Upload
anonymous-hj273cm
View
256
Download
0
Embed Size (px)
Citation preview
8/8/2019 Designer’s Reference Handbook DEIF
1/37
DESIGNER’S REFERENCE HANDBOOK
• Product information
• Protections
• Functional descriptions
• Additional information
• Programming
Document no.: 41893400660A
SW version 3.53.0 or later
Advanced Protection Unit, APU 200
8/8/2019 Designer’s Reference Handbook DEIF
2/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 2 of 37
Table of contents
1. ABOUT THIS DOCUMENT .................................................................................................... 3
GENERAL PURPOSE ...................................................................................................................... 3
INTENDED USERS.......................................................................................................................... 3
CONTENTS/OVERALL STRUCTURE .................................................................................................. 3
2.
WARNINGS AND LEGAL INFORMATION ........................................................................... 4
LEGAL INFORMATION AND RESPONSIBILITY ..................................................................................... 4
ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 4
S AFETY ISSUES ............................................................................................................................ 4
DEFINITIONS ................................................................................................................................ 4
3. PROTECTIONS ...................................................................................................................... 5
M AINS PROTECTION PACKAGE ....................................................................................................... 5
LOSS OF MAINS PROTECTION PACKAGE ......................................................................................... 5
ADDITIONAL PROTECTIONS PACKAGE ............................................................................................ 6
4TH CURRENT TRANSFORMER INPUT .............................................................................................. 7
NEUTRAL LINE AND GROUND FAULT INVERSE OVERCURRENT .......................................................... 7
4.
SYNCHRONISATION........................................................................................................... 10
CLOSE BTB ............................................................................................................................... 10
OPEN BTB ................................................................................................................................. 10
OPEN/CLOSE FAIL ....................................................................................................................... 12
5.
DIGITAL INPUT.................................................................................................................... 13
INPUT FUNCTION SELECTION ....................................................................................................... 14
6.
ANALOGUE INPUT ............................................................................................................. 15
4-20 M A ..................................................................................................................................... 15
PT100 ....................................................................................................................................... 15
VDO INPUTS .............................................................................................................................. 15
DIGITAL ...................................................................................................................................... 20
WIRE FAIL DETECTION ................................................................................................................ 21
7. GENERAL SETUP ............................................................................................................... 22
NOMINAL SETTINGS .................................................................................................................... 22
T AP SETTINGS ............................................................................................................................ 23
F AN CONTROL ............................................................................................................................ 24
SUMMER/WINTER TIME ................................................................................................................ 27
COUNTERS ................................................................................................................................. 27
L ANGUAGE SELECTION................................................................................................................ 28
8. POWER MANAGEMENT ..................................................................................................... 29
LOAD MANAGEMENT ................................................................................................................... 29
COMMAND TIMERS (TIME-DEPENDENT START/STOP) ..................................................................... 29
9. ADDITIONAL FUNCTIONS .................................................................................................. 30
ALARM INHIBIT ............................................................................................................................ 30
ACCESS LOCK ............................................................................................................................ 31
F AIL CLASS ................................................................................................................................ 32
RELAY OUTPUTS ......................................................................................................................... 33
M-LOGIC .................................................................................................................................... 33
LVHV PHASE COMPARE VIEW ...................................................................................................... 36
USW COMMUNICATION ............................................................................................................... 37
TCP/IP ...................................................................................................................................... 37
8/8/2019 Designer’s Reference Handbook DEIF
3/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 3 of 37
1. About this document
This chapter includes general user information about this handbook concerning the general
purpose, the intended users and the overall contents and structure.
General purpose
This document is the Designer’s Reference Handbook for DEIF’s Advanced Protection Unit, the
APU 200. The document mainly includes functional descriptions, presentation of display unit, menu
structure, wiring and the procedure for parameter setup.
The general purpose of the Designer’s Reference Handbook is to provide useful overall information
about the functionality of the unit and its applications. This handbook also offers the user the
information needed in order to successfully set up the parameters needed in the user’s specific
application.
Intended users
The handbook is mainly intended for the person responsible for the unit parameter setup. In most
cases, this would be a panel builder designer. Naturally, other users might also find useful
information in the handbook.
Contents/overall structureThe Designer’s Reference Handbook and Installation instructions is divided into chapters and in
order to make the structure of the document simple and easy to use, each chapter will begin from
the top of a new page. The following will outline the contents of each of the chapters.
About this document
This chapter includes general information about this handbook as a document. It deals with the
general purpose and the intended users of the Designer’s Reference Handbook. Furthermore, it
outlines the overall contents and structure of the document.
Warnings and legal information
This chapter includes information about general legal issues and safety precautions relevant in the
handling of DEIF products. Furthermore, this chapter will introduce note and warning symbols,
which will be used throughout the handbook.
Please make sure to read this handbook before working with the controller
and the unit to be controlled. Failure to do this could result in human injury or
damage to the equipment.
8/8/2019 Designer’s Reference Handbook DEIF
4/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 4 of 37
2. Warnings and legal information
This chapter includes important information about general legal issues relevant in the handling of
DEIF products. Furthermore, some overall safety precautions will be introduced and
recommended. Finally, the highlighted notes and warnings, which will be used throughout this
handbook, are presented.
Legal information and responsibility
DEIF takes no responsibility for installation or operation of the device connected to the APU 200. If
there is any doubt about how to install or operate the device controlled by the unit, the company
responsible for the installation or the operation of the set must be contacted.
Electrostatic discharge awareness
Sufficient care must be taken to protect the terminals against static discharges during the
installation. Once the unit is installed and connected, these precautions are no longer necessary.
Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.
Definitions
Throughout this document, a number of notes and warnings will be presented. To ensure that
these are noticed, they will be highlighted in order to separate them from the general text.
Notes
Warnings
The notes provide general information which will be helpful for the reader to
bear in mind.
The warnings indicate a potentially dangerous situation which could result in
death, personal injury or damaged equipment, if certain guidelines are not
followed.
Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.
The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.
8/8/2019 Designer’s Reference Handbook DEIF
5/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 5 of 37
3. Protections
This chapter describes the standard DEIF options in the APU 200.
Mains protection package
DEIF Option A1 is a software option and therefore not related to any hardware apart from thestandard-installed hardware. The Option A1 is a mix of the below listed protections as follows:
- Vector jump
- df/dt (ROCOF)
- Time-dependent undervoltage
- Undervoltage and reactive power low
Protection ANSI no.
Vector jump 78
df/dt (ROCOF) 81
Time-dependent undervoltage, Ut < 27t
Undervoltage and reactive power low, UQ < 27Q
The option A1 relates to the parameters 1960, 1420-1430 and 1630-1700, 1970.
Loss of mains protection package
DEIF option A4 is a software option and therefore not related to any hardware apart from the
standard-installed hardware.
This protection prevents malfunctioning due to insufficient or unbalanced supply voltage. Theprotection is used when running in parallel.
Protection ANSI no.
Positive sequence voltage 47 U1, 27 pos
The option A4 relates to the parameter 1440.
Detailed information regarding this option can be found in DEIF standard
document for option A1: Mains protection package, document no: 4189340434.
Detailed information regarding this option can be found in DEIF standard
document for option A4: Loss of mains protection package, document no:
4189340435.
In combination, the protections cover the requirement for G59/2, such as vector
shift, ROCOF (rate of change of frequency), voltage imbalance protection 2 times
over/under voltage and 2 times over/under frequency protection levels.
The ANSI number refers to the IEEE standard: “Standard Electrical Power
System Device Function Numbers and Contact Designations” (IEEE std C37.2-
1996).
8/8/2019 Designer’s Reference Handbook DEIF
6/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 6 of 37
Additional Protections package
DEIF option C2 is a software option and therefore not related to any hardware apart from the
standard-installed hardware.
Protection ANSI no.
Negative sequence current 46
Negative sequence voltage 47
Zero sequence current 51I0
Zero sequence voltage 59U0
Power-dependent reactive power 40
Inverse time overcurrent 51
The option C2 relates to the parameters 1080-1090, 1540-1590 and 1740-1790.
Detailed information regarding this option can be found in DEIF standard
document for option C2: Generator add-on protection package, document no:
4189340437.
8/8/2019 Designer’s Reference Handbook DEIF
7/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 7 of 37
4th current transformer input
The 4th current transformer input (terminals 59-60) is used for earth current (ground fault)
measured in the transformer star point ground connection.
The function includes a 3rd
harmonics filtering of the signal. This is selected by activating the
alarm in setting 1730.
The setting of the CT is made in setting 6045 (primary) and 6046 (secondary).
Neutral line and ground fault inverse overcurrent
These are configurable inverse alarms, based on predefined or user-configurable curve shapes.Settings are found in parameter 1730 (G Ie>> Inverse).
Formula and settings used
The inverse time overcurrent is based on IEC 60255 part 151.
The function used is dependent time characteristic, and the formula used is:
k
t(G) = TMS +c
G
- 1GS
where
t(G) is the theoretical operating time constant value of G in seconds
k, c, α are the constants characterising the selected curve
G is the measured value of the characteristic quantity
GS is the setting value
TMS is the time multiplier setting
The constants k and c have a unit of seconds, α has no dimension.
α
There is no intentional delay on reset. The function will reset when G < 2 x G S.
8/8/2019 Designer’s Reference Handbook DEIF
8/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 8 of 37
Curve shapes
Time characteristic:
There is a choice between seven different curve shapes, of which six are predefined and one is
user-definable:
IEC Inverse
IEC Very Inverse
IEC Extremely Inverse
IEEE Moderately Inverse
IEEE Very Inverse
IEEE Extremely Inverse
Custom
Common settings for all types:
Setting Parameter no. Factory setting
value
Equals
Limit 1722/1732 30/10% 2 x GS
TMS 1723/1733 1.0 Time multiplier setting
In the APU 200, the value 2 x GS is called Limit.
8/8/2019 Designer’s Reference Handbook DEIF
9/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 9 of 37
The following constants apply to the predefined curves:
Curve type k c α
IEC Inverse 0.14 0 0.02
IEC Very Inverse 13.5 0 1
IEC Extremely Inverse 80 0 2
IEEE Moderately Inverse 0.515 0.1140 0.02
IEEE Very Inverse 19.61 0.491 2
IEEE Extremely Inverse 28.2 0.1217 2
For the custom curve, these constants can be defined by the user:
Setting Parameter no. Factory setting
value
Equals
k 1724/1734 0.140 s k
c 1725/1735 0.000 s c
α (a) 1726/1736 0.020 α
The curves are shown for TMS = 1.
For the actual setting ranges, please see the parameter list.
Standard curves
8/8/2019 Designer’s Reference Handbook DEIF
10/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 10 of 37
4. Synchronisation
This chapter describe closing and opening of the BTB and the alarms linked to this function
Close BTB
It is not possible to close (synchronise) the BTB if there is live voltage at both sides of the
transformer.
Close BTB LV, No voltage LV, Voltage HV, No voltage HV, Voltage
LV, No voltage - NA Possible Possible
LV, Voltage NA - Possible Not Possible
HV, No voltage Possible Possible - NA
HV, voltage Possible Not Possible NA -
Open BTB
Open BTB Q7 ON Q7 OFF Q5B ON O5B OFF
Q7 ON NA Not Possible Possible
Q7 OFF NA Possible
Q5B ON Not Possible Possible NA
O5B OFF Possible Possible NA
It is possible to request open/close BTB by:
Display
Via the front of the display, it is possible to activate BTB open/close command
M-Logic
8/8/2019 Designer’s Reference Handbook DEIF
11/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 11 of 37
Inputs
Possible to activate BTB open
Modbus (Option H2)
For additional information, please refer to the Modbus documentation for the
APU 200.
For additional information, please use the help function in the USW, this is
activated by [F1].
8/8/2019 Designer’s Reference Handbook DEIF
12/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 12 of 37
Open/close fail
It is possible to setup the alarm settings for open/close failure. This can be done via the display or
via the USW:
Display
USW
Double-click the requested parameter.
24 kV 50 Hz A1 B1 C12160 Q6 Open fail
2170 Q6 Close fail
2240 Sep synch relay
2300 Section P>
2420 BTB33 os fail
For additional information regarding how to setup the alarm, please use the help
function in the USW; this is activated by [F1].
8/8/2019 Designer’s Reference Handbook DEIF
13/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 13 of 37
5. Digital input
The unit has 10 configurable binary inputs, and they are all available and programmed via the
USW’s I/O settings
Functional description
1. Semi-auto
Changes the present running mode to semi-auto.
2. Auto
Changes the present running mode to auto.
2. Block
Changes the present running mode to block.
4. Access lock
Activating the access lock input deactivates the control display push-buttons. It will only be
possible to view measurements, alarms and the log.
5. Remote BTB ON
The BTB ON sequence will be initiated and the BTB will synchronise.
6. Remote BTB OFF
The BTB OFF sequence will be initiated, followed by a breaker opening.
7. BTB close inhibit
When this input is activated, the BTB cannot close.
8. Enable separate sync.
Activating this input will split the breaker close and BTB synchronisation functions into two
different relays. The BTB close function will remain on the relays dedicated for breaker control.
The synchronisation function will be moved to a configurable relay dependent on the options
configuration.
9. BTB spring loaded
The APU 200 will not send a close signal before this feedback is present.
10. Remote alarm acknowledge
Acknowledges all present alarms, and the alarm LED on the display stops flashing.
Input function Configurable Input type
1 Semi-auto Configurable Pulse
2 Auto Configurable Pulse
3 Block Configurable Constant
4 Access lock Configurable Constant
5 Remote BTB ON Configurable Pulse
6 Remote BTB OFF Configurable Pulse
7 BTB close inhibit Configurable Constant
8 Enable sep. sync. Configurable Constant
9 BTB spring loaded Configurable Constant
10 Remote alarm acknowledge Configurable Constant
When block mode is selected, the running mode cannot be changed by
activating the digital inputs.
8/8/2019 Designer’s Reference Handbook DEIF
14/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 14 of 37
Input function selection
Digital input alarms can be configured with a possibility to select when the alarms are to be
activated. The possible selections of the input function are normally open or normally closed.
The drawing below illustrates a digital input used as an alarm input.
1. Digital input alarm configured to NC, normally closed
This will initiate an alarm when the signal on the digital input disappears.
2. Digital input alarm configured to NO, normally open
This will initiate an alarm when the signal on the digital input appears.
The relay output function cannot be changed. This will always be a NO relay and
will close when the alarm occurs; alarm = CC (closed contact).
D i g. in
Com
R elay out
AGC 200
+ V DC
Alarm
input
8/8/2019 Designer’s Reference Handbook DEIF
15/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 15 of 37
6. Analogue input
The APU 200 unit has three multi-inputs (46, 47 and 48) which can be configured to be used as
the following input types:
• 4-20 mA
• Pt100
• VDO
• Digital
Two alarm levels are available for each input. The menu numbers of the alarm settings for each
multi-input are controlled by the configured input type as seen in the following table.
Input type Multi-input 46 Multi-input 47 Multi-input 48
4-20 mA 4120/4130 4250/4260 4380/4390
0-40V DC 4140/4150 4270/4280 4400/4410
Pt100 4160/4170 4290/4300 4420/4430
VDO 1 4180/4190 4310/4320 4440/4450
VDO 2 4200/4210 4330/4340 4460/4470
VDO 3 4220/4230 4350/4360 4480/4490
Digital 3400 3410 3420
4-20 mA
If one of the multi-inputs has been configured as 4-20 mA, the unit and range of the measured
value corresponding to 4-20 mA can be changed in the PC utility software in order to get the
correct reading in the display.
Pt100
This input type can be used for heat sensor, e.g. cooling oil temperature. The unit of the
measured value can be changed from Celsius to Fahrenheit in the PC utility software in order to
get the desired reading in the display.
VDO inputs
The unit can contain up to three VDO inputs. The inputs have different functions as the
hardware design allows for several VDO types.
These various types of VDO inputs are available for all multi-inputs:
For each type of VDO input, it is possible to select between different characteristics including a
configurable.
The function of the multi-inputs can only be configured in the PC utility software.
Only 1 alarm level is available for the digital input type.
8/8/2019 Designer’s Reference Handbook DEIF
16/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 16 of 37
VDO 1
This VDO input is used to measure the pressure.
VDO sensor type
Pressure Type 1 Type 2 Type configurable
Bar psi Ω Ω Ω
0 0 10.0 10.0
0.5 7 27.2
1.0 15 44.9 31.3
1.5 22 62.9
2.0 29 81.0 51.5
2.5 36 99.2
3.0 44 117.1 71.0
3.5 51 134.7
4.0 58 151.9 89.6
4.5 65 168.3
5.0 73 184.0 107.3
6.0 87 124.3
7.0 102 140.4
8.0 116 155.7
9.0 131 170.2
10.0 145 184.0
The configurable type is configurable with eight points in the range 0-2500 Ω.
The resistance as well as the pressure can be adjusted.
If the VDO input is used as a level switch, then please be aware that no voltage
must be connected to the input. If any voltage is applied to the VDO input, it will
be damaged. Please refer to the Application Notes for further wiring information.
8/8/2019 Designer’s Reference Handbook DEIF
17/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 17 of 37
VDO 2
This VDO input is used to measure temperature.
VDO sensor
type
Temperature Type 1 Type 2 Type 3 Type 4
°C °F Ω Ω Ω Ω
40 104 291.5 480.7 69.3
50 122 197.3 323.6
60 140 134.0 222.5 36.0
70 158 97.1 157.1
80 176 70.1 113.2 19.8
90 194 51.2 83.2
100 212 38.5 62.4 11.7
110 230 29.1 47.6
120 248 22.4 36.8 7.4
130 266 28.9
140 284 22.8
150 302 18.2
VDO 3
This VDO input is used for the level sensor.
VDO sensor type
Type 1Value Resistance
0% 78.8 Ω
100% 1.6 Ω
VDO sensor type
Type 2
Value Resistance
0% 3 Ω
100% 180 Ω
The configurable type is configurable with eight points in the range 0-2500 Ω.
The temperature as well as the resistance can be adjusted.
If the VDO input is used as a level switch, then please be aware that no voltage
must be connected to the input. If any voltage is applied to the VDO input, it will
be damaged. Please refer to the Application Notes for further wiring information.
If the VDO input is used as a level switch, then please be aware that no voltage
must be connected to the input. If any voltage is applied to the VDO input, it willbe damaged. Please refer to the Application Notes for further wiring information.
8/8/2019 Designer’s Reference Handbook DEIF
18/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 18 of 37
VDO configurable
VDO sensor type
Value Type configurable
bar, °C or % Resistance
0 0
10 SP 1
20 SP 2
30 SP 3
40 SP 4
50 SP 5
60 SP 6
70 SP 7
80 SP 8
The configurable type is configurable with eight points in the range 0-2500 Ω.
The value as well as the resistance can be adjusted.
Setpoints
Setpoint 1Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
Setpoint 6
Setpoint 7
87654321
Value
(bar, °C or %)
Resistance
(Ω)
Setpoint 8
8/8/2019 Designer’s Reference Handbook DEIF
19/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 19 of 37
Configuration
The eight curve settings for the configurable VDO inputs cannot be changed in the display, only
in the PC utility software. The alarm settings can be changed both in the display and in the PC
utility software. In the PC utility software, the configurable inputs are adjusted in this dialogue
box:
Adjust the resistance of the VDO sensor at the specific measuring value. In the example above,the adjustment is 10 Ω at 0.0.
For additional information regarding how to setup the VDO, please use the help
function in the USW; this is activated by [F1].
8/8/2019 Designer’s Reference Handbook DEIF
20/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 20 of 37
Digital
If the multi-inputs are configured to binary “Digital”, they become available as a configurable
input.
When the parameter has been uploaded, it is possible to configure the input.
When the multi-input has been changed to binary, remember to write and upload
the parameter.
For additional information regarding how to setup the digital input, please use
the help function in the USW; this is activated by [F1].
8/8/2019 Designer’s Reference Handbook DEIF
21/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 21 of 37
Wire fail detection
If it is necessary to supervise the sensors/wires connected to the multi-inputs, then it is possible
to enable the wire break function for each input. If the measured value on the input is outside the
normal dynamic area of the input, it will be detected as if the wire has made a short-circuit or a
break. An alarm with a configurable fail class will be activated.
Input Wire failure area Normal range Wire failure area
4-20 mA < 3 mA 4-20 mA > 21 mA
VDO Oil, type 1 < 10.0 ohm - > 184.0 ohm
VDO Oil, type 2 < 10.0 ohm - > 184.0 ohm
VDO Temp, type 1 < 22.4 ohm - > 291.5 ohm
VDO Temp, type 2 < 18.3 ohm - > 480.7 ohm
VDO Temp, type 3 < 7.4 ohm - > 69.3 ohm
VDO Level, type 1 < 1.6 ohm - > 78.8 ohm
VDO Level, type 2 < 3.0 ohm - > 180.0 ohm
VDO configurable < lowest resistance - > highest resistance
Pt100 < 82.3 ohm - > 194.1 ohm
Level switch Only active if the switch is open
Principle
The illustration below shows that when the wire of the input breaks, the measured value will drop
to zero. Then the alarm will occur.
Intertrip wirebreak (menu 6270)
The alarm will occur when the Intertrip is not activated and the input is de-energised.
Wire failure
Wire failure
Wire break
Lower failure
limit
Upper failure
limit
Input signal(mA, °C, b, %)
t
8/8/2019 Designer’s Reference Handbook DEIF
22/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 22 of 37
7. General setup
Nominal settings
The nominal settings can be changed to match different voltages and frequencies. The APU 200has four sets of nominal values, and they are adjusted in menus 6000 to 6030 (nominal settings
1 to 4).
Activation
The switching between the nominal setpoint can be done in four ways: digital input (M-Logic),
AOP or menu 6006.
Digital input
M-Logic is used when a digital input is needed for switching between the four sets of nominal
settings. Select the required input among the input events, and select the nominal settings in the
outputs.
Example:
Event A Event B Event C Output
Dig. input no. 77 or Not used or Not used Set nom. parameter settings 1
Not Dig. input no. 77 or Not used or Not used Set nom. parameter settings 2
AOP
M-Logic is used when the AOP is used for switching between the four sets of nominal settings.
Select the required AOP push-button among the input events, and select the nominal settings inthe outputs.
Example:
Event A Event B Event C Output
Button 07 or Not used or Not used Set nom. parameter settings 1
Button 08 or Not used or Not used Set nom. parameter settings 2
Menu settings
In menu 6005, the switching is made between settings 1 to 4 simply by choosing the desired
nominal setting.
Please refer to the “Help” file [F1] in the PC utility software for details.
Please refer to the “Help” file [F1] in the PC utility software for details.
24kV 50Hz A1 B2 C1
6005 Enable nom. set
Nom. Setting 1
Nom. Setting 2
Nom. Setting 3
Nom. Setting 4
8/8/2019 Designer’s Reference Handbook DEIF
23/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 23 of 37
Tap settings
In order to setup the APU correctly, it is necessary to programme the actual settings of the
transformers tap. This is done in parameter 6007.
Display USW
The following tap settings relate to the programmed via the USW
Tap setting Output Tap setting Output
0 Tap setting not used 26 24 kV 50 Hz A2 B2 C1
1 14 kV 50 Hz A1 B2 C1 27 24 kV 50 Hz A3 B2 C1
2 14 kV 50 Hz A2 B2 C1 28 24 kV 50 Hz A4 B2 C1
3 14 kV 50 Hz A3 B2 C1 29 24 kV 50 Hz A1 B1 C1
4 14 kV 50 Hz A1 B1 C1 30 24 kV 50 Hz A2 B1 C1
5 14 kV 50 Hz A2 B1 C1 31 24 kV 50 Hz A3 B2 C1
6 14 kV 50 Hz A3 B1 C1 32 24 kV 50 Hz A1 B2 C2
7 14 kV 50 Hz A1 B2 C2 33 24 kV 50 Hz A2 B2 C28 14 kV 50 Hz A2 B2 C2 34 24 kV 50 Hz A3 B2 C2
9 14 kV 50 Hz A3 B2 C2 35 24 kV 50 Hz A1 B1 C2
10 14 kV 50 Hz A1 B1 C2 36 24 kV 50 Hz A2 B1 C2
11 14 kV 50 Hz A2 B1 C2 37 24 kV 50 Hz A3 B1 C2
12 14 kV 50 Hz A3 B1 C2 38 24 kV 60 Hz A1 B2 C1
13 14 kV 60 Hz A1 B2 C1 39 24 kV 60 Hz A2 B2 C1
14 14 kV 60 Hz A2 B2 C1 40 24 kV 60 Hz A3 B2 C1
15 14 kV 60 Hz A3 B2 C1 41 24 kV 60 Hz A4 B2 C1
16 14 kV 60 Hz A1 B1 C1 42 24 kV 60 Hz A1 B1 C117 14 kV 60 Hz A2 B1 C1 43 24 kV 60 Hz A2 B1 C1
18 14 kV 60 Hz A3 B1 C1 44 24 kV 60 Hz A3 B2 C1
19 14 kV 60 Hz A1 B2 C2 45 24 kV 60 Hz A1 B2 C2
20 14 kV 60 Hz A2 B2 C2 46 24 kV 60 Hz A2 B2 C2
21 14 kV 60 Hz A3 B2 C2 47 24 kV 60 Hz A3 B2 C2
22 14 kV 60 Hz A1 B1 C2 48 24 kV 60 Hz A1 B1 C2
23 14 kV 60 Hz A2 B1 C2 49 24 kV 60 Hz A2 B1 C2
24 14 kV 60 Hz A3 B1 C2 50 24 kV 60 Hz A3 B1 C2
25 24 kV 50 Hz A1 B2 C1
24 kV 50 Hz A1 B1 C16000 Nom. Settings 1
Current: 365 A
Voltage: 6240 V
Set: nom. Settings 1
Current E/N/M 100 A
Tap: 24kV 50Hz A1 B1 C1
8/8/2019 Designer’s Reference Handbook DEIF
24/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 24 of 37
Fan Control
Four configurable fans can be setup in the APU. The setup of the fans is done in menus 6562 to
6620. It is possible to use the display to setup the fans but it is recommended to setup the fans
via the USW, because then it is possible to see all settings.
Fan Input
Fan temperature input is setup in parameter 6561. This input can be selected between multi-
input 46, 47 or 48.
Fan priority update
At parameter 6562, the priority update rate is selected.
Fan control
Stop/start of the fans is setup in parameter 6563 to 6574.
The following start/stop curve will be generated if a bow setting is used.
If fan priority update is set to 0 hours, the sequence will be fixed to.:
Fan A, Fan B, Fan C and Fan D.
It is recommended to use the USW to setup the fans, because then it is possible
at the same time to overview all four settings.
8/8/2019 Designer’s Reference Handbook DEIF
25/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 25 of 37
Fan Output
At parameter 6581 to 6584, the output for fan A to D is selected. If two fans are requested to be
started at the same time, it is possible to add a start delay between the two fans; this is done in
parameter 6586.
Fan A to D Failure
It is possible to activate an alarm if the fan output is not energised. At parameter 6590 to 6620,
the fan failure is setup.
Fan running hour
The running hours is controlled by M-Logic, and each fan output needs to be programmed in
order to have correct running hour values.
The running hour can reset by entering parameter 6585 and select the fan output to be reset.
Please note that it is only possible to reset the value, not add new values.
8/8/2019 Designer’s Reference Handbook DEIF
26/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 26 of 37
Service timers The unit is able to monitor the maintenance intervals. Two service timers are available to cover
different intervals.
The service timers can be setup:
via the display or via the USW
The function is based on energised hours. When the adjusted time expires, the unit will display
an alarm.
The energised hours is counting when the energised feedback is present.
Setpoints available in menus 6110 and 6170:
Enable: Enable/disable the alarm function.
Energised hours: The number of energised hours to activate the alarm.
Day: The number of days to activate the alarm – if the hours are not reached
before this number of days, the alarm will be raised.
Fail class: The fail class of the alarm.
Output A: Relay to be activated when the alarm is raised.
Reset: Enabling this will reset the service timer to zero. This has to be done
when the alarm is activated.
24 kV 50 Hz A1 B1 C1
SETUP MENU
6110 Service timer 1
6120 Service timer 2
6130 Alarm horn
6270 Intertrip Wirebreak
The service timer is only counting when voltage is detected at the LV side of the
transformer.
8/8/2019 Designer’s Reference Handbook DEIF
27/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 27 of 37
Summer/winter time
This function is used to make the APU 200 unit adjust the clock in the unit automatically
according to summer and winter time. The function is enabled in menu 6490. This can be done:
via the display or via the USW
Counters
Counters for various values are included, and some of these can be adjusted if necessary, for
instance if the unit is installed on an existing system or a new circuit breaker has been installed.
The table shows the adjustable values and their function in menu 6100:
Description Function Comment6101 Q6 operations Offset adjustment of the number of
breaker operations.
Counting at each Q6 close
command.
6102 kWh reset Resets the kWh counter. Automatically resets to OFF
after the reset. The reset
function cannot be left active.
The function only supports the European rules.
24 kV 50 Hz A1 B1 C1
6490 Summer/Winter time
OFF
ON .
8/8/2019 Designer’s Reference Handbook DEIF
28/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 28 of 37
Language selection
The unit has the possibility to display different languages. It is delivered with one master
language which is English. This is the default language, and it cannot be changed. In addition to
the master language, 11 different languages can be configured. This is done via the PC utility
software.
The languages are selected in the system setup menu 6080. The language can be changed
when connected to the PC utility software. It is not possible to make language configuration from
the display, but the already configured languages can be selected.
After selecting a language, the unit aux. power must be cycled before the
selection takes effect.
24kV 50Hz A1 B2 C1
6081 Language
Language Left
Language Right
Language 3
Language 4
Language 5
8/8/2019 Designer’s Reference Handbook DEIF
29/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 29 of 37
8. Power Management
In the following chapter, the power management functions of the APU 200 are listed.
Power management functions:
• Load management
• Command timers
• CAN flags
Load management
The function is used to activate a relay when a specific amount of power is available. Each APU
200 has five levels which are adjusted in menus 8220-8260:
• Available power 1
• Available power 2
• Available power 3• Available power 4
• Available power 5
These setpoints can activate a relay when the specific amount of available power is reached.
The relay output can be used to connect load groups when sufficient power is available. The
relays will activate when the available power is higher than the setpoint, but be aware that when
the load groups are being connected, the available power will decrease and the relay(s)
deactivate again if the available power is below the setpoint. So it is necessary to make an
external holding circuit.
The function is not depending on the running modes. The relays will activate in all modes
including block. To avoid activation, e.g. when the APU is blocked, the inhibit function should beused.
Command timers (time-dependent start/stop)
The purpose of the time-dependent start/stop function is to be able to start and stop functions
automatically at specific times each weekday or certain weekdays.
Up to eight command timers can be used for either start or stop functions. The settings are set
up through the PC utility software. Each command can be set for the following time periods:
• Individual days (MO, TU, WE, TH, FR, SA, SU)
• MO, TU, WE, TH
• MO, TU, WE, TH, FR
•
MO, TU, WE, TH, FR, SA, SU• SA, SU
The command timers are to be used in M-Logic as events to set the command (start/stop).
It is necessary to use the PC utility software when setting up the time-dependent
start/stop function.
The time-dependent start and stop commands are pulses that are not sent until
the moment the adjusted time is reached.
8/8/2019 Designer’s Reference Handbook DEIF
30/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 30 of 37
9. Additional functions
This chapter includes functional descriptions of functions. Tables, diagrams and single-line
illustrations will be used in order to simplify the information.
Alarm inhibit
In order to select when the alarms are to be active, a configurable inhibit setting for every alarm
has been made. The inhibit functionality is only available via the PC utility software. For every
alarm, there is a drop-down window where it is possible to select which signals that have to be
present in order to inhibit the alarm.
Selections for alarm inhibit:
Function Description
Inhibit 1 M-Logic outputs:
Conditions are
programmed in M-Logic
Inhibit 2
Inhibit 3
BTB ON The bus breaker is closed
BTB OFF The bus breaker is open
BA voltage > 30% Bus A voltage is above
30% of nominal
BA voltage < 30% Bus A voltage is below
30% of nominal
Inhibit of the alarm is active as long as one of the selected inhibit functions is active.
In this example, inhibit is set to BTB ON . Here, the alarm will be active when the BTB is not
closed. When the BTB has been synchronised, the alarm will be disabled again.
8/8/2019 Designer’s Reference Handbook DEIF
31/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 31 of 37
Access lock
The purpose of access lock is to deny the operator the possibility of configuring the unit
parameters and changing the running modes.
The input to be used for the access lock function is defined in the PC utility software (USW) I/O
settings, please use the application help [F1] in the USW for additional information of how to
programme the device.
The following example is digital input 86 (terminal 86) used for access lock
Access lock will typically be activated from a key switch installed behind the door of the
switchboard cabinet.
Button Button status Comment
Active It is possible to read all alarms, but it is not possible to
acknowledge any of them
Active The horn can be silenced
Not active
Not active
Active Reading of all values is possible
Active The log can be read
Active System setup can be entered, but no changes can be
made
Active The tools can be read, but no commands can be sent
LEFT
Active
UP Active
Not active If the access lock is activated when the view menu
system is displayed, the button is not active
DOWN Active
ESC
Active
RIGHT
Active
8/8/2019 Designer’s Reference Handbook DEIF
32/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 32 of 37
The following digital input functions are affected when access lock is activated:
Input name Input status
Semi-auto Not active
Auto Not active
Block Not active
Remote BTB ON Not activeRemote BTB OFF Not active
Fail class
All activated alarms must be configured with a fail class. The fail classes define the category of
the alarms and the subsequent alarm action.
Three different fail classes can be used. The tables below illustrate the action of each fail class
The table illustrates the action of the fail classes. If, for instance, an alarm has been configured
with the “Trip BTB” fail class, the following actions occur:
• The alarm horn relay will activate.
•
The alarm will be displayed in the alarm info screen.• The BTB will open instantly.
Fail class configuration
The fail class can be selected for each alarm function either via the display or via the USW. To
change the fail class via the USW, the alarm function to be configured must be selected. Select
the desired fail class in the fail class scroll-down menu.
Display USW
Action
Fail class
Alarm
horn
relay
Alarm
display
Trip of
BTB
Block for
closing
1 Block X X x
2 Warning X X
3 Trip BTB X X X
In addition to the actions defined by the fail classes, it is possible to activate
one or two relay outputs if additional relays are available in the unit.
AOP buttons are not locked when access lock is activated.
24 kV 50 Hz A1 B1 C1
1006 HV -P> 1
Block
Warning
Trip BTB .
8/8/2019 Designer’s Reference Handbook DEIF
33/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 33 of 37
Relay outputs
The unit has 12 configurable relay outputs, and they are all available and programmed via the
USW’s I/O settings.
Relay Output function Configurable
16 Not used
HC 1 acknowledge
HC 2 acknowledge
Trip NEL 1
Trip NEL 2
Trip NEL 3
Status OK
Horn
Configurable
18 Configurable
20 Configurable
23 Configurable
26 Configurable
28 Configurable
30 Configurable
32 Configurable
34 Configurable
36 Configurable
39 Configurable
43 Configurable
M-Logic
M-Logic functionality is included in the unit and is not an option-dependent function. However,
selecting additional options can increase the functionality.
M-Logic is used to execute different commands at predefined conditions. M-Logic is not a PLC
but substitutes one if only very simple commands are needed.
M-Logic is a simple tool based on logic events. One or more input conditions are defined, and at
the activation of those inputs, the defined output will occur. A great variety of inputs can be
selected, such as digital inputs, alarm conditions and running conditions. A variety of the outputs
can also be selected, such as relay outputs, change of modes and change of running modes.
The main purpose of M-Logic is to give the operator/designer more flexible possibilities of
operating the system.
The M-Logic is part of the PC utility software 3, and as such it can only be
configured in the PC utility software and not via the display.
Please refer to the “Help” function (F1) in the PC utility software for a full
description of this configuration tool.
Please refer to DEIF standard application note: “M-Logic” for further functional
details.
8/8/2019 Designer’s Reference Handbook DEIF
34/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 34 of 37
Configurable alarm LEDs
The four LEDs on the left side of the display can be controlled via M-Logic. For each LED, there
is a choice between three colours (red, green and yellow) with or without blinking.
Example of Alarms LED configuration
It is possible to programme the Alarm LEDs, to indicate highest phase current at any alarm.
Start by programming the event A to un-acknowledge alarm, then programme event B to look athighest phase (L1, L2 or L3) current at any alarm.
Next step: Alarm LED to be active (LED 1, 2, 3 or 4), also which colour and effect this LED must
have.
The following programming will activate (steady red) Alarm LED 1, whenever an
un-acknowledge alarm is present, and the current was highest in L1 when the
alarm was activated.
8/8/2019 Designer’s Reference Handbook DEIF
35/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 35 of 37
Templates
For each LED, there is a text box, where the indication of the function can be written. This must
be done on a piece of stiff paper or a plastic transparent, as the texts are to be sided into a slot
at the top of the APU 200 unit.
The slide-in paper/transparent template looks like this:
The above template is scale 1:1 when printing on A4 paper size.
8/8/2019 Designer’s Reference Handbook DEIF
36/37
APU 200 Designer’s Reference Handbook
DEIF A/S Page 36 of 37
LvHv Phase compare view
At view 14, it is possible to see the phase rotation
This can be useful to help troubleshoot or when commissioning the application.
View Commend
LV - - - - - - HV - - - - - - No voltage is detected
LV HV HV has wrong phase rotation
LV HV LV has wrong phase rotation
LV HV LV and HV have wrong phase rotation
LV HV OK, safe to close the BTB
24 kV 50 Hz A1 B1 C1Q6 Operations 1391
U – Supply 24.5 V
LV ------- HV -------
Energy total
Run absolut 14/20
Take precautions that it is safe to close the breaker. Failure to do this may
cause personal injury or death.
8/8/2019 Designer’s Reference Handbook DEIF
37/37
APU 200 Designer’s Reference Handbook
USW communication
It is possible to communicate with the unit via the PC utility software. The purpose is to be able
to remote-monitor and control the protection application.
Application settings
Please refer to the PC utility software help file [F1].
Safety
If communication fails, the unit will operate according to the received data. If e.g. only half of the
parameter file has been downloaded when the communication is interrupted, the unit will use
this actual data.
TCP/IP
DEIF option N is an Ethernet hardware option offering a number of features (hereafter referred
to as the option N). The hardware needed for the option N is placed with an RJ45 connector on
the left side of the unit, seen from the rear.
The option N is delivered through the Ethernet port, and we recommend using a twisted pair
category 5 cable (CAT5 as defined in ANSI/TIA/EIA-568-A) for connection of the option N to the
network.
The option N port automatically detects the cable type, so both twisted and straight cables can
be used.
DEIF A/S reserves the right to change any of the above.
It is possible to remote-control from the PC utility software if a TCP/IP router isused. Take precautions that it is safe to remote-operate the system, to avoid
personal injury or death.
Detailed information regarding this option can be found in DEIF standard
document for option N: Modbus TCP/IP, document no: 4189340612.