Permit No. NH0001473 Page 1 of 30 DRAFT AUTHORIZATION TO DISCHARGE UNDER THE NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) In compliance with the provisions of the Federal Clean Water Act, as amended, (33 U.S.C. §§1251 et seq.; the "CWA"), Public Service Company of New Hampshire, dba Eversource Schiller Station is authorized to discharge from the facility located at Schiller Station 400 Gosling Road Portsmouth, NH 03801 to receiving waters named: Piscataqua River (USGS Hydrologic Basin Code 01060003) in accordance with effluent limitations, monitoring requirements and other conditions set forth herein. This permit shall become effective on the first day of the calendar month following sixty (60) days after the date of signature.* This permit supersedes the permit issued on September 11, 1990. This permit and the authorization to discharge expire at midnight, five (5) years from the last day of the month preceding the effective date. This permit consists of: 30 pages in Part I which includes effluent limitations, monitoring and reporting requirements and conditions; as well as 25 pages in Part II which includes General Conditions and Definitions. Signed this ___ day of ___________, 20__ Ken Moraff, Director Office of Ecosystem Protection U.S. Environmental Protection Agency Region I - New England Boston, Massachusetts * If no comments requesting a change to the draft permit are received, the permit will become effective upon the date of signature. DRAFT

DRAFT AUTHORIZATION TO DISCHARGE UNDER THE · PDF fileDRAFT AUTHORIZATION TO DISCHARGE UNDER THE NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM ... yard drains to the Piscataqua

  • Upload
    vohanh

  • View
    220

  • Download
    2

Embed Size (px)

Citation preview

  • Permit No. NH0001473 Page 1 of 30

    DRAFT AUTHORIZATION TO DISCHARGE UNDER THE NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)

    In compliance with the provisions of the Federal Clean Water Act, as amended, (33 U.S.C. 1251 et seq.; the "CWA"),

    Public Service Company of New Hampshire, dba Eversource Schiller Station

    is authorized to discharge from the facility located at

    Schiller Station 400 Gosling Road

    Portsmouth, NH 03801

    to receiving waters named: Piscataqua River (USGS Hydrologic Basin Code 01060003)

    in accordance with effluent limitations, monitoring requirements and other conditions set forth herein.

    This permit shall become effective on the first day of the calendar month following sixty (60) days after the date of signature.*

    This permit supersedes the permit issued on September 11, 1990.

    This permit and the authorization to discharge expire at midnight, five (5) years from the last day of the month preceding the effective date.

    This permit consists of: 30 pages in Part I which includes effluent limitations, monitoring and reporting requirements and conditions; as well as 25 pages in Part II which includes General Conditions and Definitions.

    Signed this ___ day of ___________, 20__

    Ken Moraff, Director Office of Ecosystem Protection U.S. Environmental Protection Agency Region I - New England Boston, Massachusetts

    * If no comments requesting a change to the draft permit are received, the permit will become effective upon the date of signature.

    DRAFT

  • Permit No. NH0001473 Page 2 of 30

    PART I.A. EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS

    1. During the period beginning on the effective date and lasting through the expiration date, the permittee is authorized to discharge from outfall number 001: non-contact cooling water and roof and northwest yard drains to the Piscataqua River. Such discharges shall be limited and monitored by the permittee as specified below.

    Effluent Characteristic

    Discharge Limitations Monitoring Requirements Average Monthly

    Maximum Daily Frequency

    5 Sample Type

    Flow (million gallons/day [MGD]) 40 40 Quarterly6 Recorder

    Total Residual Oxidant (mg/L)1 - 0.22 Daily when in use Grab

    Oil & Grease (mg/L) 15 20 Quarterly6 Grab

    Temperature (F) Report 953 Hourly when on-line Grab

    Temperature Rise (F) Report 254 Hourly when on-line Calculate7

    Samples taken in compliance with the monitoring requirements specified above shall be taken at a representative point prior to discharge into the receiving water.

    1 Total residual oxidant (TRO) may not be discharged for more than two hours in any one day unless the facility can demonstrate to the Regional Administrator that the unit in this particular location cannot operate at or below this level of oxidation. The term "Regional Administrator" means the Regional Administrator of Region 1 of the U.S. Environmental Protection Agency.

    2 This TRC limit shall not be exceeded at any time (instantaneous maximum); not a maximum daily limit.

    3 The 95F temperature limit shall not to be exceeded at any time (instantaneous maximum). At no time shall the discharge cause the receiving water to exceed a maximum temperature of 84F at a distance of 200 feet in any direction from the point of discharge.

    4 The temperature rise limitation is increased from 25F to 30F for a two-hour period per day during condenser maintenance.

    5 If no sampling is required for a particular parameter and monitoring period, the permittee should enter the appropriate No Data Indicator Code (NODI) in the monthly Discharge Monitoring Report (DMR).

    6 This parameter shall be monitored during each calendar quarter (January-March, April-June, July-September, and October-December) and reported on the monthly DMR following the end of each calendar quarter (i.e., April, July, October, and January).

    7 Temperature rise is defined as the difference between the influent (ambient) temperature and the effluent (discharge) temperature.

    DRAFT

  • Permit No. NH0001473 Page 3 of 30

    2. During the period beginning on the effective date and lasting through the expiration date, the permittee is authorized to discharge from outfall numbers 002 (Unit #4), 003 (Unit # 5) and 004 (Unit #6): non-contact cooling water and condenser hotwell drains. Such discharges shall be limited and monitored by the permittee as specified below.

    Effluent Characteristic

    Discharge Limitations Monitoring Requirements Average Monthly

    Maximum Daily Frequency

    5 Sample Type

    Outfall 002 Flow (MGD) 43.5 52.2 Continuous Recorder

    Outfall 003 Flow (MGD) 50.2 50.2 Continuous Recorder

    Outfall 004 Flow (MGD) 50.2 50.2 Continuous Recorder

    Total Residual Oxidants (mg/L)1 - 0.22 Daily when in use Grab

    Temperature (F) Report 953 Hourly when on line Grab

    Temperature Rise (F) Report 254 Hourly when on line Calculate6

    Samples taken in compliance with the monitoring requirements specified above shall be taken at a representative point prior to discharge into the receiving water.

    1 Total residual oxidants (TRC) may not be discharged for more than two hours in any one day from any one unit unless the facility can demonstrate to the Regional Administrator that the unit in this particular location cannot operate at or below this level of oxidation. The term "Regional Administrator" means the Regional Administrator of Region 1 of the U.S. Environmental Protection Agency.

    2 This TRC limit shall not be exceeded at any time (instantaneous maximum); not a maximum daily limit.

    3 The 95F temperature limit shall not to be exceeded at any time (instantaneous maximum). At no time shall the discharge cause the receiving water to exceed a maximum temperature of 84F at a distance of 200 feet in any direction from the point of discharge.

    4 The temperature rise limitation is increased from 25F to 30F for a two-hour period per day during condenser maintenance.

    5 If no sampling is required for a particular parameter and monitoring period, the permittee should enter the appropriate No Data Indicator Code (NODI) in the monthly Discharge Monitoring Report (DMR).

    6 Temperature rise is defined as the difference between the influent (ambient) temperature and the effluent (discharge) temperature.

    DRAFT

  • Permit No. NH0001473 Page 4 of 30

    3. During the period beginning on the effective date and lasting through the expiration date, the permittee is authorized to discharge from outfall number 006: emergency boiler blowdowns, deaerator overflows and roof drains. The outfall consists of 6 pipes; 2 for each of Units 4, 5, and 6. Such discharges shall be limited and monitored by the permittee as specified below.

    Effluent Characteristic

    Discharge Limitations Monitoring Requirements Average Monthly

    Maximum Daily Min Max Frequency

    3 Sample Type

    Flow1 (Gallons) - Report - - When in use Estimate

    pH2 (S.U.) - - 6.5 8.0 When in use Grab Total Suspended Solids (mg/L) 30 100 - - When in use Grab

    Oil & Grease (mg/L) 15 20 - - When in use Grab

    Total Nitrogen (mg/L) - Report - -

    Quarterly, when in use4 Grab

    Samples taken in compliance with the monitoring requirements specified above shall be taken at a representative point prior to discharge into the receiving water. The continuous blowdown sampling station shall be at a representative point.

    1 The discharge consists only of boiler blowdowns during an emergency condition or when a boiler experiences a severe disruption. The duration and amount of flow shall be estimated when a discharge occurs. The amount (gallons) shall be reported in the monthly DMR and the duration (hours) shall be submitted as an attachment. The flow estimate shall not include the steam portion of the discharge.

    2 The permittee shall evaluate pH control methods for the emergency blowdowns. If the discharge pH is not able to be maintained within the range of 6.5 to 8.0 standard units, the permittee is required to route this discharge to the on-site WWTP for pH neutralization.

    3 If no sampling is required for a particular parameter and monitoring period, the permittee should enter the appropriate No Data Indicator Code (NODI) in the monthly Discharge Monitoring Report (DMR).

    4 This parameter shall be monitored during each calendar quarter (January-March, April-June, July-September, and October-December) and reported on the monthly DMR following the end of each calendar quarter (i.e., April, July, October, and January).

    DRAFT

  • Permit No. NH0001473 Page 5 of 30

    4. During the period beginning on the effective date and lasting through the expiration date, the permittee is authorized to discharge from outfall number 011: Schiller Station Tank Farm drains and stormwater. The effluent from 3 individual pipes combine to create the culverted outfall. Such discharges shall be limited and monitored by the permittee as specified below.

    Effluent Characteristic

    Discharge Limitations Monitoring Requirements Average Monthly

    Maximum Daily Min Max Frequency

    5 Sample Type

    Flow (GPD) 300,000 600,000 - - Daily Estimate Total Suspended Solids (mg/L) 30 100 - - Quarterly

    6 Grab

    Oil & Grease (mg/L) 15 20 - - Quarterly6 Grab

    pH1 (S.U.) - - 6.5 8.0 Monthly Grab

    Group I Polycyclic Aromatic Hydrocarbons (PAHs)2,4 (ug/l)

    Benzo(a)anthracene - Report - - Quarterly6 Grab

    Benzo(a)pyrene - Report - - Quarterly6 Grab

    Benzo(b)fluoranthene - Report - - Quarterly6 Grab

    Benzo(k)fluoranthene - Report - - Quarterly6 Grab