D3DigitalPositioner

Manual

Page 2: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

2

Contents

1. Introduction .................................................................................................. 3Safety instruction ................................................................................................ 32. Storage ............................................................................................................ 4General ................................................................................................................. 4Storage indoors ................................................................................................... 4Storage outdoors or for a longer period .......................................................... 4Storage in a warm place ..................................................................................... 43. Design ............................................................................................................ 54. Models ............................................................................................................ 55. Function ......................................................................................................... 6Double action function....................................................................................... 6Single action function ......................................................................................... 66. Installation .................................................................................................... 7Air supply requirements ................................................................................... 7Mounting ............................................................................................................. 8Connections ......................................................................................................... 9Air ......................................................................................................................... 9Electrical connection........................................................................................... 9Dimensions .......................................................................................................... 9Single action positioner (Direct function) ....................................................... 10Actuator with fail/close spring ........................................................................ 10Actuator with fail/open spring ........................................................................ 10Double action positioner (Direct function) ..................................................... 10Double action actuator ....................................................................................... 10Electrical connections ......................................................................................... 11 7. Control ........................................................................................................... 12Menu and pushbuttons ...................................................................................... 12Other functions ................................................................................................... 12Menu indicator .................................................................................................... 13Menus ................................................................................................................... 13Changing parameter values .............................................................................. 13Menu system ....................................................................................................... 14First start .............................................................................................................. 158. Maintenance/service .................................................................................... 34Removing cover and inner cover ..................................................................... 34Circuit boards (pcb) ............................................................................................ 35Valve block ........................................................................................................... 36Single/Double action ......................................................................................... 36Potentiometer ...................................................................................................... 37Spindle adapter ................................................................................................... 37Filter change ........................................................................................................ 379. Troubleshooting ........................................................................................... 3810. Technical data ............................................................................................... 3911. Spare parts ..................................................................................................... 42

Page 3: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

3

The PMV D3 is a digital positioner de-signed primarily to control modulatingvalves.

The positioner can be used with singleor double action actuators with eitherrotary or linear movement.

The D3 can be equipped with modu-les for feedback, limit switches, and apressure gauge block.

The modules can be factory assembledbefore delivery or fitted later.

Safety instructionRead the safety instructions in this manual carefully before using the product.The installation, operation, and maintenance of the product must be done bystaff with the necessary training and experience. If any questions arise duringinstallation, contact the supplier/sales office before continuing work.

Warning• The valve package moves when in operation and can cause personal injury

or damage if handled incorrectly.• If the power supply fails or is turned off, the valve moves quickly to its end

position.• If the compressed air supply fails or is turned off, fast movements can occur.• The valve is not controlled by the input signals when in the Out of service

position. It will open/close in the event of a leak.• If a high value is set for Cut off, fast movements can occur.• When the valve is controlled in the Man mode, the valve can move quickly.• Incorrect settings can cause self-oscillation, which can lead to damage.

ImportantAlways turn off the compressed air supply before removing or disconnectingthe air supply connection or the integral filter. Remove or disconnect withcare because C- is still under pressure even after the air supply is turned off.

The modules for feedback and limitswitches can contain the following:

Feedback 4-20 mA and one of thefollowing functions:

- Two mechanical switches- Two reed switches- Two inductive sensors- Two soft contacts (relays)

1. Introduction

Page 4: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

4

General

The PMV positioner is a precision instru-ment. Therefore it is essential that it ishandled and stored in the correct way.Always follow the instructions below!

NOTE! As soon as the positioner isconnected, an very minimal internal airleakage supply will provide protectionagainst corrosion and prevent the ingressof moisture. For this reason, the airsupply pressure should always be kepton.

Storage indoors

Store the positioner in its originalpackaging. The storage environmentmust be clean, dry, and cool (15 to 26°C,60-80°F).

Storage outdoors or for alonger period

If the positioner must be stored outdoors,it is important that all the cover screwsare tightened and that all connections areproperly sealed.

The unit should be packed with adesiccant (silica gel) in a plastic bag orsimilar, covered with plastic, and notexposed to sunlight, rain, or snow.

This is also applicable for long-termstorage (more than 1 month) and for longtransport by sea.

Storage in a warm place

When the positioner is stored in a warmplace with a high relative humidity andis subjected to daily temperaturevariations, the air inside the unit willexpand and contract.

This means that air from outside theunit may be drawn into the positioner.Depending on the temperaturevariations, relative humidity, and otherfactors, condensation and corrosion canoccur inside the unit, which in turn cangive rise to functional disorders or afailure.

2. Storage

Page 5: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

5

The D3 positioner contains:• electronic board with microprocessor,

HART modem, display etc,• pneumatic valve block,• positional feedback with potentio-

meter,• sealed compartment for electrical

connections.

The pushbuttons and display areaccessible underneath the aluminumcover, which is sealed with an O-ring.

The figure shows the D3 with the coverremoved.

4. Models

Filter Display, control pushbuttons

Positional feedback Processor and motherboard

Terminal blockAdjusting-screws,damping

Valve block

3. Design

The standard D3 positioner is suitable forsingle/double action linear or rotatingactuators.

Page 6: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

6

5. Function

Control signal 4 - 20 mA

Piezo-valve 1Piezo-valve 2

Diaphragm

Air supply 2 - 6 bar, 30-90 psi

1.2 bar, 18 psi

Vent

VentH

G

Double action function

The control signal and the feedbackpotentiometer position are converted todigital signals that are processed with aPID algorithm in the microprocessor.This provides control signals to the twopiezo-valves. The two piezo–valves areclosed in the schematic diagram aboveand have no effect on the valves A andD.

Air from the pressure regulator flowsthrough the open valve A to the valve B,which opens. The supply pressure nowthrough valve B to the actuator via H.The actuator then moves in the directionof the arrow. At the same time, air flowfrom valve A keeps valve C open andallows venting of the actuator. When

Signal converterand

microprocessor

AB

CD E F

C– C+

Actuator

Potentiometer

Checkvalve

Checkvalve

both the piezo-valves open, valve Acloses but valve D opens and controlsvalves E and F so that the actuator movesin a direction opposite the arrow. Whenonly piezo-valve 1 is open, the actuatoris staionary.

Single action function

Valve B is used for the supply air andvalve F for venting. The positioner canbe converted from double acting tosingle acting by installing a screw closingH, described on page 36.

By converting to single acting function,damper I is engaged. For double actingfunction the screw should be installed atG, bypassing damper I.

ReplaceableFilter

Pressureregulator

I

Page 7: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

7

Air supply requirements

Max. air supply pressure, see the sectionTechnical Data on page 39.

The air supply must be free frommoisture, water, oil, and particles.

The air must come from a refrigerationdried supply or be treated in such a waythat its dew point is at least 10°C, 18°Fbelow the lowest expected ambienttemperature.

To ensure a stable and problem-free airsupply, we recommend the installationof a filter/pressure regulator <40µ asclose to the positioner as possible.

Before the air supply is connected to thepositioner, we recommend the hose isopened freely for 2 to 3 minutes to allowany contamination to be blown out.

Direct the air jet into a large paper bagto trap any water, oil, or other foreignmaterials. If this indicates that the airsystem is contaminated, it should beproperly cleaned.

6. Installation

WARNING. Do not direct theopen air jet towards people orobjects because it may causepersonal injury or damage.

Poor air supplies are the main sourceof problems in pneumatic and electro-pneumatic systems.

Page 8: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

8

The D3 positioner has an ISO F05footprint, A. The holes are used to attachit to the mounting bracket B, which issuitable for most types of linear actuator.

The spindle adapter C can be changedto suit the actuator in question.

Remove the existing adapter using twoscrewdrivers. Check that the spring ringon the new spindle is undamaged beforeinstalling.

Assembly example A B

C

C

Rotary movement Linear movement

Mounting

NOTE! If the positioner is installedin a hazardous environment, itmust be of a type approved for thispurpose.

It is important that the positioner ’sspindle and the arms, that transfer theactuator movements, are correctlymounted. Any tension between theseparts can cause incorrect operation andabnormal wear.

Page 9: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

9

C– S C+

For data for air and electricalconnections, see sectionTechnical Data on page 39.

Air

Port S Supply airPort C+ Connection to actuatorPort C- Connection to actuator

(only for double action)

Electrical connection

See page 11.

Dimensions

Air connections:1/4" NPT alt. G 1/4" BSP

Electrical connection:M20 x 1.5 alt. NPT 1/2"

Loctite 577 or equivalent is recom-mended as a sealant.

Must be plugged when converting tosingle action function.

Connections

Page 10: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

10

Actuator with fail/close spring

When the control signal increases, thepressure C+ to the actuator is increased.

The valve stem moves upward androtates the positioner spindle counter-clockwise. When the control signal dropsto zero, C+ is vented and the valve closes.

Actuator with fail/open spring

When the control signal increases, thepressure C+ to the actuator is increased.The valve stem moves downward andthe positioner spindle rotates clockwise.When the control signal drops to zero,C+ is vented and the valve opens.

C–SC+

C–SC+

C–SC+

Single action positioner(Direct function)

Double action positioner(Direct function)

Double action actuator

When the control signal increases, thepressure C+ to the actuator is increased.

The valve stem is pressed upward androtates the positioner spindle counter-clockwise. When the control signal isreduced, the pressure C- to the actuatorincreases and the valve stem is presseddownward. If the control signaldisappears, the pressure goes to C-, C+vents, and the valve closes.

Page 11: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

11

The terminal block for the positioner isaccessible when the aluminium cover isremoved.

1 4-20 mA + input signal2 4-20 mA – input signal3 Switch 1 NO4 Switch 1 NC5 Switch 1 COM6 Switch 2 NO7 Switch 2 NC

8 Switch 2 COM9 4-20 mA output +10 4-20 mA output –11 AUX input 4-20 mA +12 AUX input 4-20 mA –13 Deviation alarm +14 Deviation alarm –

Option

Warning! In a hazardousenvironment where there is arisk of explosion, electricalconnections must comply withthe relevant regulations.

HART-connection

Electrical connections

+ – + – + – + –

1 2 3 4 5 6 7 8 109 11 12 13 14

Page 12: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

12

Menu and pushbuttons

The positioner is controlled using thefive pushbuttons and the display, whichare accessible when the aluminium coveris removed.

For normal functioning, the displayshows the current value. Press the ESCbutton for two seconds to display themain menu.

Use the pushbuttons tobrowse through the main menu andthe sub-menus.

The main menu is divided up into abasic menu and a full menu, see page 14.

Other functions:

ESCExit the menu without making anychanges (as long as any changes have notbeen confirmed with OK).

FUNCTo select function and change para-meters.

OKTo confirm selection or change of para-meters.

MENU INDICATORDisplays the position of the currentmenu row in the menu.

ESC FUNC

OK

BASIC MENUMAN/AUTO

OUT OF SERVICE MANUAL

UNPROTECTED

7. Control

IN SERVICEThe positioner is following the input sig-nal. This is the normal status when thepositioner is working.

OUT OF SERVICEThe positioner is not following the in-put signal. Critical parameters can bechanged.

MANUALThe positioner can be adjusted manuallyusing the pushbuttons. See section”Man/Auto”, page 19”.

UNPROTECTEDMost of the parameters can be changedwhen the positioner is in the”Unprotected” position. However,critical parameters are locked when thepositioner is in the ”In service” position.

Page 13: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

13

Menu indicator

There are indicators at both sides of thedisplay window and they indicate asfollows:

Flashing in position Out of service

Flashing in position Manual

Displayed in position Unprotected

The indicators on the right-hand sideshow the position in the current menu.

Menus

To display the menu you can select:

• Basic menu, which means you canbrowse through four different steps

• Full menu, which comprises ten steps.Use the Shift Menu to browse throughthe steps.

Full Menu can be locked out using apasscode.

The main menu is shown on the nextpage and the sub-menu on thesubsequent pages.

FULL MENUCALIBRATE

FULL MENUMAN/AUTO

FULL MENUSHIFT MENU

Changing parameter values

Change by pressing until thedesired figure isflashing.

Press to step to the desiredfigure. Confirm by pressing OK.

A change can be undone by pressing theESC button, which returns you to theprevious menu.

Page 14: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

14

BASIC MENUREAD

BASIC MENUMAN/AUTO

BASIC MENU CALIBRATE

BASIC MENUSHIFT MENU

FULL MENUREAD

FULL MENUMAN/AUTO

FULL MENU CALIBRATE

FULL MENUSHIFT MENU

FULL MENUWRITE PROT

FULL MENUSTATUS

FULL MENUSETUP

FULL MENUTUNING

FULL MENUALARMS

FULL MENUFACT SET

See page 18

See page 19

See page 15

See page 20

See page 20

See page 21

See page 22

See page 26

See page 28

See page 32

Menu system

Page 15: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

15

BASIC MENUCALIBRATE

First start

Calibrate in the basic Menu is displayedautomatically the first time the positio-ner is turned on and can be selected fromthe basic/full menu at any later time.

A complete calibration takes about 3minutes and includes end limitcalibration, auto-tuning, leak test, and acheck on the speed of movement. Startthe automatic calibration by selectingAuto-Cal and then answer the questionson the display by pressing OK or therespective arrow. The menu is describedon the next page.

If a fault occurs during calibration, oneof the following error messages can bedisplayed:

Invalid movement/press ESCto abort

No movement because the airconnections are incorrectly connected,the actuator is very large, leak or sim-ilar. After the error is corrected, thecalibration sequence must be restarted.

Pot unaligned/press ESC to abortThe potentiometer has been set to an in-valid value. The potentiomenter isaligned using the Tuning - Expert - Refcal-pot Menu. The calibration sequencemust be restarted after the fault iscorrected.

Air leak detected/ESC = abortOK = go onAn air leak has been detected. If there isan abort, the calibration sequence mustbe restarted after correcting.

Increase C- damper/ESC = abortOK to retryIncrease C+ damper/ESC = abortOK to retry

Speed of movement is to fast, adjust withthe damper screws (see page 5). PressOK. Repeat the adjustment and press OKuntil the speed is correct. If there is anabort, the calibration sequence must berestarted.

C+(C-)

Clockwise = Increased damping/Less flowCCW = Decreased damping/More Flow

Page 16: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

16

BASIC MENUCALIBRATE

The contents of the menu are shown on the next page.The various menu texts are described below.

Auto-Cal Auto-tuning and calibration of end positionsStart tune Starts the tuning. Questions/commands are displayed during

calibration. Select the type of movement, function, etc. withand confirm with OK as shown in the chart on the next

page.Lose prev value? OK? A warning that the value set previously will be lost (not during

the first auto-tuning).Actuator? rotating Select for rotating actuator.Actuator? linear Select for linear actuator.Direction? direct Select for direct function.Direction? reverse Select for reverse function.Lever cal Calibration of arm length. Set the arm manually in the max.,

min., and middle positions, according to the instructionsdisplayed. (Only showed when Actuator linear is choosen.The calibration starts after the data is entered.This takes about 3 minutes.

In service? Press OKCalibration finished. Press OK to start positioner functioning. (If ESC is pressed, the positioner assumes the ”Out of service” position but the calibration is retained).

TravelCal Calibration of end positionsStart cal Start end position calibration.Lose prev value? OK? A warning that the previously set value will be lost.

Confirm with OK. The calibration sequence starts.

In service? Press OK Calibration finished. Press OK to start positioner functioning.(If ESC is pressed, the positioner assumes the ”Out of service”position but the calibration is retained).

Perform Setting gainNormal 100% gainPerform 50%, 25%, etc. Possibility to select a lower gain in steps.Preset Revert to preset values.

Page 17: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

17

CALIBRATEAutoCal

AutoCalStart tune

Actuator?rotating

Actuator?linear

IN SERVICE? Press OK

OK

OK

TravelCalStart cal

Performnormal

Perform50%

25%

12%

6%

3%

Preset

LOSE PREVVALUE?OK?

CALIBRATEPerform

OK

OK

OK

OK

OK

CALIBRATETravelCal

LOSE PREVVALUE?OK?

IN SERVICE? Press OK

OK

OK

OK

OK

OK

OK

OK

OK

Direction?direct

Direction?reverse

OK

OK

Lever calno

Lever calyes

Stroke?LEN=XX,Xmm

Set leverat max...

Set leverat center...

Set leverat min...

Set leverat center...

OK

OK

OK

OK

Direction?direct

Direction?reverse

Calibration inprogress

OK

OK

OK

Calibration inprogress

Page 18: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

18

OK

OK

BASIC MENUREAD

READpos

READset&pos

READset&dev

READtemp

READn cycles

READacc travel

READReset stat

Current valuedisplayed

Current valuesdisplayed

Current valuesdisplayed

Current valuedisplayed

Current valuedisplayed

Current valuedisplayed

Reset stat yes

Reset stat no

Current values can be read using the Read Menu and some values can be reset.

The menu contents are shownin the figures on the right and thevarious texts are described below:

Pos Shows current position

Set&pos Shows current set value andposition

Set&dev Shows current setting anddeviation

Temp Shows current temperature

n cycles Shows number of movements(turns)

Acc travel Shows accumulatedmovement

Reset stat Reset ”n cycles” and”Acc travel”

The display contrast can be adjusted in theRead menu using the arrows and

Page 19: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

19

BASIC MENUMAN/AUTO

AUT, OK=MANPOS= 12,3% OK MAN, OK=AUT

POS= 12,3%

The menu contents are shown in thefigures on the right and the various textsare described below:

AUT, OK = MANPositioner in automatic mode

MAN, OK = AUTPositioner in manual mode

In the MAN mode, the value of POS canbe changed using .The push-buttons increase/decrease thevalue in steps. The value can also bechanged in the same way as for the otherparameter values, as described on page13.

Other functionsC+ can be fully opened by pressingand OK simultaneously.

C- can be fully opened by pressingand OK simultaneously.

C+ and C- can be fully opened forblowing clean by pressingand OK simultaneously.

When changing betweenMAN and AUT mode, theOK button must bedepressed for 3 seconds.

The Man/Auto menu is used to change between manual and automatic modes.

Page 20: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

20

FULL MENUWRITE PROT

WRITE PROTno OK

OKWRITE PROTyes

The Write Protect menu is used to protect certain essential settings.

The menu contents are shown in thefigures on the right and the various textsare described below:

No Entered values are not writeprotected. ”Unprotected” isdisplayed in the lower left-handcorner.

Yes Entered values are writeprotected. Passcode needed forchange to No (Applicable whena passcode has been set up inSETUP menu).

When changing betweenYes and No mode, the OKbutton must be depressedfor 3 seconds.

BASIC MENUSHIFT MENU

Full menuno

OK

Full menuyes

OK

S The Shift Menu is used to choose between the basic menu and the fullmenu.

The menu contents are shown in thefigures on the right and the various textsare described below:

No Full menu selected.

Yes Basic menu selected.

Full Menu can be locked with apasscode, see page 24.

Page 21: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

21

FULL MENUSTATUS

OK

OKSTATUSin service

STATUSo o service

The Status Menu is used to select whether or not the positioner is in service.

The menu contents are shown in thefigures on the right and the various textsare described below:

o o service Not in service. Flashingindicator in upper left-hand corner of display.

in service Positioner in service.Critical parameters cannotbe changed.

When changing between Inservice and Out of service,the OK button must bedepressed for 3 seconds.

Page 22: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

22

FULL MENUSETUP

The Setup Menu is used for various settings.

Actuator Type of actuatorRotating Rotating actuator.LinearLinear actuator.

Lever Only for linear actuator.Lever stroke Stroke setting to achieve correct display.Level cal Calibration of positions to achieve correct display.

DirectionDirect Direct function (signal increase opens). Indicator/spindle rotates counter-clockwise.Reverse Reverse function.

Character Curves that show position as a function of input signal.LinearEqual %Quick openSqr root

Custom Create own curve.

Cust chr# of point Specify number of points (3, 5, 9,

17, or 33)Cust curve Enter values on X and Y axes.

Curr range0%=4.0 mA100%=20.0 mA Possibility of selecting which input signal values will correspond

to 0% and 100% movement respectively. Examples of settings:4 mA = 0%, 12 mA = 100%, 12 mA = 0%, 20 mA = 100%.

The menu contents are shown in the chart on the next page and the various textsare described below:

QoSqrLinEq%

Signal

Mov

emen

t

x

ySee diagram.

Page 23: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

23

LeverStroke

LeverLever cal

SETUPActuator

SETUPLever

SETUPDirection

SETUPCharacter

SETUPCust chr

SETUPcurr range

Actuatorrotating

Actuatorlinear

Directiondirect

Directionreverse

Cust chr# of point

Cust chrCust curve

Curr range0%=4,0 mA

Curr range100%=20 mA

Characterlinear

Charactersqr root

Characterequal %

Characterquick open

Charactercustom

Displayed only when Actuator linear is selected..

OK

OK

StrokeLEN=XX,Xmm

Set leverat max...

Set leverat center...

Set leverat min...

OK

OK

OKSet leverat center...

OKLever calDone

OK

OK

OK

OK

OK

OK

OK

See

text

!

OK

OK

OK

OK

Page 24: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

24

TRVL range Setting end positions0%=0.0% Select Out of Service. Set percentage value for desired end

position (e.g. 3%).Set 0% Select In Service. Connect calibrator. Move forward to desired

end position (0%) and press OK.100%=100.0% Select Out of Service. Set percentage value for desired end

position (e.g. 97%).Set 100% Select In Service. Connect calibrator. Move forward to desired

end position (100%) and press OK.

Trvl ctrl Behaviour at set end positionSet low Choose between Free (go to mechanical stop), Limit (stop at set end

position), and Cut off (go directly to mechanical stop at set end posi-tion).Set high Similar to Set low.Values Select position for Cut off and Limit at the respective end positions.

Passcodes Setting passcodes for various functionsFull menu Passcode for access to full menu.Write prot Passcode for removing write protect.Expert Passcode for access to Expert menu (TUNING).Fact set Passcode to return to default values applicable when positioner

was delivered.

Numbers between 0 and 9999 can be used as passcodes.0 = no passcode required.

Appearance On displayLanguage Select menu language.Units Select units.Def. Display Select value(s) to be displayed during service. The display reverts

to this value 10 minutes after any change is made.Start menu Start in Basic menu or Full menu.Orient Orientation of text on display.Par mode Display of control parameters such as P, I, D or K, Ti, Td.

DevicedataHART Menu with HART parameters.HW rewSW rewInterf noHW ser noCapability General parameters.

Page 25: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

25

SETUPTrvl range

SETUPTrvl ctrl

SETUPPasscodes

SETUPAppearance

SETUPDevicedata

Trvl range0%= 0,0%

Trvl rangeSet 0%

Trvl range100%=100,0%

Trvl rangeSet 100%

Trvl ctrlSet low

Trvl ctrlSet high

Trvl ctrlValues

Passcodesfull menu

Passcodeswrite prot

Passcodesexpert

Passcodesfact set

AppearanceLanguage

AppearanceUnits

AppearanceDef. Displ

AppearanceStart menu

AppearanceOrient.

AppearancePar mode

See

text

!

See

text

!

See

text

!

See

text

!

See

text

!

OK

OK

OK

OK

DevicedataHart

DevicedataHW rew

DevicedataSW rew

DevicedataInterf no

DevicedataHW ser no

DevicedataCapability

Page 26: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

26

FULL MENUTUNING

The menu contents are shown in the chart on the next page and the various textsare described below:

All

thes

e va

lues

are

set

at t

he fa

ctor

y be

fore

deli

very

and

sho

uld

not n

orm

ally

be

chan

ged.

Close time Minimum time from fully open to closed.Open time Minimum time from closed to fully open.Deadband Setting deadband. Min. 0.2%.

Expert Advanced settings.Toggletester Test tool for checking functions. Overlays a square wave on the

set value.Pid parameters Setting P, I, and D parameters.Gain Adj Gain adjustment.Ref Cal Calibration of integral functions as follows:

Set point LO: Use the calibrator set to 4 mA (or set another valueon the display). Press OK.Set point HI: Use a supply of 20 mA (or set another value on thedisplay). Press OK.Pressure LO: Use a supply of 2 bar (or set another value on the dislay). Press OK.Pressure HI: Use a supply of 6 bar (or set another value on thedisplay). Press OK.Temp. Calibrate using a known temperature.Aux input LO: Use the calibrator and a power supply of 4 mA (orset another value on the display). Press OK.Aux input HI: Use a supply of 20 mA (or set another value on the display). Press OK.Pot: Potentiometer setting, if its position relative to the gear seg-ment has been changed. See page 37.Full reset: Resets all the set values.

Self test Test of processor, potentiometer, etc.

Page 27: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

27

TUNINGClose time

TUNINGOpen time

TUNINGDeadband

TUNINGExpert

Close timeMin= 0,05

Open timeMin= 0.05

DeadbandD= 0,2%

ExpertToggletester

Toggletestertime

ExpertPid params

ExpertGain Adj

ExpertRef Cal

ExpertSelf test

Togglestepn per s

Toggletestersize

Toggletesterstart

ToggletesterAbort step

Toggletestertime

See

text

!

See

text

!

OK

OK

OK

See

text

!See

text

!

Page 28: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

28

FULL MENUALARMS

Deviation Alarm generated when deviation occursOn/Off Alarm on/off.Distance Allowed distance before alarm is generated.Time Total deviation time before alarm is generated.Valve act Behavior of valve when alarm is generated.

Limit 1 Alarm above/below a certain level.On/Off Alarm on/off.Minipos Setting of desired min. position.Maxpos Setting of desired max. position.Hysteresis Desired hysteresis.Valve act Behavior of valve when alarm is generated, see page 32.

Limit 2 See Limit 1.

The menu contents are shown in the chart on the next page and the various textsare described below:

Limit 1, maxHysteresis

Limit 2, maxHysteresis

HysteresisLimit 2, min

HysteresisLimit 1, min

0%

100%

Alarm Limit 1 on

Alarm Limit 2 on

Alarm Limit 1 off

Alarm Limit 2 off

Alarm Limit 2 on

Alarm Limit 1 onAlarm Limit 1 off

Alarm Limit 2 off

Con

trol s

igna

l

Set alarm and hysteresis values

See diagram below!

Page 29: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

29

DeviationOn/off

DeviationDistance

DeviationTime

DeviationValve act

Limit 1On/off

Limit 1Minpos

Limit 1Maxpos

Limit 1Hysteresis

Limit 1Valve act

On/offon

On/offoff

DistanceD = 10.0%

TimeT=0.00s

Valve actdo nothing

Valve actGoto open

Valve actGoto close

Valve actmanual

Valve actdo nothing

Valve actGoto open

Valve actGoto close

Valve actmanual

On/offon

On/offoff

MiniposP= 0,0%

MaxposP= 0,0%

HysteresisH= 0,0%

ALARMSDeviation

ALARMSLimit 1

ALARMSLimit 2

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

See Limit 1

OK

Page 30: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

30

Pot=aux External potentiometer

On/Off Function on/off.

Max diff Max. allowed deviation between internal and external potentio-meter.

Valve act Behavior of valve when alarm is generated.

Aux input External input signal 4-20 mA.

On/Off Alarm on/off.

Minipos Setting of desired min. position.

Maxpos Setting of desired max. position.

Hysteresis Desired hysteresis.

Valve act Behavior of valve when alarm is generated, see page 32.

Function similar to Limit 1 and 2.See chart on previous page.

Page 31: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

31

Pot=auxOn/off

Pot=auxMax diff

Pot=auxValve act

Valve actdo nothing

Valve actgoto open

Valve actgoto close

Valve actmanual

On/offon

On/offoff

Max diffP= 0,0%

ALARMSPot=aux

ALARMAux input

Aux inputOn/off

Aux inputMinpos

Aux inputMaxpos

Aux inputHysteresis

Aux inputValve act

Valve actdo nothing

Valve actgoto open

Valve actgoto close

Valve actmanual

On/offon

On/offoff

MiniposP= 0,0%

MaxposP= 0,0%

HysteresisH= 0,0%

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

to Limit 1 and 2.vious page.

Page 32: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

32

Temp Alarm based on temperatureOn/Off Temperature alarm on/off.Low temp Temperature setting.High temp Temperature setting.Hysteresis Allowed hysteresis.Valve act Behavior of valve when alarm is generated.

FULL MENUFACT SET

Valve act

Do nothing Alarm generated only. Operations not affected.

Goto open C+ gives full pressure and valve moves to fullyopen position. Positioner changes to positionManual.

Goto close C- gives full pressure and valve moves to fullyclosed position. Positioner changes to positionManual.

Manual Valve stays in unchanged position. Positionermoves to position Manual.

The menu contents are shown in the chart on the next page and the various texts aredescribed below:

The default values that were set on delivery can be reset using the Fact Set menu. Valuesfrom calibration and from other settings will then be lost.

Page 33: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

33

Valve actdo nothing

Valve actGoto open

Valve actGoto close

Valve actmanual

OK

OK

TempLow temp

TempHigh temp

TempHysteresis

TempValve act

TempOn/off

On/offon

On/offoff

On/offon

On/offoff

On/offon

On/offon

MaxP= 0,0%

ALARMStemp

OK

OK

OK

OK

OK

OK OK

OK

OK

FACT SETno

FACT SETyes

OK

OK Press OKfor 3 sek

OK OKDiscardsettings?

Inputaccepted

OK

FACT SETDone

OK

Page 34: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

34

Removing cover and innercover

• Unscrew the screws A and remove thecover.

• Pull off the disc with the arrow B.

• Unscrew the screws C, pull the innercover slightly in the direction of thearrow, and remove the cover.

When performing service, replacing a circuit board, or other repair, it may benecessary to remove and refit various parts of the positioner. This is described onthe following pages.

Read the Safety Instructions on page 3 before starting work on the positioner.

Cleanliness is essential when working with the positioner. Contamination inthe air ducts will ultimately lead to operational disturbances. Do not disassemblethe unit more than what is described here.

Do not take the valve block apart because its function will be impaired.

When working with the D3 positioner, the work place must be equipped withESD protection before the work is started. Always turn off the air and electricalsupplies before starting any work.

A

B C

8. Maintenance/service

Page 35: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

35

Circuit boards (pcb)

Disconnect or turn off the electricpower supply before starting anywork.

• Lift off the display pcb.

• Unscrew the spacers E, release thecable connections F and G, and lift upthe processor pcb.

• Remove the terminal board byunscrewing the spacers H.

F E

H

G

D

Page 36: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

36

Valve block

Turn off the air and electric powersupply before starting any work.

• Disconnect connector F from the pro-cessor pcb.

• Remove the four screws I.

• Lift out the valve block

NOTE! Do not disassemble the valveblock. Will not operate if opened.

Single/Double action

• The D3 can easily be converted fromdouble acting to single acting or viceversa by moving screw J as shown.

For single action, screw should be placedinto the bottom of the housing.

For double action, screw should beplaced into the lower side of the valveblock. Factory default setting.

J

IF

Single action

Double action

Page 37: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

37

Potentiometer

The spring-loaded potentiometer K canbe removed from the gearwheel forcalibration or replacement.

If the potentiometer is replaced or thesetting is changed, it must be calibratedin the menu Tuning - Expert - Ref cal pot.

Spindle adapter

The spindle adapter L can be changed tosuit the actuator in question.

• Remove the existing adapter using twoscrewdrivers. Check that the springring on the positioner’s spindle isundamaged. Fit the new spindle.

Filter change

Turn off the compressed air supplybefore starting any work.Otherwise the filter can beuncontrollably blown out of thepositioner by the air pressure,which can be dangerous.

• Unscrew the filter with a coin orsimilar.

.

K

L

Page 38: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

38

Fault symptom

Change in input signal to positioner doesnot affect actuator position.

Change in input signal to positioner ma-kes actuator move to its end position.

Inaccurate regulation.

Slow movements, unstable regulation.

Action

• Check air supply pressure, aircleanliness, and connection betweenpositioner and actuator.

• Check input signal to positioner.

• Check mounting and connections ofpositioner and actuator.

• Check input signal.

• Check mounting and connections ofpositioner and actuator.

• Implement auto-tuning. Check forany leaks.

• Uneven air supply pressure.• Uneven input signal.• Wrong size of actuator being used.• High friction in actuator/valve

package.• Excess play in actuator/valve

package.• Excess play in mounting of positio-

ner on actuator.• Dirty/humid supply air

• Implement auto-tuning.• Adjust the pressure adjusting screws.• Increase the deadband (Tuning

menu)• Reduce Performance (Calibrate

menu)

9. Troubleshooting

Page 39: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

39

10. Technical data

Rotation angle 30 - 100°Stroke 5 - 130 mm (0.2” to 5.1”)Input signal 4 - 20 mAAir supply 2 - 6 bar (30 - 90 psi)Air delivery 400 nl/min (13.8 scfm)Air consumption <0.3 nl/min (0.01 scfm)Air connections 1/4” G or NPTCable entry 3 x M20 or 1/ 2” NPTElectrical connections Screw terminals 2.5 mm2 /AWG14Linearity <1%Repeatability <0.5%Hysteresis <0.4%Dead band 0-10% adjustableDisplay Graphic, view area 15 x 41mm (0.6 x 1.6”)MMI 5 push buttonsProcessor 16 bitCE directives 93/68EEC, 89/336/EEC, 92 /31/EECEMC EN 50 081-2, EN 50 082-2Voltage drop <11VEnclosure IP66/NEMA 4XMaterial Die-cast aluminium, A2/A4 fastenersSurface treatment Powder epoxyTemperaturrange –30 to +85°C (–22 to 185° F)Weight 1.4 kg (3 lbs)Deviation alarm 10 < Uin < 28VDC

Ri active alarm typ = 1kΩ

Page 40: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

40

Page 41: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

41

Page 42: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

42

11. Spare parts

4 3 12 9 10 11 2 1

8 5 7

6 14 13

15

Page 43: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

43

Pos. Part no. Description

D3-SP6 Cover incl. screws

D3-SP11 Internal cover incl. screws

P3-SP13 Cover plate incl. screw

P5-Sxx Spindle adapter

D3-SP1 Block compl. Incl. cable, rubber seal, filter-plug

D3-SP9 Filter-plug incl. O-ring, filter

D3-SP8 Potentiometer compl. Incl. spring, holder, cable

D3-SP20 Shaft compl. incl. gearwheel, friction clutch

D3-SP37 Display pcb

D3-SP35X All pcbs (terminal block, processor, display)

D3-SP35H All pcbs, HART (terminal block, processor, display)

P5-21A Arrow pointer

D3-SP/SCREW Kit, bag with screws

D3-SP/SEAL Kit, bag with O-rings, seals

D3-39 Cable, pneumatic block

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Page 44: D3 Digital Positioner - Fluidcontrol · The PMV D3 is a digital positioner de-signed primarily to control modulating valves. The positioner can be used with single or double action

Distributor

PMV GmbHPostfach 2310D-41554 KaarstGERMANYTel: +49 (0) 2131 667 081/82Fax: +49 (0) 2131 667 083E-mail: [email protected]: www.pmv-germany.de

Palmstiernas Svenska ABBox 21SE-663 21 SkoghallSWEDENTel: +46 (0) 54 52 14 70Fax: +46 (0) 54 52 14 42E-mail: [email protected]: www.palmstiernas.se

SUBSIDIARIES:

PMV Controls LtdHeadlands Business ParkRingwoodHampshire BH24 3PBENGLANDTel: +44 (0) 1425 48 08 88Fax: +44 (0) 1425 48 08 89E-mail: [email protected]

Palmstiernas Instrument ABKorta Gatan 9SE-171 54 SolnaSWEDENTel: +46 (0) 8 555 106 00Fax: +46 (0) 8 555 106 01E-mail: [email protected]: www.pmv.nu

(The information in this brochure is subject to change without notice.)

PMV-USA, Inc1440 Lake Front CircleUnit 160The Woodlands, Texas 77380USATel: +1 281 292 7500Fax: +1 281 292 7760E-mail: [email protected]: www.pmvusa.com

22549/2000.1 E