    This is a presentation on DGA analysis

    using a ratio method of hot metal gases

    Will show results from four examples

    Three DGA ratios and one fluid quality

    This method is a proven tool in NHECPredictive Maintenance

    Gary B. Ell iott

    New Horizon ElectricNew Horizon ElectricNew Horizon Electric

  • 8/10/2019 DGA Analysis

    2/53

  • 8/10/2019 DGA Analysis

    3/53

    A New Way To F ind Regulator Problems

    Through Gas Ratios?

    Objectives:

    Establ ish a Pattern

    Recognize Potential Problems

    Establ ish Solid Gas Ratio Formulas

    Keep I t Simple As Possible

  • 8/10/2019 DGA Analysis

    4/53

  • 8/10/2019 DGA Analysis

    5/53

    Which Gases Should Be Evaluated?

    C CH

    H

    H

    H

    C

    H

    H

    H

    H

    C

    H

    H

    H

    C

    H

    H

    H

    C

    C C

    C

    C

    H HH H H

    HH HH

    H

    C CH H H HAcetylene

    Ethylene

    Methane

    Ethane

    Hydrogen

    HeatingHeating

    Arcing Corona

    Heating

  • 8/10/2019 DGA Analysis

    6/53

  • 8/10/2019 DGA Analysis

    7/53

    NHEC Gas Ratio Standards

    1-Ethane .5 to 1.0 of Methane

    2-Ethylene .5 to .75 of Acetylene 3-Ethylene .75 to 1.0 of Acetylene

    4-Ethane 1 to 1 or Greater of Methane

    5-Ethylene 1 to 1 or Greater of Acetylene

  • 8/10/2019 DGA Analysis

    8/53

    Regulator was last serviced 4-99 Regulator was in service

    Regulator seen normal duty Regulator load was about 75% normally

    Had no previous DGA or F luid Quali ty

    data

    Example #1

  • 8/10/2019 DGA Analysis

    9/53

    333 kva Regulator at Fairplay Sub

    TOA Software

    Targeted

    Regulator

  • 8/10/2019 DGA Analysis

    10/53

    DGA Report 5-25-2001

    TOA Software

    Ethylene 19224ppm

    Acetylene 7246ppm

    Ratio 2.65

  • 8/10/2019 DGA Analysis

    11/53

    DGA Report 10-29-2001

    TOA Software

    Ethylene 14143ppm

    Acetylene 5601ppm

    Ratio 2.52

  • 8/10/2019 DGA Analysis

    12/53

    DGA Report 12-11-2001

    TOA Software

    Ethylene 12792ppm

    Acetylene 5098ppm

    Ratio 2.50

  • 8/10/2019 DGA Analysis

    13/53

    F luid Quality Report

    TOA Software

    Color on 5-25-2001

  • 8/10/2019 DGA Analysis

    14/53

  • 8/10/2019 DGA Analysis

    15/53

  • 8/10/2019 DGA Analysis

    16/53

    Reversing Switch Assembly

    (Load Carrying)

  • 8/10/2019 DGA Analysis

    17/53

    Reversing Switch Stationary Contact

  • 8/10/2019 DGA Analysis

    18/53

    Stationary Contact

  • 8/10/2019 DGA Analysis

    19/53

    Reversing Switch Moveable Contact

  • 8/10/2019 DGA Analysis

    20/53

    Regulator fai lure was inevitable Regulator was last serviced 4-99

    Contacts were damaged due to not

    exercising the selector (reversing) switch

    Conclusion

  • 8/10/2019 DGA Analysis

    21/53

  • 8/10/2019 DGA Analysis

    22/53

    Regulator at McCormick Sub

    Targeted

    Regulator

  • 8/10/2019 DGA Analysis

    23/53

    DGA Report 4-23-2001

    TOA Software

    No indication of a

    problem

  • 8/10/2019 DGA Analysis

    24/53

    DGA Report 4-22-2002

    TOA Software

    No indication of a

    problem

  • 8/10/2019 DGA Analysis

    25/53

  • 8/10/2019 DGA Analysis

    26/53

    F luid Quality Report 2002

    Moistur e 45ppm

    IFT 13

  • 8/10/2019 DGA Analysis

    27/53

    Untanking The Regulator

  • 8/10/2019 DGA Analysis

    28/53

  • 8/10/2019 DGA Analysis

    29/53

    Rust Present

    Moisture

  • 8/10/2019 DGA Analysis

    30/53

  • 8/10/2019 DGA Analysis

    31/53

    333kva regulator currently in service Not scheduled for maintenance

    Example #3

  • 8/10/2019 DGA Analysis

    32/53

  • 8/10/2019 DGA Analysis

    33/53

  • 8/10/2019 DGA Analysis

    34/53

    DGA Report 5-09-2002

    Ethylene 10911ppm

    Acetylene 3432ppm

    Ratio 3.18

  • 8/10/2019 DGA Analysis

    35/53

    DGA Report 6-13-2002

    Ethylene 11059ppm

    Acetylene 3746ppm

    Ratio 2.95

  • 8/10/2019 DGA Analysis

    36/53

    F luid Quality Report 5-09-2002

    No indication of a

    problem

  • 8/10/2019 DGA Analysis

    37/53

  • 8/10/2019 DGA Analysis

    38/53

    Contact Lead Termination Point

  • 8/10/2019 DGA Analysis

    39/53

    Contact Lead Termination PointClose-Up

  • 8/10/2019 DGA Analysis

    40/53

  • 8/10/2019 DGA Analysis

    41/53

    Found contact wire lead missing fasteningnuts

    Failure was inevitable

    Only reason hadn t fai led is lack of

    frequency on that step

    Conclusion

  • 8/10/2019 DGA Analysis

    42/53

    333kva regulator currently in service Not scheduled for maintenance

    Regulator had been serviced in the field

    previously

    Regulator load was around 75% normally

    Had no previous DGA or F luid Quali tydata

    Example #4

  • 8/10/2019 DGA Analysis

    43/53

    Regulator at Westminster Sub

    Targeted

    Regulator

  • 8/10/2019 DGA Analysis

    44/53

    DGA Report

    Ethylene 203063ppm

    Acetylene 4390ppmRatio 46.26

  • 8/10/2019 DGA Analysis

    45/53

    F luid Quality Report

    No indication of a

    problem

  • 8/10/2019 DGA Analysis

    46/53

    Ratio Results Ethylene > Acetylene

  • 8/10/2019 DGA Analysis

    47/53

    Reversing Switch Assembly

  • 8/10/2019 DGA Analysis

    48/53

    Reversing Switch Assembly

    (Continued)

    S

  • 8/10/2019 DGA Analysis

    49/53

    Reversing Switch Assembly

    Moveable Contact

    R i S it h A bl

  • 8/10/2019 DGA Analysis

    50/53

    Reversing Switch Assembly

    Stationary Contacts

    N l S t f R i S it h

  • 8/10/2019 DGA Analysis

    51/53

    Normal Set of Reversing Switch

    Stationary and Moveable Contacts

  • 8/10/2019 DGA Analysis

    52/53

  • 8/10/2019 DGA Analysis

    53/53

    Questions ?