8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com 01/05 R Classic Series ELECTRONIC CONTROL VALVE (for Electric Valve Positioning) F113-40 (Globe) F1113-40 (Angle) Operation The Watts ACV Electronic Control Valve is designed to be electrically positioned to control ow, pressure, level or temperature for water applications. It is a throttling valve controlled by two 2-way solenoids installed in the pilot control system, one connecting the valve cover chamber with upstream pressure and the other connecting the main valve cover chamber downstream. By alternately energizing the solenoids, line pressure is admitted to or relieved from the cover chamber of the main valve, allowing the valve to be “positioned” to maintain a desired value. The valve is normally interfaced with SCADA systems or a Programmable Logic Controller that compares a Process Variable (PV) to a desired setpoint, and energizes the solenoid pilots to throttle the valve open or closed until the PV reaches the desired setpoint. Rate of valve operation is controlled by separate adjustable Opening and Closing Speed Controls that control the rate uid and pressure are admitted to or relieved from the main valve cover chamber. The valve is constructed with two “normally closed” solenoids allowing the valve to “hold last position” upon power failure. The valve may also be congured to open fully or close drip tight upon power failure if desired. Specify valve to “hold last position”, “open fully” or “close drip tight” upon power failure prior to ordering. Installation Guidelines Prior to installation, ush line to remove debris. Install valve horizontally “in line” (cover facing UP), so ow arrow matches ow through the line. Avoid installin g valves 6” and larger vertically. Consult factory prior to ordering if installation is other than described. Install inlet and outlet isolation valves. NOTE: When using buttery valves, insure disc does not contact control valve. Damage or improper valve seating may occur. Provide adequate clearance for valve servicing and maintenance. Install pressure gauges to monitor valve inlet and outlet pressure. Connect Solenoid Pilots to appropriate power source in compliance with local electrical codes. Other Watts ACV Solenoid Control Valves F1 13-12 / F11 13-12 Solenoid (On-Off) V alve (4” & smaller) F113-6 / F1113-6 Solenoid (On-Off) V alve (6” & larger) F113-25 / F1113-25 Solenoid (On-Off) V alve with Hydraulic Check Feature (4” & smaller) F1 13-32 / F1113-32 Solenoid (On-Off) V alve with Hydraulic Check Feature (6” & larger)

Classic Series F113-40 (Globe), F1113-40 (Angle) Installation Instructions

  • Upload
    watts

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Classic Series F113-40 (Globe), F1113-40 (Angle) Installation Instructions

8/8/2019 Classic Series F113-40 (Globe), F1113-40 (Angle) Installation Instructions

http://slidepdf.com/reader/full/classic-series-f113-40-globe-f1113-40-angle-installation-instructions 1/1

8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com

01/0

R

Classic Series

ELECTRONIC CONTROL VALVE(for Electric Valve Positioning)

F113-40 (Globe

F1113-40 (Angle

OperationThe Watts ACV Electronic Control Valve is designed to be electrically positioned to control flow, pressure

level or temperature for water applications. It is a throttling valve controlled by two 2-way solenoids installed

in the pilot control system, one connecting the valve cover chamber with upstream pressure and the othe

connecting the main valve cover chamber downstream. By alternately energizing the solenoids, line pressure

is admitted to or relieved from the cover chamber of the main valve, allowing the valve to be “positioned” to

maintain a desired value.

The valve is normally interfaced with SCADA systems or a Programmable Logic Controller that compares a

Process Variable (PV) to a desired setpoint, and energizes the solenoid pilots to throttle the valve open or

closed until the PV reaches the desired setpoint.

Rate of valve operation is controlled by separate adjustable Opening and Closing Speed Controls thacontrol the rate fluid and pressure are admitted to or relieved from the main valve cover chamber.

The valve is constructed with two “normally closed” solenoids allowing the valve to “hold last position

upon power failure. The valve may also be configured to open fully or close drip tight upon power failure i

desired.

Specify valve to “hold last position”, “open fully” or “close drip tight” upon power failure prior to

ordering.

Installation Guidelines• Prior to installation, flush line to remove debris.

• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid

installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than

described.

• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contac

control valve. Damage or improper valve seating may occur.

• Provide adequate clearance for valve servicing and maintenance.

• Install pressure gauges to monitor valve inlet and outlet pressure.

• Connect Solenoid Pilots to appropriate power source in compliance with local electrical codes.

Other Watts ACV Solenoid Control Valves

F113-12 / F1113-12 Solenoid (On-Off) Valve (4” & smaller)

F113-6 / F1113-6 Solenoid (On-Off) Valve (6” & larger)

F113-25 / F1113-25 Solenoid (On-Off) Valve with Hydraulic Check Feature (4” & smaller)

F113-32 / F1113-32 Solenoid (On-Off) Valve with Hydraulic Check Feature (6” & larger)