36
ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana- Champaign [email protected]

ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Embed Size (px)

Citation preview

Page 1: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

ECE 476 Power System Analysis

Lecture 21: Unsymmetrical Faults, System Protection

Prof. Tom Overbye

Dept. of Electrical and Computer Engineering

University of Illinois at Urbana-Champaign

[email protected]

Page 2: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Announcements

• Read Chapters 10 and 11• Design project due date has been extended to Tuesday,

December 8– A useful paper associated with the design project is

T. J. Overbye, "Fostering intuitive minds for power system design," IEEE Power and Energy Magazine, pp. 42-49, July-August 2003.

– You can download it from campus computers at

http://ieeexplore.ieee.org/xpl/abstractAuthors.jsp?arnumber=1213526

2

Page 3: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Unbalanced Fault Analysis

• The first step in the analysis of unbalanced faults is to assemble the three sequence networks. For example, for the earlier single generator, single motor example let’s develop the sequence networks

3

Page 4: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Sequence Diagrams for Example

Positive Sequence Network

Negative Sequence Network

4

Page 5: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Sequence Diagrams for Example

Zero Sequence Network

5

There is no zero sequenceconnection to the machinesbecause of the D-Y transformers

Page 6: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Create Thevenin Equivalents

• To do further analysis we first need to calculate the thevenin equivalents as seen from the fault location. In this example the fault is at the terminal of the right machine so the thevenin equivalents are:

0.2 in parallel with j0.455

0.21 in parallel with j0.475

th

th

Z j

Z j

6

Page 7: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Single Line-to-Ground (SLG) Faults

• Unbalanced faults unbalance the network, but only at the fault location. This causes a coupling of the sequence networks. How the sequence networks are coupled depends upon the fault type. We’ll derive these relationships for several common faults.

• With a SLG fault only one phase has non-zero fault current -- we’ll assume it is phase A.

7

Page 8: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

SLG Faults, cont’d

?

0

0

fa

fb

fc

I

I

I

0

2 0

2

Then since

1 1 1 ?1 1

1 03 3

01

f

ff f f f a

f

I

I I I I I

I

8

Page 9: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

SLG Faults, cont’d

0

2

2

0

1 1 1

1

1

This means

The only way these two constraints can be satisified

is by coupling the sequence networks in series

f fa f a

ffa

ffb

fc f

fa f f f

V Z I

VV

V V

V V

V V V V

9

Page 10: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

SLG Faults, cont’d

With the sequence networks inseries we cansolve for the fault currents(assume Zf=0)

01.05 01.964

(0.1389 0.1456 0.25 3 )

5.8 (of course, 0)

f f ff

ff fs a cb

I j I Ij Z

I j I I

I A I

10

Page 11: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Line-to-Line (LL) Faults

• The second most common fault is line-to-line, which occurs when two of the conductors come in contact with each other. With out loss of generality we'll assume phases b and c.

0

bg

Current Relationships: 0, , 0

Voltage Relationships: V

f f fa c fb

cg

I I I I

V

11

Page 12: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

LL Faults, cont'd

0

2

2

0

2 2

Using the current relationships we get

1 1 1 01

13

1

0

1 1

3 3

Hence

f

ff b

fbf

f

f ff fb b

f f

I

I I

II

I

I I I I

I I

12

Page 13: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

LL Faults, con'td

0

2

2

2

2

Using the voltage relationships we get

1 1 11

13

1

Hence

1313

ff ag

ff bg

ff cg

f ff ag bg

f ff ag f fbg

V V

V V

V V

V V V

V V V V V

13

Recall duringthis fault theb and c phasevoltagesare identical

Page 14: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

LL Faults, cont'd

To satisfy &

the positive and negative sequence networks must

be connected in parallel

f f f fI I V V

14

There is nozero sequencecurrent becausethere is nopath to ground

Page 15: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

LL Faults, cont'd

2

2

Solving the network for the currents we get

1.05 03.691 90

0.1389 0.1456

1 1 1 0 0

1 3.691 90 6.39

3.691 90 6.391

f

fa

fb

fc

Ij j

I

I

I

15

Page 16: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

LL Faults, cont'd

2

2

Solving the network for the voltages we get

1.05 0 0.1389 3.691 90 0.537 0

0.1452 3.691 90 0.537 0

1 1 1 0 1.074

1 0.537 0.537

0.537 0.5371

f

f

fa

fb

fc

V j

V j

V

V

V

16

Page 17: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Double Line-to-Ground Faults

• With a double line-to-ground (DLG) fault two line conductors come in contact both with each other and ground. We'll assume these are phases b and c.

0 ( )f f f f fa cg f cbg bI V V Z I I

17

Page 18: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

DLG Faults, cont'd

0

2

2

0

From the current relationships we get

1 1 1

1

1

Since 0 0

Note, because of the path to ground the zero

sequence current is no longer

ffa

ffb

fc f

fa f f f

II

I I

I I

I I I I

zero.

18

Page 19: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

DLG Faults, cont'd

0

2

2

0 2

2 2

0

From the voltage relationships we get

1 1 11

13

1

Since

Then ( )

But since 1 0 1

ff ag

ff bg

ff bg

f fcg f fbg

ff fbg

ff fbg

V V

V V

V V

V V V V

V V V

V V V

19

Page 20: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

DLG Faults, cont'd

0

0 2

0 2

2

0 0

0 0

( )

Also, since

Adding these together (with -1)

(2 ) with

3

ff fbg

f ff cb

ff f fb

fc f f f

ff f f f f f fbg

f f f f

V V V

Z I I

I I I I

I I I I

V Z I I I I I I

V V Z I

20

Page 21: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

DLG Faults, cont'd

• The three sequence networks are joined as follows

0

1.05 00.1389 0.092( 3 )

4.547 0

ff

VI

j jZ Z Z Z

Assuming Zf=0, then

21

Page 22: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

DLG Faults, cont'd

0

1.05 4.547 90 0.1389 0.4184

0.4184/ 0.1456 2.874

4.547 2.874 1.673

Converting to phase: 1.04 6.82

1.04 6.82

f

f

f f f

fb

fc

V j

I j j

I I I j j j

I j

I j

22

Page 23: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Unbalanced Fault Summary

• SLG: Sequence networks are connected in series, parallel to three times the fault impedance

• LL: Positive and negative sequence networks are connected in parallel; zero sequence network is not included since there is no path to ground

• DLG: Positive, negative and zero sequence networks are connected in parallel, with the zero sequence network including three times the fault impedance

23

Page 24: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Power System Protection

• Main idea is to remove faults as quickly as possible while leaving as much of the system intact as possible

• Fault sequence of events– Fault occurs somewhere on the system, changing the

system currents and voltages – Current transformers (CTs) and potential transformers

(PTs) sensors detect the change in currents/voltages– Relays use sensor input to determine whether a fault has

occurred– If fault occurs relays open circuit breakers to isolate fault

24

Page 25: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Power System Protection

• Protection systems must be designed with both primary protection and backup protection in case primary protection devices fail

• In designing power system protection systems there are two main types of systems that need to be considered:

1. Radial: there is a single source of power, so power always flows in a single direction; this is the easiest from a protection point of view

2. Network: power can flow in either direction: protection is much more involved

25

Page 26: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Radial Power System Protection

• Radial systems are primarily used in the lower voltage distribution systems. Protection actions usually result in loss of customer load, but the outages are usually quite local.

The figure showspotential protectionschemes for a radial system. Thebottom scheme ispreferred since itresults in less lost load.

26

Page 27: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Radial Power System Protection

• In radial power systems the amount of fault current is limited by the fault distance from the power source: faults further down the feeder have less fault current since the current is limited by feeder impedance

• Radial power system protection systems usually use inverse-time overcurrent relays.

• Coordination of relay current settings is needed toopen the correct breakers

27

Page 28: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Inverse Time Overcurrent Relays

• Inverse time overcurrent relays respond instan-taneously to a current above their maximum setting

• They respond slower to currents below this value but above the pickup current value

28

Page 29: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Inverse Time Relays, cont'd

• The inverse time characteristic provides backup protection since relays further upstream (closer to power source) should eventually trip if relays closer to the fault fail

• Challenge is to make sure the minimum pickup current is set low enough to pick up all likely faults, but high enough not to trip on load current

• When outaged feeders are returned to service there can be a large in-rush current as all the motors try to simultaneously start; this in-rush current may re-trip the feeder

29

Page 30: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Inverse Time Overcurrent Relays

Relays havetraditionally beenelectromechanicaldevices, but aregradually beingreplaced by digital relays

Current and timesettings had been adjusted using dialson the relay

30

Page 31: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Protection of Network Systems

• In a networked system there are a number of difference sources of power. Power flows are bidirectional

• Networked system offer greater reliability, since the failure of a single device does not result in a loss of load

• Networked systems are usually used with the transmission system, and are sometimes used with the distribution systems, particularly in urban areas

31

Page 32: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Network System Protection

• Removing networked elements require the opening of circuit breakers at both ends of the device

• There are several common protection schemes; multiple overlapping schemes are usually used

1. Directional relays with communication between the device terminals

2. Impedance (distance) relays.

3. Differential protection

32

Page 33: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Directional Relays

• Directional relays are commonly used to protect high voltage transmission lines

• Voltage and current measurements are used to determine direction of current flow (into or out of line)

• Relays on both ends of line communicate and will only trip the line if excessive current is flowing into the line from both ends– line carrier communication is popular in which a high

frequency signal (30 kHz to 300 kHz) is used– microwave communication is sometimes used; radio can also

be used– Security is a concern

33

Page 34: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Line Carrier Communication, Line Traps

• Line traps are connection in series with lines to allow the power frequency (50 or 60 Hz) to pass with low impedance but to show high impedance at the line carrier frequency

34Image source: qualitypower.com/line-trap.html

Page 35: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Impedance Relays

• Impedance (distance) relays measure ratio of voltage to current to determine if a fault exists on a particular line

1 1

12 12

Assume Z is the line impedance and x is the

normalized fault location (x 0 at bus 1, x 1 at bus 2)

V VNormally is high; during fault

I IxZ

Page 36: ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University

Impedance Relays Protection Zones

• To avoid inadvertent tripping for faults on other transmission lines, impedance relays usually have several zones of protection:– zone 1 may be 80% of line for a 3f fault; trip is

instantaneous– zone 2 may cover 120% of line but with a delay to prevent

tripping for faults on adjacent lines– zone 3 went further; most removed due to 8/14/03 events

• The key problem is that different fault types will present the relays with different apparent impedances; adequate protection for a 3f fault gives very limited protection for LL faults

36