.2 1.5 3.240 750 23.6 1.2 1.5 40.5 2.1 1.650 1000 28.7 1.5 0.7 53.7 2.7 2.960 1400 36.1 1.9 1.1 66.9 3.4 4.7

    FHX

    20 250 7.9 0.4 0.3 14.0 0.8 1.525 350 10.8 0.6 0.5 19.3 1.0 2.630 450 13.5 0.7 0.9 24.0 1.3 4.840 650 20.4 1.1 2.0 34.0 1.8 1.750 850 22.5 1.2 0.7 40.7 2.1 3.160 1200 30.9 1.6 1.2 55.4 2.9 5.5

    NOTE:Basedon70°FDBEAT,180°FEWT,40°Ftemperaturedrop,highfanspeed.

  • 10 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    elecTric HeaT

    sTandard feaTures• ETLlistedasanassembly for safety compliance• Singlepointpowerconnection• Mountedinpreheatposition• Automaticresetprimaryandback-up

    secondary thermal limits• Internalwiringratedat105°C• Integralelectricheatassemblywith removableelementforeasyservice

    • StainlesssteelterminalsandhardwareoPTional feaTures• Silentsolidstaterelays• Manualresetsecondarylimits• Doorinterlockingdisconnectswitch• Mainfusing

    useful formulaskW* = CFMx∆Tx1.085** 34131ØAMPs = kWx1000 Volts* 1kW=3413BTU/H** CapacityatsealevelAltitude Considerations:Reduceby0.034foreach1000ft.ofaltitudeabovesealevel. Example:5000ft./1000ft.=5 5x0.034=0.17 1.085 - 0.17 = 0.915

    NOTES:1. ShadedareasoftheelectricheatselectionchartindicatekWandvoltageoptionsnotavailable.2. Availablevoltagesaresinglephase,60hertz.3. SizeheaterforLeavingAirTemperature(LAT)lessthan104°F.4. Silent,solidstateheaterrelayisavailableforsoundsensitiveenvironments.5. AskyourJohnsonControlsrepresentativeaboutcontinuouslymodulatingelectricheatusingSSRandspecialcontrol

    options.

    ELECTRICAL CALCULATIONS INFORMATION1. Contact your local Johnson Controls sales office.2.Non-FusedDoorInterlockDisconnectSwitchshallbesizedaccordingtoMCA.3.FusedDoorInterlockDisconnectSwitchandMainFusingshallbesizedaccordingtoMOP.

    elecTric HeaT selecTion cHarT (amPs)

    UNITSIZE

    MBH 5.1 6.8 10.2 13.7 17.1 20.5 25.6 27.3 34.1KW 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0

    VOLTS AMPS

    20115 13.0 17.4 26.1208 7.2 9.6 14.4230 6.5 8.7 13.0277 5.4 7.2 10.8

    25115 13.0 17.4 26.1208 7.2 9.6 14.4230 6.5 8.7 13.0277 5.4 7.2 10.8

    30

    115 13.0 17.4 26.1 34.8 43.5208 7.2 9.6 14.4 19.2 24.0 28.8230 6.5 8.7 13.1 17.4 21.7 26.1277 5.4 7.2 10.8 14.4 18.1 21.7

    40115 17.4 26.1 34.8 43.5208 9.6 14.4 19.2 24.0 28.8 33.7230 8.7 13.1 17.4 21.7 26.1 30.4277 7.2 10.8 14.4 18.1 21.7 25.3

    50115 26.1 34.8 43.5208 14.4 19.2 24.0 28.8 33.7 38.5230 13.1 17.4 21.7 26.1 30.4 34.8277 10.8 14.4 18.1 21.7 25.3 28.9

    60115 26.1 34.8 43.5208 14.4 19.2 24.0 28.8 33.7 38.5230 13.1 17.4 21.7 26.1 30.4 34.8 43.5277 10.8 14.4 18.1 21.7 25.3 28.9 36.1

    JohnsonControlsofferselectricheatingcoilsforspecificapplicationwithallFHSeriesFanCoilunits.Thisallowstheflexibilitytoprovideanunrivaledamountofelectricheatoptionsinonecompletepackage.

  • Johnson Controls 11

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    fan Performance curVes

    1. Fancurvesonthefollowingpagesdepictactualperformanceofeachmotortapwithoutanyadditionalfanbalanceadjust-ment.Actualcapacitieswhichfallbeloweachcurvecanbeobtainedbyaddinganadjustmentdevice.Unitsshouldnotberunpriortoinstallationofdownstreamductwork;otherwise,damagetothemotormayresult.

    2. JohnsonControlsFanCoilUnitsareequippedwithpermanentsplit-capacitor(PSC)motorswiththreetaps(High,MediumandLow)whichprovidesvariablehorsepoweroutputs.Mostoften,sizeselectionsareconservativeandactualCFMrequire-mentsand/orexternalstaticpressurerequirementsarelowerthanthosespecified.Inthiscase,theunitfanmotorcanberunatlowormediumtap,substantiallyreducingtheoperatingcostoftheunit.

    3. Allfancurvesarefor115/1/60motorsandincludepressurelossesforcabinet,electricheater,and3or4rowcoil.Plenumunitsincludeaclean1"throwawayfilter.Forothercoilconfigurations,adjustperformancecurvesbasedonpressurelossesforthecoilsusingWeb-Select®.

    4. Seepage14forfanmotorelectricaldata.5. Foradditionalhighstaticpressureapplicationsandratingpoints,contactfactory.

    Model FHP (Plenum)

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    0.30

    0.35

    0.40

    0 50 100 150 200 250 300

    SCFM

    ES

    P (

    IN. W

    .G.)

    4 ROW COIL3 ROW COIL

    MED

    HIGH

    LOW

    Model FHF (Free Return)

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    0.30

    0.35

    0.40

    0 50 100 150 200 250 300 350 400SCFM

    ES

    P (

    IN. W

    .G.)

    4 ROW COIL3 ROW COIL

    LOW

    MED

    HIGH

    Model FHX (Exposed Cabinet)

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    0.30

    0.35

    0.40

    0 50 100 150 200 250 300

    SCFM

    ESP

    (IN. W

    .G.)

    MEDHIGH

    LOW

    4 ROW COIL3 ROW COIL

    Model FHP (Plenum)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0 50 100 150 200 250 300 350 400 450 500

    SCFM

    ESP

    (IN. W

    .G.)

    LOW

    MED

    HIGH

    4 ROW COIL3 ROW COIL

    Model FHF (Free Return)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0 50 100 150 200 250 300 350 400 450 500

    SCFM

    ESP

    (IN. W

    .G.)

    LOW

    MED

    HIGH

    4 ROW COIL3 ROW COIL

    Model FHX (Exposed Cabinet)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0 50 100 150 200 250 300 350

    SCFM

    ESP

    (IN. W

    .G.)

    LOW

    MED

    HIGH

    4 ROW COIL3 ROW COIL

    Size 25Size 20

  • 12 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    fan Performance curVes

    Model FHP (Plenum)

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    0.30

    0.35

    0 50 100 150 200 250 300 350 400 450 500 550 600

    SCFM

    ES

    P (

    IN. W

    .G.)

    4 ROW COIL3 ROW COIL

    LOW

    MED

    HIGH

    Model FHF (Free Return)

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    0.30

    0.35

    0.40

    0 50 100 150 200 250 300 350 400 450 500 550 600 650 700

    SCFM

    ES

    P (

    IN. W

    .G.)

    4 ROW COIL3 ROW COIL

    HIGH

    MED

    LOW

    Model FHX (Exposed Cabinet)

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    0.30

    0.35

    0.40

    0 50 100 150 200 250 300 350 400 450 500

    SCFM

    ESP

    (IN. W

    .G.)

    MEDHIGH

    LOW

    4 ROW COIL3 ROW COIL

    Size 40Size 30

    Model FHP (Plenum)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0 100 200 300 400 500 600 700 800 900

    SCFM

    ES

    P (

    IN. W

    .G.)

    4 ROW COIL3 ROW COIL

    HIGH

    MED

    LOW

    Model FHF (Free Return)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    0 100 200 300 400 500 600 700 800 900

    SCFM

    ESP

    (IN. W

    .G.)

    4 ROW COIL3 ROW COIL

    HIGH

    MED

    LOW

    The thick line indicates 3 row coil

    Model FHX (Exposed Cabinet)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0 50 100 150 200 250 300 350 400 450 500 550 600 650 700

    SCFM

    ESP

    (IN. W

    .G.)

    MED HIGH

    LOW

    4 ROW COIL3 ROW COIL

  • Johnson Controls 13

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    fan Performance curVes

    Model FHP (Plenum)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600

    SCFM

    ES

    P (

    IN.

    W.G

    .)

    4 ROW COIL3 ROW COIL

    HIGH

    MED

    LOW

    Model FHF (Free Return)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700

    SCFM

    ES

    P (

    IN.

    W.G

    .)

    4 ROW COIL3 ROW COIL

    HIGH

    MED

    LOW

    Model FHX (Exposed Cabinet)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0 100 200 300 400 500 600 700 800 900 1000 1100 1200

    SCFM

    ES

    P (I

    N. W

    .G.)

    MED

    HIGH

    LOW

    4 ROW COIL3 ROW COIL

    Model FHP (Plenum)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0 200 400 600 800 1000 1200

    SCFM

    ES

    P (

    IN. W

    .G.)

    HIGH

    4 ROW COIL3 ROW COIL

    MED

    LOW

    Model FHF (Free Return)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    1.00

    0 200 400 600 800 1000 1200 1400

    SCFM

    ES

    P (

    IN. W

    .G.)

    LOW

    MED

    HIGH

    4 ROW COIL3 ROW COIL

    Model FHX (Exposed Cabinet)

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850

    SCFM

    ESP

    (IN. W

    .G.)

    MED

    HIGH

    LOW

    4 ROW COIL3 ROW COIL

    Size 60Size 50

  • 14 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    moTor, fan and sound daTamoTor and fan daTa

    sound daTa

    NOTES:1.Motorelectricaldataisnameplateddata.Actualdatawillvarywithapplication.2. 230 volt motor is nameplated for 208-230/1/60. Use 230 volt motor data for 208 volt applications.3.Unitsize30,208-230and277voltmotorsare1/12HPathightap.

    UNITSIZE

    FANSPEED

    MOTOR H.P. (QTY.)

    # OF FANS

    115 VOLTS 208-230 VOLTS 277 VOLTSAMPS WATTS AMPS WATTS AMPS WATTS

    20High (1) 1/30

    10.8 57 0.6 77 0.3 71

    Medium (1) 1/50 0.4 39 0.3 49 0.3 48Low (1) 1/60 0.3 33 0.3 43 0.3 41

    25High (1) 1/15

    11.1 125 0.5 120 0.5 120

    Medium (1) 1/30 0.9 90 0.3 80 0.3 80Low (1) 1/60 0.5 60 0.2 60 0.2 60

    30High (1) 1/10

    21.9 165 0.8 158 0.8 162

    Meduim (1) 1/30 0.8 76 0.3 75 0.5 65Low (1) 1/60 0.5 47 0.2 54 0.4 41

    40High (1) 1/6

    22.5 261 1.4 284 1.0 254

    Medium (1) 1/12 1.5 162 0.5 171 0.5 152Low (1) 1/40 0.6 75 0.4 79 0.3 74

    50

    High (1) 1/8

    3

    1.6 215 0.9 216 0.8 214(1) 1/6 2.5 257 1.4 233 1.0 255

    Medium (1) 1/15 1.3 145 0.6 109 0.5 132(1) 1/12 1.5 156 0.5 106 0.5 151

    Low (1) 1/40 0.8 69 0.3 63 0.3 86(1) 1/40 0.6 75 0.4 62 0.3 84

    60High (2) 1/6

    45.0 522 2.8 568 2.0 508

    Medium (2)1/12 3.0 324 1.0 342 1.0 304Low (2) 1/40 1.2 150 0.6 158 0.6 148

    UNIT SIZE FAN SPEED SCFMTOTAL SOUND POWER LEVEL

    OCTAVE BAND / CENTER FREQUENCY (HZ)2/125 3/250 4/500 5/1000 6/2000 7/4000 8/8000

    20High 282 55 59 53 50 46 38 36

    Medium 216 50 52 47 44 38 31 32Low 175 47 48 43 39 32 27 31

    25High 420 58 62 57 54 51 44 39

    Medium 286 53 53 49 45 41 34 29Low 180 48 42 38 36 33 27 27

    30High 522 60 60 57 56 50 44 40

    Medium 458 57 55 54 52 46 40 36Low 269 48 44 43 39 32 27 31

    40High 810 65 68 64 60 55 51 47

    Medium 565 59 59 57 51 46 40 35Low 300 51 46 41 36 28 27 30

    50High 1050 61 66 68 62 56 52 49

    Medium 840 56 61 63 55 49 44 40Low 490 48 53 59 46 39 33 32

    60High 1400 67 72 70 68 59 54 51

    Medium 1050 61 65 67 57 52 47 42Low 500 50 56 48 40 33 28 31

    NOTES:1.SounddatatestedinaccordancewithARI350-2000.2.Soundlevelsareexpressedindecibels,dBRE:1x10-12 watts.3.TotalsoundpowerleveldatabasedonModelFHPwithfanCFMatcorrespondingmotortapwith115/1/60voltmotor,3or4rowcoil,1"throwawayfilter,0.0"externalstaticpressureandstandardratedinternalpressurelosses.

  • Johnson Controls 15

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    dimensional daTa

    model fHf free reTurn uniTsDrawingsarenottoscaleandnotforsubmittalorinstallationpurposes.

  • 16 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    dimensional daTa

    model fHP Plenum uniTsDrawingsarenottoscaleandnotforsubmittalorinstallationpurposes.

  • Johnson Controls 17

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    dimensional daTa

    model fHX eXPosed cabineT uniTsDrawingsarenottoscaleandnotforsubmittalorinstallationpurposes.

  • 18 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    dimensional daTa

    TelescoPing boTTom PanelDrawingsarenottoscaleandnotforsubmittalorinstallationpurposes.

  • Johnson Controls 19

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    guide sPecificaTions

    general

    Furnish and install Johnson Controls Model FH Horizontal Concealed Direct Drive Fan Coil Units where indicated on the plans and in the specifications. Units shall be completely factory assembled, tested andshipped as one piece. All units shall be capable ofmeetingorexceedingthescheduledcapacitiesforcool-ing,heatingandairdelivery.Allunitdimensionsforeachmodelandsizeshallbeconsideredmaximums.UnitsshallbeETLlistedincompliancewithUL/ANSIStandard1995,andbecertifiedascomplyingwiththelatestedi-tionofARIStandard440.

    consTrucTion

    All unit chassis shall be fabricated of heavy gaugegalvanized steel panels able tomeet 125 hour saltspray testperASTMB-117.Allexteriorpanelsshallbeinsulatedwith1/2"thickinsulationwithamaximumkvalueof.24(BTU•in)/(hr•ft2•°F)andratedforamaximumairvelocityof5000f.p.m.Insulationmustmeet all requirements of ASTM C1071 (includingC665),UL181 forerosion,andcarrya25/50 ratingfor flame spread/smokedeveloped perASTME-84,UL723andNFPA90A.

    Allconcealedunitsshallhaveaminimum1-1/2"ductcollar on the discharge. Plenum and exposed unitsshall have a minimum 3/4" duct collar on the return.

    All exposed units shall have exterior panels fabri-catedofgalvannealedsteel.Thefanandfilterbottomaccesspanelshallbeattachedwithquarterturnquickopen fasteners to allow for easy removal and access for service.

    Option: Provide foil faced insulation in lieu of standard. Foil insulationshallmeetorexceedtherequirementsstatedabove,and inadditionmeetASTMStandardsC-665andC-1136 forbiologicalgrowth in insulation.Insulationshallbelinedwithaluminumfoil,fiberglassscrim reinforcement, and 30 pound kraft paper lami-nated together with a flame resistant adhesive. Allexposededgesshallbesealed topreventany fibersfromreachingtheairstream.

    Option:ProvideElastomericClosedCellFoamInsulationinlieuofstandard.InsulationshallconformtoUL181forerosionandNFPA90Aforfire,smokeandmelting,and comply with a 25/50 Flame Spread and SmokeDevelopedIndexperASTME-84orUL723.Additionally,insulationshallcomplywithAntimicrobialPerformanceRating of 0, no observed growth, per ASTM G-21.Polyethyleneinsulationisnotacceptable.

    Unitmountingshallbebyhangerbracketsprovidedatfour locations. Hanger brackets shall include rubbergrommetisolatorswithbrasseyeletsforthreadedrod.

    PainTed finisH

    Allpaintedcabinetexteriorpanelsshallbefinishedwitha heat cured anodic acrylic powder paint of the standard factory color.

    sound

    Units shall have published sound power level datatestedinaccordancewithARIStandard350-2000(non-ductedequipment)andARIStandard260-2001(ductedequipment).

    fan assemblY

    Unit fan shall be a dynamically balanced, forwardlycurved,DWDIcentrifugaltypeconstructedof18gaugezinccoatedgalvanizedsteel forcorrosionresistance.Motorsshallbehighefficiency,permanentlylubricatedsleevebearing,permanentsplit-capacitortypewithULandCSAlistedautomaticresetthermaloverloadprotec-tionandthreeseparatehorsepowertaps.Singlespeedmotorsarenotacceptable.

    Thefanassemblyshallbeeasilyremovableforservic-ingthemotorandblowerat,orawayfromtheunit.Theentire fanassemblyshallbeable tocomeoutof theunitbyremovingtwoscrewsandunpluggingthemotor.Plenum unit fan assemblies shall be easily servicedthroughanaccesspanelprovided.

    Option: Provide an electronic (SCR) fan speed control-lerasanaidinbalancingthefancapacity.Thespeedcontroller shall have a turn down stop to prevent the possibilityofharmingthemotorbearings,andincorpo-rate electrical noise suppression to minimize noise on theincomingpowerlines.

    Option: Devices used to energize and de-energize(switch) fan speedsmust be totally silent.Magnetic,mercury,and/orquietrelaysand/orcontactorsarenotacceptable.

    coils

    All coolingandheatingcoilsshalloptimize rowsandfins per inch to meet the specified capacity. Coils shall have seamless copper tubes and shall bemechani-callyexpandedtoprovideanefficient,permanentbondbetween the tube and fin. Fins shall have high effi-ciency aluminum surface optimized for heat transfer, air pressure drop and carryover.

  • 20 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    guide sPecificaTions

    Allcoilsshallbehydrostaticallytestedat450PSIGairpressureunderwater,andratedforamaximumof300PSIGworkingpressureat200°F.

    Direct expansion cooling coils shall include a fixedorificemeteringdevice. All evaporator coils shall befactory sealed and chargedwith aminimum5PSIGnitrogenorrefrigerateddryair.

    Steamcoilsshallbestandardsteamtypesuitablefortemperaturesabove35°Fand15PSIGmaximumwork-ingpressure.

    Option:CoilcasingshallbefabricatedfromStainlessSteel.

    Allcoilsshallbeprovidedwithamanualairventfittingtoallowforcoilventing.

    Option: Provide automatic air vents in lieu of manual air vents.

    Heatingcoilsshallbefurnishedinthereheatorpreheatposition on units with chilled water coils, or in the reheat position for DX coils.

    drain Pans

    Primary condensate drain pans shall be single wall,heavygaugegalvanizedsteelforcorrosionresistance,and extendunder the entire cooling coil.Drain pansshall be of one-piece construction and be positivelysloped for condensate removal. Drain pans on con-cealedmodelsshallbefieldreversibleforrightorlefthand connections.

    Thedrainpanshallbeexternallyinsulatedwithafireretardant,closedcell foam insulation. The insulationshall carry no more than a 25/50 Flame Spread and SmokeDevelopedRatingperASTME-84andUL723and an Antimicrobial Performance Rating of 0, noobservedgrowth,perASTMG-21.

    Option:Provideasinglewallprimarydrainpancon-structed entirely of heavy gauge stainless steel forsuperior corrosion resistance. Stainless steel drain pans shallbeexternally insulatedandmeetorexceed therequirementsstatedabove.

    Option: Provide a secondary drain connection on the primary drain pan for condensate overflow.

    filTers

    Allplenumandexposedunitsshallbefurnishedwithaminimum1"nominalglassfiberthrowawayfilter.Filtersshallbetightfittingtopreventairbypass.Plenumunitfiltersshallbeeasilyremovablefromthebottomoftheunit without the need for tools.

    Option:Provideunitwith1"pleatedfilter(MERV6).

    elecTrical

    Unitsshallbefurnishedwithsinglepointpowerconnec-tion.Provideanelectricaljunctionboxwithterminalstripformotorandotherelectricalterminations.Thefactorymountedterminalwiringstripconsistsofamultipleposi-tionscrewterminalblocktofacilitatewiringterminationsfor the electric control valves and thermostats.

    Option: Provide a hinged electrical enclosure in thebottomoftheunitforeasyaccesstoallelectricalcom-ponents,terminalblocksandwiring.

    elecTric HeaT

    Furnishanelectricresistanceheatingassemblyasanintegralpartofthefancoilunit,withtheheatingcapac-ity, voltage and kilowatts scheduled. The heaterassemblyshallbedesignedandrated for installationonthefancoilunitwithouttheuseofductextensionsor transitions, and be located in the unit as to notexposethefanassemblytoexcessiveleavingairtem-peratures that could affect motor performance.

    Theheaterandunitassemblyshallbe listedforzeroclearanceandmeetallNECrequirements,andbeETLlistedwiththeunitasanassemblyincompliancewithUL/ANSIStandard1995.

    Allheatingelementsshallbeopencoiltypenichromewire mounted in ceramic insulators and located in an insulatedheavygaugegalvanizedsteelhousing. Allelementsshallterminateinamachinestakedstainlesssteel terminal secured with stainless steel hardware for corrosion resistance. The element support bracketsshallbespacednogreater than3-1/2"oncenter.Allinternalwiringshallberatedfor105°Cminimum.

  • Johnson Controls 21

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    guide sPecificaTions

    All heaters shall include overtemperature protectionconsistingofanautomaticresetprimarythermal limitandbackupsecondarythermallimit.Allheatersshallbesinglestage.

    Option: Provide a manual reset secondary thermal limit.

    Allunitswithelectricheatshallhaveabottomhingedelectrical enclosure for easy access and service to the electrical components and wiring. An incoming linepowerdistributionblockshallbeprovidedanddesig-nated toaccept singlepointpowerwiringcapableofcarrying125%ofthecalculatedloadcurrent.

    Option: Devices used to energize and de-energize(switch)electricheatmustbetotallysilent.Magnetic,mercury,and/orquietrelaysand/orcontactorsarenotacceptable.

    PiPing PacKages

    Provide a standard factory assembled valve pipingpackagetoconsistofa2or3way,on/off,motorizedelectric control valve and two ball isolation valves.

    Control valves are piped normally closed to the coil. Maximum entering water temperature on the controlvalveis200°F,andmaximumclose-offpressureis40PSIG (1/2") or 20 PSIG (3/4"). Maximum operatingpressureshallbe300PSIG.

    Option:Provide3-wirefloatingpointmodulatingcontrolvalve (fail-in-place) in lieu of standard 2-position control valvewithfactoryassembledvalvepipingpackage.

    Option:Providehighpressureclose-offactuatorsfor2-wayon/offcontrolvalves.Maximumclose-offpres-sureis50PSIG(1/2")or25PSIG(3/4)".

    Option:Provideeitherafixedoradjustableflowcontroldeviceforeachpipingpackage.

    Option: Provide pressure-temperature ports for each pipingpackage.

    Pipingpackageshallbecompletelyfactoryassembled,including interconnectingpipe,andshippedseparatefrom the unit for field installation on the coil, so as to minimizetheriskoffreightdamage.

  • 22 Johnson Controls

    FORM 115.26-EG7 (908) FH Fan-Coil Units Low-Profile, Horizontal

    noTes

  • Johnson Controls 23

    FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908)

    noTes

  • Printed on recycled paper

    Form:115.26-EG7(908)Supersedes:Nothing©2008JohnsonControls,Inc.P.O.Box423,Milwaukee,WI53201PrintedinUSAwww.johnsoncontrols.com

    FH Fan-Coil UnitsLow-Profile, HorizontalFORM 115.26-EG7 (908)Table of ContentsFeatures and BenefitsConstruction FeaturesModel FHPModel FHXModel FHFModels FHF/FHP/FHX

    Standard and Optional FeaturesCoilsPhysical DataARI Standard RatingsHeating CapacityUnit Weight Data

    Electric HeatFan Performance CurvesSize 20Size 25Size 30Size 40Size 50Size 60

    Motor, Fan and Sound DataDimensional DataModel FHF Free Return UnitsModel FHP Plenum UnitsModel FHX Exposed Cabinet UnitsTelescoping Bottom Panel

    Guide Specifications