Diagnostics of Stator Insulation by Dielectric Response and Variable Frequency Partial Discharge Measurements A study of varied low frequencies in stator insulation, with particular attention to end-winding stress-grading Licentiate presentation by Nathaniel Taylor Division of Electromagnetic Engineering, KTH Thursday 23 rd November, 2006 10 -3 10 -2 10 -1 10 0 10 1 10 2 10 3 10 -13 10 -12 10 -11 frequency, Hz C’,C’’, F 0.1 kV pk 1.0 kV pk 10.0 kV pk 20.0 kV pk phase, degrees charge, C 90 180 270 360 -8 -6 -4 -2 0 2 4 6 8 x 10 -9 0 0.06 0.12 0.17 0.23 0.29 0.35 0.4 0.46 0.52 0.58 0.63 0.69 0.75 0.81 0.86 0.92 0 0.01 0.02 -2 0 2 x 10 -4 time, s current, A 50.00Hz 0 0.1 0.2 -2 0 2 x 10 -5 time, s current, A 5.00Hz 0 1 2 -2 0 2 x 10 -6 time, s current, A 0.50Hz 0 10 20 -2 0 2 x 10 -7 time, s current, A 0.05Hz PD x 13 PD x 7 PD x 20 PD x 51 1

Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

  • Upload
    lydung

  • View
    228

  • Download
    7

Embed Size (px)

Citation preview

Page 1: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Diagnostics of Stator Insulation by Dielectric Response andVariable Frequency Partial Discharge Measurements

A study of varied low frequencies in stator insulation, with particular

attention to end-winding stress-grading

Licentiate presentation by

Nathaniel Taylor

Division of Electromagnetic Engineering, KTH

Thursday 23rd November, 2006

10−3

10−2

10−1

100

101

102

103

10−13

10−12

10−11

frequency, Hz

C’,C

’’, F

0.1 kV pk

1.0 kV pk

10.0 kV pk

20.0 kV pk

phase, degrees

char

ge, C

90 180 270 360

−8

−6

−4

−2

0

2

4

6

8

x 10−9

00.060.120.170.230.290.350.40.460.520.580.630.690.750.810.860.92

0 0.01 0.02−2

0

2x 10

−4

time, s

curr

ent,

A

50.00Hz

0 0.1 0.2−2

0

2x 10

−5

time, s

curr

ent,

A

5.00Hz

0 1 2−2

0

2x 10

−6

time, s

curr

ent,

A

0.50Hz

0 10 20−2

0

2x 10

−7

time, s

curr

ent,

A

0.05Hz

PD x 13

PD x 7

PD x 20 PD x 51

1

Page 2: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

1. Stator insulation

— Machine construction

— Stator insulation construction

— Stator insulation defects

— Current diagnostic practices

2. (HV) Dielectric spectroscopy

3. (VF) Partial discharge measurement

4. End-winding stress-grading

5. Examples on real stator insulation

6. Conclusions

2

Page 3: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Machine Construction

Stator insulation

slotend

Rotor insulation

Mechanical (bearings)

3

Page 4: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Stator Insulation

Un ' 1 kV =⇒ form-wound

Un ' 5 kV =⇒ ‘corona prevention’ (grading)

Un / 30 kV in spite of ratings ≈1—1500 MW!

turn insulation

main insulation

semicon layer

slot wedge

conductors

stator iron

Strand

Turn

Mainpicture: Siemens & vonRoll Isola

4

Page 5: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Relevant Constructional Variations

Insulation binding material

(between the mica pieces):

— bitumen high loss, migrates

— polyester resin

— epoxy resin

Hydro- or turbo-generator:

speed affects diameter/length,

which affects ratio of end-

length/slot-length and propaga-

tion of PD signals.

Cooling and coolant:

— indirect: heat comes out of

windings through the insulation

— direct: a coolant (typ. water) is

used within the windings

— air/hydrogen: air has lower

EBD and heat capacity, allows

O3 generation by PD, and assists

oxidation of organic insulation

‘Corona-prevention’ (semicon-

ductor layers) or not?

5

Page 6: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Stator Insulation Defects

Stress: Thermal, Electrical

‘Ambient’, Mechanical

Cause: primary, secondary?

Manifestation:

Delamination, cavities

Electrical Treeing

Worn slot semiconductor

Worn end semiconductor

Contamination on end-windings

6

Page 7: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Diagnostic Methods in Common Use

Many methods don’t depend on electrical connection to the windings,

e.g. detect PD by measuring RF emissions, chemicals, sound, light, or

use mechanical measurements and visual inspection, PD

measurement by couplers.

Others more relevant to this work: off-line, with galvanic connection.

Note that off-line usually implies significant differences from normal

stresses.

On-line—Off-line: expenses, realistic versus controlled conditions.

Measurement −→ (Physical State) −→ P(failure)

Complex system. Different phenomena can look similar in a

particular measurement. Cannot expect any method to give no false

positives or negatives.

7

Page 8: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Electrical Diagnostics in Common Use

Insulation ‘Resistance’ (IR): ‘DC’ with quite HV, i.e. a form of

time-domain spectroscopy with stepped voltage). This is also known as

‘megging’, and the derived quantity ‘Polarisation Index’ (PI) is popular.

Capacitance and Loss, possibly including ‘Tip-Up’: generally power

frequency (≈50 Hz), with several voltage steps typically up to the rated

line voltage per phase, i.e. overvoltage factor of√

3

Partial Discharge (PD) measurement: again, generally power

frequency, often as ‘phase resolved’ pattern.

8

Page 9: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

1. Stator Insulation

2. (HV) Dielectric Spectroscopy

— Dielectric Materials and their Response

— Dielectric Spectroscopy (DS)

— Material Measurements and Disturbances

— Non-linearity

— High-Voltage (HV) DS, and Applications

— HV DS on Stator Insulation

3. (VF) Partial Discharge measurement

4. End-Winding Stress-Grading

5. Examples on Real Stator Insulation

6. Conclusions

9

Page 10: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Dielectric Materials

Polarisation:

— bounded movement of charge, changing charge-distribution

— increases supplied charge to electrodes (if fixed V)

— many mechanisms (e−, natural dipole, ionic . . . )

— some mechanisms very fast, lumped as ε∞, an increased ε0

— other mechanisms have considerable dynamics: represent as such

with polarisation function f(t) or susceptibility χ(ω):

P (t) = ε0

∫∞

0

f(τ)E(t − τ)dτ

P (ω) = ε0χ(ω)E(ω)

χ(ω) = χ′(ω) − iχ′′(ω) . . .

= F f(t)

V free space

10

Page 11: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Dielectric Response: Exponential Model

Time

f(t) ∝ e−t/τ

10−1

100

101

10−5

10−4

10−3

10−2

10−1

100

time, s

Pol

aris

atio

n fu

nctio

n f(

t)Frequency

χ′(ω)− iχ′′(ω) ∝ 1

(1 + (iωτ)k1)k2

k1 = k2 = 1 in pure exponential case

10−2

10−1

100

101

10−4

10−3

10−2

10−1

100

frequency, Hz

Sus

cept

ibili

ty, R

e &

Im−2

−1

+1

0 imag

real

11

Page 12: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Dielectric Response: Power-Law Model

Time

f(t) ∝ t−n, 0 < n < 1

10−3

10−2

10−1

100

101

102

103

104

10−4

10−3

10−2

10−1

100

101

102

103

time, s

Pol

aris

atio

n fu

nctio

n f(

t)

n = 0.1n = 0.5n = 0.9

Frequency

χ′(ω) − iχ′′(ω) ∝ (iω)n−1

10−4

10−3

10−2

10−1

100

101

102

103

10−4

10−3

10−2

10−1

100

101

102

103

frequency, Hz

Sus

cept

ibili

ty, R

e &

Im

n = 0.1n = 0.5n = 0.9

imagreal

realimag

12

Page 13: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Power-Law Model with Two Parts

f(t) ∝ 1(tτ

)n1+(

)n2

0 < (n1, n2) < 1

10−4

10−2

100

102

104

10−2

10−1

100

101

time (t)

f(t)

n=0.1

n=0.9

13

Page 14: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Dielectric Spectroscopy

Dielectric Spectroscopy =⇒ Dielectric Response at varied t or ω.

Time-Domain (TD) measure f(t), (plus conduction and possibly prompt

response): e.g.

— Step-Response, e.g. Polarisation-Depolarisation Currents (PDC)

— Ramp-Response

— Return Voltage Measurement

Many frequencies are measured at once, but noise rejection is low.

Frequency-Domain (FD) measure χ(ω) (plus conduction and prompt

response), usually by applying a sinusoidal driving voltage V (ω) and

measuring the resultant current I(ω) for various ω.

C′(ω) − iC′′(ω) =I(ω)

iωV (ω)=

C0

ε0

ε′(ω) − iε′′(ω)”

ε′(ω) − iε′′(ω) =h

ε0χ′(ω) + (ε∞ − ε0) + ε0

i

− ih

ε0χ′′(ω) +

σ

ω

i

We favour FD: ease of PD measurement, form of non-linearity.

14

Page 15: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Practical DS Measurements

Basic Measurement sees:

— Free-space capacitance

— Polarisation current

— Bulk conduction

— Surface conduction

— (Fringing, material case)

A

σsurface

A

εmaterialσmaterial

h

Guarding: remove surface conduc-

tion and fringing.

Removal of conduction current

is harder: PDC time-domain

methods, or analysis of frequency-

domain results within assumptions

of linearity.

On actual equipment, one might be

less interested in the material pro-

perties than in the total current.

15

Page 16: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Non-linearity measured with FD-DS

Non-linearity: outin relation is dependent on amplitude.

Currents at frequencies other than the fundamental iff non-linear or

supply voltage not sinusoidal.

Frequency-representation allows even small non-linearity to be seen.

Frequency-representation still allows a lot of directly interpretable

information about the form of the time-domain distortion (odd/even,

sine/cosine).

C′ and C′′ are values calculated on the fundamental components: C′′

maintains its significance of power loss.

s(t) = Re

[K∑

n=0

|Sn|ei(nωt+∠Sn)

]=

K∑

n=0

(An cos(nωt) + Bn sin(nωt))

16

Page 17: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

HV-(FD)DS System

FB(i)

FB(v)

Vref

Vmeas

Imeas

ADC, DSP,computer

v

i

HV amplifier30kV, ~50mA

divider MeasurementObject

guardelectrode

measurementelectrode

instrumentearth

Electrometers

A much simplified block diagram, showing the measurement and

guard electrodes.

17

Page 18: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Applications of HV-DS

Why HV?

— Non-linearity

— Higher current (SNR)

Development of HV-FDDS field-test system

Water-trees in XLPE cables (picture−→)

Machines: usually in time (TD)

Megging? (Qualifies? Inverse Step Response!)

Ramp test

A little recent research interest, TD & FD

End-windings often guarded! (lab, not field)

ETKAesthetic

Obligation

18

Page 19: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

1. Stator insulation

2. (HV) Dielectric spectroscopy

3. (VF) Partial discharge measurement

— Partial discharges (PDs)

— PD detection and analysis

— Effect of frequency on PDs

— PDs and PD measurement in stator insulation

4. End-winding stress-grading

5. Examples on real stator insulation

6. Conclusions

19

Page 20: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Partial Discharges (PDs)

A discharge that fails to bridge the space between the electrodes that

are applying the field; it therefore cannot develop into a disruptive

discharge. For example:

divergent field barrier

Presence of PD can suggest a problem in an insulation system;

detection methods may allow a distinction to be seen between

different sources of PD activity.

PD may cause insulation degradation by thermal, chemical, electrical

and radiation effects.

20

Page 21: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

PD Detection

Many detectable consequences, for example . . .

— released chemicals, e.g. Ozone (O3)

— remnant chemical effects, e.g. powder on surfaces

— sound, ultrasound

— visible light, UV light

— RF emission

— HF and total (integrated) currents in supply ⇐=

Some give an averaged idea of PD activity, some give information

about each PD event (pulse).

Some localise the PD sources.

21

Page 22: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

PD Charge & Calibration

PD charge > measured charge

V

Vcavity

measured PD charge, assumingSimplistic relation of actual and

cavity voltage not changed.

Qapparent =Vcavity

VQactual

Qactual

Qapparent < Qactual

Qapparent ∝ energy in PD

(fixed V)

Calibration: relate measured

Qapparent to a known injection

at the terminals.

Frequency-response (spect-

rum of pulse) can affect

measured charge. DS methods

can (but needn’t) capture the

whole measured charge.

22

Page 23: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

VF-PRPD System

systemPR−PDPRP

sync

Vref

pre−amplifier

alternativeplacements

of measuringimpedance

DAP andcomputer

couplingcapacitor

Measurementobject200pF

HV amplifierfilter

Measuring impedance is typically in test-object earth for lab, or in

coupling capacitor earth for field tests of earthed objects.

Here, all but the PR-PD system is ‘home-brew’.

23

Page 24: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Phase-resolved PD: Simple Example

0 90 180 270 360−Qmax

0

Qmax

phase channels

char

ge c

hann

els

1

1

1

2

23

1

1

PD counts (#cycles)

For each cycle, for each phase-channel (x), any measured PD charge,

Q (y) increments the count in that phase-amplitude (x-y) point.

24

Page 25: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Phase-resolved PD: Typical Plot

phase, degrees

char

ge, C

90 180 270 360

−5

0

5

x 10−9

0

0.06

0.12

0.17

0.23

0.29

0.35

0.4

0.46

Intense cluster at bottom is typical for cavities; here there are also

many, widely distributed, large charges — delamination?

25

Page 26: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Phase-resolved PD: View as Current

phase, degrees

char

ge, C

90 180 270 360

−5

0

5

x 10−9

0

0.06

0.12

0.17

0.23

0.29

0.35

0.4

0.46

0 0.5 1 1.5 2 −1

−0.5

0

0.5

1x 10

−6 I(t)

time, s

curr

ent,

A

0 1 2 3 4 5 6 70

2

4

x 10−7

harmonic order, n

| I |,

A

I(f): Polar form

0 1 2 3 4 5 6 7−180−90

090

180

harmonic order, n

phas

e, d

egre

es

0 1 2 3 4 5 6 7−4−2

024

x 10−7 I(f): Rectangular form (sin/cos)

harmonic order, n

I sine

, A

0 1 2 3 4 5 6 7−4−2

024

x 10−7

harmonic order, n

I cosi

ne, A

26

Page 27: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

PD with Variable Frequency Excitation

Sources of frequency-

dependence

εbulkσbulkv

Ah

σsurface

τcavity — relaxation of voltage across

the cavity due to conduction of current

through σsurface on the cavity’s walls.

τmaterial — relaxation of (space-charge)

field in material, due to εbulk and σbulk.

τstatistical — delay due to the (random)

occurence of a suitable initiating ioni-

sation in the cavity volume v.

Consider e.g. large and small σmaterial

and σsurface, or both = 0.

27

Page 28: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Example: PD Frequency-Dependence

Number of PD pulses from a single cylindrical cavity. Note the

greater distinction between different cavities when at low frequency.

0

2

4

6

8

10

10-2

10-1

100

101

102

10

7

1.5

p

f

0

2

4

6

8

10

10-2

10-1

100

101

102

p

f

28

Page 29: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

PD Measurement on Stator Insulation

worn slot semicon

internal cavities/delaminations

end−windingsdischarge between

worn end−semicon

(slot)

(end)

Several very different sources: different

magnitude to fit between detection

threshold and full-scale

Large size: many ‘simultaneous’ PDs:

some lost in dead-time?

PD propagation: stator is large, con-

tains magnetic material but also the

unshielded end-windings; measuring

system frequency-response important.

29

Page 30: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Frequency-Dependence of Stator PD

All 3 general-case effects τmaterial, τcavity, τstatistical may be involved

in the many sizes and shapes of cavity and delamination that can all

be present together within the insulation.

Around the end-windings: PD on the surface, damaged

stress-grading, conductive contamination; PD between end-windings.

Spreading of earth potential increases the stress in the insulation

material under the stress-grading — more PD, from this part of

insulation too?

At extreme low frequency, end-winding stress-grading may have earth

potential up to its end — surface PD?

30

Page 31: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

(end of SI, DS, PD overview)

31

Page 32: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Advantages: HV-FDDS or VF-PRPDA

FD-DS is here extended with the independent (controlled) variable of

voltage amplitude, V , and with the independent (measured) variable

of the low harmonic spectrum.

— excite non-linearities in the test-object

— distinguish non-linear components in the current

PRPDA is here extended with the independent variable frequency, f .

— get a better idea of location and type of PD sources

— reduce driving voltage source if able to stay ≪ fn

32

Page 33: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Simultaneous VF-PRPDA and HV-FDDS

Both methods require a quite expensive HV amplifier, driven by the

controlling computer.

Both methods may take a long time, when doing LF sweeps at

several voltages!

Both methods give complementary information, and it may even be

good to compare measurements from the same measurement time if

PD currents measured by the two systems are to be compared.

=⇒ combined system, measuring simultaneously, gets more

information, more directly comparable information, takes no more

time than using just one of the methods, and costs less than the sum

of the separate systems.

33

Page 34: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Simultaneous Measurement: Usefulness

Simultaneous Measurement even without a strong link between DS

and PD measurements may be useful in itself: more clues to the state

of the insulation, without extra measurement time.

If PD current seen by integrating charges measured by PD system is

very similar to the PD current measured in the DS system, the PD

part of the DS measurement could be removed. If not, then there are

two measures of PD, which may be a useful complement.

34

Page 35: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

1. Stator insulation

2. (HV) Dielectric spectroscopy

3. (VF) Partial discharge measurement

4. End-winding stress-grading

— Purpose and methods

— Significance to HV-DS and VF-PD measurements

— Material properties, SiC paint and tape

— Physical test objects

— Numerical modelling

5. Examples on real stator insulation

6. Conclusions

35

Page 36: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

End-Winding Stress-Grading

High surface field if slot semi-

conductor just ends.

(Why not continue the slot semi-

conductor at the ends?)

Must reduce the field to prevent

surface discharge.

‘Grading’ around the end:

– geometric, refractive, capacitive:

nice frequency-response, too much

space!

– resistive: frequency-dependence,

so only useful for a narrow fre-

quency band

– non-linear resistive: small space,

wide frequency range; but, wreaks

havoc on measurement of small V

and f dependencies in diagnostic

measurements!

36

Page 37: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Effect of Stress-Grading on DS & PD

PD

Very low frequency spreading of earth potential: surface PD?

Variable stress in insulation under the stress-grading: varied PD?

DS

Considerable (some %) increase in C′, much more in C′′

Large change with V (‘tip-up’) in C′ and C′′ (∆C′ ≈ ∆C′′)

Large change in C′ and C′′ with frequency

Non-linearity: harmonic currents from a source other than PD

Need to determine current into grading, in order to remove it from

DS measurement, if any more ‘material’ property is to be seen or if

PD current is to be seen from harmonics. This modelling is described

here . . .

37

Page 38: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Possibilities of Use of Model

Get some manufacturer data or do a brief measurement to determine

parameters. Then calculate and subtract the stress-grading current!

FAIL: hopelessly poorly defined parameters: material and geometry.

Measure DS, use V ,f dependence to determine parameters. Problem

of PD currents having also a non-linear source. Is DS of

stress-grading below the PD inception level sufficient?

38

Page 39: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Physical test-objects

PTFE tube (inner 20 mm, outer 31 mm), tightly around a metal

tube, with central external metallic electrode and stress-grading

material on either side. Low loss/dispersion apart from grading.

20 31

copper pipe250

PTFE

metallic coatinggrading material

dimensions in mm

gradingsheathbare

regionoverlap bare

insulation

39

Page 40: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

SiC-based grading materials

50 100 30010

−11

10−9

10−7

10−5 SiC paint

mean electric field, V/mm

Cur

rent

, A

thicklypainted

moderatelypainted

thinlypainted

10 100 300

10−8

10−6

SiC B−stage tape

mean electric field, V/mm

Cur

rent

, A

SiC material around a 30 mm diameter insulating tube. The resistivity

spans several decades even just up to 300 V/mm. The measured results are

well fitted (the black circles) by:

Iaxial = EaxialG0 exp(n|Eaxial|2/3

)

Note the huge variation with the paint — a matter of thickness.

40

Page 41: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

SiC-based Grading Materials

Iaxial = EaxialG0 exp(n|Eaxial|2/3

)

This equation is numerically friendly, e.g. the case E = 0.

With Iaxial in A, Eaxial in V/m, the parameters are:

Material G0 (Sm) n ρ(0)surface = 2πrG0

(Ω)

Paint(thin) 2.5 × 10−16 0.00114 3.9 × 1014

Paint(medium) 1.8 × 10−15 0.00115 5.4 × 1013

Paint(thick) 1.0 × 10−13 0.00110 9.7 × 1011

Tape 5.5 × 10−13 0.00115 1.7 × 1011

The “non-linearity” coefficient, n, is very similar in all cases.

It is small as E is in V/m.

41

Page 42: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Taped Bar: Pure Grading Response

Cplotted = Cmeasured − CLV,nograding

10−2

10−1

100

101

102

10−11

frequency, Hz

C’ a

nd C

’’, F

1.48 kVpk4.44 kVpk7.41 kVpk9.88 kVpk12.84 kVpk15.31 kVpk

C’’

C’

Nearly a plain f shift

in loss-peak with V

Low V case nearly

linear: C′ ≈ C′′ at HF

‘Full’ (whole grading

length) C′ at LF

C′′ at LF and HV (high

stress at grading end)

rises: surface leakage?

42

Page 43: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

A general 1D Grading Model

Rs l/n Cp l/n Gp l/n

Cs n/l

Vsupply CendCp dx Gp dx Gend

Cs / dx

Rs dx

upper value: lumped (discrete) parameterslower value: distributed parameters

l (length)

dxn

Rs surely non-linear. End-leakage? Cs needed? Cs constant?

Assumes symmetry around axis. Rs,Cp alone popular even at HF.

43

Page 44: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Why consider simple cases

(Linear, Discrete)?

— The real case and the realistic 1D models have parts that resemble

simpler models, e.g. with low frequency or low voltage-amplitude.

— People often simplify the real case to a very primitive model for

quick qualitative discussion: how wrong is this?

Rs l/n Cp l/n Gp l/n

Cs n/l

Vsupply CendCp dx Gp dx Gend

Cs / dx

Rs dx

upper value: lumped (discrete) parameterslower value: distributed parameters

l (length)

dxn

44

Page 45: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Linear, Discrete: A simple RC-filter

10−4

10−2

100

102

10410

−20

10−18

10−16

10−14

10−12

10−10

frequency, Hz

C’,

C’’,

F C’, R/1C’, R/10C’, R/100C’’, R/1C’’, R/10C’’, R/100

RCC’, C’’

In the plot here (left), three

values of R are used, as

a crude approximation of

voltage-dependent grading.

This is the Debye response, seen earlier.

Slopes (log-log) of ±1 for C′′ away from loss peak, and −2 for C′ at

frequencies above loss-peak.

C′ − iC′′ =Cs

1 + ω2R2sC

2s

− iωRsC

2s

1 + ω2R2sC

2s

45

Page 46: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Linear, Distributed: A diffusive TL

The FD Transmission Line equations are not LC[RG] specific.

Using per-unit-length values of Rs and Cp, with l as TL length,

(characteristic impedance) Z0 =

r

Zseries

Yshunt

=

s

Rs

iωCp

(propagation constant) γ =√

ZseriesYshunt =p

iωCpRs

Zin =Z0

tanh(γl)(when Zend = ∞)

Zin = Z0

Zend + Z0 tanh(γl)

Z0 + Zend tanh(γl)(else)

Then, from Zin the complex capacitance seen at the start of the

grading is:

C′ − iC′′ =1

iωZin=

1 − i√

2

√Cp

ωRstanh

(l√

iωRsCp

)

if Zend=∞

46

Page 47: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

The Linear Models Compared

10−4

10−2

100

102

10410

−20

10−18

10−16

10−14

10−12

10−10

frequency, Hz

C’,

C’’,

F C’, R/1C’, R/10C’, R/100C’’, R/1C’’, R/10C’’, R/100

10−4

10−2

100

102

10410

−20

10−18

10−16

10−14

10−12

10−10

frequency, Hz

C’,

C’’,

F C’, R/1C’, R/10C’, R/100C’’, R/1C’’, R/10C’’, R/100

— At high frequency, distributed case end is not ‘seen’, ∴ l = ∞ and

C′ = C′′ because C′ − iC′′ = 1iωZ0

=√

1i

√C

ωR = (1 − i)√

C2 ωR .

— At low frequency, the discrete and distributed cases are very

similar; the effective length is short.

— The loss peak, C′′, is independent of resistance: this is seen for the

discrete case from ω = 1RC , and C′′ = C (ωRC)

1+(ωRC)2 .

47

Page 48: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Non-linear, Discrete

10−3

10−2

10−1

100

101

102

103

10−13

10−12

10−11

frequency, Hz

C’,C

’’, F

0.100 kVpk

1.000 kVpk

10.000 kVpk

20.000 kVpk

C’

C’’

– Even C′′ is similar for all

V at LF (low stress, so small

effect of non-linearity)

– Effect of V on loss peaks

almost as effect of scaling Rs

– Very fast HF fall-off of C′

& C′′, at different rates

VNL = Vsupply − Vcapacitor

CdVcapacitor

dt= VNLG0 exp

(n |VNL|2/3

)

48

Page 49: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Non-linear, Distributed

10−3

10−2

10−1

100

101

102

103

10−13

10−12

10−11

frequency, Hz

C’,C

’’, F

0.1 kV pk

1.0 kV pk

10.0 kV pk

20.0 kV pk

C’

C’’

– Low f → C′′ similar ∀V

(low stress, so G ≈ G0)

– Low V → ≈ linear

(low stress, so G ≈ G0)

– Increased V : n ↑ in t−n,

i.e. (1 − n) ↓ in (iω)1−n,

so gradient shallower and

C′/C′′ exceeds 1.

C∂V

∂t=

∂x

(∂V

∂xG0 exp

(n

∣∣∣∣∂V

∂x

∣∣∣∣2/3))

49

Page 50: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Comparison: Models of Varied Degree

10−3

10−2

10−1

100

101

102

103

10−13

10−12

10−11

frequency, Hz

C’,

C’’,

F

R/1

R/10

R/100

10−3

10−2

10−1

100

101

102

103

10−13

10−12

10−11

frequency, Hz

C’,

C’’,

F

R/1

R/10

R/100

10−3

10−2

10−1

100

101

102

103

10−13

10−12

10−11

frequency, Hz

C’,C

’’, F

0.100 kVpk

1.000 kVpk

10.000 kVpk

20.000 kVpk

C’

C’’

10−3

10−2

10−1

100

101

102

103

10−13

10−12

10−11

frequency, Hz

C’,C

’’, F

0.1 kV pk

1.0 kV pk

10.0 kV pk

20.0 kV pk

C’

C’’

50

Page 51: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Comparison: Model and Measurement

10−2

10−1

100

101

102

10−12

10−11

frequency, Hz

C’,

F

1.5 kV pk − measured

7.4 kV pk − measured

15.3 kV pk − measured

1.5 kV pk − simulated

7.4 kV pk − simulated

15.3 kV pk − simulated

10−2

10−1

100

101

102

10−12

10−11

frequency, Hz

C’’,

F 1.5 kV pk − measured

7.4 kV pk − measured

15.3 kV pk − measured

1.5 kV pk − simulated

7.4 kV pk − simulated

15.3 kV pk − simulated

Correct Parameters? Rs (G0), n, Cp

Sufficient Model? Any need for Cs, Gend, etc.?

The Physical Measurement: correct subtraction of bulk current?

51

Page 52: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Harmonic Content in Grading Current

1 Hz time-domain currents.

0 90 180 270 360 450 540 630 720−4

−3

−2

−1

0

1

2

3

4x 10

−6

phase, degrees

I(t)

, A

15.3 kV pk

7.5 kV pk

1.5 kV pk

voltage Solid lines: physical

Dashed lines: simulation

Quite good correspondence

(but this was close to the loss

peak, where the model fitted

well).

52

Page 53: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Potential-Distributions in the Grading

0 90 180 270 360−20

−10

0

10

20kV

End potential, 15.3 kV

0 90 180 270 360−1

−0.5

0

0.5

1

V /

Vap

plie

d

End potential, 1 Hz

0 10 20 30 40 50 60 70 800

0.5

1

distance from fixed potential, mm

V /

Vap

plie

d

Maximum potential along length

0 90 180 270 360−20

−10

0

10

20

kVphase

Waveform, by length, 50 Hz 15 kV

100 Hz

10 mHz

1.5 kV

15.3 kV

1.5 kV (green), 15.3 kV (red)10 mHz

100 Hz

end

electrode

53

Page 54: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Improvement of Modelling

Extra components in model not very helpful.

Variation of Rs (G0) allows much improved fitting.

n (non-linearity) is largely constant between the materials used.

Cp maybe not so easy in real, aged insulation.

10−2

10−1

100

101

102

10−12

10−11

frequency, Hz

C’’,

F

15 kV1.5 kV1*Rs

2*Rs

2*Rs

1*Rs

10−2

10−1

100

101

102

10−11

frequency, HzC

’, F

15 kV

1.5 kV

1*Rs

1*Rs

2*Rs

2*Rs

Suggestion: assume SG and PD is the only non-linearity; get SG

parameters from sub-PD-inception voltages.

54

Page 55: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Differences between Physical Models

and Real Stator Insulation

Geometry: not circular.

Isolation: surrounded by others, not in open space.

C0 typically larger (thinner insulation) in the real case.

Permittivity is greater for stator insulation than for PTFE.

So, Cp is larger in real case, and loss-peak at much lower frequency.

— unfounded worries about PD at end at practical LF

— HF part of model (l → ∞) is of most interest

55

Page 56: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

1. Stator Insulation

2. (HV) Dielectric spectroscopy

3. (VF) Partial discharge measurement

4. End-winding stress-grading

5. Examples on real stator insulation

— Measurements on a coil, new and aged

Accelerated thermal aging, Practical stress-grading parameters, PD current by

PD and DS methods, Frequency-dependence of PD

— Field measurement on whole windingsConstraints on frequency, Variability of different measurement methods

6. Conclusions

56

Page 57: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Real Stator Coils: A1 & A2

Newly made stator coils. Accelerated thermal aging.

le

ls

lw

transition from slot to

guard−break in slotsemicon screen

end grading material

lc

crosssection

w1

w2

end−windingslot part

end−winding

Slot length between guards ls = 1553 mm

External slot cross-section w1 × w2 = 11.5 mm × 33.0 mm.

Insulation thickness ≈ 1.9 mm.

Rated r.m.s. line voltage, Un = 7.2 kV.

57

Page 58: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Slot semiconductor resistivity

0 100 200 300 400 5000

1

2

3

4

5

6

7x 104

mean field, V/m

per−

leng

th r

esis

tanc

e, O

hm/m

1.0m, new0.5m, new1.0m, new0.5m, aged0.5m, aged1.0m, aged

10−2

100

102

10410

−11

10−10

10−9

10−8

frequency, Hz

Cp,

Cb

(C

’,C’’,

Far

ads)

12.5 Vpk50 Vpk200 Vpk

loss, Cb

capacitance, Cp

three electrodes andsparsely wrapped wire

one, centralelectrode

— Surface resistivity ≈ 5kΩ(/sq) before, ≈ 2kΩ(/sq) after aging.

— With Al foil taped around slot-section, very small loss tip-up.

— Slight voltage-dependence — blame this on the very low voltages

(contact?), not important for our usual voltage levels.

58

Page 59: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Guarded DS on New Coil (A1)

10−4

10−2

100

102

4.8

5

5.2

5.4

5.6x 10

−9

frequency, Hz

C’,

F

1 kVpk

3 kVpk

6 kVpk

10−4

10−2

100

102

10−10

frequency, Hz

C’’,

F

1 kVpk

3 kVpk

6 kVpk

Largely linear.

≈ 10% increase in C′, 50 Hz → 0.0001 Hz

≈ 5× increase in C′′ in same range.

59

Page 60: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Unguarded DS on New Coil (A1)

10−4

10−2

100

102

5

5.5

6

6.5x 10

−9

frequency, Hz

C’,

F

1 kVpk

4 kVpk

7 kVpk

10 kVpk

10−4

10−2

100

102

10−10

frequency, Hz

C’’,

F

1 kVpk

4 kVpk

7 kVpk

10 kVpk

Not linear.

Extra ≈ 10% increase in C′, 50 Hz → 0.0001 Hz

Now ≈ 10× (previously 5×) increase in C′′ in same range.

60

Page 61: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Guarded DS on Aged Coil (A1)

10−2

100

102

4.45

4.5

4.55

4.6

4.65

4.7x 10

−9

frequency, Hz

Cp

(

C’,

Far

ads)

1kVpk

3 kVpk

5 kVpk

7 kVpk

9 kVpk

10−2

100

102

2

4

6

8

10

12

14x 10

−11

frequency, Hz

Cb

(

C’’,

Far

ads)

1 kVpk

3 kVpk

5 kVpk

7 kVpk

9 kVpk

— Amplitude-dependent increase in C′ and C′′ is very similar,

reflecting the ≈ 45 phase of the non-linearity (PD).

— Amplitude-dependent increase is greater at lower frequency,

suggesting greater PD charge, implying (on average) long τcavity or

some external PD.

61

Page 62: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

DS and PD Measurement of PD Current

Accelerated thermally aged stator coil. PD and guarded DS.

0 0.01 0.02−2

0

2x 10

−4

time, s

curr

ent,

A

50.00Hz

0 0.1 0.2−2

0

2x 10

−5

time, s

curr

ent,

A

5.00Hz

0 1 2−2

0

2x 10

−6

time, s

curr

ent,

A

0.50Hz

0 10 20−2

0

2x 10

−7

time, s

curr

ent,

A0.05Hz

PD x 13

PD x 7

PD x 20 PD x 51

Waveform fits well

between DS and

PD measurements.

Magnitude doesn’t!

See scaling factors

for PD.

Very heavy PD:

— dead-time

— attenutation

— spectrum

62

Page 63: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

New and Aged Coils: Lessons

Much lower frequency of the loss-peak of stress-grading than in the

laboratory models.

Obvious large influence of stress-grading on insulation and PD

currents.

The thermal aging at 180C for about 1 week left a large number of

PD sources throughout the previously PD-free (as much as

detectable) insulation.

Even without very long windings and ferrous surroundings, DS

apparently measures much higher total PD current than is seen from

the calibrated PD pulse measurement.

63

Page 64: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Field-Test: DS on Whole Windings

Large-diameter hydro-generator.

Sn = 10 MVA, Un = 6.3 kV

About 30 years old.

Diagnostic testing before and after some maintenance work.

64

Page 65: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Whole Winding: Insulation ‘Resistance’

IR (‘megging’) at 5 kV.

3 occasions. Measure u, v, w, uvw.

0 100 200 300 400 500 6000

500

1000

1500

time, s

"r

esis

tanc

e", M

Ohm

−x− : 1a −+− : 1b −o− : 2

uv w

uvw

Expect ≈ 5000 MΩ

at 600 s

Large difference

between phases

uvw value tracks

worst of u, v, w

Large difference

between the three

measurement occa-

sions 1a,1b,2!

65

Page 66: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Whole Windings: DS with LV & LF

10−2

10−1

100

101

102

10−9

10−8

10−7

10−6

10−5

frequency, Hz

capa

cita

nce,

F

C’ uvw

C’ u, v, w

C’’ uvw

C’’ u, v, w

w rising

Occasion ‘1b’.

Measurement: 50 V

peak

C′ similar for u,v,w

LF C′′ w rises

LF C′′ uvw rises too

66

Page 67: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Whole Windings: DS with HV

0 2 4 65.71

5.72

5.73

5.74

5.75x 10

−7

applied peak voltage, kV

C’ (

0.31

6 H

z), F

u

v

w

0 2 4 61.8

2

2.2

2.4

2.6

2.8x 10

−8

applied peak voltage, kV

C’’

(0.3

16 H

z), F

u

v

w

(Note: a different occasion (2) from the LV&LF measurement (1b) ).

Too little time or current to go much lower or higher in f .

A large difference in loss is seen in u, with HV.

67

Page 68: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Whole Windings: Lessons

Time is very limited during outage: cannot do large number of V

values or very low f . Need a well-planned V ,f sequence. Particular

advantage of simultaneous measurements if doing DS & PD.

Winding capacitance is of the order of 1 µF (at 50 Hz). Maximum

frequency is therefore around 1–2 Hz for 5 kV test with our amplifier.

The above points restrict the usable range of frequencies! One

consequence is a reduced bandwidth requirement for the

stress-grading model.

Varied V and f may have a large effect on the measurement in the

presence of insulation problems.

68

Page 69: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

1. Stator Insulation

2. (HV) Dielectric spectroscopy

3. (VF) Partial discharge measurement

4. End-winding stress-grading

5. Examples on real stator insulation

6. Conclusions

69

Page 70: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Conclusions

• Stress-grading model presented seems good for fundamental and harmonic

components away from the extremes of frequency; components other than

Rs (NONLINEAR)and Cp

• Stress-grading model needs good parameters: the most variable is G0, within

the expression for Rs. Infeasible in real machines to calculate parameters a

priori; try fitting from sub-PD measurements?

• Stress-grading C′ and C′′ strongly disturb insulation DR and PD harmonics.

Different V dependence: insulation DR generally quite linear, PD doesn’t

occur below some inception voltage.

• PD measurement with varied V and f is distinctly interesting!

• Whole PD current may be measured with (suitable) DS system; this may be

a lot more than measured with a PD pulse detector (is this useful?).

Consequently, removal of PD from DS given a PR-PDP is not feasible.

• Use of harmonic spectrum in DS is a good way to consider just the

phenomena beyond the (largely linear) bulk material.

70

Page 71: Diagnostics of Stator Insulation by Dielectric Response ... · Hydro- or turbo-generator: ... (IR): ‘DC’ with quite HV, i.e. a form of ... Ramp test A little recent research interest,

Continuation

• Equipment for simultaneous measurement

• More comparison of DS and PD measurement of PD current

• Approximate removal of SG harmonics to leave PD harmonics,

using sub-inception sweep to determine parameters of SG

• Further investigation of frequency-dependence of PD in stator

insulation

• What is a good ‘index’ for PD and non-linear DS measurements?

For example, C′&C′′ ignores substantial and interesting currents.

• Some more thorough field tests on various machines.

71