Arc fault and ground fault protection in one device

Eaton Wiring DevicesOBC AF/GF dual-purpose receptacles

AF/GF dual-purpose receptacles In Stock July 2016!

Page 2: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

Electrical Sector203 Cooper CirclePeachtree City, GA 30269United StatesEaton.comEaton.com/wiringdevices

Electrical SectorCanada Operations5925 McLaughlin RoadMississauga, Ontario, L5R 1B8CanadaEatonCanada.caEaton.com/wiringdevices

Electrical SectorMexico OperationsCarr. Tlalnepantla -Cuautitlán Km 17.8 s/nCol. Villa Jardín esq.Cerrada 8 de MayoCuautitlán, Mexico CP 54800MéxicoEaton.mxEaton.com/wiringdevices

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com

© 2016 EatonAll Rights ReservedPrinted in USAPublication No. SA610016ENMay 2016

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

• Provides both arc fault protection per UL1699A and ground faultprotection per UL943 in one convenient device

• Protects from both series and parallel arcs downstream fromthe Outlet Branch Circuit (OBC) AF/GF receptacle

• OBC AF/GF receptacles also protect from upstream series arcs• Trip indicators make it easy to diagnose arc and ground faults• Device self-tests periodically to ensure proper function of both

the ground fault and arc fault protection elements • Meets and exceeds 10ka short circuit testing and Underwriters

Laboratories (UL) UL943 safety standards• Ground termination with backwire clamp provides secure wiring

and reduces installation time• Automatic grounding system eliminates the need for bonding

jumper in grounded metal enclosure; provides redundant mea-sure of ground continuity when jumper is used

• Tapered backwire openings handle multiple wire sizes andtypes for applications up to #10 AWG solid or standard wire

• When downstream receptacles are wired from load side,a 20A feed-through rating offers full protection

• Lock-out functionality prevents miswired line-load connectionsand GFCI/AFCI circuitry damage

• Visual indicator light provides quick visual reference of atripped or “end of life” condition

• Tamper resistant (TR) shutters comply with 2014 NECArticle 406.12

• Terminal screws backed out and ready to wire• Matching standard size thermoplastic wallplate included

Features & benefits

Eaton’s OBC AF/GF dual-purpose receptacle provides bothArc Fault and Ground Fault protection in one convenient device. It has the same foot print of a standard GFCI or AFCI device, and uses Eaton’s proven AFCI technology to reduce nuisance AFCI tripping. With the 2014 NEC requiring kitchens and laundry areas to have both AFCI and GFCI protection, and other areas expected in further code expansions, the AF/GF receptacle is a great new alternative solution for getting code-compliant.

Table 1. AF/GF duplex receptacles Rating

Catalog no. Description A V/AC NEMA Color suffix

TRAFGF15__ AF/GF duplex receptacle with standard-size wallplate, back & side wire

15 125 5-15R A, B, BK, GY, LA, V, W

TRAFGF20__ AF/GF duplex receptacle with standard-size wallplate, back & side wire

20 125 5-20R A, B, BK, GY, LA, V, W

For ordering devices, include Cat. no. followed by the color code: A (Almond), B (Brown), BK (Black), GY (Gray), LA (Light Almond), V (Ivory), W (White)

A B BK GY LA V W

Almond Brown Black Gray Lt. Almond Ivory White

Table 2. Color ordering information

TRAFGF15 TRAFGF20

Eaton Wiring DevicesOBC AF/GF dual-purpose receptacles

Compliances, specifications and availability are subject to change without notice.

Page 3: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

Description2-pole, 3-wire grounding15A, 125V/AC 20A, 125V/AC

Design features• Provides both arc fault protection per UL1699A and ground fault

protection per UL943 in one convenient device• Protects from both series and parallel arcs downstream from the

Outlet Branch Circuit (OBC) AF/GF receptacle• OBC AF/GF receptacles also protect from upstream series arcs• Trip indicators make it easy to diagnose arc and ground faults• Device self-tests periodically to ensure proper function of both

the ground fault and arc fault protection elements• Meets and exceeds 10ka short circuit testing and Underwriters

Laboratories (UL) UL943 safety standards• Ground termination with backwire clamp provides secure wiring

and reduces installation time• Automatic grounding system eliminates the need for bonding

jumper in grounded metal enclosure; provides redundantmeasure of ground continuity when jumper is used

• Tapered backwire openings handle multiple wire sizes and typesfor applications up to #10 AWG solid or standard wire

• When downstream receptacles are wired from load side, a 20Afeed-through rating offers full protection

• Lock-out functionality prevents miswired line-load connectionsand GFCI/AFCI circuitry damage

• Visual indicator light provides quick visual reference of a trippedor “end of life” condition

• Tamper resistant (TR) shutters comply with 2014 NEC Article406.12

• Terminal screws backed out and ready to wire• Matching standard size thermoplastic wallplate included

TRAFGF15W

TRAFGF20LA

Project Name: Prepared By:

Project Number: Date:

Catalog Number: Type:

OBC AF/GF duplex receptacle

Compliances, specifications and availability are subject to change without notice.

Table 1. Specification grade AF/GF duplex receptacles Rating

Catalog no. Description A V/AC NEMA Color suffix

TRAFGF15___ Duplex self test AF/GF with standard-size wallplate, back & side wire

15 125 5-15R A, B, BK, GY, LA, V, W

TRAFGF20___ Duplex self test AF/GF with standard-size wallplate, back & side wire

20 125 5-20R A, B, BK, GY, LA, V, W

Technical Data Effective May 2016

In Stock July 2016!

Page 4: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

Technical Data Effective May 2016

AFGFDuplex Receptacle

2 EATON www.eaton.com Compliances, specifications and availability are subject to change without notice.

Catalog no. TRAFGF15, TRAFGF20

Top housing Thermoplastic, polypropylene

Bottom housing Thermoplastic, PVCStrap 0.047” thick steel, zinc-platedLine contacts 0.030” thick brassGround contact Brass

Terminal & ground screws#8-32 steel, brass-plated; neutral screw nickel-plated, ground screw green

Terminal clamps 0.070” thick steel

Table 2. Specifications Table 3. Materials

For ordering devices, include Cat. no. followed by the color code: A (Almond), B (Brown), BK (Black), GY (Gray), LA (Light Almond), V (Ivory), W (White)

A B BK GY LA V W

Almond Brown Black Gray Lt. Almond Ivory White

Project Name: Prepared By:

Project Number: Date:

Catalog Number: Type:

Catalog no. TRAFGF15, TRAFGF20

Device type OBC AFCI/GFCI duplex receptacleWiring type Back & side wireTesting & code compliance • cULus Listed to UL 498 and UL 943, file no. E482200

• Meets all UL 943 (GFCI), UL 498 (receptacles), UL1699A and applicable CSA requirements

• NOM certifiedEnvironmental specifications Flammability: Meets UL 94 requirements; V2 rated

Temperature rating: -35ºC to 66ºC (-31ºF to 150.8ºF)Electrical specifications Dielectric voltage: Withstands 2000V per UL 498

Current interrupting: Yes, at full-rated currentTemperature rise: Max. 30ºC (86°F) after 100 cycles of overload @ 150% of

rated current (DC)Trip time: 0.025 seconds (Class A)Frequency: 60 Hz; Voltage: 125V; Amperage: 15A/20A 20A feed-throughShort circuit testing: Meets and exceeds 10 kAMaximum interrupting capacity: 20 Amps

Mechanical specifications Terminal accommodation: #14 - 10 AWGVoltage ratings: Permanently marked on device

Table 4. Color ordering information

AF/GF receptacles are designed with the safety of the user in mind. Eaton’s AF/GF receptacles protect against both unexpected paths to ground and unseen arc faults that can result in electrical fires. The NEC requires GFCI or AFCI protection on certain circuits in residential, commercial, and industrial – in some cases both AFCI and GFCI protection are required on the same circuit. These receptacles are UL Listed and fully compliant with all of the latest UL943 Class A GFCI and UL1699A requirements. Eaton’s AF/GF receptacles include tamper resistant shutters to provide compliance with the 2014 NEC Article 406.12 that states that all receptacles installed in dwelling units must be tamper resistant. Additionally, these AF/GF receptacles incorporate lock-out functionality to protect against mis-wired line-load connections and dam-age the AFCI/GFCI circuitry.

Applications

Table 5. AF/GF status indicator Test indicator Red LED

Test indicator Amber LED

Rest button status Diagnosis Action

OFF OFF In "Device is functioning properly OR branch circuit may have no power"

Manually press the TEST button to trip the device. Amber light should come ON • If Amber light does not come ON, check if there is power to the branch • If Amber light does come ON, manually press the RESET button to restore power the the device • If AF/GF receptacle does NOT reset, replace AF/GF receptacle • If AF/GF receptacle receptacle does reset, device is functioning properly

OFF ON Out Device is in tripped state (either from manually pressing TEST button or from GFCI trip)

Manually press the RESET button to restore power to the device • If AF/GF receptacle does not reset, replace the AF/GF receptacle

OFF 2 Blinks Out GENERAL SERIES ARC Manually press the RESET button to restore power to the device • If AF/GF receptacle continues to trip, contact an electrician to locate and repair the low current arc fault

OFF 3 Blinks Out PARALLEL ARC Manually press the RESET button to restore power to the device • If AF/GF receptacle continues to trip, contact an electrician to locate and repair the parallel arc fault

OFF 4 Blinks Out OVERVOLTAGE Manually press the RESET button to restore power to the device • If AF/GF receptacle continues to trip, contact an electrician to locate and repair the overcurrent condition

OFF 5 Blinks Out AFCI self-test failure Manually press the RESET button to restore power to the device • If it does not reset and/or the blinking continues, replace the AF/GF receptacle

Blinking ON or OFF In or Out GFCI self-test failure Manually press the RESET button to restore power to the device • If it does not reset and/or the blinking continues, replace the AF/GF receptacle

Page 5: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

Technical Data Effective May 2016

AFGFDuplex Receptacle

Project Name: Prepared By:

Project Number: Date:

Catalog Number: Type:

Product dimensions

Figure 1. OBC TRAFGF 15A Line art with dimensions

1.28”(32,6mm)

2.60”(66mm)

1.27”(32,3mm)

1.30”(33mm)

3.28”(83,3mm)

4.20”(106,6mm)

Figure 2. OBC TRAFGF 20A Line art with dimensions

1.28”(32,6mm)

2.62”(66,4mm)

1.27”(32,3mm)

1.30”(33mm)

3.28”(83,3mm)

4.20”(106,6mm)

Certifications & compliances

KEY: cULus NOM

Catalog no.

TRAFGF15 • •

TRAFGA20 • •

Electrical Sector203 Cooper CirclePeachtree City, GA 30269United StatesEaton.comEaton.com/wiringdevices

Electrical SectorMexico OperationsCarr. Tlalnepantla -Cuautitlan Km 17.8 s/nCol. Villa Jardin esq.Cerrada 8 de MayoCuautitlan, Mexico CP 54800MexicoEaton.mxEaton.com/wiringdevices

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com

Electrical SectorCanada Operations5925 McLaughlin RoadMississauga, Ontario, L5R 1B8CanadaEatonCanada.caEaton.com/wiringdevices

© 2016 EatonAll Rights ReservedPrinted in USAPublication No. TD610028ENMay 2016

Page 6: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

1 © 2013 Eaton. All Rights Reserved.

Dual Purpose Arc Fault Ground Fault Receptacle

• Dual purpose: device provides both self-test ground

fault protection per UL943 and combination (parallel

and series) arc fault protection per UL1699A

• Meets and exceeds 10ka short circuit testing and

UL943 safety standards

• Trip indicators make is easy to diagnose arc and

ground faults as well as “end of life” condition

• When downstream receptacles are wired from load

side, a 20A feed-through rating offers full protection

• Lock-out functionality prevents miswired line-load

connections and GFCI/AFCI circuitry damage

• Stock arriving in July 2016

Page 7: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

2 2

Duplex AF/GF Receptacle

AFCI and GFCI protection in one convenient device!

Back and side wire – up

to 10 AWG

TR Shutters standard to

ensure code compliance

with 2014 NEC

Colors: A, B, BK, GY, LA, V, W

Available in 15A and 20A

“TR” no longer on face of

device; “Tamper

Resistant” marked on

side – UL approved

marking

Amber LED: GFCI or

AFCI trips; multiple blink

patterns

Red LED: End of Life

Due to GFCI self-test

failure

14 and 12 AWG wire

strippers on strap

Autoground clip standard

Page 8: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

3 3

AF/GF Trip Codes

Red LED Amber

LED Rest button

status Diagnosis Action

OFF OFF In Device is functioning properly

OR branch circuit may have no power

Manually press the TEST button to trip the device. AMBER light should come ON

-If AMBER light does not come ON, check if there is power to the branch

-If AMBER light does come ON, manually press the RESET button to restore power

the device

-If AF/GF receptacle does NOT reset, replace AF/GF receptacle

-If AF/GF receptacle does reset, device is functioning properly

OFF ON Out Device is in tripped state (either from

manually pressing TEST button or from

GFCI trip)

Manually press the RESET button to restore power to the device

-If AF/GF receptacle does not reset, replace the AF/GF receptacle

OFF 2 Blinks Out GENERAL SERIES ARC Manually press the RESET button to restore power to the device

-If AF/GF receptacle continues to trip, contact an electrician to locate and repair the

low current arc fault

OFF 3 Blinks Out PARALLEL ARC Manually press the RESET button to restore power to the device

-If AF/GF receptacle continues to trip, contact an electrician to locate and repair the

parallel arc fault

OFF 4 Blinks Out OVERVOLTAGE Manually press the RESET button to restore power to the device

-If AF/GF receptacle continues to trip, contact an electrician to locate and repair the

overcurrent condition

OFF 5 Blinks Out AFCI self-test failure Manually press the RESET button to restore power to the device

-If it does not reset and/or the blinking continues, replace the AF/GF receptacle

Blinking ON or

OFF In or Out GFCI self-test failure

Manually press the RESET button to restore power to the device

-If it does not reset and/or the blinking continues, replace the AF/GF receptacle

Page 9: Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF ... · and series) arc fault protection per UL1699A • Meets and exceeds 10ka short circuit testing and UL943 safety standards

4 4

Additional details

• Like GFCIs, these products arrive in the

tripped state from the factory

• If wired correctly, the amber LED will be

illuminated, showing this tripped state

• Device just needs to be reset with button once

installed and it will then be ready for normal

operation

• If the amber LED is not illuminated when wired than

the product has been miswired (likely a line/load

mix up) or there is no power in the circuit