CB17 SERIES — UP-FLOW CBH17 SERIES — HORIZONTAL 63 900 to 223 200 Btuh (18.7 to 65.4 kW) Cooling Capacity 75 700 To 199 500 Btuh (22.2 To 58.5 kW) Heat Pump Heating Capacity 32 100 To 153 600 Btuh (9.4 To 45.0 kW) Optional Electric Heat 185 000 To 462 000 Btuh (54.2 To 134.4 kW) Optional Hot Water Heat CB17/CBH17 September 1994 Supersedes June 1988 Bulletin #490018 MATCHED REMOTE SYSTEMS – 50hz ENGINEERING DATA COILS — BLOWER COIL UNITS – 50hz ENGINEERING DATA Typical Applications CBH17-95V Horizontal Unit CB17-95V Up-Flow Unit Horizontal Store Installation With Optional Hot Water Heat Section and Supply Air Plenum and Grille Suspended Horizontal Installation With Optional Electric Heat and Economizer Dampers Up–Flow Installation With Optional Hot Water Heat Section and Economizer Dampers Vertical Store Cooler Installation With Optional Electric Heat Section and Supply Air Plenum and Grille NOTE — Due to Lennox’ ongoing committent to quality, Specifications, Ratings and Dimensions subject to change without notice. 1994 Lennox Industries Inc.

ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

CB17 SERIES — UP-FLOW

CBH17 SERIES — HORIZONTAL63 900 to 223 200 Btuh (18.7 to 65.4 kW) Cooling Capacity

75 700 To 199 500 Btuh (22.2 To 58.5 kW) Heat Pump Heating Capacity

32 100 To 153 600 Btuh (9.4 To 45.0 kW) Optional Electric Heat

185 000 To 462 000 Btuh (54.2 To 134.4 kW) Optional Hot Water Heat

CB17/CBH17

September 1994Supersedes

June 1988

Bulletin #490018

MATCHED REMOTE SYSTEMS – 50hzENGINEERING DATA COILS — BLOWER COIL UNITS – 50hzENGINEERING DATA

Typical Applications

CBH17-95VHorizontal Unit

CB17-95VUp-Flow Unit

Horizontal Store Installation WithOptional Hot Water Heat Section and

Supply Air Plenum and Grille

Suspended Horizontal Installation With Optional Electric Heat and

Economizer Dampers

Up–Flow Installation WithOptional Hot Water Heat Section and

Economizer Dampers

Vertical Store Cooler Installation WithOptional Electric Heat Section and

Supply Air Plenum and Grille

NOTE — Due to Lennox’ ongoing committent to quality,Specifications, Ratings and Dimensions subject to change without notice. 1994 Lennox Industries Inc.

Page 2: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

FEATURES

Application — Lennox CB17 and CBH17 model blower-coil-filter units provide installation versatility and maximum effi-ciency in cooling performance, air handling and filtering incooling or heat pump applications. Units are available in twomodel styles, CB17 series with up-flo supply air discharge orCBH17 series with horizontal supply air discharge. The unitsare equipped with dual circuit evaporator coils, this makesthem suitable for application with Lennox HS17 remotecondensing units or HP17 heat pump outdoor units. Each in-door coil circuit has a separate expansion valve and distribu-tion system for two stage capacity control during coolingcycles. Blower coil units are shipped factory assembled readyto install. Blower drives are shipped separately and must beordered extra. See condensing unit bulletins (section SpiltSystem Condensing Units) or heat pump outdoor units (sec-tion Split System — Heat Pump Units) for heating-cooling ef-ficiencies and capacities.

Completely Tested — Blower coil units are thoroughly testedwith matching outdoor units in the Lennox Research Labora-tory environmental test room which meet American Societyof Heating, Refrigeration and Air-Conditioning Engineers(ASHRAE) Standard 37 requirements. The rating test condi-tions are those included in Air-Conditioning and Refrigera-tion Institute (ARI) Standard test conditions while operatingat rated voltage and air volumes. Units and components with-in are bonded for grounding to meet safety standards forservicing required by Underwriter’s Laboratories (U.L.) andthe International Electrotechnical Commission (I.E.C.). Blow-er performance data is from actual unit tests conducted in theLennox air test chamber.

Cabinet — Cabinet is constructed of heavy gauge galvanizedsteel. A five station metal wash preparation assures a perfectbonding surface for the finish coat of baked-on enamel. Cabi-net is completely lined with thick fiberglass insulation result-ing in quiet and efficient operation due to the excellent sounddeadening and insulating qualities of fiberglass. Large re-movable panels are provided for complete service access.Electrical inlets are conveniently located in the cabinet.

Drain Pan — Deep, corrosion resistant drain pan isconstructed of heavy gauge galvanized steel. Equipped withtwin drain connections on both sides of cabinet as addedprotection from overflow. Dual galvanized pipe drain outletsextend outside the cabinet for ease of connection.

Belt Drive Blowers — CB17/CBH17-95V models are equippedwith a single blower, CB17/CBH17-135V, -185V & 275V modelshave dual blowers. Centrifugal belt driven blowers deliverlarge air volumes quietly and with low power consumption.Blower wheels are heavy duty, with forward curved bladesand double inlet. Wheels are statically and dynamically bal-anced to eliminate vibration and designed to give maximumair delivery. Bearings are heavy duty, self aligning, perma-nently sealed and lubricated. All moving parts (blowerwheels, drives and motor) are mounted on a rugged frame,resiliently mounted and isolated from the rest of the cabinet.Motor mounting frame allows simple belt adjustment andmotor mounting. Adjustable motor pulley provides variablespeed adjustments. A choice of motor outputs and drives areavailable and must be ordered extra. See drive kit table.

Dual Circuit Copper Tube Coil — Extra large surface area ofLennox designed coil provides maximum cooling efficiency,excellent heat transfer and low air resistance. Coil is face splitwith separate circuits, each circuit has its separate expansionvalve. Precise circuiting gives uniform refrigerant distribu-tion. Lennox fabricated coil is constructed of precisely spacedripple-edged aluminum fins fitted to durable seamless cop-per tubes. Fins are strengthened to resist bending and areequipped with collars that grip tubing for maximum contactarea. Flared tubing connections and silver soldering providetight, leakproof joints. Long life copper tubing is corrosion-re-sistant and easy to field service. Coil is thoroughly factorytested under high pressure to insure leakproof construction.

Expansion Valve — Factory installed and piped. Dual cir-cuited coils have two expansion valves, one for each coil sec-tion. Valves are sized for best performance.

Refrigerant Piping Connections — Refrigerant line inlets areprovided on both sides of the cabinet. Refrigerant lines re-quire sweat connections and are made internal to the cabinet.

Air Filters — 1 inch (25 mm) thick throwaway fiberglass mediafilters are furnished as standard. Filter rack is adjustable to ac-commodate up to two inch (51 mm) thick throwaway or clean-able optional filters. Filter rack design permits quick and easyremoval of filters for servicing.

OPTIONAL ACCESSORIES (Must Be Ordered Extra)

EMD17M Series Economizer Damper Section (Optional) —Factory assembled and wired economizer dampers and con-trols are available for field installation. Heavy gauge steelcabinet has a baked-on enamel finish and is completely insu-lated with thick matte faced fiberglass insulation. Large re-movable panels on both sides of cabinet provide completeservice access. Mounting flanges provide ease of connectionto unit. Flanges on outdoor air opening and return air openingpermit easy duct connection. Economizer has mechanicallylinked outdoor air and recirculated air dampers. Formeddampers rotate smoothly in nylon bearings. Outdoor airdampers are reinforced and gasketed for tight seal and quietoperation. Damper linkage and shafts are plated. The posi-tioning of the dampers is accomplished by a 24 volt fully mod-ulating electronic spring return damper motor with adjust-able minimum position potentiometer and controlled by theroom thermostat, adjustable mixed air sensor and adjustableenthalpy control. The enthalpy control allows 0 to 100% out-door air to be used for ”free cooling” when outdoor tempera-ture and humidity are acceptable.

Differential Enthalpy Control (Optional For EMD17M-95 andEMD17M-135 only) — A solid-state return air enthalpy sensoris available to be used with the outdoor air enthalpy control todetermine which air has the lowest enthalpy. The air with thelowest enthalpy will be selected. Return air enthalpy sensor(54G44) field installs in the economizer damper section andmust be ordered extra.

Heat Pump Check Valve Kit (Optional) — Field installed kitcontains check valves with connecting tubing, sweat connec-tions. Kit must be ordered extra. See Specifications Table.

CBH17 Suspension Kits (Optional For CBH17-95V &CBH17-135V only) — Provides support of units in sus-pended horizontal applications. Kit consists of 2 angle ironchannels with holes at each end. CBH17-95V usesLB-50866CA (44F93), 60 inches (1.5 m) long, andCBH17-135V uses LB-50866CB (44F94), 72 inches (1.8 m)long. Kits are not available for the CBH17-185V &CBH17-275V models and must be field provided.

— 2 —

Page 3: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

OPTIONAL ACCESSORIES (Must Be Ordered Extra)

EH17 Series Electric Heat (Optional) — Furnished in a sepa-rate add-on matching cabinet. Bolts, nuts and washers are fur-nished to secure cabinets together. Holes are pre-punched.Cabinet is constructed of heavy gauge galvanized steel with abaked-on enamel finish. Completely insulated with thick fiber-glass insulation. Removable panel permits service access.Electrical inlet provides wiring entry. Factory installed electricheaters are available in several sizes, see electric heat datatable. Helix wound nichrome heating elements are exposeddirectly in the air stream resulting in instant heat transfer, low-er coil temperatures and long service life. Elements are accu-rately located and insulated from the heavy gauge steel sup-port frame by high quality insulators. Time delays bring theelements on and off the line in sequence and equal incre-ments in response to demand with a time delay between eachelement. Elements are equipped with individual limit controlsproviding positive protection in case of excessive overheat-ing. Heaters may be two stage controlled with each stage be-ing energized only when required. Heaters must be orderedextra. Sub-fusing, contactors, control relays, 24 volt trans-former, terminal block and blower motor contactor are fur-nished as standard equipment.

HW17 Series Hot Water Heat (Optional) — Furnished in a sep-arate add-on matching cabinet. Bolts, nuts and washers arefurnished to secure cabinets together. Holes are pre-punched. Cabinet is constructed of heavy gauge galvanizedsteel with a baked-on enamel paint finish. Completely insu-lated with thick matte faced fiberglass insulation. Removablepanel permits service access. Piping inlets are furnished inboth sides of cabinet. Factory installed Lennox designed andbuilt coil has large face area, excellent heat transfer and lowair resistance. Constructed of precisely spaced ripple-edgedaluminum fins fitted to durable copper tubes. Fins areequipped with collars that grip tubing for maximum contactarea. Flared shoulder tubing connections and silver solderingprovide tight, leakproof joints. Long life copper tubing is easyto field service. Coil is thoroughly factory tested under highpressure to insure leakproof construction. Must be orderedextra. Valves and pumps must be furnished by installer.

Outdoor Thermostat (Optional) — An outdoor thermostatcan be used to lock out some of the heating elements on unitswhere two stage control is applicable. Outdoor thermostatmaintains the heating load on the low power input as long aspossible before allowing the full power load to come on theline. Thermostat LB-29740BA (56A87) and mounting boxM-1595 (31461) must be ordered extra.

SPG17 and SPGH17 Supply Air Plenum & Grille (Optional) —Constructed of heavy gauge galvanized steel with a baked-onenamel paint finish. Completely lined with thick matte facedfiberglass insulation. Equipped with anodized aluminumgrille with double deflection and four-way directional controlin vertical and horizontal planes for precise control of dis-charge air. Bolts, nuts and washers are furnished to secureplenum to cabinet. Must be ordered extra.

”00” Spacer Cabinets (Optional) — Matching ”00” emptyspacer cabinets give additional height required for plenumand grille in up-flo store cooler applications and providesspacing between unit and plenum and grille in horizontalinstallations not using an electric heat or hot water heat cabi-net. Constructed of heavy gauge galvanized steel with abaked-on enamel paint finish. Completely lined with thickmatte faced fiberglass insulation. Must be ordered extra.

RG17 Return Air Grille (Optional) — Anodized aluminumgrille field installs in return air opening of blower-coil unit.Must be ordered extra.

DRIVE KIT SELECTIONUsing Total Air Volume and System External Static Pressure needed for unit requirements,determine from blower performance table blower speed and blower motor output required.

UnitModel

Number

Drive KitModel

Number

*NominalMotorOutput

Blower SpeedRev./Min.

at 1440 Rev./Min.

ShippingWeight

Electrical Data380/420V — 50hz — 3 phase

Number Numberhp kW Motor Speed lbs. kg Full Load (A) Locked Rotor (A)

CB17-95VCBH17-95V

DKB17-95/135-1.5–5 1.5 1.1 600 — 780 42 19 2.7 17.8

CB17-135VCBH17-135V �DKB17-95/135-2–9 2 1.5 710 — 890 49 22 3.3 21.6

CB17-185VCBH17 185V

DKB17185/275-2–16 2 1.5 520 — 640 49 22 3.3 21.6CBH17-185VCB17-275V DKB17185/275-3–17 3 2.2 590 — 710 55 25 5.0 28.0CB17 275V

CBH17-275V DKB17185/275-5–18 5 3.7 700 — 850 74 34 7.8 50.0*Service Factor = 1.15�Drive Kit includes belt to be field installed in place of belt shipped in blower Coil unit.NOTE — Motors do not have internal overload protectors.NOTE — Magnetic Starters and Overload Protectors are available and must be ordered extra. See Lennox Price Book.

INSTALLATION CLEARANCES

Model NumberCB17-95V

CBH17-95VCB17-135V

CBH17-135VCB17-185V

CBH17-185VCB17-275V

CBH17-275V

Cabinet 0 inch (0 mm) 0 inch (0 mm) 0 inch (0 mm) 0 inch (0 mm)

Plenum 1 inch (25 mm) 1 inch (25 mm) 1 inch (25 mm) 1 inch (25 mm)

Duct *1 inch (*25 mm) **1 inch (**25 mm) *1 inch (*25 mm) *1 inch (*25 mm)

*Within 3 feet (90 cm) of the unit.**Within 4 feet (122 cm) of the unit.

— 3 —

Page 4: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

SPECIFICATIONS

Model NumberCB17-95V

CBH17-95VCB17-135V

CBH17-135VCB17-185V

CBH17-185VCB17-275V

CBH17-275V

Nominal Cooling Capacity — Tons (kW) 7-1/2 (26) 10 (35) 15 (53) 20 (70)

Blower wheel nominal diameter x width — in. (mm) (1) 15 x 15 (381 x 381) (2)15 x 9 (381 x 229) (2) 15 x 11 (381 x 279) (2) 15 x 15 (381 x 381)

Blower motor output and blower drives See Drive Kit Table (shipped separately)

*Number and size of air filters

in. (2) 16 x 25 x 1(1) 20 x 25 x 1 (4) 16 x 25 x 1 (6) 16 x 20 x 1

(2) 16 x 25 x 1(6) 20 x 20 x 1(2) 20 x 25 x 1

*Number and size of air filters

mm (2) 406 x 635 x 25(1) 508 x 635 x 25 (4) 406 x 635 x 25 (6) 406 x 508 x 25

(2) 406 x 635 x 25(6) 508 x 508 x 25(2) 508 x 635 x 25

Condensate drain connection — in. (2) 1-1/4 (2) 1-1/4 (2) 1-1/4 (2) 1-1/4

female pipe thread mm (2) 31.8 (2) 31.8 (2) 31.8 (2) 31.8

Refrigerant HCFC-22

Net face area — ft.2 (m2) 7.98 (0.74) 10.07 (0.94) 17.38 (1.61) 23.16 (2.15)

Number of rows 4 4 4 4

Tube outside diameter — in. (mm) 3/8 (9.5) 3/8 (9.5) 1/2 (12.7) 1/2 (12.7)

Evapora-tor

Fins per inch (fins per m) 14 (551) 13 (512) 13 (512) 13 (512)torCoil Suction line connection — in. 1-3/8 1-3/8 (2) 1-1/8 (2) 1-3/8

outside diameter (sweat) mm 34.9 34.9 (2) 28.5 (2) 34.9

Liquid line connection — in. (2) 3/8 (2) 3/8 (2) 1/2 (4) 3/8qoutside diameter (sweat) mm (2) 9.5 (2) 9.5 (2) 12.7 (4) 9.5

**Shipping weight — lbs. (kg) Up-flow 350 (159) 418 (190) 720 (327) 815 (370)g g g(�2 packages) Horizontal 312 (142) 379 (172) 760 (345) 860 (390)

� Optional Accessories (Must Be Ordered Extra) �

Electric Heat Model Number EH17-95 EH17-135 EH17-185/275

Model Number HW17-95 (41F20) HW17-135 (41F21) HW17-185/275 (27G75)

Shipping weight — lbs. (kg) 95 (43) 104 (47) 160 (73)

��Heating capacity — Btuh (kW) 185 000 (54.2) 257 000 (75.3) 405 000 (118.7) 462 000 (135.4)

Hot Wa- Net face area — ft.2 (m2) 6.4 (0.59) 8.5 (0.79) 15.6 (1.45)

terCoil Tube outside diameter — in. (mm)

number of rows1/2 (12.7)

21/2 (12.7)

21/2 (12.7)

2

Fins per inch (fins per m) 12 (472) 12 (472) 12 (472)

Water line connections Inlet 1-3/8 (35) sweat 1-3/8 (35) sweat 1-5/8 (41) sweat

Outside diameter — in. (mm) Outlet 1-3/8 (35) sweat 1-3/8 (35) sweat 1-5/8 (41) sweat

Supply Air Plenum and GrilleUp-flow SPG17-95 (68F08)

124 lbs. (56 kg)SPG17-135 (68F09)

148 lbs. (67 kg)SPG17-185/275 (25G89)

242 lbs. (110 kg)pp y(shipping weight)

Horizontal SPGH17-95 (68F10)41 lbs. (19 kg)

SPGH17-135 (68F11)50 lbs. (23 kg)

SPGH17-185/275 (25G88)86 lbs. (39 kg)

Return Air Grille (shipping weight) RG17-95 (68F14)29 lbs. (13 kg)

RG17-135 (68F15)37 lbs. (17 kg)

RG17-185 (25G97)65 lbs. (29 kg)

RG17-275 (25G98)82 lbs. (37 kg)

Empty Spacer Cabinet (shipping weight) CB17-95-00 (50F06)55 lbs. (25 kg)

CB17-135-00 (50F07)60 lbs. (27 kg)

CB17-185/275-00 (27G76)82 lbs. (37 kg)

Economizer Dampers (shipping weight) EMD17M-95 (74G20)145 lbs. (66 kg)

EMD17M-135 (74G21)185 lbs. (84 kg)

EMD17M-185 (43G63)395 lbs. (179 kg)

EMD17M-185 (43G64)542 lbs. (264 kg)

Differential Enthalpy Control 54G44

CBH17 Horizontal Suspension Kit (shipping weight) LB-50866CA (44F93)21 lbs. (10 kg)

LB-50866CB (44F94)25 lbs. (11 kg) Not Available

Heat Pump Check Valve Kit LB-51486CA (53F21) LB-51486CA (53F21) LB-55674CA (29G19) LB-51486CB (29G20)

*Standard filters are 1 inch (25 mm) thick. 2 inch (51 mm) filters may also be used.**Weight does not include motor and drives.�Packages consist of: blower coil unit and drive kit with motor and drives.��Rated at 180�F (82�C) supply water temperature, 70�F (21�C) entering air temperature, 20�F (11�C) water temperature drop and 450 cfm air volume per ton (60 L/sair volume per kW) of cooling capacity. See Hot Water Capacity Curves for heating capacities at different conditions.

— 4 —

Page 5: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

BLOWER DATA

CB17-95V AND CBH17-95V BLOWER PERFORMANCE

AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)

AirVolume

cfm0 (0) 0.2 (50) 0.4 (100) 0.6 (150) 0.8 (200) 1.0 (250) 1.25 (310) 1.5 (375)

cfm(m3/s) Rev/ hp

Min (W)Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

2000(0.95)

0.25375

(186)0.35

440(261)

0.405150

(298)0.50

590(373)

0.60650

(448)0.75

720(560)

1.05790

(783)1.30

850(970)

2500(1.20)

0.35425

(261)0.40

500(298)

0.50560

(373)0.65

630(485)

0.80700

(597)1.00

760(746)

1.30830

(970)1.40

880(1044)

3000(1.40)

0.55490

(410)0.60

560(448)

0.75625

(560)0.95

690(709)

1.15750

(858)1.30

800(970)

1.55860

(1156)1.80

925(1343)

3500(1.65)

0.85575

(634)0.95

620(709)

1.05685

(783)1.30

740(970)

1.50800

(1119)1.65

840(1231)

1.95910

(1455)2.20

970(1641)

4000(1.90)

1.30650

(970)1.40

700(1044)

1.60750

(1194)1.75

800(1306)

1.95850

(1455)2.15

900(1604)

- - - - - - - -

NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.

CB17-135V AND CBH17-135V BLOWER PERFORMANCE

AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)

AirVolume

cfm0 (0) 0.2 (50) 0.4 (100) 0.6 (150) 0.8 (200) 1.0 (250) 1.25 (310) 1.5 (375)

cfm(m3/s) Rev/ hp

Min (W)Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

3000(1.40)

0.30425

(224)0.45

500(336)

0.60575

(448)0.80

650(597)

1.05725

(783)1.30

790(970)

1.55860

(1156)1.85

925(1380)

3500(1.65)

0.50475

(373)0.60

550(448)

0.80620

(597)1.05

680(793)

1.25750

(933)1.55

820(1156)

1.95900

(1455)2.10

950(1567)

4000(1.90)

0.75525

(560)0.85

595(634)

1.10665

(821)1.30

725(970)

1.55790

(1156)1.90

850(1417)

2.15920

(1604)- - - -

4500(2.10)

1.00580

(746)1.15

650(858)

1.40715

(1044)1.70

755(1268)

1.95840

(1455)2.25

890(1679)

- - - - - - - -

5000(2.35)

1.40650

(1044)1.55

710(1156)

1.80760

(1343)2.15

825(1604)

- - - - - - - - - - - - - - - -

NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.

CB17-185V AND CBH17-185V BLOWER PERFORMANCE

AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)

AirVolume

cfm0.1 (25) 0.2 (50) 0.3 (75) 0.4 (100) 0.5 (125) 0.6 (150) 0.7 (175) 0.8 (200) 0.9 (225) 1.0 (250) 1.25 (310)

cfm(m3/s) Rev/ hp

Min (W)Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

5000(2.35) - - - - - - - -

1.00500

(746)1.05

530(783)

1.20560

(895)1.50

630(1119)

1.55640

(1156)1.65

660(1231)

1.75685

(1306)1.90

720(1417)

2.25800

(1679)

5500(2.60) - - - -

1.05495

(783)1.20

525(895)

1.35555

(1007)1.50

585(1119)

1.65635

(1231)1.70

650(1268)

1.85680

(1380)2.05

710(1529)

2.20740

(1641)2.55

825(1902)

6000(2.85)

1.20490

(895)1.30

520(970)

1.45550

(1082)1.60

580(1194)

1.75610

(1306)1.90

640(1417)

2.10675

(1567)2.20

705(1641)

2.35730

(1753)2.50

760(1865)

2.90840

(2163)

6500(3.05)

1.45515

(1082)1.60

550(1194)

1.75575

(1306)1.90

610(1417)

2.05635

(1529)2.25

670(1679)

2.35700

(1753)2.50

725(1865)

2.65750

(1977)2.75

780(2052)

3.30870

(2462)

7000(3.30)

1.75550

(1306)1.90

575(1417)

2.05605

(1529)2.25

635(1679)

2.35665

(1753)2.55

690(1902)

2.65720

(1977)2.85

745(2126)

3.00775

(2238)3.20

810(2387)

- - - -

7500(3.55)

2.05575

(1529)2.25

605(1679)

2.55635

(1828)2.45

660(1902)

2.75690

(2052)2.90

720(2163)

3.05740

(2275)3.25

775(2425)

3.40800

(2536)3.55

835(2648)

- - - -

8000(3.80)

2.40605

(1790)2.60

635(1940)

2.80660

(2089)2.95

690(2201)

3.15720

(2350)3.30

740(2462)

3.50775

(2611)3.65

800(2723)

3.85835

(2872)4.10

870(3059)

- - - -

NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.

— 5 —

Page 6: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

BLOWER DATACB17-275V AND CBH17-275V BLOWER PERFORMANCE

AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)

AirVolume

cfm0.1 (25) 0.2 (50) 0.3 (75) 0.4 (100) 0.5 (125) 0.6 (150) 0.7 (175) 0.8 (200) 0.9 (225) 1.0 (250) 1.25 (310)

cfm(m3/s) Rev/ hp

Min (W)Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

Rev/ hpMin (W)

6500(3.05)

1.35515

(1007)1.45

535(1082)

1.70570

(1268)1.80

585(1343)

1.90615

(1417)2.00

635(1492)

2.25670

(1679)2.30

690(1716)

2.45720

(1828)2.50

740(1865)

2.95805

(2201)7000(3.30)

1.55525

(1156)1.70

545(1268)

1.85575

(1380)2.00

600(1492)

2.15625

(1604)2.30

650(1716)

2.45680

(1828)2.55

705(1902)

2.70730

(2014)2.80

755(2089)

3.25820

(2425)

7500(3.55)

1.70530

(1268)1.85

555(1380)

2.05585

(1529)2.25

615(1679)

2.30630

(1716)2.55

665(1902)

2.65685

(1977)2.80

720(2089)

2.90740

(2163)3.15

770(2350)

3.60825

(2686)8000(3.80)

1.90540

(1417)2.15

565(1604)

2.25590

(1679)2.45

625(1828)

2.65650

(1977)2.80

675(2089)

2.95705

(2201)3.05

730(2275)

3.35760

(2499)3.40

785(2536)

3.95840

(2947)

8500(4.00)

2.15555

(1604)2.30

580(1714)

2.55610

(1902)2.70

630(2014)

2.90665

(2163)3.10

690(2313)

3.20720

(2387)3.35

745(2499)

3.60775

(2686)3.80

805(2835)

4.40855

(3282)

9000(4.25)

2.35565

(1753)2.60

595(1940)

2.85630

(2126)3.05

655(2275)

3.20680

(2387)3.40

710(2536)

3.55735

(2648)3.75

760(2798)

4.00795

(2894)4.20

820(3133)

4.70870

(3506)9500(4.50)

2.65585

(1977)2.95

620(2201)

3.15640

(2350)3.05

670(2275)

3.55700

(2648)3.75

730(2798)

3.90755

(2909)4.15

785(3096)

4.40815

(3282)4.65

840(3469)

4.90880

(3655)

10 000(4.70)

3.05610

(2275)3.30

635(2462)

3.45660

(2574)3.30

690(2462)

3.90720

(2909)4.10

750(3059)

4.35775

(3245)4.55

805(3394)

4.85835

(3618)5.15

860(3842)

- - - -

10 500(4.95)

3.35625

(2499)3.55

655(2648)

3.80685

(2835)4.05

715(3021)

4.30745

(3208)4.60

775(3432)

4.75800

(3544)5.05

830(3767)

5.40860

(4028)5.70

880(4252)

- - - -

NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.

SUPPLY AIR PLENUM AND GRILLE AIR THROW DATA

Blower Coil and Supply Air Volume*Effective Throw — ft. (m)

Blower Coil and SupplyPlenum and Grille

M d l N b

Air Volume�10 ft. (3.0 m) Ceiling

Model Numbercfm m3/s Front of Unit 45� From Unit

2000 0.95 40 (12.2) 31 (9.4)�CB17-95V With

SPG17 95 or2500 1.20 46 (14.0) 36 (11.0)

SPG17-95 orCBH17-95V With 3000 1.40 53 (16.2) 41 (12.5)CBH17 95V With

SPGH17-95 3500 1.65 56 (17.1) 45 (13.7)

4000 1.90 63 (19.2) 50 (15.2)

3000 1.40 50 (15.2) 35 (10.7)

�CB17-135V With 3500 1.65 55 (16.8) 40 (12.2)�CB17 135V With

SPG17-135 or 4000 1.90 61 (18.6) 44 (13.4)CBH17-135V With

SPGH17 1354500 2.10 67 (20.4) 50 (15.2)

SPGH17-1355000 2.35 71 (21.6) 56 (17.1)

5500 2.60 74 (22.6) 61 (18.6)

5000 2.35 30 (9.1) 19 (5.8)

5500 2.60 31 (9.4) 19 (5.8)�CB17-185V WithSPG17 185/275 or

6000 2.85 35 (10.7) 22 (6.7)SPG17-185/275 orCBH17-185V With 6500 3.05 36 (11.0) 22 (6.7)CBH17 185V WithSPGH17-185/275 7000 3.30 36 (11.0) 22 (6.7)

7500 3.55 39 (11.9) 24 (7.3)

8000 3.80 41 (12.5) 26 (7.9)

6500 3.05 36 (11.0) 22 (6.7)

7000 3.30 36 (11.0) 22 (6.7)

7500 3.55 39 (11.9) 24 (7.3)�CB17-275V WithSPG17 185/275 or

8000 3.80 41 (12.5) 26 (7.9)SPG17-185/275 orCBH17-275V With 8500 4.00 43 (13.1) 27 (8.2)CBH17 275V WithSPGH17-185/275 9000 4.25 46 (14.0) 29 (8.8)

9500 4.50 49 (14.9) 30 (9.1)

10 000 4.70 53 (16.2) 33 (10.1)

10 500 1.95 55 (16.8) 34 (10.4)*Effective throw is terminated at a point where conditioned air reaches a level of 3 feet (90 cm) above the floor or where velocityhas decreased to 50 feet per minute (0.25 m/s.�Ceiling height not applicable to CB17 Up-Flow models.

— 6 —

Page 7: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

BLOWER DATA

ACCESSORY AIR RESISTANCE — CB17-95V, CBH17-95V, CBH17-135V AND CB17-135V

M d l Air VolumeTotal Resistance — inches water gauge (Pa)

ModelNumber

Air VolumeHW17 Hot Water Coil EMD17M Economizer Dampers

Number

cfm m3/s HW17-95 HW17-135 EMD17M-95 EMD17-135

2000 0.95 0.13 (32) - - - - 0.02 (5) - - - -

CB17 95V2500 1.20 0.16 (40) - - - - 0.04 (10) - - - -

CB17-95VCBH17-95V 3000 1.40 0.18 (45) - - - - 0.07 (17) - - - -CBH17 95V

3500 1.65 0.20 (50) - - - - 0.09 (22) - - - -

4000 1.90 0.24 (60) - - - - 0.12 (30) - - - -

3000 1.40 - - - - 0.14 (350 - - - - 0.03 (70

CB17 135V3500 1.65 - - - - 0.17 (42) - - - - 0.05 (12)

CB17-135VCBH17-135V 4000 1.90 - - - - 0.18 (45) - - - - 0.07 (17)CBH17 135V

4500 2.10 - - - - 0.20 (50) - - - - 0.09 (22)

5000 2.35 - - - - 0.24 (60) - - - - 0.13 (32)NOTE — Electric heat section, plenum and grilles have no appreciable air resistance.

ACCESSORY AIR RESISTANCE — CB17-185V, CBH17-185V, CBH17-275V AND CB17-275V

M d l Air VolumeTotal Resistance — inches water gauge (Pa)

ModelNumber

Air VolumeHW17 Hot Water Coil EMD17M Economizer Dampers

Number

cfm m3/s HW17-185/275 EMD17M-185 EMD17-275

5000 2.35 0.08 (20) 0.04 (10) - - - -

5500 2.60 0.10 (25) 0.05 (12) - - - -

CB17 185V6000 2.85 0.11 (27) 0.06 (15) - - - -

CB17-185VCBH17-185V 6500 3.05 0.13 (32) 0.07 (17) - - - -CBH17 185V

7000 3.30 0.15 (37) 0.08 (20) - - - -

7500 3.55 0.17 (42) 0.09 (22) - - - -

8000 3.80 0.18 (45) 0.10 (25) - - - -

6500 3.05 0.13 (32) - - - - 0.04 (10)

7000 3.30 0.15 (37) - - - - 0.05 (12)

7500 3.55 0.17 (42) - - - - 0.06 (15)

CB17 275V8000 3.80 0.18 (45) - - - - 0.07 (17)

CB17-275VCBH17-275V 8500 4.00 0.21 (52) - - - - 0.08 (20)CBH17 275V

9000 4.25 0.23 (57) - - - - 0.08 (20)

9500 4.50 0.25 (62) - - - - 0.09 (22)

10 000 4.70 0.27 (67) - - - - 0.10 (25)

10 500 4.95 0.30 (75) - - - - 0.11 (27)NOTE — Electric heat section, plenum and grilles have no appreciable air resistance.

HOT WATER COIL PRESSURE DROP

Flow Rate Pressure Drop — feet of water (kPa)

gpm L/s HW17-95 HW17-135 HW17-185/275

15 0.95 0.93 (3.0) 1.18 (3.5) - - - -

20 1.25 1.56 (4.5) 1.99 (6.0) 0.55 (1.5)

25 1.60 2.33 (7.0) 2.97 (9.0) 0.82 (2.5)

30 1.90 3.24 (9.5) 4.13 (12.5) 1.14 (3.5)

35 2.20 4.27 (12.5) 5.44 (16.0) 1.50 (4.5)

40 2.50 5.44 (16.0) 6.92 (20.5) 1.91 (5.5)

45 2.85 6.72 (20.0) 8.56 (25.5) 2.36 (7.0)

50 3.15 - - - - - - - - 2.86 (8.5)

55 3.45 - - - - - - - - 3.39 (10.0)

60 3.80 - - - - - - - - 3.97 (12.0)

65 4.10 - - - - - - - - 4.58 (13.5)

70 4.40 - - - - - - - - 5.23 (15.5)

— 7 —

Page 8: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

OPTIONAL ELECTRIC HEAT DATA

NOTE — Refer to local electrical codes to determine wire, fuse and disconnect requirements. Use wires suitable for at least 75�C (167�F).

ECH17 ELECTRIC HEAT FOR CB17/CBH-95V and -135V

Electric HeatNumber Number

HeatingElectric HeatModel Number

and

Numberof

Numberof

VoltsInput

gCapacity

andShipping Weight

oElements

oSteps

Input

kW Btuh

ECH17-95-15 380 9.4 32 100ECH17 95 15(63F22)

170 lb (77 k )1 2 400 10.4 35 500

170 lbs. (77 kg)1 2

420 11.2 38 200ECH17-95-30 380 18.8 64 100

(63F23)176 lb (80 k )

2 1 400 20.8 71 000176 lbs. (80 kg) 420 22.4 76 400ECH17-95-45 380 28.2 96 100

(63F24)182 lb (83 k )

3 �2 400 31.3 106 800182 lbs. (83 kg) 420 33.6 114 600ECH17-135-15 380 9.4 32 100

(63F34)193 lb (88 k )

1 1 400 10.4 38 200193 lbs. (88 kg) 420 11.2 38 200ECH17-135-30 380 18.8 64 100

(63F35)200 lb (91 k )

2 � 400 20.8 71 000200 lbs. (91 kg) 420 22.4 76 400ECH17-135-45 380 28.2 96 200

(63F36)207 lb (94 k )

3 �2 400 31.3 106 800207 lbs. (94 kg) 420 33.6 114 600

ECH17-135-60 380 37.6 128 300ECH17 135 60(63F37) 4 �2 400 41.7 142 300

214 lbs. (97 kg)�

420 45.0 153 600�May be used with two stage control.

ECH17 ELECTRIC HEAT FOR CB17/CBH-185V and -275V

Electric HeatNumber Number

HeatingElectric HeatModel Number

d

Numberof

Numberof

VoltsI t

gCapacity

andShipping Weight

oElements

oSteps

InputkW Btuh

ECH17 185/275 15380 9.4 32 100

ECH17-185/275-15(27G01)

193 lbs (88 kg)1 1 400 10.4 35 500

193 lbs. (88 kg)420 11.2 38 200

ECH17 185/275 30380 18.8 64 100

ECH17-185/275-30(27G02)

200 lbs (91 kg)2 � 400 20.8 71 000

200 lbs. (91 kg)420 22.4 76 400

ECH17 185/275 45380 28.2 96 200

ECH17-185/275-45(27G03)

207 lbs (94 kg)3 �2 400 31.3 106 800

207 lbs. (94 kg)420 33.6 114 600

ECH17 185/275 60380 37.6 128 300

ECH17-185/275-60(27G04)

214 lbs (97 kg)4 �2 400 41.7 142 300

214 lbs. (97 kg)420 45.0 153 600

�May be used with two stage control.

GUIDE SPECIFICATIONS

Prepared for the guidance of architects, consulting engineers andmechanical contractors.

General — Furnish and install a blower-coil-filter unit. The unit shallbe a standard product of a firm regularly engaged in the manufactureof heating-cooling equipment.

The installed weight shall not be more than . . . . . . . lbs. (kg) Unit shallhave a width of not more than . . . . . . . inches (mm), a depth of notmore than . . . . . . . inches (mm) and an overall height of not more than .. . . . . . inches (mm).

The equipment shall be shipped assembled ready for necessary fieldconnections. Blower motor and pulley shall be shipped separate andfield installed. CB17 models shall be capable of up-flo air distribution.CBH17 models shall have horizontal air distribution.

Cooling System — The total certified cooling capacity shall not beless than . . . . . . . . Btuh (kW) with an evaporator air volume of . . . . . . .cfm (m3/s), an entering wet bulb temperature of . . . . . . . �F ( �C) and . . . . . . . �F ( �C) coil refrigerant evaporating temperature.

The coil shall be non-ferrous construction with aluminum fins ma-chine fitted to copper tubes. The coil shall be dual circuit with each cir-cuit having an expansion valve. Coil shall be factory pressure leaktested. Coil face area shall be not less than . . . . . . . sq. ft. (m2).

Heat Pump Heating System — The total certified heating capacityshall not be less than . . . . . . . Btuh (kW) with an indoor coil air volumeof . . . . . . .. cfm (m3/s), an entering dry bulb temperature of . . . . . . . �F( �C) and a condensing temperature of . . . . . . . �F ( �C).

Air Movers — Centrifugal conditioned air blowers shall have stati-cally and dynamically balanced, forwardly curved, double inletblower wheels, permanently lubricated bearings, adjustable beltdrives and be capable of delivering . . . . . . . cfm at an external staticpressure of . . . . . . .inches water gauge (Pa), requiring not more than. . . . . . . bhp (W) and . . . . . . . rpm. CB17/CBH17-95V models shall beequipped with a single blower. CB17/CBH17-135V, 185V and 275Vmodels shall have dual blowers.

Cabinet — The unit cabinet shall be constructed of galvanized steelwith a baked-on enamel finish. Panels shall be insulated with not lessthan one inch thick fiberglass insulation. Cabinet shall be equippedwith large removable panels providing service access to interior. In-lets shall be provided for refrigerant line and power connection entry.Dual drain connections shall be accessible external to the cabinet.

Air Filters — One inch (25 mm) thick throwaway filters furnished shallhave not less than . . . . . . . sq. ft. (m2) of area. Filter rack shall be capa-ble of holding optional two inch (51 mm) thick throwaway or clean-able filters.

OPTIONAL ACCESSORIES

Additive Electric Heat — The certified total heating capacity output shallbe . . . . . . . . Btuh with . . . . . . . . kw input at . . . . . . . . volts power supply.Optional electric heaters shall be available in a separate matchingcabinet. Heating elements shall be nichrome bare wire exposed di-rectly to the air stream. Time delays shall bring the elements on andoff in sequence with a time delay between each element. Limit con-trols shall provide overload and short circuit protection. Cabinet shallbe constructed of galvanized steel with a baked-on enamel paint fin-ish and insulated with fiberglass insulation. Shall have removable ac-cess panel and electrical inlets.Additive Hot Water Heat — The certified total heating capacity outputshall be . . . . . . . . Btuh (kW) with a heating coil air volume of . . . . . . . cfm(m3/s), at water entering temperature of . . . . . . . �F ( �C) and a flow rateof . . . . . . . gpm (L/s) and an entering air temperature of . . . . . . . �F ( �C).Optional hot water coil shall be available in a separate matching cabi-net. Cabinet shall be constructed of galvanized steel with a baked-onenamel finish and insulated with fiberglass insulation. Shall have re-movable access panel and piping inlet openings. The coil shall benon-ferrous construction with aluminum fins mechanically bondedto copper tubes. Coil shall be factory pressure leak tested. Coil facearea shall be not less than . . . . . . . sq. ft (m2).Economizer Damper Section — Furnish and install complete withcontrols an optional air mixing damper assembly including outdoorair and recirculated air dampers. The assembly shall provide for theintroduction of outside air for minimum ventilation and free cooling.The assembly shall be furnished in a fully insulated heavy gauge gal-vanized steel cabinet with baked-on enamel finish. The damper mo-tor shall be 24 volt, fully modulating electronic spring return. Controlsshall include adjustable mixed air sensor, adjustable minimum posi-tion potentiometer, and adjustable enthalpy control. Optional differ-ential enthalpy control (return air sensor) shall be available forEMD17M-95 and EMD17M-135 models.Supply Air Plenum and Grille — Optional plenum and grille shall beconstructed of galvanized steel with baked-on enamel paint finishand insulated with fiberglass insulation. Shall be equipped with an-odized aluminum discharge air grille with double deflection and four-way directional control in the vertical and horizontal planes.Spacer Cabinets — Optional empty cabinets shall match cabinet sec-tions in size and provide necessary spacing between cabinet sectionsfor varying applications. Shall be constructed of galvanized steel withbaked-on enamel paint finish and insulated with fiberglass insulation.Return Air Grille — Optional anodized grille shall be available for fieldaddition to blower-coil unit.Suspension Kit — Kit shall be available for CBH17-95V andCBH17-135V models in suspended horizontal applications.

— 8 —

Page 9: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

DIMENSIONS — inches (mm)

CB17-95V AND CB17-135V HORIZONTAL MODELS52 (1321)

27(686)

64 (1626)

27(686)

INLET END

SUPPLY END(CB17-135V)

SUPPLY END(CB17-95V)

ELECTRICAL INLET(Either Side)

LIQUID LINEINLETS (2)

(Either Side)

SUCTION (VAPOR)LINE INLETS(Either Side)

AIR FILTERS

16-3/8(416)

18-5/8(473)

12-1/4(311) SUPPLY

AIROPENING

12-7/8(327)

12-7/8(327)

9-1/2(241)

7-3/4(197)

16-3/8(416)

SUPPLY AIROPENINGS ELECTRICAL INLET

(Electric Heat)

47-7/8 (1216) — CB17-95V

59-7/8 (1521) — CB17-135V

2-1/16(52)

24-1/2(622)

1-1/2(38)

RETURNAIR

OPENING

2-1/16(52)

49(1245)

52-1/2(1308)

8 (203)

6 (152)

2 (51)

12-7/8(352)

EXTERNAL STATICPRESSURE TEST HOLE

INDOOR COIL

DRIVE END VIEW

AIR FLOW27 (686)

1 (25) 1 (25)

ELECTRICAL INLET(Electric Heat)

2-1/2(64)

AIRFLOW

BLOWER

45-1/2 (1156) — CB17-95V

57-1/2 (1461) — CB17-135V

2-1/2(64)

3/4 (19) 3/4 (19)

2-1/2(64) 4

(102)

2(51)

4(102)

CONDENSATE DRAIN (Either Side)12-1/4(311)

CB17-185V AND CB17-275V HORIZONTAL MODELS

85 (2159)

19(483)

19(483)

17-3/8(441)

9-3/8(238) 16-5/8

(422)

1 (25)

SUPPLY AIROPENINGS

ELECTRICALINLET

(Electric Heat)

SUPPLY END

AIR FLOW

DRIVE END VIEW

LIQUID LINEINLETS

(Either Side)

1-7/8(48)10-1/2

(267)

D

F

B E

C

C

F

10-5/8(207)

RETURNAIR

OPENING

81-3/4 (2076)

1-5/8(41)

1-5/8(41)

33-1/8(841)

CB17-185VONLY

7/8(22)

10(254)

42-1/8(1070)

CB17-275VONLY

7/8(22)

1 (25)

75-1/2 (1918)

4(102)

4(102)

3/4(19)

3/4(19)

44(1118)

3(76)

47(1194)

SUCTION(VAPOR)

LINE INLETS(Either Side)

INLET VIEW

AIR FLOW

ELECTRICALINLET

INDOOR COIL

AIR FILTERS

CONDENSATEDRAIN

(Either Side)

BLOWERS

A

Model NoA B C D E F

Model No.in. mm in. mm in. mm in. mm in. mm in. mm

CB17-185V 35 889 18-3/8 467 2-1/2 57 12-1/2 318 22-5/8 575 1-1/4 32

CB17-275V 44 1118 22-3/4 578 2–5/8 67 14-1/4 362 22-1/2 572 4-7/8 124

— 9 —

Page 10: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

DIMENSIONS — inches (mm)

CBH17-95V AND CBH17-135V HORIZONTAL MODELS52

(1321)

27(686)16-3/8

(416)18-5/8(473)

12-1/4(311)

SUPPLYAIR

OPENING

64(1626)

27(686)

12-7/8(327)

12-7/8(327)

9-1/2(241)

9-1/2(241)

16-3/8(416)

2-1/4(57)

2-1/4(57) SUPPLY AIR

OPENINGSELECTRICAL

INLET(Electric Heat)

ELECTRICALINLET

(Electric Heat)

AIR

FLOW

47-7/8 (1216) — CBH17-95V

59-7/8 (1521) — CBH17-135V

2-1/16(52)

2-1/16(52)

24-1/2(622)

1-1/4(32)

1-1/4(32)

RETURNAIR

OPENING

IND

OO

R C

OIL

INLET END

SUPPLY END(CBH17-135V)

SUPPLY END(CBH17-95V)

DRIVE END VIEW

36(914)

ELECTRICAL INLET(Either Side)

LIQUID LINEINLETS (2)

(Either Side)

SUCTION (VAPOR)LINE INLET(Either Side)

AIR FILTERS

CONDENSATE DRAIN(Either Side)

2 (51)

6 (152)

6 (152)

2 (51)

12-3/8(314)

13-1/4(337)

EXTERNALSTATIC

PRESSURETEST HOLE

AIRFLOW

BLOWERS

CBH17-185V AND CBH17-275V HORIZONTAL MODELS

85 (2159)

19(483)

19(483)

17-3/8(441)

9-3/8(238)

16-5/8(422)

1 (25) SUPPLY AIROPENINGS

ELECTRICALINLET

(Electric Heat)

AIR

FLOW

82 (2083)1-1/2(38)

1-1/8(29)

7/8(22)

RETURNAIR

OPENING

INLET END

SUPPLY END

DRIVE END VIEW

44(1118)

ELECTRICAL INLET (Either Side) LIQUID LINE INLETS(Either Side)

SUCTION (VAPOR)LINE INLETS(Either Side)

AIR FILTERS

CONDENSATE DRAIN(Either Side)

7/8 (22)

10-1/2(267)

1-1/2(38)

G

A

F

E

B D

C

C

E

10-5/8(207)

AIRFLOW

BLOWERS

Model NoA B C D E F G

Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm

CBH17-185V 35 889 18-3/8 467 2-1/4 57 22-5/8 575 1-1/4 32 13-1/8 333 33 838

CBH17-275V 44 1118 22-11/16 576 2-5/8 67 22-7/16 570 4-7/8 124 14-7/8 378 42 1067

— 10 —

Page 11: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

OPTIONAL ACCESSORY DIMENSIONS — inches (mm)

EH17-95 AND EH17-135 ELECTRIC HEAT SECTION

A A

BC

1 (25)

24(610)

17-5/8(448)

D19-1/2(495)

1 (25)

OUTLET VIEWINLET VIEW FRONT VIEW

OUTDOORAIR

OPENING

INLETAIR

OPENING AIR

FLOW

ELECTRICINLETS

WIRING OUTLET(To Blower Motor)

19 (483) 7/8(22)

27(686)

Model NoA B C D

Model No.in. mm in. mm in. mm in. mm

EH17-95 52 1321 29-7/8 759 14-9/16 370 21-1/16 535

EH17-135 64 1626 39-7/8 1013 18-1/8 470 37-15/16 948

EH17-185/275 ELECTRIC HEAT SECTION

1 (25)

29-7/8(759)

20-1/4(514)

OUTLET VIEWINLET VIEW FRONT VIEW

INLET AIROPENING AIR

FLOW

ELECTRICINLETS

14(356)

1(25)

69-7/8(1775)OPENING

OUTDOOR AIR

35(889)

85 (2159)85 (2159)

20-1/2(521)

20-1/2(521)

14-1/2(368)

14-1

/8 (

359)

16-7/8(429)

WIRING OUTLET(To Blower Motor)

1 (25)

HW17 SERIES HOT WATER HEAT SECTION

OUTDOOR AIROPENING

B

A

C

D

F

14(356)

OUTLET VIEW

1 (25)

J

INLET AIROPENING

A

C

D

INLET VIEW

1 (25)

GH

AIR

FLOW

FRONT VIEW

HO

T W

AT

ER

CO

IL

K

L

MWATER INLET(EITHER SIDE)

WATER OUTLET(EITHER SIDE)

Model No. A B C D E F G H J K L M

HW17-95in. 52 27 41-1/2 25 50 9-1/2 1 1 1 3 2-3/8 4

HW17-95mm 1321 686 1054 635 1270 241 25 25 25 76 60 102

HW17-135in. 64 27 53-1/2 25 62 9-1/2 1 1 1 3 2-3/8 4

HW17-135mm 1626 686 1359 635 1575 241 25 25 25 76 60 102

HW17-185/275in. 85 35 69 33 70 13 13 2 3 2-1/4 2 2-3/4

HW17-185/275mm 2159 889 1753 838 1778 330 330 51 76 57 51 70

— 11 —

Page 12: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

OPTIONAL ACCESSORY DIMENSIONS — inches (mm)

CB17-00 SERIES EMPTY SPACER CABINETS

OUTDOOR AIROPENING

B

A

C

D

F

14(356)

OUTLET VIEW

1 (25)

J

INLET AIROPENING

A

E

D

INLET VIEW

1 (25)

GH

AIR

FLOW

FRONT VIEW

Model NoA B C D E F G H J

Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm

CB17-95-00 52 1321 27 686 41-1/2 1054 25 635 50 1270 9-1/2 241 1 25 1 25 1 25

CB17-135-00 64 1626 27 686 53-1/2 1359 25 635 62 1575 9-1/2 241 1 25 1 25 1 25

CB17-185/275-00 85 2159 35 889 69 1753 33 838 70 1778 13 330 13 330 2 51 3 76

EMD17 SERIES ECONOMIZER DAMPERS

SIDE VIEW

AIR

OUTDOOR

OUTDOORAIR

DAMPERS

C

C A

RETURN AIR

B

E

F

D

B

E

F

D

1 (25) 1 (25)

1 (25)

1 (25)

DAMPERMOTOR

RECIRCULATEDAIR

DAMPERS

END VIEW

TOP VIEW

NOTE — Economizer section may be rotated180� for bottom return air connection.

SUPPLYAIR

TOUNIT

Model NoA B C D E F

Model No.in. mm in. mm in. mm in. mm in. mm in. mm

EMD17-95 48 1219 36 914 25 635 6 152 18 457 3-1/2 89

EMD17-135 60 1524 48 1219 25 635 6 152 18 457 3-1/2 89

EMD17-185 83 2108 60 1524 33 838 11-1/2 292 24 610 4-1/2 114

EMD17-275 83 2108 60 1524 42 1067 11-1/2 292 30 762 6 152

— 12 —

Page 13: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

DIMENSIONS — inches (mm)

CB17 UP-FLOW MODELS WITH OPTIONAL ACCESSORY SECTIONS

Model NoGrille Free Area

Model No.sq. ft. m2

Supply SPG17-95 4.5 0.42SupplyAir

G illSPG17-135 5.6 0.52

Grille SG17-185/275 9.7 0.90

RG17-95 7.3 0.68Return

AirRG17-135 9.0 0.84

AirGrille RG17-185 16.5 1.53

RG17-275 21.2 1.97

Model NoA B C D E F G H

Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm

CB17-95V Basic Unit 51-1/2 1308 – – – – – – – – – – – – – – – – – – 52 1321 27 686 – – – – – – – – – – – –

CB17-135V Basic Unit 51-1/2 1308 – – – – – – – – – – – – – – – – – – 64 1626 27 686 – – – – – – – – – – – –

CB17-185V Basic Unit 47 1194 – – – – – – – – – – – – – – – – – – 85 2159 35 889 – – – – – – – – – – – –

CB17-275V Basic Unit 47 1194 – – – – – – – – – – – – – – – – – – 85 2159 44 1118 – – – – – – – – – – – –

EH17-95 Electric Heat Section – – – – – – 19 483 – – – – – – 94-1/2 2400 – – – – – – – – – – – – 27 686 52 1321

EH17-135 Electric Heat Section – – – – – – 19 483 – – – – – – 94-1/2 2400 – – – – – – – – – – – – 27 686 64 1626

EH17-185/275 Electric Heat Section – – – – – – 14 356 – – – – – – 91 2311 – – – – – – – – – – – – 35 889 85 2159

HW17-95 or CB17-95-00 – – – – – – 14 356 – – – – – – 89-1/2 2273 – – – – – – – – – – – – 27 686 52 1321

HW17-135 or CB17-135-00 – – – – – – 14 356 – – – – – – 89-1/2 2273 – – – – – – – – – – – – 27 686 64 1626

HW17-185/275 or CB17-185/275-00 – – – – – – 14 356 – – – – – – 91 2311 – – – – – – – – – – – – 35 889 85 2159

SPG17-95 Supply Air Plenum & Grille – – – – – – – – – – – – 24 610 – – – – – – – – – – – – – – – – – – 27 686 52 1321

SPG17-135 Supply Air Plenum & Grille – – – – – – – – – – – – 24 610 – – – – – – – – – – – – – – – – – – 27 686 64 1626

SPG17-185/275 Supply Air Plenum & Grille – – – – – – – – – – – – 30 762 91 2311 – – – – – – – – – – – – 35 889 85 2159

CB17 UP-FLOW MODELS WITH ECONOMIZER DAMPER SECTION

Model NoA

Model No.in. mm

EMD17-95 & 135 25 635

EMD17-185 33 838

EMD17-275 42 1067

— 13 —

SUPPLY

AIR

HW17 HOT WATER CABINET“00” EMPTY SPACER CABINETEH17 ELECTRIC HEAT CABINET

CB17 BLOWER COIL UNIT

FRONT VIEW(Without Economizer)

DRIVE SIDE VIEW(Without Economizer)

AIR

RETURN

B

C

A

D

GH

FE

RG17RETURN AIR

GRILLE(Optional)

OPTIONAL

SUPPLY AIR

SPG17SUPPLY AIR PLENUM

AND GRILLE

NOTE — Plenum may be rotated 180�for change in direction of discharge air.

SUPPLY

AIR

EMD17ECONOMIZER

DAMPERSECTION

RETURNAIR

SPG17SUPPLY AIR

PLENUM

HW17 HOT WATER CABINET“00” EMPTY SPACER CABINETEH17 ELECTRIC HEAT CABINET

CB17 BLOWER COIL UNIT

FRONT VIEW(With Economizer)

DRIVE SIDE VIEW(With Economizer)

AIR

OUTDOOR

A

A

Page 14: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

DIMENSIONS — inches (mm)

CBH17 HORIZONTAL MODELS WITH OPTIONAL ACCESSORY SECTIONS

SUPPLY

AIR

EMD17ECONOMIZER

DAMPERSECTION

RETURNAIR

HW17 HOT WATER CABINET“00” EMPTY SPACER CABINETEH17 ELECTRIC HEAT CABINET

CB17 BLOWERCOIL UNIT

RETURN AIR VIEW(With Economizer)

AIR

OUTDOOR

G

G

SPGH17SUPPLY

AIR GRILLE

RG17RETURN AIR

GRILLE(Optional)

C B

D

F

A

A A

RETURN AIR VIEW(Without Economizer)

SUPPLY AIR VIEWOPTIONALRETURN AIR(Rotate 180�)

SPGH17SUPPLY AIR PLENUM

AND GRILLE

4 (102)

E

GRILLE AREA

Model NoGrille Free Area

Model No.sq. ft. m2

SupplySPGH17-95 4.5 0.42

SupplyAir

GrilleSPGH17-135 5.6 0.52

GrilleSPGH17-185/275 9.7 10.90

RG17-95 7.3 0.68

ReturnAir

RG17-135 9.0 0.84Air

Grille RG17-185 16.5 1.53

RG17-275 21.2 1.97

Model NoA B C D E F G

Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm

CBH17-95V Basic Unit 52 1321 – – – – – – 36 914 – – – – – – 27 686 – – – – – – – – – – – –

CBH17-135V Basic Unit 64 1626 – – – – – – 36 914 – – – – – – 27 686 – – – – – – – – – – – –

CBH17-185V Basic Unit 85 2159 – – – – – – 44 1118 – – – – – – 35 889 – – – – – – – – – – – –

CBH17-275V Basic Unit 85 2159 – – – – – – 44 1118 – – – – – – 44 1118 – – – – – – – – – – – –

EH17-95 Electric Heat Section 52 1321 19 483 – – – – – – 59 1499 – – – – – – 27 686 – – – – – –

EH17-135 Electric Heat Section 64 1626 19 483 – – – – – – 59 1499 – – – – – – 27 686 – – – – – –

EH17-185/275 Electric Heat Section 85 2159 14 356 – – – – – – 62 1575 – – – – – – 35 889 – – – – – –

HW17-95 or CBH17-95-00 52 1321 14 356 – – – – – – 54 1375 – – – – – – 27 686 – – – – – –

HW17-135 or CBH17-135-00 64 1626 14 356 – – – – – – 54 1375 – – – – – – 27 686 – – – – – –

HW17-185/275 or CBH17-185/275-00 85 2159 14 356 – – – – – – 62 1575 – – – – – – 35 889 – – – – – –

SPGH17-95 Supply Air Plenum & Grille 52 1321 – – – – – – – – – – – – – – – – – – – – – – – – 27 686 – – – – – –

SPGH17-135 Supply Air Plenum & Grille 64 1626 – – – – – – – – – – – – – – – – – – – – – – – – 27 686 – – – – – –

SPGH17-185/275 Supply Air Plenum & Grille 85 2159 – – – – – – – – – – – – – – – – – – – – – – – – 35 889 – – – – – –

EMD17-95 or EMD17-135 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 25 635

EMD17-185 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 33 838

EMD17-275 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 42 1067

— 14 —

Page 15: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

HOT WATER HEATING CAPACITY CURVES

Water Temp. BtuhDrop (�F) 500 x U.S. gpm

Air Temp. BtuhRise (�F) 1.08 x cfm

Water Temp. kWDrop (�C) 4.19 x L/s (water)

Air Temp. kWRise (�C) 1210 x L/s (air)

=

=

=

=

HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART

Multiply rating in hot water capacity

chart by correction factor below

% Of CorrectionGlycol Factor

0 1.0010 .9720 .9430 .9140 .8750 .84

Water Temp. BtuhDrop (�F) 500 x U.S. gpm

Air Temp. BtuhRise (�F) 1.08 x cfm

Water Temp. kWDrop (�C) 4.19 x L/s (water)

Air Temp. kWRise (�C) 1210 x L/s (air)

=

=

=

=

HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART

Multiply rating in hot water capacity

chart by correction factor below

% Of CorrectionGlycol Factor

0 1.0010 .9720 .9430 .9140 .8750 .84

4000

3500

3000

2500

130 140 150 160 170 180 190 200 210 220 230 240 250 260120Btuh (1000) Btuh (1000)

35 49 45 50 55 60 65 70 75kW kW

TOTAL HEATING CAPACITY1800

1600

1400

1200

1000

L/s

L/s

TO

TA

L A

IR V

OLU

ME

HW17-95 HOT WATER HEATING CAPACITY

cfm

cfm

4500

4000

3500

3000

130 140 150 160 170 180 190 200 210 220 230 240 250 260120Btuh (1000) Btuh (1000)

35 40 45 50 55 60 65 70 75kW kW

TOTAL HEATING CAPACITY

TO

TA

L A

IR V

OLU

ME

HW17-135 HOT WATER HEATING CAPACITY

2000

1800

1600

1400

L/s

L/scfm

cfm

— 15 —

Page 16: ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …

HOT WATER HEATING CAPACITY CURVES

180 200 220 240 260 280 300 320 340 360 380 400 420

50 60 70kW kW80 90 100 110 120 130

TOTAL HEATING CAPACITY

Btuh (1000) Btuh (1000)

7500

7000

6500

6000

5500

3400

3200

3000

2800

2600

2400

L/s

L/scfm

cfm

TO

TA

L A

IR V

OLU

ME

HW17-185/275 HOT WATER HEATING CAPACITY with CB17/CBH17-185V

240 260 280 300 320 340 360 380 400 420 440 460 480

TOTAL HEATING CAPACITY

Btuh (1000) Btuh (1000)

9500

9000

8500

8000

7500

4400

4200

4000

3800

3600

3400

L/s

L/s

cfm

cfm

TO

TA

L A

IR V

OLU

ME

HW17-185/275 HOT WATER HEATING CAPACITY with CB17/CBH17-275V

70 80 90kW kW100 110 120 130 140 150

Water Temp. BtuhDrop (�F) 500 x U.S. gpm

Air Temp. BtuhRise (�F) 1.08 x cfm

Water Temp. kWDrop (�C) 4.19 x L/s (water)

Air Temp. kWRise (�C) 1210 x L/s (air)

=

=

=

=

HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART

Multiply rating in hot water capacity

chart by correction factor below

% Of CorrectionGlycol Factor

0 1.0010 .9720 .9430 .9140 .8750 .84

Water Temp. BtuhDrop (�F) 500 x U.S. gpm

Air Temp. BtuhRise (�F) 1.08 x cfm

Water Temp. kWDrop (�C) 4.19 x L/s (water)

Air Temp. kWRise (�C) 1210 x L/s (air)

=

=

=

=

HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART

Multiply rating in hot water capacity

chart by correction factor below

% Of CorrectionGlycol Factor

0 1.0010 .9720 .9430 .9140 .8750 .84

— 16 —