EARTHING & LIGHTNING PROTECTION

CATALOGUE

Page 2: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

INDEX

1

Information

Conductors 2

Earthing 3

Down Conductors 4Clamps, Terminals, Test Points

Air Terminals, 5Masts, Saddles, Conductor Holders

Equipotential Bonding 6

Tools and Accessories 7

Index 8

1

Page 3: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Pontins’ Earthing & Lightning Protection Products

Codes of Practice

INFORMATION

2

History

Established in 1972, Pontins’ earthing and lightning protection products have evolved through experience, research, on-site testing and development into a world class range for the installation of conventional lightning protection systems.

In order to stay up to date with the latest trends in the protection of human lives And material assets from hazards of lightning, we are actively involved with Various international and national standards committees. This assures that our Products offer the highest levels of protection in even the harshest of lightning environments.

All of our products have undergone extensive on-site testing and development And with over 40 years of experience our products are long lasting and able to withstand multiple direct strikes with little or no detrition.

The production of our products have through experience been refined to the Highest quality standards and reliability.

Our range of products offer complete solutions for any conventional lightning protection application for any industry sector including : mining, petrochemical, power generation, aviation, commercial, medical, industrial and many more.

In order to supply only the highest level of protection all of our products, designs, installations and site surveys comply with the stringent requirements of the following local and international codes of practice :

SANS Code 10313 - Protection Against Lightning

SANS Code 10199 - Design & Installation of an Earth Electrode

SANS Code 10089-2 - Electrical Installations - The Petroleum Industry

IEC 62305 Part 1, 2, 3 & 4 - Protection Against Lightning

IEEE 80 - Safety in Substation Earthing / Grounding

IEC 60479 - Effects of Current on Human Beings and Livestock

South African Codes of Practice

International Codes of Practice

Page 4: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

All Lightning Protection Systems include the following components :

Part Numbers stating with ‘E’ , ‘EB’

Part Numbers starting with ‘D’

Part numbers starting with ‘A’

Part Numbers starting with ‘EB’

Part Numbers starting with ‘EB’

Products used for various components will haveVarious letters, eg. EBD = Earthing, Down Conductors & Bonding

Earth Termination Systems

Down Conductor Systems

Air Termination Systems

Internal Equipotential Bonding

External Equipotential Bonding

Product Caregories

Supplementary Services

3

The correct installation and positioning of earthing and lightning protection conductors, fixings and assemblies is critical to the efficiency of the protection systems. Pontins` therefore not only supplies all of the necessary earthing and lightning protection products but supplies the following supplementary services :

Ÿ Full SystemsFull Design, Supply, Installation and certification of earthing and lightningprotection systems in all industry sectors.

Ÿ Survey and DesignSoil Resistivity SurveysLightning Protection Risk AssessmentsDesign and Detail DrawingsInstallation Method Statements

Ÿ Site Supervision, Testing and CertificationOn-site Supervision and Management of InstallationsTesting and CommissioningTest Reports and Certification

Ÿ Consultancy Services

Ÿ Seminars

Ÿ Maintenance of Protection Systems

EXAMPLE

PAGE 6

3,1 Soil Resistivity Survey S/XXXX-01 (Contd.)

3,1,4 Step & Touch Analysis

3,0 Soil Resistivity Surveys

CAll rights reserved

Surface Potentials

Step Potentials

Touch Potentials

INFORMATION

AIR TERMINATIONSYSTEM

DOWN CONDUCTORSYSTEM

EARTH TERMINATIONSYSTEM

GAS WATERPOWER SUPPLY

TELEPHONE SUPPLY

230/400V AC

FOUNDATION EARTHING SYSTEM

LIGHTNING CURRENTARRESTER FOR230/400V AC

LIGHTNING CURRENTARRESTER FORTELEPHONE LINE

LIGHTNING EQUIPOTENTIAL BONDING

Page 5: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Lightning Protection Systems are installed to virtually all industry sectors :

Industry Caregories

References

4

INFORMATION

Pontins earthing and lightning protection products have been tried and tested since 1972. Over the years our list of successfully completed projects has exceed the 12000 mark.

We are proud that we have involved ourselves in some of Southern Africa`s largest and most prestigious projects including :Ÿ GautrainŸ Soccer CityŸ Michaelangelo Towers / Sandton CityŸ M-net Broadcast CentreŸ ORT International AirportŸ Overberg Missile Test BaseŸ Melrose ArchŸ Sasol 2 & 3Ÿ Khumani Iron OreŸ Moatize Coal MineŸ Cradle of HumankindŸ SentechŸ Absa TowersŸ BMW IT FacilityŸ Impala Platinum MinesŸ Anglo PlatinumŸ Exxaro CoalŸ BHP BillitonŸ Netcare HospitalsŸ AECI Explosive AreasŸ And many more....

Mining, Oil & Gas

Offices, Hotels & Commercial Government & DefenceAviation & Traffic Control Industrial Plants

Education & Medical Telecommunications Sports & Recreation

Computer & IT Networks Railway Electric Facilities Wind & Solar Farms

Page 6: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Copper Conductors

Copper Conductors

CONDUCTORS

5

Part Number EBD2120 EBD2070 EBD2050 EBD2035 EBD2016

Conductor Dia. (Core) 12.4mm 9.5mm 8mm 6.7mm 4.5mm

Conductor Section 120mm² 70mm² 50mm² 35mm² 16mm²

Material PVC Ins. PVC Ins. PVC Ins. PVC Ins. PVC Ins.

Packing Unit (mtr) 50 100 100 100 100

Uses :

PVC Insulated Copper conductors are to for use in lightning protection and earth

termination systems.

PVC Insulated conductors have a UV stabilized coating offering additional

mechanical protection as well as protection from corrosion; can be installed

Directly into soil, concrete and mortar.

Part Number EBD3300 EBD3150 EBD3075

Conductor Size 50X6mm 50X3mm 25X3mm

Conductor Section 300mm² 70mm² 50mm²

Material Flat Copper Flat Copper Flat Copper

Packing Unit (mtr) 20 50 100

Uses :

Bare Copper conductors are for use in lightning protection and earth

termination systems.

Conductors can be installed directly into soil, concrete and mortar.

Bare Copper Conductors PVC Insulated Copper Conductors

Flat Copper Conductors

Part Number EDB1120 EBD1070 EBD1050 EBD1035 EBD1016

Conductor Dia. 12.4mm 9.5mm 8mm 6.7mm 4.5mm

Conductor Section 120mm² 70mm² 50mm² 35mm² 16mm²

Material BCEW BCEW BCEW BCEW BCEW

Packing Unit (mtr) 50 100 100 100 100

Uses :

Bare Copper conductors are to for use in lightning protection and earth

termination systems.

Conductors can be installed directly into soil, concrete and mortar.

Part Number EB4170

Conductor Dia. 10mm

Conductor Section 70mm²

Material Solid Copper Rod

Packing Unit (mtr) 100

Uses :

Solid Copper conductors are to for use in lightning protection and earth

termination systems.

Useful for Power Stations

Conductors can be installed directly into soil, concrete and mortar.

Solid Copper Conductors

Page 7: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Anti Theft Conductors

Anti Theft Conductors - Fushi Copperweld

CONDUCTORS

6

Part Number EB6400 EB6300 EB6185 EB6150 EB6120

Kwena Conductor Size 400mm² 300mm² 185mm² 150mm² 120mm²

Copper Equal Section 140mm² 120mm² 95mm² 70mm² 50mm²

Material Cu/Fe Cu/Fe Cu/Fe Cu/Fe Cu/Fe

Packing Unit (mtr) 20 50 100 100 100

Uses :

Kwena anti theft conductors are for use in lightning protection, earth termination and equipotential bonding systems.

Unique conductor consists of a copper and steel woven / braided strands making

it difficult to cut mechanically. Kwena conductors have extremely low or nil scrap

Value, therefore theft deterrent.

Part Number EB7090 EB7070 EB7035 EB7016Conductor Size 12.4mm 9.5mm 8mm 6.7mm

Copper Equal Section 90mm² 70mm² 35mm² 16mm²

Material Copper Clad Steel (CCS)

Packing Unit (mtr) 100 100 100 100

Uses :

Fushi Copperweld conductors are for use in lightning protection, earth termination

and Equipotential bonding systems.

Conductors are copper clad steel which combines the strength of steel with the

conductivity and corrosion resistance of copper.

Conductors have extremely low or nil scrap value, therefore theft deterrent.

Pontitheft Conductors Kwena Anti Theft Conductors

Fushi Copperweld Conductors

Part Number EB5095 EB5070 EB5050 EB5035

Conductor Dia. 10.4mm 9.5mm 8mm 6.7mm

Conductor Section 95mm² 70mm² 50mm² 35mm²

Material Anti Theft Anti Theft Anti Theft Anti Theft

Packing Unit (mtr) 50 100 100 100

Uses :

Anti Theft Copper conductors are to for use in lightning protection and earth

termination above ground applications.

Anti Theft properties include black PVC insulation and armoring to disguise conductors to look like electrical cable - not earthing cables.

Fushi Copperweld Hide Conductors

Part Number EB8090 EB8070 EB8035 EB8016Conductor Size 12.4mm 9.5mm 8mm 6.7mm

Copper Equal Section 90mm² 70mm² 35mm² 16mm²

Material Copper Clad Steel (CCS) - PVC Insulated

Packing Unit (mtr) 100 100 100 100

Uses :

Fushi Copperweld conductors are for use in lightning protection, earth termination

and Equipotential bonding systems.

Conductors are copper clad steel which combines the strength of steel with the

conductivity and corrosion resistance of copper.

Conductors have extremely low or nil scrap value, therefore theft deterrent.

Page 8: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Aluminium Conductors

Stainless Steel Conductors

CONDUCTORS

7

Part Number AD8075 AD8120

Conductor Size 25mmX3mm 40mmX3mm

Conductor Section 75mm² 120mm²

Material Al - Flat Bar Al - Flat Bar

Packing Unit (mtr) 100 50

Uses :

Aluminium Alloy conductors are to for use in lightning protection air termination and down conductor systems.

Conductors can not be installed directly into soil, concrete and mortar.

Aesthetically flat conductors serve as excellent down conductors.

Part Number EB9150

Conductor Size 50mmX3mm

Conductor Section 150mm²

Material Stainless Steel

Packing Unit (mtr) 50

Uses :

Stainless conductors are to for use in lightning protection and earth

termination systems in highly corrosive areas.

Conductors can be installed directly into soil, concrete and mortar.

Stainless steel conductors can also be used for the equipotential bonding of concrete steel reinforcing.

Solid Round Aluminium Conductors

Flat Stainless Steel Conductors

Part Number AD8050 AD8070

Conductor Dia. 8mm 9mm

Conductor Section 50mm² 70mm²

Material Al - Soft Twistable Al - Soft Twistable

Packing Unit (mtr) 100 100

Uses :

Aluminium Alloy conductors are to for use in lightning protection air termination and down conductor systems.

Conductors can not be installed directly into soil, concrete and mortar.

Part Number EB1020 EB1070 EB1050 EB1035 EB1016

Conductor Dia. 12.4mm 9.5mm 8mm 6.7mm 4.5mm

Conductor Section 120mm² 70mm² 50mm² 35mm² 16mm²

Material Stranded Stainless Steel Conductor

Packing Unit (mtr) 50 100 100 100 100

Uses :

Stainless Steel conductors are to for use in lightning protection and earth

termination systems.

Conductors can be installed directly into soil, concrete and mortar.

Stranded Stainless Steel Conductors

Flat Aluminium Conductors

Page 9: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earthing Systems

8

EARTHING SYSTEMS

The shape and dimension of the are important when dealing with safe dispersion of lightning, electrical and static type fault currents intothe ground.

In order to minimize any dangerous overvoltages low resistance earthing systems are recommended.

Earthing systems are designed for the following applications :

Power / Electrical Systems

Data Systems

Depending on the required application the followingtypes of earthing systems form the basis for anyEarth termination design :

Type ‘B’ Earthing Systems - Ring Type

Combination Type ‘A’ & ‘B’

A single integrated earthing system is preferable, which is suitable for all purposes (i.e. Lightning protection, electrical systems, telecommunications systems and data systems).

Alternatively all earthing system be equipotentially bonded together.

Lightning Protection Systems

T

Type ‘A’ Earthing Systems - Vertical Electrodes

Foundation Ring Type Earthing Systems

Crows Foot Earthing Systems

elecommunications Systems

shall

Page 10: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earth Electrodes

Electrode Couplings

EARTHING SYSTEMS

9

Part Number E-2150 E-2300

Electrode Length 1500mm 3000mm

Electrode Diameter 16mm 16mm

Material Solid Stainless Steel Bar - Grade 316

Packing Unit (mtr) 10 10

Uses :

Earth electrodes used for installing earth termination systems.

Electrodes are threaded for additional length.

Electrode ends are chamfer and pointed for easier driving into ground.

Part Number E-2160 E-2161 E-2200

Coupling for Rod Dia. 16mm 16mm 20mm

Material BRASS Stainless Steel Stainless Steel

Packing Unit (each) 10 10 10

Uses :

Rod Coupling are used to lengthen earth electrodes to the desired length.

Earth electrodes can be lengthened from 2,4m to 30m in length depending on the

Soil Resistivity values.

Earth electrodes can be easily lengthened as the various lengths are being installed

Be simply screwing the couplings onto the threaded portions and then adding on

The next earth electrode.

Copper Coated Earth Electrodes Stainless Steel Earth Electrodes

Part Number E-1240 E-1150 E-1120

Electrode Length 2400mm 1500mm 1200mm

Electrode Diameter 16mm 16mm 16mm

Material High Tensile Steel Core / Cu Coated (99% Pure Copper)

Cu Layer 250 micron 250 micron 250 micron

Packing Unit (pcs) 10 10 10

Uses :

Earth electrodes used for installing earth termination systems.

Electrodes are threaded for additional length.

Electrode ends are chamfer and pointed for easier driving into ground.

Part Number E-3120

Description Earth electrode holding bracket

Material Mild Steel Plated

Packing Unit (each) 1

Uses :

Bracket is used to safely hold earth electrodes in place whilst driving the earth electrodes into the ground.

Enables safe work procedures when driving earth electrodes into ground.

Earth Electrodes Holding BracketBrass Rod Coupling Stainless Steel Rod Coupling

Page 11: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earth Inspection Pits

EARTHING SYSTEMS

10

Water Resistant Inspection Pit

Part Number E-4240

Material PVC 5mm Thick

Inspection Pit Size 256mm X 259mm

Additional Assembly Parts 300mm Dia. PVC Pipe

Packing Unit (pcs) 1

Uses :

n Water Resistant Earth Electrode have been developed to prevent water build-up i

the void between electrode and inspection pit top, this is ideal for the prevention

of corrosion of the earth electrodes.

Lids can be attached to pit body by means of a 1.5mm galvanised wire to prevent

loss of lids.

TEST BOX

OPEN

CLOSE

MADE IN SOUTH AFRICA

256

263259

334

231

250 ROUNDVALVE BOX

256

Cast Iron Inspection Pit

Part Number E-5225 E-5150

Material Cast Iron - Painted Cast Iron - Painted

Inspection Pit Size 225mm X 225mm 150mmX150mm

Additional Assembly Parts 300mm Dia. PVC Pipe 150mm Dia. PVC Pipe

Packing Unit (pcs) 1 1

Uses :

Cast Iron inspection pits are extremely robust and are ideal for earth termination

systems in industrial areas where the is constant traffic flow.

Cast iron inspection pits can be labeled in accordance with individual site requirements.

Earth Inspection Pits

GROUND LEVEL

INSPECTION BOX

EARTH ELECTRODE

PVC INSULATED CONDUCTOR

PVC PIPE

PONTONITE EARTHENHANCING MATERIAL

Page 12: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earth Inspection Pits

EARTHING SYSTEMS

11

Part Number E-6240

Material Concrete Earth Pit & Steel Top

Inspection Pit Size Top = 300mmX300mm

Base = 350mmX350mm

Opening = 200mm, Height = 350mm

Additional Assembly Parts 300mm Dia. PVC Pipe

Packing Unit (pcs) 1

Uses : Concrete inspection pits are extremely robust and are ideal for earth

termination systems in industrial areas where the is constant traffic flow.

Concrete inspection pits can be labeled in accordance with individual site requirements.

Concrete Inspection Pit

Exothermic Connections

The Exothermic Welding process has been proven to provide a low resistance, durable and permanent connection of various types of conductors. The Exothermic Reaction produces a high temperature molecular bond between the conductors, the result is superior performance over any known mechanical or pressure type connection.

Exothermic Connection Advantages :

Ÿ Requires no external source of heat or power so it is ideal for field operations.

Ÿ Connections will not loosen or corrode over time because of the atomic bond.

Ÿ Exothermic connections provide greater current carrying capacity than the conductors.

Ÿ Versatile applications almost any conductor type and size connection is possible.

Ÿ Lasts indefinitely and will not age.

Part Number E-7140 E-7141 E-7142

Description Starter Kit Ignitor Handle

Starter Kit : Tool Box, Mould, Brushes, Sealant, Gloves, Crucible Cover, Handle,

Scrappers and Sealant 1

Ignitor : Ignitor and Batteries / Charger

Handle : Handle and Crucible Cover

Uses :

For all Exothermic welding connection applications.

Exothermic Accesories

Item Discontinued - refer to DEHN Cataogue for alternative

Page 13: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Exothermic Connections

Exothermic Connections

EARTHING SYSTEMS

12

Part Number E-7310 E-7320 E-7330

Type of Weld T-Weld Straight Weld Cross Weld

Conductor Type Stranded/ Flat/Solid - Copper/Steel Conductors

Conductor Size 16/140mm² / 10mm dia. /25 to 50X3mm

Packing Unit (pcs) 10

Uses :

Exothermically welded of earthing conductors to form atomic bonds which are able to withstand multiple fault currents.

Connections are permanent and are able to last for many years.

Part Number ED7420 EB7421 ED7422 ED7423

Type of Weld Steelwork Railway Rebar Tanks/Vessels/Pipe

Conductors Type Stranded/ Flat/Solid - Copper/Steel Conductors

Conductor Size 16/140mm² / 10mm dia. /25 to 50X3mm

Packing Unit (pcs) 10

Uses :

Exothermically welded of earthing conductors to form atomic bonds which are able to withstand multiple fault currents.

Connections are permanent and are able to last for many years.

Conductor to Electrode Exothermic Weld Conductor to Conductor Exothermic Weld

Conductor to Steelwork Exothermic Weld

Part Number E-7200 E-7220 E-7230

Type of Weld Stranded to Rod Solid to Rod Flat to Rod

Electrode Diameter 16/20mm 16/20mm 16/20mm

Conductor Size 16/140mm² 10mm dia. 25 to 50X3mm

Cu Layer 250 micron 250 micron 250 micron

Packing Unit (pcs) 10 10 10

Uses :

Earth electrodes are exothermically welded to earthing conductors to form atomic bonds which are able to withstand multiple fault currents.

Connections are permanent and are able to last for many years.

Part Number E-8120

Type of Weld All exothermic welded applications

Conductors Type Stranded/ Flat/Solid - Copper/Steel Conductors

Conductor Size 16/140mm² / 10mm dia. /25 to 50X3mm

Packing Unit (pcs) 10

Uses :

Moulds are manufactured for all standard exthermic type connections.

Moulds can also be individually designs and manufactured to suite just about any type of application.

Exothermic Weld Moulds

Page 14: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earthing Connections

Earth Enhancing Compounds

EARTHING SYSTEMS

13

Part Number E-8120

Type of Clamp Hydraulic Crimp

Electrode Diameter Solid Conductor to Solid Conductor

Conductor Size 70mm²/150mm²

Material Bronze

Packing Unit (pcs) 10

Uses :

Conductor C- Clamps are used for above and below ground connection of earthing conductors.

Part Number E-9120

Description Earth Enhancing Compound

Hole Volume d X 0.7854 X D = m³ (d=Hole Dia., D=Hole Depth)

Trench Volume w X h X L = m³ (w=Width, h= Depth of trench, L = Length)

Packing Unit (mtr) 25kg Bag = 0.03m³

Uses :

Easy to use compound that reduces soil resistivity and enhances earthing system performance.

Improves earth electrode contact with the soil, lowers earthing system resistance,

traps moisture and will not leach over time.

Rod Clamps (Standard) Conductor C- Clamps

Pontonite Earthing Compound

Part Number E-8700 E-8720(Lrg)

Type of Clamp Stranded/ Solid conductor to Rod

Electrode Diameter 16/20mm 16/20mm

Conductor Size 50mm²/70mm² 95mm²/120mm²

Material Bronze Bronze

Packing Unit (pcs) 10 10

Uses :

Earth electrodes Clamps are used for the connection of earthing conductors to earth electrodes where inspection pits are installed.

Pontinite Application

SOIL BACKFILL

PONTINITE

EARTH ELECTRODE

SOIL BACKFILL

CONDUCTORPONTINITE

Pontinite Application

Page 15: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earth Bars

Earth Bars

EARTHING SYSTEMS

14

Part Number EB1110 EB1150 SE1130

Earth Bar Size 50mmX6mm 50mmX6mm 50mmX6mm

Earth Bar Length 1000mm 500mm 300mm

Material Flat Cu (Tinned) / Stainless steel Backing Plate

Complete Assembly Ceramic pin insulators mounted on backing plate

Packing Unit (pcs) 1 1 1

Uses :

Flat copper earth bar mounted backing plate allow for easy installation.

Test clamps allow for identification and testing of earth termination cables.

Part Number EB1210 EB1250 EB1230

Earth Bar Size 50mmX6mm 50mmX6mm 50mmX6mm

Earth Bar Length 1000mm 500mm 300mm

Material Flat Cu / Galvanised steel Backing Plate

Complete Assembly Ceramic pin insulators mounted on backing plate

Packing Unit (pcs) 1 1 1

Uses :

Flat copper earth bar mounted backing plate allow for easy installation.

Earth Bars can be tinned if required.

Earth Bar with Double Test Clamps Earth Bar with Single Test Clamp

Earth Mounted on Backing Plate

Part Number EB1024 EB1050 EB1030

Earth Bar Size 50mmX6mm 50mmX6mm 50mmX6mm

Earth Bar Length 1000mm 500mm 300mm

Material Flat Cu / Galvanised steel Backing Plate

Complete Assembly Ceramic pin insulators mounted on backing plate

Packing Unit (pcs) 1 1 1

Uses :

Flat copper earth bar mounted backing plate allow for easy installation.

Double test clamps allow for identification and testing of earth termination cables.

Page 16: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earth Bars

Earth Bars

EARTHING SYSTEMS

15

Part Number EB1410 EB1450 EB1430

Description Perspex earth bar cover

Earth Bar Length 1000mm 500mm 300mm

Material 6mm Thick Perspex

Packing Unit (pcs) 1 1 1

Uses :

Earth Bar covers are used to protect connection point from damage.

Wall Mounted Earth Bar Earth Bar Covers

Part Number EB1310 EB1350 EB1330

Earth Bar Size 50mmX6mm 50mmX6mm 50mmX6mm

Earth Bar Length 1000mm 500mm 300mm

Material Flat Cu / Tinned Cu

Complete Assembly Ceramic pin insulators with wall anchor bolts

Packing Unit (pcs) 1 1 1

Uses :

Flat copper earth bar mounted on walls for the termination of earthing systems and equipment.

Earth Bars can be tinned if required.

Page 17: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earth Bars

Anti-moisture Sealant

EARTHING SYSTEMS

16

Anti-moisture Sealant

Part Number E-1701 E-1702

Description Denso Sealant

Tape Paste

Size 50mmX10m Roll 500g Bucket

Packing Unit (pcs) 1 1

Uses :

Used to prevent moisture ingress into below ground earthing system connection points.

Easy to use.Anti-moisture Sealant

Part Number EB1510 EB1320

Earth Bar Size 25mmX6mm 25mmX6mm

Earth Bar Length 100mm 200mm

Material Flat Cu / Tinned

Complete Assembly Ceramic pin insulators with wall anchor bolts

Packing Unit (pcs) 1 1

Uses :

Smaller cross section earth bars are used in lower fault current environments where fewer connections are required.

Telecommunications Earth Bar

Part Number EB1600

Description Earthing D/B` complete

Assembly Detail Sheet Metal Enclosure - 500mmX400mmX300mm

2 of 50mmX6mmX500mm Earth bars

Connections and Copper Conductors

Packing Unit (pcs) 1

Uses :

Earthing D/B`s are used as the main entry point connection for the earth termination systems to the internal part of structures.

Earth Bar D/B

Page 18: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

In the event of a direct lightning strike to the lightning protection system, the down conductor system is designed to safely guide the lightning current from the air termination system towards the earth termination system.In order to reduce the probability of damage due to Lightning current flowing in the lightning protection System, the down conductors be arranged in such a way from the point of strike to earth :

shall

So that several parallel current paths to earth exist

So that equipotential bonding to conducting parts of the structure is performed.

So that the length of current path is kept to a minimum

So that the Separation Distance between the down conductors and other electrically conductive elements within the structure shall be taken into account.

Down Conductor Systems

Natural Down Conductors

17

The following parts of a structure can be considered as a natural down conductor.

Structural Steelwork

Rainwater Down Pipes (Provided that the cross section exceeds 50mm², the thickness exceeds 0,5mm and that the sections are welded together)

Concrete Steel Reinforcing (care must be taken to ensure electrical continuity across the interconnected concrete steel reinforcing).

Steel Facades (provided that the thickness exceeds 0,5mm and that there is electrical Continuity in a vertical direction)

The use of natural elements of the structure will result in a more effectivelightning protection system, an aesthetically pleasing installation and theseparation distance between the lightning protection system and the Internal conductive can be ignored.

DOWN CONDUCTORS

Natural down conductor

Aluminium down conductor

Page 19: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Natural Down Conductors

Natural Down Conductors

DOWN CONDUCTORS

18

Part Number D-7340

Description: Concrete Steel Reinforcing Bonding Assembly

Assembly Parts U-clamp, Galv. Conductor (300mm),

Nuts, Bolts, Washers

Packing Unit (pcs) 1

Uses :

The installation of the down conductor system during construction.

Installed at top of concrete columns or at ring beam level.

Bonding Terminal with Test Box Assembly

Part Number D-7240

Description: Concrete Steel Reinforcing Bonding Assembly with Test Box

Assembly Parts U-clamp, Galv. Conductor (300mm),

Brass Terminal, Test Box,

Cu Conductor (1000mm), PVC Conduit (200mm)

Nuts, Bolts, Washers, Cover Plate

Packing Unit (pcs) 1

Uses :

The installation of the down conductor system during construction.

Use of natural elements (Rebar) enhances

Part Number D-7440

Description: Concrete Steel Reinforcing Bonding Assembly with Brass Terminal

Assembly Parts U-clamp, Galv. Conductor (300mm),

Brass Terminal, Nuts, Bolts, Washers

Packing Unit (pcs) 1

Uses :

The installation of the down conductor system during construction.

Bonding Terminal with Test Box Assembly

Ring Beam bonding Terminal Bonding Assembly with Brass Terminal

Page 20: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Natural Down Conductors

Natural Down Conductors

DOWN CONDUCTORS

19

Part Number D-7540

Description: Concrete Steel Reinforcing Bonding Assembly

Assembly Parts U-clamp, Galv. Conductor (300mm),

Nuts, Bolts, Washers

Packing Unit (pcs) 1

Uses :

The installation of the down conductor system during construction.

Installed at top of concrete columns or at ring beam level.

Spring Loaded Rebar Bonding Assembly

Clamp to Steelwork / I-Beams

Structural Steelwork Clamp

Part Number D-7740

Description Structural Steel / I-Beam Clamp

Steelwork Clamp Size 6mm - 50mm

Material Plated Steel

Packing Unit (pcs) 10

Uses :

Clamp is used for the effective connection to structural steelwork (natural down conductor).

Can be fitted to almost any size or thickness of steelwork

Allows for disconnection for testing purposes.

Spring Loaded Rebar Bonding Assembly

Item Discontinued - refer to DEHN Cataogue for alternative

Page 21: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

External Down Conductors

External Down Conductors

DOWN CONDUCTORS

20

Part Number ABD7925

Description Flat Copper Saddle

Conductor Size 25mm X 3mm

Material Brass

Packing Unit (pcs) 10

Uses :

25mmX3mm Brass saddles are used for mounting flat copper down conductors neatly to walls. Can also be used for equipotential bonding and air termination systems.

Flat Copper Saddle

Part Number D-7840

Description Rainwater Down Pipe Clamp

Down Pipe Size 20mm - 200mm Dia.

Material Plated Steel

Packing Unit (pcs) 10

Uses :

Clamp is used for the connection and use of rainwater down pipes as fixings to run down conductors from roof level to ground floor level.

Can be fitted to almost any size or thickness of down pipes.

Part Number AD8025

Description Flat Aluminium Saddle

Conductor Size 25mm X 3mm

Material Al

Packing Unit (pcs) 10

Uses :

25mmX3mm Aluminium saddles are used for mounting flat aluminium down conductors neatly to walls. Can also be used for air termination systems.

Flat Aluminium Saddle

Rain Water Down Pipe Clamp

Rain Water Down Pipe Clamp

Page 22: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

External Down Conductors

DOWN CONDUCTORS

21

Part Number AD8109

Description Round Aluminium Down Conductor

Down Conductor Size 8mm - 9mm Dia.

Material Al

Packing Unit (mtr) 100

Uses :

Alumunium down conductors are for use on structures where the use of natural down conductors is not possible.

Often used in retrofit projects.

Round Aluminium Down Conductors

Round Aluminium Down Conductors

Page 23: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Air Termination Systems

22

AIR TERMINALS

The probability of structure penetration by lightning is considerably decreased by the presence of a properly designed air termination system.

Air termination systems can comprise any of the following elements:

Individual air termination rods should be connected together at roof level to ensure current division.

PositioningAir terminals installed to a structure shall be located at Corners, exposed points and edges in accordance with One or all of the following methods:

Air terminals should be installed as follows:· If the roof is made of non-combustible material, air terminals may be installed on the surface of

the roof.· If the roof is made of readily-combustible material, due care needs to be taken with regard to the

distance between the air termination conductors and the material. Typically, for thatch roofs, a distance of 1,0 m is adequate.

Natural air terminalsMetal components of a roof structure may be considered as natural air terminals and therefore part of the LPS – provided they are in accordance with the following table :

· Rods and finials (including free-standing masts)

· Meshed conductors

· Protection angle method

· Mesh method

· Catenary wires

· Rolling sphere method

Air Termination Rod

Protective Angle

a

Mesh Size M

Earth Termination System

RollingSphere

r

h1

Page 24: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Free Standing Air Terminals 2000 to 12 000mm

AIR TERMINALS

23

12m Long Freestanding Air Terminal

Part Number A-1800 A-1900 A-1100 A-1110 A-1120

Max Height 8000mm 9000mm 10000mm 11000mm 12000mm

Space Req. For Tripod 4920X5640mm

Material (Mast) Al Al Al Al Al

Qty of Concrete Bases 6 x 15kg 6 x 15kg 6 x 15kg 6 x 15kg 6 x 15kg

Packing Unit (each) 1 1 1 1 1

Uses :

Freestanding Air Terminals with weighted Tripod stays are used to protect large roof superstructures and plant structures located on roofs.

Can be installed to roofs with a max 10° roof pitch. Easy to retrofit to structures - no drilling required.

Air terminals are dimensioned for wind speeds up to 140km/h.

4920X5640mm 4920X5640mm 4920X5640mm 4920X5640mm

4000

2000

2000

2000

1000

1000

2300

12000

4920 7501400

1800

3000

5640

Ø16

Ø70

Ø80

Ø90

Ø100

Ø10

Concrete Base

Item Discontinued - refer to DEHN Cataogue for alternative

Page 25: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Free Standing Air Terminals 2000 to 8000mm

AIR TERMINALS

24

8m Long Freestanding Air Terminal

Part Number A-2500 A-2600 A-2700 A-2800

Max Height 5000mm 6000mm 7000mm 8000mm

Space Req. For Tripod 4920X5640mm

Material (Mast) Al Al Al Al

Qty of Concrete Bases 6 x 15kg 6 x 15kg 6 x 15kg 6 x 15kg

Packing Unit (each) 1 1 1 1

Uses :

Freestanding Air Terminals with weighted Tripod stays are used to protect large roof superstructures and plant structures located on roofs.

Can be installed to roofs with a max 10° roof pitch. Easy to retrofit to structures - no drilling required.

Air terminals are dimensioned for wind speeds up to 140km/h.

4920X5640mm 4920X5640mm 4920X5640mm

4920

7501400

1800

3000

5640

Item Discontinued - refer to DEHN Cataogue for alternative

Page 26: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Free Standing Mast

AIR TERMINALS

25

25m Long Freestanding Mast

Part Number A-3800 A-3900 A-3100

Height of Mast 8000mm-25000mm 8000mm-25000mm 8000mm-25000mm

Mast Base 500X500mmX1000mm

Material (Mast) Steel / Painted Steel / Galvanised Al

Packing Unit (each) 1 1 1

Uses :

Freestanding Masts are used in Explosive type areas and for thatch roofed structures.

Freestanding Masts are installed directly into ground.

Freestanding Masts are specifically manufactured to suite clients` requirements and can be stayed for high wind environments.

500X500mmX1000mm 500X500mmX1000mm

700

PLATE:400 X 400 X 10mm THK

1000

101mmØ

88mmØ

6000

700

5300

76mmØ

60mmØ

700

2300

23

0070

0

FINIAL

50mmØ

6mm TOP PLATE16mm NUT

23

00

70

0

23

00

70

01

80

07

00

23000

114mmØ200

1000

Page 27: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Free Standing Mast - Roof / Concrete Mounted

AIR TERMINALS

26

Freestanding Mast - Roof / Concrete Mounted

Part Number A-4800 A-4900 A-4100

Height of Mast 8000mm-16000mm 8000mm-16000mm 8000mm-16000mm

Mast Base 500X500mmX1000mm

Material (Mast) Steel / Painted Steel / Galvanised Al

Packing Unit (each) 1 1 1

Uses :

Roof Mounted Freestanding Masts are used to create isolated protection zones over electronic equipment where simple bonding is not applicable.

Roof Mounted Masts are installed directly onto concrete roofs by means of chemi-bolts.

Freestanding Masts are specifically manufactured to suite clients` requirements and can be stayed for high wind environments.

500X500mmX1000mm 500X500mmX1000mm

10mm THK GUSSETS

300 X 300 X 10mm THK

GUSSETS 8mm THK

300 X 300 X 10mm THK

300 X 300 X 10mm THKPLATE:

PLATE:

HINGE:34mmØ X 3mm THK

18

0

11480 80

18

0

Page 28: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Free Standing Catenary Mast

AIR TERMINALS

27

25m Long Freestanding Catenary Mast

Part Number A-5800 A-5900

Height of Mast 8000mm-25000mm 8000mm-25000mm

Mast Base 500X500mmX1000mm

Catenary Wire 6mm Dia. Galv. Steel 6mm Dia. Galv. Steel

Material (Mast) Steel / Painted Steel / Galvanised

Packing Unit (each) 1 1

Uses :

Freestanding Catenary Masts are used in Explosive type areas and are equipped with Catenary Wires to afford greater zones of protection.

Freestanding Catenary Masts are installed directly into ground.

Freestanding Masts are specifically manufactured to suite clients` requirements and are stayed for greater stability.

500X500mmX1000mm

LightningProtection Mast

h

d > 0.1 h

Catenary Wire 25 mm

Earth Termination System

Page 29: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Finials

Finials

AIR TERMINALS

28

Wall Mounted Aluminium Finial

Base Mounted Finial

Part Number A-6300 A-6430 A-6530

Finial Length/Base Type 300-1200mm 1300-2000mm 2000-5000mm

Finial Diameter 20mm 20mm 20mm

Material Al Al Al

Packing Unit (pcs) 1 1 1

Uses :

Finials are for use in air termination systems.

Used for protection of electronic equipment at roof level.

Offer Angle of Protection & Rolling Sphere applications.

Zones are determined by requirements of IEC 62305 Part 3

225

130

225

30

30

332

130

MAST BRACKET

Part Number A-7200 A-7400 A-7600

Finial Length/Base Type 2000mm 4000mm 6000mm

Finial Diameter 20mm 20mm 20mm

Material Galv Steel Galv Steel Galv Steel

Packing Unit (pcs) 1 1 1

Uses :

Finials are for use in air termination systems base mount means no drilling into concrete. Used for protection of electronic equipment at roof level.

Offer Angle of Protection & Rolling Sphere applications.

Zones are determined by requirements of IEC 62305 Part 3

Item Discontinued - refer to DEHN Cataogue for alternative

Page 30: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Finials

Finials

AIR TERMINALS

29

Galvanised Steel Finial

Plated Steel Finial - Multi-angle

Part Number A-8300 A-8430 A-8530

Finial Length/Base Type 300-1000mm Flat Roof Wall Mount

Finial Diameter 16mm 16mm 16mm

Material Galv. Steel Galv. Steel Galv. Steel

Packing Unit (pcs) 1 1 1

Uses :

Finials are for use in air termination systems.

Wall or flat mounted base selection required.

Offer Angle of Protection & Rolling Sphere applications.

Zones are determined by requirements of IEC 62305 Part 3

Part Number A-9300

Finial Length/Base Type 300mm

Finial Diameter 16mm

Material Plated Steel

Packing Unit (pcs) 1

Uses :

Finials are for use in air termination systems.

Finial can be set at various angles to offer superior zone of protection.

Offer Angle of Protection & Rolling Sphere applications.

Zones are determined by requirements of IEC 62305 Part3

Page 31: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Saddles

Saddles

AIR TERMINALS

30

Part Number AD1020

Saddle Type Aluminium stand-off

Saddle Dimension 34mm(L)X12mm(W)X30mm(H)

Material Aluminium / PVC Backing Strip

Packing Unit (mtr) 50

Uses :

Stand-off aluminium saddles are used to house aliminium alloy Air Termination and

Down Conductor systems.

Saddles are equipped with PVC backing strips to prevent direct contact with concrete and mortar.

Saddles to be installed 700mm apart.

Aluminium Saddle

Stainless Steel Saddle

Part Number AD1120

Conductor Dia. 8mm-10mm

Saddle Dimension 10mm(L)X5mm(W)X12mm(H)

Material Stainless Steel

Packing Unit (mtr) 50

Uses :

Stand-off aluminium saddles are used to house aliminium alloy and stainless steel Air Termination and Down Conductor systems.

Saddles are fixed by means of a 5mm fisher plug and screw or can be fixed by

means of an epoxy bond.

Saddles to be installed 700mm apart.

34

12

30

12

Page 32: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Stand-off Saddles

Stand-off Saddles

AIR TERMINALS

31

Part Number A-1220

Conductor Dia. 8mm-10mm

Saddle Dimension 25mm(L)X20mm(W)X26mm(H)

Material Galvanised Steel

Packing Unit (mtr) 50

Uses :

Stand-off aluminium saddles are used to house aliminium alloy and stainless steel air termination conductors.

Saddles are designed for easy fixing onto steel roof sheeting less than 6mm thick .

Stand-off Saddle - Steel Roofs

3Part Number A-1320

Conductor Dia. 8mm-10mm

Saddle Dimension 25mm(L)X20mm(W)X26mm(H)

Material Galvanised Steel

Packing Unit (mtr) 50

Uses :

Stand-off aluminium saddles are used to house aliminium alloy and stainless steel Air Termination conductors.

Saddles are designed for easy fixing onto steel roof sheeting eves less than 6mm

thick .

42

25

26

Stand-off Saddle - Steel Roofs

Stand-off Saddle - Steel Roofs

Stand-off Saddle - Steel Roofs

Page 33: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Expansion Joints

Special Joints & Connections

AIR TERMINALS

32

Aluminium Expansion Loop Braided Expansion Joint

Part Number A-1720

Conductor Type Flat & Round

Expansion Loop Dimension 25mmX3mmX300mm

Material Braided Galv. Steel

Packing Unit (mtr) 10

Uses :

Aluminium Expansion Loops are used as part of the air termination conductor system to make provision of for the expansion and contraction of the conductors due to heat and cold.

Expansion Loops should be installed at intervals of 30m apart.

Part Number A-1610

Conductor Dia. 8mm-10mm

Ezpansion Loop Dimension 34mm(L)X12mm(W)X30mm(H)

Material Aluminium

Packing Unit (mtr) 10

Uses :

Aluminium Expansion Loops are used as part of the air termination conductor system to make provision of for the expansion and contraction of the conductors due to heat and cold.

Expansion Loops should be installed at intervals of 30m apart.

158 8

395

6666

Universal Conductor Clamp

Part Number ADB1820

Conductor Clamp Size 8mm-20mm

Clamp Dimension 40mm(L)X30mm(W)X34mm(H)

Material Galvinised Steel

Packing Unit (mtr) 10

Uses :

Universal clamps are used for the following types of connections :

Ÿ Down conductors to air terminals,

Ÿ Finials to air terminal conductors,

Ÿ Air terminals to air terminals.

Ideal for use as a Bi-metallic connection.

Universal conductor clamps can effectively connect different size conductors together.

Universal conductor clamps are used for the connection of expansion loops into the

air termination system.

20

34

34

40

Page 34: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Stand-off Saddles

Air Terminals

AIR TERMINALS

33

Part Number A-1920

Conductor Dia. 8mm-10mm

Saddle Dimension 25mm(L)X20mm(W)X26mm(H)

Material Galvanised Steel

Packing Unit (mtr) 50

Uses :

Stand-off aluminium saddles are used to house aliminium alloy and stainless steel Air Termination conductors.

Saddles are designed for easy fixing onto flat concrete roofs.

Stand-off Saddle - Flat Roofs

Stand-off Saddle - Flat Roofs

Page 35: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Internal Equipotential Bonding

34

EQUIPOTENTIAL BONDING

Eqipotentialization is performed to prevent dangerous sparking within a structure due to lightning current flowing in the external LPS or any conductive parts of a structure.

The equipotential bonding of the following elements to the external LPS is essential :

Internal Systems

The interconnection of the LPS to these systems can be done by means of the following :

The value of carrying out of the correct equipotential bonding cannot be understated in value of protecting electronic equipment.

Metal Installations

External conductive parts and lines connected to the structure.

Bonding conductors, where electrical continuity is not provided by natural bonding

Surge Protection Devices, where direct connections with bonding conductors is not feasible.

Various earth termination systems

Internal Bonding Of Internal Conductive Elements

Equipotential Bonding of Earths

LIGHTNING PROTECTIONEARTH

TELECOMEARTH

MAINEARTH

TELECOMEARTH BAR

MAINEARTH BAR

DOWNCONDUCTOR

GAS WATER WASTEWATER

HEATING

INTERNAL METALELEMENTS

INTERNALSTEELWORK

POWER SUPPLY

POWER SUPPLY

230/400V AC

FOUNDATION EARTHING SYSTEM

EXTERNALLIGHTNINGPROTECTION

CATHODICPROTECTED

TANK

DATA SURGE PROTECTIONDEVICE

POWER SURGE PROTECTIONDEVICE

ISOLATION SPARK GAP

EQUIPOTENTIAL EARTH BAR

Page 36: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Computer Room Earthing & Bonding

Pipe Bonding Clamp

35

Part Number B-2120

Description Pipe Bonding Clamp

Pipe Size 20mm - 200mm Dia.

Material Plated Steel

Packing Unit (pcs) 10

Uses :

Clamp is used for the connection and equipotential bonding of pipes and other conductive elements into the lightning protection system.

Can also be used for the bridging of pipe flanges.

Pipe Bonding Clamp

Part Number B-1120

Description Access Floor Bonding Clamp

Clamp Dimension 110mm(L)X45mm(W)X20mm(H)

Material Galvanised Steel

Packing Unit (mtr) 50

Uses :

Used for the earthing and bonding of access floor systems in computer and data facilities. Unique design allows for the bonding of long runs without having to cut bonding conductors. The use of lugs is also eliminated.

Access Floor Bonding Clamp

EQUIPOTENTIAL BONDING

Access Floor Bonding Clamp

60

45

20

50

Page 37: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Substation Bonding

Bonding of Pipe Flanges

36

Part Number D-4120

Conductor Size 16mm²-95mm²

Bolt Size 10mm - 45mm

Material Stainless Steel

Packing Unit (mtr) 10

Uses :

Bonding of Pipe Flanges to ensure electrical continuity along pipelines.

Also use for equipotential bonding of other conductive elements of structures.

Bonding brackets utilise existing nuts and bolts to form a good connection to the pipe flanges.

Pipe Flange Bonding Bracket

EQUIPOTENTIAL BONDING

Part Number B-3120 B-3121

Description Braided Bonding Strap for Transformer gate posts

Dimension 25mmX5mmX300mm 40mmX5mmX300mm

Material Braided Galv. Steel Braided Galv. Steel

Packing Unit (mtr) 10 10

Uses :

Braided bridge straps are for the equipotential bonding of the transformer gate posts into the earth termination system.

Bonding straps are also available in 180mm long lengths.

Transformer Gate Bonding Straps

Transformer Gate Bonding Strap

250 2525

25

5 5

300

Pipe Flange Bonding Bracket

10

16

10

1835

33

16

180

35355

Page 38: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Bonding of Pipe Flanges

Bonding of Off-loading Vehciles

37

Part Number D-4120

Conductor Size 50mm² Low Resistance Cu Cable

Cable Length 5000mm

Packing Unit (each) 1

Uses :

Bonding assembly for off-loading facilities complete with : Bonding Earth Bar,

Retractable Reel, 50mm² Cu Cable, Brass Fittings, Galv Clamp and Rubber Stopper.

Essential for the off-laoding of flammable, explosive and hazardous materials.

Pipe Flange Bonding Bracket

EQUIPOTENTIAL BONDING

Part Number B-3120 B-3121

Description Braided Bonding Strap for Transformer gate posts

Dimension 25mmX5mmX300mm 40mmX5mmX300mm

Material Braided Galv. Steel Braided Galv. Steel

Packing Unit (mtr) 10 10

Uses :

Braided bridge straps are for the equipotential bonding of the transformer gate posts into the earth termination system.

Bonding straps are also available in 180mm long lengths.

Pipe Flange Bonding Bracket

Truck Off-loading Connection Clamp

Pipe Flange Bonding Bracket

Page 39: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Earthing Parts

38

PART Nos. / INDEX

Part Number Page

EDB1120 5

EDB1070 5

EBD1050 5

EBD1035 5

EBD1016 5

EBD2120 5

EBD2070 5

EBD2050 5

EBD2035 5

EBD2016 5

EBD3300 5

EBD3150 5

EDB3150 5

EBD3075 5

EB4170 5

EB5095 6

EB5070 6

EB5050 6

EB5035 6

EB6400 6

EB6300 6

EB6185 6

EB6150 6

EB6120 6

EB7090 6

EB7070 6

EB7035 6

EB7016 6

EB8090 6

EB8070 6

EB8035 6

EB8016 6

EB9150 6

E-1240 9

E-1150 9

E-1120 9

E-2150 9

E-2300 9

E-2152 9

E-2132 9

E-2160 9

E-2161 9

E-2200 9

E-3120 9

E-4240 10

E-5225 10

E-5150 10

E-6240 11

E-7140 11

E-7141 11

E-7142 11

E-7200 12

E-7220 12

E-7230 12

E-7310 12

E-7320 12

E-7330 12

ED7420 12

EB7421 12

ED7422 12

Part Number Page

ED7423 12

E-8120 12

E-8700 13

E-8120 13

E-9120 13

EB1024 14

EB1050 14

EB1030 14

EB1110 14

EB1150 14

EB1130 14

EB1210 14

EB1250 14

EB1230 14

EB1310 15

EB1350 15

EB1330 15

EB1410 15

EB1450 15

EB1430 15

EB1510 15

EB1320 15

EB1600 15

E-1701 16

E-1702 16

Part Number Page

Page 40: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Down Conductor Parts

39

PART Nos. / INDEX

Part Number Page

EDB1120 5

EDB1070 5

EBD1050 5

EBD1035 5

EBD1016 5

EBD2120 5

EBD2070 5

EBD2050 5

EBD2035 5

EBD2016 5

EBD3300 5

EBD3150 5

EDB3150 5

EBD3075 5

AD8050 7

AD8070 7

AD8075 7

AD8120 7

ED7420 12

ED7422 12

ED7423 12

D-7240 19

Air Termination Parts

Part Number Page

D-7340 19

D-7440 19

D-7540 20

D-7640 20

D-7740 20

D-7840 21

ABD7925 21

AD8125 21

AD1020 31

AD1120 31

AD1420 32

AD1520 32

ADB1820 33

Part Number Page

Part Number Page

AD8050 7

AD8070 7

AD8075 7

AD8120 7

ABD7925 21

AD8125 21

A-1800 24

A-1900 24

A-1100 24

A-1110 24

A-1120 24

A-2500 25

A-2600 25

A-2700 25

A-2800 25

A-3800 26

A-3900 26

A-3100 26

A-4800 27

A-4900 27

A-4100 27

A-5800 28

A-5900 28

A-6300 29

A-6430 29

Part Number Page

A-6530 29

A-7200 29

A-7400 29

A-7600 29

A-8300 30

A-8430 30

A-8530 30

A-9300 30

AD1020 31

AD1120 31

A-1220 32

A-1320 32

AD1420 32

AD1520 32

A-1610 33

A-1720 33

ADB1820 33

Part Number Page

Page 41: EARTHING & LIGHTNING PROTECTION · PDF fileSANS Code 10199 - Design & Installation of an Earth Electrode SANS Code 10089-2 ... Earth termination design : Type ‘B’ Earthing Systems

Equipotential Bonding Parts

40

PART Nos. / INDEX

Part Number Page

EDB1120 5

EDB1070 5

EBD1050 5

EBD1035 5

EBD1016 5

EBD2120 5

EBD2070 5

EBD2050 5

EBD2035 5

EBD2016 5

EBD3300 5

EBD3150 5

EDB3150 5

EBD3075 5

EB7421 12

EB1024 14

EB1050 14

EB1030 14

EB1110 14

EB1150 14

EB1130 14

EB1210 14

EB1250 14

EB1230 14

EB1310 15

EB1350 15

Part Number Page

EB1410 15

EB1450 15

EB1430 15

EB1510 15

EB1320 15

EB1600 15

ABD7925 21

ABD8125 21

ABD1820 33

B-1120 36

B2120 36

B-3120 37

B-3121 37

Part Number Page