Designer’s Reference Handbook DEIF

Embed Size (px)

Citation preview

  • 8/8/2019 Designer’s Reference Handbook DEIF

    1/37

    DESIGNER’S REFERENCE HANDBOOK

    •  Product information

    •  Protections

    •  Functional descriptions

    •  Additional information

    •  Programming

    Document no.: 41893400660A

    SW version 3.53.0 or later

    Advanced Protection Unit, APU 200

  • 8/8/2019 Designer’s Reference Handbook DEIF

    2/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 2 of 37

    Table of contents

    1.  ABOUT THIS DOCUMENT .................................................................................................... 3 

    GENERAL PURPOSE ...................................................................................................................... 3 

    INTENDED USERS.......................................................................................................................... 3 

    CONTENTS/OVERALL STRUCTURE .................................................................................................. 3 

    2. 

    WARNINGS AND LEGAL INFORMATION ........................................................................... 4 

    LEGAL INFORMATION AND RESPONSIBILITY ..................................................................................... 4 

    ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 4 

    S AFETY ISSUES ............................................................................................................................ 4 

    DEFINITIONS ................................................................................................................................ 4 

    3.  PROTECTIONS ...................................................................................................................... 5 

    M AINS PROTECTION PACKAGE ....................................................................................................... 5 

    LOSS OF MAINS PROTECTION PACKAGE ......................................................................................... 5 

     ADDITIONAL PROTECTIONS PACKAGE ............................................................................................ 6 

    4TH CURRENT TRANSFORMER INPUT .............................................................................................. 7 

    NEUTRAL LINE AND GROUND FAULT INVERSE OVERCURRENT .......................................................... 7 

    4. 

    SYNCHRONISATION........................................................................................................... 10 

    CLOSE BTB ............................................................................................................................... 10 

    OPEN BTB ................................................................................................................................. 10 

    OPEN/CLOSE FAIL ....................................................................................................................... 12 

    5. 

    DIGITAL INPUT.................................................................................................................... 13 

    INPUT FUNCTION SELECTION ....................................................................................................... 14 

    6. 

    ANALOGUE INPUT ............................................................................................................. 15 

    4-20 M A ..................................................................................................................................... 15 

    PT100 ....................................................................................................................................... 15 

    VDO INPUTS .............................................................................................................................. 15 

    DIGITAL ...................................................................................................................................... 20 

    WIRE FAIL DETECTION ................................................................................................................ 21 

    7.  GENERAL SETUP ............................................................................................................... 22 

    NOMINAL SETTINGS .................................................................................................................... 22 

    T AP SETTINGS ............................................................................................................................ 23 

    F AN CONTROL ............................................................................................................................ 24 

    SUMMER/WINTER TIME ................................................................................................................ 27 

    COUNTERS ................................................................................................................................. 27 

    L ANGUAGE SELECTION................................................................................................................ 28 

    8.  POWER MANAGEMENT ..................................................................................................... 29 

    LOAD MANAGEMENT ................................................................................................................... 29 

    COMMAND TIMERS (TIME-DEPENDENT START/STOP) ..................................................................... 29 

    9.  ADDITIONAL FUNCTIONS .................................................................................................. 30 

     ALARM INHIBIT ............................................................................................................................ 30 

     ACCESS LOCK ............................................................................................................................ 31 

    F AIL CLASS ................................................................................................................................ 32 

    RELAY OUTPUTS ......................................................................................................................... 33 

    M-LOGIC .................................................................................................................................... 33 

    LVHV PHASE COMPARE VIEW ...................................................................................................... 36 

    USW COMMUNICATION ............................................................................................................... 37 

    TCP/IP ...................................................................................................................................... 37 

  • 8/8/2019 Designer’s Reference Handbook DEIF

    3/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 3 of 37

    1. About this document

    This chapter includes general user information about this handbook concerning the general

    purpose, the intended users and the overall contents and structure.

    General purpose

    This document is the Designer’s Reference Handbook for DEIF’s Advanced Protection Unit, the

     APU 200. The document mainly includes functional descriptions, presentation of display unit, menu

    structure, wiring and the procedure for parameter setup.

    The general purpose of the Designer’s Reference Handbook is to provide useful overall information

    about the functionality of the unit and its applications. This handbook also offers the user the

    information needed in order to successfully set up the parameters needed in the user’s specific

    application.

    Intended users

    The handbook is mainly intended for the person responsible for the unit parameter setup. In most

    cases, this would be a panel builder designer. Naturally, other users might also find useful

    information in the handbook.

    Contents/overall structureThe Designer’s Reference Handbook and Installation instructions is divided into chapters and in

    order to make the structure of the document simple and easy to use, each chapter will begin from

    the top of a new page. The following will outline the contents of each of the chapters.

    About this document

    This chapter includes general information about this handbook as a document. It deals with the

    general purpose and the intended users of the Designer’s Reference Handbook. Furthermore, it

    outlines the overall contents and structure of the document.

    Warnings and legal information

    This chapter includes information about general legal issues and safety precautions relevant in the

    handling of DEIF products. Furthermore, this chapter will introduce note and warning symbols,

    which will be used throughout the handbook.

    Please make sure to read this handbook before working with the controller

    and the unit to be controlled. Failure to do this could result in human injury or

    damage to the equipment. 

  • 8/8/2019 Designer’s Reference Handbook DEIF

    4/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 4 of 37

    2. Warnings and legal information

    This chapter includes important information about general legal issues relevant in the handling of

    DEIF products. Furthermore, some overall safety precautions will be introduced and

    recommended. Finally, the highlighted notes and warnings, which will be used throughout this

    handbook, are presented.

    Legal information and responsibility

    DEIF takes no responsibility for installation or operation of the device connected to the APU 200. If

    there is any doubt about how to install or operate the device controlled by the unit, the company

    responsible for the installation or the operation of the set must be contacted.

    Electrostatic discharge awareness

    Sufficient care must be taken to protect the terminals against static discharges during the

    installation. Once the unit is installed and connected, these precautions are no longer necessary.

    Safety issues

    Installing the unit implies work with dangerous currents and voltages. Therefore, the installation

    should only be carried out by authorised personnel who understand the risks involved in working

    with live electrical equipment.

    Definitions

    Throughout this document, a number of notes and warnings will be presented. To ensure that

    these are noticed, they will be highlighted in order to separate them from the general text.

    Notes

    Warnings

    The notes provide general information which will be helpful for the reader to

    bear in mind.

    The warnings indicate a potentially dangerous situation which could result in

    death, personal injury or damaged equipment, if certain guidelines are not

    followed.

    Be aware of the hazardous live currents and voltages. Do not touch any AC

    measurement inputs as this could lead to injury or death.

    The units are not to be opened by unauthorised personnel. If opened anyway, the

    warranty will be lost.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    5/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 5 of 37

    3. Protections

    This chapter describes the standard DEIF options in the APU 200.

    Mains protection package

    DEIF Option A1 is a software option and therefore not related to any hardware apart from thestandard-installed hardware. The Option A1 is a mix of the below listed protections as follows:

    -  Vector jump

    -  df/dt (ROCOF)

    -  Time-dependent undervoltage

    -  Undervoltage and reactive power low

    Protection ANSI no.

    Vector jump 78

    df/dt (ROCOF) 81

    Time-dependent undervoltage, Ut < 27t

    Undervoltage and reactive power low, UQ < 27Q

    The option A1 relates to the parameters 1960, 1420-1430 and 1630-1700, 1970.

    Loss of mains protection package

    DEIF option A4 is a software option and therefore not related to any hardware apart from the

    standard-installed hardware.

    This protection prevents malfunctioning due to insufficient or unbalanced supply voltage. Theprotection is used when running in parallel.

    Protection ANSI no.

    Positive sequence voltage 47 U1, 27 pos

    The option A4 relates to the parameter 1440.

    Detailed information regarding this option can be found in DEIF standard

    document for option A1: Mains protection package, document no: 4189340434.

    Detailed information regarding this option can be found in DEIF standard

    document for option A4: Loss of mains protection package, document no:

    4189340435.

    In combination, the protections cover the requirement for G59/2, such as vector

    shift, ROCOF (rate of change of frequency), voltage imbalance protection 2 times

    over/under voltage and 2 times over/under frequency protection levels.

    The ANSI number refers to the IEEE standard: “Standard Electrical Power

    System Device Function Numbers and Contact Designations” (IEEE std C37.2-

    1996).

  • 8/8/2019 Designer’s Reference Handbook DEIF

    6/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 6 of 37

    Additional Protections package

    DEIF option C2 is a software option and therefore not related to any hardware apart from the

    standard-installed hardware.

    Protection ANSI no.

    Negative sequence current 46

    Negative sequence voltage 47

    Zero sequence current 51I0 

    Zero sequence voltage 59U0 

    Power-dependent reactive power 40

    Inverse time overcurrent 51

    The option C2 relates to the parameters 1080-1090, 1540-1590 and 1740-1790.

    Detailed information regarding this option can be found in DEIF standard

    document for option C2: Generator add-on protection package, document no:

    4189340437.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    7/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 7 of 37

    4th current transformer input

    The 4th  current transformer input (terminals 59-60) is used for earth current (ground fault)

    measured in the transformer star point ground connection.

    The function includes a 3rd

     harmonics filtering of the signal. This is selected by activating the

    alarm in setting 1730.

    The setting of the CT is made in setting 6045 (primary) and 6046 (secondary).

    Neutral line and ground fault inverse overcurrent

    These are configurable inverse alarms, based on predefined or user-configurable curve shapes.Settings are found in parameter 1730 (G Ie>> Inverse).

    Formula and settings used

    The inverse time overcurrent is based on IEC 60255 part 151.

    The function used is dependent time characteristic, and the formula used is:

    k

    t(G) = TMS +c

    G

    - 1GS 

    where

    t(G) is the theoretical operating time constant value of G in seconds

    k, c, α  are the constants characterising the selected curve

    G is the measured value of the characteristic quantity

    GS  is the setting value

    TMS is the time multiplier setting

    The constants k  and c  have a unit of seconds, α has no dimension.

    α 

    There is no intentional delay on reset. The function will reset when G < 2 x G S.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    8/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 8 of 37

    Curve shapes

    Time characteristic:

    There is a choice between seven different curve shapes, of which six are predefined and one is

    user-definable:

    IEC Inverse

    IEC Very Inverse

    IEC Extremely Inverse

    IEEE Moderately Inverse

    IEEE Very Inverse

    IEEE Extremely Inverse

    Custom

    Common settings for all types:

    Setting Parameter no. Factory setting

    value

    Equals

    Limit 1722/1732 30/10% 2 x GS 

    TMS 1723/1733 1.0 Time multiplier setting

    In the APU 200, the value 2 x GS is called Limit.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    9/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 9 of 37

    The following constants apply to the predefined curves:

    Curve type k c α 

    IEC Inverse 0.14 0 0.02

    IEC Very Inverse 13.5 0 1

    IEC Extremely Inverse 80 0 2

    IEEE Moderately Inverse 0.515 0.1140 0.02

    IEEE Very Inverse 19.61 0.491 2

    IEEE Extremely Inverse 28.2 0.1217 2

    For the custom curve, these constants can be defined by the user:

    Setting Parameter no. Factory setting

    value

    Equals

    k 1724/1734 0.140 s k

    c 1725/1735 0.000 s c

    α (a) 1726/1736 0.020 α

     

    The curves are shown for TMS = 1.

    For the actual setting ranges, please see the parameter list.

    Standard curves

  • 8/8/2019 Designer’s Reference Handbook DEIF

    10/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 10 of 37

    4. Synchronisation

    This chapter describe closing and opening of the BTB and the alarms linked to this function

    Close BTB

    It is not possible to close (synchronise) the BTB if there is live voltage at both sides of the

    transformer.

    Close BTB LV, No voltage LV, Voltage HV, No voltage HV, Voltage

    LV, No voltage - NA Possible Possible

    LV, Voltage NA - Possible Not Possible

    HV, No voltage Possible Possible - NA

    HV, voltage Possible Not Possible NA -

    Open BTB

    Open BTB Q7 ON Q7 OFF Q5B ON O5B OFF

    Q7 ON NA Not Possible Possible

    Q7 OFF NA Possible

    Q5B ON Not Possible Possible NA

    O5B OFF Possible Possible NA

    It is possible to request open/close BTB by:

    Display

    Via the front of the display, it is possible to activate BTB open/close command

    M-Logic

  • 8/8/2019 Designer’s Reference Handbook DEIF

    11/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 11 of 37

    Inputs

    Possible to activate BTB open

    Modbus (Option H2)

    For additional information, please refer to the Modbus documentation for the

    APU 200.

    For additional information, please use the help function in the USW, this is

    activated by [F1].

  • 8/8/2019 Designer’s Reference Handbook DEIF

    12/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 12 of 37

    Open/close fail 

    It is possible to setup the alarm settings for open/close failure. This can be done via the display or

    via the USW:

    Display

    USW

    Double-click the requested parameter.

    24 kV 50 Hz A1 B1 C12160 Q6 Open fail

    2170 Q6 Close fail

    2240 Sep synch relay

    2300 Section P>

    2420 BTB33 os fail

    For additional information regarding how to setup the alarm, please use the help

    function in the USW; this is activated by [F1].

  • 8/8/2019 Designer’s Reference Handbook DEIF

    13/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 13 of 37

    5. Digital input

    The unit has 10 configurable binary inputs, and they are all available and programmed via the

    USW’s I/O settings

    Functional description

    1. Semi-auto

    Changes the present running mode to semi-auto.

    2. Auto

    Changes the present running mode to auto.

    2. Block

    Changes the present running mode to block.

    4. Access lock

     Activating the access lock input deactivates the control display push-buttons. It will only be

    possible to view measurements, alarms and the log.

    5. Remote BTB ON

    The BTB ON sequence will be initiated and the BTB will synchronise.

    6. Remote BTB OFF

    The BTB OFF sequence will be initiated, followed by a breaker opening.

    7. BTB close inhibit

    When this input is activated, the BTB cannot close.

    8. Enable separate sync.

     Activating this input will split the breaker close and BTB synchronisation functions into two

    different relays. The BTB close function will remain on the relays dedicated for breaker control.

    The synchronisation function will be moved to a configurable relay dependent on the options

    configuration.

    9. BTB spring loaded

    The APU 200 will not send a close signal before this feedback is present.

    10. Remote alarm acknowledge

     Acknowledges all present alarms, and the alarm LED on the display stops flashing.

    Input function Configurable Input type

    1 Semi-auto Configurable Pulse

    2 Auto Configurable Pulse

    3 Block Configurable Constant

    4 Access lock Configurable Constant

    5 Remote BTB ON Configurable Pulse

    6 Remote BTB OFF Configurable Pulse

    7 BTB close inhibit Configurable Constant

    8 Enable sep. sync. Configurable Constant

    9 BTB spring loaded Configurable Constant

    10 Remote alarm acknowledge Configurable Constant

    When block mode is selected, the running mode cannot be changed by

    activating the digital inputs.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    14/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 14 of 37

    Input function selection

    Digital input alarms can be configured with a possibility to select when the alarms are to be

    activated. The possible selections of the input function are normally open or normally closed.

    The drawing below illustrates a digital input used as an alarm input.

    1. Digital input alarm configured to NC, normally closed

    This will initiate an alarm when the signal on the digital input disappears.

    2. Digital input alarm configured to NO, normally open

    This will initiate an alarm when the signal on the digital input appears.

    The relay output function cannot be changed. This will always be a NO relay and

    will close when the alarm occurs; alarm = CC (closed contact).

    D i g. in 

    Com 

    R elay out 

     AGC 200 

    + V DC 

     Alarm  

    input 

  • 8/8/2019 Designer’s Reference Handbook DEIF

    15/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 15 of 37

    6. Analogue input

    The APU 200 unit has three multi-inputs (46, 47 and 48) which can be configured to be used as

    the following input types:

    •  4-20 mA

    •  Pt100

    •  VDO

    •  Digital

    Two alarm levels are available for each input. The menu numbers of the alarm settings for each

    multi-input are controlled by the configured input type as seen in the following table.

    Input type Multi-input 46 Multi-input 47 Multi-input 48

    4-20 mA 4120/4130 4250/4260 4380/4390

    0-40V DC 4140/4150 4270/4280 4400/4410

    Pt100 4160/4170 4290/4300 4420/4430

    VDO 1 4180/4190 4310/4320 4440/4450

    VDO 2 4200/4210 4330/4340 4460/4470

    VDO 3 4220/4230 4350/4360 4480/4490

    Digital 3400 3410 3420

    4-20 mA

    If one of the multi-inputs has been configured as 4-20 mA, the unit and range of the measured

    value corresponding to 4-20 mA can be changed in the PC utility software in order to get the

    correct reading in the display.

    Pt100

    This input type can be used for heat sensor, e.g. cooling oil temperature. The unit of the

    measured value can be changed from Celsius to Fahrenheit in the PC utility software in order to

    get the desired reading in the display.

    VDO inputs

    The unit can contain up to three VDO inputs. The inputs have different functions as the

    hardware design allows for several VDO types.

    These various types of VDO inputs are available for all multi-inputs:

    For each type of VDO input, it is possible to select between different characteristics including a

    configurable.

    The function of the multi-inputs can only be configured in the PC utility software.

    Only 1 alarm level is available for the digital input type.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    16/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 16 of 37

    VDO 1

    This VDO input is used to measure the pressure.

    VDO sensor type

    Pressure Type 1 Type 2 Type configurable

    Bar psi Ω  Ω  Ω 

    0 0 10.0 10.0

    0.5 7 27.2

    1.0 15 44.9 31.3

    1.5 22 62.9

    2.0 29 81.0 51.5

    2.5 36 99.2

    3.0 44 117.1 71.0

    3.5 51 134.7

    4.0 58 151.9 89.6

    4.5 65 168.3

    5.0 73 184.0 107.3

    6.0 87 124.3

    7.0 102 140.4

    8.0 116 155.7

    9.0 131 170.2

    10.0 145 184.0

    The configurable type is configurable with eight points in the range 0-2500 Ω.

    The resistance as well as the pressure can be adjusted.

    If the VDO input is used as a level switch, then please be aware that no voltage

    must be connected to the input. If any voltage is applied to the VDO input, it will

    be damaged. Please refer to the Application Notes for further wiring information.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    17/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 17 of 37

    VDO 2

    This VDO input is used to measure temperature.

    VDO sensor

    type

    Temperature Type 1 Type 2 Type 3 Type 4

    °C °F Ω  Ω  Ω  Ω 

    40 104 291.5 480.7 69.3

    50 122 197.3 323.6

    60 140 134.0 222.5 36.0

    70 158 97.1 157.1

    80 176 70.1 113.2 19.8

    90 194 51.2 83.2

    100 212 38.5 62.4 11.7

    110 230 29.1 47.6

    120 248 22.4 36.8 7.4

    130 266 28.9

    140 284 22.8

    150 302 18.2

    VDO 3

    This VDO input is used for the level sensor.

    VDO sensor type

    Type 1Value Resistance

    0% 78.8 Ω 

    100% 1.6 Ω 

    VDO sensor type

    Type 2

    Value Resistance

    0% 3 Ω 

    100% 180 Ω 

    The configurable type is configurable with eight points in the range 0-2500 Ω.

    The temperature as well as the resistance can be adjusted.

    If the VDO input is used as a level switch, then please be aware that no voltage

    must be connected to the input. If any voltage is applied to the VDO input, it will

    be damaged. Please refer to the Application Notes for further wiring information.

    If the VDO input is used as a level switch, then please be aware that no voltage

    must be connected to the input. If any voltage is applied to the VDO input, it willbe damaged. Please refer to the Application Notes for further wiring information.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    18/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 18 of 37

    VDO configurable

    VDO sensor type

    Value Type configurable

    bar, °C or % Resistance

    0 0

    10 SP 1

    20 SP 2

    30 SP 3

    40 SP 4

    50 SP 5

    60 SP 6

    70 SP 7

    80 SP 8

    The configurable type is configurable with eight points in the range 0-2500 Ω.

    The value as well as the resistance can be adjusted.

    Setpoints

    Setpoint 1Setpoint 2

    Setpoint 3

    Setpoint 4

    Setpoint 5

    Setpoint 6

    Setpoint 7

    87654321

    Value

    (bar, °C or %)

    Resistance

    (Ω)

    Setpoint 8

  • 8/8/2019 Designer’s Reference Handbook DEIF

    19/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 19 of 37

    Configuration 

    The eight curve settings for the configurable VDO inputs cannot be changed in the display, only 

    in the PC utility software. The alarm settings can be changed both in the display and in the PC

    utility software. In the PC utility software, the configurable inputs are adjusted in this dialogue

    box:

     Adjust the resistance of the VDO sensor at the specific measuring value. In the example above,the adjustment is 10 Ω at 0.0.

    For additional information regarding how to setup the VDO, please use the help

    function in the USW; this is activated by [F1].

  • 8/8/2019 Designer’s Reference Handbook DEIF

    20/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 20 of 37

    Digital

    If the multi-inputs are configured to binary “Digital”, they become available as a configurable

    input.

    When the parameter has been uploaded, it is possible to configure the input.

    When the multi-input has been changed to binary, remember to write and upload

    the parameter.

    For additional information regarding how to setup the digital input, please use

    the help function in the USW; this is activated by [F1].

  • 8/8/2019 Designer’s Reference Handbook DEIF

    21/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 21 of 37

    Wire fail detection

    If it is necessary to supervise the sensors/wires connected to the multi-inputs, then it is possible

    to enable the wire break function for each input. If the measured value on the input is outside the

    normal dynamic area of the input, it will be detected as if the wire has made a short-circuit or a

    break. An alarm with a configurable fail class will be activated.

    Input Wire failure area Normal range Wire failure area

    4-20 mA < 3 mA 4-20 mA > 21 mA

    VDO Oil, type 1 < 10.0 ohm - > 184.0 ohm

    VDO Oil, type 2 < 10.0 ohm - > 184.0 ohm

    VDO Temp, type 1 < 22.4 ohm - > 291.5 ohm

    VDO Temp, type 2 < 18.3 ohm - > 480.7 ohm

    VDO Temp, type 3 < 7.4 ohm - > 69.3 ohm

    VDO Level, type 1 < 1.6 ohm - > 78.8 ohm

    VDO Level, type 2 < 3.0 ohm - > 180.0 ohm

    VDO configurable < lowest resistance - > highest resistance

    Pt100 < 82.3 ohm - > 194.1 ohm

    Level switch Only active if the switch is open

    Principle

    The illustration below shows that when the wire of the input breaks, the measured value will drop

    to zero. Then the alarm will occur.

    Intertrip wirebreak (menu 6270)

    The alarm will occur when the Intertrip is not activated and the input is de-energised.

    Wire failure

    Wire failure

    Wire break

    Lower failure

    limit

    Upper failure

    limit

    Input signal(mA, °C, b, %)

  • 8/8/2019 Designer’s Reference Handbook DEIF

    22/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 22 of 37

    7. General setup

    Nominal settings

    The nominal settings can be changed to match different voltages and frequencies. The APU 200has four sets of nominal values, and they are adjusted in menus 6000 to 6030 (nominal settings

    1 to 4).

    Activation

    The switching between the nominal setpoint can be done in four ways: digital input (M-Logic),

     AOP or menu 6006.

    Digital input

    M-Logic is used when a digital input is needed for switching between the four sets of nominal

    settings. Select the required input among the input events, and select the nominal settings in the

    outputs.

    Example:

    Event A Event B Event C Output

    Dig. input no. 77 or Not used or Not used Set nom. parameter settings 1

    Not Dig. input no. 77 or Not used or Not used Set nom. parameter settings 2

     AOP

    M-Logic is used when the AOP is used for switching between the four sets of nominal settings.

    Select the required AOP push-button among the input events, and select the nominal settings inthe outputs.

    Example:

    Event A Event B Event C Output

    Button 07 or Not used or Not used Set nom. parameter settings 1

    Button 08 or Not used or Not used Set nom. parameter settings 2

    Menu settings

    In menu 6005, the switching is made between settings 1 to 4 simply by choosing the desired

    nominal setting.

    Please refer to the “Help” file [F1] in the PC utility software for details.

    Please refer to the “Help” file [F1] in the PC utility software for details.

    24kV 50Hz A1 B2 C1

    6005 Enable nom. set

    Nom. Setting 1

    Nom. Setting 2

    Nom. Setting 3

    Nom. Setting 4

  • 8/8/2019 Designer’s Reference Handbook DEIF

    23/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 23 of 37

    Tap settings

    In order to setup the APU correctly, it is necessary to programme the actual settings of the

    transformers tap. This is done in parameter 6007.

    Display USW

    The following tap settings relate to the programmed via the USW

    Tap setting Output Tap setting Output

    0 Tap setting not used 26 24 kV 50 Hz A2 B2 C1

    1 14 kV 50 Hz A1 B2 C1 27 24 kV 50 Hz A3 B2 C1

    2 14 kV 50 Hz A2 B2 C1 28 24 kV 50 Hz A4 B2 C1

    3 14 kV 50 Hz A3 B2 C1 29 24 kV 50 Hz A1 B1 C1

    4 14 kV 50 Hz A1 B1 C1 30 24 kV 50 Hz A2 B1 C1

    5 14 kV 50 Hz A2 B1 C1 31 24 kV 50 Hz A3 B2 C1

    6 14 kV 50 Hz A3 B1 C1 32 24 kV 50 Hz A1 B2 C2

    7 14 kV 50 Hz A1 B2 C2 33 24 kV 50 Hz A2 B2 C28 14 kV 50 Hz A2 B2 C2 34 24 kV 50 Hz A3 B2 C2

    9 14 kV 50 Hz A3 B2 C2 35 24 kV 50 Hz A1 B1 C2

    10 14 kV 50 Hz A1 B1 C2 36 24 kV 50 Hz A2 B1 C2

    11 14 kV 50 Hz A2 B1 C2 37 24 kV 50 Hz A3 B1 C2

    12 14 kV 50 Hz A3 B1 C2 38 24 kV 60 Hz A1 B2 C1

    13 14 kV 60 Hz A1 B2 C1 39 24 kV 60 Hz A2 B2 C1

    14 14 kV 60 Hz A2 B2 C1 40 24 kV 60 Hz A3 B2 C1

    15 14 kV 60 Hz A3 B2 C1 41 24 kV 60 Hz A4 B2 C1

    16 14 kV 60 Hz A1 B1 C1 42 24 kV 60 Hz A1 B1 C117 14 kV 60 Hz A2 B1 C1 43 24 kV 60 Hz A2 B1 C1

    18 14 kV 60 Hz A3 B1 C1 44 24 kV 60 Hz A3 B2 C1

    19 14 kV 60 Hz A1 B2 C2 45 24 kV 60 Hz A1 B2 C2

    20 14 kV 60 Hz A2 B2 C2 46 24 kV 60 Hz A2 B2 C2

    21 14 kV 60 Hz A3 B2 C2 47 24 kV 60 Hz A3 B2 C2

    22 14 kV 60 Hz A1 B1 C2 48 24 kV 60 Hz A1 B1 C2

    23 14 kV 60 Hz A2 B1 C2 49 24 kV 60 Hz A2 B1 C2

    24 14 kV 60 Hz A3 B1 C2 50 24 kV 60 Hz A3 B1 C2

    25 24 kV 50 Hz A1 B2 C1

    24 kV 50 Hz A1 B1 C16000 Nom. Settings 1

    Current: 365 A

    Voltage: 6240 V

    Set: nom. Settings 1

    Current E/N/M 100 A

    Tap: 24kV 50Hz A1 B1 C1 

  • 8/8/2019 Designer’s Reference Handbook DEIF

    24/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 24 of 37

    Fan Control

    Four configurable fans can be setup in the APU. The setup of the fans is done in menus 6562 to

    6620. It is possible to use the display to setup the fans but it is recommended to setup the fans

    via the USW, because then it is possible to see all settings.

    Fan Input

    Fan temperature input is setup in parameter 6561. This input can be selected between multi-

    input 46, 47 or 48.

    Fan priority update

     At parameter 6562, the priority update rate is selected.

    Fan control

    Stop/start of the fans is setup in parameter 6563 to 6574.

    The following start/stop curve will be generated if a bow setting is used.

    If fan priority update is set to 0 hours, the sequence will be fixed to.:

    Fan A, Fan B, Fan C and Fan D.

    It is recommended to use the USW to setup the fans, because then it is possible

    at the same time to overview all four settings.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    25/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 25 of 37

    Fan Output

     At parameter 6581 to 6584, the output for fan A to D is selected. If two fans are requested to be

    started at the same time, it is possible to add a start delay between the two fans; this is done in

    parameter 6586.

    Fan A to D Failure

    It is possible to activate an alarm if the fan output is not energised. At parameter 6590 to 6620,

    the fan failure is setup.

    Fan running hour

    The running hours is controlled by M-Logic, and each fan output needs to be programmed in

    order to have correct running hour values.

    The running hour can reset by entering parameter 6585 and select the fan output to be reset.

    Please note that it is only possible to reset the value, not add new values.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    26/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 26 of 37

    Service timers The unit is able to monitor the maintenance intervals. Two service timers are available to cover

    different intervals.

    The service timers can be setup:

    via the display or via the USW

    The function is based on energised hours. When the adjusted time expires, the unit will display

    an alarm.

    The energised hours is counting when the energised feedback is present.

    Setpoints available in menus 6110 and 6170:

    Enable: Enable/disable the alarm function.

    Energised hours:  The number of energised hours to activate the alarm.

    Day:  The number of days to activate the alarm – if the hours are not reached

    before this number of days, the alarm will be raised.

    Fail class:  The fail class of the alarm.

    Output A:  Relay to be activated when the alarm is raised.

    Reset:  Enabling this will reset the service timer to zero. This has to be done

    when the alarm is activated.

    24 kV 50 Hz A1 B1 C1

    SETUP MENU

    6110 Service timer 1

    6120 Service timer 2

    6130 Alarm horn

    6270 Intertrip Wirebreak

    The service timer is only counting when voltage is detected at the LV side of the

    transformer.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    27/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 27 of 37

    Summer/winter time

    This function is used to make the APU 200 unit adjust the clock in the unit automatically

    according to summer and winter time. The function is enabled in menu 6490. This can be done:

    via the display or via the USW

    Counters

    Counters for various values are included, and some of these can be adjusted if necessary, for

    instance if the unit is installed on an existing system or a new circuit breaker has been installed.

    The table shows the adjustable values and their function in menu 6100:

    Description Function Comment6101 Q6 operations Offset adjustment of the number of

    breaker operations.

    Counting at each Q6 close

    command.

    6102 kWh reset Resets the kWh counter. Automatically resets to OFF

    after the reset. The reset

    function cannot be left active.

    The function only supports the European rules.

    24 kV 50 Hz A1 B1 C1

    6490 Summer/Winter time

    OFF

    ON . 

  • 8/8/2019 Designer’s Reference Handbook DEIF

    28/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 28 of 37

    Language selection

    The unit has the possibility to display different languages. It is delivered with one master

    language which is English. This is the default language, and it cannot be changed. In addition to

    the master language, 11 different languages can be configured. This is done via the PC utility

    software.

    The languages are selected in the system setup menu 6080. The language can be changed

    when connected to the PC utility software. It is not possible to make language configuration from

    the display, but the already configured languages can be selected.

    After selecting a language, the unit aux. power must be cycled before the

    selection takes effect.

    24kV 50Hz A1 B2 C1

    6081 Language

    Language Left

    Language Right

    Language 3

    Language 4

    Language 5

  • 8/8/2019 Designer’s Reference Handbook DEIF

    29/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 29 of 37

    8. Power Management

    In the following chapter, the power management functions of the APU 200 are listed.

    Power management functions:

    •  Load management

    •  Command timers

    •  CAN flags

    Load management

    The function is used to activate a relay when a specific amount of power is available. Each APU

    200 has five levels which are adjusted in menus 8220-8260:

    •  Available power 1

    •  Available power 2

    •  Available power 3•  Available power 4

    •  Available power 5

    These setpoints can activate a relay when the specific amount of available power is reached.

    The relay output can be used to connect load groups when sufficient power is available. The

    relays will activate when the available power is higher than the setpoint, but be aware that when

    the load groups are being connected, the available power will decrease and the relay(s)

    deactivate again if the available power is below the setpoint. So it is necessary to make an

    external holding circuit.

    The function is not depending on the running modes. The relays will activate in all modes

    including block. To avoid activation, e.g. when the APU is blocked, the inhibit function should beused.

    Command timers (time-dependent start/stop)

    The purpose of the time-dependent start/stop function is to be able to start and stop functions

    automatically at specific times each weekday or certain weekdays.

    Up to eight command timers can be used for either start or stop functions. The settings are set

    up through the PC utility software. Each command can be set for the following time periods:

    •  Individual days (MO, TU, WE, TH, FR, SA, SU)

    •  MO, TU, WE, TH

    •  MO, TU, WE, TH, FR

      MO, TU, WE, TH, FR, SA, SU•  SA, SU

    The command timers are to be used in M-Logic as events to set the command (start/stop).

    It is necessary to use the PC utility software when setting up the time-dependent

    start/stop function.

    The time-dependent start and stop commands are pulses that are not sent until

    the moment the adjusted time is reached.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    30/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 30 of 37

    9. Additional functions

    This chapter includes functional descriptions of functions. Tables, diagrams and single-line

    illustrations will be used in order to simplify the information.

    Alarm inhibit

    In order to select when the alarms are to be active, a configurable inhibit setting for every alarm

    has been made. The inhibit functionality is only available via the PC utility software. For every

    alarm, there is a drop-down window where it is possible to select which signals that have to be

    present in order to inhibit the alarm.

    Selections for alarm inhibit:

    Function Description

    Inhibit 1 M-Logic outputs:

    Conditions are

    programmed in M-Logic

    Inhibit 2

    Inhibit 3

    BTB ON The bus breaker is closed

    BTB OFF The bus breaker is open

    BA voltage > 30% Bus A voltage is above

    30% of nominal

    BA voltage < 30% Bus A voltage is below

    30% of nominal

    Inhibit of the alarm is active as long as one of the selected inhibit functions is active.

    In this example, inhibit is set to BTB ON . Here, the alarm will be active when the BTB is not

    closed. When the BTB has been synchronised, the alarm will be disabled again.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    31/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 31 of 37

    Access lock

    The purpose of access lock is to deny the operator the possibility of configuring the unit

    parameters and changing the running modes.

    The input to be used for the access lock function is defined in the PC utility software (USW) I/O

    settings, please use the application help [F1] in the USW for additional information of how to

    programme the device.

    The following example is digital input 86 (terminal 86) used for access lock

     Access lock will typically be activated from a key switch installed behind the door of the

    switchboard cabinet.

    Button Button status Comment

     Active It is possible to read all alarms, but it is not possible to

    acknowledge any of them

     Active The horn can be silenced

    Not active

    Not active

     Active Reading of all values is possible

     Active The log can be read

     Active System setup can be entered, but no changes can be

    made

     Active The tools can be read, but no commands can be sent

    LEFT

     Active

    UP  Active

    Not active If the access lock is activated when the view menu

    system is displayed, the button is not active

    DOWN  Active

    ESC 

     Active

    RIGHT

     Active

  • 8/8/2019 Designer’s Reference Handbook DEIF

    32/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 32 of 37

    The following digital input functions are affected when access lock is activated:

    Input name Input status

    Semi-auto Not active

     Auto Not active

    Block Not active

    Remote BTB ON Not activeRemote BTB OFF Not active

    Fail class

     All activated alarms must be configured with a fail class. The fail classes define the category of

    the alarms and the subsequent alarm action.

    Three different fail classes can be used. The tables below illustrate the action of each fail class

    The table illustrates the action of the fail classes. If, for instance, an alarm has been configured

    with the “Trip BTB” fail class, the following actions occur:

    •  The alarm horn relay will activate.

      The alarm will be displayed in the alarm info screen.•  The BTB will open instantly.

    Fail class configuration

    The fail class can be selected for each alarm function either via the display or via the USW. To

    change the fail class via the USW, the alarm function to be configured must be selected. Select

    the desired fail class in the fail class scroll-down menu.

    Display USW

    Action

    Fail class 

    Alarm

    horn

    relay

    Alarm

    display

    Trip of

    BTB

    Block for

    closing

    1 Block X X x

    2 Warning X X

    3 Trip BTB X X X

    In addition to the actions defined by the fail classes, it is possible to activate

    one or two relay outputs if additional relays are available in the unit.

    AOP buttons are not locked when access lock is activated.

    24 kV 50 Hz A1 B1 C1

    1006 HV -P> 1

    Block

    Warning

    Trip BTB . 

  • 8/8/2019 Designer’s Reference Handbook DEIF

    33/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 33 of 37

    Relay outputs

    The unit has 12 configurable relay outputs, and they are all available and programmed via the

    USW’s I/O settings.

    Relay Output function Configurable

    16 Not used

    HC 1 acknowledge

    HC 2 acknowledge

    Trip NEL 1

    Trip NEL 2

    Trip NEL 3

    Status OK

    Horn

    Configurable

    18 Configurable

    20 Configurable

    23 Configurable

    26 Configurable

    28 Configurable

    30 Configurable

    32 Configurable

    34 Configurable

    36 Configurable

    39 Configurable

    43 Configurable

    M-Logic

    M-Logic functionality is included in the unit and is not an option-dependent function. However,

    selecting additional options can increase the functionality.

    M-Logic is used to execute different commands at predefined conditions. M-Logic is not a PLC

    but substitutes one if only very simple commands are needed.

    M-Logic is a simple tool based on logic events. One or more input conditions are defined, and at

    the activation of those inputs, the defined output will occur. A great variety of inputs can be

    selected, such as digital inputs, alarm conditions and running conditions. A variety of the outputs

    can also be selected, such as relay outputs, change of modes and change of running modes.

    The main purpose of M-Logic is to give the operator/designer more flexible possibilities of

    operating the system.

    The M-Logic is part of the PC utility software 3, and as such it can only be

    configured in the PC utility software and not via the display.

    Please refer to the “Help” function (F1) in the PC utility software for a full

    description of this configuration tool.

    Please refer to DEIF standard application note: “M-Logic” for further functional

    details.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    34/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 34 of 37

    Configurable alarm LEDs

    The four LEDs on the left side of the display can be controlled via M-Logic. For each LED, there

    is a choice between three colours (red, green and yellow) with or without blinking.

    Example of Alarms LED configuration

    It is possible to programme the Alarm LEDs, to indicate highest phase current at any alarm.

    Start by programming the event A to un-acknowledge alarm, then programme event B to look athighest phase (L1, L2 or L3) current at any alarm.

    Next step: Alarm LED to be active (LED 1, 2, 3 or 4), also which colour and effect this LED must

    have.

    The following programming will activate (steady red) Alarm LED 1, whenever an

    un-acknowledge alarm is present, and the current was highest in L1 when the

    alarm was activated.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    35/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 35 of 37

    Templates

    For each LED, there is a text box, where the indication of the function can be written. This must

    be done on a piece of stiff paper or a plastic transparent, as the texts are to be sided into a slot

    at the top of the APU 200 unit.

    The slide-in paper/transparent template looks like this:

    The above template is scale 1:1 when printing on A4 paper size.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    36/37

     APU 200 Designer’s Reference Handbook  

    DEIF A/S  Page 36 of 37

    LvHv Phase compare view

     At view 14, it is possible to see the phase rotation

    This can be useful to help troubleshoot or when commissioning the application.

    View Commend

    LV - - - - - - HV - - - - - - No voltage is detected

    LV HV HV has wrong phase rotation

    LV HV LV has wrong phase rotation

    LV HV LV and HV have wrong phase rotation

    LV HV OK, safe to close the BTB

    24 kV 50 Hz A1 B1 C1Q6 Operations 1391

    U – Supply 24.5 V

    LV ------- HV -------

    Energy total

    Run absolut  14/20

    Take precautions that it is safe to close the breaker. Failure to do this may

    cause personal injury or death.

  • 8/8/2019 Designer’s Reference Handbook DEIF

    37/37

     APU 200 Designer’s Reference Handbook  

    USW communication

    It is possible to communicate with the unit via the PC utility software. The purpose is to be able

    to remote-monitor and control the protection application.

    Application settings

    Please refer to the PC utility software help file [F1].

    Safety

    If communication fails, the unit will operate according to the received data. If e.g. only half of the

    parameter file has been downloaded when the communication is interrupted, the unit will use

    this actual data.

    TCP/IP

    DEIF option N is an Ethernet hardware option offering a number of features (hereafter referred

    to as the option N). The hardware needed for the option N is placed with an RJ45 connector on

    the left side of the unit, seen from the rear.

    The option N is delivered through the Ethernet port, and we recommend using a twisted pair

    category 5 cable (CAT5 as defined in ANSI/TIA/EIA-568-A) for connection of the option N to the

    network.

    The option N port automatically detects the cable type, so both twisted and straight cables can

    be used.

    DEIF A/S reserves the right to change any of the above. 

    It is possible to remote-control from the PC utility software if a TCP/IP router isused. Take precautions that it is safe to remote-operate the system, to avoid

    personal injury or death.

    Detailed information regarding this option can be found in DEIF standard

    document for option N: Modbus TCP/IP, document no: 4189340612.