The TE 5 - TE 55 series expansion valve regulate the injection of refrigerant into evaporators. It controls the refrigerant flow based on the superheat. The exchangeable power element is produced with the well known Danfoss laser welding technology for extended lifetime capability. The TE 5 - TE 55 series is available with a wide range of orifices which will cover a wide range of applications. Applications: - Air conditioning system - Chiller - Cold room - Freezer - Other refrigeration systems Features • Wide operating range: -40 – 10 °C / -40 – 50 °F -60 – -25 °C / -75 – -15 °F Refrigerants: R407F, R407A, R448A, R449A, R452A,R404A, R507, R22, R513A, R134a and R407C. • Interchangeable orifice assembly: - easy storage - easy capacity matching - better service Laser welded stainless steel power element, capillary tube and bulb. Wide capacity range, rated capacity from: R448A/R449A : 9 – 225 kW / 2.5 – 64 TR R407F : 11 – 250 kW / 3 – 71 TR R404A/R507 : 7 – 183 kW / 2 – 52 TR MOP function is available. • Superior charge performance. PS / MWP (maximum working pressure): 28 bar / 400 psig. Minimized capacity gap and overlap between orifices. TE 55 has balanced port design. Patented bulb strap design. Data sheet Thermostatic expansion valves Type TE 5 – TE 55 DKRCC.PD.AB0.A7.02 | 1 © Danfoss | DCS (sw) | 2019.01

Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

The TE 5 - TE 55 series expansion valve regulate the injection of refrigerant into evaporators. It controls the refrigerant flow based on the superheat. The exchangeable power element is produced with the well known Danfoss laser welding technology for extended lifetime capability. The TE 5 - TE 55 series is available with a wide range of orifices which will cover a wide range of applications.

Applications:- Air conditioning system- Chiller- Cold room- Freezer- Other refrigeration systems

Features • Wide operating range: -40 – 10 °C / -40 – 50 °F -60 – -25 °C / -75 – -15 °F

• Refrigerants: R407F, R407A, R448A, R449A, R452A,R404A, R507, R22, R513A, R134a and R407C.

• Interchangeable orifice assembly: - easy storage - easy capacity matching - better service

• Laser welded stainless steel power element, capillary tube and bulb.

• Wide capacity range, rated capacity from: R448A/R449A : 9 – 225 kW / 2.5 – 64 TR R407F : 11 – 250 kW / 3 – 71 TR

R404A/R507 : 7 – 183 kW / 2 – 52 TR • MOP function is available.• Superior charge performance. • PS / MWP (maximum working pressure):

28 bar / 400 psig.• Minimized capacity gap and overlap

between orifices.• TE 55 has balanced port design.• Patented bulb strap design.

Data sheet

Thermostatic expansion valves Type TE 5 – TE 55

DKRCC.PD.AB0.A7.02 | 1© Danfoss | DCS (sw) | 2019.01

Page 2: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

MADE IN CHINA 067B2709

131

5 TE

12 06

6

Identification

Element label

Orifice assembly marking for TE 5 – TE 55

The thermostatic element is fitted with a label (on top of the diaphragm).

The label holds information like valve type, evaporating temperature range, MOP point, refrigerant, max. working pressure PS / MWP and production date.

Production place and date (BE1315B) mean: BE = Wuqing, China 13 = Week 15 = Year 2015 B = Tuesday

Orifice assembly for TE 5 – TE 55The orifice assembly is marked on top of the spring cup, e.g. as shown in the figure.

TE 12 = For valve type06 = Orifice no.067B2709 = Orifice code no. for sales order1315 = week 13, year 2015

Capillary tube tag for TE 5 – TE 55The label gives the orifice size (06). A new label always accompanies a new orifice assembly.

Capillary tube tagTE 5 – TE 55

Max. temperatureBulb, when valve is assembled:100 °C / 210 °F.Complete valve when not assembled: 70 °C / 160 °F.Min. temperature: -60 °C / -75 °F.

SS = static superheatOS = opening superheatSH = SS + OS = total superheatQnom = rated capacityQmax = maximum capacity

SS can be adjusted with setting spindle.The standard factory SS setting is 4 K / 7.2 °F.The OS is 4 K / 7.2 °F from when opening begins to where the valve reaches its rated capacity Qnom. OS is determined by the design and cannot be changed.

Superheat ExampleStatic superheat SS = 4 K / 7.2 °FOpening superheat OS = 4 K / 7.2 °FTotal superheat SH = 4 + 4 = 8 K SH = 7.2 + 7.2 = 14.4 °F

Using orifice with range B element, please check superheat under running conditions and readjust SS setting, if necessary.

Max. test pressure: 32 bar / 465 psig.Maximum working pressure: 28 bar / 400 psig.

MOP-points SI units

Refrigerant

Range-40 − 10 °C

Range-40 − -5 °C

Range-40 − -15 °C

Range-60 − -25 °C

MOP-point in evaporating temperature te and evaporating pressure pe

15 °C 0 °C -10 °C -20 °C

R407F/R407A 7.5 bar 4.2 bar 2.6 bar 1.5 bar

R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar

R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar

R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar

R407C 6.6 bar 3.6 bar 2.2 bar 1.1 bar

MOP = Max. Operating Pressure

Technical data

US unitsRange

-40 – 50 °FRange

-40 – 25 °FRange

-40 – 5 °FRange

-75 – -15 °F

MOP-point in evaporating temperature te and evaporating pressure pe

60 °F 32 °F 15 °F -5 °F

110 psig 60 psig 40 psig 20 psig

120 psig 70 psig 45 psig 30 psig

100 psig 60 psig 35 psig 20 psig

55 psig 30 psig 15 psig 5 psig

95 psig 50 psig 30 psig 15 psig

For MOP of R448A/R449A, R452A, R513A, please contact Danfoss for more information.

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 2

Page 3: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

TE 55

Design / Function GeneralTE 5 – TE 55 valves have an interchangeable orifice assembly.

TE 5 – TE 55 valves are built up of three main components (Parts program):1. Thermostatic element2. Orifice assembly3. Valve body with connections

The orifice is refrigerant and range independend.

All valves are equipped with external pressure equalization.

To ensure long operating life, the valve cone and seat are made of a special alloy with particularly good wear properties.

TE 5

1. Thermostatic element.2. Interchangeable orifice assembly. 3. Valve body.4. Superheat setting spindle. 5. External pressure equalizing

connection with 1⁄4 in / 6 mm flare nut (solder is available on TE 5).

TE 12 / TE 20

1. Thermostatic element

2. Orifice assembly

3. Valve body with connections

Danfoss67B52.10

1

23

4

5

Danfoss67B53.10

1

2

3

45

Danfoss68B53.10

1

2

345

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 3

Page 4: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Element for expansion valve - including bulb strap. R407F/R407AValve type

Pressure equalization MOP Range Capillary tubeCode no.

Size Type [°C] [°F] [°C] [°F] [m] [in]

TE 5

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B35011/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B35021/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3503

1/4 in Solder ODF – – -40 – 10 -40 – 50 3 118 067B3504

TE 12

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B35321/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B35311/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3533

TE 20

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B35611/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B35601/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3562

TE 55 1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067G3500

Element for expansion valve - including bulb strap. R448A/R449A Valve type

Pressure equalization MOP Range Capillary tubeCode no.

Size Type [°C] [°F] [°C] [°F] [m] [in]

TE 51⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32521⁄4 in. / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3600

TE 12 1⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B2512

TE 20 1⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B3294

TE 55 1⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067G3219

Ordering

Element for expansion valve - including bulb strap. R452AValve type

Pressure equalization MOP Range Capillary tubeCode no.

Size Type [°C] [°F] [°C] [°F] [m] [in]

TE 51⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B36011⁄4 in. / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3602

TE 12 1⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B3652

TE 20 1⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B3680

TE 55 1⁄4 in. / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067G3600

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 4

Page 5: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Element for expansion valve - including bulb strap. R404A/R507

Valve typePressure equalization MOP Range Capillary tube

Code noSize Type [°C] [°F] [°C] [°F] [m] [in]

TE 5

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B33421/4 in Solder ODF – – -40 – 10 -40 – 50 3 118 067B3380

1/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B32381/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B33571/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3358

1/4 in Solder ODF -10 15 -40 – -15 -40 – 5 3 118 067B33841/4 in / 6 mm Flare – – -60 – -25 -75 – -15 3 118 067B3344

6 mm Solder ODF – – -60 – -25 -75 – -15 3 118 067B33921/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3343

1/4 in Solder ODF -20 -5 -60 – -25 -75 – -15 3 118 067B3381

TE 12

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B33471/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B33451/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B33481/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B33491/4 in / 6 mm Flare – – -60 – -25 -75 – -15 3 118 067B33681/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067B33461/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3350

TE 20

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B33521/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B33511/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B33531/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B33541/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067B33561/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3355

TE 55

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067G33021/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067G33031/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067G33041/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067G33051/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067G33011/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067G3306

Ordering

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 5

Page 6: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

OrderingElement for expansion valve - including bulb strap. R22/R407C 1)

Valve typePressure equalization MOP Range Capillary tube

Code no.Size Type [°C] [°F] [°C] [°F] [m] [in]

TE 5

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32501/4 in Solder ODF – – -40 – 10 -40 – 50 3 118 067B3420

1/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B32671/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B32491/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B32531/4 in / 6 mm Flare – – -60 – -25 -75 – -15 3 118 067B32631/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3251

TE 12

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32101/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067B32091/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B32271/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B32071/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B32131/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B32111/4 in / 6 mm Flare – – -60 – -25 -75 – -15 3 118 067B32251/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3212

TE 20

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32741/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067B32901/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B32861/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B32731/4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B32751/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B32761/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3287

TE 55

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067G32051/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067G32091/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067G32201/4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067G32061/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067G32071/4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067G3217

1) For R407C plants. please select elements from the dedicated R407C program

Element for expansion valve - including bulb strap. R513AValve type

Pressure equalization MOP Range Capillary tubeCode no.

Size Type [°C] [°F] [°C] [°F] [m] [in]

TE 5 1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B3603

TE 12 1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B3651

TE 20 1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B3681

TE 55 1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067G3601

Element for expansion valve - including bulb strap. R134aValve type

Pressure equalization MOP Range Capillary tubeCode no.

Size Type [°C] [°F] [°C] [°F] [m] [in]

TE 5

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32971/4 in Solder ODF – – -40 – 10 -40 – 50 3 118 067B3430

1/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3298

TE 12

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32321/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B32331/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067B3363

TE 20

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32921/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B32931/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067B3370

TE 55

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067G32221/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067G32231/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067G3230

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 6

Page 7: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Orifice for expansion valves. Rated capacity.

Valve type

Orifice no.

R407F R407A R448A/R449A R452A R404A/

R507 R22 R513A R134a R407C R407F R407A R448A/R449A R452A R404A/

R507 R22 R513A R134a R407CCode no.

[kW] [TR]

TE 5

0.5 11 9 9 7 7 9 5 5 11 3 2.5 2.5 2 2 2.5 1.5 1.5 3 067B2788

01 18 18 18 14 14 16 11 11 18 5 5 5 4 4 4.5 3 3 5 067B2789

02 28 25 25 21 19 25 14 16 25 8 7 7 6 5.5 7 4 4.5 7 067B2790

03 35 32 32 28 25 32 18 21 32 10 9 9 8 7 9 5 6 9 067B2791

04 46 42 46 39 35 42 25 28 46 13 12 13 11 10 12 7 8 13 067B2792

TE 12

05 70 56 53 46 49 56 30 35 53 20 16 15 13 14 16 8.5 10 15 067B2708

06 95 74 70 63 63 74 39 49 74 27 21 20 18 18 21 11 14 21 067B2709

07 113 95 91 81 81 95 49 63 91 32 27 26 23 23 27 14 18 26 067B2710

TE 2008 141 127 123 84 84 127 74 77 116 40 36 35 24 24 36 21 22 33 067B2771 1)

09 158 148 141 98 102 148 81 91 134 45 42 40 28 29 42 23 26 38 067B2773 1)

TE 55

9B 123 109 113 84 84 113 70 74 109 35 31 32 24 24 32 20 21 31 067G2705 2)

10 172 165 155 116 127 169 98 109 162 49 47 44 33 36 48 28 31 46 067G2701

11 186 183 169 127 137 183 106 120 176 53 52 48 36 39 52 30 34 50 067G2704

12 208 200 186 141 151 200 116 134 190 59 57 53 40 43 57 33 38 54 067G2707

13 250 243 225 172 183 246 144 165 232 71 69 64 49 52 70 41 47 66 067G2710

The rated capacity is based on:Evaporating temperature te = 4.4 °C / 40 °FCondensing temperature tc = 38 °C / 100 °FRefrigerant temperature ahead of valve tl = 37 °C / 98 °F

1) Recommend to use orifice no. 9B as alternative for orifice no. 08 and 09 on TE 55 when selecting the valve to work in range -60 – -25 °C / -75 – -15 °F. Extend capacity tables for range -60 – -25 °C / -75 – -15 °F are not provided.2) Alternative for orifice no. 08 and 09 in range -60 – -25 °C / -75 – -15 °F. Extend capacity tables for range -40 – 10 °C / -40 –50 °F are not provided.

OrderingElement for expansion valve - including bulb strap. R407C

Valve typePressure equalization MOP Range Capillary tube

Code no.Size Type [°C] [°F] [°C] [°F] [m] [in]

TE 51/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B32781/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3277

TE 121/4 in / 6 mm Flare – – -40 – 10 -40 – 50 3 118 067B33661/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3367

TE 20

1/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067B33711/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 5 197 067B3372

TE 551/4 in / 6 mm Flare – – -40 – 10 -40 – 50 5 197 067G32401/4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 5 197 067G3241

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 7

Page 8: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Flare angleway

Solder straightway

Solder angleway

Flanges

Solder straightway

Valve body for expansion valves

TypeConnection

Inlet × Outlet Connections / Flow direction Connection type 1) Code no.

[in] [mm]

TE 5

1/2 × 5/8 12 × 16 Flare angleway – 067B40131/2 × 5/8 – Solder angleway ODF × ODF 067B40091/2 × 7/8 – Solder angleway ODF × ODF 067B40105/8 × 7/8 – Solder angleway ODF × ODF 067B4011

7/8 × 11/8 – Solder angleway ODF × ODM 067B40341/2 × 5/8 – Solder straightway ODF × ODF 067B40071/2 × 7/8 – Solder straightway ODF × ODF 067B40085/8 × 7/8 – Solder straightway ODF × ODF 067B4032

7/8 × 11/8 – Solder straightway ODF × ODM 067B4033

– 12 × 16 Solder angleway ODF × ODF 067B4004

– 12 × 22 Solder angleway ODF × ODF 067B4005

– 16 × 22 Solder angleway ODF × ODF 067B4012

– 22 × 28 Solder angleway ODF × ODM 067B4037

– 12 × 16 Solder straightway ODF × ODF 067B4002

– 12 × 22 Solder straightway ODF × ODF 067B4003

– 16 × 22 Solder straightway ODF × ODF 067B4035

– 22 × 28 Solder straightway ODF × ODM 067B4036

TE 12

5/8 × 7/8 – Solder angleway ODF × ODF 067B40227/8 × 11/8 – Solder angleway ODF × ODM 067B4023

5/8 × 7/8 – Solder straightway ODF × ODF 067B40207/8 × 11/8 – Solder straightway ODF × ODM 067B4021

– 22 × 28 Solder angleway ODF × ODM 067B4017

– 16 × 22 Solder straightway ODF × ODF 067B4018

– 22 × 28 Solder straightway ODF × ODM 067B4016

TE 12

5/8 × 7/8 – Solder flanges ODF × ODF 067B40257/8 × 1 – Solder flanges ODF × ODF 067B4026

– 16 × 22 Solder flanges ODF × ODF 067B4027

– 22 × 25 Solder flanges ODF × ODF 067B4015

TE 20

7/8 × 11/8 – Solder angleway ODF × ODM 067B4023

– 22 × 28 Solder angleway ODF × ODM 067B40177/8 × 11/8 – Solder straightway ODF × ODM 067B4021

– 22 × 28 Solder straightway ODF × ODM 067B4016

TE 55

11/8 × 13/8 – Solder angleway ODM × ODM 067G4004

– 28 × 35 Solder angleway ODM × ODM 067G4002

11/8 × 13/8 – Solder straightway ODM × ODM 067G4003

– 28 × 35 Solder straightway ODM × ODM 067G40011) ODF = Internal diameter ODM = External diameter

Ordering

Bulb straps (delivered separately ) in Industrial pack Type Max. tube diameter Code no.

TE 5 / TE 12 2 1⁄8 in / 53 mm 067N0557

TE 20 / TE 55 3 1⁄8 in / 78 mm 067N0559

Spareparts

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 8

Page 9: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Q (capacity) = 45 kWTcon (condensing temperature) = 25 °CTevap (evaporator temperature) = -30 °CTsub (subcooling temperature) =10 KDpd (distributer pressure drop) = 2 bar

Q (capacity) = 45 kW

fsub (subcooling correction factor) = 1.09

fp (distributer correction factor) = 0.92

Q= Selected capacity

fsub x fp

50= 44.9 kW1.09 x 0.92

The selection will be:TE 20 orifice 9 (54.2 kW > 44.9 kW)

How to select a valveExample:

SI units

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K

SI unitsR404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20

TE 208 25 35.7 48.4 62.29 25 39.5 54.2 71.3

TE 55

10 25 46.5 64.9 86.111 25 51.1 71.2 94.412 25 54.8 76.8 10313 25 66.5 93.7 126

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15Correction factor 0,97 1,00 1,09 1,16

Distributer correction factor, fp

SI unitsR404A/R507

Pressure drop [bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10

Correction factor0 1 1 1 11 0.96 0.96 0.96 0.95

1.5 0.94 0.94 0.94 0.93

2 0.92 0.92 0.91 0.90

Calculated at 32 °C condensing temperature.

Capacity in kW. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F.

US unitsR404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0

TE 2008 75 10.2 14.2 18.609 75 11.3 16.1 21.5

TE 55

10 75 13.4 19.2 26.011 75 14.7 21.1 28.512 75 15.8 22.8 31.113 75 19.2 27.9 38.2

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20Correction factor 0.96 1.00 1.03 1.11

Distributer correction factor, fp

US units R404A/R507

Pressure drop [psi] ∆p

Evap. temp. [°F]

-40 -20 0 20Correction factor

0 1 1 1 115 0.96 0.96 0.96 0.9525 0.94 0.93 0.92 0.91

30 0.92 0.92 0.91 0.89

Calculated at 90 °F condensing temperature.

Q (capacity) = 14 TRTcon (condensing temperature) = 75 °FTevap (evaporator temperature) = -20 °FTsub (subcooling temperature) = 10 °FDpd (distributer pressure drop) = 30 psi

Q (capacity) = 14 TR

fsub (subcooling correction factor) = 1.03

fp (distributer correction factor) = 0.92

Q= Selected capacity

fsub x fp

14= 14.8 TR1.03 x 0.92

The selection will be:TE 20 orifice 9 (16.1 TR > 14.8 TR)

US units

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 9

Page 10: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407F

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 4.70 5.94 7.36 8.83 10.06 10.501 25 8.60 10.9 13.5 16.2 18.4 19.102 25 12.0 15.3 19.0 22.7 25.5 26.103 25 15.3 19.4 24.1 28.8 32.8 34.104 25 20.3 26.0 32.6 39.4 44.7 46.1

TE 1205 25 26.1 34.7 45.0 56.7 67.3 70.906 25 32.8 44.3 58.4 74.6 89.4 94.407 25 42.6 59.2 77.5 96.2 113 124

TE 2008 25 52.3 69.5 90.2 113 131 13409 25 56.6 76.3 101 130 155 162

TE 55

10 25 65.7 86.2 111 139 164 17711 25 72.3 94.9 123 153 180 19312 25 77.7 103 133 167 200 21613 25 94.7 126 163 206 245 262

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.12 1.17 1.23 1.28

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407F

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 1.33 1.72 2.17 2.62 2.91 2.9201 75 2.44 3.17 4.00 4.81 5.32 5.3202 75 3.41 4.44 5.60 6.70 7.32 7.2603 75 4.34 5.64 7.11 8.55 9.48 9.4904 75 5.76 7.58 9.66 11.7 12.9 12.8

TE 1205 75 7.42 10.2 13.5 17.2 19.7 19.706 75 9.32 13.0 17.6 22.7 26.2 26.207 75 12.0 17.4 23.2 29.0 33.6 34.7

TE 2008 75 14.9 20.4 27.0 33.8 37.8 37.309 75 16.1 22.5 30.6 39.5 45.4 45.1

TE 55

10 75 18.8 25.3 33.4 42.0 48.4 49.411 75 20.7 27.9 36.8 46.1 52.9 53.912 75 22.3 30.3 40.1 50.8 59.1 60.313 75 27.2 37.1 49.3 62.6 72.3 73.2

Distributer correction factor, fp SI units R407FPressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.97 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.95 0.94 0.94 0.93 0.91

2 0.93 0.93 0.92 0.91 0.90 0.87

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R407FPressure drop

[psi] ∆p

Evap. temp. [°C]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.95 0.9425 0.94 0.94 0.93 0.92 0.91 0.8930 0.93 0.92 0.92 0.91 0.89 0.87

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407F

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 4.70 5.98 7.49 9.14 10.7 11.901 35 8.60 11.0 13.8 16.8 19.7 21.702 35 12.0 15.4 19.4 23.6 27.4 29.903 35 15.2 19.4 24.4 29.7 34.8 38.504 35 20.0 26.0 33.0 40.6 47.7 52.0

TE 1205 35 25.8 33.8 43.6 55.6 68.8 79.006 35 31.9 42.6 56.1 72.8 91.3 10607 35 43.6 58.0 75.1 93.7 112 129

TE 2008 35 51.2 67.4 87.6 112 136 15309 35 54.3 71.9 94.9 123 156 181

TE 55

10 35 61.4 81.6 107 137 167 19111 35 67.2 89.3 117 150 182 20812 35 70.7 94.5 124 160 200 23313 35 84.6 113 150.1 195 243 282

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407F

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 1.33 1.74 2.23 2.75 3.21 3.3701 95 2.44 3.20 4.11 5.06 5.89 6.1602 95 3.41 4.49 5.77 7.09 8.17 8.4803 95 4.32 5.67 7.26 8.95 10.4 10.904 95 5.69 7.57 9.83 12.2 14.3 14.9

TE 1205 95 7.33 9.87 13.1 17.0 21.1 22.606 95 9.07 12.5 16.9 22.4 28.1 30.207 95 12.4 17.0 22.5 28.4 34.2 36.6

TE 2008 95 14.6 19.7 26.3 34.1 41.3 43.509 95 15.4 21.1 28.6 38.1 47.9 51.3

TE 55

10 95 17.4 23.9 32.2 41.8 50.9 54.311 95 19.1 26.2 35.3 45.7 55.4 58.912 95 20.1 27.7 37.4 49.3 61.4 66.213 95 24.0 33.3 45.3 59.8 74.5 80.1

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.27

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 10

Page 11: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407F

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 4.58 5.86 7.39 9.11 10.9 12.401 45 8.36 10.7 13.6 16.8 20.0 22.702 45 11.7 15.1 19.1 23.6 28.0 31.503 45 14.7 18.9 23.9 29.5 35.2 40.004 45 19.2 25.0 32.2 40.2 48.3 54.8

TE 1205 45 25.2 32.3 41.2 52.3 65.6 79.506 45 30.7 40.2 52.5 68.0 87.0 10707 45 41.9 54.0 69.3 87.0 106 125

TE 2008 45 49.5 64.2 82.8 106 132 15709 45 51.5 66.8 86.9 113 145 179

TE 55

10 45 55.2 74.2 98.8 129 162 19211 45 60.0 80.8 108 140 175 20712 45 62.3 83.9 112 146 187 22913 45 73.1 99.0 132 175 224 274

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.12 1.17 1.23 1.28

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407F

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 1.29 1.70 2.19 2.75 3.29 3.5201 115 2.36 3.12 4.04 5.07 6.05 6.4702 115 3.29 4.38 5.69 7.13 8.45 8.9703 115 4.14 5.48 7.10 8.90 10.6 11.404 115 5.40 7.27 9.58 12.2 14.6 15.6

TE 1205 115 7.12 9.37 12.3 15.9 20.3 22.406 115 8.66 11.7 15.6 20.8 27.1 30.207 115 11.8 15.6 20.5 26.2 32.3 35.2

TE 2008 115 14.0 18.6 24.6 32.2 40.6 44.409 115 14.5 19.4 25.9 34.6 45.1 50.4

TE 55

10 115 15.5 21.5 29.5 39.3 49.6 54.211 115 16.8 23.4 32.1 42.7 53.7 58.612 115 17.4 24.2 33.2 44.7 57.9 64.513 115 20.4 28.6 39.4 53.3 69.5 77.3

Distributer correction factor, fp SI units R407FPressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.97 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.95 0.94 0.94 0.93 0.91

2 0.93 0.93 0.92 0.91 0.90 0.87

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R407FPressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.95 0.9425 0.94 0.94 0.93 0.92 0.91 0.8930 0.93 0.92 0.92 0.91 0.89 0.87

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407F

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 4.33 5.56 7.06 8.77 10.6 12.301 55 7.89 10.2 13.0 16.2 19.5 22.602 55 11.0 14.3 18.3 22.9 27.5 31.603 55 13.7 17.8 22.7 28.2 34.1 39.504 55 17.7 23.4 30.3 38.4 46.8 54.3

TE 1205 55 24.3 30.6 38.3 48.0 59.8 73.606 55 29.1 37.5 48.1 61.8 79.0 99.207 55 37.6 47.1 60.4 76.7 95.2 115

TE 2008 55 47.3 60.3 76.8 97.4 122 14909 55 48.6 61.6 78.6 101 130 163

TE 55

10 55 47.2 64.2 86.7 115 148 18011 55 51.0 69.3 93.7 124 159 19412 55 53.0 71.9 96.3 127 166 20813 55 61.0 83.3 112 150 196 247

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407F

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 1.21 1.60 2.08 2.63 3.19 3.4501 135 2.20 2.93 3.83 4.85 5.89 6.3702 135 3.06 4.10 5.40 6.86 8.29 8.9103 135 3.82 5.10 6.66 8.44 10.3 11.104 135 4.91 6.69 8.92 11.5 14.1 15.3

TE 1205 135 6.84 8.78 11.2 14.3 18.2 20.406 135 8.16 10.8 14.1 18.6 24.3 27.507 135 10.3 13.2 17.4 22.7 28.6 31.8

TE 2008 135 13.3 17.3 22.6 29.2 37.3 41.509 135 13.6 17.6 23.0 30.3 39.7 45.1

TE 55

10 135 12.8 18.1 25.3 34.5 44.9 50.011 135 13.8 19.5 27.3 37.2 48.3 53.712 135 14.5 20.3 28.1 38.2 50.6 57.313 135 16.5 23.4 32.6 44.7 59.8 67.9

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.27

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 11

Page 12: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 4.36 5.50 6.80 8.10 9.14 9.4401 25 8.00 10.1 12.5 14.9 16.7 17.202 25 11.2 14.2 17.5 20.7 23.1 23.503 25 14.2 18.0 22.3 26.6 29.9 30.504 25 19.0 24.2 30.2 36.2 40.6 41.2

TE 1205 25 19.7 26.4 34.3 42.7 49.9 52.806 25 25.1 33.8 44.4 56.0 66.1 70.307 25 32.6 43.9 58.1 74.1 88.2 94.2

TE 2008 25 46.6 59.8 75.2 91.3 104 10709 25 51.3 66.8 85.6 106 124 130

TE 55

10 25 60.0 77.7 99.1 123 145 15611 25 66.1 85.6 109 135 159 17112 25 71.2 92.4 118 148 176 19113 25 86.9 113 146 182 216 232

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.13 1.19 1.24 1.30

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 1.24 1.60 2.01 2.40 2.63 2.6301 75 2.27 2.94 3.69 4.39 4.79 4.7702 75 3.19 4.13 5.15 6.09 6.59 6.5203 75 4.03 5.24 6.60 7.86 8.56 8.4904 75 5.40 7.07 8.95 10.7 11.6 11.5

TE 1205 75 5.62 7.75 10.3 12.9 14.6 14.706 75 7.16 9.96 13.4 16.9 19.4 19.607 75 9.32 13.0 17.6 22.5 26.0 26.3

TE 2008 75 13.3 18.0 22.4 27.2 30.0 29.809 75 14.7 20.0 25.7 32.1 36.2 36.2

TE 55

10 75 17.2 22.8 29.7 37.1 42.8 43.611 75 19.0 25.2 32.7 40.8 46.9 47.812 75 20.0 27.2 35.6 44.8 52.1 53.413 75 25.0 33.4 43.9 55.3 63.9 64.9

Distributer correction factor, fp SI units R407APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.94 0.94 0.93 0.92 0.90

2 0.93 0.92 0.92 0.91 0.89 0.87

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R407APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9325 0.94 0.93 0.93 0.92 0.90 0.8930 0.92 0.92 0.91 0.90 0.88 0.86

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 4.25 5.41 6.78 8.30 9.75 10.801 35 7.79 9.93 12.5 15.2 17.9 20.002 35 10.9 14.0 17.5 21.3 24.8 27.003 35 13.7 17.5 22.1 27.1 31.8 34.804 35 18.2 23.5 29.8 36.8 43.3 47.2

TE 1205 35 18.9 25.0 32.6 41.6 50.8 57.906 35 23.7 31.7 41.9 54.2 67.1 77.207 35 30.1 39.9 52.9 68.9 86.3 100

TE 2008 35 43.9 56.5 72.0 89.9 107 12009 35 47.2 61.3 79.3 101 124 142

TE 55

10 35 54.5 71.5 92.8 118 146 16911 35 59.7 78.2 101 129 159 18412 35 63.7 83.7 109 139 173 20313 35 76.4 100 132 169 211 246

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 1.21 1.58 2.02 2.50 2.92 3.0601 95 2.21 2.89 3.71 4.59 5.34 5.5802 95 3.10 4.07 5.20 6.40 7.38 7.6603 95 3.89 5.11 6.57 8.15 9.49 9.8804 95 5.15 6.84 8.89 11.1 12.9 13.4

TE 1205 95 5.36 7.31 9.80 12.7 15.5 16.406 95 6.73 9.30 12.6 16.6 20.5 21.907 95 8.55 11.7 15.9 21.2 26.5 28.5

TE 2008 95 12.5 16.5 21.5 27.3 32.4 34.009 95 13.4 17.9 23.8 31.0 37.9 40.2

TE 55

10 95 15.5 20.9 27.9 36.2 44.7 48.111 95 16.9 22.9 30.5 39.6 48.7 52.312 95 18.1 24.5 32.8 42.9 53.4 57.713 95 21.7 29.5 39.7 52.2 64.9 69.9

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.09 1.16 1.23 1.29

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 12

Page 13: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 4.00 5.11 6.47 8.05 9.73 11.201 45 7.33 9.39 11.9 14.8 17.9 20.602 45 10.3 13.2 16.8 20.8 25.0 28.503 45 12.8 16.4 20.8 26.0 31.6 36.304 45 16.8 21.8 28.0 35.4 43.2 49.6

TE 1205 45 17.5 22.8 29.6 38.1 47.8 57.306 45 21.7 28.7 37.8 49.3 62.9 76.407 45 27.4 35.3 46.1 60.1 77.1 95.0

TE 2008 45 40.2 51.4 65.7 83.4 103 12109 45 42.2 54.3 70.2 90.6 115 139

TE 55

10 45 47.4 62.9 82.9 108 137 16711 45 51.6 68.4 90.0 117 149 18112 45 54.6 72.5 95.8 125 160 19713 45 64.3 85.8 114 150 193 236

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.13 1.19 1.24 1.30

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 1.13 1.48 1.92 2.43 2.96 3.1801 115 2.06 2.72 3.53 4.48 5.44 5.8502 115 2.89 3.82 4.97 6.29 7.58 8.1003 115 3.60 4.74 6.17 7.86 9.58 10.304 115 4.72 6.30 8.32 10.7 13.1 14.1

TE 1205 115 4.92 6.58 8.78 11.6 14.7 16.206 115 6.10 8.28 11.2 15.0 19.4 21.507 115 7.67 10.2 13.6 18.3 23.8 26.6

TE 2008 115 11.3 14.8 19.5 25.3 31.6 34.309 115 11.8 15.6 20.8 27.5 35.5 39.2

TE 55

10 115 13.2 18.1 24.6 32.9 42.5 47.111 115 14.4 19.7 26.7 35.7 46.0 50.912 115 15.2 20.9 28.4 38.2 49.7 55.413 115 17.9 24.6 33.8 45.7 59.6 66.5

Distributer correction factor, fp SI units R407APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.94 0.94 0.93 0.92 0.90

2 0.93 0.92 0.92 0.91 0.89 0.87

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R407APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9325 0.94 0.93 0.93 0.92 0.90 0.8930 0.92 0.92 0.91 0.90 0.88 0.86

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 3.65 4.66 5.91 7.42 9.12 10.8301 55 6.68 8.56 10.9 13.7 16.9 20.002 55 9.34 12.0 15.4 19.4 23.8 27.903 55 11.6 14.8 18.8 23.8 29.4 35.004 55 15.0 19.5 25.2 32.3 40.3 48.2

TE 1205 55 15.9 20.2 25.8 33.1 42.0 51.906 55 19.4 25.1 32.7 42.6 55.0 69.107 55 24.5 30.7 39.0 50.0 64.3 81.3

TE 2008 55 35.6 45.1 57.4 73.2 92.5 11309 55 36.8 46.6 59.6 76.9 99.2 124

TE 55

10 55 39.3 52.7 70.3 93.0 121 15211 55 42.5 57.0 75.8 100 130 16412 55 44.6 59.8 79.9 106 139 17613 55 51.4 69.4 93.4 125 164 209

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 1.01 1.32 1.72 2.21 2.75 3.0201 135 1.85 2.43 3.17 4.08 5.09 5.5802 135 2.58 3.42 4.49 5.77 7.16 7.8103 135 3.20 4.19 5.47 7.06 8.86 9.7304 135 4.13 5.52 7.34 9.63 12.2 13.4

TE 1205 135 4.39 5.70 7.47 9.80 12.7 14.206 135 5.34 7.08 9.46 12.7 16.7 19.007 135 6.78 8.63 11.2 14.7 19.4 22.0

TE 2008 135 9.80 12.7 16.6 21.7 27.9 31.209 135 10.1 13.1 17.1 22.8 30.1 34.1

TE 55

10 135 10.6 14.7 20.3 27.8 37.0 41.911 135 11.5 15.9 21.9 29.9 39.7 45.012 135 12.0 16.7 23.0 31.6 42.3 48.213 135 13.8 19.3 26.8 37.1 50.1 57.2

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.09 1.16 1.23 1.29

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 13

Page 14: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 4.27 5.53 6.90 8.31 9.50 9.9501 25 7.84 10.2 12.7 15.3 17.4 18.102 25 11.0 14.3 17.8 21.3 24.0 24.703 25 13.9 18.0 22.6 27.2 31.1 32.2

04 25 18.4 24.2 30.6 37.1 42.3 43.4

TE 1205 25 22.5 29.0 36.5 44.8 52.5 56.106 25 28.5 37.2 47.5 59.0 69.7 74.607 25 37.4 48.4 61.8 77.3 92.3 100

TE 2008 25 49.9 65.4 83.2 102 118 12209 25 54.0 71.7 93.3 118 140 147

TE 55

10 25 56.3 76.7 101 128 153 16611 25 62.0 84.4 111 141 168 18112 25 66.5 90.8 120 154 185 20213 25 80.7 112 148 189 228 246

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 4.22 5.50 6.96 8.54 10.1 11.401 35 7.73 10.1 12.8 15.7 18.6 20.702 35 10.8 14.2 18.0 22.0 25.9 28.503 35 13.6 17.8 22.6 27.9 33.0 36.804 35 17.9 23.8 30.6 38.0 45.2 50.1

TE 1205 35 21.6 27.8 35.3 44.0 53.5 61.406 35 27.1 35.4 45.6 57.7 70.9 82.107 35 35.0 44.9 57.4 72.8 90.1 105

TE 2008 35 47.2 62.2 80.1 101 122 13709 35 49.8 66.2 86.7 112 139 161

TE 55

10 35 51.1 70.5 94.4 123 153 17911 35 55.8 77.0 103 134 167 19512 35 59.4 82.1 111 144 182 21513 35 70.7 98.4 133 175 221 260

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.13 1.18 1.24 1.31

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 1.21 1.61 2.04 2.47 2.75 2.7601 75 2.23 2.96 3.75 4.52 5.02 5.0202 75 3.12 4.15 5.25 6.29 6.90 6.8403 75 3.93 5.26 6.70 8.09 8.96 8.9304 75 5.24 7.08 9.09 11.0 12.2 12.0

TE 1205 75 6.40 8.47 10.9 13.5 15.4 15.606 75 8.13 10.9 14.2 17.8 20.5 20.807 75 10.7 14.2 18.6 23.5 27.4 28.0

TE 2008 75 14.2 19.2 24.8 30.6 34.2 33.909 75 15.4 21.2 28.2 35.8 41.0 40.9

TE 55

10 75 16.2 22.7 30.5 38.9 45.4 46.311 75 17.8 24.9 33.6 42.8 49.7 50.612 75 19.1 26.9 36.5 46.9 55.2 56.613 75 23.2 32.9 44.8 57.8 67.6 68.6

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 1.20 1.61 2.07 2.58 3.05 3.2201 95 2.20 2.95 3.82 4.75 5.59 5.8902 95 3.07 4.15 5.36 6.64 7.74 8.0903 95 3.85 5.20 6.74 8.41 9.94 10.504 95 5.08 6.96 9.13 11.5 13.6 14.2

TE 1205 95 6.13 8.12 10.5 13.4 16.3 17.506 95 7.70 10.3 13.7 17.6 21.7 23.307 95 9.95 13.1 17.2 22.3 27.7 29.9

TE 2008 95 13.4 18.2 24.0 30.6 36.9 38.909 95 14.1 19.4 26.1 34.3 42.7 45.6

TE 55

10 95 14.5 20.7 28.5 37.7 47.0 50.911 95 15.8 22.6 31.1 41.1 51.2 55.412 95 16.9 24.1 33.4 44.5 56.1 61.013 95 20.1 28.9 40.3 54.1 68.2 73.9

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.28

Distributer correction factor, fp SI units R448A/R449APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.94 0.94 0.93 0.92 0.90

2 0.93 0.92 0.92 0.91 0.90 0.87

* Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R448A/R449APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9425 0.94 0.93 0.93 0.92 0.90 0.8930 0.93 0.92 0.92 0.90 0.88 0.87

Calculated at 90 °F condensing temperature.

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 14

Page 15: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 4.07 5.34 6.79 8.42 10.2 11.801 45 7.45 9.80 12.5 15.5 18.7 21.702 45 10.4 13.8 17.6 21.9 26.2 30.003 45 13.0 17.1 21.9 27.2 33.0 38.304 45 16.9 22.7 29.4 37.1 45.3 52.6

TE 1205 45 20.3 26.0 32.9 41.3 51.1 61.106 45 25.2 32.8 42.2 53.7 67.5 81.907 45 32.0 40.6 51.5 65.2 82.0 100

TE 2008 45 43.6 57.6 74.5 94.7 117 13909 45 44.9 59.4 77.8 101 129 158

TE 55

10 45 45.1 62.8 85.0 112 142 17411 45 48.9 68.2 92.2 121 154 18712 45 51.6 72.1 97.9 129 166 20413 45 60.3 84.9 116 154 199 245

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 3.84 5.05 6.43 7.99 9.69 11.401 55 7.01 9.26 11.8 14.8 17.9 21.102 55 9.77 13.0 16.7 20.9 25.3 29.503 55 12.1 16.0 20.5 25.6 31.2 36.804 55 15.6 21.0 27.4 34.7 42.9 50.9

TE 1205 55 18.6 23.6 29.7 37.1 45.9 55.906 55 22.8 29.5 37.7 47.9 60.4 74.807 55 28.7 35.8 44.7 56.0 70.3 87.3

TE 2008 55 39.4 52.0 67.1 85.3 107 12909 55 39.7 52.1 67.7 87.6 113 142

TE 55

10 55 38.9 54.8 74.6 98.7 127 15711 55 42.0 59.1 80.3 106 136 16912 55 43.9 61.9 84.4 112 145 18113 55 50.3 71.5 98.4 132 171 215

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.13 1.18 1.24 1.31

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 1.15 1.55 2.02 2.54 3.09 3.3501 115 2.10 2.85 3.72 4.69 5.70 6.1502 115 2.94 4.00 5.23 6.60 7.96 8.5403 115 3.66 4.97 6.49 8.23 10.0 10.904 115 4.77 6.59 8.75 11.2 13.8 14.9

TE 1205 115 5.70 7.50 9.74 12.5 15.7 17.306 115 7.07 9.47 12.5 16.3 20.8 23.107 115 8.99 11.7 15.2 19.7 25.2 28.1

TE 2008 115 12.3 16.7 22.1 28.7 36.0 39.309 115 12.6 17.2 23.1 30.8 40.0 44.5

TE 55

10 115 12.6 18.2 25.4 34.1 44.0 48.911 115 13.7 19.8 27.5 36.9 47.5 52.812 115 14.4 20.9 29.2 39.5 51.3 57.313 115 16.8 24.5 34.6 47.2 61.6 68.8

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 1.07 1.45 1.89 2.38 2.92 3.1801 135 1.96 2.66 3.48 4.41 5.41 5.8902 135 2.73 3.74 4.91 6.23 7.61 8.2503 135 3.38 4.60 6.01 7.63 9.38 10.304 135 4.34 6.03 8.04 10.4 13.0 14.2

TE 1205 135 5.16 6.71 8.62 11.0 13.8 15.406 135 6.30 8.36 11.0 14.2 18.3 20.607 135 7.92 10.08 12.9 16.5 21.1 23.8

TE 2008 135 10.9 14.79 19.6 25.4 32.2 35.809 135 10.9 14.73 19.6 26.0 34.2 38.8

TE 55

10 135 10.7 15.58 21.9 29.6 38.6 43.411 135 11.5 16.77 23.5 31.8 41.4 46.512 135 12.0 17.54 24.7 33.6 44.1 49.813 135 13.7 20.20 28.7 39.4 52.1 58.9

Distributer correction factor, fp* SI units R448A/R449APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.94 0.94 0.93 0.92 0.90

2 0.93 0.92 0.92 0.91 0.90 0.87

* Calculated at 32 °C condensing temperature.

Distributer correction factor, fp* US units R448A/R449APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9425 0.94 0.93 0.93 0.92 0.90 0.8930 0.93 0.92 0.92 0.90 0.88 0.87

* Calculated at 90 °F condensing temperature.

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.28

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 15

Page 16: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F.

US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 65 0.74 0.92 1.14 1.41 1.7001 65 1.34 1.68 2.09 2.58 3.1302 65 1.87 2.35 2.93 3.62 4.3903 65 2.31 2.93 3.70 4.61 5.6404 65 3.01 3.85 4.90 6.16 7.62

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F.

US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 105 0.72 0.89 1.11 1.38 1.7001 105 1.30 1.62 2.03 2.53 3.1302 105 1.79 2.25 2.83 3.54 4.4003 105 2.24 2.81 3.52 4.41 5.4804 105 2.85 3.59 4.55 5.77 7.29

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F.

US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 85 0.74 0.92 1.15 1.42 1.7401 85 1.34 1.68 2.10 2.61 3.2002 85 1.86 2.34 2.93 3.65 4.4903 85 2.31 2.92 3.67 4.60 5.7004 85 2.97 3.78 4.81 6.09 7.66

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F.

US units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 125 0.68 0.84 1.05 1.30 1.6001 125 1.22 1.52 1.90 2.37 2.9302 125 1.68 2.11 2.64 3.31 4.1203 125 2.13 2.63 3.27 4.06 5.0304 125 2.67 3.33 4.17 5.25 6.62

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K

SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 20 2.57 3.35 4.33 5.53 6.1801 20 4.67 6.11 7.94 10.2 11.402 20 6.51 8.54 11.1 14.2 15.903 20 8.03 10.7 14.0 18.2 20.504 20 10.4 14.0 18.6 24.4 27.7

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K

SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 40 2.50 3.25 4.23 5.46 6.1701 40 4.51 5.90 7.71 10.0 11.302 40 6.24 8.19 10.8 14.1 15.903 40 7.80 10.2 13.4 17.5 19.904 40 9.91 13.1 17.4 23.1 26.6

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K

SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 30 2.56 3.34 4.34 5.59 6.2901 30 4.64 6.08 7.94 10.3 11.602 30 6.44 8.47 11.1 14.4 16.303 30 8.0 10.6 13.9 18.2 20.604 30 10.3 13.7 18.3 24.2 27.7

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K

SI units R448A/R449A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 50 2.39 3.09 4.01 5.17 5.8501 50 4.29 5.59 7.30 9.48 10.702 50 5.91 7.74 10.2 13.3 15.103 50 7.46 9.67 12.6 16.3 18.504 50 9.37 12.2 16.1 21.3 24.5

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.08 1.14 1.20 1.27 1.33

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.09 1.15 1.22 1.30

Distributer correction factor, fp* SI units R448A/R449APressure drop

[bar] ∆p

Evap. temp. [°C]-60 -50 -40 -30 -25

Correction factor0 1 1 1 1 11 0.97 0.97 0.96 0.96 0.96

1.5 0.95 0.95 0.95 0.94 0.94

2 0.93 0.93 0.93 0.92 0.92

* Calculated at 32 °C condensing temperature.

Distributer correction factor, fp* US units R448A/R449APressure drop

[psi] ∆p

Evap. temp. [°F]

-75 -60 -45 -30 -15

Correction factor0 1 1 1 1 1

15 0.96 0.96 0.96 0.96 0.9625 0.94 0.94 0.94 0.94 0.9330 0.93 0.93 0.93 0.92 0.92

* Calculated at 90 °F condensing temperature.

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 16

Page 17: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 3.60 4.78 6.04 7.27 8.23 8.4101 25 6.62 8.78 11.1 13.3 15.0 15.202 25 9.28 12.3 15.5 18.5 20.6 20.603 25 11.7 15.6 19.8 23.8 26.7 26.904 25 15.5 21.0 26.8 32.4 36.3 36.1

TE 1205 25 18.2 25.2 33.1 41.4 48.4 49.906 25 23.0 32.3 43.2 54.8 64.5 66.507 25 29.8 41.0 54.7 70.6 85.0 88.8

TE 2008 25 32.4 44.4 58.1 72.6 84.4 86.809 25 35.3 49.3 66.0 84.6 101 105

TE 55

10 25 44.1 59.5 78.1 98.7 117 12511 25 48.6 65.6 86.1 109 129 13712 25 52.4 70.9 93.6 119 143 15313 25 64.0 87.2 115 147 176 186

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.08 1.15 1.22 1.29 1.38

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 1.03 1.40 1.79 2.16 2.36 2.3301 75 1.89 2.57 3.29 3.95 4.30 4.2202 75 2.65 3.61 4.60 5.47 5.87 5.7203 75 3.32 4.56 5.87 7.05 7.63 7.4604 75 4.43 6.16 7.98 9.60 10.3 10.0

TE 1205 75 5.22 7.44 9.97 12.5 14.1 13.906 75 6.59 9.57 13.1 16.6 18.7 18.507 75 8.55 12.2 16.7 21.6 25.0 24.8

TE 2008 75 9.25 13.1 17.5 21.8 24.4 24.109 75 10.1 14.6 20.0 25.8 29.5 29.3

TE 55

10 75 12.6 17.6 23.6 29.9 34.5 34.811 75 14.0 19.4 26.0 33.0 37.9 38.112 75 15.1 21.0 28.3 36.3 42.2 42.713 75 18.4 25.9 35.0 44.9 51.8 52.0

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 3.40 4.58 5.89 7.30 8.64 9.5701 35 6.24 8.43 10.9 13.4 15.8 17.402 35 8.75 11.9 15.3 18.8 21.9 23.803 35 10.9 14.8 19.1 23.7 28.0 30.804 35 14.4 19.8 26.0 32.4 38.3 41.7

TE 1205 35 16.6 23.1 30.6 39.3 48.3 55.106 35 20.7 29.3 39.7 51.8 64.5 74.007 35 26.2 36.1 48.5 63.8 81.1 94.9

TE 2008 35 29.7 41.0 54.6 70.0 85.9 97.309 35 31.6 44.3 59.9 78.8 99.4 115

TE 55

10 35 38.9 53.5 71.8 93.5 117 13611 35 42.6 58.6 78.6 102 128 14812 35 45.5 62.8 84.6 111 139 16413 35 54.7 75.9 103 135 170 199

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 0.96 1.34 1.76 2.20 2.59 2.7201 95 1.77 2.46 3.24 4.05 4.74 4.9502 95 2.48 3.47 4.55 5.65 6.53 6.7603 95 3.09 4.33 5.72 7.17 8.39 8.7304 95 4.08 5.81 7.77 9.81 11.4 11.8

TE 1205 95 4.71 6.77 9.22 12.0 14.7 15.706 95 5.88 8.63 12.0 15.9 19.7 21.007 95 7.44 10.6 14.6 19.7 25.0 26.9

TE 2008 95 8.42 12.0 16.4 21.4 26.1 27.609 95 8.98 13.0 18.1 24.3 30.6 32.8

TE 55

10 95 11.0 15.7 21.7 28.7 35.8 38.611 95 12.1 17.2 23.7 31.5 39.1 42.012 95 12.9 18.4 25.6 34.2 43.0 46.513 95 15.5 22.3 31.1 41.7 52.4 56.4

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.96 1.00 1.02 1.10 1.18 1.25 1.34

Distributer correction factor, fp SI units R452APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.94 0.94 0.93 0.92 0.90

2 0.93 0.92 0.92 0.91 0.90 0.87

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R452APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9325 0.94 0.94 0.93 0.92 0.90 0.8930 0.93 0.92 0.92 0.90 0.88 0.86

Calculated at 90 °F condensing temperature.

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 17

Page 18: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 3.09 4.22 5.49 6.91 8.38 9.7201 45 5.66 7.76 10.1 12.8 15.5 17.802 45 7.94 10.9 14.3 17.9 21.6 24.603 45 9.80 13.5 17.7 22.3 27.1 31.304 45 12.8 18.0 23.9 30.6 37.3 42.9

TE 1205 45 14.7 20.4 27.1 35.1 44.1 53.206 45 18.1 25.7 34.8 45.9 58.8 71.807 45 22.6 30.8 41.2 54.3 70.5 87.6

TE 2008 45 26.3 36.5 48.8 63.5 80.1 96.109 45 27.5 38.5 52.1 69.0 89.3 110

TE 55

10 45 32.7 45.8 62.5 83.0 107 13011 45 35.6 49.9 68.0 90.3 116 14112 45 37.8 53.0 72.4 96.7 125 15413 45 44.6 62.9 86.5 116 151 186

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 0.86 1.22 1.63 2.08 2.54 2.7501 115 1.58 2.25 3.01 3.84 4.68 5.0402 115 2.22 3.17 4.24 5.40 6.51 6.9503 115 2.74 3.90 5.24 6.72 8.22 8.8504 115 3.58 5.21 7.11 9.23 11.3 12.1

TE 1205 115 4.10 5.88 8.03 10.6 13.5 14.906 115 5.05 7.42 10.4 14.0 18.1 20.207 115 6.28 8.87 12.2 16.5 21.8 24.5

TE 2008 115 7.35 10.6 14.5 19.3 24.6 27.009 115 7.68 11.1 15.5 21.0 27.7 31.0

TE 55

10 115 9.07 13.2 18.6 25.3 32.9 36.611 115 9.87 14.4 20.2 27.5 35.7 39.712 115 10.5 15.2 21.5 29.5 38.7 43.213 115 12.3 18.1 25.7 35.4 46.7 52.1

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 2.70 3.73 4.89 6.19 7.59 8.9701 55 4.94 6.87 9.05 11.5 14.1 16.602 55 6.92 9.70 12.8 16.2 19.8 23.103 55 8.49 11.8 15.6 19.8 24.4 28.804 55 11.0 15.6 21.0 27.1 33.7 40.0

TE 1205 55 12.6 17.5 23.1 29.6 37.3 45.706 55 15.4 21.7 29.3 38.5 49.5 61.807 55 18.9 25.7 33.9 44.0 56.7 71.5

TE 2008 55 22.6 31.4 41.9 54.4 69.1 85.009 55 23.3 32.4 43.5 57.3 74.3 94.0

TE 55

10 55 26.1 37.3 51.6 69.4 90.7 11411 55 28.2 40.4 55.8 75.0 97.8 12312 55 29.6 42.4 58.8 79.5 104 13213 55 34.3 49.5 69.1 93.9 124 158

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.08 1.15 1.22 1.29 1.38

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.96 1.00 1.02 1.10 1.18 1.25 1.34

Distributer correction factor, fp SI units R452APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.96 0.95 0.94

1.5 0.95 0.94 0.94 0.93 0.92 0.90

2 0.93 0.92 0.92 0.91 0.90 0.87

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R452APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9325 0.94 0.94 0.93 0.92 0.90 0.8930 0.93 0.92 0.92 0.90 0.88 0.86

Calculated at 90 °F condensing temperature.

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 0.74 1.06 1.42 1.83 2.26 2.4701 135 1.35 1.95 2.63 3.39 4.19 4.5702 135 1.89 2.75 3.73 4.80 5.88 6.3703 135 2.32 3.35 4.53 5.85 7.25 7.9304 135 2.98 4.43 6.11 8.04 10.1 11.0

TE 1205 135 3.44 4.92 6.65 8.70 11.1 12.406 135 4.18 6.13 8.48 11.4 14.8 16.707 135 5.15 7.18 9.70 12.9 16.9 19.1

TE 2008 135 6.17 8.87 12.1 16.1 20.7 23.109 135 6.35 9.11 12.5 16.9 22.3 25.4

TE 55

10 135 6.97 10.4 14.9 20.6 27.4 31.011 135 7.53 11.3 16.1 22.2 29.5 33.312 135 7.89 11.8 17.0 23.6 31.5 35.813 135 9.08 13.7 19.8 27.8 37.5 42.6

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 18

Page 19: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 65 0.56 0.71 0.89 1.10 1.3301 65 1.03 1.30 1.64 2.02 2.4402 65 1.44 1.82 2.29 2.84 3.4303 65 1.78 2.28 2.90 3.63 4.4104 65 2.33 3.01 3.86 4.88 5.98

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 105 0.49 0.62 0.80 1.01 1.2501 105 0.89 1.13 1.45 1.84 2.3002 105 1.22 1.57 2.03 2.58 3.2303 105 1.52 1.95 2.51 3.21 4.0204 105 1.94 2.51 3.27 4.23 5.37

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 85 0.54 0.68 0.87 1.08 1.3301 85 0.98 1.25 1.58 1.99 2.4502 85 1.36 1.74 2.21 2.79 3.4303 85 1.68 2.16 2.78 3.52 4.3504 85 2.18 2.82 3.66 4.68 5.87

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R452A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 125 0.42 0.54 0.69 0.88 1.1001 125 0.75 0.97 1.25 1.60 2.0102 125 1.04 1.34 1.74 2.24 2.8303 125 1.30 1.66 2.14 2.74 3.4604 125 1.64 2.11 2.74 3.56 4.57

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 20 1.95 2.58 3.37 4.32 4.8101 20 3.56 4.72 6.19 7.93 8.8502 20 4.96 6.59 8.68 11.1 12.403 20 6.13 8.27 11.0 14.2 15.904 20 8.03 10.9 14.7 19.2 21.6

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 40 1.70 2.28 3.05 4.01 4.5501 40 3.09 4.16 5.58 7.37 8.3602 40 4.27 5.78 7.80 10.3 11.703 40 5.30 7.15 9.67 12.9 14.704 40 6.78 9.24 12.6 17.1 19.6

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 30 1.86 2.48 3.28 4.27 4.8001 30 3.39 4.53 6.02 7.84 8.8302 30 4.70 6.31 8.42 11.0 12.403 30 5.81 7.85 10.6 13.9 15.704 30 7.52 10.3 14.0 18.6 21.2

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R452A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 50 1.49 2.0 2.70 3.58 4.0701 50 2.69 3.64 4.93 6.56 7.4802 50 3.71 5.04 6.86 9.20 10.503 50 4.63 6.22 8.43 11.3 12.904 50 5.86 7.94 10.9 14.8 17.1

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.10 1.17 1.25 1.33 1.41

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.96 1.00 1.02 1.10 1.18 1.26 1.37

Distributer correction factor, fp* SI units R452APressure drop

[bar] ∆p

Evap. temp. [°C]-60 -50 -40 -30 -25

Correction factor0 1 1 1 1 11 0.97 0.97 0.96 0.96 0.96

1.5 0.95 0.95 0.95 0.94 0.94

2 0.93 0.93 0.93 0.93 0.92

* Calculated at 32 °C condensing temperature.

Distributer correction factor, fp* US units R452APressure drop

[psi] ∆p

Evap. temp. [°F]

-75 -60 -45 -30 -15

Correction factor0 1 1 1 1 1

15 0.97 0.97 0.96 0.96 0.9625 0.94 0.94 0.94 0.94 0.9330 0.93 0.93 0.93 0.92 0.92

* Calculated at 90 °F condensing temperature.

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 19

Page 20: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 3.68 4.77 5.91 6.93 7.54 7.3001 25 6.76 8.76 10.8 12.7 13.7 13.202 25 9.49 12.3 15.1 17.6 18.8 17.903 25 12.0 15.6 19.4 22.6 24.4 23.304 25 16.1 21.1 26.3 30.8 33.1 31.2

TE 1205 25 20.7 28.0 36.0 43.9 48.9 47.206 25 24.9 34.1 44.5 55.0 61.7 59.607 25 32.5 43.9 57.6 71.9 81.4 78.3

TE 2008 25 35.7 48.4 62.2 75.2 82.9 79.709 25 39.5 54.2 71.3 88.4 100 97.0

TE 55

10 25 46.5 64.9 86.1 108 124 12511 25 51.1 71.2 94.4 118 136 13512 25 54.8 76.8 103 130 151 15213 25 66.5 93.7 126 159 183 181

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.09 1.16 1.23 1.30 1.37

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 1.05 1.39 1.74 2.03 2.11 2.0201 75 1.93 2.56 3.20 3.70 3.83 3.6502 75 2.71 3.58 4.45 5.11 5.21 4.9303 75 3.42 4.56 5.71 6.61 6.78 6.4304 75 4.59 6.17 7.76 8.98 9.15 8.62

TE 1205 75 5.94 8.23 10.8 13.0 13.8 13.106 75 7.14 10.1 13.4 16.4 17.4 16.507 75 9.36 13.1 17.4 21.6 22.9 21.7

TE 2008 75 10.2 14.2 18.6 22.2 23.2 22.009 75 11.3 16.1 21.5 26.4 28.2 26.8

TE 55

10 75 13.4 19.2 26.0 32.4 35.6 34.611 75 14.7 21.1 28.5 35.5 38.8 37.512 75 15.8 22.8 31.1 39.2 43.4 42.213 75 19.2 27.9 38.2 47.9 52.3 50.3

Distributer correction factor, fp SI units R404A/R507Pressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.95 0.94 0.92

1.5 0.94 0.94 0.94 0.93 0.91 0.88

2 0.92 0.92 0.91 0.90 0.88 0.84

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R404A/R507Pressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.93 0.9225 0.94 0.93 0.92 0.91 0.89 0.8730 0.92 0.92 0.91 0.89 0.86 0.84

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 3.45 4.55 5.78 7.05 8.12 8.6101 35 6.34 8.37 10.6 12.9 14.8 15.602 35 8.90 11.8 14.9 18.0 20.4 21.303 35 11.1 14.8 18.8 22.9 26.3 28.004 35 14.9 19.9 25.5 31.2 35.7 37.1

TE 1205 35 18.7 25.3 33.3 42.3 50.5 54.406 35 22.3 30.7 41.0 52.7 63.6 68.707 35 27.8 37.9 50.7 66.0 81.2 89.1

TE 2008 35 32.4 44.3 58.4 73.6 86.9 92.609 35 34.9 48.2 64.6 83.5 101 110

TE 55

10 35 40.6 57.7 78.7 103 126 14111 35 44.3 62.9 85.7 112 137 15312 35 47.1 67.2 92.1 121 150 17013 35 56.0 80.5 110 146 181 203

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 0.98 1.33 1.72 2.11 2.39 2.4401 95 1.80 2.44 3.16 3.87 4.37 4.4402 95 2.53 3.43 4.42 5.37 5.98 6.0403 95 3.16 4.31 5.60 6.86 7.71 7.8004 95 4.21 5.81 7.60 9.34 10.5 10.5

TE 1205 95 5.29 7.42 10.0 12.9 15.1 15.406 95 6.32 9.02 12.4 16.1 19.0 19.507 95 7.90 11.1 15.3 20.3 24.5 25.3

TE 2008 95 9.18 13.0 17.5 22.3 25.8 26.309 95 9.89 14.1 19.5 25.5 30.4 31.3

TE 55

10 95 11.5 17.0 23.8 31.5 38.3 40.111 95 12.6 18.5 25.9 34.2 41.4 43.412 95 13.4 19.8 27.9 37.2 45.7 48.213 95 15.9 23.7 33.6 45.0 54.9 57.5

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.96 1.00 1.03 1.11 1.20 1.28 1.37

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 20

Page 21: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 3.08 4.11 5.32 6.67 8.02 9.0501 45 5.65 7.57 9.81 12.3 14.7 16.502 45 7.94 10.7 13.8 17.2 20.4 22.703 45 9.85 13.2 17.2 21.6 25.9 29.004 45 13.0 17.7 23.3 29.4 35.4 39.4

TE 1205 45 16.1 21.9 29.1 37.8 47.4 55.306 45 19.1 26.4 35.6 46.9 59.6 70.107 45 23.1 31.4 42.0 55.7 71.9 86.8

TE 2008 45 28.0 38.4 51.3 66.6 82.8 95.209 45 29.5 40.7 55.0 73.0 93.2 110

TE 55

10 45 33.5 48.5 67.4 90.6 117 14011 45 36.2 52.5 72.9 97.9 126 15012 45 38.3 55.5 77.5 104 136 16513 45 44.6 65.3 91.8 125 162 196

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.09 1.16 1.23 1.30 1.37

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 0.86 1.18 1.57 2.00 2.41 2.5601 115 1.58 2.18 2.90 3.69 4.42 4.6902 115 2.22 3.07 4.07 5.15 6.11 6.4303 115 2.75 3.81 5.07 6.48 7.77 8.2104 115 3.63 5.11 6.88 8.84 10.6 11.2

TE 1205 115 4.48 6.29 8.60 11.4 14.4 15.606 115 5.29 7.59 10.6 14.3 18.2 19.807 115 6.41 8.97 12.4 16.9 22.1 24.3

TE 2008 115 7.79 11.1 15.2 20.1 25.1 26.909 115 8.19 11.7 16.3 22.2 28.5 31.1

TE 55

10 115 9.25 14.0 20.1 27.6 35.9 39.511 115 10.0 15.1 21.7 29.8 38.6 42.412 115 10.6 16.0 23.1 32.0 41.9 46.313 115 12.3 18.6 27.3 38.0 49.9 55.1

Distributer correction factor, fp SI units R404A/R507Pressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.95 0.94 0.92

1.5 0.94 0.94 0.94 0.93 0.91 0.88

2 0.92 0.92 0.91 0.90 0.88 0.84

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R404A/R507Pressure drop

[psi] ∆p

Evap. temp. [°C]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.93 0.9225 0.94 0.93 0.92 0.91 0.89 0.8730 0.92 0.92 0.91 0.89 0.86 0.84

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 2.60 3.50 4.57 5.83 7.20 8.5001 55 4.76 6.44 8.45 10.8 13.3 15.702 55 6.69 9.10 11.9 15.2 18.6 21.703 55 8.24 11.1 14.6 18.7 23.2 27.304 55 10.8 14.9 19.8 25.6 31.9 37.5

TE 1205 55 13.3 16.0 23.8 31.1 40.0 49.406 55 15.5 21.4 28.9 38.4 50.3 63.107 55 18.6 24.9 33.0 43.4 56.9 72.4

TE 2008 55 23.1 31.5 42.1 55.4 71.1 86.809 55 23.8 32.6 43.9 58.6 77.2 97.3

TE 55

10 55 25.7 38.1 53.8 73.7 97.8 12411 55 27.7 41.0 57.8 79.0 105 13212 55 28.9 42.9 60.8 83.6 112 14213 55 33.1 49.6 70.7 97.9 131 168

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 0.70 0.98 1.31 1.71 2.14 2.3401 135 1.29 1.80 2.42 3.16 3.95 4.3102 135 1.81 2.55 3.43 4.45 5.52 5.9803 135 2.22 3.10 4.18 5.47 6.87 7.5004 135 2.90 4.14 5.67 7.50 9.47 10.3

TE 1205 135 3.57 4.98 6.77 9.07 11.9 13.406 135 4.15 5.93 8.24 11.3 15.1 17.107 135 4.99 6.87 9.33 12.6 16.9 19.3

TE 2008 135 6.21 8.76 12.0 16.2 21.2 23.709 135 6.38 9.00 12.5 17.2 23.1 26.3

TE 55

10 135 6.78 10.5 15.4 21.8 29.5 33.511 135 7.29 11.3 16.5 23.3 31.5 35.712 135 7.61 11.8 17.4 24.6 33.6 38.413 135 8.67 13.6 20.2 28.8 39.5 45.2

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.96 1.00 1.03 1.11 1.20 1.28 1.37

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 21

Page 22: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 20 2.01 2.87 3.92 5.12 5.7301 20 3.66 5.25 7.21 9.41 10.502 20 5.09 7.33 10.1 13.2 14.703 20 6.38 9.22 12.8 16.8 18.804 20 8.32 12.2 17.1 22.8 25.6

TE 1205 20 10.3 14.7 20.5 27.3 30.806 20 12.8 18.6 26.2 35.5 40.507 20 16.5 24.0 33.9 46.1 52.6

TE 55

9B 20 20.6 29.2 40.1 52.4 58.510 20 24.1 34.7 49.0 66.8 76.611 20 26.6 38.4 54.1 73.8 84.612 20 28.6 41.3 58.5 80.2 92.313 20 34.7 50.5 71.9 99.2 114

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.09 1.16 1.23 1.30 1.37

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 65 0.59 0.79 1.03 1.30 1.5801 65 1.07 1.44 1.89 2.39 2.9102 65 1.49 2.01 2.64 3.35 4.0603 65 1.87 2.53 3.34 4.25 5.1904 65 2.44 3.35 4.46 5.74 7.07

TE 1205 65 3.01 4.06 5.36 6.87 8.5206 65 3.77 5.13 6.85 8.90 11.207 65 4.87 6.63 8.87 11.6 14.6

TE 55

9B 65 6.04 8.08 10.6 13.4 16.310 65 7.10 9.62 12.8 16.8 21.311 65 7.84 10.6 14.2 18.5 23.512 65 8.45 11.5 15.4 20.1 25.613 65 10.3 14.1 18.9 24.9 31.9

Distributer correction factor, fp SI units R404A/R507Pressure drop

[bar] ∆p

Evap. temp. [°C]-60 -50 -40 -30 -25

Correction factor0 1 1 1 1 11 0.97 0.96 0.96 0.96 0.96

1.5 0.95 0.95 0.94 0.94 0.94

2 0.93 0.93 0.92 0.92 0.92

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R404A/R507Pressure drop

[psi] ∆p

Evap. temp. [°F]

-75 -60 -45 -30 -15

Correction factor0 1 1 1 1 1

15 0.96 0.96 0.96 0.96 0.9625 0.94 0.94 0.94 0.93 0.9330 0.93 0.93 0.92 0.92 0.92

Calculated at 90 °F condensing temperature.

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.96 1.00 1.03 1.11 1.20 1.28 1.37

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 30 1.88 2.72 3.79 5.04 5.7201 30 3.42 4.97 6.96 9.29 10.502 30 4.72 6.93 9.76 13.1 14.803 30 5.87 8.63 12.2 16.5 18.704 30 7.54 11.3 16.2 22.3 25.5

TE 1205 30 9.33 13.6 19.3 26.3 30.206 30 11.4 16.9 24.4 33.9 39.307 30 14.4 21.3 30.8 43.0 49.9

TE 55

9B 30 18.5 26.6 37.3 50.0 56.610 30 21.2 31.0 44.3 61.7 71.711 30 23.2 34.0 48.7 67.7 78.612 30 24.8 36.3 52.1 72.8 84.813 30 29.5 43.6 61.0 88.6 104

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 85 0.55 0.75 0.99 1.27 1.5801 85 1.00 1.36 1.81 2.34 2.9102 85 1.38 1.90 2.54 3.29 4.0903 85 1.71 2.36 3.18 4.13 5.1804 85 2.20 3.08 4.20 5.55 7.06

TE 1205 85 2.72 3.73 5.02 6.57 8.3506 85 3.34 4.63 6.30 8.39 10.907 85 4.22 5.85 7.97 10.6 13.8

TE 55

9B 85 5.39 7.32 9.73 12.6 15.710 85 6.18 8.49 11.5 15.3 19.811 85 6.79 9.32 12.6 16.8 21.712 85 7.25 9.97 13.5 18.0 23.513 85 8.66 12.0 16.3 21.9 28.6

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 22

Page 23: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 40 1.69 2.48 3.51 4.75 5.4301 40 3.06 4.53 6.44 8.76 10.002 40 4.21 6.29 9.03 12.4 14.203 40 5.17 7.75 11.2 15.4 17.704 40 6.52 9.96 14.7 20.8 24.1

TE 1205 40 8.10 12.0 17.4 24.2 28.0

06 40 9.70 14.6 21.5 30.7 36.007 40 12.0 18.1 26.6 37.9 44.6

TE 55

9B 40 15.8 23.1 33.0 45.1 51.810 40 17.7 26.2 38.2 54.0 63.311 40 19.2 28.6 41.6 58.8 68.912 40 20.4 30.3 44.2 62.7 73.613 40 23.8 35.7 52.3 74.8 88.3

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 105 0.49 0.67 0.90 1.18 1.4901 105 0.88 1.22 1.65 2.17 2.7502 105 1.21 1.70 2.31 3.05 3.8803 105 1.49 2.09 2.86 3.80 4.8604 105 1.88 2.68 3.73 5.06 6.60

TE 1205 105 2.33 3.25 4.43 5.91 7.6606 105 2.79 3.93 5.46 7.41 9.8007 105 3.44 4.84 6.72 9.13 12.1

TE 55

9B 105 4.52 6.23 8.43 11.1 14.210 105 5.06 7.05 9.68 13.1 17.211 105 5.51 7.68 10.6 14.2 18.712 105 5.83 8.14 11.2 15.1 20.013 105 6.81 9.56 13.2 18.0 23.9

Capacity in kW. Range: -60 – -25 °C.Opening superheat sh = 4 K SI units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 50 1.47 2.18 3.13 4.29 4.9501 50 2.64 3.97 5.73 7.92 9.1502 50 3.61 5.50 8.04 11.2 13.003 50 4.36 6.66 9.81 13.8 16.104 50 5.35 8.39 12.7 18.4 21.7

TE 1205 50 6.68 10.1 14.9 21.1 24.806 50 7.75 12.0 18.1 26.3 31.207 50 9.28 14.4 21.6 31.5 37.4

TE 55

9B 50 12.7 18.9 27.5 38.5 44.610 50 13.8 21.0 31.1 44.7 52.811 50 14.9 22.7 33.6 48.3 57.012 50 15.6 23.8 35.4 51.0 60.313 50 17.8 27.4 41.0 59.5 70.8

Capacity in TR. Range: -75 – -15 °F.Opening superheat sh = 7.2 °F. US units R404A/R507

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 125 0.41 0.58 0.79 1.04 1.3301 125 0.74 1.05 1.44 1.92 2.4702 125 1.02 1.45 2.01 2.70 3.5003 125 1.23 1.75 2.44 3.30 4.3104 125 1.50 2.19 3.13 4.34 5.81

TE 1205 125 1.87 2.65 3.70 5.02 6.6106 125 2.15 3.12 4.42 6.13 8.2707 125 2.56 3.71 5.25 7.29 9.85

TE 55

9B 125 3.51 4.93 6.80 9.14 11.910 125 3.81 5.43 7.60 10.4 13.911 125 4.11 5.87 8.21 11.2 15.012 125 4.30 6.15 8.61 11.8 15.913 125 4.89 7.04 9.92 13.7 18.5

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.97 1.00 1.09 1.16 1.23 1.30 1.37

Distributer correction factor, fp SI units R404A/R507Pressure drop

[bar] ∆p

Evap. temp. [°C]-60 -50 -40 -30 -25

Correction factor0 1 1 1 1 11 0.97 0.96 0.96 0.96 0.96

1.5 0.95 0.95 0.94 0.94 0.94

2 0.93 0.93 0.92 0.92 0.92

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R404A/R507Pressure drop

[psi] ∆p

Evap. temp. [°F]

-75 -60 -45 -30 -15

Correction factor0 1 1 1 1 1

15 0.96 0.96 0.96 0.96 0.9625 0.94 0.94 0.94 0.93 0.9330 0.93 0.93 0.92 0.92 0.92

Calculated at 90 °F condensing temperature.

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.96 1.00 1.03 1.11 1.20 1.28 1.37

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 23

Page 24: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 4.53 5.73 7.00 8.17 8.87 8.5601 25 8.33 10.5 12.9 15.0 16.2 15.502 25 11.7 14.8 18.0 20.8 22.3 21.203 25 14.9 18.8 23.1 26.8 28.9 27.504 25 19.9 25.5 31.4 36.6 39.3 37.0

TE 1205 25 24.4 31.2 38.8 46.0 50.7 49.406 25 31.4 40.5 50.8 60.9 67.5 65.707 25 41.2 53.1 67.0 80.9 90.4 88.3

TE 2008 25 54.5 70.9 88.6 104 113 10509 25 60.1 79.7 102 123 136 127

TE 55

10 25 65.5 86.3 110 133 150 14911 25 72.3 95.2 121 147 165 16312 25 78.1 103 132 161 183 18313 25 95.8 127 163 199 225 221

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.05 1.10 1.14 1.19 1.23

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 1.28 1.66 2.05 2.38 2.47 2.3501 75 2.35 3.05 3.77 4.35 4.49 4.2602 75 3.30 4.28 5.26 6.02 6.16 5.8003 75 4.20 5.45 6.76 7.80 8.01 7.5604 75 5.64 7.39 9.20 10.6 10.8 10.2

TE 1205 75 6.93 9.08 11.4 13.5 14.2 13.606 75 8.91 11.8 15.1 17.9 18.9 18.107 75 11.7 15.5 19.9 24.0 25.5 24.4

TE 2008 75 15.5 20.7 26.2 30.5 31.1 29.109 75 17.1 23.4 30.4 36.4 37.6 35.1

TE 55

10 75 18.7 25.2 32.6 39.4 42.5 41.011 75 20.6 27.9 36.0 43.4 46.6 44.812 75 22.3 30.3 39.4 48.0 52.1 50.413 75 27.4 37.4 48.8 59.3 63.6 60.8

Distributer correction factor, fp SI units R22Pressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.95 0.95 0.94 0.93 0.91

1.5 0.93 0.93 0.92 0.91 0.90 0.86

2 0.91 0.90 0.90 0.88 0.86 0.81

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R22Pressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.95 0.95 0.95 0.94 0.92 0.9125 0.92 0.92 0.91 0.89 0.87 0.8430 0.91 0.90 0.89 0.87 0.84 0.80

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 4.67 5.93 7.34 8.80 10.0 10.601 35 8.56 10.9 13.5 16.2 18.4 19.302 35 12.0 15.3 18.9 22.6 25.4 26.503 35 15.2 19.3 24.0 28.8 32.7 34.204 35 20.1 26.0 32.5 39.2 44.5 46.2

TE 1205 35 24.6 31.2 39.0 47.6 55.3 59.506 35 31.2 40.1 50.8 62.7 73.6 79.507 35 40.3 51.3 64.7 80.1 95.0 103

TE 2008 35 54.1 70.2 88.9 109 125 13009 35 58.0 76.4 98.7 124 146 155

TE 55

10 35 62.5 83.4 108 136 162 17811 35 68.6 91.4 118 149 177 19412 35 73.3 98.2 128 162 194 21513 35 88.3 119 156 197 237 260

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 1.33 1.73 2.18 2.63 2.96 3.0201 95 2.43 3.17 4.01 4.82 5.40 5.4902 95 3.41 4.46 5.61 6.71 7.44 7.5103 95 4.30 5.62 7.12 8.58 9.59 9.7204 95 5.72 7.57 9.67 11.7 13.0 13.1

TE 1205 95 6.98 9.08 11.6 14.3 16.4 16.906 95 8.85 11.7 15.1 18.9 21.9 22.607 95 11.5 15.0 19.3 24.3 28.4 29.5

TE 2008 95 15.4 20.5 26.5 32.6 36.6 36.909 95 16.5 22.3 29.6 37.4 43.2 44.0

TE 55

10 95 17.8 24.4 32.5 41.2 48.5 50.611 95 19.5 26.8 35.5 45.0 52.9 55.012 95 20.8 28.8 38.4 49.1 58.5 61.213 95 25.1 34.9 46.8 60.0 71.0 73.8

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.07 1.12 1.17 1.22

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 24

Page 25: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 4.71 5.98 7.45 9.06 10.6 11.801 45 8.62 11.0 13.7 16.67 19.5 21.602 45 12.1 15.4 19.3 23.4 27.2 29.803 45 15.2 19.3 24.1 29.4 34.5 38.104 45 20.0 25.7 32.6 40.1 47.1 51.9

TE 1205 45 24.2 30.3 37.8 46.6 55.8 63.706 45 30.3 38.6 48.9 61.1 74.2 85.307 45 38.8 48.4 60.4 75.1 91.7 107

TE 2008 45 52.6 67.8 86.0 107 127 14209 45 55.0 71.5 92.1 117 144 165

TE 55

10 45 58.0 78.1 102 132 163 19011 45 63.2 85.0 112 143 176 20512 45 67.0 90.4 119 154 191 22513 45 79.1 107 143 185. 231 271

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.05 1.10 1.14 1.19 1.23

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 1.34 1.74 2.22 2.73 3.21 3.3901 115 2.45 3.20 4.08 5.03 5.88 6.1902 115 3.42 4.50 5.74 7.04 8.16 8.5303 115 4.30 5.61 7.17 8.85 10.4 10.904 115 5.65 7.50 9.70 12.1 14.2 14.8

TE 1205 115 6.85 8.79 11.2 14.0 16.9 18.106 115 8.58 11.2 14.5 18.5 22.6 24.307 115 11.0 14.0 17.8 22.7 27.9 30.3

TE 2008 115 14.9 19.7 25.5 32.2 38.4 40.609 115 15.5 20.7 27.4 35.5 43.8 47.0

TE 55

10 115 16.3 22.7 30.7 40.1 49.8 53.911 115 17.8 24.7 33.3 43.5 53.9 58.312 115 18.8 26.2 35.6 46.9 58.7 63.913 115 22.2 31.2 42.6 56.4 70.7 76.8

Distributer correction factor, fp SI units R22Pressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.95 0.95 0.94 0.93 0.91

1.5 0.93 0.93 0.92 0.91 0.90 0.86

2 0.91 0.90 0.90 0.88 0.86 0.81

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R22Pressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.95 0.95 0.95 0.94 0.92 0.9125 0.92 0.92 0.91 0.89 0.87 0.8430 0.91 0.90 0.89 0.87 0.84 0.80

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 4.68 5.92 7.38 9.02 10.74 12.301 55 8.55 10.9 13.6 16.7 19.8 22.602 55 11.9 15.3 19.2 23.4 27.8 31.403 55 14.9 18.9 23.6 29.0 34.6 39.604 55 19.4 25.0 31.8 40.0 47.5 54.2

TE 1205 55 23.5 29.0 35.8 44.0 53.3 62.706 55 29.1 36.5 45.9 57.4 70.7 84.207 55 37.0 45.0 55.1 68.0 83.5 101

TE 2008 55 50.5 64.3 81.1 101 123 14309 55 51.7 66.0 84.1 107 134 161

TE 55

10 55 52.5 71.1 94.3 123 155 18711 55 56.8 76.9 102 132 167 20112 55 59.7 81.0 108 141 179 21813 55 69.1 94.6 127 167 213 260

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 1.32 1.72 2.18 2.71 3.25 3.5001 135 2.42 3.15 4.03 5.01 6.00 6.4402 135 3.38 4.43 5.68 7.05 8.39 8.9403 135 4.22 5.47 6.98 8.71 10.5 11.204 135 5.48 7.24 9.40 11.9 14.4 15.4

TE 12

05 135 6.61 8.32 10.5 13.1 16.1 17.6

06 135 8.17 10.5 13.5 17.2 21.5 23.6

07 135 10.4 12.8 16.0 20.2 25.2 27.9

TE 2008 135 14.2 18.5 23.8 30.3 37.2 40.409 135 14.5 18.9 24.6 32.0 40.7 45.0

TE 55

10 135 14.5 20.4 27.8 37.0 47.4 52.511 135 15.7 22.0 30.0 39.9 50.9 56.412 135 16.5 23.1 31.7 42.4 54.7 60.913 135 19.0 26.9 37.2 50.2 65.1 72.6

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.07 1.12 1.17 1.22

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 25

Page 26: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -60°C – -25°C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 20 2.63 3.66 4.87 6.18 6.8401 20 4.80 6.71 8.95 11.4 12.602 20 6.68 9.38 12.6 15.9 17.603 20 8.39 11.9 15.9 20.3 22.504 20 11.0 15.7 21.4 27.6 30.6

TE 1205 20 12.2 16.9 22.5 28.8 32.006 20 15.9 22.1 29.9 38.7 43.307 20 20.8 29.0 39.2 51.1 57.3

TE 55

9B 20 30.7 41.9 54.5 67.2 72.910 20 36.3 50.4 67.5 86.3 95.711 20 40.6 55.9 74.9 95.9 10612 20 43.3 60.4 81.4 104 11713 20 53.1 74.6 101 131 147

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30

Correction factor 0.98 1.00 1.05 1.10 1.14 1.19 1.23

Capacity in TR. Range: -75°F – -15°F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 65 0.76 1.00 1.27 1.57 1.8801 65 1.38 1.83 2.34 2.89 3.4502 65 1.93 2.56 3.28 4.06 4.8203 65 2.43 3.23 4.16 5.17 6.1804 65 3.19 4.29 5.58 7.00 8.41

TE 1205 65 3.53 4.61 5.89 7.31 8.8006 65 4.60 6.06 7.81 9.80 11.907 65 6.04 7.96 10.3 12.9 15.8

TE 55

9B 65 8.89 11.5 14.4 17.4 20.210 65 10.6 13.9 17.8 22.1 26.511 65 11.7 15.4 19.7 24.6 29.512 65 12.6 16.7 21.4 26.8 32.313 65 15.5 20.6 26.7 33.6 40.7

Distributer correction factor, fp SI units R22Pressure drop

[bar] ∆p

Evap. temp. [°C]-60 -50 -40 -30 -25

Correction factor

0 1 1 1 1 11 0.96 0.96 0.96 0.95 0.95

1.5 0.94 0.93 0.93 0.93 0.932 0.91 0.91 0.91 0.90 0.90

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R22Pressure drop

[psi] ∆p

Evap. temp. [°F]

-75 -60 -45 -30 -15

Correction factor

0 1 1 1 1 115 0.96 0.96 0.95 0.95 0.9525 0.93 0.93 0.92 0.92 0.9230 0.91 0.91 0.91 0.90 0.90

Calculated at 90 °F condensing temperature.

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50

Correction factor 0.97 1.00 1.02 1.07 1.12 1.17 1.22

Capacity in kW. Range: -60°C – -25°C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 30 2.70 3.78 5.07 6.52 7.2801 30 4.90 6.90 9.30 12.0 13.402 30 6.78 9.61 13.0 16.8 18.803 30 8.43 12.0 16.4 21.3 23.804 30 10.8 15.7 21.8 28.8 32.4

TE 1205 30 12.1 16.9 22.8 29.7 33.406 30 15.6 21.8 29.9 39.5 44.807 30 19.9 28.0 38.6 51.2 58.1

TE 55

9B 30 30.0 41.3 54.6 68.7 75.510 30 34.7 48.7 66.0 86.0 96.411 30 38.1 53.6 72.8 95.0 10712 30 40.8 57.5 78.5 103 11613 30 49.1 69.7 95.9 127 143

Capacity in TR. Range: -75°F – -15°F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 85 0.78 1.03 1.33 1.66 2.0101 85 1.42 1.89 2.44 3.05 3.7102 85 1.96 2.63 3.41 4.29 5.2003 85 2.44 3.29 4.29 5.41 6.6004 85 3.15 4.29 5.68 7.27 8.95

TE 1205 85 3.51 4.63 5.98 7.53 9.2306 85 4.49 5.98 7.82 9.97 12.407 85 5.77 7.69 10.1 12.9 16.1

TE 55

9B 85 8.69 11.4 14.4 17.7 21.010 85 10.1 13.4 17.3 21.9 26.811 85 11.1 14.7 19.1 24.2 29.612 85 11.9 15.8 20.6 26.1 32.113 85 14.3 19.2 25.1 32.1 39.8

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 26

Page 27: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -60°C – -25°C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 40 2.72 3.82 5.16 6.70 7.5301 40 4.92 6.96 9.45 12.3 13.902 40 6.76 9.66 13.2 17.3 19.503 40 8.31 11.9 16.5 21.7 24.504 40 10.5 15.3 21.6 29.1 33.1

TE 1205 40 11.8 16.5 22.5 29.7 33.606 40 14.8 21.0 29.1 39.1 44.607 40 18.6 26.4 36.8 49.6 56.8

TE 55

9B 40 28.6 39.8 53.2 68.0 75.310 40 32.3 45.8 62.7 82.7 93.511 40 35.3 50.1 68.7 90.8 10312 40 37.5 53.3 73.4 97.5 11113 40 44.2 63.3 88.0 118 135

Capacity in TR. Range: -75°F – -15°F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 105 0.79 1.05 1.35 1.70 2.0901 105 1.43 1.90 2.48 3.13 3.8402 105 1.96 2.64 3.46 4.39 5.4103 105 2.41 3.26 4.29 5.48 6.7904 105 3.03 4.17 5.60 7.29 9.16

TE 1205 105 3.40 4.51 5.87 7.48 9.2906 105 4.26 5.73 7.56 9.76 12.307 105 5.35 7.19 9.51 12.3 15.6

TE 55

9B 105 8.26 10.9 14.0 17.4 20.910 105 9.33 12.5 16.3 20.8 25.811 105 10.2 13.6 17.9 22.8 28.312 105 10.8 14.5 19.0 24.4 30.513 105 12.7 17.2 22.8 29.4 37.0

Capacity in kW. Range: -60°C – -25°C.Opening superheat sh = 4 K SI units R22

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-60 -50 -40 -30 -25

TE 5

0.5 50 2.71 3.81 5.17 6.75 7.6201 50 4.87 6.91 9.44 12.4 14.002 50 6.65 9.55 13.2 17.5 19.803 50 8.08 11.7 16.2 21.6 24.604 50 9.94 14.7 21.0 28.8 33.0

TE 1205 50 11.2 15.8 21.7 29.0 33.006 50 13.8 19.8 27.7 37.6 43.307 50 17.0 24.3 34.2 46.6 53.7

TE 55

9B 50 26.9 37.6 50.6 65.4 73.010 50 29.6 42.1 58.1 77.4 88.011 50 32.0 45.7 63.2 84.3 95.912 50 33.7 48.2 66.9 89.7 10213 50 38.8 56.1 78.6 107 122

Capacity in TR. Range: -75°F – -15°F.Opening superheat sh = 7.2 °F. US units R22

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-75 -60 -45 -30 -15

TE 5

0.5 125 0.78 1.04 1.35 1.71 2.1101 125 1.41 1.89 2.46 3.13 3.8802 125 1.92 2.60 3.43 4.40 5.4703 125 2.33 3.17 4.20 5.42 6.7904 125 2.86 3.97 5.39 7.11 9.08

TE 1205 125 3.21 4.29 5.62 7.22 9.0506 125 3.96 5.35 7.12 9.28 11.807 125 4.83 6.54 8.72 11.4 14.6

TE 55

9B 125 7.68 10.2 13.2 16.5 20.110 125 8.42 11.3 14.9 19.2 24.011 125 9.12 12.3 16.2 20.8 26.112 125 9.57 12.9 17.1 22.1 27.813 125 11.0 15.0 20.0 26.0 33.1

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30

Correction factor 0.98 1.00 1.05 1.10 1.14 1.19 1.23

Distributer correction factor, fp SI units R22Pressure drop

[bar] ∆p

Evap. temp. [°C]-60 -50 -40 -30 -25

Correction factor

0 1 1 1 1 11 0.96 0.96 0.96 0.95 0.95

1.5 0.94 0.93 0.93 0.93 0.932 0.91 0.91 0.91 0.90 0.90

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R22Pressure drop

[psi] ∆p

Evap. temp. [°F]

-75 -60 -45 -30 -15

Correction factor

0 1 1 1 1 115 0.96 0.96 0.95 0.95 0.9525 0.93 0.93 0.92 0.92 0.9230 0.91 0.91 0.91 0.90 0.90

Calculated at 90 °F condensing temperature.

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50

Correction factor 0.97 1.00 1.02 1.07 1.12 1.17 1.22

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 27

Page 28: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R513A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 0.60 0.81 1.06 1.30 1.43 1.4001 75 1.11 1.50 1.95 2.38 2.62 2.5502 75 1.55 2.10 2.73 3.32 3.62 3.5003 75 1.98 2.69 3.50 4.28 4.70 4.5604 75 2.67 3.64 4.76 5.84 6.39 6.17

TE 1205 75 3.24 4.33 5.62 6.95 7.79 7.6606 75 4.19 5.65 7.39 9.21 10.4 10.207 75 5.63 7.61 9.98 12.5 14.1 13.9

TE 2008 75 7.62 10.6 13.9 17.2 18.9 18.209 75 8.21 11.4 15.3 19.3 21.7 21.0

TE 55

10 75 9.29 13.1 17.8 22.8 26.0 25.611 75 10.3 14.6 19.8 25.3 28.7 28.212 75 11.2 15.9 21.7 27.9 32.1 31.713 75 13.9 19.9 27.2 35.0 39.8 39.0

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R513A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 0.60 0.82 1.09 1.39 1.67 1.7701 95 1.10 1.51 2.0 2.56 3.06 3.2302 95 1.53 2.11 2.81 3.58 4.25 4.4503 95 1.96 2.69 3.58 4.57 5.48 5.7604 95 2.61 3.62 4.85 6.24 7.47 7.83

TE 1205 95 3.19 4.28 5.64 7.23 8.82 9.4206 95 4.08 5.52 7.36 9.55 11.7 12.607 95 5.45 7.33 9.70 12.5 15.5 16.7

TE 2008 95 7.35 10.3 13.8 17.9 21.6 22.609 95 7.78 10.8 14.8 19.5 24.2 25.7

TE 55

10 95 8.51 12.3 17.2 23.1 29.0 31.111 95 9.39 13.6 19.0 25.5 31.9 34.112 95 10.1 14.7 20.6 27.9 35.2 37.913 95 12.3 18.0 25.4 34.5 43.4 46.5

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R513A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 2.12 2.79 3.56 4.37 5.02 5.1001 25 3.90 5.14 6.56 8.03 9.18 9.2902 25 5.47 7.21 9.19 11.2 12.7 12.803 25 6.99 9.22 11.8 14.4 16.5 16.604 25 9.39 12.5 16.0 19.7 22.5 22.5

TE 1205 25 11.4 14.9 18.9 23.3 27.0 27.906 25 14.7 19.3 24.8 30.8 36.0 37.107 25 19.8 26.0 33.4 41.5 48.7 50.5

TE 2008 25 26.8 36.0 46.7 57.8 66.4 66.109 25 28.8 38.8 50.9 64.2 75.3 76.4

TE 55

10 25 32.5 44.6 59.2 75.4 89.5 93.111 25 36.1 49.5 65.7 83.6 99.0 10312 25 39.1 53.8 71.9 92.1 110 11513 25 48.6 67.2 90.0 115 137 141

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R513A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 2.10 2.80 3.63 4.58 5.53 6.2201 35 3.86 5.15 6.68 8.42 10.1 11.402 35 5.40 7.22 9.38 11.8 14.1 15.703 35 6.90 9.19 11.9 15.0 18.1 20.304 35 9.20 12.4 16.2 20.5 24.7 27.6

TE 1205 35 11.2 14.7 18.8 23.7 28.9 33.206 35 14.4 18.9 24.5 31.2 38.4 44.207 35 19.2 25.1 32.3 41.0 50.5 58.7

TE 2008 35 25.9 35.0 46.0 58.6 71.2 79.709 35 27.4 37.0 49.0 63.4 78.9 90.5

TE 55

10 35 30.0 41.9 56.9 75.0 94.3 11011 35 33.1 46.2 62.8 82.7 104 12012 35 35.6 49.8 68.0 90.1 114 13413 35 43.4 61.1 83.8 111 141 164

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.13 1.18 1.24 1.31

Distributer correction factor, fp SI units R513APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.94 0.93 0.93 0.92 0.90 0.87

1.5 0.90 0.90 0.89 0.88 0.85 0.80

2 0.87 0.86 0.85 0.83 0.79 0.72

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R513APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.93 0.93 0.92 0.91 0.89 0.8725 0.89 0.88 0.87 0.85 0.81 0.7730 0.86 0.85 0.84 0.82 0.76 0.71

Calculated at 90 °F condensing temperature.

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.29

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 28

Page 29: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R513A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 0.57 0.79 1.07 1.39 1.74 1.9001 115 1.05 1.46 1.96 2.56 3.20 3.4902 115 1.47 2.04 2.76 3.60 4.47 4.8403 115 1.88 2.59 3.48 4.55 5.68 6.1904 115 2.47 3.45 4.69 6.18 7.76 8.46

TE 1205 115 3.04 4.07 5.37 6.98 8.83 9.7506 115 3.83 5.19 6.94 9.15 11.7 13.007 115 5.11 6.80 8.95 11.6 14.9 16.6

TE 2008 115 6.89 9.60 13.0 17.1 21.7 23.709 115 7.15 9.92 13.5 18.1 23.5 26.2

TE 55

10 115 7.45 11.0 15.7 21.7 28.5 31.911 115 8.16 12.0 17.2 23.7 31.2 34.812 115 8.69 12.8 18.4 25.6 34.0 38.113 115 10.4 15.5 22.3 31.2 41.5 46.5

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R513A

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 0.54 0.75 1.01 1.32 1.68 1.8701 135 0.98 1.37 1.85 2.44 3.10 3.4302 135 1.37 1.91 2.60 3.42 4.34 4.7903 135 1.75 2.42 3.26 4.28 5.44 6.0304 135 2.28 3.19 4.35 5.79 7.43 8.25

TE 1205 135 2.82 3.75 4.92 6.38 8.14 9.0906 135 3.51 4.72 6.29 8.29 10.7 12.107 135 4.69 6.14 7.96 10.3 13.1 14.8

TE 2008 135 6.29 8.72 11.8 15.5 19.9 22.209 135 6.43 8.82 11.9 15.9 20.9 23.7

TE 55

10 135 6.22 9.35 13.6 19.0 25.7 29.311 135 6.76 10.2 14.7 20.6 27.9 31.712 135 7.12 10.7 15.6 22.0 30.0 34.313 135 8.30 12.6 18.5 26.3 36.1 41.3

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R513A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 2.03 2.72 3.57 4.56 5.66 6.6901 45 3.72 5.0 6.56 8.40 10.4 12.302 45 5.20 7.01 9.21 11.8 14.5 17.003 45 6.65 8.89 11.6 14.9 18.5 21.804 45 8.78 11.9 15.7 20.2 25.2 29.7

TE 1205 45 10.8 14.0 18.0 22.9 28.6 34.406 45 13.6 17.9 23.3 30.0 37.8 45.907 45 18.1 23.5 30.2 38.4 48.1 58.8

TE 2008 45 24.5 33.0 43.5 56.1 70.3 83.709 45 25.5 34.2 45.3 59.2 75.8 92.6

TE 55

10 45 26.7 37.8 52.2 70.3 91.4 11311 45 29.2 41.4 57.2 76.9 100 12312 45 31.2 44.3 61.4 83.0 109 13513 45 37.3 53.3 74.3 101 133 165

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R513A

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 1.92 2.58 3.40 4.37 5.49 6.6401 55 3.51 4.73 6.24 8.05 10.1 12.202 55 4.90 6.63 8.76 11.3 14.2 17.003 55 6.27 8.39 11.0 14.2 17.8 21.504 55 8.18 11.1 14.7 19.1 24.2 29.4

TE 1205 55 10.1 13.1 16.8 21.3 26.7 32.706 55 12.6 16.5 21.4 27.6 35.0 43.507 55 16.9 21.6 27.3 34.5 43.3 53.6

TE 2008 55 22.6 30.4 40.0 51.6 65.3 79.909 55 23.2 30.9 40.7 53.0 68.2 85.7

TE 55

10 55 22.8 32.9 46.0 62.7 83.1 10611 55 24.9 35.8 50.0 68.2 90.3 11512 55 26.2 37.9 53.1 72.8 97.1 12413 55 30.7 44.7 63.1 87.0 117 150

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.13 1.18 1.24 1.31

Distributer correction factor, fp SI units R513APressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.94 0.93 0.93 0.92 0.90 0.87

1.5 0.90 0.90 0.89 0.88 0.85 0.80

2 0.87 0.86 0.85 0.83 0.79 0.72

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R513APressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.93 0.93 0.92 0.91 0.89 0.8725 0.89 0.88 0.87 0.85 0.81 0.7730 0.86 0.85 0.84 0.82 0.76 0.71

Calculated at 90 °F condensing temperature.

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.29

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 29

Page 30: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R134a

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 2.59 3.33 4.16 5.00 5.65 5.7201 25 4.76 6.12 7.65 9.18 10.3 10.402 25 6.69 8.60 10.7 12.8 14.4 14.403 25 8.55 11.0 13.8 16.5 18.6 18.704 25 11.5 14.9 18.7 22.5 25.4 25.4

TE 1205 25 15.2 19.3 24.1 29.0 33.0 33.606 25 19.7 25.2 31.6 38.4 43.9 44.807 25 26.3 33.8 42.6 51.9 59.5 60.8

TE 2008 25 30.2 39.1 49.3 59.8 67.8 68.309 25 34.8 45.4 58.0 71.5 82.4 84.0

TE 55

10 25 40.0 52.7 67.7 84.0 98.1 10211 25 44.6 58.7 75.4 93.4 109 11312 25 48.5 64.0 82.6 103 121 12713 25 60.6 80.4 104 130 152 156

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.06 1.12 1.17 1.22 1.28

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R134a

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 0.73 0.96 1.22 1.47 1.61 1.5701 75 1.35 1.78 2.25 2.70 2.94 2.8702 75 1.89 2.49 3.15 3.76 4.06 3.9503 75 2.42 3.19 4.06 4.87 5.27 5.1404 75 3.27 4.33 5.53 6.64 7.18 6.97

TE 1205 75 4.29 5.61 7.12 8.59 9.42 9.2606 75 5.57 7.32 9.36 11.4 12.6 12.407 75 7.47 9.85 12.7 15.5 17.1 16.8

TE 2008 75 8.57 11.4 14.6 17.7 19.3 18.809 75 9.88 13.3 17.3 21.3 23.6 23.1

TE 55

10 75 11.4 15.4 20.2 25.2 28.4 28.111 75 12.7 17.2 22.5 28.0 31.5 31.112 75 13.8 18.8 24.7 31.0 35.2 34.913 75 17.3 23.6 31.2 39.0 43.9 43.2

Distributer correction factor, fp SI units R134aPressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.93 0.93 0.92 0.92 0.90 0.87

1.5 0.90 0.89 0.88 0.87 0.84 0.79

2 0.86 0.85 0.84 0.82 0.79 0.71

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R134aPressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.93 0.93 0.92 0.91 0.89 0.8625 0.88 0.87 0.86 0.84 0.80 0.7630 0.86 0.85 0.83 0.81 0.75 0.70

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R134a

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 2.65 3.42 4.34 5.36 6.35 7.0301 35 4.86 6.29 7.98 9.85 11.6 12.802 35 6.81 8.83 11.2 13.8 16.2 17.703 35 8.70 11.3 14.3 17.6 20.8 22.904 35 11.6 15.2 19.3 24.0 28.4 31.1

TE 1205 35 15.3 19.5 24.5 30.3 36.1 40.206 35 19.6 25.1 31.9 39.8 47.8 53.607 35 26.1 33.3 42.1 52.5 63.2 71.1

TE 2008 35 30.3 39.2 50.0 62.3 74.4 82.409 35 34.1 44.4 57.3 72.6 88.3 99.3

TE 55

10 35 38.2 51.0 66.8 85.5 105 12111 35 42.3 56.4 73.9 94.4 116 13312 35 45.6 61.0 80.3 103 128 14813 35 56.0 75.3 99.4 128 159 182

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R134a

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 0.75 1.00 1.30 1.62 1.91 2.0001 95 1.38 1.84 2.38 2.97 3.49 3.6502 95 1.93 2.58 3.34 4.15 4.84 5.0303 95 2.47 3.29 4.26 5.33 6.24 6.5104 95 3.30 4.43 5.78 7.25 8.50 8.84

TE 1205 95 4.35 5.67 7.31 9.17 10.9 11.406 95 5.57 7.34 9.54 12.1 14.5 15.207 95 7.42 9.70 12.6 15.9 19.1 20.2

TE 2008 95 8.60 11.4 14.9 18.9 22.4 23.409 95 9.69 13.0 17.2 22.1 26.8 28.2

TE 55

10 95 10.8 14.9 20.1 26.6 32.1 34.311 95 12.0 16.5 22.2 28.9 35.4 37.712 95 113.0 17.9 24.2 31.6 39.1 41.913 95 15.9 22.1 29.9 39.3 48.5 51.7

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.27

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 30

Page 31: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R134a

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 2.64 3.42 4.37 5.49 6.70 7.8001 45 4.83 6.28 8.04 10.1 12.3 14.302 45 6.75 8.80 11.3 14.1 17.2 19.803 45 8.62 11.2 14.3 17.9 21.9 25.404 45 11.4 14.9 19.2 24.3 29.8 34.5

TE 1205 45 15.0 19.0 24.0 30.0 36.7 43.206 45 19.0 24.3 31.0 39.1 48.5 57.507 45 25.2 31.7 39.9 50.1 62.1 73.9

TE 2008 45 29.5 38.0 48.7 61.6 76.1 89.309 45 32.6 42.1 54.4 69.9 87.7 105

TE 55

10 45 35.1 47.5 63.1 82.6 105 12811 45 38.6 52.1 69.4 90.6 115 14012 45 41.4 56.0 74.7 98.1 126 15313 45 49.8 67.8 90.9 120 154 189

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.06 1.12 1.17 1.22 1.28

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R134a

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 0.75 1.00 1.31 1.67 2.06 2.2301 115 1.37 1.83 2.40 3.08 3.78 4.0802 115 1.91 2.57 3.37 4.31 5.26 5.6603 115 2.44 3.25 4.27 5.47 6.71 7.2504 115 3.23 4.34 5.75 7.42 9.14 9.87

TE 1205 115 4.25 5.51 7.12 9.10 11.3 12.306 115 5.38 7.04 9.21 11.9 15.0 16.407 115 7.12 9.15 11.8 15.2 19.1 20.9

TE 2008 115 8.34 11.1 14.5 18.8 23.4 25.409 115 9.19 12.2 16.2 21.3 27.1 29.8

TE 55

10 115 9.86 13.8 18.9 25.4 32.7 36.211 115 10.8 15.1 20.8 27.8 35.8 39.612 115 11.6 16.2 22.3 30.1 39.1 43.513 115 13.9 19.6 27.2 36.8 47.9 53.2

Distributer correction factor, fp SI units R134aPressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.93 0.93 0.92 0.92 0.90 0.87

1.5 0.90 0.89 0.88 0.87 0.84 0.79

2 0.86 0.85 0.84 0.82 0.79 0.71

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R134aPressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.93 0.93 0.92 0.91 0.89 0.8625 0.88 0.87 0.86 0.84 0.80 0.7630 0.86 0.85 0.83 0.81 0.75 0.70

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R134a

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 2.56 3.32 4.27 5.41 6.72 8.0601 55 4.68 6.09 7.84 9.95 12.4 14.802 55 6.52 8.54 11.0 14.0 17.3 20.603 55 8.34 10.8 13.8 17.5 21.8 26.104 55 10.9 14.3 18.5 23.7 29.6 35.7

TE 1205 55 14.4 18.0 22.6 28.3 35.2 42.806 55 18.0 22.8 29.0 36.8 46.4 56.907 55 23.8 29.4 36.6 45.8 57.3 70.4

TE 2008 55 28.1 35.9 45.9 58.4 73.4 89.409 55 30.5 38.9 49.9 64.2 82.0 102

TE 55

10 55 31.2 42.6 57.3 76.2 99.2 12511 55 34.0 46.5 62.6 83.1 108 13612 55 36.1 49.4 66.7 89.0 117 14813 55 42.7 58.7 79.8 107 141 179

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R134a

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 0.72 0.96 1.27 1.64 2.07 2.2901 135 1.32 1.76 2.33 3.02 3.81 4.2002 135 1.83 2.47 3.27 4.24 5.33 5.8603 135 2.34 3.11 4.09 5.31 6.71 7.4004 135 3.06 4.11 5.48 7.19 9.15 10.1

TE 1205 135 4.05 5.16 6.63 8.51 10.8 12.006 135 5.04 6.53 8.50 11.1 14.3 16.007 135 6.67 8.37 10.6 13.7 17.5 19.6

TE 2008 135 7.87 10.3 13.5 17.6 22.6 25.209 135 8.49 11.1 14.6 19.3 25.3 28.5

TE 55

10 135 8.57 12.1 16.9 23.2 30.8 35.011 135 9.34 13.2 18.4 25.2 33.5 38.012 135 9.89 14.0 19.6 27.0 36.2 41.213 135 11.6 16.6 23.4 32.4 43.6 49.8

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.27

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 31

Page 32: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407C

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 25 4.62 5.82 7.18 8.56 9.66 10.001 25 8.48 10.7 13.2 15.7 17.7 18.202 25 11.9 15.0 18.4 21.8 24.4 24.903 25 15.0 19.0 23.6 28.1 31.6 32.404 25 20.1 25.6 31.9 38.2 42.9 43.7

TE 1205 25 20.9 27.9 36.2 45.1 52.7 55.906 25 26.6 35.8 46.9 59.1 69.8 74.507 25 34.5 46.5 61.4 78.2 93.2 99.8

TE 2008 25 49.3 63.2 79.4 96.4 110 11409 25 54.3 70.6 90.4 112 131 138

TE 55

10 25 63.6 82.2 105 130 153 16611 25 70.1 90.5 115 143 168 18112 25 75.5 97.8 125 156 186 20213 25 92.1 120 154 192 228 246

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.12 1.18 1.23 1.28

Distributer correction factor, fp SI units R407CPressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.95 0.95 0.93

1.5 0.94 0.94 0.94 0.93 0.92 0.90

2 0.92 0.92 0.91 0.91 0.89 0.86

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R407CPressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9325 0.93 0.93 0.93 0.92 0.90 0.8830 0.92 0.92 0.91 0.90 0.88 0.86

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407C

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 35 4.54 5.77 7.22 8.82 10.4 11.501 35 8.34 10.6 13.3 16.2 19.0 20.902 35 11.7 14.9 18.6 22.7 26.4 28.703 35 14.7 18.7 23.5 28.8 33.8 37.004 35 19.4 25.0 31.7 39.1 46.0 50.2

TE 1205 35 20.2 26.7 34.7 44.2 54.0 61.606 35 25.4 33.9 44.7 57.6 71.3 82.107 35 32.2 42.6 56.3 73.2 91.7 107

TE 2008 35 47.0 60.3 76.7 95.6 114 12709 35 50.5 65.4 84.4 108 132 151

TE 55

10 35 58.3 76.3 98.9 126 155 18011 35 63.9 83.5 108 138 169 19612 35 68.2 89.4 116 149 185 21613 35 81.8 108 141 181 225 262

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407C

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 95 1.29 1.68 2.15 2.66 3.10 3.2501 95 2.37 3.09 3.95 4.88 5.68 5.9302 95 3.32 4.34 5.54 6.81 7.85 8.1503 95 4.16 5.45 7.00 8.67 10.1 10.504 95 5.52 7.30 9.46 11.8 13.7 14.3

TE 1205 95 5.74 7.80 10.4 13.5 16.4 17.506 95 7.21 9.92 13.5 17.7 21.8 23.307 95 9.15 12.5 17.0 22.5 28.2 30.3

TE 2008 95 13.4 17.6 22.9 29.0 34.4 36.109 95 14.4 19.1 25.4 32.9 40.2 42.9

TE 55

10 95 16.6 22.3 29.7 38.5 47.6 51.211 95 18.1 24.4 32.4 42.1 51.8 55.712 95 19.4 26.1 34.9 45.6 56.8 61.413 95 23.2 31.5 42.3 55.5 69.0 74.4

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.27

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407C

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 75 1.31 1.69 2.12 2.53 2.78 2.7801 75 2.41 3.11 3.89 4.63 5.07 5.0602 75 3.38 4.36 5.44 6.42 6.96 6.9103 75 4.27 5.54 6.96 8.29 9.05 9.0004 75 5.71 7.47 9.45 11.3 12.3 12.2

TE 1205 75 5.95 8.19 10.9 13.6 15.4 15.606 75 7.58 10.5 14.1 17.9 20.5 20.807 75 9.87 13.7 18.6 23.8 27.5 27.9

TE 2008 75 14.1 18.5 23.6 28.7 31.7 31.609 75 15.5 20.8 27.2 33.9 38.3 38.4

TE 55

10 75 18.2 24.1 31.3 39.1 45.2 46.311 75 20.1 26.6 34.5 43.0 49.6 50.612 75 21.6 28.8 37.6 47.3 55.1 56.613 75 26.5 35.3 46.3 58.3 67.5 68.8

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 32

Page 33: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407C

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 45 4.34 5.52 6.96 8.65 10.4 12.001 45 7.96 10.2 12.8 15.9 19.2 22.102 45 11.1 14.3 18.1 22.4 26.8 30.503 45 13.9 17.7 22.4 28.0 33.9 38.904 45 18.2 23.6 30.2 38.0 46.3 53.1

TE 1205 45 19.0 24.6 31.9 40.9 51.3 61.406 45 23.6 31.0 40.7 53.0 67.4 81.907 45 29.7 38.2 49.6 64.5 82.7 102

TE 2008 45 43.6 55.5 70.8 89.6 111 13009 45 45.8 58.7 75.6 97.4 123 149

TE 55

10 45 51.5 68.0 89.2 116 147 17911 45 56.0 73.9 97.0 126 160 19412 45 59.3 78.4 103 135 172 21113 45 69.8 92.7 123 161 207 253

Subcooling correction factor, fsub

Subcooling [K] 2 4 10 15 20 25 30Correction factor 0.98 1.00 1.07 1.12 1.18 1.23 1.28

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407C

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 115 1.22 1.60 2.07 2.61 3.17 3.4201 115 2.24 2.94 3.80 4.81 5.84 6.2702 115 3.14 4.13 5.36 6.76 8.13 8.6903 115 3.91 5.12 6.65 8.45 10.3 11.104 115 5.13 6.82 8.97 11.5 14.1 15.1

TE 1205 115 5.35 7.12 9.46 12.4 15.8 17.306 115 6.63 8.96 12.1 16.2 20.9 23.107 115 8.34 11.0 14.7 19.6 25.6 28.6

TE 2008 115 12.2 16.0 21.0 27.2 33.9 36.809 115 12.8 16.9 22.4 29.6 38.1 42.1

TE 55

10 115 14.4 19.6 26.5 35.4 45.6 50.611 115 15.6 21.3 28.8 38.3 49.3 54.712 115 16.5 22.6 30.6 41.0 53.3 59.413 115 19.4 26.7 36.4 49.1 64.0 71.3

Distributer correction factor, fp SI units R407CPressure drop

[bar] ∆p

Evap. temp. [°C]-40 -30 -20 -10 0 10

Correction factor0 1 1 1 1 1 11 0.96 0.96 0.96 0.95 0.95 0.93

1.5 0.94 0.94 0.94 0.93 0.92 0.90

2 0.92 0.92 0.91 0.91 0.89 0.86

Calculated at 32 °C condensing temperature.

Distributer correction factor, fp US units R407CPressure drop

[psi] ∆p

Evap. temp. [°F]

-40 -20 0 20 40 50

Correction factor0 1 1 1 1 1 1

15 0.96 0.96 0.96 0.95 0.94 0.9325 0.93 0.93 0.93 0.92 0.90 0.8830 0.92 0.92 0.91 0.90 0.88 0.86

Calculated at 90 °F condensing temperature.

Capacity in kW. Range: -40 – 10 °C.Opening superheat sh = 4 K SI units R407C

Valve type

Orificeno.

Cond.temp.

[°C]

Evap. temp. [°C]

-40 -30 -20 -10 0 10

TE 5

0.5 55 4.04 5.12 6.46 8.08 9.91 11.701 55 7.38 9.40 11.9 15.0 18.3 21.702 55 10.3 13.2 16.8 21.1 25.8 30.3

03 55 12.8 16.3 20.6 25.9 31.9 37.9

04 55 16.6 21.4 27.6 35.2 43.8 52.2

TE 1205 55 17.5 22.2 28.2 36.0 45.6 56.206 55 21.4 27.6 35.7 46.4 59.8 74.907 55 27.1 33.7 42.6 54.5 69.9 88.1

TE 2008 55 39.4 49.6 62.8 79.8 100 12209 55 40.6 51.2 65.2 83.8 109 135

TE 55

10 55 43.5 57.9 76.9 101 132 16511 55 47.0 62.6 82.9 109 142 17812 55 49.3 65.7 87.4 116 151 19113 55 56.8 76.3 102 136 179 227

Capacity in TR. Range: -40 – 50 °F.Opening superheat sh = 7.2 °F. US units R407C

Valve type

Orificeno.

Cond.temp.

[°F]

Evap. temp. [°F]

-40 -20 0 20 40 50

TE 5

0.5 135 1.12 1.46 1.89 2.41 3.00 3.2801 135 2.05 2.68 3.48 4.46 5.54 6.0702 135 2.87 3.78 4.92 6.31 7.80 8.5003 135 3.55 4.63 6.01 7.72 9.65 10.5904 135 4.59 6.10 8.06 10.5 13.3 14.6

TE 1205 135 4.88 6.29 8.20 10.7 13.8 15.506 135 5.94 7.82 10.4 13.8 18.2 20.607 135 7.54 9.53 12.3 16.1 21.1 24.0

TE 2008 135 10.9 14.0 18.2 23.7 30.4 33.909 135 11.2 14.4 18.8 24.9 32.7 37.1

TE 55

10 135 11.8 16.3 22.3 30.3 40.3 45.611 135 12.7 17.5 24.0 32.6 43.2 49.012 135 13.3 18.4 25.3 34.5 46.1 52.513 135 15.3 21.3 29.5 40.5 54.5 62.2

Subcooling correction factor, fsub

Subcooling [°F] 2 7 10 20 30 40 50Correction factor 0.97 1.00 1.02 1.08 1.15 1.21 1.27

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 33

Page 34: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

Danfoss67B66.10Danfoss67B66.10

L1 L1

L4

ØD3

L3

2.95

in

0.76 in

1.62 in 1.37 in1.

22 in

2.77

in

0.56

in

ØD3

L1

L1

41mm L4

35mm

32m

m

71m

m75m

m

19,2mm

L3

Danfoss67B67.10

L1 L1

41mm 35mm

L4

31m

m

70m

m

14m

m

75m

m

19,2mm

L3Ø D3

Danfoss67B65.10

Dimensions and weights

TE 5 - Flare, anglewayWeight: 1.1 kg

TE 5 - Solder, straightwayWeight: 1 kg

TE 5 - Solder, anglewayWeight: 1 kg

Valve body L3[mm]

L3[in]

Straight way

7⁄₈ × 11⁄₈ 28 1.1022 X 28 mm 28 1.10

⁵⁄₈ × 7⁄₈ 28 1.1016 X 22 mm 28 1.10

Others 25 0.98

Angle way

7⁄₈ × 11⁄₈ 39 1.5422 × 28 mm 39 1.54

Others 28 1.10

Inlet side ØD1

L1 [mm]

L1 [in]

½ In. / 12 mm ODF 10 0.395⁄₈ In. / 16 mm ODF 12 0.477⁄₈ In. / 22 mm ODF 17 0.67

Outlet side ØD2

L1 [mm]

L1 [in]

⁵⁄₈ In. / 16 mm ODF 12 0.477⁄₈ In. / 22 mm ODF 17 0.67

11⁄₈ In. / 28 mm ODM 25 0.98

TE 5 - Flare, anglewayWeight: 2.43 lbs

Element ØD3 [mm]

ØD3 [in]

Standard 53 2.09Range -60 – -25 °C (-75 – -15 °F)

60 2.36

Valve bodyL4

[mm]L4[in]

Straight way

7⁄₈ × 11⁄₈ 97 3.8222 X 28 mm 97 3.82

⁵⁄₈ × 7⁄₈ 97 3.8216 X 22 mm 97 3.82

Others 74 2.91

Angle way

7⁄₈ × 11⁄₈ 52 2.0522 × 28 mm 52 2.05

Others 40 1.57

TE 5 - Solder, straightwayWeight: 2.02 lbs

Danfoss67B66.10Danfoss67B66.10

L1

L1

L4

L3

ØD3

2.79

in

1.24

in

2.95

in

0.76 in

1.62 in1.37 in

TE 5 - Solder, anglewayWeight: 2.02 lbs

41mm 55mm

35mm

43m

m

29m

m

69m

m

75 m

m

19.2mm

D3

Danfoss67B55.10 Danfoss

67B56.10Danfoss67B56.10

D3

0.76 in

2.95

in

1.62 in 2.17 in

1.37 in

1.69

in

1.14

in

2.69

in

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 34

Page 35: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

ØD1

ØD

2

ØD3

L1

L1

L2

41mm 37mm

51mm

39.5

mm

29m

m

82m

m

19.2mm

Danfoss67B68.10 Danfoss

67B69.10Danfoss67B69.10

ØD1

ØD

2

ØD3

L1L2

L2

1.62 in 1.45 in

2.01 in

1.56

in

1.14

in

3.22

in

0.76 in

TE 12 and TE 20Solder, straightwayWeight: TE 12: 1.5 kg TE 20: 1.7 kg

TE 12 and TE 20Solder, anglewayWeight: TE 12: 1.5 kg TE 20: 1.6 kg

Dimensions and weights

TE12 / TE20Inlet side

ØD1L1

[mm]L1[in]

7/8 in. / 22 mm ODF 17 0.67

Outlet side ØD2

L1 [mm]

L1[in]

11/8 in. / 28 mm ODM 25 0.98

L1

L1

ØD1

ØD2

L2

ØD3

19,2mm

41mm 37mm

97mm

36m

m

29m

m

82m

mDanfoss67B67.10

Danfoss67B68.10Danfoss67B68.10

ØD1

ØD2

L1

L1

ØD3

L2

1.62 in 1.45 in

3.82 in

0.76 in

1.4

in

1.14

in

3.22

in

TE 12 and TE 20Solder, straightwayWeight: TE 12: 3.31 lbs TE 20: 3.75 lbs

TE 12 and TE 20Solder, anglewayWeight: TE12: 3.31 lbs TE20: 3.53 lbs

TE 12 - Solder flanges, straightwayWeight: Without filter: 2.3 kgWeight: Without filter: 7.72 lbs

Element ØD3 [mm]

ØD3 [in]

TE 12 Standard 60 2.36TE 12 Range -60 – -25 °C (-75 – -15 °F) 72 2.83

TE 20 72 2.83

Bulb L2 [mm]L2 [in]

TE 12 Standard 75 2.95TE 12 Range -60 – -25 °C (-75 – -15 °F) 120 4.72

TE 20 120 4.72

ØD3

1.62 in 1.45 in

4.57 in

1.36

in

3.44

in

1.36

in

Danfoss67B58.10 L2

0.76 in

3.15 in

Danfoss67B59.10

Danfoss67B70.10Danfoss67B70.10

ØD3

41mm 37mm

116mm

35m

m

35m

m

87m

m

Danfoss67B71.10Danfoss67B71.10

L2

19.2mm

80mm

Data sheet | Thermostatic expansion valves, type TE 5 – TE 55

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 35

Page 36: Data sheet Thermostatic expansion valves Type TE 5 TE 55...R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar R407C

120m

m

19,2mm

72mm

94m

m

42m

m

53m

m

L2

L1

37mm51mm

41mm

ØD2

ØD

1

Danfoss67B60.10

TE 55 - Solder, straightwayWeight: 1.7 kg

TE 55 - Solder, anglewayWeight: 1.6 kg

TE 55Inlet side

ØD1

L1 [mm]

L1 [in]

7/8 in. / 22 mm ODF 17 0.67

11/8 in. / 28 mm ODM 25 0.98

Outlet side ØD2

L2 [mm]

L2 [in]

11/8 in. / 28 mm ODF 22 0.87

13/8 in. / 35 mm ODM 27 1.06

ØD2

ØD

1

L2

L1

1.44 in 1.62 in

2.01 in

1.64

in

2.07

in3.

71 in

4.72

in

0.76 in

2.83 in

Danfoss67B62.10

TE 55 - Solder, anglewayWeight: 3.53 lbs

TE 55 - Solder, straightwayWeight: 3.75 lbs

ØD2

ØD1

L1

L2

109mm

37mm 41mm

19,2mm

120m

m

30m

m

42m

m

94m

m

72mm

Danfoss67B64.10

ØD

2

ØD

1

L2

L1

1.47 in 1.62 in

1.16

in3.

71 in

1.64

in

4.29 in

2.83 in

4.72

in

0.76 in

Danfoss67B63.10

© Danfoss | DCS (sw) | 2019.01 DKRCC.PD.AB0.A7.02 | 36