76
System Earthing & Protective Earthing

Earthing Systems

Embed Size (px)

Citation preview

Page 1: Earthing Systems

System Earthing

&

Protective Earthing

Page 2: Earthing Systems

Low Voltage Earthing System

All points that generate electricity or changes

system voltage must be earthed.

Type of Earthing Systems:-

Protective Earthing for persons and equipments

against electric shock

Technical earthing (Functional )

Page 3: Earthing Systems

Protective earthing system must be bounded at some

points to the technical earthing system.

Technical earthing systems must not designed only to

clear earth fault current but also, it bust be to provide a

high integrity, low impedance path to earth for high

frequency leakage (up to 30 MHz ) currents and noise

caused by switching and lightning.

( due to high frequency current components, we must

use several parallel paths to earth)

Page 4: Earthing Systems

Technical Earthing Systems

T N

• TN-C

• TN-S

TT

IT

Page 5: Earthing Systems

Grounding systemsIEC 364

TN system

TN-C systems3 pole CB

Page 6: Earthing Systems
Page 7: Earthing Systems

•The transformer neutral is earthed;

•The frames of the electrical loads are

connected to the neutral.

The insulation fault turns into a short-circuit

and the faulty part is disconnected by Short-

Circuit protection Devices (SCPD).

The fault voltage (deep earth/frame), known as

«indirect contact» is » Uo/2 if the impedance of

the «outgoing» circuit is equal to that of the

«return» one.

When it exceeds the safety limit voltage, which

is normally 50 V, it requires disconnection.

Page 8: Earthing Systems
Page 9: Earthing Systems

• provides a return path for faults in the

LV grid.

• This ensures a distributed grounding

and reduces the risk of a customer nothaving a safe grounding.

• However faults in the MV network may

migrate into the LV grid grounding

causing touch voltages at LV clients.

Page 10: Earthing Systems

• The utility is not only responsible for aproper grounding but also for the safety ofcustomers during disturbances in the powergrid.

• A fault in the LV network may cause touchvoltages at other LV clients.

• Most critical are faults at the ends of thebranches, where the circuit impedance is thehighest. In the design of LV-grids, this circuitimpedance should be limited.

• The maximum length of an outgoing cable istherefore limited. A practical length of acable was 300 m.

Page 11: Earthing Systems

Advantages:

Provides a return path for faults in the LV grid.

Ensures a distributed grounding and reduces the risk of a

customer not having a safe grounding

Disadvantages:

Faults in the electrical network at a higher voltage level may

migrate into the LV grid

The utility is not only responsible for a proper grounding

A fault in the LV network may cause touch voltages at other LV

clients

Most critical are faults at the ends of the branches, where the circuit

impedance is the highest.

The maximum length of an outgoing cable is therefore limited

Page 12: Earthing Systems

• Needs a very good earthing impedance of the network (about 2

Ω ) TN-C Inadequate for EMC problems

• The TN-C should be avoided since rank 3 harmonics and

multiples of it to flow in the PEN.

prevent the latter from being used as a potential

reference for communicating electronic systems, if

the PEN is connected to metal structures, both these

and the electric cables become sources of

electromagnetic disturbance

Page 13: Earthing Systems

Multiple Earthing

Page 14: Earthing Systems

Grounding systemsIEC 364

TN system

TN-S systems4 Pole CB

Load Load

Page 15: Earthing Systems

Ud

Id

Page 16: Earthing Systems

• LV cable with a grounded sheath is applied.

• Additional electrodes in the LV grid,

preferably at each user, divert external

induced (lightning) currents.

• In a TN-S system five conductors are

required.

• We prefer TN-S For:-

Very long network.

Loads with low natural insulation

(furnaces) or, with large HF filter (large

computers) and communication systems

Page 17: Earthing Systems
Page 18: Earthing Systems

Grounding systemsIEC 364

TN system

TNC-S system

Page 19: Earthing Systems

Grounding systemIEC 364

TT system

Page 20: Earthing Systems
Page 21: Earthing Systems
Page 22: Earthing Systems
Page 23: Earthing Systems

• The transformer neutral is earthed;

• The frames of the electrical loads are also

connected to an earth connection.

• The insulation fault current is limited by the

impedance of the earth connections an the

faulty part is disconnected by a Residual

Current Device (RCD).

Page 24: Earthing Systems
Page 25: Earthing Systems

• Each customer needs to install and maintain it’s own ground

electrode.• The ground impedance at the customer should be low (Rc<30 Ω)

• RCD’s are required

Advantages

• Faults in the LV and MV grid do not migrate to other clients in the

LV grid

• A broken neutral conductor does not affect a single-phase

connection, but may cause damage to equipment using a three-

phase connection

• Good security condition : potential rise of the grounded

conductive part - limited at 50 V for a fault inside the installation

• No influence of the network evolution (fault loop impedance)

Page 26: Earthing Systems

Disadvantages

• For large customers it is impossible to apply a TT system, since

the disconnecting time of the over-current protective device is

too long. A TN system always provides a low impedance return

path.

• In TT-systems high over-voltages may occur between all live

parts and PE conductor

The TT provides a good separation between the responsibilities

of the supplier and the customer and needs less control of the

transferred potentials for assessing safety in case of HV fault.

The same is valid in case of a phase to neutral fault in the LV

network.

• It is a very good for communication systems for very

low interferences

Page 27: Earthing Systems

Grounding systemIEC 364

IT system

Page 28: Earthing Systems

It is naturally earthed by the stray capacities of the network

cables. voluntarily by a high impedance of around 1,500 Ω

(impedance earthed neutral)

Ud

V1V2

V3

V13V23

Page 29: Earthing Systems

We must avoid second fault by using very fast protection

(1st fault) : Id < 1 A

(2nd fault): Id ≈ 20 kA

Page 30: Earthing Systems

AdvantagesThe voltage developed in the earth connection of the frames (a

few volts at the most) does not present a risk.

continuity of service

loads sensitive to high fault currents

Disadvantages

If a second fault occurs and the first one has not yet been

eliminated, a short-circuit appears and the SCPDs must provide

the necessary protection.

The frames of the relevant loads are brought to the potential

developed by the fault current in their protective conductor (PE).

Page 31: Earthing Systems

Restrictions and precautions for using the IT earthing system

The restrictions for using the IT system are linked to loads and networks.

high earth capacitive coupling (presence of filters)

Page 32: Earthing Systems

system for use in:

• Hospitals

• Airport take-off runways

• Arc Furnaces

• Plants with continuous manufacturing

processes

• Laboratories

• Cold storage units

• Welding Machines.

Page 33: Earthing Systems

influence of MV earthing

systems

In MV, the neutral is not distributed and there is no

protective conductor (PE) between substations or

between the MV load and substation.

A phase/earth fault thus results in a single-phase

short-circuit current limited by earth connection

resistance and the presence of limitation

impedances.

Page 34: Earthing Systems

IEC 364-4-442 states:

The earthing system in a MV/LV substation

must be such that the LV installation is not

subjected to an earthing voltage of:

Uo + 250 V : more than 5 s

Uo + 1,200 V: less than 5 s

Page 35: Earthing Systems

This means that the

various devices connected to the LV

network must be able to withstand this

constraint.

The same standard states that if Rp > 1 Ω,

the voltage Rpx IhMT must be eliminated, for

example:

100 V under 500 ms;

500 V under 100 ms.

Page 36: Earthing Systems

if Rp and RB are connected, the fault current

causes the potential of the LV network to rise

with respect to the earth.

Page 37: Earthing Systems

If this is not so, Rp and RN must be

separate whatever the LV earthing

system.

If all the earth connections (substation

neutral- applications) have been grouped

into a single one, a rise in potential of LV

frames may be observed which can be

dangerous.

Page 38: Earthing Systems
Page 39: Earthing Systems

LV Grounding systems

• LV electrical network may supply several

types of applications.

• Only one type of Earthing System cannot

be suitable for all applications.

• It is advisable to ”mix” various

Grounding Systems in an electrical

installation.

Page 40: Earthing Systems

A clash of technical cultures is inevitable:

• Electrical engineers have problems with the harmonicsgenerated by static

• converters. These harmonics cause temperature rises intransformers, destruction of capacitors and abnormalcurrents in the neutral;

• Electronic engineers place filters upstream of theirproducts, which do not always withstand over-voltagesand lower network insulation;

• lamp manufacturers are unaware of the problemscaused by energizing inrush currents, harmonics andhigh frequencies generated by certain electronic ballasts;

• Computer engineers (same applies to designers ofdistributed intelligence systems) are concerned withequipotentiality of frames and conducted and radiatedinterference.

Page 41: Earthing Systems

Mixing of different Grounding systems

Page 42: Earthing Systems

LV distribution

The most common systems are TT and TN

The TN-C system is particularly used but it needs

carefully designed SCPD.

It is not currently recommended in premises equipped

with communicating electronic systems as currents in

the neutral and thus in the PE cause potential

references to vary ( TT system)

RCDs are used for personnel protection (for very long

cables)

Page 43: Earthing Systems

The TT system Is the easiest one to implement; insulation fault

currents are smaller than in TN or IT thus accounting for its value as

regards risk of fire, explosion, material damage and electromagnetic

disturbances.

The IT Systems (unearthed neutral) is used whenever continuity of

service is essential.

The TNC-S is increasingly chosen for large projects.

Page 44: Earthing Systems

Actual grounding system

In residential areas

EDC

network

TN-C

Consumer

installation

Page 45: Earthing Systems

HazardsIn residential

areas

Page 46: Earthing Systems
Page 47: Earthing Systems

F1) Direct contact fault loop

Page 48: Earthing Systems

HazardsIn residential

areas

Page 49: Earthing Systems

HazardsIn residential

areasF2) Indirect contact fault loop

Page 50: Earthing Systems

Effects of sinusoidal alternating current in

the range of 15 Hz to 100 Hz

Risk of electric shocks

Page 51: Earthing Systems

Electric shock

• -It is caused by the current that flows through the human body.

• -The current depends mainly upon the skin contact resistance.

• -The contact resistance varies with ( thickness, wetness and

resistively of the skin ).

• -In general :

Current<5mA is not dangerous .

10mA< current <20mA

The current is dangerous because the victim loses muscular

control and so may not be able to let go .

Current>50mA the consequences can be fatal .

Page 52: Earthing Systems

• Resistance of human body Rb:

Rb : between two hands or between one hand and a leg ranges

from 500 Ohms to 50 K Ohms

• if Rb = 50 K ohms

The momentary contact with 600 V may not be fatal .

I body = 600 V / 50 K Ohms = 12 mA

• but if Rb = 500 ohm and voltage is as low as 25V ac

I body = 25 V / 500 Ohms = 50 mA (may be fatal )

• the current is particularly dangerous when it flows in the region of the heart .

Page 53: Earthing Systems

• statistical investigations have shown that a current may cause

death if it satisfies the following equation

Ib = 116/ square root ( t )

where :-

Ib : current flow through the body in mA

t : time of current flow second

116 : an empirical constant, expressing the probability of a

fatal out come .

[ IEEE transactions on industry and general application ]

vol. IGA - 4, No. 5 , pages 467 to 475.

• example:

A current of 116 mA for 1 s could be fatal .

Breaking time for RCDs 30mA (300mS), 60mA(150mS), 150mA(40mS)

Ventricular Fibrillation is considered to be the main cause of

Electrocution

Page 54: Earthing Systems

CDetection

Measurement

Tripping

Operating principle of Earth

leakage protection

Page 55: Earthing Systems

General Specifications

• Number of poles 2 or 4

• Rated voltage not exceeding 1000 v.

• Rated breaking load current

• Rated breakage earth leakage fault

current.

Page 56: Earthing Systems

Installation of RCD

General Notes

Every installation which includes exposed

conductive parts should be protected by one or more

RCD

If an installation is protected by one RCD , This

device should be Located at the starting point of the

installation

The exposed conductive parts of the protected

appliance should be all connected to an earth

electrode of suitable resistance

Page 57: Earthing Systems

Depending on the type of the installation and

the risks involved , it may be necessary to

provide RCD having different sensitivities in

order to protect different parts of the

installation

It is also necessary to arrange for a measure

of selectivity ( Coordination ) between the

operation of the RCD’s located at different

parts in the installation

Installation of RCD

Page 58: Earthing Systems

RCD 300 mA

Page 59: Earthing Systems

It is very important to use the current-operated residual

current devices (RCDs).

Current operated devices rated at up to 500mA have

been available for protecting installations and individual

sub-circuits for many years.

More recently sensitive RCDs (30mA and below) have

become available.

These are regarded as providing excellent protection

against electric shock, and can be fitted to sub-circuits

or socket outlets.

Page 60: Earthing Systems

Protective Earthing

• Safety for persons.

• Proper operation and long life

time for equipments

Page 61: Earthing Systems

Step & Touch Potential

Page 62: Earthing Systems

• Earthing systems allow unwanted electrical

currents to flow harmlessly to earth.

• Their main function is to provide low

impedance (not only resistance) paths for high-

energy discharges and high frequency,

particularly lightning strikes, other transients

and fault currents.

Page 63: Earthing Systems

The main markets for installing earthing systems:-

utility power generation, transmission and distribution.

lightning protection for buildings and high structures

Private electricity distribution networks in industrial and

commercial premises.

Protection of electronic equipment e.g. computer

installations, telecommunications.

Domestic housing and small commercial premises

Situations where a build-up of electrostatic potential

could

be dangerous, including oil refineries, petroleum filling

stations, grain storage, hospitals.

Page 64: Earthing Systems
Page 65: Earthing Systems
Page 66: Earthing Systems
Page 67: Earthing Systems
Page 68: Earthing Systems
Page 69: Earthing Systems

Earthing Installation

Typical earth electrodes include

simple surface earth electrodes rod (vertical) electrodes meshed electrodes,

cable with earth electrode effect foundation earth electrodes

Page 70: Earthing Systems

Earth surface potential distributionVx* = f(x) around a vertical rod earth electrode

with length l = 3 m, diameter d = 0.04 m

Page 71: Earthing Systems

Resistance and surface potential distribution

Page 72: Earthing Systems
Page 73: Earthing Systems

Step and Touch potentials

Page 74: Earthing Systems

The most frequently used electrode materials are:

Steel

Galvanized steel

Steel covered by copper

High-alloy steel

Copper and copper alloys.

Page 75: Earthing Systems

Earthing, Backfilling Materials

SOIL ENHANCEMENT OPTIONS

1. Conductive Concrete

30 to 90 ohm-meters

2. Bentonite

2.5 ohm-meters

3. Carbon-Based Backfill Materials

0.1 to 0.5 ohm-meters

4. Clay-Based Backfill Materials (GAF)

0.2 to 0.8 ohm-meters depending on moisture content

5- Marconite

0.1 ohm.meters

Page 76: Earthing Systems

Grounding Grids

A common method for obtaining a low ground

resistance at high­ voltage substations is to use

interconnected ground grids. A typical grid system for a

substation would comprise solid copper conductors

buried at a depth of from 30 to 60 cm, spaced in a grid

pattern of about 3 to 10 m. At each junction, the

conductor: are securely bonded together.