ABBREVIATIONS EDR EQUIVALENT DIRECT RADIATION SA GALV GALVANIZED STP HWCF HEATING HOT WATER CHEMICAL FEED HHWR HWP HEATING HOT WATER RETURN HEATING HOT WATER PUMP STS STRUCT HPWS HPWP HSPF HRP HR HE HD HORIZ HP HPWR HEAT RECOVERY PUMP HEAT PUMP WATER SUPPLY HEAT PUMP WATER PUMP HOUR HEATING SEASONAL PERFORMANCE FACTOR HEAT PUMP WATER RETURN HEAT EXCHANGER HORSEPOWER/HEAT PUMP HORIZONTAL HEAD (FT.) GR GRV GS H GIV GC GPM GPH GLYCOL RETURN GLYCOL SUPPLY HUMIDITY/HUMIDIFIER GRAVITY RELIEF VENTILATOR GENERAL CONTRACTOR GALLONS PER MINUTE GALLONS PER HOUR GRAVITY INTAKE VENTILATOR STD ST SS SPEC SRV SHT SD SG SHR SECT SF SCC SF SAT PTS F&T FLOAT & THERMOSTATIC STEAM TRAP FIRE DAMPER FTR GAL GA FT FPM FTG FINNED TUBE RADIATION GALLON GAUGE FEET PER MINUTE FOOTING FOOT/FEET FLR FCP FD FCU FLOOR FLUID COOLER PUMP FAN COIL UNIT RV RS RP RPM RM RHG RL RG RHC RH RAT RECIR RES RF R RA R(#) ENTERING WATER TEMPERATURE (°F) EVAPORAT(E), (ING), (ED), (OR) EXTERNAL STATIC PRESSURE (IN WG) EX EXP F&B °F EUH EVAP ET EWT DEGREES FAHRENHEIT FACE AND BY-PASS EXPANSION EXISTING EXPANSION TANK ELECTRIC UNIT HEATER EMER ENCL EOM ESP EQUIP EF EFF ELEV ELEC EG EMERGENCY END OF MAIN DRIP EQUIPMENT ENCLOSURE EXHAUST GRILLE ELEVATION ELECTRIC EFFICIENCY EXHAUST FAN PSIG PT PRESS PSI PREFAB PPM PNEU PER (%) PHWR PHWS PI PHC PH PCHS PD PE PCHR SUPPLY AIR STORAGE TANK PUMP STORAGE TANK SUPPLY STRUCTURE(E), (AL) STORAGE TANK STAINLESS STEEL STANDARD SAFETY RELIEF VALVE SPECIFICATIONS SHEET STEAM CONDENSATE COOLER SUPPLY AIR TEMPERATURE (°F) SUPPLY DIFFUSER SENSIBLE HEAT RATIO SUPPLY GRILLE SQUARE FOOT SECTION SUPPLY FAN PNEUMATIC TUBE STATION RELATIVE HUMIDITY RADIANT PANEL (CEILING-MOUNTED) REVOLUTIONS PER MINUTE REFRIGERANT SUCTION REFRIGERANT VENT RELATIVE HUMIDITY REFRIGERANT HOT GAS REFRIGERANT LIQUID REHEAT COIL RETURN GRILLE ROOM RECIRCULAT(E), (OR), (ING) RETURN AIR TEMPERATURE (°F) RETURN FAN THERMAL RESISTANCE REFRIGERANT (NUMBER) RETURN AIR POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH GAUGE PNEUMATIC TUBE PRESSURE PARTS PER MILLION PREFABRICATED PNEUMATIC PANEL CHILLED WATER SUPPLY PERIMETER HEATING HOT WATER RETURN PERIMETER HEATING HOT WATER SUPPLY PRESSURE DROP (IN OR WG AS NOTED) PANEL CHILLED WATER RETURN PERCENT PRESSURE INDICATOR PREHEAT COIL PHASE PNEUMATIC-ELECTRIC BFW BOILER FEED WATER MISC CONV CONVECTOR ENTERING AIR TEMPERATURE (°F) CONDENSER WATER CHEMICAL FEED CLASSROOM UNIT VENTILATOR EA EAT EC DN DWG ELECTRICAL CONTRACTOR EXHAUST AIR DRAWING DOWN CWP CWCF D DB CP CT CV CUV CUH CONDENSER WATER PUMP DRAIN BOX DRAIN CONTROL VALVE COOLING TOWER CABINET UNIT HEATER CONDENSATE PUMP P PBD OFOI OFCI OBD OA OAT NA NO NTS NIC NC MV MTD CONTRACTOR FURNISHED/OWNER INSTALLED CHILLED WATER RETURN CHILLED WATER CHEMICAL FEED BRITISH THERMAL UNIT PER HOUR CO CI CONN CHWR CF CFM CFOI CH CHCF CHP CONNECTION CAST IRON CLEANOUT CHILLED WATER PUMP CUBIC FEET PER MINUTE CHILLER CUBIC FEET CD BTUH CAB CAV BHP BFWP BOD BOP BLDG CONSTANT AIR VOLUME CONDENSATE DRAIN CABINET BOTTOM OF PIPING BOTTOM OF DUCT BRAKE HORSEPOWER BOILER FEED WATER PUMP BUILDING MIN MECH MD MCC MC MBH MAT LWT LPS LFC LFD LP LEC LD ACCESS DOOR ("M" DWGS). AREA DRAIN ("P" DWGS) AIR COOLED CONDENSING UNIT AMPERE (AMP, AMPS) BBD BFC BDD AMP ARCH AS AV APD APPROX BOILER BLOW DOWN BACKDRAFT DAMPER BELOW FINISHED CEILING AIR PRESSURE DROP (IN WG) ARCHITECT (URAL) APPROXIMAT(E), (LY) AIR SEPARATOR AUTOMATIC VENT ADJ AFF AHU ALTER AFM ACCU ACU AD ADA AAF ADJUSTABLE AIR FLOW MONITORING ABOVE FINISHED FLOOR AIR HANDLING UNIT ALTERNATE AIR CONDITIONING UNIT AUTOMATIC AIR VENT AMERICAN DISABILITIES ACT LBS LAT LAF LAD LAB KW KEC IN INDIC INSUL INT INCIN INCL IB ID HHWS HZ UV UNIT VENTILATOR VARIABLE FREQUENCY DRIVE W/O WITHOUT MISCELLANEOUS OWNER FURNISHED/CONTRACTOR INSTALLED OWNER FURNISHED/OWNER INSTALLED OUTSIDE AIR TEMPERATURE (°F) PARALLEL BLADE DAMPER PUMP OPPOSED BLADE DAMPER OUTSIDE AIR NOT APPLICABLE NORMALLY CLOSED NORMALLY OPEN NOT TO SCALE NOT IN CONTRACT MANUAL VENT MOUNTED ZN WTR WPD ZONE WATER PRESSURE DROP WATER MIXED AIR TEMPERATURE (°F) THOUSANDS OF BTU PER HOUR MOTOR CONTROL CENTER MOTORIZED DAMPER MECHANICAL MINIMUM MECHANICAL CONTRACTOR MAXIMUM LABORATORY FURNISHINGS CONTRACTOR LOW PRESSURE STEAM LEAVING WATER TEMPERATURE (°F) LABORATORY EQUIPMENT CONTRACTOR LAMINAR FLOW DIFFUSER LIQUID PETROLEUM LINEAR DIFFUSER WG W/ WATER GAUGE WITH VB VERT VFD VIF VC VD VAC VAR VAV VA VACUUM BREAKER VOLUME DAMPER VERIFY IN FIELD VACUUM CLEANING VERTICAL VOLT AMPERE VARIABLE AIR VOLUME VACUUM VARIABLE TEMPERATURE CONTROL CONTRACTOR TEMPERATURE DIFFERENCE TOTAL STATIC PRESSURE (IN WG) UNLESS NOTED OTHERWISE HEAT TRANSFER COEFFICIENT LEAVING AIR TEMPERATURE (°F) KITCHEN EQUIPMENT CONTRACTOR LAMINAR AIR FLOW LAMINAR AIR DIFFUSER LABORATORY POUND KILOWATT HEATING HOT WATER SUPPLY INVERTED BUCKET STEAM TRAP INCH/INCHES INSULAT(E), (ED), (ION) INCLUD(E), (ED) INCINERATOR INDICATOR INTERIOR FREQUENCY (MEGAHERTZ) INSIDE DIAMETER UNO UC UH U TYP. TSTAT TSP UNIT HEATER UNDER CUT THERMOSTAT TYPICAL TC TEMP TONS TCC TD SV TB SUCT TEMPERATURE CONTROL TONS OF REFRIGERATION TEMPERATURE STEAM VENT TERMINAL BOX SUCTION CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY COP COEFFICIENT OF PERFORMANCE CHILLED WATER SUPPLY CHWS EER ENERGY EFFICIENCY RATIO SEER SEASONAL ENERGY EFFICIENCY RATIO HTR HEATER MAX STR STORAGE TANK RETURN VRV VARIABLE REFRIGERANT VOLUME BRANCH SELECTOR BOX BSB ABBREVIATIONS C COMMON LPC LOW PRESSURE CONDENSATE MPC MEDIUM PRESSURE CONDENSATE MPS MEDIUM PRESSURE STEAM HPS HIGH PRESSURE STEAM HPC HIGH PRESSURE CONDENSATE 2 M-301 3 M-501 SECTION REFERENCE DETAIL REFERENCE PLAN NOTE DRAWING NOTATIONS NOTE: ALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED FOR THIS PROJECT 1 1 DEMO NEW NEW TO EXISTING DEMO TO THIS POINT EQUIPMENT TAG - (SEE SCHEDULE SHEETS) DIFFUSER, REGISTER, GRILLE TAG - (SEE SCHEDULE SHEETS) SD24-12 300 XXX-1 CFM MARK DUCTWORK SYMBOLS BLADE DAMPER PBD = PARALLEL BLADE DAMPER DUCT-MOUNTED REHEAT COIL (HYDRONIC) INTERNALLY INSULATED DUCTWORK FLEXIBLE CONNECTION ACCESS DOOR MOTORIZED CONTROL DAMPER BDD = BACKDRAFT DAMPER OBD = OPPOSED FD = FIRE DAMPER FSD = FIRE/SMOKE MANUAL VOLUME DAMPER DAMPER SD = SMOKE DAMPER SHOETAP (OR 45° ENTRY) FITTING BELLMOUTH FITTING 45° LATERAL FITTING 90° TEE FITTING SHOETAP WITH SQUARE TO ROUND TRANSITION DUCT TRANSITION CONICAL FITTING AIR FLOW 20° 30° M AD FD 90° ELBOW WITH TURNING VANES STANDARD RADIUS ELBOW, CENTER RADIUS INSULATED FLEXIBLE DUCTWORK OFFSET IN DUCTWORK (R = RISE D = DROP) RECTANGULAR DUCTWORK ROUND SPIRAL DUCTWORK OVAL DUCTWORK DROP IN DUCTWORK (EXHAUST, RETURN, ETC.) RISE IN DUCTWORK (EXHAUST, RETURN, ETC.) RISE IN DUCTWORK (SUPPLY ONLY) DROP IN DUCTWORK (SUPPLY ONLY) 1-1/2 TIMES WIDTH OF DUCT 12"x8"ϴ 12"Ø 12"x8" R COUNTERBALANCED BACKDRAFT DAMPER BDD AD MOTORIZED BACKDRAFT DAMPER MBDD D DUCTWORK SYSTEMS EXHAUST AIR EXHAUST/RELIEF AIR KITCHEN EXHAUST AIR OUTSIDE AIR RELIEF AIR RETURN AIR SUPPLY AIR TRANSFER AIR EA EA/RL KEA OA RLA RA SA TA CO2 EQUIPMENT SYMBOLS SUPPLY DIFFUSER W/TYPE AND CFM (ONE-WAY SIDE TYPE) LINEAR DIFFUSER W/TYPE AND CFM (TWO-WAY SIDE TYPE) SUPPLY DIFFUSER W/TYPE AND CFM (THREE-WAY TYPE) SIDEWALL GRILLE W/TYPE AND CFM RETURN GRILLE W/ TYPE AND CFM SUPPLY DIFFUSER W/TYPE AND CFM (FOUR-WAY TYPE) SUPPLY DIFFUSER W/TYPE AND CFM (TWO-WAY SIDE TYPE) ROOF-MOUNTED EXHAUST FAN CEILING-MOUNTED EXHAUST FAN CARBON DIOXIDE SENSOR AT ROOF AT CEILING EXHAUST GRILLE W/ TYPE AND CFM H HUMIDITY SENSOR T THERMOSTAT F&T GENERAL DUTY VALVES & FITTINGS EXPANSION LOOP (SIZE INDICATED ON DRAWINGS) CONCENTRIC REDUCER ECCENTRIC REDUCER PRESSURE REDUCING VALVE STEAM TRAP W/DESIGNATION GAS COCK PETE'S PLUG PIPE EXPANSION JOINT FLEXIBLE PIPING CONNECTOR Y-STRAINER W/BLOWDOWN VALVE & CAP PIPE ANCHORS PIPE GUIDES THERMOMETER WELL AUTOMATIC AIR VENT GAUGE CONNECTION(S) & WELL THERMOMETER & WELL MANUAL AIR VENT AUTOMATIC BALANCING VALVE TWO-WAY CONTROL VALVE THREE-WAY CONTROL VALVE UNION MANUAL BALANCING VALVE VALVE IN RISER ANGLE VALVE PLUG VALVE TRIPLE DUTY VALVE PRESSURE REGULATING VALVE BUTTERFLY VALVE RELIEF VALVE VALVE - SEE SPECIFICATIONS FOR VALVE TYPE PIPE CONTINUED ON ANOTHER DRAWING CHECK VALVE CAPPED PIPE RISE IN PIPING DROP IN PIPING GATE VALVE BALL VALVE 1. THESE GENERAL NOTES APPLY TO M-SERIES DRAWINGS. ADDITIONAL GENERAL NOTES SPECIFIC TO A PARTICULAR DRAWING ARE NOTED ON THOSE SHEETS. 2. IT IS THE INTENT OF THESE DOCUMENTS TO PROVIDE MECHANICAL SYSTEMS THAT ARE FULLY FUNCTIONAL. PROVIDE ALL ITEMS SPECIFIED AND REQUIRED FOR COMPLETE OPERATIONAL SYSTEMS. 3. ON MECHANICAL "M" SERIES DRAWINGS, DARK LINE ITEMS INDICATE NEW WORK. LIGHT LINE ITEMS ARE ITEMS THAT SHALL REMAIN. 4. THESE DRAWINGS INDICATE REQUIRED SIZE AND POINTS OF TERMINATION FOR PIPING, DUCTWORK, CONDUIT, ETC.. THE EQUIPMENT SHOWN ILLUSTRATES SUGGESTED ROUTING, BUT ALL NECESSARY OFFSETS MAY NOT BE SHOWN. DIVISION 23 SHALL INSTALL HIS WORK IN A MANNER THAT WILL CONFORM WITH THE STRUCTURE. DIVISION 23 SHALL AVOID OBSTRUCTIONS, PRESERVE HEADROOM AND MAINTAIN MAXIMUM CLEARANCE WITHOUT FURTHER INSTRUCTION FROM THE ARCHITECT/ENGINEER OR ADDITIONAL COST TO THE OWNER. 5. ALL DUCTWORK, PIPING, AND VALVES SHALL BE CONCEALED ABOVE CEILING AND WITHIN WALLS IN FINISHED AREAS UNLESS OTHERWISE INDICATED. 6. ALL VALVES, ETC. SHALL BE INSTALLED ALLOWING EASY ACCESS BETWEEN LIGHT FIXTURES AND NO HIGHER THAN 12" TO 24" ABOVE THE CEILING. PROVIDE FITTINGS IN DUCTWORK AND PIPING AS REQUIRED SO THAT NO PIPING REMAINS TIGHT TO ROOF STRUCTURE. PROVIDE ACCESS PANELS AS REQUIRED. AREA ADJACENT TO THE ACCESS PANELS SHALL BE CLEAR OF ANY OBSTRUCTIONS. PROVIDE EXTENDED VALVE HANDLES FOR INSULATED PIPING. 7. DIVISION 23 SHALL BE GUIDED BY THE ARCHITECT/ENGINEER'S REFLECTED CEILING PLAN FOR LOCATION OF DIFFUSERS, REGISTERS, GRILLES SHOWN OR COVERED BY THESE PLANS. RETURN GRILLES SHALL NOT ALIGN WITH SUPPLY AIR THROW. 8. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL GRILLES, REGISTERS AND DIFFUSERS IN CEILINGS WITH THE CEILING SYSTEM AND LIGHT FIXTURES. PROVIDE FLEXIBLE DUCT UPSTREAM OF EACH DIFFUSER WHERE SHOWN. 9. ARROWS ON THE HOT WATER COLD WATER MAINS INDICATE THE DIRECTION OF FLOW. PITCH MAINS UPWARD A MINIMUM OF 1" PER 60' IN THE DIRECTION OF FLOW. ARROWS ON STEAM AND CONDENSATE PIPING AND DRAIN LINE INDICATE THE DOWNWARD PITCH OF THE PIPING. 10. INSTALL AIR VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS OF WATER PIPING SYSTEMS. DRAINS TO HAVE HOSE END THREADS WITH CLEARANCE TO ATTACH HOSE. 11. PIPING BRANCHES TO EQUIPMENT SHALL HAVE SAME SIZE VALVES AND FITTINGS AS THAT OF THE LINE SIZE WITH THE EXCEPTION OF THE TEMPERATURE CONTROL VALVES. 12. PIPE "SWING" CONNECTIONS WITH UNIONS OR FLANGES SHALL BE MADE EXTERNAL TO COILS OR A TUBE BUNDLE TO FACILITATE REMOVAL OF THAT ITEM WITHOUT DISTURBING THE BRANCH VALVES AND/OR PIPING. 13. DUCT AND PIPING PENETRATING FLOOR SLABS AND/OR WALLS SHALL BE SEALED WITH ACOUSTIC SEALANT. IF THE FLOOR OR WALL IS FIRE RATED PROVIDE THE FIRE STOPPING OR FIRE DAMPER TO MAINTAIN THE FIRE RATING. 14. ALL RECTANGULAR SHEET METAL DUCT SIZES ARE INSIDE DIMENSIONS. ALL ROUND DUCT SIZES SHOWN ARE INSIDE DIAMETERS. ALLOWANCE FOR ACOUSTICAL LINER WHERE INDICATED ON DRAWINGS MUST BE ADDED TO OBTAIN OUTSIDE SHEET METAL DIMENSION. 15. ALL WALL THERMOSTATS, TEMPERATURE SENSORS, AND/OR HUMIDISTATS SHALL BE APPROXIMATELY 48" ABOVE FINISHED FLOOR TO CENTER AND LINED UP HORIZONTALLY WITH LIGHT SWITCHES UNLESS OTHERWISE NOTED OR DIRECTED BY THE ARCHITECT/ENGINEER. 16. DIVISION 23 CONTRACTOR SHALL BE RESPONSIBLE FOR HIS RESPECTIVE WORK FOR REPAIRING AND PATCHING TO MATCH EXISTING SURFACES, SIDEWALKS, STREETS, FLOORS, WALLS, ROOFS, CEILING AND PAVEMENT. CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS FOR CUTTING AND PATCHING REQUIRED TO INSTALL NEW OR REMOVE EXISTING WORK, EQUIPMENT, OR SYSTEMS. 17. DIVISION 23 CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL OF HIS WORK TO BE INSTALLED WITH ANY AND ALL OTHER CONTRACTORS TO BE AFFECTED BY SUCH WORK, PRIOR TO ORDERING ANY OF THE EQUIPMENT. THIS SHALL INCLUDE BUT NOT LIMITED TO ELECTRICAL CHARACTERISTICS, CONNECTIONS REQUIRED, PHYSICAL SIZE, COLOR AND FIT. ALSO REFER TO SPECIFICATIONS. 18. ALL EQUIPMENT SHALL BE OF, AND CONSIST OF, AT LEAST MINIMUM SIZES SELECTED, AND SHALL PERFORM TO OR SURPASS THE MINIMUM REQUIREMENTS, SCHEDULES, NOTED AND SPECIFIED. 19. COORDINATE INSTALLATION OF NEW WORK WITH ALL OTHER TRADES AND EXISTING CONDITIONS AS REQUIRED FOR A COMPLETE AND OPERABLE HVAC SYSTEM. CLEARANCES ABOVE CEILINGS ARE EXTREMELY TIGHT IN CERTAIN AREAS. RELOCATE PIPING, ELECTRIC CONDUIT, STRUCTURAL BRACING, ETC., AS REQUIRED FOR A COMPLETE INSTALLATION OF HVAC WORK. COORDINATE ROUTING OF NEW DUCTWORK ABOVE CEILINGS WITH EXISTING ELECTRIC CABLE TRAY. M.C. TO COORDINATE ALL DUCTWORK ROUTING AND DUCTWORK ELEVATIONS WITH STRUCTURAL STEEL SUPPORTS FOR FOLDING WALLS. REFERENCE STRUCTURAL DRAWINGS FOR SIZE AND LOCATIONS OF STEEL. FIELD VERIFY ALL EXISTING CONDITIONS. 20. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL VAV REHEAT BOXES AND DUCTWORK WITH THE CEILING SYSTEM AND LIGHT FIXTURES. FIELD VERIFY EXISTING CEILING SYSTEMS AND LOCATION OF EXISTING LIGHT FIXTURES. ALLOW REQUIRED CLEARANCES FOR SERVICE TO BOX AND CONTROLS. 21. CONTRACTOR SHALL RELOCATE EXISTING LIGHT FIXTURE AND CEILING GRID SUPPORT HANGERS AS REQUIRED FOR INSTALLATION OF NEW VAV REHEAT BOXES, DUCTWORK AND PIPING. 22. PROVIDE VOLUME DAMPERS IN ALL SUPPLY AIR BRANCH DUCTWORK AS REQUIRED TO BALANCE EACH SYSTEM. ALL VOLUME DAMPERS LOCATED ABOVE DRYWALL CEILINGS SHALL BE CABLE OPERATED WITH REMOTE REGULATOR LIKE YOUNG REGULATOR. FIELD VERIFY EXISTING CEILINGS FOR DRYWALL CEILINGS. COORDINATE LOCATION OF ALL DAMPERS WITH AIR BALANCE CONTRACTOR. IN HARD CEILINGS PROVIDE VOLUME DAMPER BEHIND THE GRILLE, REGISTER, OR DIFFUSER. 23. PROVIDE 45°/90° FITTING WITH VOLUME DAMPER LIKE FLEXMASTER MODEL STO AT ALL SUPPLY AIR AND PRIMARY AIR BRANCH DUCTWORK TAKEOFFS. 24. CONTRACTOR SHALL REVIEW RETURN AIR PATH BACK TO ALL HVAC EQUIPMENT. PROVIDE RETURN AIR OPENINGS AND/OR JUMPER DUCTS IN WALLS ABOVE THE CEILING WHERE REQUIRED. COORDINATE WITH GENERAL TRADES. VELOCITY THRU R.A. OPENINGS SHALL NOT EXCEED 500 FPM. FIELD VERIFY LOCATION OF EXISTING WALLS EXTENDING TO DECK. 25. ALL TRANSFER AIR DUCTS TO BE INTERNALLY INSULATED TO DETER NOISE TRANSFER. SIZE SHOWN ON PLANS INDICATES ACTUAL FREE AREA. 26. ALL NEW PIPING AND DUCTWORK CROSSING THRU EXISTING CORRIDOR AND/OR CLASSROOM WALLS TO DECK; CUT WALLS AS REQUIRED. COORDINATE ALL OPENINGS THROUGH EXISTING WALL CONSTRUCTION WITH GENERAL TRADES. SEAL AROUND DUCTWORK AND PIPING TO HELP REDUCE THE TRANSFER OF NOISE BETWEEN CLASSROOMS. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING OF BID. 27. ROUND DUCT SIZE TO BE THE SAME SIZE AS THE DIFFUSER NECK; UNLESS OTHERWISE NOTED. MAXIMUM LENGTH OF FLEXIBLE DUCTWORK CONNECTED TO A DIFFUSER SHALL BE 5'-0". 28. ALL DUCTWORK CONSTRUCTION SHALL BE FABRICATED SHEET METAL & BUILT IN ACCORDANCE WITH "SMACNA" STANDARDS. 29. ALL SUPPLY, RETURN, RELIEF/EXHAUST, AND OUTDOOR AIR DUCTWORK SHALL BE EXTERNALLY INSULATED. SEE SPECIFICATION FOR ADDITIONAL INSULATION REQUIREMENTS. 30. ALL ROUND DUCT TO BE EXTERNALLY INSULATED UNLESS NOTED OTHERWISE. SIZE SHOWN INDICATES ACTUAL DUCT FREE AREA. SEE SPECIFICATION FOR ADDITIONAL INSULATION REQUIREMENTS. 31. ALL NEW ROOF WORK TO BE IN ACCORDANCE WITH OWNER'S EXISTING ROOF WARRANTY. 32. ALL ROOF PENETRATIONS TO BE SEALED WATER TIGHT. PACK VOID BETWEEN DUCT PENETRATING ROOF AND STRUCTURE WITH FIBERGLASS INSULATION AND CAULK WATER TIGHT. FOR HIGH TEMPERATURE OR GREASE DUCTS UTILIZE MINERAL WOOL. 33. TEMPERATURE CONTROL CONTRACTOR SHALL PROVIDE ALL CONTROL WIRING COMPLETE FOR THIS PROJECT. ALL WIRING (AND INTERLOCK WIRING) TO THERMOSTATS, SPACE SENSORS, HUMIDISTATS, CARBON DIOXIDE MONITORS, ETC. ARE TO BE CONCEALED WITHIN THE WALL. 34. ALL HARD 90° ELBOWS IN SUPPLY DUCTWORK ARE TO HAVE TURNING VANES PER SPECIFICATION AIR DUCT ACCESSORIES. 35. REMOVE ALL WORK MADE OBSOLETE BY NEW CONSTRUCTION. 36. DEMOLITION OF EXISTING MECHANICAL EQUIPMENT TO INCLUDE ASSOCIATED PIPING AND DUCTWORK NECESSARY FOR NEW EQUIPMENT INSTALLATION. 37. ALL EXISTING TO REMAIN AND NEW PVC PLUMBING VENT LINES LOCATED ABOVE CEILING IN RETURN PLENUM ARE TO BE EXTERNALLY WRAPPED WITH FLAME AND SMOKE SPREAD RATED INSULATION MATERIAL AS REQUIRED. 38. REFERENCE SECTION DIVISION 01 "SUMMARY" [MULTIPLE CONTRACT SUMMARY] FOR CONSTRUCTION PHASING. 39. CONTRACTOR SHALL THOROUGHLY EXAMINE THE CONTRACT DOCUMENTS, INCLUDING THE WORK OF OTHER CONTRACTORS PRIOR TO SUBMITTING A BID PROPOSAL. 40. ALL EXHAUST FANS, RELIEF VENTS, FLUES, AND PLUMBING VENTS TO BE INSTALLED A MINIMUM OF 10 FT. FROM OUTDOOR AIR INTAKES. 41. CONTRACTOR SHALL CLEAN ALL OF HIS WORK INSIDE AND OUT. AIR DISTRIBUTION SYSTEMS SHALL HAVE ALL DIRT AND FOREIGN MATERIAL REMOVED FROM INSIDE AND OUTSIDE OF DUCTS, PLENUMS, HOUSINGS, DEVICES, TERMINALS, ETC. AS INSTALLATION PROGRESSES, PROTECT OPEN ENDS OF DUCTWORK AND INLETS AND OUTLETS OF EQUIPMENT AND DEVICES DURING CONSTRUCTION. CLEAN ALL ACCESSIBLE PARTS OF DUCTWORK AND AIR PASSAGES IN EQUIPMENT BEFORE FILTERS ARE INSTALLED OR REPLACED FOR SYSTEM BALANCING. 42. FURNISH AND INSTALL ACCEPTABLE CONCRETE INSERTS, ANCHORS, CLAMPS, BRACKETS, HANGERS, STRUCTURAL MEMBERS (ANGLES, CHANNELS, ETC.) AND FRAMES, ETC., REQUIRED FOR SUPPORTING ALL RESPECTIVE WORK. SUPPORTING DEVICES, ASSEMBLIES AND ATTATCHMENTS SHALL BE DESIGNED AND ARRANGED TO CARRY THE WEIGHT OF THE SUPPORTED ITEMS INCLUDING HANGER AND CONTENTS WITHOUT TRANSMITTING VIBRATION OR NOISE TO THE BUILDING CONSTRUCTION; DESIGNED, APPROPRIATE AND APPROVED FOR THE PURPOSE USED; HAVE A NEAT AND FINISHED APPEARANCE AND COMPLEMENT THE INSTALLATION; HAVE CORROSION PROTECTION SUITABLE FOR THE ATMOSPHERE WHERE INSTALLED; ADEQUATELY AND SAFELY ATTACHED TO THE BUILDING STRUCTURE OR STRUCTURAL MEMBERS. EXPOSED SUPPORTS SHALL BE PAINTED UNLESS OF NON-FERROUS MATERIAL OR PROVIDED WITH PLATED (RUSTPROOF) FINISH. 43. PROVIDE NEC CLEARANCES AND SERVICE CLEARANCES FOR EQUIPMENT. COORDINATE EQUIPMENT SERVICE ACCESS. CLEARANCES INDICATED ARE BASED UPON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL VERIFY PIPING, DUCTWORK, ETC., ROUTING PRIOR TO SUBMITTING A BID PROPOSAL AND INCLUDE ANY SUCH COSTS AS REQUIRED TO INSTALL WORK AS SHOWN AND INTENDED. 44. ELEVATOR EQUIPMENT ROOMS : DO NOT ROUTE ANY SYSTEMS THROUGH ELEVATOR EQUIPMENT ROOMS. FOR SYSTEMS THAT SERVE ELEVATOR EQUIPMENT ROOMS, DO NOT ROUTE OVER ELEVATOR EQUIPMENT OR ELECTRICAL COMPONENTS AND DO NOT HINDER SERVICE ACCESS. 45. TELECOMMUNICATIONS ROOMS (MDF AND IDF) : DO NOT ROUTE ANY SYSTEMS THROUGH TELECOMMUNICATIONS ROOMS. FOR SYSTEMS THAT SERVE T-COMM ROOMS, DO NOT ROUTE OVER EQUIPMENT OR ELECTRICAL COMPONENTS AND DO NOT HINDER SERVICE ACCESS. 46. ELECTRICAL EQUIPMENT ROOMS : DO NOT ROUTE ANY SYSTEMS THROUGH ELECTRIC ROOMS. FOR SYSTEMS THAT SERVE ELECTRIC ROOMS, DO NOT ROUTE OVER EQUIPMENT, PANELS, TRANSFORMERS, VFD’S, OR ELECTRICAL COMPONENTS AND DO NOT HINDER SERVICE ACCESS. 47. EXISTING VALVES MADE INACCESSIBLE BY NEW DUCT AND/OR PIPING SHALL BE RELOCATED AS REQUIRED FOR ACCESS. 48. DURING REMOVAL OF ITEMS, CAUTION SHALL BE USED TO PREVENT DAMAGE TO ANY EQUIPMENT HAVING SALVAGE VALUE. ALL REUSABLE SALVAGED MATERIAL SHALL REMAIN THE PROPERTY OF THE OWNER AND BE RETAINED FOR HIS INSPECTION. ONLY ITEMS SO INSPECTED AND REJECTED BY THE OWNER SHALL BE DISPOSED OF BY THE CONTRACTOR. ALL OTHER ITEMS SHALL BE TURNED OVER AND DEPOSITED AS DIRECTED BY THE OWNER. 49. CONTRACT DOCUMENTS CONSIST OF BOTH PROJECT MANUAL AND DRAWINGS AND BOTH ARE MEANT TO BE COMPLEMENTARY - ANYTHING APPEARING ON EITHER MUST BE EXECUTED THE SAME AS IF SHOWN ON BOTH. 50. VERIFY EXACT SIZE AND LOCATION OF ALL EXISTING PIPING AND DUCTWORK PRIOR TO CONSTRUCTION OR BIDDING. 51. ALL DUCTWORK LOCATED IN ATTIC TO BE EXTERNALLY WRAPPED WITH MINIMUM OF 3" THICK INSULATION. GENERAL NOTES CHILLED WATER RETURN CHILLED WATER SUPPLY CONDENSATE DRAIN CONDENSER WATER RETURN CONDENSER WATER SUPPLY HEAT PUMP RETURN HEAT PUMP SUPPLY HEATING HOT WATER RETURN HEATING HOT WATER SUPPLY HIGH PRESSURE STEAM RETURN HIGH PRESSURE STEAM SUPPLY LOW PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY MEDIUM PRESSURE STEAM RETURN MEDIUM PRESSURE STEAM SUPPLY REFRIGERANT RETURN REFRIGERANT SUPPLY REFRIGERANT SUCTION GAS RETURN STEAM CONDENSATE PUMP DISCHARGE STEAM VENT CHWR CHWS CD CWR CWS HPR HPS HHWR HHWS HPSR HPSS LPSR LPSS MPSR MPSS RR RS RSGR CPD SV PIPING SYSTEMS N 1 2 3 4 5 6 A B C D E 1 2 3 4 5 6 A B C D E Project No. Project Date Produced These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this Project and are not to be used on any other Project or Work without prior written permission from the Architect. KEY PLAN 6/13/2017 9:44:05 AM C:\_RevitLocal\2016-010.GTC_Bldg001_M_2016\2016-010.GTC_Bldg001_M_2016_montesa.rvt 2016-010.GTC 06.12.2017 MECHANICAL SYMBOLS AND ABBREVIATIONS M-001 BAW/ AM Greencastle Community School Corporation Greencastle Transportation Center 2016-010.GTC_Greencastle Community School Corporation_Greencastle Transportation Center_ 800 Tennessee Street Greencastle, IN 46135 M-001_ MECHANICAL SYMBOLS AND ABBREVIATIONS # Revision Date

DUCTWORK Project No.SYMBOLSkeymarkcompany.com/sites/default/files/projects/5.7...HD HORIZ HP HPWR HEAT RECOVERY PUMP HEAT PUMP WATER SUPPLY HEAT PUMP WATER PUMP HOUR HEATING SEASONAL

  • Upload
    voxuyen

  • View
    251

  • Download
    4

Embed Size (px)

Citation preview

Page 1: DUCTWORK Project No.SYMBOLSkeymarkcompany.com/sites/default/files/projects/5.7...HD HORIZ HP HPWR HEAT RECOVERY PUMP HEAT PUMP WATER SUPPLY HEAT PUMP WATER PUMP HOUR HEATING SEASONAL

ABBREVIATIONS

EDR EQUIVALENT DIRECT RADIATION

SA

GALV GALVANIZED

STP

HWCF HEATING HOT WATER CHEMICAL FEED

HHWR

HWP

HEATING HOT WATER RETURN

HEATING HOT WATER PUMP

STS

STRUCT

HPWS

HPWP

HSPF

HRP

HR

HE

HD

HORIZ

HP

HPWR

HEAT RECOVERY PUMP

HEAT PUMP WATER SUPPLY

HEAT PUMP WATER PUMP

HOUR

HEATING SEASONAL PERFORMANCE FACTOR

HEAT PUMP WATER RETURN

HEAT EXCHANGER

HORSEPOWER/HEAT PUMP

HORIZONTAL

HEAD (FT.)

GR

GRV

GS

H

GIV

GC

GPM

GPH

GLYCOL RETURN

GLYCOL SUPPLY

HUMIDITY/HUMIDIFIER

GRAVITY RELIEF VENTILATOR

GENERAL CONTRACTOR

GALLONS PER MINUTE

GALLONS PER HOUR

GRAVITY INTAKE VENTILATOR

STD

ST

SS

SPEC

SRV

SHT

SD

SG

SHR

SECT

SF

SCC

SF

SAT

PTS

F&T FLOAT & THERMOSTATIC STEAM TRAP

FIRE DAMPER

FTR

GAL

GA

FT

FPM

FTG

FINNED TUBE RADIATION

GALLON

GAUGE

FEET PER MINUTE

FOOTING

FOOT/FEET

FLR

FCP

FD

FCU

FLOOR

FLUID COOLER PUMP

FAN COIL UNIT

RV

RS

RP

RPM

RM

RHG

RL

RG

RHC

RH

RAT

RECIR

RES

RF

R

RA

R(#)

ENTERING WATER TEMPERATURE (°F)

EVAPORAT(E), (ING), (ED), (OR)

EXTERNAL STATIC PRESSURE (IN WG)

EX

EXP

F&B

°F

EUH

EVAP

ET

EWT

DEGREES FAHRENHEIT

FACE AND BY-PASS

EXPANSION

EXISTING

EXPANSION TANK

ELECTRIC UNIT HEATER

EMER

ENCL

EOM

ESP

EQUIP

EF

EFF

ELEV

ELEC

EG

EMERGENCY

END OF MAIN DRIP

EQUIPMENT

ENCLOSURE

EXHAUST GRILLE

ELEVATION

ELECTRIC

EFFICIENCY

EXHAUST FAN

PSIG

PT

PRESS

PSI

PREFAB

PPM

PNEU

PER (%)

PHWR

PHWS

PI

PHC

PH

PCHS

PD

PE

PCHR

SUPPLY AIR

STORAGE TANK PUMP

STORAGE TANK SUPPLY

STRUCTURE(E), (AL)

STORAGE TANK

STAINLESS STEEL

STANDARD

SAFETY RELIEF VALVE

SPECIFICATIONS

SHEET

STEAM CONDENSATE COOLER

SUPPLY AIR TEMPERATURE (°F)

SUPPLY DIFFUSER

SENSIBLE HEAT RATIO

SUPPLY GRILLE

SQUARE FOOT

SECTION

SUPPLY FAN

PNEUMATIC TUBE STATION

RELATIVE HUMIDITY

RADIANT PANEL (CEILING-MOUNTED)

REVOLUTIONS PER MINUTE

REFRIGERANT SUCTION

REFRIGERANT VENT

RELATIVE HUMIDITY

REFRIGERANT HOT GAS

REFRIGERANT LIQUID

REHEAT COIL

RETURN GRILLE

ROOM

RECIRCULAT(E), (OR), (ING)

RETURN AIR TEMPERATURE (°F)

RETURN FAN

THERMAL RESISTANCE

REFRIGERANT (NUMBER)

RETURN AIR

POUNDS PER SQUARE INCH

POUNDS PER SQUARE INCH GAUGE

PNEUMATIC TUBE

PRESSURE

PARTS PER MILLION

PREFABRICATED

PNEUMATIC

PANEL CHILLED WATER SUPPLY

PERIMETER HEATING HOT WATER RETURN

PERIMETER HEATING HOT WATER SUPPLY

PRESSURE DROP (IN OR WG AS NOTED)

PANEL CHILLED WATER RETURN

PERCENT

PRESSURE INDICATOR

PREHEAT COIL

PHASE

PNEUMATIC-ELECTRIC

BFW BOILER FEED WATER

MISC

CONV CONVECTOR

ENTERING AIR TEMPERATURE (°F)

CONDENSER WATER CHEMICAL FEED

CLASSROOM UNIT VENTILATOR

EA

EAT

EC

DN

DWG

ELECTRICAL CONTRACTOR

EXHAUST AIR

DRAWING

DOWN

CWP

CWCF

D

DB

CP

CT

CV

CUV

CUH

CONDENSER WATER PUMP

DRAIN BOX

DRAIN

CONTROL VALVE

COOLING TOWER

CABINET UNIT HEATER

CONDENSATE PUMP

P

PBD

OFOI

OFCI

OBD

OA

OAT

NA

NO

NTS

NIC

NC

MV

MTD

CONTRACTOR FURNISHED/OWNER INSTALLED

CHILLED WATER RETURN

CHILLED WATER CHEMICAL FEED

BRITISH THERMAL UNIT PER HOUR

CO

CI

CONN

CHWR

CF

CFM

CFOI

CH

CHCF

CHP

CONNECTION

CAST IRON

CLEANOUT

CHILLED WATER PUMP

CUBIC FEET PER MINUTE

CHILLER

CUBIC FEET

CD

BTUH

CAB

CAV

BHP

BFWP

BOD

BOP

BLDG

CONSTANT AIR VOLUME

CONDENSATE DRAIN

CABINET

BOTTOM OF PIPING

BOTTOM OF DUCT

BRAKE HORSEPOWER

BOILER FEED WATER PUMP

BUILDING

MIN

MECH

MD

MCC

MC

MBH

MAT

LWT

LPS

LFC

LFD

LP

LEC

LD

ACCESS DOOR ("M" DWGS). AREA DRAIN ("P" DWGS)

AIR COOLED CONDENSING UNIT

AMPERE (AMP, AMPS)

BBD

BFC

BDD

AMP

ARCH

AS

AV

APD

APPROX

BOILER BLOW DOWN

BACKDRAFT DAMPER

BELOW FINISHED CEILING

AIR PRESSURE DROP (IN WG)

ARCHITECT (URAL)

APPROXIMAT(E), (LY)

AIR SEPARATOR

AUTOMATIC VENT

ADJ

AFF

AHU

ALTER

AFM

ACCU

ACU

AD

ADA

AAF

ADJUSTABLE

AIR FLOW MONITORING

ABOVE FINISHED FLOOR

AIR HANDLING UNIT

ALTERNATE

AIR CONDITIONING UNIT

AUTOMATIC AIR VENT

AMERICAN DISABILITIES ACT LBS

LAT

LAF

LAD

LAB

KW

KEC

IN

INDIC

INSUL

INT

INCIN

INCL

IB

ID

HHWS

HZ

UV UNIT VENTILATOR

VARIABLE FREQUENCY DRIVE

W/O WITHOUT

MISCELLANEOUS

OWNER FURNISHED/CONTRACTOR INSTALLED

OWNER FURNISHED/OWNER INSTALLED

OUTSIDE AIR TEMPERATURE (°F)

PARALLEL BLADE DAMPER

PUMP

OPPOSED BLADE DAMPER

OUTSIDE AIR

NOT APPLICABLE

NORMALLY CLOSED

NORMALLY OPEN

NOT TO SCALE

NOT IN CONTRACT

MANUAL VENT

MOUNTED

ZN

WTR

WPD

ZONE

WATER PRESSURE DROP

WATER

MIXED AIR TEMPERATURE (°F)

THOUSANDS OF BTU PER HOUR

MOTOR CONTROL CENTER

MOTORIZED DAMPER

MECHANICAL

MINIMUM

MECHANICAL CONTRACTOR

MAXIMUM

LABORATORY FURNISHINGS CONTRACTOR

LOW PRESSURE STEAM

LEAVING WATER TEMPERATURE (°F)

LABORATORY EQUIPMENT CONTRACTOR

LAMINAR FLOW DIFFUSER

LIQUID PETROLEUM

LINEAR DIFFUSER

WG

W/

WATER GAUGE

WITH

VB

VERT

VFD

VIF

VC

VD

VAC

VAR

VAV

VA

VACUUM BREAKER

VOLUME DAMPER

VERIFY IN FIELD

VACUUM CLEANING

VERTICAL

VOLT AMPERE

VARIABLE AIR VOLUME

VACUUM

VARIABLE

TEMPERATURE CONTROL CONTRACTOR

TEMPERATURE DIFFERENCE

TOTAL STATIC PRESSURE (IN WG)

UNLESS NOTED OTHERWISE

HEAT TRANSFER COEFFICIENT

LEAVING AIR TEMPERATURE (°F)

KITCHEN EQUIPMENT CONTRACTOR

LAMINAR AIR FLOW

LAMINAR AIR DIFFUSER

LABORATORY

POUND

KILOWATT

HEATING HOT WATER SUPPLY

INVERTED BUCKET STEAM TRAP

INCH/INCHES

INSULAT(E), (ED), (ION)

INCLUD(E), (ED)

INCINERATOR

INDICATOR

INTERIOR

FREQUENCY (MEGAHERTZ)

INSIDE DIAMETER

UNO

UC

UH

U

TYP.

TSTAT

TSP

UNIT HEATER

UNDER CUT

THERMOSTAT

TYPICAL

TC

TEMP

TONS

TCC

TD

SV

TB

SUCT

TEMPERATURE CONTROL

TONS OF REFRIGERATION

TEMPERATURE

STEAM VENT

TERMINAL BOX

SUCTION

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

COP COEFFICIENT OF PERFORMANCE

CHILLED WATER SUPPLYCHWS

EER ENERGY EFFICIENCY RATIO

SEER SEASONAL ENERGY EFFICIENCY RATIO

HTR HEATER

MAX

STR STORAGE TANK RETURN

VRV VARIABLE REFRIGERANT VOLUME

BRANCH SELECTOR BOXBSB

ABBREVIATIONS

C COMMON

LPC LOW PRESSURE CONDENSATE

MPC MEDIUM PRESSURE CONDENSATE

MPS MEDIUM PRESSURE STEAM

HPS HIGH PRESSURE STEAM

HPC HIGH PRESSURE CONDENSATE

2

M-301

3

M-501

SECTION REFERENCE

DETAIL REFERENCE

PLAN NOTE

DRAWING NOTATIONS

NOTE:ALL SYMBOLS AND ABBREVIATIONSMAY NOT BE USED FOR THIS PROJECT

11 DEMO NEW

NEW TO EXISTING

DEMO TO THIS POINT

EQUIPMENT TAG - (SEE SCHEDULE SHEETS)

DIFFUSER, REGISTER, GRILLE TAG -(SEE SCHEDULE SHEETS)

SD24-12300

XXX-1

CFMMARK

DUCTWORK SYMBOLS

BLADE DAMPER PBD = PARALLEL BLADE DAMPER

DUCT-MOUNTED REHEAT COIL (HYDRONIC)

INTERNALLY INSULATED DUCTWORK

FLEXIBLE CONNECTION

ACCESS DOOR

MOTORIZED CONTROL DAMPER

BDD = BACKDRAFT DAMPER OBD = OPPOSED

FD = FIRE DAMPER FSD = FIRE/SMOKE

MANUAL VOLUME DAMPER

DAMPER SD = SMOKE DAMPER

SHOETAP (OR 45° ENTRY) FITTING

BELLMOUTH FITTING

45° LATERAL FITTING

90° TEE FITTING

SHOETAP WITH SQUARE TO ROUND TRANSITION

DUCT TRANSITION

CONICAL FITTING

AIR FLOW

20° 30°

M

AD

FD

90° ELBOW WITH TURNING VANES

STANDARD RADIUS ELBOW, CENTER RADIUS

INSULATED FLEXIBLE DUCTWORK

OFFSET IN DUCTWORK (R = RISE D = DROP)

RECTANGULAR DUCTWORK

ROUND SPIRAL DUCTWORK

OVAL DUCTWORK

DROP IN DUCTWORK (EXHAUST, RETURN, ETC.)

RISE IN DUCTWORK (EXHAUST, RETURN, ETC.)

RISE IN DUCTWORK (SUPPLY ONLY)

DROP IN DUCTWORK (SUPPLY ONLY)

1-1/2 TIMES WIDTH OF DUCT

12"x8"ϴ

12"Ø

12"x8"

R

COUNTERBALANCED BACKDRAFT DAMPERBDD

AD

MOTORIZED BACKDRAFT DAMPERMBDD

D

DUCTWORK SYSTEMS

EXHAUST AIR

EXHAUST/RELIEF AIR

KITCHEN EXHAUST AIR

OUTSIDE AIR

RELIEF AIR

RETURN AIR

SUPPLY AIR

TRANSFER AIR

EA

EA/RL

KEA

OA

RLA

RA

SA

TA

CO2

EQUIPMENT SYMBOLS

SUPPLY DIFFUSER W/TYPE AND CFM(ONE-WAY SIDE TYPE)

LINEAR DIFFUSER W/TYPE AND CFM(TWO-WAY SIDE TYPE)

SUPPLY DIFFUSER W/TYPE AND CFM(THREE-WAY TYPE)

SIDEWALL GRILLE W/TYPE AND CFM

RETURN GRILLE W/ TYPE AND CFM

SUPPLY DIFFUSER W/TYPE AND CFM(FOUR-WAY TYPE)

SUPPLY DIFFUSER W/TYPE AND CFM(TWO-WAY SIDE TYPE)

ROOF-MOUNTED EXHAUST FAN

CEILING-MOUNTED EXHAUST FAN

CARBON DIOXIDE SENSOR

AT ROOF

AT CEILING

EXHAUST GRILLE W/ TYPE AND CFM

H HUMIDITY SENSOR

T THERMOSTAT

F&T

GENERAL DUTY VALVES & FITTINGS

EXPANSION LOOP (SIZE INDICATEDON DRAWINGS)

CONCENTRIC REDUCER

ECCENTRIC REDUCER

PRESSURE REDUCING VALVE

STEAM TRAP W/DESIGNATION

GAS COCK

PETE'S PLUG

PIPE EXPANSION JOINT

FLEXIBLE PIPING CONNECTOR

Y-STRAINER W/BLOWDOWNVALVE & CAP

PIPE ANCHORS

PIPE GUIDES

THERMOMETER WELL

AUTOMATIC AIR VENT

GAUGE CONNECTION(S) & WELL

THERMOMETER & WELL

MANUAL AIR VENT

AUTOMATIC BALANCING VALVE

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

UNION

MANUAL BALANCING VALVE

VALVE IN RISER

ANGLE VALVE

PLUG VALVE

TRIPLE DUTY VALVE

PRESSURE REGULATING VALVE

BUTTERFLY VALVE

RELIEF VALVE

VALVE - SEE SPECIFICATIONSFOR VALVE TYPE

PIPE CONTINUED ON ANOTHERDRAWING

CHECK VALVE

CAPPED PIPE

RISE IN PIPING

DROP IN PIPING

GATE VALVE

BALL VALVE

1. THESE GENERAL NOTES APPLY TO M-SERIES DRAWINGS. ADDITIONAL GENERAL NOTES SPECIFIC TOA PARTICULAR DRAWING ARE NOTED ON THOSE SHEETS.

2. IT IS THE INTENT OF THESE DOCUMENTS TO PROVIDE MECHANICAL SYSTEMS THAT ARE FULLYFUNCTIONAL. PROVIDE ALL ITEMS SPECIFIED AND REQUIRED FOR COMPLETE OPERATIONAL SYSTEMS.

3. ON MECHANICAL "M" SERIES DRAWINGS, DARK LINE ITEMS INDICATE NEW WORK. LIGHT LINE ITEMS AREITEMS THAT SHALL REMAIN.

4. THESE DRAWINGS INDICATE REQUIRED SIZE AND POINTS OF TERMINATION FOR PIPING, DUCTWORK,CONDUIT, ETC.. THE EQUIPMENT SHOWN ILLUSTRATES SUGGESTED ROUTING, BUT ALL NECESSARYOFFSETS MAY NOT BE SHOWN. DIVISION 23 SHALL INSTALL HIS WORK IN A MANNER THAT WILLCONFORM WITH THE STRUCTURE. DIVISION 23 SHALL AVOID OBSTRUCTIONS, PRESERVE HEADROOMAND MAINTAIN MAXIMUM CLEARANCE WITHOUT FURTHER INSTRUCTION FROM THE ARCHITECT/ENGINEEROR ADDITIONAL COST TO THE OWNER.

5. ALL DUCTWORK, PIPING, AND VALVES SHALL BE CONCEALED ABOVE CEILING AND WITHIN WALLS INFINISHED AREAS UNLESS OTHERWISE INDICATED.

6. ALL VALVES, ETC. SHALL BE INSTALLED ALLOWING EASY ACCESS BETWEEN LIGHT FIXTURES AND NOHIGHER THAN 12" TO 24" ABOVE THE CEILING. PROVIDE FITTINGS IN DUCTWORK AND PIPING ASREQUIRED SO THAT NO PIPING REMAINS TIGHT TO ROOF STRUCTURE. PROVIDE ACCESS PANELS ASREQUIRED. AREA ADJACENT TO THE ACCESS PANELS SHALL BE CLEAR OF ANY OBSTRUCTIONS.PROVIDE EXTENDED VALVE HANDLES FOR INSULATED PIPING.

7. DIVISION 23 SHALL BE GUIDED BY THE ARCHITECT/ENGINEER'S REFLECTED CEILING PLAN FORLOCATION OF DIFFUSERS, REGISTERS, GRILLES SHOWN OR COVERED BY THESE PLANS. RETURNGRILLES SHALL NOT ALIGN WITH SUPPLY AIR THROW.

8. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL GRILLES, REGISTERS AND DIFFUSERS INCEILINGS WITH THE CEILING SYSTEM AND LIGHT FIXTURES. PROVIDE FLEXIBLE DUCT UPSTREAM OFEACH DIFFUSER WHERE SHOWN.

9. ARROWS ON THE HOT WATER COLD WATER MAINS INDICATE THE DIRECTION OF FLOW. PITCHMAINS UPWARD A MINIMUM OF 1" PER 60' IN THE DIRECTION OF FLOW. ARROWS ON STEAM ANDCONDENSATE PIPING AND DRAIN LINE INDICATE THE DOWNWARD PITCH OF THE PIPING.

10. INSTALL AIR VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS OF WATER PIPINGSYSTEMS. DRAINS TO HAVE HOSE END THREADS WITH CLEARANCE TO ATTACH HOSE.

11. PIPING BRANCHES TO EQUIPMENT SHALL HAVE SAME SIZE VALVES AND FITTINGS AS THAT OF THELINE SIZE WITH THE EXCEPTION OF THE TEMPERATURE CONTROL VALVES.

12. PIPE "SWING" CONNECTIONS WITH UNIONS OR FLANGES SHALL BE MADE EXTERNAL TO COILS OR ATUBE BUNDLE TO FACILITATE REMOVAL OF THAT ITEM WITHOUT DISTURBING THE BRANCH VALVESAND/OR PIPING.

13. DUCT AND PIPING PENETRATING FLOOR SLABS AND/OR WALLS SHALL BE SEALED WITH ACOUSTICSEALANT. IF THE FLOOR OR WALL IS FIRE RATED PROVIDE THE FIRE STOPPING OR FIRE DAMPER TOMAINTAIN THE FIRE RATING.

14. ALL RECTANGULAR SHEET METAL DUCT SIZES ARE INSIDE DIMENSIONS. ALL ROUND DUCT SIZESSHOWN ARE INSIDE DIAMETERS. ALLOWANCE FOR ACOUSTICAL LINER WHERE INDICATED ONDRAWINGS MUST BE ADDED TO OBTAIN OUTSIDE SHEET METAL DIMENSION.

15. ALL WALL THERMOSTATS, TEMPERATURE SENSORS, AND/OR HUMIDISTATS SHALL BEAPPROXIMATELY 48" ABOVE FINISHED FLOOR TO CENTER AND LINED UP HORIZONTALLY WITH LIGHTSWITCHES UNLESS OTHERWISE NOTED OR DIRECTED BY THE ARCHITECT/ENGINEER.

16. DIVISION 23 CONTRACTOR SHALL BE RESPONSIBLE FOR HIS RESPECTIVE WORK FOR REPAIRINGAND PATCHING TO MATCH EXISTING SURFACES, SIDEWALKS, STREETS, FLOORS, WALLS, ROOFS,CEILING AND PAVEMENT. CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS FOR CUTTING ANDPATCHING REQUIRED TO INSTALL NEW OR REMOVE EXISTING WORK, EQUIPMENT, OR SYSTEMS.

17. DIVISION 23 CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL OF HIS WORK TO BEINSTALLED WITH ANY AND ALL OTHER CONTRACTORS TO BE AFFECTED BY SUCH WORK, PRIOR TOORDERING ANY OF THE EQUIPMENT. THIS SHALL INCLUDE BUT NOT LIMITED TO ELECTRICALCHARACTERISTICS, CONNECTIONS REQUIRED, PHYSICAL SIZE, COLOR AND FIT. ALSO REFER TOSPECIFICATIONS.

18. ALL EQUIPMENT SHALL BE OF, AND CONSIST OF, AT LEAST MINIMUM SIZES SELECTED, AND SHALLPERFORM TO OR SURPASS THE MINIMUM REQUIREMENTS, SCHEDULES, NOTED AND SPECIFIED.

19. COORDINATE INSTALLATION OF NEW WORK WITH ALL OTHER TRADES AND EXISTING CONDITIONS ASREQUIRED FOR A COMPLETE AND OPERABLE HVAC SYSTEM. CLEARANCES ABOVE CEILINGS AREEXTREMELY TIGHT IN CERTAIN AREAS. RELOCATE PIPING, ELECTRIC CONDUIT, STRUCTURAL BRACING,ETC., AS REQUIRED FOR A COMPLETE INSTALLATION OF HVAC WORK. COORDINATE ROUTING OF NEWDUCTWORK ABOVE CEILINGS WITH EXISTING ELECTRIC CABLE TRAY. M.C. TO COORDINATE ALLDUCTWORK ROUTING AND DUCTWORK ELEVATIONS WITH STRUCTURAL STEEL SUPPORTS FORFOLDING WALLS. REFERENCE STRUCTURAL DRAWINGS FOR SIZE AND LOCATIONS OF STEEL. FIELDVERIFY ALL EXISTING CONDITIONS.

20. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL VAV REHEAT BOXES AND DUCTWORKWITH THE CEILING SYSTEM AND LIGHT FIXTURES. FIELD VERIFY EXISTING CEILING SYSTEMS ANDLOCATION OF EXISTING LIGHT FIXTURES. ALLOW REQUIRED CLEARANCES FOR SERVICE TO BOX ANDCONTROLS.

21. CONTRACTOR SHALL RELOCATE EXISTING LIGHT FIXTURE AND CEILING GRID SUPPORT HANGERS ASREQUIRED FOR INSTALLATION OF NEW VAV REHEAT BOXES, DUCTWORK AND PIPING.

22. PROVIDE VOLUME DAMPERS IN ALL SUPPLY AIR BRANCH DUCTWORK AS REQUIRED TO BALANCEEACH SYSTEM. ALL VOLUME DAMPERS LOCATED ABOVE DRYWALL CEILINGS SHALL BE CABLEOPERATED WITH REMOTE REGULATOR LIKE YOUNG REGULATOR. FIELD VERIFY EXISTING CEILINGS FORDRYWALL CEILINGS. COORDINATE LOCATION OF ALL DAMPERS WITH AIR BALANCE CONTRACTOR. INHARD CEILINGS PROVIDE VOLUME DAMPER BEHIND THE GRILLE, REGISTER, OR DIFFUSER.

23. PROVIDE 45°/90° FITTING WITH VOLUME DAMPER LIKE FLEXMASTER MODEL STO AT ALL SUPPLY AIRAND PRIMARY AIR BRANCH DUCTWORK TAKEOFFS.

24. CONTRACTOR SHALL REVIEW RETURN AIR PATH BACK TO ALL HVAC EQUIPMENT. PROVIDE RETURNAIR OPENINGS AND/OR JUMPER DUCTS IN WALLS ABOVE THE CEILING WHERE REQUIRED. COORDINATEWITH GENERAL TRADES. VELOCITY THRU R.A. OPENINGS SHALL NOT EXCEED 500 FPM. FIELD VERIFYLOCATION OF EXISTING WALLS EXTENDING TO DECK.

25. ALL TRANSFER AIR DUCTS TO BE INTERNALLY INSULATED TO DETER NOISE TRANSFER. SIZE SHOWNON PLANS INDICATES ACTUAL FREE AREA.

26. ALL NEW PIPING AND DUCTWORK CROSSING THRU EXISTING CORRIDOR AND/OR CLASSROOMWALLS TO DECK; CUT WALLS AS REQUIRED. COORDINATE ALL OPENINGS THROUGH EXISTING WALLCONSTRUCTION WITH GENERAL TRADES. SEAL AROUND DUCTWORK AND PIPING TO HELP REDUCE THETRANSFER OF NOISE BETWEEN CLASSROOMS. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TOSUBMITTING OF BID.

27. ROUND DUCT SIZE TO BE THE SAME SIZE AS THE DIFFUSER NECK; UNLESS OTHERWISE NOTED.MAXIMUM LENGTH OF FLEXIBLE DUCTWORK CONNECTED TO A DIFFUSER SHALL BE 5'-0".

28. ALL DUCTWORK CONSTRUCTION SHALL BE FABRICATED SHEET METAL & BUILT IN ACCORDANCEWITH "SMACNA" STANDARDS.

29. ALL SUPPLY, RETURN, RELIEF/EXHAUST, AND OUTDOOR AIR DUCTWORK SHALL BE EXTERNALLYINSULATED. SEE SPECIFICATION FOR ADDITIONAL INSULATION REQUIREMENTS.

30. ALL ROUND DUCT TO BE EXTERNALLY INSULATED UNLESS NOTED OTHERWISE. SIZE SHOWNINDICATES ACTUAL DUCT FREE AREA. SEE SPECIFICATION FOR ADDITIONAL INSULATION REQUIREMENTS.

31. ALL NEW ROOF WORK TO BE IN ACCORDANCE WITH OWNER'S EXISTING ROOF WARRANTY.

32. ALL ROOF PENETRATIONS TO BE SEALED WATER TIGHT. PACK VOID BETWEEN DUCT PENETRATINGROOF AND STRUCTURE WITH FIBERGLASS INSULATION AND CAULK WATER TIGHT. FOR HIGHTEMPERATURE OR GREASE DUCTS UTILIZE MINERAL WOOL.

33. TEMPERATURE CONTROL CONTRACTOR SHALL PROVIDE ALL CONTROL WIRING COMPLETE FORTHIS PROJECT. ALL WIRING (AND INTERLOCK WIRING) TO THERMOSTATS, SPACE SENSORS,HUMIDISTATS, CARBON DIOXIDE MONITORS, ETC. ARE TO BE CONCEALED WITHIN THE WALL.

34. ALL HARD 90° ELBOWS IN SUPPLY DUCTWORK ARE TO HAVE TURNING VANES PER SPECIFICATION AIRDUCT ACCESSORIES.

35. REMOVE ALL WORK MADE OBSOLETE BY NEW CONSTRUCTION.

36. DEMOLITION OF EXISTING MECHANICAL EQUIPMENT TO INCLUDE ASSOCIATED PIPING ANDDUCTWORK NECESSARY FOR NEW EQUIPMENT INSTALLATION.

37. ALL EXISTING TO REMAIN AND NEW PVC PLUMBING VENT LINES LOCATED ABOVE CEILING IN RETURNPLENUM ARE TO BE EXTERNALLY WRAPPED WITH FLAME AND SMOKE SPREAD RATED INSULATIONMATERIAL AS REQUIRED.

38. REFERENCE SECTION DIVISION 01 "SUMMARY" [MULTIPLE CONTRACT SUMMARY] FOR CONSTRUCTIONPHASING.

39. CONTRACTOR SHALL THOROUGHLY EXAMINE THE CONTRACT DOCUMENTS, INCLUDING THE WORKOF OTHER CONTRACTORS PRIOR TO SUBMITTING A BID PROPOSAL.

40. ALL EXHAUST FANS, RELIEF VENTS, FLUES, AND PLUMBING VENTS TO BE INSTALLED A MINIMUM OF 10FT. FROM OUTDOOR AIR INTAKES.

41. CONTRACTOR SHALL CLEAN ALL OF HIS WORK INSIDE AND OUT. AIR DISTRIBUTION SYSTEMS SHALLHAVE ALL DIRT AND FOREIGN MATERIAL REMOVED FROM INSIDE AND OUTSIDE OF DUCTS, PLENUMS,HOUSINGS, DEVICES, TERMINALS, ETC. AS INSTALLATION PROGRESSES, PROTECT OPEN ENDS OFDUCTWORK AND INLETS AND OUTLETS OF EQUIPMENT AND DEVICES DURING CONSTRUCTION. CLEANALL ACCESSIBLE PARTS OF DUCTWORK AND AIR PASSAGES IN EQUIPMENT BEFORE FILTERS AREINSTALLED OR REPLACED FOR SYSTEM BALANCING.

42. FURNISH AND INSTALL ACCEPTABLE CONCRETE INSERTS, ANCHORS, CLAMPS, BRACKETS, HANGERS,STRUCTURAL MEMBERS (ANGLES, CHANNELS, ETC.) AND FRAMES, ETC., REQUIRED FOR SUPPORTINGALL RESPECTIVE WORK. SUPPORTING DEVICES, ASSEMBLIES AND ATTATCHMENTS SHALL BE DESIGNEDAND ARRANGED TO CARRY THE WEIGHT OF THE SUPPORTED ITEMS INCLUDING HANGER AND CONTENTSWITHOUT TRANSMITTING VIBRATION OR NOISE TO THE BUILDING CONSTRUCTION; DESIGNED,APPROPRIATE AND APPROVED FOR THE PURPOSE USED; HAVE A NEAT AND FINISHED APPEARANCEAND COMPLEMENT THE INSTALLATION; HAVE CORROSION PROTECTION SUITABLE FOR THEATMOSPHERE WHERE INSTALLED; ADEQUATELY AND SAFELY ATTACHED TO THE BUILDING STRUCTUREOR STRUCTURAL MEMBERS. EXPOSED SUPPORTS SHALL BE PAINTED UNLESS OF NON-FERROUSMATERIAL OR PROVIDED WITH PLATED (RUSTPROOF) FINISH.

43. PROVIDE NEC CLEARANCES AND SERVICE CLEARANCES FOR EQUIPMENT. COORDINATE EQUIPMENT SERVICE ACCESS. CLEARANCES INDICATED ARE BASED UPON BESTAVAILABLE INFORMATION. CONTRACTOR SHALL VERIFY PIPING, DUCTWORK, ETC., ROUTING PRIOR TOSUBMITTING A BID PROPOSAL AND INCLUDE ANY SUCH COSTS AS REQUIRED TO INSTALL WORK ASSHOWN AND INTENDED.

44. ELEVATOR EQUIPMENT ROOMS:DO NOT ROUTE ANY SYSTEMS THROUGH ELEVATOR EQUIPMENT ROOMS. FOR SYSTEMS THATSERVE ELEVATOR EQUIPMENT ROOMS, DO NOT ROUTE OVER ELEVATOR EQUIPMENT OR ELECTRICALCOMPONENTS AND DO NOT HINDER SERVICE ACCESS.

45. TELECOMMUNICATIONS ROOMS (MDF AND IDF):DO NOT ROUTE ANY SYSTEMS THROUGH TELECOMMUNICATIONS ROOMS. FOR SYSTEMS THATSERVE T-COMM ROOMS, DO NOT ROUTE OVER EQUIPMENT OR ELECTRICAL COMPONENTS AND DO NOTHINDER SERVICE ACCESS.

46. ELECTRICAL EQUIPMENT ROOMS:DO NOT ROUTE ANY SYSTEMS THROUGH ELECTRIC ROOMS. FOR SYSTEMS THAT SERVE ELECTRICROOMS, DO NOT ROUTE OVER EQUIPMENT, PANELS, TRANSFORMERS, VFD’S, OR ELECTRICALCOMPONENTS AND DO NOT HINDER SERVICE ACCESS.

47. EXISTING VALVES MADE INACCESSIBLE BY NEW DUCT AND/OR PIPING SHALL BE RELOCATED ASREQUIRED FOR ACCESS.

48. DURING REMOVAL OF ITEMS, CAUTION SHALL BE USED TO PREVENT DAMAGE TO ANY EQUIPMENTHAVING SALVAGE VALUE. ALL REUSABLE SALVAGED MATERIAL SHALL REMAIN THE PROPERTY OF THEOWNER AND BE RETAINED FOR HIS INSPECTION. ONLY ITEMS SO INSPECTED AND REJECTED BY THEOWNER SHALL BE DISPOSED OF BY THE CONTRACTOR. ALL OTHER ITEMS SHALL BE TURNED OVER ANDDEPOSITED AS DIRECTED BY THE OWNER.

49. CONTRACT DOCUMENTS CONSIST OF BOTH PROJECT MANUAL AND DRAWINGS AND BOTH AREMEANT TO BE COMPLEMENTARY - ANYTHING APPEARING ON EITHER MUST BE EXECUTED THE SAME AS IFSHOWN ON BOTH.

50. VERIFY EXACT SIZE AND LOCATION OF ALL EXISTING PIPING AND DUCTWORK PRIOR TOCONSTRUCTION OR BIDDING.

51. ALL DUCTWORK LOCATED IN ATTIC TO BE EXTERNALLY WRAPPED WITH MINIMUM OF 3" THICKINSULATION.

GENERAL NOTESCHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSATE DRAIN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

HEAT PUMP RETURN

HEAT PUMP SUPPLY

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

HIGH PRESSURE STEAM RETURN

HIGH PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM RETURN

LOW PRESSURE STEAM SUPPLY

MEDIUM PRESSURE STEAM RETURN

MEDIUM PRESSURE STEAM SUPPLY

REFRIGERANT RETURN

REFRIGERANT SUPPLY

REFRIGERANT SUCTION GAS RETURN

STEAM CONDENSATE PUMP DISCHARGE

STEAM VENT

CHWR

CHWS

CD

CWR

CWS

HPR

HPS

HHWR

HHWS

HPSR

HPSS

LPSR

LPSS

MPSR

MPSS

RR

RS

RSGR

CPD

SV

PIPING SYSTEMS

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copiesthereof are and shall remain the property and copyright ofthe Architect. They shall be used only with respect to this

Project and are not to be used on any other Project orWork without prior written permission from the Architect.

KEY PLAN

6/1

3/2

017 9

:44:0

5 A

M

C:\

_R

evitLocal\2016-0

10.G

TC

_B

ldg001_

M_2016\2

016

-010.G

TC

_B

ldg001_M

_2016_

monte

sa.r

vt

2016-010.GTC

06.12.2017

MECHANICAL SYMBOLSAND ABBREVIATIONS

M-001

BAW/ AM

GreencastleCommunity School

Corporation

GreencastleTransportation

Center

2016-0

10.G

TC

_G

reencastle C

om

munity S

chool C

orp

ora

tion_G

reencastle T

ransport

ation C

ente

r_

800 Tennessee StreetGreencastle, IN 46135

M-0

01_ M

EC

HA

NIC

AL S

YM

BO

LS

AN

D A

BB

RE

VIA

TIO

NS

# Revision Date

Page 2: DUCTWORK Project No.SYMBOLSkeymarkcompany.com/sites/default/files/projects/5.7...HD HORIZ HP HPWR HEAT RECOVERY PUMP HEAT PUMP WATER SUPPLY HEAT PUMP WATER PUMP HOUR HEATING SEASONAL

T

T

T

T T

TT

CO

CO

OFFICE/STOR

A102

M

EF-1EF-2

PUH-4PUH-3

PUH-2PUH-1

VF-1

PUH-5

FURN-1

FURN-222"x12" 24"x12"

6"Ø

10"Ø

10"Ø

10"Ø

10"Ø

12"x12" 16"x12"

SD24-10250

SD24-10250

SD24-10250

SD24-10250

SD24-650

SD24-8235

SD24-8235

SD24-8225

SD24-10250

12"x12"18"x12" 10"x10"

6"Ø

6"Ø

SD24-675

SD24-675

SD24-675

SD24-650

SD24-8150 SD24-10

250SD24-10

250SD24-8

175

EC12/12250

EC12/12225

EC12/12470 EC24/12

750

24"x12"

12"x12"

24"x12"

12"x

8"

14"x14"

8"x

8"

ERV-2ERV-1

12"x12"EC12/12

300

10"Ø

10"Ø

12"x8"

10"Ø

8"x6"

8"x6"

8"x

8"

EC8/8100

EC8/8100

EC8/8100

EC8/875

EC12/12150

EC24/10500

EC8/8175

DRIVER'S LOUNGE

A103

OFFICE

A101

LOBBY

A100 OFFICE

A110

STOR

A110A

FLUID STOR

A116

PARTS STOR

A115

HALL

A107DRIVER RR

A106

SERVICE BAY B

A118

SERVICE/WASH BAY D

A120

SERVICE BAY C

A119

SERVICE BAY A

A117

CUST

A111

STAFF RR

A112

ELEC.

A108

MECH

A109

DRIVER RR

A105

HALL

A104

3

1

2

CU-1 CU-2

D

D

10"x

10"

12"x12"

4 56

7

8

9

10

11

12

15

16

19

20

12

10

15

15

9

9

10

10

10

6

9

9 915

16

34

5

66

19

SG8/8

8"x

8"

M

14"x14"12"x12"

18"x10"

SG8/8(2)

9

CU-1 CU-2

FURN-2

FURN-1

PUH-2PUH-1ERV-2ERV-1

EF-2 EF-1

VF-1

PUH-5

OFFICE/STOR

A102

OFFICE

A101

LOBBY

A100

DRIVER'S LOUNGE

A103

HALL

A104

DRIVER RR

A106

DRIVER RR

A105

HALL

A107

CUST

A111

STAFF RR

A112

PARTS STOR

A115 FLUID STOR

A116

STOR

A110A

OFFICE

A110

ELEC.

A108

MECH

A109

SERVICE BAY B

A118

SERVICE/WASH BAY D

A120

SERVICE BAY C

A119

SERVICE BAY A

A117

3C

MH1A1

PUH-3 PUH-4

5

7

8

12

13

14

16

17

18

12

16

5

66

1417

18

13

FURN-1

FURN-2

66

PUH-5

PUH-4

PUH-2

PUH-1

PUH-3

A1

10"Ø

OA

10"Ø RA10"Ø SA

10"Ø

EA

ERV-1 ERV-2

SG8/8

PUH-1 PUH-2

10"Ø

OA

10"Ø

EA

10"Ø SA 10"Ø RA

4"Ø

4"Ø

4"Ø

4"Ø

GOOSENECKSEE DETAIL 3E/M-501

GOOSENECKSEE DETAIL 3E/M-501 GOOSENECK

SEE DETAIL 3E/M-501GOOSENECKSEE DETAIL 3E/M-501

3

1

4

5

6

11

20

11

6

20

34

5

SG8/8

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copiesthereof are and shall remain the property and copyright ofthe Architect. They shall be used only with respect to this

Project and are not to be used on any other Project orWork without prior written permission from the Architect.

KEY PLAN

6/1

3/2

017 9

:44:2

9 A

M

C:\

_R

evitLocal\2016-0

10.G

TC

_B

ldg001_

M_2016\2

016

-010.G

TC

_B

ldg001_M

_2016_

monte

sa.r

vt

2016-010.GTC

06.12.2017

FIRST FLOOR HVAC &PIPING PLAN-

TRANSPORTATION BLDG

MH1A1

BAW/ AM

GreencastleCommunity School

Corporation

GreencastleTransportation

Center

2016-0

10.G

TC

_G

reencastle C

om

munity S

chool C

orp

ora

tion_G

reencastle T

ransport

ation C

ente

r_

800 Tennessee StreetGreencastle, IN 46135

MH

1A

1_ F

IRS

T F

LO

OR

HV

AC

& P

IPIN

G P

LA

N-

TR

AN

SP

OR

TA

TIO

N B

LD

G

1/8" = 1'-0"1A

FIRST FLOOR HVAC PLAN - TRANSPORTATION BUILIDING

1/8" = 1'-0"4A

FIRST FLOOR PIPING PLAN - TRANSPORTATION BUILDING

1/4" = 1'-0"3C

ERV SECTION VIEW

MECHANICAL HVAC PLAN NOTES

1 ROUTE 4” COMBINATION FLUE & COMBUSTION AIR VENT THROUGH ROOF. SEE DETAIL1E/M-501.

2 ROUTE 4” COMBINATION FLUE & COMBUSTION AIR VENT THROUGH EXTERIOR WALL. SEEDETAIL 4E/M-501.

3 10” ROUND OUTSIDE AIR DUCT UP THROUGH ROOF TO GOOSENECK. SEE DETAIL 3E/M-501.

4 10” ROUND EXHAUST AIR DUCT UP THROUGH ROOF TO GOOSENECK. SEE DETAIL3E/M-501.

5 ENERGY RECOVERY VENTILATOR MOUNTED ON WALL +/- 13’-0” ABOVE FINISH FLOOR. SEESECTION ON THIS SHEET. INSTALL PER MANUFACTURES RECOMMENDATIONS. SEESCHEDULE ON SHEET M-601

6 GAS FIRED PROP UNIT HEATER MOUNTED +/- 17’-0” ABOVE FINISH FLOOR. SEE SCHEDULEON SHEET M-601 & DETAIL 3B/M-501

7 EXPLOSION PROOF ELECTRIC PROP UNIT HEATER MOUNTED TIGHT TO BOTTOM OFCEILING. SEE SCHEDULE ON SHEET M-601 & DETAIL 6D/M-501

8 VENTILATION FAN MOUNTED IN CEILING OF PARTS STORAGE. SEE SCHEDULE ON SHEETM-601 & DETAIL 3D/M-501

9 TYPICAL 24/24 SUPPLY AIR DIFFUSER. SEE SCHEDULE ON SHEET M-601 & DETAIL 1A/M-501.PROVIDE DUCT MOUNTED VOLUME DAMPER.

10 TYPICAL EGGCRATE GRILLE. SEE SCHEDULE ON SHEET M-601. PROVIDE DUCT MOUNTEDVOLUME DAMPER.

11 TYPICAL SIDEWALL GRILLE. SEE SCHEDULE ON SHEET M-601.

12 AIR COOLED CONDESNSING UNIT LOCATED ON CONCRETE PAD. MOUNT AIR COOLEDCONDENSING UNIT ON STAND +/- 8” ABOVE CONCRETE PAD. SEE SCHEDULE ON SHEETM-601

13 REFRIGERANT PIPING FROM AIR COOLED CONDENSING UNIT TO FURNACE TO BE SIZEDPER MANUFACTURES RECOMMENDATIONS. ROUTE REFRIGERANT PIPING LOCATEDOUTSIDE ON SUPPORTS AS REQUIRED TO PREVENT SAGGING OF REFRIGERANT PIPING. 1"CLOSED CELL INSULATED WITH ALUMINUM JACKET.

14 GAS FIRED FURNACE LOCATED IN MECHANICAL ROOM A109. SEE SCHEDULE ON SHEETM-601 & DETAIL 3A/M-501. PROVIDE COMBINATION FLUE & COMBUSTION AIRVENTTHROUGH ROOF. SEE DETAIL 2E/M501.

15 TYPICAL VOLUME DAMPER. SEE DETAIL 5A/M-501.

16 ROOF MOUNTED EXHAUST FAN MOUNTED ON 12” ROOF CURB. COORDINATEINSTALLATION WITH STRUCTURAL. INSTALL PER MANUFACTURE RECOMMENDATION. SEESCHEDULE ON SHEET M-601.

17 TYPICAL WALL MOUNTED THERMOSTAT. SEE 700 SERIES DRAWINGS.

18 ROUTE 1” CONDENSATE DRAIN FROM FURNACE TO NEAREST FLOOR DRAIN. SEEPLUMBING PLANS & DETAIL 1C/501

19 CONCENTRIC HORIZONTAL VENT/COMBUSTION AIR SYSTEM. LIKE REZNOR OPTION CC9.SEE DETAIL 4E/M-501

20 CONCENTRIC VERTICAL VENT/COMBUSTION AIR SYSTEM. LIKE REZNOR OPTION CC2. SEEDETAIL 1E/M501.

# Revision Date

A1 Addendum 1 1/9/17

Page 3: DUCTWORK Project No.SYMBOLSkeymarkcompany.com/sites/default/files/projects/5.7...HD HORIZ HP HPWR HEAT RECOVERY PUMP HEAT PUMP WATER SUPPLY HEAT PUMP WATER PUMP HOUR HEATING SEASONAL

NEW ADDITION MEZZANINEEXTERIOR WALL.

REFRIGERANT PIPING.

SEAL PIPE PENETRATIONINSIDE AND OUT.

FINISHED FLOOROF MECH. ROOM

NEW ROOF

PROVIDE WEATHERPROOF BOX WITH WALL

SLEEVE AT WALLPENETRATION TO ROUTEREFRIGERANT PIPE THRU

TO MECHANICAL ROOM.

EXTERIOR WALLSURFACE

WALL STUD AND/OR PLYWOOD

STAINLESS STEELADJUSTABLE CLAMP

FLEXIBLE INLETSLEEVE

ANTI-CORROSION,LUBRICATED, ALL-MATERIAL TAPSCREWS

NEOPRENEWASHERS(PRE-MOUNTED)

WALL- MOUNTEDOUTLET ALL-SURFACE LIGHT-DENSITY

WALL GASKET (PRE-LOADED)

SEE DETAIL 3A/M-501

DISCONNECT SWITCH

SHIELDED PIGTAIL CORD

EXTERNAL ALUMINUM WIREPOST BY FAN MANUFACTURER

SECURE FAN TO ROOF CURB AS REQUIRED WITHA MINIMUM OF TWO (2) FASTENERS PER SIDE

INSULATION

ROOF CONSTRUCTION, REFER TOARCHITECTURAL DRAWINGS FOR TYPE

CHANNEL FILLERS IF APPLICABLE (TYP.)

MOTORIZED BACKDRAFT DAMPER.SEE DRAWINGS FOR SIZE.

EXHAUST DUCTWORK. PROVIDE EXPANDED METALGRILLE OVER OPENING OF DUCTWORK. SEE HVACFLOOR PLANS FOR SIZE.

MOTORALUMINUM HOUSING

FAN

DUCT

1/2" THICKFOAMEDNEOPRENE SEAL

BIRDSCREEN

COUNTERFLASHING

PREFABRICATED ROOF CURB

ROOF STRUCTURE. SEESTRUCTURAL DRAWINGS

NOTES:1. ALL POWER ROOF VENTILATORS SHALL BE MOUNTED LEVEL. 12"

TALL PROVIDE SLOPED CURBS AND SHIMS AS REQUIRED FORSLOPED ROOFS. REFER TO ARCHITECTURAL DRAWINGS FOR PITCHOF ROOF.

12"

MIN

M

SHORT (1') PIECE OF FLEXIBLE DUCT WILLABSORB VIBRATION & NOISE.

SEALAROUND THE

UNIT WITHCAULK.

POWERCORD

JOISTS

1" INSULATED DUCT WILLHELP ABSORB VIBRATION. USE THESHORTEST RUNS POSSIBLE & LONGRADIUS ELBOWS.

ROOF

INTERIOR SHOP WALL

USE FOIL TAPE ON THEJOINTS TO ENSURE AGOOD SEAL.

SEE FLOOR PLANFOR GRILLE SIZE

SEE SCHEDULE ON SHEET M-601

LOW PRESSURESUPPLYBRANCH DUCT

45°/90° ENTRY FITTING WITH MANUALVOLUME DAMPER LIKE FLEXMASTER

MODEL STO AT ALL SUPPLY AIRBRANCH DUCTWORK TAKE-OFFS,

AND/OR RECTUANGULAR TO ROUNDWHERE REQUIRED.

SUPPLY DIFFUSER

CEILING

SQUARE-TO-ROUNDFITTING FOR SQUARE

NECK SUPPLYDIFFUSERS

INSULATED FLEXIBLEDUCTWORK, MAXIMUM 5'-0"

IN LENGTH AND NO MORETHAN ONE (1) 90° TURN

FLEX BOOT LIKE MODEL"FLEXRIGHT" BYBUILDRIGHT PRODUCTS

PROVIDE MANUFACTURER'SINSULATED BACK PAN ON

DIFFUSER, AND FOIL TAPEEDGES.

SECURE FLEXIBLE DUCT TOSUPPLY DIFFUSER NECK WITHSTAINLESS STEEL DRAWBANDTO INNER PART OF FLEX DUCT.PROVIDE FOIL TAPE TOSECURE INSULATION OVERDRAW BAND.

NOTE:SEE DETAIL 1A/M-501

1" BAND CLAMP WITHWIRE (OPTIONAL)

MINIMUM 1" WIDE CLAMP

WIRE SUPPORT

STRAP BRACING SHALL BEPROVIDED AT A MAXIMUMOF 3'-0" ON CENTERS

MAXIMUM SAG SHALL BE 1/2"PER FOOT OF SUPPORT SPACING

DETAIL 1

DETAIL 2

DETAIL 3

NOTES:

1. METALLIC FLEXIBLE DUCTWORK SHALL BE ATTACHED USING A MINIMUM OF THREE(3) #8 SHEET METAL SCREWS EQUALLY SPACED AROUND THE DUCTWORKCIRCUMFERENCE. DUCTWORK LARGER THAN 12" SHALL HAVE A MINIMUM OF FIVE(5) #8 SHEET METAL SCREWS. SCREWS SHALL BE LOCATED AT LEAST 1/2" FROMTHE DUCTWORK END.

2. NON-METALLIC FLEXIBLE DUCTWORK SHALL BE SECURED TO THE SLEEVE ORCOLLAR USING A DRAW BAND. IF THE DUCTWORK COLLAR EXCEEDS 12" THEDRAW BAND MUST BE POSITIONED BEHIND A BEAD ON THE METAL COLLAR.

3. INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY-FABRICATEDDUCTWORK SHALL BE FITTED OVER THE CORE CONNECTION AND SHALL BESUPPLEMENTALLY SECURED WITH A DRAW BAND.

4. FLEXIBLE DUCTWORK SEALING SHALL BE A CLASS "B" SEAL FOR LOW PRESSUREDUCTWORK.

5. SUPPORT SYSTEM SHALL NOT DAMAGE OR CAUSE OUT-OF-ROUND SHAPE.

NOTE:DEE DETAIL 6A/M-501

2"

6"

6"

MASONRYPARTITIONCONSTRUCTION

INSULATED PIPEOR DUCTWORK

DRYWALL PARTITIONCONSTRUCTION

PARTITION SUPPORT

3/4" APPROVEDFIRESTOP INSULATIONWITH VAPOR BARRIER

FIRESTOP MATERIAL

WALL PENETRATION

INSULATED PIPEOR DUCTWORK.

PIPE SLEEVE

1/4" DIAMETERANCHOR ROD FORNEW CONSTRUCTION

FIRESTOP MATERIAL

FLOOR

FLOOR PENETRATION

NOTE: APPLICABLE TO PENETRATIONS OF ALL FIRERATED MEMBRANES. REFER TO SPECIFICATIONS FORFIRE STOP MATERIAL AND REQUIREMENTS.

3/4" APPROVEDFIRESTOP INSULATIONWITH VAPOR BARRIER.

3'-0"

MIN

.

DUCT WATER PROOF SEAMSAND JOINTS

STORM COLLAR

TALL CONE SHEET METALFLASHING W/FLANGE

ROOF CONSTRUCTION, REFERTO ARCHITECTURAL DRAWINGSFOR TYPE

ROOF STRUCTURE, REFER TOSTRUCTURAL DRAWINGS FORTYPE

REFER TO HVAC DRAWINGSFOR EXHAUST INTAKE DUCT SIZE

TREATED 2X4 BLOCKING

SUPPORT PLATE

125% DUCT SIZE WITH 1/2" X 1/2"ALUMINUM SCREEN

CONCENTRIC ROOF TERMINATION(FURNISHED BY FURNACE MFGR.)

EXHAUST AIR

INTAKE AIR

PVC FLUEPIPE

EPDM BOOT WITH STAINLESSSTEEL ADJUSTABLE CLAMPS

FLASHING BY ROOFINGCONTRACTOR

ROOF SHINGLES

PROVIDE ROOF OPENINGAS REQUIRED

INTAKE AIR

EXHAUST AIR

ROOF DECK

SEE DETAIL 3A/M-501 FORCONTINUATION

STORM COLLAR

FLASHING

COMBUSTION AIR INLET

EXHAUSTTERMINAL

FLUE EXHAUSTPIPE

SEAL WITH HIGHTEMPERATURE SILICONERUBBER SEALANT

COMBUSTIONAIR PIPE

FLUE VENT PIPE CONCENTRICADAPTER

COMBUSTIONAIR PIPE

GAS-FIRED PROPUNIT HEATER SEE DETAIL3B/M-501.

VERIFY ACTUALROOF CONSTRUCTION

NOTE:INSTALLATION SHALLBE PER UNIT MFGR'SINSTRUCTIONS. FLUEAND COMBUSTION AIRPIPES SHALL BE SINGLEWALL PIPE (SEAL ASRECOMMENDED BY MFGR.)

12"

1' - 6" MIN.

5' - 0" MAX.

DRAW THROUGH COIL

BLOW THROUGH COIL

UNIT MANUFACTURERS THREADEDDRAIN PIPE CONNECTION (TYP.)

SEE DRAWINGS FOR SIZE (1" MIN.)

CLEANOUT PLUG

COOLING COILDRAIN PAN

DRAIN LINE. (BOTTOMCONNECTION ONLY)

CLEANOUT PLUG

FLOOR DRAIN(SEE PLUMBING)

PITCH CONDENSATEPIPE TO NEAREST FLOORDRAIN (1/4" PER FOOT)

VENT TO ATMOSPHERE

ST

AT

IC P

RE

SS

UR

E

FA

N T

OT

AL

ST

AT

IC P

RE

SS

UR

E

FA

N T

OT

AL

PITCH CONDENSATE PIPETO NEAREST FLOOR DRAIN(1/4" PER FOOT)

VENT TO ATMOSPHERE

FLOOR DRAIN(SEE PLUMBING)

CLEANOUT PLUGDRAIN LINE (BOTTOMCONNECTION ONLY)

COOLING COILDRAIN PAN

UNIT MANUFACTURERS THREADEDDRAIN PIPE CONNECTION (TYP.)

SEE DRAWINGS FOR SIZE(1" MIN.)

CLEANOUT PLUG

ST

AT

IC P

RE

SS

UR

E

FA

N T

OT

AL

ST

AT

IC P

RE

SS

UR

E

1/2

FA

N T

OT

AL

NOTE:SEE DETAIL 3A/M-501

SUPPLY DUCT

INTERNALLY LINEDRETURN DUCT

FLUE VENT

COMBUSTION AIR

FLEXIBLECONNECTION

CASED COOLING COIL

TRAP FULL SIZECONDENSATE DRAINAND ROUTE TO DRAIN

FURNACE CONDENSATE

FURNACE

(FOR 5 TON UNITS ONLY)PROVIDE ADDITIONAL RETURN AIRPLENUM CONNECTED TO BOTTOM OFUNIT TO UTILIZE BOTH BOTTOM ANDSIDE RETURN CONNECTION. REFERANCEMANUFACTURERS RECOMMENDATION.FURNACE TO BE SUPPORTED ON METALANGLE IRON STAND; NOT SUPPORTED BYDUCTWORK.

2" PLEATED FILTER WITHAIRTIGHT ACCESS DOOR

AIR FLOW

DUCT SIZE SHOWN ONCONTRACT DOCUMENTS IS FREEAREA. TYPICAL OF SUPPLY & RETURN.

SEE DETAIL 2E/M-501

NOTE:REFRIGERANT PIPINGTO CONDENSING UNIT &CASED COOLING COIL TO BESIZED BY UNIT MANUFACTURER.

SEE DETAIL1C/M-501

LOUVER FINDIFFUSER

UNION (TYP.)

FULL LINE SIZEGAS VALVE

FAN MOTOR

FLUE VENT UP THRUROOF. REFER TO VENTDETAIL. 1E/M-501

GAS-FIRED UNIT HEATER

REDUCE TO MATCH GASVALVE CONNECTION SIZE

4" LONG DIRT LEG

G

ALL THREAD RODHANGERS. FOUR POINTSUSPENSION (MIN.) ORPROVIDE ANGLE IRONBRACES TO ADJACENTWALLS OR STRUCTURETO PREVENT HEATERFROM SWAYING

COMBUSTION AIRVENT.

SEE DETAIL 1E/M-501 &6E/M-501 FOR CONTINUATION.

FLUE VENT PIPE

COMBUSTION AIR PIPIE

CONCENTRIC ADAPTER LIKEREZNOR OPTION CC9

EXTERIOR WALL. REFERENCE ARCHITECTURALPLANS FOR WALL CONSTRUCTION

NOTE: INSTALLATION SHALL BE PER UNIT& MFGR'S INSTUCTIONS. FLUE & COMBUSTIONAIR PIPES SHALL BE SINGLE WALL PIPIE(SEAL AS RECOMMENDED BY MFGR.)

GAS FIRED PROP UNITHEATER SEE DETAIL 3B/M-501

FLUE EXHAUST PIPE

EXHAUST TERMINAL

COMBUSTION AIR INLET

LOUVER FINDIFFUSER

FAN MOTOR

EXPLOSION PROOF HEATER

ALL THREAD RODHANGERS. FOUR POINTSUSPENSION (MIN.) ORPROVIDE ANGLE IRONBRACES TO ADJACENTWALLS OR STRUCTURETO PREVENT HEATERFROM SWAYING

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copiesthereof are and shall remain the property and copyright ofthe Architect. They shall be used only with respect to this

Project and are not to be used on any other Project orWork without prior written permission from the Architect.

KEY PLAN

6/1

3/2

017 9

:44:1

6 A

M

C:\

_R

evitLocal\2016-0

10.G

TC

_B

ldg001_

M_2016\2

016

-010.G

TC

_B

ldg001_M

_2016_

monte

sa.r

vt

2016-010.GTC

06.12.2017

MECHANICAL DETAILS

M-501

BAW/ AM

GreencastleCommunity School

Corporation

GreencastleTransportation

Center

2016-0

10.G

TC

_G

reencastle C

om

munity S

chool C

orp

ora

tion_G

reencastle T

ransport

ation C

ente

r_

800 Tennessee StreetGreencastle, IN 46135

M-5

01_ M

EC

HA

NIC

AL D

ET

AIL

S

NOT TO SCALE4D

EXTERIOR REFRIGERANT PIPING DETAIL

NOT TO SCALE4B

POWER ROOF VENTILATOR INSTALLATION

DETAIL

NOT TO SCALE3D

CEILING MOUNTED VENTILATION FAN

DETAIL - WALL TERMINATION

NOT TO SCALE5A

SUPPLY DIFFUSER FLEXIBLE DUCT

CONNECTION DETAIL

NOT TO SCALE1A

INSULATED FLEXIBLE DUCTWORK DETAIL

NOT TO SCALE2A

FIRE BARRIER PIPE/DUCTWORK

PENETRATION DETAIL

NOT TO SCALE3E

ROUND GOOSENECK DETAIL

NOT TO SCALE2E

FURNACE INTAKE AND EXHAUST AIR

VENTING

NOT TO SCALE1E

GAS-FIRED UNIT HEATER VERTICAL VENT

INSTALLATION

NOT TO SCALE1C

CONDENSATE DRAIN PIPING DETAIL

NOT TO SCALE3A

UP FLOW FURNACE DETAIL

NOT TO SCALE3B

GAS FIRED PROPELLER UNIT HEATER PIPING

DETAIL

NOT TO SCALE4E

GAS FIRED PROPELLER UNIT HEATER PIPING

DETAIL

NOT TO SCALE6D

GAS FIRED PROPELLER UNIT HEATER PIPING

DETAIL

# Revision Date

Page 4: DUCTWORK Project No.SYMBOLSkeymarkcompany.com/sites/default/files/projects/5.7...HD HORIZ HP HPWR HEAT RECOVERY PUMP HEAT PUMP WATER SUPPLY HEAT PUMP WATER PUMP HOUR HEATING SEASONAL

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copiesthereof are and shall remain the property and copyright ofthe Architect. They shall be used only with respect to this

Project and are not to be used on any other Project orWork without prior written permission from the Architect.

KEY PLAN

3/8

/2017 1

1:0

8:4

1 A

M

C:\

_R

evitLocal\2016-0

10.G

TC

_B

ldg001_

M_2016\2

016

-010.G

TC

_B

ldg001_M

_2016_

monte

sa.r

vt

2016-010.GTC

12.12.2016

MECHANICAL SCHEDULES

M-601

BAW/ AM

GreencastleCommunity School

Corporation

GreencastleTransportation

Center

2016-0

10.G

TC

_G

reencastle C

om

munity S

chool C

orp

ora

tion_G

reencastle T

ransport

ation C

ente

r_

800 Tennessee StreetGreencastle, IN 46135

M-6

01_ M

EC

HA

NIC

AL S

CH

ED

ULE

S

EXHAUST FAN SCHEDULE

IDENTITY DATA

FAN TYPE

FAN DATA NOISE CRITERIA ELECTRICAL DATA

UNIT CONTROL NOTESMARK MANUFACTURER MODEL SERVESWEIGHT

(LBS) LOCATION

EXHAUSTAIRFLOW

(CFM)ESP

(IN-WG) RPM SONES DBA HP BHPVOLTS

(V) PHASEFREQ(HZ)

DISCONNECTPROVIDER

EF-1 Loren Cook Company ACEB 270 TRANSPORTATION BUILDING 287 SERVICE BAY BELT DRIVE 4,500 0.3 472 6.5 53 0.5 0.465 120 1 60 MFGR LOCAL SWITCH/CO2 1-2

EF-2 Loren Cook Company ACEB 270 TRANSPORTATION BUILDING 287 SERVICE BAY BELT DRIVE 4,500 0.3 472 6.5 53 0.5 0.465 120 1 60 MFGR LOCAL SWITCH/CO2 1-2

ENERGY RECOVERY VENTILATOR SCHEDULE

IDENTITY DATA

AIRFLOW(CFM)

ELECTRICAL DATA

NOTESMARK MANUFACTURER MODELWEIGHT

(LBS) FLA MCA MOCP HPVOLTS

(V)PHAS

EFREQ(HZ)

ERV-1 RENEW AIRE EV450IN 200 300 3.9 4.90 15 120 1 60

ERV-2 RENEW AIRE EV450IN 200 300 3.9 4.90 15 120 1 60

DIFFUSERS, REGISTERS, AND GRILLES

IDENTITY DATANECK SIZE

(IN) MODULE SIZE

MATERIAL NOTESMARK DESCRIPTION MANUFACTURER MODEL Ø W LEC8/8 EGG CRATE FACE RETURN PRICE 80 8" 8" ALUMINUM

EC12/12 EGG CRATE FACE RETURN PRICE 80 12" 12" ALUMINUM

EC24/10 EGG CRATE FACE RETURN PRICE 80 24" 10" ALUMINUM

EC24/12 EGG CRATE FACE RETURN PRICE 80 24" 12" ALUMINUM

SD24-6 SQUARE CONE DIFFUSER PRICE ASCDA 6" 24" 24" STEEL

SD24-8 SQUARE CONE DIFFUSER PRICE ASCDA 8" 24" 24" STEEL

SD24-10 SQUARE CONE DIFFUSER PRICE ASCDA 10" 24" 24" STEEL

SG8/8 LOUVER FACE GRILLE SUPPLY PRICE 520 8" 8" STEEL

FURNACE SCHEDULE

IDENTITY DATA LOCATION COOLING / HEATING DATA DIMENSIONS ELECTRICAL DATA

NOTESMARK MANUFACTURER MODELWEIGHT

(LBS) NAME

NOMINALCOOLING

(TONS)

COOLINGCAPACITY

(BTU/h)

HEATINGCAPACITY

(BTU/h)AIRFLOW

(CFM)REFRIG

TYPE H W LVOLTS

(V) PHASEFREQ(HZ)

MCA(A)

MFA(A)

FURN-1 DAIKIN DM96VC1005 120 lb 5 60,000 100,000 1,995 R410A 2'-11" 2'-3" 2'-5" 115 1 60 14.4 20 1-6

FURN-2 DAIKIN DM96VC0603 125 lb 3 36,000 60,000 1,200 R410A 2'-11" 1'-11" 2'-5" 115 1 60 7.8 15 1-6

VENTILATION FAN SCHEDULE

IDENTITY DATA

FAN TYPE

FAN DATA NOISE CRITERIA ELECTRICAL DATA

UNIT CONTROL NOTESMARK MANUFACTURER MODEL SERVESWEIGHT

(LBS)AIRFLOW

(CFM)ESP

(IN-WG) SONES DBAHP(W)

VOLTS(V) PHASE

FREQ(HZ)

DISCONNECTPROVIDER

VF-1 Loren Cook Company GN-186 PARTS STORAGE A115 25 FC 200 0.25 5.5 51 89 115 1 60 MFGR LOCAL SWITCH

SERVICE BAY A

FLUID STOR A116

MECH

MECH A109

A109

GAS FIRED PROP UNIT HEATER SCHEDULE

IDENTITY DATA ROOM HEATING DATA FAN DATA ELECTRICAL DATA

NOTESMARK MANUFACTURER MODEL NAMEINPUT(BTUH)

OUTPUT(BTUH)

EAT(°F)

LAT(°F)

AIRFLOW(CFM)

ESP(IN-WG) FAN TYPE DRIVE RPM HP SPEEDS

VOLTS(V) PHASE FLA (A)

MOCP(A)

PUH-1 REZNOR UDAS125 60 120 1,537 0 PROP DIRECT 1050 0 120 1 5.1 15 1-8

PUH-2 REZNOR UDAS125 60 120 1,537 0 PROP DIRECT 1050 0 120 1 5.1 15 1-8

PUH-3 REZNOR UDAS125 60 120 1,537 0 PROP DIRECT 1050 0 120 1 5.1 15 1-8

PUH-4 REZNOR UDAS125 60 120 1,537 0 PROP DIRECT 1050 0 120 1 5.1 15 1-8

AIR COOLED CONDENSING UNIT SCHEDULE

IDENTITY DATA

REFG. TYPE

COOLING DATA ENERGY DATA ELECTRICAL DATA

NOTESMARK MANUFACTURER MODELWEIGHT

(LBS) LOCATION SYSTEM SERVED

NOMINALCOOLING

(TONS)TOTAL COOLING

(BTUH)AMBIENT

DRY BULB SEERVOLTS

(V)FREQ.(HZ) PHASE

MCA(A)

MOCP(A) DISCONNECT PROVIDER

CU-1 DAIKIN DX18TC060 275 ON GRADE FURN-1 R410A 5 57,000 208 60 1 36.7 60 1-7

CU-2 DAIKIN DX18TC036 210 ON GRADE FURN-2 R410A 3 35,000 208 60 1 21.9 35 1-7

ELECTRIC PROP UNIT HEATER SCHEDULE

IDENTITY DATA ROOM HEATING DATA FAN DATAELECTRICAL

DATA

CONTROL NOTESMARK MANUFACTURER MODELWEIGHT

(LBS) NAMECAPACITY

(KW) STEPSEAT(°F)

LAT(°F)

AIRFLOW(CFM)

FANTYPE DRIVE

VOLTS(V) PHASE

PUH-5 QMARK GUX300812 135 3 1 60 73 700 PROP DIRECT 208 1 T-STAT 1

SERVICE BAY B

MECHANICAL SPECIFICATIONS1. ALL WORK SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE LATEST EDITIONS OF THE INDIANA MECHANICAL CODE, INDIANA

ELECTRICAL CODE AND THE INDIANA PLUMBING CODE, AND ALL OTHER APPLICABLE LOCAL CODES AND/OR ORDINANCES.2. EQUIPMENT SHALL BE INSTALLED AND ADJUSTED AS REQUIRED TO PROVIDE SAFE AND SATISFACTORY OPERATING CONDITIONS. ALL

MISCELLANEOUS AUXILIARY EQUIPMENT NECESSARY TO THE OPERATION OF THE FINISHED SYSTEM SHALL BE PROVIDED, EVEN THOUGHNOT SHOWN.

3. CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS FOR CUTTING AND PATCHING REQUIRED TO INSTALL NEW WORK, EQUIPMENTOR SYSTEMS.

4. CONTRACTOR SHALL THOROUGHLY EXAMINE THE WORK OF OTHER CONTRACTORS AND VERIFY ALL CONDITIONS PRIOR TO SUBMITTING ABID PROPOSAL.

5. DEFINITIONS: THE GENERAL, HEATING, PLUMBING AND ELECTRICAL TRADES ARE REFERRED TO HEREIN AND ON DRAWINGS AS G.C., M.C.,P.C., AND E.C. RESPECTIVELY.

6. EQUIPMENT: BASIS OF DESIGN IS AS FOLLOWS;a. LOREN COOK: EXHAUST & VENTILATION FANS.b. QMARK: EXPLOSION PROOF ELECTRIC WALL HEATERS.c. REZNOR: GAS FIRED PROP UNIT HEATERS.d. RENEWAIRE: ENERGY RECOVERY UNITS.e. DAIKIN: HEATING AND COOLING AC SYSTEMS.WHERE A CONTRACTOR PROPOSES TO USE ANOTHER MANUFACTURE OTHER THAN THAT DETAILED OR SCHEDULED ON THE DRAWINGS, ITIS THE CONTRACTORS RESPONSIBILITY TO MAKE SURE THAT THE ALTERNATE MANUFACTURE CAN MEET OR EXCEED THE CAPACITIES ANDREQUIREMENTS THAT ARE SHOWN ON THE CONTRACT DOCUMENT SCHEDULES. CONTRACTOR TO COORDINATE ALL ELECTRICALREQUIREMENTS WITH THE ELECTRICAL CONTRACTOR PRIOR TO ORDERING AND INSTALLATION OF EQUIPMENT.7. TEMPERATURE CONTROL SYSTEM TO BE LOCATED AS SHOWN ON CONTRACT DOCUMENTS. CONTROL SYSTEM TO OPERATE EXHAUSTFAN’S, ASSOCIATED MOTORIZED DAMPERS, FURNACE AC SYSTEMS, GAS FIRED PROP HEATERS, AND ELECTRIC WALL HEATERS ASREQUIRED.8. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, TAXES, FEES AND OTHER COSTS IN CONNECTION WITH THE WORK THEYPERFORM.9. THE LOCATIONS OF EQUIPMENT SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC ONLY. EXACT LOCATIONS SHALL BE DETERMINED ONTHE JOB GOVERNED BY THE WORK OF OTHER CONTRACTORS. THIS CONTRACTOR SHALL COORPORATE IN THE LOCATION OF ALL WORK TOPROVIDE A FINISHED WORKMANLIKE JOB. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIAL, EQUIPMENT AND LABOR PROVIDED BY HIMTO BE FREE OF DEFECTS AND SHALL AGREE TO REPLACE AND/OR REPAIR, WITHOUT COST TO THE OWNER, ANY SUCH DEFECTS AT ANYTIME WITHIN ONE YEAR OF DATE OF FINAL ACCEPTANCE.10.IN CASE OF ANY DISCREPANCY BETWEEN THE VARIOUS DRAWINGS, OR BETWEEN DRAWINGS AND SPECIFICATIONS, THE CONTRACTORSHALL IMMEDIATELY REFER THE MATTER TO THE ENGINEER FOR HIS INTERPERTATION BY MEANS OF A DULY ISSUED ADDENDA. ALLINTERPRETATIONS OF DRAWINGS AND SPECIFICATIONS SHALL REST SOLELY WITH THE ENGINEER, AND HIS INTERPRETATION SHALL BECONSIDERED FINAL. NO ORAL INTERPRETATION OF ANY KIND REGARDING ANY PART OF THE CONTRACT DOCUMENTS SHALL BE BINDINGUPON THE OWNER, ARCHITECT, ENGINEER OR BIDDER. ANY ADDENDA’S ISSUED DURING THE TIME OF BIDDING SHALL BE INCLUDED IN THEBID PROPOSAL AND SHALL BECOME A PART OF THE CONTRACT DOCUMENTS UPON AWARD OF THE CONTRACT.11.CONTRACTOR SHALL VISIT THE SITE TO VERIFY ALL CONDITIONS WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT.12.CONTRACTOR TO SUBMIT SHOP DRAWINGS SHOWING DETAILED ARRANGEMENTS OF ALL WORK BEOFRE COMMENCING WORK ON THEJOB. A MINIMUM OF TWO (2) COPIES SHALL BE REQUIRED. DRAWINGS SUBMITTED SHALL BEAR STAMPS OF THE APPROVAL OF CONTRACTORAS EVIDENCE THAT DRAWINGS HAVE BEEN CHECKING BY CHECKED BY HIM AND COMPLY WITH REQUIREMENTS OF THE CONTRACTDOCUMENTS AND SPECIFICATIONS. ANY DRAWINGS SUBMITTED WITHOUT THIS STAMP OF APPROVAL WILL NOT BE CONSIDERED AND WILLBE RETURNED TO THE CONTRACTOR FOR RESUBMISSION. IF DRAWINGS SUBMITTED SHOW VARIATIONS FROM REQUIREMENTS OFCONTRACT, CONTRACTOR WILL MAKE SPECIFIC MENTION OF SUCH VARIATIONS IN HIS LETTER OF TRANSMITTAL IN ORDER THAT IFACCEPTABLE, SUITABLE ACTION MAY BE TAKEN FOR POROPER ADJUSTMENT.13.THE CONTRACTOR SHALL RECORD ALL INSTALLED WORK, INCLUDING ALL CHANGES FROM THE DESIGN DRAWINGS. RECORDINGS SHALLBE MADE ON PRINTS KEPT IN GOOD CONDITION AT THE JOB SITE AS THE WORK PROGRESSES AND BEFORE ANY WORK IS COVERED. UPONCOMPLETIOTION OF THE WORK, THE JOB SITE PRINTS SHALL BE DELIVERED TO THE DESIGN ENGINEER CERTIFIED THAT ALL WORK WASINSTALLED AS SHOWN. AFTER APPROVAL BY ENGINEER, THE CONTRACTOR SHALL TRANSFER ALL DATA FROM PRINTS TO REVIT. THE REVITDRAWINGS AND TWO (2) SETS OF PRINTS SHALL BE DELIVERED TO THE ENGINEER. FINAL APPROVAL OF THE WORK AND FINAL PAYMENTSHALL BE WITHHELD UNTIL RECEIPT OF THE DRAWINGS.14.FINISH PAINTING WILL BE DONE UNDER THE G.C. FINISHED SURFACES OF EQUIPMENT SHALL BE TOUCHED UP WITH THE SAME PAINT ASAPPLIED AT THE FACTORY.15.CONTRACTOR SHALL MAKE TESTS TO DETERMINE THAT ALL SYSTEMS PROVIDED UNDER THIS CONTRACT ARE IN SATISFACTORYCONDITION TO BE STARTED.16.THE WORK COVERED UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL INCLUDE FURNISHING OF ALL EQUIPMENT, MATERIALS,LABOR AND TOOLS NECESSARY FOR A COMPLETE SYSTEM FOR EACH OF THE VARIOUS PHASES OF THE HEATING, AIR CONDITIONING ANDVENTILATING WORK, AS HEREIN SPECIFIED AND INDICATED ON THE DRAWINGS.17.THIS CONTRACTOR SHALL FURNISH ALL LABOR AND MATERIALS NECESSARY TO COMPLETE ALL WORK AS SHOWN ON THE DRAWINGSAND SPECIFICATIONS. THIS WORK SHALL INCLUDE A PERFECTLY OPERABLE AND FUNCTIONING SYSTEM.18.CONTRACTOR TO COORDINATE ALL VOLTAGE REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR PRIOR TO ORDERING ANDINSTALLING OF MECHANICAL EQUIPMENT.19.MECHANICAL CONTRACTOR TO COORDINATE INSTALLATION OF HIS EQUIPMENT WITH ALL OTHER TRADES.

SERVICE BAY A

SERVICE BAY B

120,000

120,000

120,000

120,000

99,600

99,600

99,600

99,600

1/4

1/4

1/4

1/4

1

1

1

1

0.6

0.6

MFGR

MFGR18

18

92°

92°

AIR COOLED CONDESING UNIT SCHEDULE NOTES:

1. COORDINATE MOUNTING LOCATION OF AIR COOLED CONDENSING UNIT WITHSITE PLAN.

2. CONTRACTOR TO ROUTE REFRIGERATION PIPING THRU BUILDING AS REQUIREDREFRIGERANT PIPING TO BE SIZED BY UNIT MANUFACTURER.

3. CONDENSER WITH BUILT IN HAIL PROTECTION.4. UNIT SELECTED FOR 92° F AMBIENT OUTSIDE SUMMER.5. CAPACITIES ARE BASED ON 45° F SUCTION TEMPERATURE, 95° F CONDENSING

TEMPERATURE, AND 95° F AMBIENT TEMPERATURE.6. CONTRACTOR TO SEE DETAIS ON SHEET M-501 FOR INSTALLAION REQUIREMENTS.7. FOR UNITS WITH LINSETS EXCEEDING 80' IN LENGTH 20' IN HEIGHT, PROVIDE

COMPRESSOR START ASSIST CAPACITOR AND RELAY. CRANKCASE HEATER HARDSHUT OFF TXV. LIQUID LINE SHUT SOLENOID AND ADJUST EXPANSION DEVICE PERMANUFACTURERS GUIDELINES.

EXHAUST FAN SCHEDULE NOTES:

1. FAN TO BE CONTROLLED BY THERMOSTAT.2. FAN TO BE CONTROLLED BY MANUAL WALL SWITCH & CO2 CONTROL. TIGHTSEAL MOTORIZED DAMPER WITH END SWITCH ON BLADE TO OPEN WHEN FANIS ENERGIZED.

GAS FIRED PROP UNIT SCHEDULE NOTES:

1. COORDINATE LOCATION OF UNIT WITH STRUCTURAL DRAWINGS.2. UNIT MOUNTED WITH HANGERS FROM STUCTURE.3. INLET GAS PRESSURE 5"-14" IN WG. UNIT SUPPLIED WITH GAS PRESSURE

REGULATOR.4. UNIT SUPPLIED WITH DISCONNECT SWITCH. COORDINATE ELECTRIC POWER

REQUIREMENTS WITH E.C.5. PROVIDE COMBUSTION AIR INTAKE VENT PIPING AND EXHAUST FLUE PIPING AS

REQUIRED FOR INSTALLLATION. INSTALL PER MGFR'S RECOMMENDATIONS FORVENTING INSTALLATION. BE MINIMUM OF 36" CLEAR FROM COMBUSTION AIR INTAKE.

6. PROVIDE BELT GUARD.7. E.A.T = 50°F ADJUSTABLE.8. TRANSFORMER FOR LOW VOTAGE WALL MOUNTED THERMOSTAT.

GAS FIRED FURNACE SCHEDULE NOTES:

1. PROVIDE FURNACE WITH RETURN AIR FILTER.2 PROVIDE ELECTRONIC PROGRAMMABLE THERMOSTAT.3. PROVIDE TWO (2) SETS EACH OF MINIMUM 30% EFFICIENCY 2" PLEATEDFILTERS.4. PROVIDE UNITS COMPLETE WITH CASED COOLING COILS.5. MINIMUM 18 SEER.6. GAS EFFICIENCY 96%

ELECTRIC PROP UNIT HEATER SCHEDULE NOTES:

1. EXPOLSION PROOF.

# Revision Date

A1 Addendum 1 1/9/17

TEMPERATURE CONTROL SEQUENCE OF OPERATIONS

FURN-1 SUPPLIER SHALL PROVIDE ELECTRONIC PROGRAMMABLE THERMOSTAT AND USE AN OWNER-DEFINED TIME SCHEDULE ANDHEATING/COOLING SETPOINTS. ERV-1 SHALL RUN WHEN FURN-1 RUNS.

FURN-2 SUPPLIER SHALL PROVIDE ELECTRONIC PROGRAMMABLE THERMOSTAT AND USE AN OWNER-DEFINED TIME SCHEDULE ANDHEATING/COOLING SETPOINTS. ERV-2 SHALL RUN WHEN FURN-2 RUNS.

PUH-1 & 2 SHALL UTILIZE A LINE VOLTAGE THERMOSTAT WITH HEATING/COOLING/FAN CONTROL. PROPELLER UNIT HEATERS (PUH-1,2)SHALL RUN WHEN THEIR RESPECTIVE LINE VOLTAGE THERMOSTAT IS BELOW SETPOINT. EXHAUST FAN SHALL RUN WHEN THE LINEVOLTAGE THERMOSTAT IS ABOVE SETPOINT. FAN SWITCH ON THERMOSTAT SHALL HAVE THE CAPABILITY TO RUN EXHAUST FAN ASNEEDED. COOLING CONTROL FOR EF-1 SHALL COME FROM THERMOSTAT ON PUH-1. COOLING CONTROL OF EF-2 SHALL COME FROMTHERMOSTAT ON PUH-2. BOTH EXHAUST FANS SHALL RUN IF CARBON MONOXIDE IS DETECTED. CARBON MONOXIDE SENSORS SHALLBE LOCATED BELOW PUH-1 AND PUH-3 (TO SENSE BOTH SIDES OF SERVICE BAYS).

PROPELLER UNIT HEATERS (PUH-3,4,5) SHALL RUN WHEN THEIR RESPECTIVE LINE VOLTAGE THERMOSTAT IS BELOW SETPOINT. PUH-3,4 AND 5 SHALL UTILIZE A HEATING ONLY LINE VOLTAGE THERMOSTAT.

A1