BMM ISPAT LTD EXPANSION OF STEEL PLANT IN DANAPUR VILLAGE NEAR HOSPET BELLARY DISTRICT, KARNATAKA TECHNICAL SPECIFICATION FOR CIVIL WORKS MECON LIMITED BANGALORE – 560 004 INDIA MEC/01/56/Q6WX/CIVIL WORKS/TS/201, Rev.0 DECEMBER , 2011

Civil Works Spec

Embed Size (px)

Citation preview

Page 1: Civil Works Spec

BMM ISPAT LTD

EXPANSION OF STEEL PLANT IN DANAPUR VILLAGE NEAR HOSPET BELLARY DISTRICT, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

MECON LIMITED BANGALORE – 560 004

INDIA  MEC/01/56/Q6WX/CIVIL WORKS/TS/201, Rev.0

DECEMBER , 2011

Page 2: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 1 of 10

CHAPETER – I   

SECTION–I   

GENERAL SCOPE FOR CIVIL WORKS  1.0    SCOPE AND SCOPE RELATED GENERAL REQUIREMENTS 

 1.1  SCOPE 

 1.   This  section of  the  specification  covers entire Civil engineering work  including Design and 

engineering for all buildings, structures and facilities for Indoor Switchyard and other related auxiliary units  including foundations for all buildings and equipment, roads, ramps, paving, parking  areas,  storm  water  drainage  and  faecal  sewers,  plumbing  and  sanitary  fittings, service  lines  and  all  other miscellaneous  civil  engineering work  as  shall  be  necessary  for completing this package on a turnkey basis within the battery limit. 

 2.  The  construction materials  required  for  successful execution of  civil works are  included  in 

the scope of work of the Bidder.  3.     Construction water shall be provided free of cost by the client at one point. The bidder shall 

make his own arrangements for emergency supply and distribution.  4.  Works shall  include amongst others all activities as detailed below but not  limited to them 

for the entire plant facility.                        5.   Cable and pipe trenches within the battery limit.  6.   Permanent road and  its connection to the plant main road and pavements for the various 

facilities including providing culverts, drains etc. Surface drains are to be connected to storm water  drainage  system  of  the  plant within  the  battery  limit  and  its  connection  to  plant network. 

 7.   All plumbing,  sanitary  and water  supply  fittings  and  fixtures,  rainwater drainage,  sanitary 

faecal  sewerage  and  industrial  contaminated  sewerage  and  connection  to  manholes  / junction boxes of plants area drainage and  sewerage network    located upto a distance of 20m from outer face of any building / premises / open area are in the scope of this contract. 

 8.   All  necessary  waterproofing,  heat  resisting,  fireproofing,  and  anticorrosive  treatment  to 

buildings, concrete structures and foundations including underground construction.  

 9. All  necessary  protective  civil works  below  roadways  for water  and  other  services  inside  

battery limit. 

Page 3: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 2 of 10

 10. Necessary sealing arrangement and PVC water stops at expansion joints.  11. All under deck type roof insulation wherever necessary.  12. Civil work for utilities and services.   13. All  temporary  facilities  and  preliminaries  like  buildings,  offices,  labour  colonies,  staff 

quarters, roads and services for construction for this package.   14. Removal  and disposal of debris, micro  leveling of  the  site up  to battery  limits  all  around 

buildings and premises within the scope of contract prior to completion of work.   15. Within battery  limits, diversion, relocation and protection of existing underground services 

at no additional cost to the purchaser.  16.  Protection of existing  service  lines beyond battery  limits,  if  required,  shall be done while  

executing the work within battery limits.   17. All necessary civil work  required  for approach  roads, connected culverts and  road  lighting 

with in the battery limits.  18.   Dismantling of buried / semi‐buried structures,  if any, encountered within the battery  limit 

and disposal of generated debris as directed by the owner  19.  Earthwork  including  dewatering,  side  shoring  as  required  for  buildings  and  equipment 

foundations,  trenches,  pits,  sewers  and  other  construction  work  including  controlled blasting of soft rock or hard strata as required. If at all, blasting is required, it shall be done at no extra cost with  the prior approval of the owner.   Apart  from shoring and temporary supports,  all  other  necessary measures  like  use  of  sheet  piling  etc.  shall  be  provided,  if necessary, at no additional cost to the owner. 

 20.   Site micro  leveling, clearing, dressing and grading of formation of ground up to maximum 

of  top  200 mm  of  soil  to  achieve  required  terrace  levels  and  compaction  as  necessary within the battery limit. 

 21. Necessary Survey work as may be required for the execution of work.  22. Soling and sub‐grade work  including backfilling and compaction  for all  foundations,  floor, 

apron, paving, trenches, pits and other underground structures. 23.     Reinforced  concrete  foundation  system,  as  required  in  foundation  for building,  equipment, 

technological structures, pits, sumps, trenches, concrete encasing, grouting, basement and all underground structures. 

 

Page 4: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 3 of 10

24.     Concrete  and  Reinforced  concrete work  in  columns,  tie  beams,  beams,  slabs,  frames  and other super structures. 

 25.     All masonry works in substructure and superstructure including plastering as required.  26.     Fixing and finishing of Doors, windows, ventilators, louvers, rolling shutters, fire check doors, 

gates, shutters etc.  27.      All finishing work to flooring, walls, ceiling and false ceiling as required.  29.       All finishing and painting work to masonry, concrete structures, steel works.  30.        All necessary technological and equipment supporting structures.  31.        Hand railings, inserts, kerb angles, bolts etc.   32.    All fencing and gates as required.  33.  Encasing all conduits above ground and below ground wherever necessary with PCC M–15.  34.  Maintenance facilities for gutters, rainwater down pipes.  35. The scope shall also include setting up by Bidder complete testing laboratory in  the field to 

carryout  relevant  tests  at  specified  /  required  frequency  and  manning  of  field  lab  by competent technical personnel. 

 36. The Bidder shall undertake within the battery limits any change in the location of the units / 

items  and/or  building  numbers  /  parameters,  sizes  etc  which  may  be  necessary  during engineering / execution from those  indicated by the Bidder  in their contract drawings at no additional cost to the owner.  

37.      It is not the intent to specify herein all the works in the scope of this contract.   Construction shall conform in every respect to all local and state regulations governing such works and to stipulations of Indian Standards unless stipulated otherwise in detail specification. 

 38.       Necessary Co‐ordination with Other Package Contractor/Bidder / other agencies /   Statutory 

bodies  / Client’s etc.  shall be done by  the  Successful Bidder, without affecting  the Project Schedule. 

 2.0  GENERAL  2.1  The  detailed  specifications  given  hereafter  are  for  the  items  of  works  described  in  the 

schedule of quantities attached herein, and shall be guidance for proper execution of work to the required standards. 

 

Page 5: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 4 of 10

2.2 It may also be noted that the specification are of generalized nature and these shall be read in conjunction with the description of item in schedule of quantities and drawings. 

 2.3 All  the  structures  constructed  are  expected  to  be  crackfree,  seepage  free  and  leakproof. 

Adequate  care  shall be  exercised during  construction phases  to  ensure  these  aspects.  Post constructional  problems,  if  any,  leading  to  the  above  mentioned  conditions  shall  be immediately  rectified  to  the  complete  satisfaction of  the Owner  / Engineer  In  charge at no extra cost. 

 2.4 All  construction works, mainly,  underground works,  shall  conform  to  the  requirements  of 

IS6316:1981 – Code of Practice for AntiTermite measures in Buildings – Part I – Constructional Measures. 

 2.5 If the contractor has any reservation about the achievement of the requirements stated in 2.3 

above using the specifications given in the tender document, he shall bring it the notice during prebid meeting. 

 2.6  The  work  also  includes  all  minor  details  of  construction  which  are  obviously  and  fairly 

intended and which may not have been referred to  in these documents but are essential for the entire completion in accordance with standard engineering practice. 

 2.7                   The Chief Engineer or his authorised representative shall be the deciding authority as to the 

meaning,  interpretations and  implication  for various provisions of  the  specifications and his decision in writing shall be final and binding on all concerned. 

 2.8  In case of any difference or discrepancy between the specifications and the description in the 

schedule of quantities, the schedule of quantities shall take precedence.  2.9  In  case  of  any  difference  or  discrepancy  between  the  specifications  and  the  drawing,  the 

specification shall take precedence.  2.10 Unless  specifically  otherwise  mentioned,  all  the  applicable  latest  codes  and  standards 

published by the Bureau of Indian Standards shall be  referred therein. In case for any work BIS is not available, the work shall be executed to international standards. workmanship, quality, properties of materials, method of testing and method of measurements. 

 2.11 The Contractor will have to draw up the program of work in consultation with the Consultant 

and the project authorities to match with the overall project requirements.  3.0             DRAWINGS  3.1  The work shall be executed in accordance with the specification and the drawings `Issued for 

Construction’.   Drawings will be  issued  in stages  in close coordination with the availability of data and sequence of construction. Only latest revisions of the drawings shall be followed. All 

Page 6: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 5 of 10

old  revisions  shall  be  clearly  marked  `SUPERSEDED’  and  kept  separately  or  destroyed  as directed by Engineer Incharge. 

 4.0            SITE RECORDS  4.1  All works  shall be  recorded  in  appropriate proformas  to be  firmed up by  the  contractor  in 

consultation  with  the  Engineer  Incharge.  Wherever  required,  reference  to  drawings  and clauses of specification shall be recorded in the correspondence. 

 4.2  Records of  steel  receipts,  issue, and  consumption  shall be  scrutinized  from  time  to  time by 

Engineer  Incharges  and  Owner.  Statement  of  steel  receipts,  statement  of  theoretical consumption  and  reconciliation  should  accompany  every  bill.  Records  of  spot  levels  jointly recorded before the start of the work shall form the basis of all measurements. 

 5.0  SCOPE OF WORK  5.1  Setting out of all structures including layout and levels, etc. shall be made by the Contractor at 

his own cost from the general grid of the plot and bench mark given by the Engineer Incharge. Contractor  shall  provide  all  instrument,  materials  and  men  to  the  Engineer  Incharge  for checking  the  layout  and  levels.  However,  the  Contractor  shall  be  fully  responsible  for correctness of layout and levels. 

 5.2  The work to be performed under this specification consists of providing all  labour, materials, 

construction  equipment,  tools  and  plant,  scaffolding,  supplies,  transportation,  all  incidental items not shown or specified, but reasonably  implied or necessary for successful completion of the work including Contractor’s supervision and in strict accordance with the drawings and specifications. The nature of  the work  shall generally  involve  site  clearance  including  jungle clearance,  re‐plantation  of  trees,    earthwork  in  excavation,  construction  of  retaining walls, under  ground  passage  ways,  controlled  filling,  dewatering,  backfilling  around  completed structures,  grading,  disposal  of  surplus  excavated  materials,  concreting  including reinforcement  and  formwork,  brickwork,  inserts  (embedded  parts),  steel  gratings, architectural  items and  finishes  like plastering, painting,  flooring  (including access  flooring & special  floorings),  doors, windows  and  ventilators,  rolling  shutters,  false  ceiling,  expansion joints,  light  structural work, platforms,  etc.,  anchor bolts, RCC  trenches with  covers,  folded plate roofs, water proofing and public health works, roads, culverts, drains etc. 

 5.3  The drawings included with this document provide a general representation of the work to be 

performed under the scope of this contract. These are preliminary drawings only and are by no means the final drawings or show the full range of the work under the scope. Work has to be  executed  according  to  construction  drawings  to  be  released  by  the  Engineer  Incharge progressively. 

 5.4  The contractor will be required to set up site  laboratory at his own cost and maintain all the 

equipment in proper condition with all calibration and certificates of the equipment. The site laboratory will be manned by an  independent qualified engineer. The cost of setting up site 

Page 7: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 6 of 10

laboratory  and  performance  of  all  the  tests  shall  be  borne  by  the  Contractor.  In  case,  any specific  test  such  as  testing  of  reinforcement,  testing  of  any  specific  materials  requiring specialist equipment and conditions, they shall be done in approved laboratories. The cost of such tests and the arrangements for witnessing such tests shall be borne by the Contractor. 

 5.5  The scope of work also includes clearance of site of any vegetation, bushes, scrap, debris, etc. 

before starting the work and recording spot levels at the site of work as well as storage areas. The Contractor  shall also clear  the construction  site of all debris and construction materials before handing over.  

 5.6  All  specimens  and  approved  samples  shall  be  retained  with  the  Engineer  Incharge  for 

reference  unless  handed  over  to  Contractor  for  safe  custody.  The  Contractor  shall make arrangements  for  proper  storage  of  the  same.  These  specimens may  be  retained with  the owner as a permanent record. 

 6.0  APPROVAL AND TESTS  6.1  A high standard of quality is required for all materials and workmanship in construction work. 

They shall be best of the kind obtainable indigenously in each case and shall be procured from manufacturers of repute in order to ensure uniformity of quality and timely supply. 

 6.2 The  quality  of  work  shall  be  of  highest  standard.  The  executed  works  shall  be  open  to 

inspection by high level committees from time to time. The direction of the committee will be binding on the contractor. 

 6.3  All materials shall be subjected to inspection and testing. The Contractor shall submit samples 

for testing as may be required by the Engineer Incharge. Sampling and testing shall be carried out in accordance with relevant IS Standards. 

 6.4  Where ever  IS codes are referred  to, they shall be  the  latest edition/ publication as on date 

irrespective of the date of finalisation of the work.  6.5  Contractor  shall prepare  and  submit  quality  assurance plan  for  the  execution of work.  The 

frequency of testing shall be guided by the quality assurance plan approved by the Engineer Incharge. 

 7.0  REJECTION OF MATERIALS  7.1  Any material  brought  to  site which,  in  the  opinion  of  the  Engineer  Incharge  is  damaged, 

contaminated,  deteriorated  or  does  not  comply with  the  requirement  of  this  specification shall be rejected. 

 7.2  If the routine tests or random site tests show that any of the materials brought to site, do not 

comply  in any way with  the  requirements of  this  specification or of  IS  codes as applicable, then that material shall be rejected. 

Page 8: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 7 of 10

 7.3  The  Contractor  at  his  own  cost  shall  remove  from  site  any  and  all  such  rejected material 

within the time specified by the Engineer Incharge.  8.0   ACCEPTANCE CRITERIA  8.1 The criteria  for acceptance of work shall be generally  in accordance with  the  testing norms 

and approved quality assurance plan. Any defective workmanship will be rectified/ replaced complete to the satisfaction of the Engineer In‐charge solely at the cost of contractor.  

 8.2  Rectification of defective work shall be taken up by the contractor at no extra cost the owner 

including such measures which need use of specialised materials/ treatments/ injections.   8.3 Percentage  of  wastage  of  materials  meant  for  reconciliation  shall  be  decided  with  the 

successful tenderer.   9.0 QUALITY MANAGEMENT REQUIREMENTS   9.1 This chapter specifies  requirements  to be  incorporated  in  the contractor’s quality assurance 

programme  for  construction.  The  contractor  is  responsible  for  planning  and  developing  a programme  that  assures  that  all  the  construction  management,  procurement,  technical coordination and technical responsibility for quality are incorporated and executed effectively. The programme  is aimed primarily at ensuring efficient quality management  in construction and taking corrective actions, when necessary.  

 Planning and detailed written procedures are essential for specifying how such activities as the following, which affect quality, are to be performed and controlled.  a)    Responsibilty of inter disciplinary works coordination.  b)    Procurement.  c)    Construction.  d)    Special processes.  e)    Measuring and testing equipment.  f)     Inspection and test. g)    Handling, storing, preservation , packaging and shipping.  h)    Item identification and traceability. i)     Documentation and quality records.  j)     Disposition of non conformances and corrective action.   

9.2     APPLICABILITY        The requirements of this chapter apply to the construction activities.     

Page 9: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 8 of 10

9.3     CONTRACTORS RESPONSIBILITIES   

The Contractor’s responsibilities are–  a)  To  develop  and  implement  the  controls  and  quality  assurance  procedures,  specified 

herein,  that  will  promptly  detect  and  dispose  of,  or  prevent,  non  conformances  to contractual requirements.  

b)  To comply with the requirements as specified in the contract.  c)  To  prepare  a  quality  assurance  manual  which  shall  be  submitted  for  the  Engineer’s 

concurrence before the contract is awarded or at the latest before the work starts.  d)  To  prepare  a  quality  plan which  shall  be  submitted  to  the  Engineer  before  the work 

starts.  e) To update and resubmit the quality assurance manual and quality plan to reflect current 

practices when significant changes occur  in the Contractor’s programme or organization in order to improve its effectiveness or to prevent recurrence of non‐conformance.  

f) To  initiate  corrective  measures  promptly  when  the  quality  assurance  representative notifies the Contractor of deviations from established requirements. 

g) To submit a detailed activity schedule (unit / building wise/ activity wise) in PERT / GANTT chart form. This shall be submitted  immediately after placement of order. The schedule approved  by  the  Engineer  Incharge  shall  be  tracked  and monitored  on  a  fortnightly  / monthly basis and submitted to the Engineer Incharge for review. 

9.4          BASIC REQUIREMENTS   

9.4.1  Quality Assurance Programme.   

The Contractor shall plan, establish, implement and maintain a quality assurance programme that complies with the requirements of this chapter.  

 9.4.2 Organization   

The Contractor shall:  

a) Clearly define management polices, objectives and responsibilities for quality assurance, including  the  responsibility  of  each  division within  a multi‐divisions  organization.  The responsibility and authority for quality of those managing and performing the work and of these audition and verifying conformance to quality requirements shall be defined and their relationships shown on organization charts.  

b) Provide  for  the  review  by  management  of  the  status  and  adequacy  of  the  quality assurance programme.  

Page 10: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 9 of 10

c) Appoint  a  representative  who  shall  report  regularly  to  management  at  a  level  that ensures  that  quality  assurance  requirements  are  not  subordinated  to  design, manufacturing,  construction  or  delivery  and  define  his  authority  to  resolve  quality matters.  Engineer shall be notified of the appointment in writing.  

d)  Design  the  responsibility  and  authority of personnel who  are primarily  responsible  for quality  assurance  and  their  organizational  independence  during  audits  and  define  the responsibility and authority of personnel who are primarily responsible for quality control and their organizational independence to:  

•  Identify and record quality problems.  •  Initiate or recommend or provide solutions through designated channels.  •  Verify the implementation of dispositions.  •  Control  further processing, delivery or  installation of a non  conforming  item or 

service untill the deficiency or unsatisfactory condition has been resolved.  • Note  that,  generally,  audit  personnel  shall  not  be  within  the  pattern  of  daily 

activities.   e)  Use  competent  persons  for  inspection,  other  than  those  performing  or  directly 

supervising  the  work  being  inspected,  unless  specifically  designated  otherwise  in  the quality plan.   Such persons shall report to an adequate  level of management, excluding direct reports to supervisors responsible for producing the work being inspected.  

        9.4.3   Quality Assurance Documents  

       a)  Quality Assurance Manual  

              i)      The Contractor shall:  

  Prepare a quality assurance manual, approved and signed by a senior management official, and submit it for the Engineer’s concurrence before the contract is awarded or at the latest before the work starts.  A quality assurance manual submitted under a previous contract or tender may be referred to.    Review and update the manual to reflect current quality assurance policies and procedures and resubmit the resulting manual.    Implement the programme according to the provisions specified in the manual.  

      ii) The quality assurance manual shall deal as appropriate with the following:  

Organization – The manual shall define the organizations  measures.  

Quality manual – The manual shall define the organizational measures.  

Quality plan – The manual shall  identify the group responsible for the quality plant as specified and define its main principles and features in adequate procedures.  

Quality  assurance  procedures  –  Documented  quality  assurance  procedures  as 

Page 11: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 10 of 10

specified shall be included or shall be outlined and cross referenced. Referenced QA procedures shall be made available to the quality assurance representative.  

  Manual review – A statement shall be incorporated for reviewing and updating the 

manual as specified.   b)  Quality plan                 i)  The Contractor shall:  

• Plan the inspection and test activities.  • Identify  in the quality plan the  inspections and tests to be performed on the  items 

listed  in  the  contract,  in  compliance  with  contractual  and  /  or  technical requirements.  

  Submit the plan for the Engineer’s concurrence following the award of the contract 

and before  the work starts. Referenced  inspection and  test specifications and / or procedures shall be made available  to  the quality assurance  representative during the implementation of the quality plan.  

  Update  the  plan  during  the  life  of  the  contract  to  reflect  current  conditions  of 

manufacturing,  construction,  inspecting  and  testing  and  resubmit  the  plan  to  the Engineer.  

              ii)  The quality plan may be of any format to suit the contractor’s system.  The quality plan 

shall deal as appropriate with :            

Identification of the characteristics or items to be inspected and tested.   Identification of  required  inspection,  test and special process operations and  their 

relative location in the construction cycle.  The contractor may include additional in‐process inspection points for his own evaluation of quality which will not be subject to acceptance and witness by the quality assurance representative.  

Reference to inspection, test and special process procedures, standards, acceptance criteria and sampling plan, if any. 

Indication  of  hold  points  beyond  which  the  activity  shall  not  proceed  until  the required  inspections  or  tests  have  shown  satisfactory  results  and  have  been documented. 

Provision  for  the Engineer  Incharge  to  insert witness points at which  the activities are to be observed. The activity may nevertheless proceed beyond a witness point should the Engineer fail to attend in spite of due notification. 

iii) The quality plan  for subcontracted  items, when concurred with by  the Contractor, shall be submitted  to  the Engineer as applicable,  for concurrence and  insertion of witness points. 

Page 12: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 1 of 139

Chapter‐ I  

SECTION – II:    DETAILED SPECIFICATION FOR CIVIL CONSTRUCTION WORKS  

TABLE OF CONTENTS  

Section  Title 

C‐01  Technical Specification For Site Clearance And Grading 

C‐02  Technical Specification for Excavation and backfilling 

C‐03  Technical Specification for Anti ‐ termite treatment 

C‐04  Technical Specification for Soling and Hardcore 

C‐05  Technical Specification for Plain & reinforced concrete and allied works 

C‐06  Technical Specification for Masonry and Allied Works 

C‐07  Technical Specification for Plastering & pointing 

C‐08  Technical Specification for Flooring & Allied Works 

C‐09  Technical Specification for Steel Doors, Windows, Ventilators, Louvers 

C‐10  Technical Specification for wood work, carpentry & joinery 

C‐11  Technical Specification for Rolling Steel Shutter & Grills 

C‐12  Technical Specification for Aluminum works 

C‐13  Technical Specification for Glass and Glazing 

C‐14 Technical Specification for Painting, White‐Washing. Distempering and other finishing work 

C‐15  Technical Specification for Drainage, Sanitation and Water Supply 

C‐16  Technical Specification for Road & Pavements 

C‐17  Technical Specification for Supply and Laying of RCC pipes 

C‐18  Technical Specification for Water proofing treatment for roofs. 

C‐19  Technical Specification for Heat  Resistant  Concrete. 

C‐20  Technical Specification for Site  Levelling and  Load Bearing  Fills. 

  

Page 13: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 2 of 139

 C ‐ 01: SITE CLEARANCE & LEVELLING 

 1.0                       SITE CLEARING  1.1                      This specification covers the requirements of site clearance and site leveling.  1.2                        The Tenderer shall  inspect the site to determine the extent of all  items to 

be cleared and  the cost of  this work  is deemed  to be  included  in  the  item allowed for site clearance. 

 1.3                        No  trees  or  bushes  are  to  be  cut  without  the  prior  approval  of  the 

Department who shall have to be notified at  least 48 hours before starting this  work.  All  trees  and  bushes  cut  shall  become  the  property  of  the Department  and  shall  have  to  be  stacked  in  an  orderly  manner  by  the Tenderer and as directed by the officers of the Department adjacent to the main road so that they can be easily loaded on lorries by the Department 

 1.4  All boulders shall be stacked in neat piles on approved sites and locations.  1.5  All combustible matter shall be disposed of as directed by the Consultant  2.0  LEVELING  2.1  The site shall be brought to a fairly good level for grid marking pillars to be 

established. The  formation  level of the site shall be a minimum of 150mm higher than the average existing ground level, unless otherwise specified in the drawings. 

 2.2  Any  special natural  features  such as  small hillock,  trees, etc.,  shall not be 

disturbed and shall form part of light landscaped area. 2.3  The site development includes leveling and filling, outside the boundary for 

approaches,  construction  of  compound  walls,  drains,  and  culverts  at required locations 

          

Page 14: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 3 of 139

C‐ 02 : EXCAVATION  WORK AND BACKFILLING  1.0    SCOPE   1.1  This  section  of  the  specification  covers  the  technical  requirements  for 

excavation  and  filling  &  around  structures,  buildings,  pipes,  foundations, trenches, pits, drains, channels, cable ducts, underground facilities & similar works.  It  also  covers  filling  areas  and  plinths  with  selected  materials, conveyance and disposal of surplus spoils at the waste dumps shown on the drawings  and/or  stacking  them  properly  as  directed  by  the Engineer/Consultant. 

     1.2                       The Tenderer shall be fully responsible for proper setting out works, profiling 

in  excavation,  stacking,  etc.  taking  adequate  safety  measures  etc.  The Tenderer  shall  carry  out  all  works  meant  within  the  intent  of  this specification  even  if  not  explicitly  mentioned  herein.  All  works  shall  be executed to the satisfaction of the Consultant. 

 1.3  Existing  trees,  shrubs,  any  other  plants,  pole  lines,  fences,  signs, 

monuments,  buildings,  pipelines,  drains,  sewers  or  other  surface  or subsurface systems/ drainage facilities within or adjacent to the works being carried out which are not to be disturbed, shall be protected from damage by the Tenderer. The Tenderer shall provide and  install suitable safeguards approved by the Consultant for this purpose. 

 1.4  Excavated  material  if  permitted  by  Consultant  shall  be  used  for  filling/ 

backfilling.  Unsuitable  material/  excess material  shall  be  disposed  off  as directed  by  Consultant  at  waste  dump  locations  shown  on  the  tender drawings. 

 2.0  GENERAL  2.1                        The Tenderer shall make his own surveying arrangements  for  locating  the 

coordinates  and  positions  of  all work  and  establishing  the  reduced  levels (RL’s) at  these  locations based on  two  reference grid  lines and one bench mark which will be furnished by the Owner. The Tenderer has to provide at site all  the  required  survey  instruments, along with qualified  surveyors,  to the  satisfaction  of  the  Consultant  so  that  the  work  can  be  carried  out accurately and according to the specification and drawings. 

 2.2  The Tenderer shall control the grade in the vicinity of all excavations so that 

the  surface  of  the  ground  will  be  properly  sloped  or  dyked  to  prevent surface water from running into the excavated areas during construction. 

 

Page 15: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 4 of 139

2.3  Excavation shall include removal of trees including roots & organic remains, vegetation, grass, bushes,  shrubs, plants, poles,  fences etc.  that are  in  the area to be excavated as well as beyond the excavation  line so as to ensure safety of the excavated side slopes and of men and equipment operating in the  area.  Before  start  of  excavation work,  joint measurements  of  ground level shall be taken after clearing all grass, vegetation etc. 

 2.4  Excavation shall include the removal of all materials required to execute the 

work properly and shall be made with sufficient clearance as decided by the Consultant  to  permit  the  placing  and  setting  of  forms,  inspection  and completion of all works  to  the satisfaction of  the Consultant  for which  the excavation was done. 

 3.0  CODES AND STANDARDS  3.1  All  standards,  specifications,  acts  and  code  of  practice  referred  to  herein 

shall be the  latest editions  including all applicable official amendments and revisions. 

 3.2  In case of conflict between this specification and those (IS standards, codes 

etc.) referred to here‐in, the former shall prevail.  3.3                 Some of the relevant Indian standards, Acts and Codes are referred to here 

below:  

IS: 3764  1992  Safety code for excavation work IS: 4081  1986  Safety  code  for blasting and  related drilling 

operations IS: 4701  1982  Code of practice for earth work on canals IS: 9759  1981  Guide  lines  of  dewatering  during 

construction IS: 10379  1982  Code of practice for field control of moisture 

and  compaction  of  soils  for  embankment and sub grade 

    Indian Explosives Act 1940 as updated.       4.0  EXCAVATION IN SOIL  4.1    Side and bottom of excavation shall be cut sharp and true to  line and  level. 

Undercutting  shall  not  be  permitted.  When  machines  are  used  for excavation,  the  last  300 mm  before  reaching  the  required  level  shall  be excavated manually or by such equipment that soil at the required final level 

Page 16: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 5 of 139

will  be  left  in  its  natural  condition.  Suitability  of  strata(at  the  bottom excavations)  for  laying  the  foundation  thereon  shall be determined by  the Consultant. 

 4.2  Excavation  for  foundation  shall be  to  the bottom of  lean  concrete  and  as 

shown  on  drawing  or  as  directed  by  the  Consultant.  The  bottom  of  all excavations  shall  be  trimmed  to  required  levels  and  when  excavation  is carried below such  levels by error,  it shall be brought back to the specified level by filling with concrete of nominal mix (1:3:6) (cement: coarse sand: 40 mm down aggregates) as directed by the Consultant at no extra cost.  

 4.3  All excavation  for  installation of underground  facilities,  such  as pipe  lines, 

drain  lines  etc.  shall be open  cuts.  For deep  and huge  excavations  and  in other excavations,  if required by the Consultant, the Tenderer shall submit for Consultant’s approval an “Excavation Scheme” showing the methodology to be adopted for excavation.  

 4.4  When  excavation  requires  bracing,  sheeting  or  shoring  etc.  the  Tenderer 

shall submit drawings to the Consultant, showing arrangements and details of  proposed  installation.  The  Tenderer  shall  also  furnish  all  supporting calculations as called for and shall not proceed until he has received written approval  from  the Consultant. However,  the  responsibility  for adequacy of such bracing, sheeting, shorting etc. will rest with the Tenderer, irrespective of any approval of the Consultant. 

 4.5  The  Tenderer  shall  have  to  constantly  pump  out  any  water  collected  in 

excavated pits and other areas due to rain water, springs etc. and maintain dry  working  conditions  at  all  times  until  the  excavation,  placement  of reinforcement,  shuttering,  concreting,  backfilling  is  completed.  The Tenderer shall remove all slush/muck from the excavated areas to keep the work area dry. The Tenderer, if required, shall employ sludge pumps, for this purpose. 

 4.6  The Tenderer  shall  remove all materials arising  from excavations  from  the 

vicinity of the work either for direct filling, stacking for the subsequent filling or for ultimate disposal at the waste dumps shown on the drawings and as directed  by  the Owner/Consultant.  In  no  case  shall  the  excavated  soil  be stacked within a distance of 1.5 m from the edge of excavation or one‐third the depth of excavation whichever  is more. Material  to be used  for  filling shall be kept separately. 

    

Page 17: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 6 of 139

5.0  EXCAVATION IN ROCK  5.1 For the work of excavation in rock, Tenderer shall engage specialized agency 

having experience of excavation in rock involving wedging and blasting. The agency  shall  be  approved  by  Consultant  and  the  Tenderer  shall  furnish details  of  relevant  experience  in  support  while  seeking  approval  for  the agency.  All  relevant  approvals  from  the  Licensing  agency  and  regulations shall be followed. 

 5.2  In  case  of  over  breaks  in  rock  excavation,  the  excavated  level  shall  be 

brought  to  the  level  shown  on  drawings  with  plain  cement  concrete  of nominal mix (1:3:6) as described earlier. 

 5.3  Where blasting  is prohibited  for any  reasons or  it  is not practicable  in  the 

opinion  of  the  Consultant,  then  the  excavation  shall  be  carried  out  by chiseling,  wedging  or  any  other  approved  method.  The  decision  of  the Consultant in this regard shall be final binding on Tenderer. 

 6.0    EXCAVATION BELOW GROUND WATER TABLE  6.1                  The  Tenderer  shall  dewater  and  maintain  dry  working  conditions  by 

maintaining  the water  table  below  the  bottom  of  the  excavation  level  by well‐point  dewatering  or  deep  well  dewatering  or  any  other  method approved  by  the  Consultant.  He  shall  continue  doing  so  till  excavation, concreting,  curing,  and  all other operation  included  in  the  scope of work, which require dry condition in the area are completed. 

 7.0    FILLING  7.1    MATERIALS 

 7.1.1  Materials to be used for filling purpose shall be approved earth, stone, sand 

or other  inorganic materials and  they shall be clean and  free  from shingle, salts,  organic  matter,  large  roots  and  excessive  amount  of  sod,  lumps, concrete or  any other  foreign  substances which  could harm or  impair  the strength of the substances in any manner. All clods shall be suitably broken to small pieces. When the materials are mostly rock boulders, these shall be broken into pieces not larger then 150 mm size. Sand used for filling shall be clean, medium grained and free from impurities. Fines less than 75 microns shall not be more than 20%. In any case, the materials to be used for filling purposes shall have the prior written approval of the Consultant.  

7.1.2  If  excavated materials  are  to  be  used  for  filling,  then  the  Tenderer  shall select the materials from the stockpile, land and transport this material and 

Page 18: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 7 of 139

execute the filling. This shall include excavation of earth, which may become hard due to laying in stockyard for a long period of time.  

7.1.3  In case the materials have to be brought  from pits/quarries,  it shall be the Tenderer’s  responsibility  for  identification  of  such  quarry  areas,  obtaining approval  from  their  use  from  concerned  authorities,  excavation/quarrying loading  and  carriage  of  such  material,  unloading  and  filling  at  specified locations. The Tenderer shall pay any fees, royalties etc. that may have to be paid for utilization of borrow areas. 

 7.2    FILLING PROCEDURE  7.2.1  After  completion  of  foundation,  footings,  walls  and  other  construction 

below  the  elevation of  the  final  grades,  and prior  to  filling,  all  temporary shoring,  timber  etc.  shall  be  sequentially  removed  and  the  excavation cleaned of all trash, debris, and. perishable materials. Filling shall begin only with the written approval of the Consultant. Also, areas identified for filling shall be cleared of all soft pockets, vegetation, bushes, slash etc.  In case of plinth  and  similar  filling  the  ground  shall  be  dressed  and  consolidated  by ramming and light rolling. 

 7.2.2  Fill materials shall not be dropped directly upon or against any structure or 

facility where  there  is  danger  of  displacement  or  damage.  Filling  shall  be started after the concrete/masonry has fully set and shall be carried out  in such a manner so as not to cause any undue lateral thrust on any part of the structure. 

 7.2.3  All  space  between  foundation  (concrete  or  masonry)  and  the  sides  of 

excavation shall be filled to the original surface after making allowance for settlement, Fill  shall be placed  in horizontal  layers not exceeding 200 mm loose  thickness.  Each  layer  shall  be watered  and  compacted with  proper moisture content and with such equipment as may be required to obtain a compaction/ density as specified. Trucks or heavy equipment for depositing or  compacting  fill  shall  not  be  used within  1.50 meters  of  building walls, piers  for  operation.  The  methods  of  compaction  shall  be  subjected  to approval of Consultant under any circumstances. 

 7.2.4  Fill adjacent to pipes shall be free of stones, concrete etc. and shall be hand 

placed  and  compacted  uniformly  on  both  sides  of  the  pipes  and  where practicable up to a minimum depth of 300 mm over the top of pipes. While tamping around the pipes, care should be taken to avoid unequal pressure. 

 7.2.5  Filling shall be accurately  finished to  line, slope, cross section and grade as 

shown on  the drawings. Finished  surface  shall be  free of  irregularities and 

Page 19: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 8 of 139

depressions and shall be within 20mm, of the specified level.  7.2.6  Where  filling with  stone  from  excavated materials  is  specified,  it  shall  be 

from broken pieces of boulders. At  first a 75 mm thick cushion of selected earth shall be laid over which the 200mm thick graded stones shall be laid in loose  layers of 200mm, then the  interstices filled with properly graded fine materials consisting of selected earth brought from borrow areas. Each layer shall  be watered  and  compacted  to  the  specified  density  before  the  next layer is laid. However, no cushion shall be required where filling is over non‐rocky surface. 

 7.2.7 Where  filling with 65 mm down graded  stone obtained  from excavated,  it 

shall  be  selected  stone  laid  over  and  initial  50 mm  thick  cushion  layer  of selected earth  and  then  stone  laid  in 200 m  loose  thick  layers,  interstices filled with  the  specified density before  the next  layer  in  laid. However, no cushion shall, be required where filling is over non‐rocky surface. 

 7.2.8  Where  clean  stone  fill  is  specified,  it  shall  consist  of  clean  selected  stone 

metal of 40 mm nominal size. It shall be laid in layers not exceeding 150 mm (loose) and lightly tamped before the next layer is laid. No compaction shall be required for this type stone filling.  

7.3 COMPACTION  7.3.1  Where compaction to 95% Standard Proctor Density or more is called for, it 

shall be by mechanical means only. Where  access  is possible,  compaction shall be by 12 tonne rollers smooth wheeled, sheep foot or wobbly wheeled as directed by the Consultant. A smaller weight roller may be permitted by the Consultant in special cases, but in any case not less than 10 passes of the roller will be accepted for each layer. Each layer shall be wetted or dried by aeration  to  a  moisture  content  of  3‐5%  above  the  Optimum  Moisture Content  to  be  determined  by  the  Tenderer.  Each  layer  shall  be watered, rammed and compacted to the density as specified Consultant. 

 7.3.2  For compacting each sand layer, water shall be sprayed and kept flooded for 

24 hours  to ensure maximum  compaction. Vibro‐compactors  shall  also be used  if  necessary  to  obtain  the  required  degree  of  compaction.  Any temporary works  required  to  contain  sand  under  flooded  condition  shall also be undertaken. The surface of the consolidated sand shall be dressed to required levels or slope. 

 7.3.3  After the compacted  fill has reached  the desired  level, the surface shall be 

flooded  with  water  for  24  hours,  allowed  to  dry  and  then  rammed  and consolidated to avoid any settlement, at a later date. The compacted surface 

Page 20: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 9 of 139

shall be properly shaped, trimmed and consolidated to an even gradient or level. All soft spots shall be excavated, filled and consolidated. 

 7.3.4  The degree of compaction of compacted fill  in place will be subject to tests 

by  the Consultant as  the work progresses, and  the Tenderer  shall provide the  necessary  facilities  to make  such  tests.  If  any  test  indicates  that  the compaction  achieved  is  less  than  the  specified degree of  compaction,  the Consultant may require  fill placed subsequent to the  last successful test to be removed and re‐compacted by the Tenderer. Compaction procedure shall be amended as necessary to obtain satisfactory results. 

 7.3.5  When semi‐compacted fill is specified by the Consultant, the Tenderer shall 

fill  up  such  areas with  available  earth  from  stock  piles  of  borrow  pits  or directly from excavation without special compaction except that obtained by moving trucks etc. 

               C‐ 03: ANTI ‐ TERMITE TREATMENT 

 1.0    GENERAL   1.1  Pre‐constructional anti–termite treatment shall be provided to all buildings 

with a chemical barrier against the sub‐terrain termites.  1.2  Anti‐termite  treatment  being  a  specialized  job,  should  be  got  executed 

through  specialized  agencies  only.  The  specialized  agency  should  be preferably a member of the Indian Pest Control Association.  

 1.3  The  scope  of  pre‐constructional  anti‐termite  treatment  covers  the  soil 

treatment  with  approved  chemicals  in  water  emulsion  in  foundation trenches for columns, plinth beams, pile caps, brick walls, service trenches, lift pits, steps, ramps etc., in top surfaces of plinth filling, at junction of walls and floor, in expansion joints etc., in stages as detailed in this specifications and drawings, unless otherwise specified, the anti‐termite treatment will be carried out as per  IS  : 6313  (Part‐II)‐2001 and  / or as per direction of  the Consultant.   

2.0    CHEMICAL TO BE USED   2.1  The  following  chemical  in  water  emulsion,  after  approval  from  the 

Consultant, shall be used uniformly over the area to be treated.   

  

Page 21: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 10 of 139

CHLROPYROPHOS  2.2  The Tenderer  should produce  voucher  (s)  for  the  chemical purchased and 

should  get  verified  the  sealed  container(s) of  the  specified  chemical  from the Consultant before preparing the emulsion / use for the treatment.  

 3.0    GUARANTEE  3.1  The Tenderer has to furnish the guarantee for 10 (ten) years from the date 

of  completion  of  work,  stating  that  in  case  of  reappearance  of  termites within the building area due to defective materials or workmanship or due to  any  other  reasons,  the  Tenderer  will  carry  out  the  necessary  post constructional  treatment  to  keep  the  entire  area  free  from  termite,  once again,  without  any  extra  cost  to  the  Department  during  the  guarantee period.  

 

Page 22: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 11 of 139

C – 04: SOLING & HARDCORE  1.0    GENERAL   1.1  The work  covered under  this  specification  includes all  type of  soling work 

either by rubble stones laid under floors / hardcore under foundations, hand packed, complete as per specification and applicable drawings.   

 2.0   RUBBLE STONE SOLING   2.1  The rubble stone shall be of best variety of black  trap / granite / basalt or 

other approved variety of stone available  locally.   The stone shall be hard, durable, free from defects and of required size and shall be approved by the consultant before incorporation in the work.  

  2.2                 Preparation of Surface & lying:   2.2.1   The  bed  on which  rubble  soling  is  to  be  laid  shall  be  cleared  of  all  loose 

materials,  leveled,  watered  and  compacted  and  got  approved  by  the Consultant before  laying  rubble soling.   Cable or pipe  trenches  if shown  in the drawing and as required by the Consultant shall be got done before the soling is started. 

  2.2.2   Over the prepared surface, the stone shall be set as closely as possible and 

well packed and firmly set.  The stones shall be of full height and shall be laid so as to have their bases of the largest area resting on the sub‐grade.  Soling shall be  laid  in one  layer of 230mm or 150mm or other specified thickness and  no  stones  shall  be  less  than  230mm  or  150mm  depth  or  specified thickness of soling with a tolerance of 25mm.  

 2.2.3  After packing the stones properly  in position, the  interstices between them 

shall  be  carefully  filled  with  quarry  spoils  of  stone  chips  of  larger  size possible  to  obtain  a  hard,  compact  surface.    Spreading  of  loose  spoils  or stone chips is prohibited.  

 2.2.4  All  interstices shall be  filled with approved murrum.   Excess murrum  if any 

over the surfaces shall be removed.  Unless otherwise specified, the murrum shall be supplied by  the Tenderer at his own cost  from  the selected areas. The  surfaces  shall  then  be watered  and  consolidated with mechanical  or sufficiently  heavy wooden  tampers  and  log‐rammers  as  approved  by  the Consultant  to  give  the  required  slope or  level  and dense  sub‐base.   After compaction,  the  surface  shall present  clean  look.   Adequate  care  shall be taken by the Tenderer while laying and compacting the rubble soling to see that concrete surfaces in contact with soling are not damaged.   

Page 23: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 12 of 139

 3.0  HARDCORE FOR FOUNDATIONS  3.1  Where specifically mentioned in the drawings, on specific recommendation 

of soil expert, hardcore  layer shall be provided as a preparatory surface to receive blinding concrete/ leveling course. 

 3.2  Hardcore layer shall comprise of well‐graded broken stones 80mm nominal 

size with the following gradation:  

IS Sieve designation  % passing 80 mm  100 63 mm  85‐100 40 mm  0‐30 20 mm  0‐5 10 mm  0‐5 

 3.3  The hard broken  stones  layer  shall be directly placed over  the  compacted 

layer  of  under  lying  soil  in  layers.  The  stones  shall  be  hand  packed  and crevices filled with broken stones. 

 3.4  Each layer shall be covered with clean river sand and thoroughly worked into 

the crevices with a water jet. Additional layers of sand shall be placed on top and worked  into  the  void  spaces.  The  process  shall  be  repeated  until  no more sand and water get into the voids.  

 3.5  Earth rammer shall be used to compact each layer if directed by Consultant.  3.6  The  thickness  and  area  covered  beyond  the  blinding  concrete  shall  be  as 

indicated in the drawings or as indicated by Consultant.    

C‐ 05: PLAIN AND REINFORCED CONCRETE & ALLIED WORKS  1.0    SCOPE 

 1.1  This  specifications  covers  the  general  requirements  for  concreting  to  be 

used  on  jobs  using  on‐site  production  facilities  including  requirements  in regard  to handling,  storage of  ingredients, proportioning, batching, mixing and  testing  and  quality  assurance.    This  also  covers  the  transportation  of concrete  from  the  mixer  to  the  place  of  final  deposit  and  the  placing consolidation, curing, protecting, repairing and finishing of concrete.  

Page 24: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 13 of 139

 1.2           The  Tenderer  shall  carry  out  all  works  meant  within  the  intent  of  this 

specification  even  if  not  explicitly  mentioned  herein.  All  works  shall  be executed to the satisfaction of the Consultant. 

 2.0    CODES AND STANDARDS 

 2.1        All work  shall  be  carried  out  as  per  the  stipulations  contained  in  various 

sections of these specifications and the latest Indian Standards, Acts, Codes and best practices. 

 2.2             All  applicable  standards,  specifications,  etc.  and  codes  of  practice  shall 

generally be the latest editions, including all applicable official amendments and  revisions.  A  complete  set  of  all  these  documents  shall  generally  be available at site, with the Tenderer. 

 2.3           In case of conflict between the stipulations contained  in various sections of 

these  specifications  and  stipulations  of  Indian  Standards,  Codes,  etc.  the requirements  of  stipulations  contained  in  various  sections  of  these specifications, shall prevail over that of Indian Standards, Codes, etc. 

 2.4              The following are the various relevant Indian Standards:  

IS ‐  73  1992  Specification for paving bitumen IS – 216  1961  Specification for coal tar pitch IS – 269  1989  Specification  for  33  grade  Ordinary  Portland 

cement IS – 280  1978  Specification  for  mild  steel  wire  for  general 

Engineering purposes  IS – 383  1970  Specification  for  coarse  and  fine  aggregates  from 

natural sources for concrete IS ‐ 432 (Parts I)  1982  Specification  for  mild  steel  medium  tensile  steel 

bars  and  hard  drawn  steel  wire  for  concrete reinforcement – Mild steel & medium tensile bars 

IS ‐ 432(Parts II)  1982  Specification  for  mild  steel  medium  tensile  steel bars  and  hard  drawn  steel  wire  for  concrete reinforcement  ‐ Hard drawn steel wire 

IS: 455  1989  Specification for Portland slag cement IS: 456  2000  Code of practice for plain and reinforced concrete IS. 457    Code of practice  for plain and  reinforced concrete 

for dams and other massive structures. IS. 515    Specification  for  natural  and  manufactured 

aggregate for use in mass concrete. 

Page 25: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 14 of 139

IS: 516  1959  Method of test for strength of concrete  IS – 650  1991  Specification  for  standard  sand  for  testing  of 

cement IS: 702  1988  Specification for industrial bitumen IS: 800  1984  Code of practice for general construction in steel IS: 816  1969  Code  of  practice  for  use  of metal  are welding  for 

general construction in mild steel IS: 1161  1998  Specification for steel tubes for structural purpose 

IS: 1322  1993  Specification  for  bitumen  felts  for  waterproofing and damp proofing  

IS: 1363 (Part 1)  2002  Hexagon head bolts, screws and nuts of product grade ‘C’ – Hexagon head bolts (size range M 5 to M 64) 

IS: 1363 (Part 2)  2002  Hexagon head bolts, screws and nuts of product grade ‘C’ – Hexagon head screws (size range M 5 to M 64) 

IS: 1363 (Part 3)  2002  Hexagon head bolts, screws and nuts of product grade ‘C’ – Hexagon nuts (size range M5 to M 64) 

IS – 1609  1991  Code  of  practice  for  laying  damp  proofing treatment using bitumen felts. 

IS – 1786  1985  Specification for high strength deformed steel bars and wires for concrete reinforcement. 

IS: 1834  1984  Specification  for hot applied sealing compound  for joints in concrete 

IS: 2016  1967  Plain washers IS: 2074  1992  Specification  for  ready  mix  paint,  air  drying,  red 

oxide zinc chrome IS ‐ 2386 (Part 1)  1963  Methods  of  test  of  aggregates  for  concrete  – 

Particle size & shape IS ‐ 2386 (Part 2)  1963  Methods  of  test  of  aggregates  for  concrete  – 

Estimation  of  deleterious  material  and  organic impurities 

IS ‐ 2386 (Part 3)  1963  Methods  of  test  of  aggregates  for  concrete  – Specific  gravity,  Density,  voids,  absorption  and bulking 

IS ‐ 2386 (Part 4)  1963  Methods  of  test  of  aggregates  for  concrete  – Mechanical properties 

IS ‐ 2386 (Part 5)  1963  Methods  of  test  of  aggregates  for  concrete  – Soundness 

IS ‐ 2386 (Part 6)  1963  Methods  of  test  of  aggregates  for  concrete  – Measuring  mortar  making  properties  of  fine aggregates 

IS ‐ 2386 (Part 7)  1963  Methods of test of aggregates for concrete – Alkali 

Page 26: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 15 of 139

aggregate reactivity IS ‐ 2386 (Part 8)  1963  Methods  of  test  of  aggregates  for  concrete  – 

Petrographic examination I.S. 2438    Specification for roller pan mixer. IS – 2502  1963  Code of practice  for bending and  fixing of bars  for 

concrete reinforcement. I.S 2505.     Specification  for  immersion  type  concrete 

vibrators. I.S. 2506    Specification for screed board concrete vibrators. I.S. 2514    Specification for concrete vibrating table. IS – 2571  1970  Code of practice for  laying  in‐situ cement‐concrete 

flooring. IS – 2645  2003  Specification  for  Integral  cement  water  proofing 

compounds for cement mortar and concrete I.S. 2722    Specification  for portable  swing weigh batcher  for 

concrete. IS ‐ 2751  1979  Code of practice for welding of mild steel plain and 

deformed  bars  for  reinforced  concrete construction. 

IS. 3025    Methods  of  sampling  and  test  (physical  and chemical) for water used in industry. 

IS ‐ 3037  1986  Specification  for  bitumen mastic  for  use  in water proofing of roofs 

IS ‐ 3150  1982  Specification for hexagonal wire netting for general purposes. 

I.S. 3366    Specification for pan vibrator. IS ‐ 3370 (Part I)   1965  Code  of  practice  for  concrete  structures  for  the 

storage of liquids – General requirements IS ‐ 3370 (Part II)   1965  Code  of  practice  for  concrete  structures  for  the 

storage of liquids‐ Reinforced concrete structures IS ‐ 3384  1986  Specification  for  bitumen  primer  for  use  in 

waterproofing & damp proofing. IS ‐ 3414  1968  Code of practice for design and installation of joints 

in buildings. IS ‐ 3550  1965  Methods of test for routine control for water used 

in Industry. IS ‐ 4130  1991  Safety Code for demolition of buildings. IS ‐ 4326  1993  Code  of  practice  for  earthquake  resistant  design 

and construction of buildings. IS ‐ 5525  1969  Recommendations for detailing of reinforcement in 

reinforced concrete work. IS ‐ 5624  1993  Specification for foundation bolts. IS ‐ 7861 (Parts I)  1975  Code of practice for extreme weather concreting –

Page 27: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 16 of 139

Recommended practice for hot weather concreting IS: 8112  1989  Specification  for  43  Grade  Ordinary  Portland 

Cement IS ‐ 10262  1982  Recommended guidelines for concrete mix design. IS. 12269    Specifications  for  high  strength  ordinary  Portland 

cement (Grade 53). IS.13311 (Part‐I)    Non‐destructive testing of concrete: Method of test 

for ultrasonic pulse velocity. IS. 13311 (Part‐II)     Non‐destructive  testing  of  concrete:  Method  of 

testing by rebound hammer. SP ‐ 23   1982  Handbook of concrete mixes. SP ‐ 24   1983  Explanatory Handbook on IS: 456 SP ‐ 34  1987  Handbook  on  concrete  reinforcement  and 

detailing.  

3.0      MATERIALS   3.1    GENERAL:  3.1.1           All the materials used in the manufacture of concrete shall be in accordance 

with  these  specifications,  Storage  and  Handling  of  Common  Building Materials, which shall be deemed to form a part of this specification. 

 3.1.2  The Consultant shall have the right to  inspect the sources of materials, the 

layout and operation of procurement and storage of materials, the concrete batching  and  mixing  equipments  and  the  quality  control  system.    The Tenderer  shall  arrange  such  an  inspection  and  the  Consultant  s  approval shall be obtained prior to starting the work. 

 3.2    AGGREGATES  3.2.1  Aggregate shall consist of natural sand, crushed stone/gravel from a source 

known  to  produce  satisfactory  aggregate  for  concrete  and  shall  be chemically  inert,  strong,  hard,  durable  against  weathering,  of  limited porosity and free from deleterious materials that may cause corrosion to the reinforcement or may  impair  the  strength and  / or durability of  concrete.  Aggregates shall conform to IS:383. 

    

Page 28: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 17 of 139

3.2.2   STORAGE OF AGGREGATES:      All coarse and  fine aggregates shall be stacked separately  in stock piles  in 

the material yard near  the work  site  in bins properly constructed  to avoid inter mixing of different aggregates.   Contamination with  foreign materials and earth during storage and while heaping the materials shall be avoided.  The aggregate must be of specified quality not only at the time of receiving at site but also at the time of loading into mixer.   

 3.3    CEMENT  3.3.1  The cement generally used  shall be  the Ordinary Portland cement 43  / 53 

grade. However, any special type of cement such as High strength cement or sulphate resisting cement may be used under specific circumstances. 

 3.3.2  The Tenderer shall make his own arrangements for the storage of adequate 

quantity of cement.  If supplies are arranged by the Department, cement will be  issued  in quantities to cover work requirements of one month or more, as  deemed  fit  by  the  Consultant  and  it  will  be  the  responsibility  of  the Tenderer  to  ensure  adequate  and  proper      storage,  which  will  provide complete  protection  from  dampness,  contamination  and minimize  caking and  false set. Cement bags shall be stored  in a dry enclosed shed  (storage under tarpaulins will not be permitted), well away from the outer walls and insulated from the floor to avoid contact with moisture from ground and so arranged  as  to  provide  ready  access. Damaged  or  reclaimed  or  partly  set cement will not be permitted to be used and shall be removed from the site.  The storage arrangements shall be such that there  is no dead storage.   Not more  than 12 bags  shall be  stacked  in any  tier.   The  storage arrangement shall be got approved by  the Consultant. Consignments of cement shall be stored as received and shall be consumed in the order of their delivery. 

 3.4    REINFORCEMENT 

 3.4.1  Steel reinforcement bars for concrete shall be corrosion resistant TMT bars 

with strength requirements conforming  to Grade Fe‐415/Fe500 of  IS: 1786 manufactured by SAIL, TATA or RINL.  

 3.4.2  Storage: Steel reinforcement shall be stored in such a manner that they are 

not  in direct contact with ground but stacked on top of an arrangement of timbers sleepers or  the  like. Bars of different classifications and sizes shall be  stored  separately.  In  cases  of  long  storage  or  in  coastal  areas, reinforcement shall be stacked above ground level by at least 15 cm, and a coat  of  cement wash  shall  be  given  to  prevent  scaling  and  rusting  at  no 

Page 29: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 18 of 139

extra cost to the owner. Fabricated reinforcement shall be carefully stored to prevent, distortion, corrosion and deteriorations. 

 3.5                WATER  3.5.1            Water  used  for mixing  and  curing  shall  be  clean  and  free  from  injurious 

amounts of oils, acids, alkalis, sugar, organic materials or other substances that may  be  deleterious  to  concrete  or  steel.  Potable  water  is  generally considered  satisfactory  for  mixing  concrete.  The  maximum  permissible values of impurities shall be as given in clause no. 5.4 of lS: 456. 

 3.6  ADMIXTURES  3.6.1        Admixtures  in concrete  for promoting workability, entraining air  for similar 

purposes may be used only after the written permission from the Consultant is  obtained.  These  shall  be  free  from  injurious  amount  of  chloride,  etc. Addition  of  admixtures  should  not  reduce  the  specified  strength  or durability  of  concrete  and  should  not  have  detrimental  effect  on reinforcement.  The  admixtures  shall  conform  to  lS‐9103  and  shall  be  of proven  make  and  from  a  reputed  manufacturer.  Calcium  chloride  as accelerating  admixture  is  not  permitted  to  be  used  other  than  in  mass concrete works. The Tenderer shall produce latest test results carried out at approved  Government  Test  Houses  for  the  approval  of  the  Consultant, before use. 

 3.7    EMBEDDED PARTS  3.7.1  Steel for light structural work and for preparation of inserts and embedment 

shall conform to IS:2062.  3.7.2  Bolts  to  be  embedded  in  concrete  shall,  unless  otherwise  detailed  in 

drawings,  conform  to  IS:5624. Material  for  bolts,  shall,  unless  otherwise mentioned  in  drawings  or  the  schedule  of  items,  be  corrosive resistant/coated steel conforming to IS:2062. 

 3.7.3  Nuts and  locknuts shall conform to  IS:1363 (Part 1 to 3) for diameters 6 to 

39 and IS: 3138 for  Hexagon Bolts and Nuts (M‐42 to M‐150)  3.7.4  Plain washers shall conform to IS:2016 and spring washers shall conform to 

IS:3063.  

3.7.5                 Steel pipe sleeves shall conform to Medium class of IS:1161.   

Page 30: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 19 of 139

4.0    CONCRETE MIX, WORKABILITY & DURABILITY  4.1             Concrete mix proportions  shall be  selected  based on  the  requirements of 

workability, strength, and durability. The proportions of cement, aggregates and  water  shall  be  determined  only  by  designing  the  mix.  Design  mix concrete shall be designated as M20, M25, etc.  

 4.2     WORKABILITY  

 Workability of  fresh concrete  is mainly governed by placing conditions and compaction. The degree of workability necessary to allow the concrete to be well compacted and to be worked into the corners of formwork and around the reinforcement shall be as stipulated under clause no. 7.0 of IS:456.   a) Consultant may permit use of plasticizers for improving workability. Use 

of  certain  other  admixtures  such  has water  proofing  compounds  also have an effect on workability and shall be considered during mix design. 

 4.3      DURABILITY OF CONCRETE:   

a) Durability  requirement  is  decided,  depending  on  the  exposure conditions  as  stipulated  in  clause  8.2  of  IS:456.  is  to  be  taken  into account  while  designing  the  mix.  For  given  aggregates,  the  cement content should be sufficient to make sufficiently low water cement ratio and  table  5  of  IS:  456‐2000  shall  be  taken  as  guideline  for  durability considerations. 

 b) Stipulations  of minimum  cement  content  and  limiting  water  cement 

ratio should be considered during design of mix.  5.0    PREPARATORY WORKS  5.1             Earth surface on which direct placement of concrete is to be placed shall be 

rammed and consolidated such that it does not crumble and get mixed with concrete during or after placement. If the foundation is quite wet, the same shall be kept dry and then sufficiently consolidated,  if necessary, a thin top layer of the wet soil shall be removed and replaced by sand or other suitable materials as directed by the Consultant without any extra cost to the Owner. Where  specified,  lean  concrete  shall be provided  in  the  earth  stratum  for receiving concrete.  The surface of absorptive soil against which concrete is to  be  placed  shall  be moistened  thoroughly  so  that  no moisture will  be drawn  form  the  freshly  placed  concrete.  In  case  the  drawings  indicate hardcore  below  the  blinding  concrete,  the  same  shall  be  provided  as  per relevant specifications. 

Page 31: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 20 of 139

 5.2  Preparation  of  concrete  surface  upon which  additional  concrete  is  to  be 

placed  later,  shall preferably be done by  scarifying and  cleaning while  the concrete  is  between  its  initial  and  final  set.    This method  shall  be  used wherever practicable and shall consist of cutting the surface with picks and stiff brooms and by use of an approved combination of air and water jet as directed by Consultant.  Great care shall be taken in performing this work to avoid  removal  of  too much mortar  and  the weakening  of  the  surface  by loosening  of  aggregate.   When  it  is  not  practicable  to  follow  the  above method,  it will  be  necessary  to  employ  air  tools  to  remove  laitance  and roughen  the  surface.  The  final  resulting  surface  shall  be  a  pitted  surface, from which all dirt, unsound concrete, laitance and glazed mortar have been removed.  

 5.3        All  such  joints  shall  have  continuous  square  bond  grooves  to  produce  a 

substantial and water‐tight key. Where the placement of concrete has to be resumed on a surface which has hardened, it shall be roughened, cleaned by wire  or  bristle  brushing,  compressed  air,  water  jet  etc.,  and  thoroughly wetted.  

 6.0    FORMWORK AND STAGING  6.1           Formwork shall compose of steel, best quality wood or non‐absorbent type 

plywood. Timber shall be free from significant knots and shall be of medium grain as  far as possible and hard woods shall be used as caps and wedges under or over posts. Timber shall be well seasoned,  free  from sap, shakes, wormholes, warps or other surface defects and shall have smooth finish. 

 6.2           The Tenderer shall maintain necessary camber in centering for all floor slabs 

and  beams  in  all  spanning  directions,  so  as  to  offset  the  deflection  and assume correct shape. The camber shall have the crown of not  less than 8 mm  for every 5 metres span unless otherwise shown on  the drawings. For cantilever, camber at free end shall be 1 in 100. 

 6.3           The Tenderer shall begin the removal of formwork only after approval of the 

Consultant.  Forms  of  various  types  of  structural  components  shall,  under normal  circumstances,  not  be  removed  before  the  minimum  periods specified in Cl. 11.3 of IS:456 

 6.3.1            Tolerances  is  a  specified  permissible  variation  from  lines,  grade  or 

dimensions  given  in  drawings.    Unless  otherwise  specified,  the  following tolerances will be permitted.  

  

Page 32: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 21 of 139

TOLERANCES FOR R.C. BUILDINGS  

Variation from the plumb In the line and surfaces of columns, piers, walls and in buttresses 

5 mm per 2.5 m, but not more than 25 mm 

For exposed corner columns and other conspicuous lines In any bay or 5 m. maximum  (+/‐) 5 mm 

In 10 m. or more  (+/‐) 8 mm.   Variation from the level or from the grades indicated on the drawings 

In slab soffits, ceilings, beam soffist and in arises.   

 

In 2.5 m    (+/‐) 5 mm. In any bay or 5 m. maximum  (+/‐) 8 mm 

In 10 m. or more  (+/‐)15mm For exposed lintels, sills, parapets, horizontal grooves and other conspicuous lines In any bay or 5 m. maximum  (+/‐)15mm 

In 10 m. or more  (+/‐)10mm Variation of the linear building lines from established position in plan and related position of columns, walls and partitions In any bay 5 m. maximum  (+/‐) 10 mm 

In 10 m. or more  (+/‐) 20 mm. 5  Variations in the sizes and locations of 

sleeves, openings in walls and floors except in the case of and for anchor bolts 

(+/‐) 5 mm 

6  Variation in  cross‐sectional dimensions of columns and beams and in the thickness of slabs and walls 

(+)10mm / (‐)5 mm     

Footings   variation in dimensions in plan  (+) 50 mm / (‐) 5 mm Misplacement of concentricity   2% of footing within the 

direction of misplacement but not more than 50 mm. 

Reduction in thickness    (‐) 5% of specified thickness subject to maximum of 50 mm.     

Variation in steps   In a flight of stairs   Rise  (+/‐) 3.0 mm 

Tread  (+/‐) 5.0 mm 

Page 33: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 22 of 139

In consecutive steps   Rise  (+/‐) 1.5 mm Tread  (+/‐) 3 mm 

  

TOLERANCE IN OTHER CONCRETE STRUCTURE  

All structures Variation of the constructed linear out line from established position in plan In 5 m  (+/‐) 10 mm. 

In 10 m. or more  (+/‐) 15 mm.   Variation of dimensions to individual structure features from established positions in plan In 20m. or more  (+/‐) 25 mm. 

In buried constructions  (+/‐) 150 mm Variation from plumb, from specifies batter or from cured surfaces of all structures In 2.5 m  (+/‐) 10 mm. In 5.0 m  (+/‐) 15 mm. In 10.0 m. or more :  (+/‐) 25 mm 

In buried constructions  (+/‐) Twice the above limits. Variation from level or grade indicated on drawings in slabs, beams, soffits, horizontal grooves and visible arises In 2.5 m  (+/‐) 5 mm. In 7.5 m. or more  (+/‐) 10 mm 

In buried constructions  (+/‐) Twice the above limits 5  Variation in cross‐sectional dimensions of 

columns, beams, buttresses, piers and similar members 

(+) 10mm./(‐) 5 mm. 

6  Variation in the thickness of slabs, walls, arch sections and similar members 

(+) 10 mm./(‐) 5 mm 

  FOOTINGS FOR COLUMNS, PIERS, WALLS, BUTTRESSES AND SIMILAR MEMBERS 

1  Variation of dimensions in plan  (+) 50 mm./(‐) 10 mm 2  Misplacement or eccentricity  2% of footing within the 

direction of misplacement but not more than 50 mm 

3  Reduction in thickness  5%  of specified thickness subject to a maximum of 50 mm. 

Page 34: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 23 of 139

7.0    REINFORCEMENT PLACEMENT  7.1  All  reinforcement  for  concrete  works  shall  be  provided  as  per  approved 

drawings.  The  Tenderer  shall  prepare  and  furnish  to  the  Consultant,  bar bending  schedules  for all RCC works  for his  review and approval. No work shall commence without  the approval of  the bar bending schedules by  the Consultant in writing. 

 7.2  All  bars  shall  be  thoroughly  cleaned  before  being  fabricated.  Pitted  and 

defective  bars  shall  not  be  used. All  steel  for  reinforcement  shall  be  free from  loose scales, rust coatings, oil, grease, paint or other harmful matters immediately  before  placing  the  concrete.  To  ensure  this,  reinforcements with rust coatings shall be cleaned thoroughly before bending/placement of the same. 

  7.3  Unless shown otherwise on the drawings, minimum clear concrete cover for 

reinforcement (exclusive of plaster or other finishes) shall be as specified in Cl. 26.4 of IS:456. 

 7.4  Special  requirements  in  corrosive  atmosphere:  Unless  special  protective 

coatings are used, the appropriate measures for structures exposed to sever conditions shall be followed. 

 8.0    EMBEDDED PARTS  8.1  Embedded  steel  parts  shall  be  supplied,  fabricated  and  erected  by  the 

Tenderer  and  shall  include  items  such  as,  but  not  limited  to,  foundation grillages, anchor bolts, pipe sleeves, equipment mounting plates, steel rolled sections with or without properly welded lugs, plate inserts, edge protection angles, as shown on the drawings, auxiliary framing for equipment supports, pegstay  plugs  for  door  and  window  frames,  miscellaneous  frames,  etc. Embeded parts shall not be welded to the reinforcement. 

 9.0    MIXING OF CONCRETE  9.1  Concrete  shall  be  mixed  in  a  mechanical  mixer  conforming  to  IS:1791. 

However, mixing shall preferably be done at a single central batching plant, conforming to IS:4925, situated within the area allocated for the Tenderer’s particular  use  as  directed  by  the  Consultant.  The  plant  shall  have  a mechanically  operated  mixer  of  an  approved  size  and  type,  capable  of ensuring a uniform distribution of  the materials  throughout  the mass and the mass is uniform in colour and consistency. 

 

Page 35: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 24 of 139

9.2  BATCHING OF CONCRETE  9.2.1  Aggregates  and  Cement  shall  always  be  batched  by  weight.  A  separate 

weighing device shall be provided  for weighing cement. Where the weight of cement  is determined by accepting the weight per bag, number of bags shall be weighed separately to determine the average net weight of cement per bag and the same shall be checked regularly. Water may be measured either by weight or by volume. 

 9.2.2         Any solid admixture, to be added, shall be measured by weight, but liquid or 

semi‐liquid admixture may be measured by weight or volume.  10.0    TRANSPORTATION OF CONCRETE  

 10.1  Concrete shall be handled and conveyed as rapidly as practicable, from the 

place of mixing to the place of final  laying, by approved means, before the initial setting of the cement starts. Concrete shall be conveyed in such a way that there is no segregation or loss of any of the ingredients and maintaining the  required  workability.  If  segregation  does  occur  during  transport,  the concrete  shall be  remixed. During very hot or cold weather,  if directed by the Consultant, concrete shall be transported in deep containers, which will reduce the rate of water loss by evaporation in hot weather and heat loss in cold weather, at no extra cost to Owner. 

 10.2  Concrete  may  be  conveyed  and  placed  by  mechanically  operated 

equipment,  e.g.  pumps  or  pneumatic  placers  only  with  the  written permission of  the Consultant, who  shall also  review  the entire  scheme  for which comprehensive details shall be furnished by the Tenderer. 

 11.0    CONCRETE PLACING  11.1  Before the concrete is actually placed in position, the inside of the formwork 

shall be inspected to see that they have been cleaned and oiled.  Temporary openings  shall be provided  to  facilitate  inspection, especially at bottom of columns  and wall  forms,  to  permit  removal  of  saw  dust, wood  shavings, binding wire,  rubbish, dirt etc., Opening  shall be placed or holes drilled  so that  these materials  and water  can  be  removed  easily.    Such  openings  / holes shall be later suitably plugged.  

 11.2  Formwork and reinforcement shall be approved in writing by the Consultant 

before  concrete  is  placed.  Concrete  shall  be  placed  only  after  all preparations  for  casting  have  been  approved  by  the  Consultant  and approval  given  to  proceed with  the  casting  in writing  on  pour  card  to  be maintained by the Tenderer for this purpose and to be submitted along with 

Page 36: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 25 of 139

the Tenderer’s bills.  

11.3  Slabs,  beams  and  similar members  shall  be  poured  in  one  operation.  In special  circumstances, with  the  approval  of  the  Consultant,  these  can  be poured  in horizontal  layers, but  it must be ensured  that  the under  layer  is not  already  hardened. Bleeding  of  under  layer,  if  any,  shall  be  effectively removed. Moulding, throating, drip course, etc. shall be poured as shown on the drawings or as desired by the Consultant. 

 11.4  No  concrete  shall be placed  in wet weather or on water  covered  surface.  

Any concrete that has been washed by heavy rain shall be entirely removed, if there  is any sign of cement and sand having been washed away from the concrete mixture.   

 11.5  For members involving vertical placing of concrete (eg. Columns, walls, etc.), 

each  lift  shall  be  deposited  in  horizontal  layer  extending  the  full  width between  shutterings  and of  such depth  that each  layer  can be easily  and effectively  vibrated  and  incorporated with  the  layer  before  by means  of compaction. 

 11.6    During hot weather (atmospheric temperature above 40 degree centigrade) 

the concreting shall be done as per the procedures and precautions set out in lS‐7861 (Parts I and II) 

 11.7   Under all ordinary conditions all foundations shall be completely de‐watered 

and  concrete  placed  on  the  dry  surface.    However,  when  concrete placement  under  water  is  necessary,  all  work  shall  be  executed  in accordance with clause 14.2 of IS ‐456  

 12.0  COMPACTION 

 12.1  After  the  concrete  has  been  placed,  it  shall  be  spaded  and  thoroughly 

compacted  by  approved mechanical  vibrators  to  a maximum  subsidence without segregation and thoroughly worked around reinforcement or other embedded fixtures  into the correct form and shape. Hand tamping in some cases may be allowed subject to the approval of the Consultant. Care must be  taken  to ensure  that  the  inserts,  fixtures,  reinforcement and  formwork are not displaced or disturbed during placing of concrete. 

 13.0  PROTECTION AND CURING OF CONCRETE 

 13.1    Newly placed concrete shall be protected by approved means from rain, sun 

and  wind.  Concrete  placed  below  ground  level,  shall  be  protected  from falling earth, during and after placing. Concrete placed in ground containing 

Page 37: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 26 of 139

any  deleterious  substances,  shall  be  kept  free  from  contact  with  such ground or with water draining from such ground, during placing of concrete and  for  a  period  of  at  least  three  days  or  as  otherwise  instructed  by  the Consultant. 

 13.2  The ground water around newly poured concrete shall be kept down to an 

approved level by pumping or other approved means of drainage. Adequate steps shall be taken to prevent floatation or flooding. Steps, as approved by the Consultant, shall be  taken  to protect  immature concrete  from damage by debris, excessive  loading, vibration, abrasion, mixing with earth or other deleterious materials, etc. that may impair the strength and durability of the concrete. 

 13.3  As soon as the concrete has hardened sufficiently, it shall be kept in a damp 

or wet condition by ponding or by covering with a  layer of sacking, canvas, hessian  or  similar materials  and  kept  continuously wet  for  at  least  seven days after final setting. This period may be extended, at the discretion of the Consultant,  upto  fourteen  days.  Curing  of  horizontal  surfaces  exposed  to drying  winds  shall  begin  immediately  after  the  concrete  has  hardened. Concrete slabs and floors shall be cured for the periods mentioned above by flooding with water of minimum 25 mm depth. 

 14.0  JOINTS IN CONCRETE  14.1  Joints  including  joint  filler  materials,  water  bars,  resilient  pads  type 

vibration, damping material in and around the sides of concrete works, etc. shall be provided as shown in the drawings or as directed by the Consultant. Where necessary or/and specified, joints shall be made watertight by use of water stops. 

14.2   Construction Joints: Location and treatment of construction joints shall be as approved by Consultant  

14.3  Contraction  Joints  provided  to  eliminate  tensile  stresses  due  to  shrinkage where temperature variations are small and where there is no likelihood of expansion, such as spaces below water and earth levels and not exposed to atmosphere.  At  contraction  joints,  the  reinforcement  is  discontinued  and bond is not allowed to develop between the joint faces, thereby introducing a  structural discontinuity. A contraction  joint also  serves as a construction joint so far as break in the pouring of concrete is concerned.  

14.4    Expansion  Joints provided either  to completely eliminate or  to significantly reduce  compressive  stresses  in  concrete  that  would  otherwise  result  by thermal expansion which might crush, buckle or crack, part of the structure. 

Page 38: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 27 of 139

Expansion  joints  serve  the  purpose  of  contraction  and  also  construction joints. Bitumen  impregnated  fiber board  shall be used as  joint  filler which shall  fill  space between  the  concrete  surfaces  at  the  joints. The minimum thickness of board shall be 12mm and the material shall conform to IS: 1838. Expanded polystyrene slab when used shall be of fire retarding grade (type‐2)  conforming  to  IS:  4671.  Density  of  material  shall  not  be  less  than 25kg/cum. 

 14.5  Water  stops  shall be provided  at  the  joints  as  a  continuous diaphragm  to 

contain the filler material and/or to exclude passage of water or any other material  into or out of the structure. The Water stops shall be nonmetallic like  P.V.C.  The  material  is  to  be  procured  from  reputed  manufacturers having proven records of satisfactory supply of Water Stops of similar make and shape for other jobs.  

 14.6  The bitumen  sealing  compound  shall be  from approved manufacturer and 

shall conform to the requirements of lS:1834. For joints in concrete lining on canals/reservoirs, sealing compound conforming to lS‐5256 shall be used.  

14.7  Polysulphide  sealant  shall be  from  approved manufacturer,  conforming  to lS:12118. Materials shall consist of polysulphide polymer and a curing agent. Gun grade material shall be used unless otherwise specified. The application of the sealant shall be strictly followed as per manufacturer’s guidelines. 

 14.8  Metal cover strips shall be made of aluminium as shown on drawings. The 

minimum thickness of aluminium strips shall be 3 mm.  Aluminium alloy strip shall be corrosion resistant grade 31000 as per IS:737.  

  

15.0  CEMENT ADDITIVES/ADMIXTURES IN CONCRETE  15.1  The admixtures  shall conform  to  IS:9103 and  shall be of proven make and 

from  a  reputed  manufacturer.  In  addition,  for  plasticizer‐cum‐water proofing compound, materials shall meet the permeability requirements as per  lS‐2645.  Similarly  for plasticizer‐cum  retarder  admixture material  shall satisfy  the  setting  time  requirements  of  retarder  and  other  properties  of plasticizer as per IS:9103 

 15.2  Admixtures  in  concrete  for  promoting  workability,  improving  strength, 

entraining  air  or  for  similar  purposes may  be  used  only  after  the written permission  from  the  Consultant,  is  obtained. Addition  of  admixtures  shall not reduce the specified strength or durability of concrete in any case.  

  

Page 39: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 28 of 139

16.0    GROUTING  

16.1    Ready mixed non‐shrink cementitious grout for Grouting under base plates and  foundation  pockets  shall  be  done  as  indicated  in  the  drawings,  or  as directed by Consultant. The contact area between the grout and base plate shall not be less than 80%  

16.2  Grouting  of  pockets/holes  in  concrete:  shall  be  done  using  cement‐sand grout or cement, sand and aggregate grout depending upon the size of the pockets/holes  in  the  concrete.  This mix  shall  generally  be  used  for  grout thickness above 40 mm for dry pack application. Normally the grade of such concrete/mortar shall not be less than the grade of parent concrete. In filling the  holes  of  foundation  bolts  and  expanding  admixture  of  approved  type shall be used as per manufacturer’s specification.. 

 16.3  Surface  to  be  grouted  shall  be  thoroughly  roughened  and  cleaned  of  all 

foreign matter and laitance. The block outs, bolt holes etc. which have to be grouted, shall be cleaned thoroughly by use of compressed air  just prior to taking up the grouting operation. 

 17.0    PRECAST CONCRETE ELEMENTS  17.1  Precast  concrete  elements  such  as  fencing  posts,  copings,  sills,  shelves, 

trench/ pit cover slabs, louvers, etc., shall be at least of mix M‐20. Concrete for Precast concrete shall comply with IS:456.  

 17.2  Precast  concrete  elements  shall be  cast  in  forms or moulds.    The  forms  / 

mould shall be of fiberglass or of steel sections for better finish.   Provision shall be made in the forms and moulds to accommodate fixing devices such as nibs, clips, hooks, bolts and forming of notches and holes. 

 17.3  Elements  shall  be  cast  on  suitable  bed  or  platform with  firm  foundation. 

Precast  elements  shall  have  a  dense  surface  finish  showing  no  coarse aggregate  and  shall  have  no  cracks,  crevices  or  other  defects  that would interfere with the proper placing of the units.  All angles of the precast units with  the exception of  the angles  resulting  from  the  splayed or  chamfered faces shall be true right angles.   

 17.4  All precast work shall be cured  for at  least 7 days after casting and during 

that  period  each  units  shall  be  kept  constantly watered  or  preferably  by completely immersed in water if the size of unit so permits.   

 17.5   No precast unit  shall be  lifted until  the  concrete  reaches  a  strength of  at 

least twice the stress to which the concrete may be subjected at the time of 

Page 40: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 29 of 139

lifting.  The  precast  articles  shall  be  stored  for  28  days  before  erection  or being built  in so that the concrete shall have sufficient strength to prevent damage to units when first handled  

 18.0    SAMPLING, TESTING AND QUALITY ASSURANCE  

 18.1    Samples from fresh concrete shall be taken  in accordance with IS:1199 and 

tested as per IS:516. Normally only compressive test shall be performed, but the Consultant may require other tests to be performed in accordance with lS‐516. For Trial Mixes & mix design, at  least four trial mixes shall be made with minimum  6  test  cubes  for  each mix.  For  works  tests  the minimum frequency of sampling of concrete of each grade shall be according to clause 15.2.2 of  lS:456. However, after getting continuous satisfactory results, the Consultant  may  at  his  discretion  reduce  the  frequency  of  sampling.  All sampling and testing shall be done in the presence of the Consultant.  

18.2  To control  the consistency of concrete  from every mixing, slump  tests and compaction  factor  tests  in accordance with  lS‐1199 shall be carried out by the  Tenderer  as  directed  by  the  Consultant.  Slumps  corresponding  to  the test specimens shall be recorded for reference.  

18.3  If  the  strength  of  the  laboratory  controlled  cubes,  for  any  portion  of  the concrete  work,  falls  below  the  compressive  strength  specified,  the Consultant shall have the right to order a change  in the proportions or the water content for the remaining portion of the structure. 

 18.4  If  the  strength  of  the  works  cured  test  cubes  falls  below  the  specified 

strength,  the  Consultant  shall  have  the  right  to  require  provisions  for temperature and moisture control during the period of curing as necessary to secure the required strength, and may require retests in accordance with the  standard method  of  securing,  preparing  and  testing  specimens  from hardened concrete  for compressive and  flexural strengths, or  load  tests  to be made on  the portion of  the building so affected. All such  tests shall be made at the Tenderer’s expense. 

 18.5  Unacceptable  concrete  work  shall  be  dismantled  by  the  Tenderer  and 

replaced  by  fresh  work,  meeting  the  specification  requirements.  In  the course  of  dismantling,  if  any  damage  is  done  to  the  embedded  items  or adjacent structures, the same shall be made good, by the Tenderer, to the satisfaction of the Consultant, at no extra cost. 

 18.6  Only as a very special case and that too in non‐critical areas, the Consultant 

may  accept  concrete  work  which  is  marginally  unacceptable  as  per  the criteria laid down in lS‐456. For such accepted work, payment shall be made 

Page 41: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 30 of 139

at a  reduced  rate prorata  to  the  concrete  cube  strength obtained, against that stipulated. 

 18.7                  If directed by Consultant, Ultrasonic  tests and  core  tests on  structures  to 

ascertain the quality and grade of concreting shall be carried out. Tenderer shall arrange  for  the specialised agency  for conducting  the  test at his own cost. The Tenderer shall provide all the necessary facilities and arrangement for conducting the test at site  in terms of access, scaffolding etc.  In case of any  defects,  the  Tenderer  shall  rectify  the  same  as  directed  by  the Consultant. Rebound hammer  test shall be carried out  for ascertaining  the quality of concrete work, as directed by the Consultant. 

 18.8  Consultant  ,  if  he  so  desires, may  order  for  tests  to  the  carried  out  on 

cement, sand, coarse aggregate, water etc., in accordance with the relevant Indian Standards.  

19.0    APPLICATION OF LIVE LOAD  19.1        The designated live load shall be allowed on any structure only after 28 days, 

after proper curing is carried out on the last concrete poured in structure.  

C‐ 06: MASONRY AND ALLIED WORKS  1.0    SCOPE  

 This  section of  the  specification  covers providing,  constructing of masonry and allied works including DPC and plinth protection. 

 2.0  GENERAL REQUIREMENTS  2.1  All workmanship shall be  in accordance with  the  latest standards and best 

possible practice. Masonry work  shall be  true  to  line &  level as  shown on drawings. All such masonry shall be tightly built against structural members and bonded with dowels, anchors, inserts, etc. as shown on the drawings. 

 2.2  The  Tenderer  shall  carryout  all  works  for  setting  out  the  building  lines, 

locating  the  co‐ordinates and establishing  the  reduced  levels  (RL’s) on  the basis of reference grid lines and bench mark, which shall be furnished by the Owner, at one or more locations. 

 2.3  Any approval, instructions permission, checking, review, etc. whatsoever by 

the  Consultant  shall  not  relieve  the  Tenderer  of  his  responsibility  and obligation regarding adequacy, correctness, completeness, safety, strength, quality, workmanship, etc. 

Page 42: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 31 of 139

3.0  CODES AND STANDARDS 3.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions  including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 3.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 3.3  the former shall prevail.  3.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below:  

IS: 177  1992  Specification for Common burnt clay bricks  IS ‐ 2116  1980  Specification for sand for masonry mortars IS:2212  1991  Code of practice for brick work IS:2250  1981  Code of practice for preparation and use of 

masonry mortar IS: 2386 (Part 1)  1963  Methods of test for aggregate for concrete – 

Particle size & shape IS: 2386 (Part 2)  1963  Methods of test for aggregate for concrete – 

Estimation of deleterious materials and organic impurities 

IS: 2691  1988  Specification for burnt clay facing work IS: 3495 (Part 1)  1992  Method of tests for burnt clay building bricks – 

Determination of compressive strength IS: 3495 (Part 2)  1992  Method of tests for burnt clay building bricks – 

Determination of water absorption IS: 3495 (Part 3)  1992  Method of tests for burnt clay building bricks – 

Determination of efflorescence IS: 3495 (Part 4)  1992  Method of tests for burnt clay building bricks – 

Determination of warpage IS: 4031 (Part 5)  1998  Methods of physical tests for hydraulic cements ‐ 

Determination of initial and final setting time  

IS: 4031 (Part 7)  1998  Methods of physical tests for hydraulic cements ‐ Determination of compressive strength of masonry cement 

IS:4130  1991  Safety code during demolition of buildings IS:4326  1993  Code of practice for earth quake resistant design 

and construction of buildings SP‐ 20  1991  Hand book on masonry design & construction SP‐ 25  1984  Handbook on causes and prevention of cracks in 

buildings 

Page 43: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 32 of 139

4.0                STONE MASONRY  4.1 Random  rubble masonry:    The  rubble  shall  be  of  the  best  quality  trap  / 

granite / ballast stones obtained from the approved quarry.   The sample of the stone, to be used shall be got approved from the Consultant.  All stones shall,  generally  be  freshly  quarried  and  shall  be  sound,  dense,  hard,  free from segregation, cracks, weathered portions and other structural defects or imperfections, tending to off set soundness and strength.  The percentage of water absorption shall generally not exceed 5% by weight.   All stones shall be wetted before use.   Stones shall be neatly worked  to  requisite sections and forms and shall have fully dressed beds and joints.  At least 50% of the stones  shall  be  0.015  cum.  in  content  when  reckoned  individually.    The length of stones for stone masonry shall not exceed three times the height and the breadth or base shall not be greater than three fourth the thickness of wall, or not  less  than 15  cm.  The height of  stone may be upto 30  cm. Stones shall be  laid on the natural beds and shall run sufficiently  inside the wall thickness.  No hollow space shall be left out and inter spaces of stones being  filled with mortar and  stone chips, driven hard and not with mortar only.   

4.2 All mortar to be used shall be of proportion (1:5).  Cement, sand and water to be used shall conform to their relevant specifications as described under cement concrete.   The masonry shall be  laid  to plumb,  lines  levels, curves, shapes  as  shown  in drawings.   All  required holes  for passage of water or pipes are to be embedded during construction as specified.   

4.3  All  stones  shall be wetted before  laying  in masonry.   Concrete  surfaces of columns, beams,  lintels, chajjas etc.   coming  in contact with masonry shall be properly chipped, washed and wetted before start of masonry work.  The concrete surface coming in contact of masonry shall be given a thick coat of cement  slurry  as  the masonry work  progress  in  height.    Clean  chips  and sprawls carefully selected to fit in the space shall be wedged into the mortar joints and beds wherever necessary to avoid thick beds or joints or mortar.  However, proper shaping and dressing of stones shall be done prior to their laying  in masonry and hammering  shall not be  resorted  to often after  the stones are  laid  in position.   The bond stones shall be used  in every square meter area of masonry wall and shall extend from front to back to thin walls having width  of  600 mm.  and  shall  overlap  by  at  least  150 mm.  in walls having thickness more than 600 mm. when laid from both sides.  When the work has to be started on the old or the one completed a long while ago or in the previous working seasons. Care shall be  taken to roughen and clean old  surface  satisfactorily without disturbing  the masonry before  laying  the new masonry.  It shall be wetted before laying the bedding mortar. 

Page 44: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 33 of 139

4.3 When practicable,  the whole masonry  in any structure shall be carried out upto  a  uniform  level  throughout.    But  when  breaks  are  unavoidable  in carrying the work continuously in uniform level,  sufficiently long steps shall be  left.   All  junction  of walls  shall  be  formed  at  the  time when walls  are being built.  Cross walls should be carefully bonded into the main walls.  All masonry built  in cement mortar shall be kept continuously wet for 14 days from the date of laying. Should  the mortar perish i.e. becomes dry, white  or powder through neglect of watering and if the masonry shows hollow joints or non adherence of mortar to the stones or if the work does not conform to drawings and  specifications,  the work  shall be pulled down and  rebuilt by the  Tenderer  at  his  own  cost  and  risk.    All masonry  shall  be  thoroughly cleaned  and washed  down  on  completion  and  all  stains,  adhering mortar removed from the surface and raking of joints carried out as the scaffolding is  being  lowered  and  removed.    Holes  left  in  masonry  for  supporting scaffolding shall be filled and made good before pointing / plastering. 

4.4 Coursed  rubble  masonry  :  The  face  of  the  stones  shall  be  square  / rectangular in shape and shall be so dressed all‐round that those can be set on  proper  bases  and  shall  render  uniform  joints.    The  stones may  have bushing on  the  face but  shall not project more  than 40 mm.    the external faces shall be laid in courses of about 200 mm. height or as specified and the internal face shall be finished with rubble  backing. 

 

5.0  PRECAST CEMENT CONCRETE SOLID BLOCK MASONRY :   

 

5.1  Precast cement concrete solid blocks shall be of best quality locally available / manufactured  at  site  and  should be  approved by  the Consultant before incorporation  in  the work.   The  ingredient and cement concrete used shall confirm  to  relevant  I.S.  as  stipulated  in  specification  for  cement  concrete works herein before.  

5.1.1            Minimum crushing strength of the solid blocks shall be 50 kg / Sqcm. at 28 

days. The size of the blocks shall be 300 x 200 x 150mm and the proportion used  in making the blocks shall be (1:5:8). The blocks shall be cured well at least for 14 days.   The cement mortar for concrete blocks masonry shall be (1:4) and joints shall not be more than 10 mm. thick. The type of the bond to be  adopted will  be  decided  by  the  Consultant  but  vertical  joints  shall  be staggered. 

 

 

 

Page 45: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 34 of 139

6.0    DAMP PROOF COURSE (DPC)   6.1 Damp  proof  course  shall  be  50 mm  thick  (unless  specified  otherwise) 

consisting of cement concrete  in  the proportion  (1: 1½: 3)  (1 cement, 1 ½ sand,  3  stone  chips  10  mm  down)  with  admixture  of  a  water  proofing compound  as  approved  by  the  Consultant.  The  percentage  of  admixture shall be as per manufacturer’s specification.  

 6.2  The  surface  of  the  brick work/  stone masonry work  shall  be  leveled  and 

prepared before  laying the cement concrete. Edges of DPC shall be straight and  even.  The  side  shuttering  shall  consist of wooden  forms  and  shall be strongly  and  properly  fixed  so  that  it  does  not  get  disturbed  during compaction and mortar does not leak through.  

 6.3  The concrete mix shall be of workable consistency and dense. When the side 

shuttering  is removed the surface should come smooth without any honey combing. The top surface shall be double chequerred and cured by ponding for at  least 7 days. Cement  concrete  shall be allowed  to dry  for 24 hours after curing and hot bitumen of grade 85/25 Conforming  to  IS: 702 at  the rate  of  1.7  kg/sqm  shall  be  applied  over  the  dried  surface  of  cement concrete  properly  cleaned  with  brush  and  finally  with  a  cloth  soaked  in kerosene oil. The bitumen shall be applied uniformly so that no blank spaces are left anywhere. 

 7.0  PLINTH PROTECTION  7.1  Plinths  of  all  buildings  shall  be  protected  with  1000  mm  wide  plinth 

protection consisting of 50 mm thick PCC M20 grade with 12 mm maximum size aggregate over 200 mm  thick  stone  soling using 40 mm nominal  size, rammed  consolidated & grouted with  fine  sand. Plinth protection  shall be laid with a minimum outward slope of 1:50. 

 7.2  For the purpose of stone filling, the ground shall be dressed consolidated by 

ramming or by light rolling & 12 mm thick cushion of sand be laid. Over this, 75 mm thick layer of stone aggregate, with stone size not more than 40 mm, shall be  spread uniformly. This  shall be  then  compacted by  light  roller  (by 1/2  ton  roller  &  4  to  5  passes)  or  any  other  means  as  approved  by Consultant. After compacting, sand shall be uniformly spread & water shall be sprayed over it to ensure that the voids are filled with sand. Water shall be spread in such a manner that bulking in sand does not take place. 

 7.3  This process shall be repeated till the filling reaches the desired level. When 

it  reaches  the  finished  level,  surface  shall  be  flooded  with  water  for  24 hours,  allowed  to  dry  &  then  rammed  &  consolidated  to  avoid  any settlement at a later stage. 

Page 46: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 35 of 139

8.0                       SAMPLING TESTING AND QUALITY CONTROL  8.1  The Tenderer shall carry out all sampling and testing in accordance with the 

relevant  Indian Standards and/or  International Standards and shall conduct such  tests  as  are  called  for  by  the  Consultant. Where  no  specific  testing procedure  is mentioned, the tests shall be carried out as per the prevalent accepted Engineering practice to the directions of the Consultant. Tests shall be done in the field and at a laboratory, approved by the Consultant and the Tenderer shall submit to the Consultant, the test results  in triplicate within three days after completion of a test. The Consultant may, at his discretion, waive some of the stipulations given below, for small and minor operations.  

8.2  Material/work  found  unsuitable  for  acceptance,  shall  be  removed  and replaced  by  the  Tenderer.  The works  shall  be  redone  as  per  specification requirements and to the satisfaction of the Consultant. 

 8.3  All masonry shall be built true and plumb within the tolerances prescribed as 

below. Care shall be taken to keep the perpends properly aligned.  

a)     Deviation in verticality in total height of any wall of a building more than one storey in height shall not exceed +/‐ 12.5 mm. 

 b)  Deviation from vertical within a story shall not exceed +/‐ 6 mm per 3 m 

height.  b) Deviation  from  the position shown on  the plan of any brickwork more 

than one storey in height shall not exceed 12.5 mm.  d)  Relative  displacement  between  load  bearing walls  in  adjacent  storeys 

intended to be in vertical alignment shall not exceed 6 mm.  e)   Deviation of bed joint from horizontal in any length upto 12 m shall not 

exceed 6mm, and  in any  length over 12m  it shall not exceed 12.5 mm total. 

 f)  Deviation  from  the  specified  thickness  of  bed‐joints,  cross‐joints  or 

perpends shall not exceed ± 3 mm.        

Page 47: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 36 of 139

C‐ 07: PLASTERING & POINTING  1.0  SCOPE  1 .1  This  specification  covers  the plastering work on brick or  concrete  faces of 

specified  thickness  with  architectural  features  wherever  necessary.  For application  of  Cement  and  Cement  lime  ‐  plaster  finishing.  IS:1661‐1972 “Code of practice  for application of cement and  lime plaster  finishes” shall be applicable. 

 2.0  MIX  2.1  Mortar  for  plastering  in  the  proportion  as  specified  on  drawings/ 

specification,  shall  be mixed  in  a  dry  state  and  then  wetted  and mixed thoroughly to obtain the required consistency. The mortar shall be mixed in an approved manner  including machine mixing  if desired by the Consultant and in batches so that the mortar is consumed within half an hour of mixing. Any mortar  for plaster which  is partially set shall be rejected and removed from site. 

 2.2  The mix for plastering shall be as follows: 

200 thk. Solid CC block  walls    Outside Plaster First  layer  (base  coat)  of  12  mm  thick   

(1:6),  (1 Cement, 6 Fine sand and second layer (finish coat) of 6 mm thick (1 : 4) (1 Cement, 4 Fine sand) 

Inside Plaster 12 mm  thick  (1  :  6),  (1  Cement,  6  Fine sand) 

100  thk. Solid CC block   walls  (To be used only for inside walls) 

12  mm  thick  (1:  4),  (1Cement,  4  Fine sand) 

Concrete Ceiling Plaster  6 mm  thick  –  (1  :  4),  (1Cement,  4  Fine sand) 

     3.0    APPLICATION  3.1  Before  application  of  plaster,  surface  is  to  be  prepared  conforming  to 

IS:1661 latest revision.  3.2  In all plaster work, mortar shall be applied with somewhat more than that 

the required thickness and well pressed into the joint and in the surface and rubbed and levelled with a flat wooden rule to give required thickness. 

 

Page 48: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 37 of 139

3.3  Plaster, when more  than 12 mm  thick,  shall be applied  in  two coats, base coat  followed  by  the  finishing  coat.  Thickness  of  base  coat  shall  be  just sufficient  to  fill up all unevenness  in  the  surface; no  single  coat, however, shall  exceed  12 mm  in  thickness.  The undercoat  shall be  thicker  than  the upper  coat. The overall  thickness of  the plaster  shall not be  less  than  the minimum  thickness  shown  in  the drawings or  as  specified.  The undercoat shall  be  allowed  to  dry  and  shrink  before  applying  the  second  coat  of plaster. 

   3.4  Cement mortar  for plastering work  shall be used within 30 minutes  after 

adding  water  to  cement  and  should  be  kept  agitated  at  intervals  of  10 minutes. 

 3.5            The undercoat shall be scratched or roughened before it is fully hardened to 

form  a mechanical  key.  The method  of  application  shall  be  ‘thrown  on’ rather than ‘applied by trowel’. The finished surface shall be true to line and plumb and the Tenderer shall without any extra cost to Owner make up any irregularity  in  the masonry/  concrete work with  plaster.  The mortar  shall adhere  to  the  surface  intimately when  set and  there  should be no hollow sound when  struck.  All  vertical  edges  of  pillars,  door  jambs  etc.  shall  be chamfered or rounded off as directed by the Consultant. All corner must be finished to their true angles or rounded. Any plastering that is damaged shall be repaired and left in good condition at the completion of the job without any extra cost to Owner. 

 3.6        All external plaster shall be done with approved water proofing compound. 

The external plaster shall be at least 20mm thick.  3.7  Cement Pointing shall be done on exposed masonry. Exposed faces shall be 

cement  rule pointed with  (1:3) CM. The mortar  shall be  raked out of  the joints to a depth of 12 mm. The dust shall be brushed out of the joints and the wall well wetted. The pointing shall be kept wet for 7 days. During this period it shall be suitably protected from all damages. 

 3.8                       Lime punning:  

 For  plastered  surface,  where  an  even  smooth  surface  is  specified,  lime punning with 5 parts of shell  lime properly slaked, sieved and aged, mixed with 1 part clean, washed, sieved,  fine sand by volume shall be done. The thickness of lime punning shall not be less than 2 mm and not more than 3 mm. The plastered surface shall be saturated with water before application of the  lime punning. The  lime punning shall be applied by skilled workmen and given a smooth and even finish. 

 

Page 49: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 38 of 139

C‐ 08 : FLOORING & ALLIED WORKS  1.0    SCOPE   1.1    This  specification  covers  furnishing,  installation,  finishing,  curing,  testing, 

protection, maintenance till handing over various types of floor finishes and allied items of work as listed below: 

 a)  Integral finish to concrete base b)  In situ Terrazzo finish d)  Metallic hardener like ‘Ironite’ finishes e)  IPS Flooring f)  Terrazzo Tiled finish g) Glazed tile finish h) Vitrified ceramic tiles finish i)  Acid resistant tile finish i)  PVC tile finish k)  False flooring 

 2.0    GENERAL  2.1    BASE:  The  base  to  receive  the  finish  either  formed  concrete  sub‐base  or 

floor slab covered under other relevant specifications.  2.2            Only workers specially experienced in particular items of finishing work shall 

be  engaged;  where  such  workers  are  not  readily  available,  with  the Consultant’s  permission,  experienced  supervisors  recommended  by  the manufacturer shall be engaged.  In particular case where  the Consultant so desire,  the  Tenderer  shall  get  the  finishing  items  installed  by  the manufacturer. 

 2.3                The surface to be treated shall be thoroughly examined by the Tenderer. Any 

rectification necessary shall be brought to the notice of the Consultant and his  approval  shall  be  obtained  regarding  method  and  extent  of  such rectification work. For all types of flooring, skirting, dado and similar works, the base  to  receive  the  finish  shall be  adequately  roughened by  chipping, raking out joints and cleaning thoroughly all dirt, grease etc., with water and hard  brush  and  detergent  if  required,  unless  otherwise  directed  by  the manufacturer  of  any  special  finishing  treatment,  the  base  shall  be thoroughly soaked with water and all excess water mopped up. The surface shall be done dry where adhesive are used  for  fixing  the  finishes. Prior  to commencement of actual  finishing  the approval of  the Consultant  shall be taken as to the acceptability of the surface. 

 

Page 50: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 39 of 139

3.0  CODES AND STANDARDS  3.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions  including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 3.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 3.3.0 the former shall prevail.  3.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below:  

IS ‐1237  1980  Specification for Cement concrete flooring tiles IS ‐ 1443  1972  Code  of  practice  for  laying  and  finishing  of 

cement concrete flooring tiles. IS ‐ 2114  1984  Code of practice for laying in situ terrazzo floor IS ‐ 2571  1970  Code  of  practice  for  laying‐in‐situ  concrete 

flooring IS ‐ 5318  1969  Laying of flexible sheet and tile flooring IS: 4441  1980  Code of practice  for use of  silica  type chemical 

resistant mortar IS ‐ 4457  1982  Specification for Ceramic unglazed vitreous acid 

resistant tiles. IS ‐ 13753  1993  Specification for dust pressed ceramic tiles with 

water absorption of E> 10% Group (B III) IS ‐ 13753  1993  Specification for dust pressed ceramic tiles with 

water absorption of 6% <E< 10% Group (B II b) IS ‐ 13753  1993  Specification for dust pressed ceramic tiles with 

water absorption of 3% <E< 6% Group (B II a) IS ‐ 13753  1993  Specification for dust pressed ceramic tiles with 

low water absorption of E< 3% Group (B I)  

Page 51: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 40 of 139

 4.0    MATERIALS  4.1         Materials  required  for  individual  finishing  items  are  specified  under 

respective  items.  In  general,  all  such materials  shall  be  as  per  relevant  IS Codes  where  available.  In  all  cases  these materials  shall  be  of  the  best quality available indigenously unless specified otherwise. 

 4.2           The  materials  for  finishing  items  must  be  procured  from  well‐reputed 

specified  manufacturers  and  on  the  basis  of  samples  approved  by  the Consultant.  The materials  shall  be  ordered,  procured  and  stored  well  in advance  to  avoid  compulsion  to  use  substandard  items  to maintain  the construction schedule. 

 5.0    INTEGRAL FINISHING TO CONCRETE BASE  5.1  While  the  surface of  the concrete  laid as per  specification  for “cast‐in  situ 

concrete and allied works” has been  fully  compacted and  levelled but  the concrete is still ‘green’, thick slurry made with neat cement shall be applied evenly and worked  in with  iron floats. When the slurry starts to set,  it shall be pressed with iron floats, to have a firm compact smooth surface without any  trowel mark or undulations. This  finish  shall be as  thin as possible by using 2.2 Kg of cement per sqm. of area. The surface shall be kept in shade for 24 hours and then cured for at least 7 days continuously by flooding with water. The surface shall not be subjected to any load or abrasion till 21 days after laying. As desired by the Consultant, the surface, while still ‘green’ shall be  indented  by  pressing  strings.  The markings  shall  be  of  even  depth,  in straight lines and the panels shall be of uniform and symmetrical patterns. 

 6.0    IN‐SITU  TERRAZZO FINISH   6.1  It shall consist of an underbed and a  topping  laid over an already  laid and 

mature concrete base.  6.2  Unless otherwise specified the total thickness of the finish shall be minimum 

40mm  for horizontal and 20 mm  for vertical  surface of which  the  topping shall be not less than 12 mm and 10mm respectively. While the topping shall be  of  uniform  thickness  the  thickness  of  underbed may  vary,  to  provide necessary  slopes.  The  vertical  surface  shall  project  out  6  mm  from  the adjacent  plaster  or  other  finishes.  Necessary  cutting  into  the  surface receiving the finish shall be done to accommodate the specified thickness. 

 6.2.1  All  junctions of vertical with horizontal shall be  rounded neatly  to uniform 

radius of 25 mm. 

Page 52: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 41 of 139

 6.3   MIX  6.3.1  UNDERBED  :  the  underbed  for  floors  and  similar  horizontal  surface  shall 

consist of a mix of 1 part  cement, 2 part  sand and 4 parts  stone  chips by volume. For vertical surfaces the mix shall consist of 1 part cement to 3 parts of  coarse  sand  by  volume.  The  stone  chips  shall  be  12.5mm  down  well graded. Just sufficient water shall be added to give a workable consistency. 

   6.3.2  TOPPING  :  The mix  for  the  topping  shall  be  composed  of  cement,  colour 

pigment, marble powder and marble  chips. Proportions of  the  ingredients shall  be  such  as  to  produce  the  terrazzo  of  colour,  texture  and  pattern approved by  the Consultant.  The  cement  shall  be  grey,  to which  pigment shall be added to achieve the desired colour. 3 parts of this mixture to 1 part marble powder  by weight  shall  be  added  and  thoroughly mixed  dry.  To  1 part  of  this mix,  1.5  parts  of marble  chips  by  volume  shall  be  added  and thoroughly  mixed  dry  again.  The  pigment  added  shall  conform  to  the relevant Indian Standard specification and must be stable and non fading. It must be very finely ground. The marble  powder shall be from white marble and  shall be  finer  than  I  S  Seive No.  30.  the  size of marble  chips may be between 3 mm to 20 mm. Sufficient quantity to cover each visible area shall be prepared in one lot to ensure uniform colour. Sufficient water to make it just workable  shall  be  added,  to  a  quantity  of mix  that  can  be  used  up immediately before it starts to set. 

 6.4    LAYING  6.4.1  The underbed  shall be  laid  in panels. The panels  shall not be more  than 5 

sq.m.  in area of which no side shall be more than 2.5 m  long. For exposed locations the maximum area of a panel shall be 2.0 sq.m. The panels shall be laid  in  alternate  bays  or  chequered  board  pattern.  No  panels  shall  be  in contact with another already  laid until  the  latter has contracted  to  the  full extent.  

 6.4.2  Dividing  strips  made  of  aluminium/glass  shall  be  used  for  forming  the 

panels.  The  strips  shall  exactly  match  the  total  depth  of  underbed  plus topping.  

 6.4.3  After  laying,  the  underbed  shall  be  levelled  compacted  and  brought  to 

proper grade with a screed or float. The topping shall be laid after about 24 hours  while  the  underbed  is  still  somewhat  ‘green’  but  firm  enough  to receive the topping. A slurry of the mixture of cement and pigment already made shall be spread evenly and brushed  in  just before  laying the topping. The topping shall be rolled for horizontal areas and thrown and pressed for 

Page 53: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 42 of 139

vertical  areas  to  extract  all  superfluous  cement  water  and  to  achieve  a compact  dense mass  fully  bonded with  the  underbed.  The  surface  of  the topping  shall  be  trowelled  over,  pressed  and  brought  to  a  smooth  dense surface showing a minimum 75% area covered by marble chips  in an even pattern of distribution. 

 6.5   Curing: The  surface after  laying  shall be  left  for about 12  to 18 hours and 

then  cured by allowing water  to  stand on  the  surface or by  covering with wet sack for four days. 

 6.6     GRINDING AND POLISHING  6.6.1                 When the surface has sufficiently hardened it shall be watered, and ground 

evenly with  rapid  cutting  coarse grade  (No. 60) grit blocks,  till  the marble chips  are  exposed  and  the  surface  is  smooth.  Then  the  surface  shall  be thoroughly washed and cleaned. A grout, with already prepared mixture of cement and pigment shall be applied to fill up all pinholes. 

 6.6.2                  This surface shall be cured for 7 days by keeping  it moist and then ground 

with fine grit block (No. 120). It shall again be cleaned with water, the slurry applied again to fill up pinhole that might have appeared and allowed to be cured again for 5 days. Finally the surface is ground third time with very fine grit  blocks  (No.  320)  to  get  smooth  surface  without  any  pinhole.  The grinding  shall  be  done  by  a  suitable  machine.  Where  grinding  machine cannot be used hand grinding may be allowed when the  first rubbing shall be with carborundum stone of coarse grade  (No. 60), second rubbing with medium grade (No. 80) and final rubbing and polished with fine grade (No. 120). The surface shall be cleaned with water, dried and 4 covered with oil free clean sawdust. The  final polishing shall be postponed until  just before handing over, if desired by the Consultant. 

 6.6.3             Just before handing over, the surface shall be dusted with Oxalic acid at the 

rate of 0.33 gm per sq. m., water sprinkled on it and finished by buffing with felt or hessain bobs. The floor be cleaned with soft moist rag and dried. 

 7.0  METALLIC HARDENER FINISH   7.1  It shall consist of an underbed and a topping (incorporating iron  particles) 

laid over  an already laid and matured concrete base.  7.2  THICKNESS:   7.2.1  Unless otherwise specified the total thickness of the finish shall be minimum 

25mm for horizontal surface of which topping shall not be less than 12 mm. 

Page 54: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 43 of 139

While  topping  shall  be  of  uniform  thickness,  the  underbed  may  vary  in thickness to provide necessary slope. The vertical surface shall project 6 mm from adjacent plaster or other  finishes. Necessary  cutting  into  the  surface receiving the finish shall be done to accommodate the specified thickness.  

7.3    MATERIAL:   7.3.1                 The hardening compound shall be uniformly graded iron particles, free from 

non‐ferrous metal  impurities, oil, grease, sand, soluble alkaline compounds or other injurious materials. When desired by the Consultant, actual samples shall be tested. 

 7.4    MIX  7.4.1  The  underbed  for  floor  and  similar  horizontal  surfaces  and  for  vertical 

surface shall be as per clause 6.3.1 of this section.  7.4.2                  Proportion of metallic hardener shall be as specified or as indicated by the 

manufacturer.  However,  in  absence  of  any  such  direction  1  part metallic hardener shall be mixed dry with 4 parts cement, by weight. To this mixture 6 mm nominal size stone chips shall be added in proportion of 1 part cement mixed with  hardener  to  2  parts  of  stone  chips  by  volume  and  uniformly mixed. Minimum quantity of water shall be added to make it workable. 

 7.5    LAYING  7.5.1  The concrete  floor shall be  laid  in panels of 1m x 1m or as directed by the 

Consultant. Alternate panels shall be  laid on one day followed by the other group  of  alternate  panels  the  next  day.  The  edges  of  the  panels  shall  be supported either by wooden strips or flat angle iron pieces fixed in position properly. The concrete floor shall be laid upto the required grade. The forms if any shall remain sufficiently projecting to take the finish. The surface shall be roughened by wire brush as soon as possible. 

 7.5.2             The junction of floor and walls, floors and dado or skirting shall be rounded 

off as directed.  7.5.3           Wooden strips or flat iron pieces shall be removed from their places before 

the  succeeding  alternate  layers  are  laid.  The  finish  shall be  laid while  the concrete underbed  is still very ‘green’ within about 3 hours of  laying of the later.  The  finish  shall  be  of  uniform  thickness  and  even  dense  surface without trowel marks, pinhole etc. The top layer shall be pressed firmly and worked vigorously and quickly  to  secure  full bond with  the concrete base. Just when the initial set starts the surface shall be finished and smoothened 

Page 55: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 44 of 139

with steel trowel. The finish floor shall be cured for 7 days by keeping it wet.  8.0    IPS FLOORING (Concrete Floor finish with floating Coat of Neat Cement)  8.1  It  shall  consist  of  an  underbed  and  topping  laid  on  an  already  laid  and 

mature concrete base.  8.2  THICKNESS  8.2.1  It  shall  have  thickness  of  40 mm  for  horizontal  and  20 mm  for  vertical 

surfaces  unless  otherwise  specified.  All  junctions  between  vertical  and horizontal work shall be rounded neatly to a uniform radius of 25 mm. 

 8.3    UNDERBED MIX  8.3.1    The underbed for floor and similar horizontal surfaces consists of a mix of 1 

part  cement, 2 parts  sand and 4 parts  stone  chips by volume. For vertical surfaces  the mix shall consist of 1 part cement  to 3 parts sand by volume. The  sand  shall  be  coarse.  The  stone  chips  shall  be  12.5 mm  down  well graded. Only sufficient water to be added to give a workable consistency. 

 8.4  TOPPING MIX  8.4.1  The topping shall be floating coat of neat cement using not less than 2.2 kg 

of cement per sq. m. area.  8.5    LAYING  8.5.1  The  IPS flooring  including the underbed shall be  laid  in alternate bays or  in 

chequered  board  pattern. No  panel  shall  be  cast  in  contact with  another already  laid  till  the  contraction  of  the  latter  has  already  taken  place.  The maximum area of each panel  shall be 5 m  x 5m. A  cement grout  shall be applied  and worked  in  to  the  surface  to  receive  the  finish,  the  underbed then laid, compacted and levelled to proper grade with a screed or float. The requisite slope as shown in the drawings or directed by the Consultant shall also be provided  in under bed only maintaining a minimum thickness of 25 mm at the edges. The topping shall be applied evenly on the underbed while it is not fully set but firm enough and rolled and pressed to get full bond. The topping  shall  be  trowelled  to  a  dense  finish  to  the  satisfaction  of  the Consultant. After  the  surface  is  sufficiently  set,  the  finished  floor  shall be kept moist for 7 days for curing. 

   

Page 56: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 45 of 139

9.0  TERRAZZO TILE FINISH  

9.1  These shall include terrazzo tiles finish over already laid and mature base of concrete or masonry by means of underbed cement : sand (1:4) mortar. 

 9.2    THICKNESS  9.2.1        The  total  thickness  including  the  underbed  shall  be minimum  40 mm  for 

floors  and  32 mm  for walls unless otherwise  specified.  The  skirting, dado and  similar  vertical  surfaces  shall  project  out  6 mm  uniformly  from  the adjacent  plaster  or  other  wall  finishes.  The  necessary  cuttings  into  the surface  receiving  tiled  finish,  to accommodate  the  specified  thickness shall be done.  

 9.3    TERRAZZO TILES  9.3.1          The  tiles  shall,  unless  specifically  permitted  in  special  cases,  be machine 

made, under quality control in a shop. The tiles shall be pressed hydraulically to  a  minimum  of  140  kg.  per  sq.  cm.  Each  tile  shall  bear  on  its  back permanent  and  legible  trade mark  of  the manufacturer. All  angles  of  the tiles shall be right angles, all edges sharp and true, colour and texture of the wearing  face  uniform  throughout.  Tolerance  on  length,  breadth  and thickness of tiles shall be as specified in lS‐1237 latest edition. Wearing faces of the tile shall be plane, free from pinholes and other blemishes. 

 9.3.2             The tiles shall be composed of a backing and topping. The topping measured 

as per  IS:1237  (latest edition) shall be of uniform  thickness not  less  than 8 mm. The total thickness  including  the  topping shall be as specified but not less  than  20 mm  in  any  case.  The  backing  shall  be  composed  of  1  part ordinary grey cement 2 parts of sand and 3 parts of stone chips by weight mixed with water. 

 9.3.3  The shade and texture of   topping shall be as approved by consultant. The 

tiles  shall be cured at  the  shop  for at  least 14 days before delivery  to  the site. First grinding shall be given to the tiles at the shop before delivery. Tiles shall be packed properly to prevent damage during transit and storage. The tiles must  be  stored  carefully  to  prevent  staining  by  damp,  rust,  oil  and grease, or other chemicals. Tiles made in each batch shall be kept and used separately so that colour of each area of the floor may remain uniform. The manufacturer  shall  supply  alongwith  the  tiles  the  grout  mix  containing cement  and pigment  in  exact proportions  as used  in  topping of  tiles.  The container  for  the  grout mix  shall  be  suitably marked  to  relate  it  to  the particular type and batch of tiles 

 

Page 57: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 46 of 139

9.4     MIX: UNDERBED  9.4.1  The underbed for floor and similar horizontal surfaces shall be 1 part cement  

2 parts coarse sand  4 parts stone chips by volume (12.5 mm nominal size), mixed with sufficient water. For skirting and dado and all vertical surface  it shall be 12 mm  thick and  composed of 1 part  cement and 3 parts  coarse sand by volume. 

 9.5    LAYING  9.5.1  The underbed mortar  shall be evenly  spread and brought  to proper grade 

and consolidated  to a  smooth  surface. The  surface  shall be  roughened  for better bond. Before the underbed had time to set and while  it  is still fairly moist  but  firm,  cement  shall  be  hand  dusted  over  it  or  a  cement  slurry applied and the tiles shall immediately be placed upon and firmly pressed by wooden mallet on  to  the underbed until  it achieves  the desired  level. The tiles shall be kept soaked for about 10 minutes just before laying. The joints between tiles shall be as close as possible and not more than 1.5 mm wide. Special care shall be taken to check the level of the surface and the lines of the joints frequently so that they are perfect. When tiles are required to be cut to match the dimensions, these shall be sawn and edges rubbed smooth. The  location  of  cut  tiles  shall  be  planned  in  advance  and  approval  of  the Consultant shall be taken. 

 9.5.2                 At  the  junction of horizontal  surface with vertical  surface,  the  tiles on  the 

former  shall  enter  at  least 12 mm under  the  latter. After  fixing,  the  floor shall be  kept moist  and  allowed  to mature undisturbed  for 7 days. Heavy traffic  shall  not  be  allowed.  If  desired  dividing  strips  as  specified  under Clause 6.4 may be used for dividing the work into suitable panels. 

 9.6     GRINDING AND POLISHING  9.6.1  Procedure shall be same as Clause 6.6.2 Only grinding shall not commence 

earlier than 14 days after laying of tiles.  

10.0    GLAZED TILE FINISH  10.1                 This  finish  shall be  composed of glazed earthware  tiles of approved make 

and quality, with an underbed laid over a concrete or masonry base.  10.2     THICKNESS  10.2.1                The total thickness shall be minimum 20 mm including the underbed.  

Page 58: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 47 of 139

10.2.2                  The tile finish on vertical surface shall project out 6 mm uniformly from the adjacent  plaster  or  other wall  finishes.  The  necessary  cutting  into  surface receiving the finish, to accommodate the specified thickness shall be done. 

 10.3     TILES ‐ GLAZED  10.3.1    The tiles shall be of earthware, covered with glaze, white or coloured, plain 

or with designs, of 150 mm x 150 mm nominal sizes and 5 mm thick unless otherwise specified.. The tolerance shall be + 1.5 mm for length and breadth and + 0.5 mm for thickness. Specials  like  internal and external angle beads, covers, cornices, corner pieces etc. shall match. The top surface of the tiles shall be glazed with a gloss or matt unfading stable finish as desired by the Consultant.  The  tiles  shall  be  true  in  shape  and  size.  The  colour  shall  be uniform and  fractured  section  shall be  fine grained  in  textures, dense and homogenous. The tiles shall be strong. and free from flaws like cracks, chips craze,  spacks,  crawlings  etc.  and  other  imperfections.  The  edges  and  the underside of the tiles shall be completely free from glaze and the underside shall have ribs or  indentations for better anchorage with the fixing mortar. The coloured tiles, when supplied shall preferably come from one batch to avoid difference in colour. 

 10.4      MIX ‐ UNDERBED  10.4.1  The mix for the under bed shall consist of 1 part cement and 3 parts coarse 

sand by weight mixed with sufficient water or any other mix if specified.  10.5  LAYING:  Laying shall be as per Clause 9.5  10.6     FINISHING  10.6.1  The  joints shall be cleaned and flush pointed with white cement and cured 

for  7  days  by  keeping  it wet.  The  surface  shall  be  cleaned with  soap  or suitable  detergent,  washed  fully  and  wiped  with  soft  cloth  to  prevent scratching before handing over. 

  11.0    PVC TILE FINISH (Rubberised)  11.1            This shall  include various types of tiles manufactured from rubber, set with 

an adhesive on a concrete or masonry base. An underbed may be required to obtain a satisfactory surface and grade. 

 11.2     THICKNESS  11.2.1  The  thickness  of  the  tiles  shall  be  3mm  unless  otherwise  specified.  The 

Page 59: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 48 of 139

thickness including underbed shall be 40 mm for floors and 25 mm for walls, unless otherwise specified. 

 11.3   TILES  11.3.1  Unless  otherwise  required  the  tiles  shall  be  square  and  of  approved 

dimensions. The tolerance in dimensions shall be +/‐1.5 mm.  11.3.2  The face of the tiles shall be free from porosity, blisters, cracks, embedded 

foreign  matter  or  other  physical  defects  which  affect  appearance  or serviceability. All edges shall be cut true and square. The colour shall be non‐fading and uniform in appearance, insoluble in water and resistant to alkalis, cleaning agents and all usual floor polishes. 

 11.4    FINISHING  11.4.1  If  any  adhesive marks  are  present  on  the  surface  a  soft  cloth  soaked  in 

solvent shall be used to wipe them off. The surface shall be cleaned with soft soap,  dried  and  polished  or  sealed  with  an  approved  type  of  polish  or sealant just before handling over. 

 12.0    VITRIFIED CERAMIC TILE FINISH 

 The   vitrified  ceramic   tiles   shall be  polished  & of approved shade and of   size  300  x  300  mm,  400  x  400  mm,  600  x  600  mm    with      minimum    thickness   7.0 mm    and shall be compact   and   homogenous   throughout   its     cross‐section.   These     shall     be     made of      finest white clay, quartz, feldspars  and  calcined metal  oxides  pressed  to minimum      450    kg/cm2      and     shall   be   fully  sintered  at  a temperature   of around    1200º .  Technical  specifications  shall  be  as  per  international  standards  ISO‐13006/EN176 and following properties shall be maintained: 

   

Sl. No.  Property International Standard 

ISO‐136 / EN176 Method of Testing 

1  Deviation in length  + 0.6%  EN98 2  Deviation in thickness  + 5.0%  EN98 3  Straightness of sides  + 0.5%  EN98 4  Rectangularity  + 0.6%  EN98 5  Surface Flatness  + 0.5%  EN98 6  Water absorption  <0.5%  EN99 7  MOHS Hardness  >6  EN101 8  Flexural strength  >27N/mm2  EN100 

Page 60: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 49 of 139

9  Abrasion resistance  <204 mm3  EN12 10  Skid resistance  >0.4  ASTM C‐1028 11  Breaking strength  1113 N  ASTM C‐648 12  Density   >2  DIN S‐1082 

 13.0              ACID RESISTANT TILE FINISH  13.1      This  finish  shall  be  composed  of  ceramic  unglazed  vitreous  tiles  of  approved 

make and quality, with an underbed  laid over a concrete or masonry base. The tiles are laid with chemical resistant mortars.  

 13.2    THICKNESS  13.2.1    The total thickness shall be minimum 25 mm including the underbed.  13.2.2  The  tile  finish on  vertical  surface  shall project out 12 mm uniformly  from  the 

adjacent  plaster  or  other  wall  finishes.  The  necessary  cutting  into  surface receiving the finish, to accommodate the specified thickness shall be done. 

 13.3          Tiles  –  Ceramic  unglazed  vitreous  acid  resistant  shall  generally  conform  to 

IS:4457.  13.3.1     The  tiles  shall  be  of  vitreous  ware  and  shall  be  free  from  deleterious 

substances. The acid resistant shall be determined in accordance with appendix –F of IS:4457. The size of tile shall be 150 mm x 150 mm  or 200 mm x 200 mm nominal sizes and 12 mm  thick unless otherwise specified.. The  tolerance shall be +/‐ 2.5 % for length, breadth and thickness. Specials like internal and external angle beads, covers, cornices, corner pieces etc. shall match. The  tiles shall be true in shape and size. The colour shall be uniform and fractured section shall be fine grained  in textures, dense and homogenous. The tiles shall be strong. and free  from  flaws  like  cracks,  chips  craze,  spacks,  crawlings  etc.  and  other imperfections. The edges and the underside of the tiles shall be completely free from  glaze  and  the  underside  shall  have  ribs  or  indentations  for  better anchorage  with  the  fixing  mortar.  The  coloured  tiles,  when  supplied  shall preferably come from one batch to avoid difference in colour. 

 13.4      MIX – UNDERBED & MORTAR  13.4.1  The mix for the under bed and  joint filling mortar shall be also of chemical 

resistant type conforming to IS: 4441.  

Laying:    The  laying  shall  be  done  by  approved  specialist  agency  as  per recommendation of manufacturer. 

 

Page 61: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 50 of 139

14.0    MODULAR ACCESS FLOORING (FALSE FLOORING)  14.1.1                  Access flooring wherever required to be provided shall be  in modular grid 

pattern with  grid  spacing  of  approximately  600mm.  The  flooring  shall  be supported  on  ordinary  cement  concrete  floor/slab  with  integral  smooth finish as specified elsewhere. 

 14.1.2                  The flooring shall be of heavy duty type suitable to take up  live  load of at 

least 500 kg/sqm or as may be required for the equipment being supplied. The panel shall have antistatic finish of approved shade. The flooring system shall be supplied and erected by approved agency. 

 15.0    ACCEPTANCE CRITERIA  

The finish shall be checked specially for   

♦ Level, slope, plumb as the case may be  ♦ Pattern, and symmetry ♦ Alignment of joints, dividing strips etc. ♦ Colour, texture ♦ Surface finish ♦ Thickness of joints ♦ Details of edges, junction etc ♦ Performance 

  

C‐09: STEEL DOORS, WINDOWS, VENTILATORS & LOUVERS   1.0    SCOPE 

 The work  in general shall consist of supplying, erecting and  installing of all metal  doors,  windows,  ventilators,  louvers,  glazed  partitions  etc.  as stipulated  here  or  elsewhere  in  these  specifications  with  all  materials complete including labour and equipment. 

 2.0    GENERAL  2.1          The  Tenderer  shall  submit  3  copies  of  shop  drawing  covering  all  types  of 

work under this specification before manufacture.   The drawing shall show all dimensions, details of construction, installation, relating to adjoining and related work etc 

  

Page 62: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 51 of 139

3.0  CODES AND STANDARDS  3.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions  including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 3.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 3.3 the former shall prevail.  3.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below: IS ‐ 1038  1983  Specifications for Steel doors, windows and 

ventilators IS ‐ 1081  1960  Code of practice for fixing and glazing of metal 

(steel and aluminium) doors, windows & ventilators 

IS ‐ 1361  1978  Specifications for Steel windows for industrial building 

IS: 1477 (Part 1)  2000  Code of practice for painting ferrous metals in buildings ‐ Pretreatment 

IS: 1477 (Part 2)  2000  Code of practice for painting ferrous metals in buildings ‐ Painting 

IS: 2074  1992  Specifications for ready mixed paint, air drying, red oxide zinc chrome, priming 

IS:  3564  1996  Specifications for hydraulically regulated door closers 

IS ‐ 4351  2003  Specifications for Steel door frames IS ‐ 7452  1990  Specifications for Hot rolled steel sections for 

doors, windows and ventilators   4.0    MATERIALS  4.1            Steel  sections used  for  fabrication of doors, windows, etc.  shall be  standard 

rolled steel section specified  in  IS:1038,  lS‐1361 and  IS:4351 or as specified in  drawing.  The Mild  Steel  sheets  for  frames,  shutters,  louvre  blades  etc. shall be of approved quality and of gauge mentioned  in  this  specification. Hardware  and  fixtures  of  the  best  quality  from  approved manufacturers shall  only  be  used.  The  Tenderer  shall  specifically  state  the  particular manufacturer’s materials he proposes to use. All hardware and fixtures shall be  able  to withstand  repeated use. Door  closers  shall  conform  to  IS:3564 and shall be  suitable  for doors weighing 61‐80 kg unless otherwise stated. 

Page 63: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 52 of 139

Each  closer  shall be  guaranteed  against manufaturing defect  for one  year and  any  defect  found  within  this  period  shall  be  rectified  or  the  closer replaced free of charge. Concealed door closes shall be either floor mounted or  transom  mounted,  suitable  for  installation  with  metal  doors.  It  shall conform  to  the  performance  requirements  and  endurance  test  stated  in IS:3564 ‐ Appendix A.  

4.2  The  Tenderer  shall  submit  samples  of  each  type  of  hardware  to  the Consultant. The approved  samples  shall be  retained by  the Consultant  for comparison with bulk supply. The mastic for caulking shall be of best quality from a manufacturer approved by the Consultant.  

5.0                FABRICATION  

5.1                      DOOR FRAMES  

5.1.1                  Frames  shall  be  reinforced  for  door  closers.  They  shall  be  mortised, reinforced, drilled  and  tapped  for hinges,  lock  and bolt  strikes.  Flush butt welding  to  form a  solid  fused  joint,  so  that all  frames are  square and  flat shall be used with sections cut to required  length and mitred. Rubber door silencers shall be furnished for the striking jamb. Loose “T” masonry anchors shall be provided.  Frames  shall  finish  flush with  floor and adjustable  floor anchors  shall  be  supplied.  Frames  shall  be  brought  to  site  with  floor ties/weather bars installed in place.  

5.2   DOUBLE PLATE FLUSH DOOR SHUTTERS  5.2.1          Door  shutters  shall  be  45  mm  thick,  completely  flush  design  and  shall 

comprise of two sheets of 18G steel sheets, rigidly connected and reinforced inside with continuous vertical 20G stiffeners, spot welded in position at not more  than  150 mm  on  centres.  Both  edges  of  doors  shall  be  joined  and reinforced  to  full  height  by  steel  channels  placed  immediately  inside  and welded  to  the  door  faces.  Top  and  bottom  of  doors  shall  be  reinforced horizontally  by  steel  channels  running  full width  of  door. Doors  shall  not have more  than  2.5 mm  clearance  at  jambs  and  head,  shall  have  proper level  on  lock  stiles  and  rails  to  operate  without  binding,  and  shall  be reinforced at corners  to prevent sagging or  twisting. Pairs or double doors shall have meeting stile edges beveled or rebated.  

5.2.2    Doors  shall be mortised,  reinforced, drilled and  tapped  in  shop  for hinges, locks  and  bolts.  They  shall  also  be  reinforced  for  closer,  push‐plates  and other surface hardware where necessary. Any drilling and tapping required for  surface  hardware  shall  be  done  at  site. Wherever  required,  provision shall be made for fixing glazing, vision panels, louvers etc. Glazing mouldings 

Page 64: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 53 of 139

shall  be  of  18G  mild  steel  or  extruded  aluminum  sections  with  profiles shown in drawings and suitable for fixing 6 mm glass. Louver blades shall be V or Z shaped and made out of 16G sheets.  

5.3    SLIDING DOORS  

5.3.1    Sliding doors shall be either single or double plate construction as required and  made  out  of  18  Gauge  steel  sheets  with  adequate  stiffeners.  The Tenderer shall specify the weight of the door in his shop drawing and submit the manufacturer’s catalogue of the sliding gear he proposes to use. Where shown on the drawings the Tenderer shall make provisions for openings  in the  door  for monorail  beams.  Door  shall  close  positively  to  exclude  rain water  from  seeping  in.  Sliding  doors  shall withstand  specified wind  loads without buckling or  jamming. The door shall slide  freely under all ambient conditions. 

 5.4    Steel Windows, Sashes, Ventilators etc.  5.4.1    These shall conform in all respects to IS:1038, lS‐7452 and lS‐1361 and are as 

shown  on  drawings.  The  details  as  called  for  in  the  above  codes  shall  be applicable for coupling mullions, transom, weather bars, pivot arrangements for ventilators etc. 

 5.4.1.1             WINDOWS:  

Window  shutters  shall  be  hung  on  projecting    hinges.    One    leaf  of  the hinges shall be welded  into a slot  in  the outer  frame and  the other  leaf of the hinges  riveted  to  the opening  shutters.   Hinges may be of  the  friction type  in which case the window shall not be fitted with peg stay.   In case of non‐friction  projecting  hinges,  a  brass  or  bronze  three  holes  peg  stays 300mm. Long with pegs and brackets, welded or riveted to the frame shall also be provided.  Handles shall be of brass or bronze, and shall be mounted on  a mild  steel  handle  plate welded  to  the  shutter  in  such  a way  that  it should be  fixed  after  the  shutter  is  glazed.   The handles  shall have  a  two point  nose  which  shall  engage  with  brass,  bronze  or  aluminium  alloy  as specified, striking plate, on the fixed frame so that it can hold the shutters in a slightly openable as well in a fast position. 

 5.4.2         Top hung ventilators: These shall be  fixed with plain hinges,  riveted  to  the 

fixed frames or welded to it after cutting a slot in it.  A peg stay 300mm long of brass or bronze with three holes, as in case of windows shall be provided. The  locking  bracket  shall  either  be  fitted  to  the  fixed  frame  or  to  the ventilators. 

 

Page 65: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 54 of 139

5.4.4  Centre Hung Ventilators: These shall be hung on two pairs of brass of lead / tin/ bronze cup pivots, riveted to the inner and outer frame of the ventilator to permit  these  to  swing  through an  angle of approximately 85 deg.   The opening portion of the ventilators shall be so balanced that it remains open at any desired angle under normal weather condition. 

 5.4.5  A bronze or brass  spring  catch  shall be provided  at  the  top  centre of  the 

ventilator.    A  brass  cord  pulley  wheel  in  a  mild  steel  or  malleable  iron brackets, shall be fitted with screws or welded at the sill and a cord eye shall be fixed to inner frame of ventilators to facilitate opening of ventilators. 

 5.5                  All welds shall be  flush butt welded  to  form a solid  fused  joint so  that all 

frames are square and flat.  5.6                 Where  composite  unit  openings  are  shown  on  drawings,  the  individual 

window units shall be jointed together with requisite transoms and mullions. All  windows  shall  be  inside  glazed,  fixed  with  metal  glazing  beads.  All windows,  ventilators,  sashes  shall be  fixed with handles, peg  stays etc. of approved make and best quality.  

5.7    PRESSED STEEL LOUVERS  5.7.1             The louver blade shall be ‘Z’ shaped and made out of 18G sheets in EZ7 steel 

frames. The frames shall be of ISMC 100.  5.8                  Fabrication drawings  shall be  submitted by  the Tenderer which  shall also 

include  weights  of  the  materials  used  and  got  approved  from  the Consultant. 

 6.0    SHOP COAT OF PAINT 

 6.1                 Unless  otherwise  specified  in  Sub‐section,  the  shop  paint  for  steel  doors, 

windows, ventilators, louvers etc. shall be best quality Zinc Chromate primer paint from approved manufacturer conforming to lS‐274. All surface shall be thoroughly cleaned of  rust, grease,  loose mill  scales and  foreign matter as per  lS‐1477 Part‐I, and given one coat of shop paint. Portions  like mullions, transom etc. which will be inaccessible after assembly of units shall be given an extra coat of paint before assembly. 

 6.2                 All steel doors, windows, etc. shall have one shop coat and one site coat of 

Zinc  chromate paint  (Primer)  conforming  to  IS:2074 with  a pigment  to be specified  by  the  Consultant  and  two  coats  of  synthetic  enamel  paint  of approved  quality  and  conforming  to  relevant  l.S.  Code,  unless  specified otherwise  in  these  specifications.  Wherever  required,  all  steel  doors, 

Page 66: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 55 of 139

windows, etc. shall be hot dip galvanized to give a coating weight of 460 gms to  610  gms  per  sq.m. One  coat  zinc  chromate  primer  coat  shall  then  be applied as shop paint.  

7.0    HANDLING AND STORAGE   All metal doors, windows, etc.  shall be packed and crated properly before despatch,  to  ensure  that  there  will  be  no  damage  to  the  fabricated materials.  Loading  into wagons  and  trucks  shall  be  done with  all  care  to ensure  safe  arrival  of materials  at  site  in  undamaged  condition. All metal doors, windows etc. shall be stored under cover in a way to prevent damage or distortion.  

8.0    ASSEMBLY AND ERECTION   8.1.0                 In general, the fixing of metal doors, windows ventilators, louvers, etc. shall 

conform to  IS:1081. The Tenderer shall assemble and  install all steel doors, windows, sashes,  fixed metal  louvers, etc.  including transoms and mullions for composite units in respective places keeping proper lines and levels, and in  approved  workmanlike  manner,  to  give  trouble  free  and  leak‐proof installation.  If  required by  the Consultant,  the  installation  shall have  to be carried out under the supervision of the manufacturer’s staff. The Tenderer shall  take  every  precaution  against  damage  of  the  components  during installation. Necessary holes chases etc. required for fixing shall be made by the Tenderer and made good again as per original, after installation. 

 8.2                  After installation of metal doors, windows, etc. all abrasions to shop‐coat of 

paint shall be retouched and made good with the same quality of paint used in shop‐coat.  

8.3  All coupling mullions, transoms, frames. etc. in contact with unpainted steel and other members, shall be well embedded  in mastic. The Tenderer shall bring  to  the  site  the  mastic  cement  in  original  sealed  containers  of manufacturer and shall apply it as per the instructions. 

 8.4  Door  shutters,  partitions,  hardware  fixtures  etc.  shall  be  fixed  only  after 

major equipments have been  installed  in rooms. Wherever required, nylon cords of approved quality  shall be  supplied along with pivoted  sashes and shall be of adequate  length  to  terminate one meter  from  the  floor.  Loose ends  of  cords  shall  end  in  metal  or  plastic  pull  as  approved  by  the Consultant.     

Page 67: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 56 of 139

9.0  ACCEPTANCE CRITERIA  

9.1    FOR FABRICATED ITEMS  

a)   Overall dimension shall be within + 1.5 mm of the size  

b)    Mullions,  transoms  etc.  shall  be  in  one  length  and  permissible deviations from straightness shall be limited to 1.5 mm from the axis of the member. 

 

c)  Door  and  window  shutters  shall  operate  without  jamming.  The clearance at head and jamb for door shutters shall not exceed 1.5 mm. For double leaf doors, the gap at the meeting of stiles shall not be more than 1.5mm 

d)    Door leaves shall be undercut wherever required.  

e)  Doors, windows, frames etc. shall be on a true plane, free from warp or buckle. 

 

f)  All welds shall be dressed flush on exposed and contact surfaces.    

g)     Correctness  of  location  and  smoothness  of  operations  of  all  shop installed hardware and fixtures. 

 

h)     Provision for hardware and fixtures to be installed  at site.  

i)        Glazing  clips,  fixing  devices  etc.  shall  be  supplied  in  adequate numbers 

 

j)       Shop coats shall be properly applied.  

k)    Glazing beads shall be cut with mitered corners.  

9.2  FOR INSTALLED ITEMS  a) Installations shall be at correct  location, elevation and  in     general, 

on a true vertical plane.  

b) Fixing details shall be strictly as shown on drawings.  

c) Assembly of  composite units  shall be  strictly  as per  the   drawings with mastic  caulking  at  transoms  and mullions,  gaskets,  weather strips etc. complete. 

 

d) All  frames  on  external  walls  shall  be  mastic  caulked  to  prevent  leakage through joint between frames and masonry. 

 

e) All openable sections shall operate smoothly without jamming. 

Page 68: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 57 of 139

 

f) Locks,  fasteners  etc.  shall  engage  positively.  Key  shall  be  non‐interchangeable. 

 

g)  Cutting  to  concrete  or  masonry  shall  be  made  good  and  all abrasions  to  shop  paint  shall  be  touched  up with   paint  of  same  quality as shop paint. 

  

C‐10: WOODEN WORK, CARPENTRY & JOINERY  

1.0  SCOPE  This  shall  include  supply,  fitting  and  fixing  of  timber  frames  to  doors  and windows with M.S. Holdfasts,  panelled  or  flush  doors, windows,  shutters, etc. as shown in drawings, including a prime coat of approved paint/varnish or  fixing  of  plastic  laminate  where  called  for.  This  shall  also  include  the supply and fixing of all hardware and fixtures.  

2.0    CODES  2.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions  including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 2.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 2.3. the former shall prevail.  2.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below:  

IS: 204 (Part 1)  1991  Specification for Tower bolts‐ ferrous metals ;  IS: 204 (Part 2)  1992  Specification  for  Tower  bolts‐  Non  ferrous 

metals IS: 205  1992  Specification for Non‐ferreus metal butt hinges IS: 206  1992  Specification for Tee and strap binges  IS: 207  1964  Specification  for  Gate  and  shutter  hooks  and 

eyes IS: 208  1996  Specification for Door handles IS: 281  1991  Specification for Mild steel sliding door bolts for 

use with padlocks.  IS: 287  1993  Recommendation  for  maximum  permissible 

moisture  contents  of  timber  used  for  different 

Page 69: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 58 of 139

purposes.  IS:‐ 303  1989  Specification for Plywood for general purpose IS:362  1991  Specification for Parliament hinges IS: 363  1993  Specification for Hasps and staples IS: 364  1993  Fanlight catch  IS: 401  2001  Code of practice for preservation of timber  IS: 451  1999  Technical supply condition for wood screws IS: 452  1973  Specification for Door springs, vatl‐tail type IS: 453  1993  Specification for Double acting spring hinges IS: 723  1972  Specification  for  Steel  counter  sunk  head wire 

nails IS: 729  1979  Specification  for Drawer  locks, cup board  locks, 

and box locks IS: 848  1974  Specification for Synthetic resin adhesives for 

plywood (Phenolic & Aminoplastic) IS: 851  1978  Specification  for  Synthetic  resin  adhesive  for 

construction work (non structural ) in wood IS: 852  1994  Specifications  for animal glue  for general wood 

working purposes.  IS: 1019  1974  Specification for Rim latches  IS: 1141  1993  Code of practice for seasoning of timber IS:1200(Pt. XIV)  1984  Method  of measurement  of  Building  and  Civil 

Engineering works ‐ Glazing  IS:1200(Pt. XXI)  1973  Method  of measurement  of  Building  and  Civil 

Engineering works‐  Wood work and joinery IS: 1328  1996  Specification for Veneered decorative plywood IS: 1341  1992  Specification for Steel Butt hinges 

IS: 1378  1987  Specification for Oxidized copper finishes IS: 1658  1977  Specification for Fiber hard board IS: 1659  1990  Specification for Block boards IS: 1823  1980  Specification for Floor door stoppers IS: 1868  1996  Specification for Anodic coating on Aluminium  IS: 1911  1967  Schedule of unit weights of building materials IS:2191 (Part‐ 1)  1983  Specification for wooden flush door shutters 

(cellular & hollow core type) – plywood face panels 

IS‐2191(Part‐ 2)  1983  Specification for wooden flush door shutters (cellular & hollow core type) ‐ Particle board face panels and hard board 

IS: 2202 (Part 1)  1999  Specification for wooden flush door shuters (solid core type) – plywood face panels 

IS: 2202 (Part ‐2   1983  Specification for wooden flush door shuters 

Page 70: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 59 of 139

(solid core type) – Particle board face panels and hard board 

IS: 2209  1976  Specification for Mortise locks (vertical type) IS:2380  (Parts  1  to 21) 

1977  Method  of  test  for  wood  particle  board  and boards from lignocellulosic materials 

IS:2380 (Part 22)  1981  Method  of  test  for  wood  particle  board  and boards  from  lignocellulosic  materials  – Determination of surface gulability 

IS: 2380 (Part 23)  1981  Method  of  test  for  wood  particle  board  and boards from lignocellulosic materials – Vibration test for particle boards 

IS: 2681  1993  Non  ferrous metal  sliding  door  bolts  (aldrops) for use with pad locks 

IS: 2835  1987  Flat transparent sheet glass (3rd Revision). IS: 3087  1985  Specification for wood particle board (medium 

density) for general engineering purpose IS: 3097  1980  Specification  for  Veneered  particle  boards  (1st 

Revision) IS: 3400‐(Pt.II)  1980  Method of test for vulcanized rubbers ‐Hardness IS:3400‐(Pt.IV)  1987  Method  of  test  for  vulcanized  rubbers  ‐

Accelerated aging  IS:3400‐(Pt.IX)  1978  Method of  test  for vulcanized  rubbers  ‐Relative 

density and density IS: 3564  1986  Specification  for  Door  closers  (Hydraulically 

regulated) IS: 3618  1966  Phosphate  treatment  of  iron  and  steel  for 

protection against corrosion IS: 3813  1967  Specification for ‘C’ hooks for use with swivels IS: 3818  1992  Specification for Continuous (Piano) hinges IS: 3847  1992  Specification for Mortise night latches  IS: 4020 (Part 1 to 16)  1998  Methods of  tests  for wooden  flush Doors  (Type 

tests) IS: 4021  1995  Specification  for  Timber  door,  window  and 

ventilator frames IS: 4827  1983  Electroplated coating of nickel and chromium on 

copper and copper alloys IS: 4948  2002  Specification  for  Welded  steel  wire  fabric  for 

general use. IS: 4992  1975  Specification  for Door Handles for mortise  locks 

(vertical type) IS: 5187  1972  Specification for Flush bolts IS: 5523  1983  Method of testing anodic coating on aluminium 

& its alloys.  

Page 71: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 60 of 139

IS: 5930  1970  Specification for Mortise latch (vertical types) IS: 6318  1971  Specification  for  Plastic  window  stays  & 

fasteners  IS: 6607  1972  Specification  for Rebated mortise  locks  (vertical 

type) IS: 6760  1972  Specification for Slotted countersunk head wood 

screws IS: 7196  1974  Specification for Hold fasts IS: 7197  1974  Specification  for  Double  action  floor  springs 

(without oil check) for heavy doors IS: 7534  1985  Specification  for Mild  steel bolts with holes  for 

padlocks   3.0  MATERIALS 

 3.1   TIMBER  3.1.1                 Unless  otherwise  specified,  all  timber  shall  be  best  quality well  seasoned 

Grade  I  teakwood  free  from  large or  loose  knots,  cracks or other defects. Where specified,  timber shall be  treated with approved wood preservative before use. Before starting the carpenter’s work, the Tenderer shall have the rough timber approved by the Consultant. Size of doors and windows frame shall be 100 x 60mm. 

 3.2     LAMINATED PLASTIC SHEETS  3.2.1                 All  laminated plastic  sheets  shall be minimum 1.50 mm  thick and  shall be 

Formica, Decolam or approved equivalent make. The colour, pattern, finish and  texture  shall  be  approved  by  the  Consultant  and  the  bulk  supply procured  in sheet sizes which will ensure the  least number of  joints  in one surface. 

 3.3  FLUSH DOORS  3.3.1            Flush door shall be solid core doors with commercial or decorative faces and 

hardwood edges. It shall have 3 layer flat pressed teak wood particle board (Commercial  veneer)  bonded  with  BWP  type  phenol  formaldehyde conforming  to  lS‐848  and  total  thickness  shall be 35 mm.  The board  core shall conform  to  lS‐3087 Type‐1. The door shall be given 35 x 12 mm  teak wood beading all around as per drawings and as directed by the Consultant. 

   

Page 72: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 61 of 139

3.4     FITTINGS AND FIXTURES  3.4.1           Fixtures and fittings for doors, windows, furniture etc. shall be as shown on 

drawing  and  as directed  by  the Consultant.  These  shall be of heavy  type, best quality and from approved manufacturer.  

4.0    JOINERY  4.1  GENERAL  4.1.1  The  work  shall  be  done  by  skilled  carpenters  as  per  details  shown  on 

drawings or  as  instructed by    the     Consultant.  Framing  timber  and other work  shall  be  closed  fitting  with  proper  wood  joinery,  accurately  set  to required lines or levels and rigidly secured in place. 

 4.1.2                 The  surface of  frames etc. which will  come  in  contact with masonry after 

fixing,  shall  be  given  two  coats  of  approved  paint  before  fixing.  Mastic caulking shall be done after fixing external door and window frames. Special care shall be  taken  to match  the grain of  timber of plywood which will be subsequently polished. Screwing or nailing will not be permitted to the edge of plywood or chipboard sheets. 

 4.1.3                  Fixing of frames and partitions shall generally be with 40 mm x 5 mm x 225 

mm long M.S. Hold fasts at bifurcated end and grouted with (1:2:4) cement concrete, The gap between masonry and external door and window  frame shall be caulked with mastic. M.S. grills or guard bars  shall be provided  to windows where called for in the specification. 

 4.2   FINISH  4.2.1                  All carpentry work after  finishing shall be sand papered smooth, A primer 

coat of paint shall be given after inspection by the Consultant to all surfaces other  than  those  which  shall  be  subsequently  polished  or  covered  with laminated plastic sheet. 

 4.3     SURFACE TREATMENT  4.3.1          When shown on drawings, decorative ply or laminated plastic sheets shall be 

bonded  under  pressure  to  the  surface  to  be  finished.  The  adhesive  used shall be of a approved brand and brought  to site  in sealed containers. The rate of application and  the  length of  time  for which  the pressure  is  to be applied shall be as per the manufacturer’s  instructions. The edge of sheets shall be protected by teak lipping or beveled as shown on drawings. 

 

Page 73: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 62 of 139

4.4   PRESERVATIVE  4.4.1                 Where  required as per  the drawings or by  the Consultant,  timber shall be 

treated  with  specified  preservative  strictly  in  accordance  with  the manufactuer’s instructions and to the satisfaction of the Consultant. 

 5.0.  FITTINGS AND FIXTURES:    5.1        The work covered under  these  specifications consist of  supplying different 

types  of  fittings  and  fixtures  required  for  teak  wood  door  shutters  etc., complete  in  strict  accordance  with  these  specifications  and drawings/samples approved. 

 

5.2          All fittings and fixtures shall be of heavy quality brass, anodised aluminium, iron oxidised  (M.S) or  as  specified.   These  shall be well made,  reasonably smooth and free from sharp edges, corners, flaws and other defects.  Screws holes  shall be  counter  sunk  to  suit  the heads of  the  specified  screws.   All hinges pins  shall be of  steel  for brass hinges and aluminium alloy NR‐6 or steel  pins  for  aluminium  hinges  with  nylon  washers  or  as  specified.    All riveted heads pertaining to hinge pins shall be well‐formed. Screws supplied for  fittings  shall be of  the  same metal and  finish as  the  fittings.   However brass  cadmium  plated  /  chromium  plated  screws  shall  be  supplied  with aluminum fittings.  Samples of each fixture / fitting shall be furnished by the Tenderer  for  the  approval  of  the  Consultant  and  got  approved  from  him before  placing  bulk  order  for  purchase.    The  fittings  and  fixtures  to  be incorporated in the work shall be strictly according to the approved sample.  Fittings  shall  be  fixed  in  proper  position  as  shown  in  the  drawing  and  as directed by the Consultant.  These shall be truly vertical or horizontal as the case may  be.    Screws  shall  be  driven  home with  a  screw  driver  and  not hammered in.  Recess shall be cut to the exact size and depth of fittings and fixtures  shall  be  done  in  a workman  like manner  and  any  damages  (one either to fittings and fixtures or the shutter frames etc.)  Should be rectified by the Tenderer at his own cost.    

5.3    BUTT HINGES :    5.3.1  Brass  and  aluminum  hinges  shall  be  manufactured  from  the  extruded 

sections and shall be  free  from cracks and other defects.   M.S. butt hinges shall  be  cranked  and  manufactured  from  M.S.  Sheets.    All  butt  hinges conform to latest I.S. specifications.  The size of butt hinges shall be taken as the  length of  the hinge.   Width of  the hinge  shall  be measured  from  the centre line of hinge pin to end of flange. 

  

Page 74: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 63 of 139

5.4  PARLIAMENTARY HINGES :    5.4.1  These shall be manufactured from cast brass or aluminum or M.S. and shall 

be free from cracks and other defects.  The size of the parliamentary hinges shall be taken as the width between open flanges, while the depth shall be as specified.   

 5.5  PIANO HINGES :    5.5.1  These shall  conform to I.S. specifications and shall be either brass oxidised, 

aluminum anodised,  iron oxidised (M.S.)   or as specified. Piano hinges shall be fixed  in the entire  length of the cupboard shutters  in a single piece.   No joints are allowed. 

 5.6  TOWER BOLTS:    5.6.1 The tower bolts shall be of the following types :    

a) M.S. semi barrel tower bolt with MS sheet pressed barrel and G.I. bolt or with M.S. barrel and M.S. sheet bolt.   

 b) Oxidised brass barrel  tower bolt with brass  sheet barrel  and  rolled or 

drawn brass bolt.  c)  Anodised aluminum tower bolt with barrel and bolt of extruded sections 

of aluminum alloy.    5.6.2  In case of M.S.  tower bolt plates and  straps after assembly  shall be  firmly 

riveted or spot welded properly.    5.6.3  The knobs of brass tower bolts shall be cast and the bolt fixed into the knob 

firmly as per  I.S. specifications.   The  tower bolt shall be  finished  to correct shape  and  pattern  so  as  to  have  a  smooth  action.   Wherever  specified, aluminum barrel tower bolts shall be manufactured from extruded sections of barrel and bolts. 

 5.6.4  Knobs shall be properly screwed to the bolt and riveted at the back.  The size 

of the tower bolt shall be taken as the length of barrel without top socket.  5.7  FLUSH BOLTS :    5.7.1  These shall be cast brass and shall be  finished chromium plated / oxidised, 

as  specified.   The  size of  the  flush bolt  shall be  taken as  the  length of  the flush plate without top socket. 

Page 75: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 64 of 139

 5.8  ALDROPS :    5.8.1  These  shall  be  oxidised  brass  or  anodised  aluminum,  iron  oxidised  or  as 

specified and shall be capable of smooth sliding action and shall be as per IS:2681‐1964.   Brass  sliding door bolt  (aldrop)    shall be made  from  rolled brass.  The hasp shall be of cast brass and screwed to the bolt in a workman like manner.  Alternatively the hasp and the bolt may be in one piece.  Bolts shall be  finished to shape and threaded with worth standard and provided with  round  brass  washers  and  nuts  of  square  or  hexagonal  shape.    All components  shall  be  smooth  and  polished.    The  leading  dimensions  of aldrop shall be as per the length of the bolt and specified diameter. 

 

5.9  DOOR HANDLES – BOW / PLATE HANDLES :    

5.9.1  These shall be of cast brass of specified size, shape and pattern as approved by the Consultant.   Brass handles shall be finished bright, chromium plated or oxidised as specified.   Aluminum or  iron oxidised (M.S)   handles shall be of specified size, shape and pattern.   The size of the handle  is taken as the inside grip of the handle.  In case of iron oxidised handles, the same shall be manufactured from M.S. sheet pressed into oval section as per I.S. 

 

5.10  MORTISE LOCK :    

5.10.1  Mortise  lock with  latches and a pair of  level handles shall be 6  levers, with zinc alloy pressure die cast / brass or as specified body of approved quality, and shall be right or  left handed as specified.   The pair of handles shall be either brass chromium plated or anodixed aluminium of approved shape and pattern  or  as  specified.    It  shall  be  of  the  best  Indian make  of  approved quality.  The size of the lock shall be determined by its length.  The lock for single leaf door shall have plain face and that for double leaf door a rebated face.  Level handles with springs shall be mounted on plates and shall be of approved quality, anodised aluminium or as specified. 

 

5.11  HYDRAULIC DOOR CLOSER :    5.11.1  Hydraulic door closer shall be of approved quality and make.  The operation 

of the Hydraulic door closer shall be very smooth.    5.11.2  This should be of H.D.‐66 for external / main doors and elegant – 63 for all 

internal doors.    The overall height  should not be more  than 170 mm.  for H.D.‐66 and 160 mm. for elegant‐63. Base shall be 110 x 60 mm. for H.D.‐66 and 100 x 55 mm. for elegant – 63. weighing not less than 4.5 kg. For H.D. – 66 and 4 kg.  for elegant – 63. Speed of  the Hydraulic door closer  shall be 

Page 76: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 65 of 139

adjustable and  latch closing also shall be adjustable  type.   Suspension and lubrication of door closer shall be in perfect line and level. 

 5.12  The Tenderer  shall provide  for all  the  incidentals  required  for  fixing  these 

fixtures and fittings such as cadmium plated screws etc.  Fittings and fixtures shall  be  fixed  securely  in  a  workman  like manner  all  as  directed  by  the Consultant.   Any of the fixture damaged during the fixing shall be removed and  new  one  fixed  in  their  place  and  the  surface  of  joinery made  good where affected, at his own expense.  Mortise plates shall be used over holes where the bolts enter in the wood work.  Metal sockets shall be provided to all bolts where  the  shoot enter brick,  stone,  concrete etc.    The  incidental  fixtures  like mortise plates, metal sockets, screws etc. shall not be paid for separately 

 6.0    ACCEPTANCE CRITERIA  6.1    DOOR AND WINDOW FRAMES  6.1.1                  All  frames  shall  be  square  and  flat  at  the  time  of  delivery  and  shall  be 

checked for dimensions and corner angles. After fixing they shall be in a true vertical plane. All external door and window  frames  shall be  caulked with mastic. 

 6.2    DOOR AND WINDOW SHUTTERS  6.2.1            These  shall be of proper  size,  shape  and design  and  free of warps. When 

fixed  to  frames  these  shall  operate  smoothly  without  jamming  and  all latching or locking devices shall engage properly without under pressure. 

 6.3  DOOR AND WINDOW FITTINGS  6.3.1  One set of all approved door and window fittings shall be submitted to the 

Consultant for reference and comparison with the fittings being provided.  

 C‐11: ROLLING SHUTTERS & GRILLS 

 1.0    SCOPE  1.1.0            This specification covers the design, supply of materials, fabrication, delivery 

and  erection  of  Rolling  Shutters/Grills  with  motor  drives  and/or  manual operation  including  all  accessories  as  hereinafter  specified.  All  electrical work shall be in accordance with the latest Indian Electricity Rules. 

 

Page 77: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 66 of 139

2.0  CODES AND STANDARDS  2.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions  including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 2.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 2.3  the former shall prevail.  2.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below:  

IS ‐ 6248  1979  Specification for Rolling Shutters and Grills 

IS – 10451  1983  Steel sliding shutters   3.0    FABRICATION 

 3.1    COMPONENTS  

a)  Slats  for  rolling  shutters  shall  be made  from  tested  bright  cold  rolled, annealed M.S. strips, not  less than 0.9 mm thick for shutters upto 3.5 M wide and not less than 1.24 mm thick for shutters 3.5 M wide and above, machine  rolled  at  75 mm  rolling  centres,  interlocking with  each  other. The profile will be such as to prevent excessive deflection under specified wind load. 

 b)  Rolling  grill  shall  be  constructed  out  of  6 mm  dia  rods  at  35 mm  on 

centres running horizontally flexibly connected with vertical links spaced not more than 200 mm centres. Alternatively, rolling grills shall be made from  perforated  slats  of  approved  design  reinforced  with  6 mm  dia. rods. 

 c)     End  locks shall be heavy  type M.C.I./C.I. and shall be provided at each 

end of alternate slats.  d)  Bottom bars shall be finished with two angles not  less than 6 mm thick 

for external shutters. When shown on drawings a flexible weather strip shall be applied to make tight contact with the floor. 

 e)  Guides  shall  be  of  such  depth  as  to  retain  the  shutter  under  a wind 

pressure of 200 kg/sq.m. The minimum thickness of guide to be 12 G. 

Page 78: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 67 of 139

 f)    Shafts shall be of steel pipe of sufficient size to carry the torsional  load 

with  a  maximum  deflection  of  1/360th  of  span.  Grease  packed  ball bearings  or  bushings  shall  be  provided  for  smooth  trouble  free operation. 

 g) Hoods  shall  be  formed  of  not  less  than  20  gauge  steel,  suitably 

reinforced to prevent sag.  

h)  Locks shall be slide bolt and hasp, or cylinder lock operable from one or both sides. Provision for securing hand chain with padlock, provisions for removable handle for hand cranks etc. shall be made as desired by the Consultant. 

 i)    Power unit shall be suitable  for 3 phase, 50 cycle, 400 volts A.C. Power 

supply and shall be either floor or wall mounted unit. The motor shall be of sufficient capacity to move the unit. The motor shutter shall move in either direction at  speed of 0.3 metres per  second.  In addition  to  the gear motor each standard power unit shall  include a magnetic brake, a reversing starter with built‐in overload protection, a geared limit switch and one push button station located inside the building unless otherwise stated. It is desirable that the bottom bar of motor operated doors shall be  provided with  a  sensitive  edge,  electrically  connected  to  stop  the travel of the door on meeting an obstruction. 

 k)     Operating chains shall be of tested quality, heavily galvanized and with 

all ends rounded to assure smooth operation and hand protection.  l)     Reduction  gears  shall  be  of  high  strength  grey  cast  iron,  machine 

mounted from machine cut patterns.  3.2                MANUALLY OPERATED SHUTTERS/GRILLS 

 3.2.1            Manually  operated  shutters  shall  be  easily  operable  by  one  person.  The 

speed  of  operation  shall  be  about  0.3  metres  per  second.  In  general, manually operated  shutters  shall be push pull  type of opening upto 9  sq. metre  in  area.  Larger  shutters  shall be  either  chain  and  gear operated or crank and gear operated. The crank handle shall be removable. All shutters shall be lockable from one or both sides as desired by the Consultant. 

 3.3    POWER OPERATED SHUTTER/GRILL  3.3.1       These  shall  be  operable  from  a  push  button  station  conveniently  located 

besides  the  door  or  as  shown  on  drawings.  One  emergency  hand 

Page 79: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 68 of 139

chain/crank operation shall also be provided for use in case of failure of the electric system. 

 4.0  FIXING  4.1  Brackets  shall  be  fixed  on  the  lintel/beam  or  under  the  lintel/beam  as 

specified  in  item with  rawlplugs and  screws, bolts, washers etc.   The shaft along  with  the  spring  shall  then  be  fixed  on  the  brackets.    The  guide channels shall be fixed to the wall through the plates welded to the guides.  These plates and brackets shall be fixed by means of steel screws, bolts and rawlplugs  drilled  into  the  wall.    The  plates  and  screws,  bolts  shall  be concealed  in plaster  to make  their  locations  invisible.   Fixing shall be done accurately  in  a workman  like manner  that  the operation of  the  shutter  is easy and smooth.   All grout holes and damages on  the wall while  fixing of shutters shall be made good by the Tenderer at no extra cost to the Owner.  The Tenderer shall ensure smooth and easy working of shutters.   

 5.0    PAINTING  5.1  All the members of the rolling shutter shall be thoroughly cleaned off dust, 

scales, rust etc. and shall be given approved priming coat of red oxide paint before fixing the shutter in position and then shall be painted with two coats of flat/synthetic enamel paint of approved quality and shade. 

 6.0    ACCEPTANCE CRITERIA 

 6.1    FIELD INSPECTION 

 After  installing the shutters, the Tenderer shall test the performance of the shutter  in  the  presence  of  the  Consultant.  The  doors  shall  be  smoothly operable under all ambient conditions. All control and  locking devices shall give fault‐free performance. 

 6.2    GUARANTEE 

 The Tenderer shall give one year’s guarantee for the successful operation of the shutters. 

  

     

Page 80: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 69 of 139

 C‐12: ALUMINIUM WORKS 

 1.0    SCOPE 

 1.1  The  work  in  general  shall  consist  of  fabrication,  supplying,  erecting  and 

installing  of  all  aluminium  doors,  windows,  ventilators,  louvers,  glazed partitions etc. as stipulated here or elsewhere in these specifications with all materials complete including labour and equipment. 

 2.0    GENERAL:  2.1          The  Tenderer  shall  submit  3  copies  of  shop  drawing  covering  all  types  of 

work under this specification before manufacture.   The drawing shall show all  dimensions, member  designations,  details  of  construction,  installation, relating  to adjoining and related work etc The work shall be carried out as per approved shop drawings, relevant detailed approved shop drawings. 

 2.2  The  Tenderer  shall  submit  3  copies  of  shops  drawings  covering  all 

type/details  of  work  and  generally  shown  in  architectural  drawings  and envisaged  under  these  specifications  before manufacture.    The  drawings shall  show  all  dimensions,  details  of  constructions,  installation  of  fixtures and  relation  to adjoining and  related works.   No  fabrication work  shall be undertaken  prior  to  obtaining  approval  of  the  shop  drawings  from  the Consultant.  The Tenderer shall intimate at the time of tendering the type of sections he proposes to use on the works. 

 3.0  CODES AND STANDARDS  3.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions  including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 3.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 3.3  the former shall prevail.  3.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below:  

IS – 733  1983  Specifications for wrought aluminium and aluminium alloy bars, rods, sections (for general engineering purposes) 

IS – 181  1960  Code of practice for fixing and glazing of metal 

Page 81: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 70 of 139

(steel and aluminium) doors, windows & ventilators 

IS – 1868  1996  Specifications for anidic coatings on aluminium and its alloys 

 4.0    MATERIALS  4.1  Aluminium alloy for extruded sections for the above work shall correspond 

to  I.S‐733  (extruded  sections  shall  conform  to  IS Designation HE  9  – WP.  Hollow  sections  shall  conform  to  IS  Designation  HV9‐WP)  and  shall  be anodised before  incorporating  in the work.   The Door, Window, Ventilator, glazing  framework,  beadings,  hinges,  pegstays,  stiles, mullions,  beadings, transoms and handles etc., shall be of aluminium anodised section as shown in  detailed  approved  drawings.    All  aluminum  sections  shall  be  from approved reputed manufacturer.   

 4.2  The  Tenderers  can  also  propose  nearest  alternative  sections  they 

manufacture/posses without changing the elevation, structural stability and functional  requirement.    Consultant  reserves  the  right  to  accept  the alternative section or otherwise.   The sections shall be structurally suitable to withstand all the loads, the members have to sustain.   

 4.3  Counter  sunk  screws, nuts, bolts, washers,  rivets  and other miscellaneous 

fastenings devices  shall be of approved brass  cadmium plated or  stainless steel as specified in the approved drawing.  Each door leaf shall be prepared to receive glazed panel of required thickness.   

 4.4  Glazing shall be done with neoprene dry set glazing gasket  (of best quality 

and  approved make) with  snap –  in – beveled white  anodised matt  finish aluminium metal glazing stops inside and outside,   

 5.0  FABRICATION:  5.1  DOORS  5.1.1  The frames shall be manufactured square and flat, the corners of the frame 

being fabricated to true right angle.  All the fixed, sliding and opening frames shall be constructed of sections which have been to  length, mitred, welded and mechanically fixed at the corners.   

 5.1.2  Where  hollow  sections  are  used with welded  joints,  argon‐arc welding  or 

flash  butt  welding  shall  be  employed  (Gas  welding  or  brazing  not  to  be done).    In  case  welded  joints  are  used,  anodising  shall  be  done  after fabrication as a whole.   All welding shall be on unexposed sides  in order to 

Page 82: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 71 of 139

prevent pitting / discoloration of other surface imperfections after fixing etc.    5.1.3  Necessary  allowance  shall  be  made  while  manufacturing  the  aluminium 

door  entrances,  wall  spans  and  glazing  for  receiving  plaster.    Field fabrication of frames shall be done only if permitted by Consultant.   

 5.1.4  A  thick  layer  of  clear  transparent  lacquer  based  on  methacrylates  or 

cellulose butyrate shall be applied on the finished sections of the aluminium work by the Tenderer to protect the surfaces from wet cement,  lime, dirts, dust  etc  during  the  construction  activities.    The  size  for  door, window  or ventilator frames shall not vary by more than (+/‐) 1.5 mm. 

 5.1.5  All aluminium surfaces in contact with masonry or concrete shall be given a 

thick coat of bitmastic paint.   After fabrication, aluminium sections shall be protected from construction hazards that may damage their appearance or finish.   All exposed surfaces of aluminum door entrance shall be protected by masking tape during transshipment and erection 

 5.2.  WINDOWS, VENTILATORS AND GLAZINGS  5.2.1  The  frames  shall  be  manufactured  square  and  flat.    The  corners  of  the 

frames  shall  be  fabricated  to  true  right  angles.    All  the  fixed,  sliding, openable frames shall be constructed from sections which have been cut to length, mitred and mechanically jointed or welded at the corners.   

 5.2.2  Where hollow  sections  are used with welded  joints,  argon  arc welding or 

flash  butt  welding  shall  be  employed  (Gas  welding  or  brazing  not  to  be done).  Sub‐dividing  bars  of  units  shall  be  tennoned  and  rivetted  into  the frames.    In case welded  joints are used, all welding shall be on unexposed sides  in  order  to  prevent  pitting,  discoloration  and  other  surface imperfections after finishing.   

 5.2.3  The dimensions shown in the drawing are overall heights and widths to the 

outside of frames of aluminium windows.  The side‐hung shutters shall have projected  friction  type  hinges  of  aluminium  alloy.    Concealed  projected hinges having structural stability and of good quality will also be considered only after the inspection of the sample submitted by the Tenderer 

 5.2.4  The  necessary  pegstays,  handles,  window  fasteners  etc  shall  be  of 

aluminium.   The handle shall be mounted on a handle plate rivetted to the opening  frame.    The  pegstays  shall  be  300  mm.  long  or  as  required, complete with peg and locking bracket and shall have holes for keeping the shutter open in three different positions.  Field fabrication of frames shall be done only if permitted by Consultant.   

Page 83: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 72 of 139

5.2.5  The complete fabricated assembly shall be anodised in approved satin finish with minimum  film  thickness of 0.015 mm  for  the entire  surface.   A  thick layer  of  clear  transparent  lacquer  based  on  methacrylate  or  cellulose butyrate shall be applied on the finished sections of the aluminium windows etc. by the supplier to protect the surfaces from wet cement, lime, dirt, dust etc  during  the  installation.    The  lacqure  coating  shall  be  removed  after installation is complete, if approved by the Consultant and all sections of the windows shall be protected by PVC film covering 

 6.0   HARDWARE:  6.1  All  sections  and  hardware  shall  have  anodic  film  and  cover  a  minimum 

thickness of 0.015 mm  6.2  All doors shall have off‐set pivots, double action (180 minimum swing) floor 

springs with oil check boxes of approved manufacture.  All doors shall have 4 lever  concealed  brass  body  mortise  lock  without  handles  as  per manufactures design, with concealed  flush C.P. brass  tower bolts provided at suitable locations.  All doors shall have push plates of design shown in the approved drawing as described  in the schedule of quantities.   All entrances shall be without thresholds.   

 6.3  All  cutouts,  recess, mortising or milling  and operations  required  for  fixing 

the  hardware  shall  be  accurately  made  reinforced  with  pacing  plate  as required to ensure adequate strength of the connection.   

 6.4  All the hardware accessories shall be of best approved type and of anodised 

finish same as of rate frames and other sections.  Each lock shall be supplied with  two  stainless  steel keys and each key  shall be with number  stamped thereon according to the number on doors so installed.   

 6.5  All hardware  shall be  free  from defects which may  affect  the  appearance 

and  serviceability.    All  hardware  shall  be  fixed  after  obtaining  the  prior approval of the Consultant.   

 6.6  Approved  samples  of  hardware  shall  be  kept  in  the  custody  of  the 

Consultant.  Working and moving parts of lock sets shall be accurately fitted to smooth, close bearings and shall be free from rattle.   

 6.7  The  floor  springs  shall  be  of  heavy  duty  type  and  should  allow  door 

operation smoothly.    6.8  The  tenderer  shall  furnish  a  guarantee  for  all  finishing  and  quality  of 

hardware items covered under this section and which shall remain free from 

Page 84: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 73 of 139

defects of any kind, either materials and / or workmanship  for a period of one year (unless otherwise specified) from the date of completion / handling over of work.   

 6.9  The Tenderer shall repair or replace any and all defective work and damage 

caused,  at  any  time  or  times  during  that  period  within  3  days  from  the written notice.  This shall be done without any extra cost to the Owner. 

 7.0     FIXING 

 7.1  The  frames shall be accurately  fixed  in  the  flooring/brick masonry or R.C.C 

works.    The  fixing of  the  frame  shall be done with  cadmium plated brass counter sunk screws driven on to the teak wood, rough ground, or fixed to the  wall  with  holdfasts  as  directed  by  the  Consultant,  and  as  shown  in approved drawings.   

 7.2  All aluminum works shall be fixed in position as per relevant Indian Standard 

Specifications and code of practice for fixing and glazing of aluminum work.  Joints between metal  and masonry  shall be neatly painted with matching cement and excess materials shall be removed.   

 7.3  Fixing  of  aluminum  door  entrances,  hardware  etc  shall  be  done  in  best 

workmanship  like manner  true  to  line,  level,  plane,  plumb  etc  and  all  as directed by the Consultant.  Breaking of floor for providing floor springs and restoration of the floor finishes to the original specification and finishes and minor additions and alternations  to  the openings shall be deemed  to have been included in the quoted rates. 

 7.4  All aluminum windows shall be  fixed  in position as per  IS  : 1081.   All  joints 

between metal  and masonry  /  rough  ground wooden  frame  shall be  fully caulked with mastic  or  ploysulphidc  compound  in  order  to  ensure water tight joints.  Joints shall be neatly painted with matching cement and excess materials  shall  be  removed.    Hardware  shall  be  fixed  in  workman  like manner all as directed by the Consultant.  

8.0    HANDLING AND STORAGE   All  aluminum  doors,  windows,  etc.  shall  be  packed  and  crated  properly before despatch,  to ensure  that  there will be no damage  to  the  fabricated materials.  Loading  into wagons  and  trucks  shall  be  done with  all  care  to ensure  safe arrival of materials at  site  in undamaged  condition. All Doors, Windows etc.  shall be  stored under  cover  in a way  to prevent damage or distortion.  

Page 85: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 74 of 139

9.0  ACCEPTANCE CRITERIA  

9.1    For Fabricated Items  a)  Overall dimension shall be within + 1.5 mm of the size  b)  Mullions, transoms etc. shall be in one length and permissible deviations 

from  straightness  shall  be  limited  to  1.5  mm  from  the  axis  of  the member. 

 c)  Door  and  window  shutters  shall  operate  without  jamming.  The 

clearance at head and  jamb for Door shutters shall not exceed 1.5mm. For double leaf Doors, the gap at the meeting of stiles shall not be more than 1.5mm. 

 d)  Door leaves shall be undercut wherever required.  e)  Doors, Windows, frames etc. shall be on a true plane, free from warp or 

buckle.  f) All welds shall be dressed flush on exposed and contact surfaces.  g) Correctness  of  location  and  smoothness  of   operations  of  all  shop 

installed hardware and fixtures.  h) Provision to be made for hardware and fixtures to be installed at site.  i) Glazing clips, fixing devices etc. shall be supplied in adequate numbers  j) Shop coats shall be properly applied.  k)  Glazing beads shall be cut with mitered corners.  

9.2    For Installed Items  a)   Installations shall be at correct  location, elevation  in general, on a true 

vertical plane.  b)  Fixing details shall be strictly as shown on drawings.  c)  Assembly of  composite units  shall be  strictly as per  the drawings with 

mastic  caulking  at  transoms  and mullions,  gaskets, weather  strips etc. complete. 

 

Page 86: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 75 of 139

d)  All frames on external walls shall be mastic caulked to prevent  leakage through joints between frames and masonry. 

 e)  All openable sections shall operate smoothly without jamming.  f)  Locks,  fasteners  etc.  shall  engage  positively.  Key  shall  be  non‐

interchangeable.  g) Cutting to concrete or masonry shall be made good and all

abrasions to shop paint shall be touched up with paint of same quality as shop paint.

C‐ 13: GLASS & GLAZING  

1.0  SCOPE  1.1            The work in general shall consist of supplying and fixing all glass and glazing 

including all clips, putty, mastic cement etc. wherever required as shown on drawings. 

 2.0  CODES AND STANDARDS  2.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions, including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 2.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 2.3  the former shall prevail.  2.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below:  

IS ‐ 419  1967  Putty for use on window frames IS ‐ 1081  1960  Code of practice for fixing and glazing metal (steel 

& aluminum) Doors, Windows and Ventilators IS ‐ 2835  1987  Flat transparent sheet glass IS ‐ 3548  1988  Code of practice for glazing in building IS ‐ 5437  1994  Figured rolled and wired glass IS ‐ 14900  2000  Specification for transparent float glass 

  

Page 87: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 76 of 139

3.0    MATERIALS  3.1            The  Tenderer  shall  supply  and  install  all  glass  and  glazing  as  required  for 

various  Doors,  Windows,  Sashes,  Ventilators,  and  fixed  louvers, miscellaneous  glazing  and  partitions,  unless  otherwise  stated,  from approved manufacture having uniform refractive index and free from flaws, specks and bubbles. The glass shall be brought to site in the original packing from the manufacturer and cut to size at site. The cut edges shall be straight and free from chips, spall or any other damages. 

 3.2  The glass shall be plain float glass from approved manufacture, as specified 

and  it shall be  free  from bubbles,  flaws specs, waves, air holes, distortion, scratches or other defects.  The glasses in bulk quantities shall be brought to site  in Makers original packings and Makers guarantee shall be produced  if called  for  by  the  Consultant.    The  glass  shall  be  of  required  thickness  as mentioned  in  the  items  of  schedule  of  quantities  and  /  or  drawing  or  as directed by  the Consultant.   The Tenderer  shall  submit  the  sample of  the glass which he proposes to use  on the work and only such approved quality of  glass  shall  be  used  in  the  works.    The  glass  brought  to  site  shall  be protected against damages.  Wherever frosted (obscure)  glass is mentioned in the  item of schedule of quantities and / or shown  in drawings, the glass shall  be  of  sand  blown  pattern  and  shall  also  be  got  approved  by  the Consultant.   

 3.3  After  the  inspection  is over  and permitted by  the Consultant,  glass panes 

shall be cleaned off any labels paints smears and spots and shall be washed from both the sides and all glazing left clear, perfect and free from rattling.  The Tenderer shall provide all the scaffolding tools and plants for fixing the glass panes at his own cost.  

 3.4                  Glare  reducing  (tinted)  or  heat  absorbing  glass  shall  be  “Calores”  of 

Hindustan Pilkington or approved equivalent and special care shall be taken to grind smooth and round off the edges before fixing. 

 3.5                  Clear glass shall be flat drawn and shall be at least 4 mm thick, Conforming 

to lS‐2835. Sheet glass for doors shall be minimum 6.3 mm thick.  3.6            Wired glass shall be 6 mm thick rolled glass with centrally embedded 24 G 

wire mesh  of  Georgian  type.  This may  be  of  clear  or  coloured  glass,  as required by Consultant and shall conform to lS‐5437. 

 3.7                 Obscure glass shall have a cast surface on one side.  3.8          Coloured and figured glass shall be as per approved sample. 

Page 88: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 77 of 139

 3.9            In  general,  the  putty  shall  conform  to  lS‐419  and  be  of  best  quality  from 

approved manufacturer.  it  shall  be  brought  to  site  in  the manufacturer’s original packing. Quick setting putty shall be used  for windows and sashes except when  glare  reducing  glass  is  used where  it  shall  be  of non‐setting type. 

 3.10  Neoprene gaskets with snap‐fit glazing shall be fixed as per manufacturer’s 

instruction  and  shall  fit  firmly  against  the  glass  to  give  a  leak  proof Installation. 

 4.0    FIXING  4.1       The glass shall be cut to the required sizes of panels where it is to be fitted 

and it shall be so cut that it fits properly in the frames without rattling.  Pre‐measurement of each panel prior to the cutting of glass is essential.    

4.2           The beading shall then be fixed to glass panes and screwed at close intervals not more than 10 cm. from each corner and the intermediate not more than 20  cm.  apart.   When  glass  panes  are  fixed with wooden  beadings  having mitred  joints  or  aluminium  beading,  thin  layer  of  glazier  putty  shall  be applied  covering  the  area  in  contact  between  the  glass  and  sashbars  and beadings.    In  case  of  louvers,  all  the  exposed  edges  of  the  glass  shall  be ground properly 

 4.3                  All glazing clips, bolts, nuts, putty, mastic cement, etc. as required shall be 

supplied by the Tenderer.  4.4         ll  glass  shall be  thoroughly  cleaned before placing  in positions.  Each  glass 

pane  shall  be  held  in  place  by  special  glazing  clips  of  approved  type.  As specified in relevant l.S. Codes, four glazing clips shall be provided per glass pane, except  for  large panes where  six or more  clips  shall be used as per Consultant’s  instructions. All  holes  that may  be  necessary  for  holding  the clips,  glazing  beads  and  all  other  attachments  shall  be  drilled  by  the Tenderer. 

 4.5           Glass pane shall be set without springing, and shall be bedded  in putty and 

back putted, except where mouldings or gaskets are specified. Putty, mastic cement  etc.  shall  be  smoothly  finished  to  a  true  even  line.  Obscure  and figured glass shall be set with smooth. side out. 

 4.6  After completion of glazing work,  the Tenderer shall emove all dirt, stains, 

putty etc. clean the glass panes and  leave the work  in perfectly acceptable 

Page 89: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 78 of 139

condition.  All  broken,  racked  or  damaged  glass  shall  be  replaced  by  new ones  

 4.7  The beading shall be of teak wood of superior quality timber in case of teak 

wood  doors  and  windows  of  required  sizes  mentioned  in  the  items  of schedule  of  quantities  as  shown  in  drawing.    In  case  of  steel  doors  and windows  the  beading  shall  be  anodised  aluminium  beading  of  channel section as per  size mentioned  in  the  item and  / or  shown  in  the drawing.  The junction of the beadings shall be mitre jointed.   

 5.0    ACCEPTANCE CRITERIA  

a) All  installations  shall  be  free  from  cracked,  broken  or  damaged  glass. Edges of  large panes of  thicker glass and heat absorbing glass shall be inspected carefully for chipped, cracked or unground edges. 

 c) Glazing  shall  be  carefully  done  to  avoid  direct  contact  with  metal 

frames.  d) All glass  shall be embedded  in mastic or  fixed by neoprene gaskets  to 

give a leak‐proof installation.  

e) At completion, the panes shall be free from dirt, stains, excess putty etc. and to complete satisfaction of the Consultant. 

   

C‐14: PAINTING, WHITE WASHING, DISTEMPERING AND OTHER FINISHING WORKS  1.0    SCOPE  1.1         This  Specification  covers  painting, white washing.  polishing,  distempering 

etc.  of  both  interior  and  exterior  surfaces  of masonry,  concrete,  plaster, plaster of Paris,  structural and other miscellaneous  steel  items,  rain water down comer, floor and roof drains, waste and service water pipes, and other ferrous  and  non‐ferrous  metal  items  as  indicated  elsewhere  in  these specifications or as directed by the Consultant. 

 1.2           If surface to be finished cannot be put  in suitable condition for painting by 

customary preparatory methods, the Tenderer shall notify the Consultant in writing  or  assume  responsibility  for  the  same  and    rectify  unsatisfactory finishing.  Before  commencing  painting,  the  Tenderer  shall  obtain  the approval of  the Consultant  in writing  regarding  the  scheduling of work  to minimise  damage,  disfiguration  or  staining  by  other  trades.  He  shall  also 

Page 90: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 79 of 139

undertake normal precautions to prevent damage, disfiguration or staining to work of other trades or other installations. 

 2.0  CODES AND STANDARDS  2.1  All applicable standards, acts and codes of practice referred to shall be the 

latest editions  including all applicable official amendments and revisions. A complete set of all these documents shall generally be available at site, with the Tenderer. 

 2.2  In case of conflict between this specification and those (IS Standards, Codes 

etc.) referred to in clause 2.3  the former shall prevail.  2.3  Some of  the  applicable  Indian  standards, Codes,  etc.  are  referred  to here 

below:  

75‐1973  Linseed oil, raw and refined 77‐1976  Linseed oil, boiled, for paints 102‐1962  Ready  mixed  paint,  brushing,  red,  lead,  nonsetting, 

priming  103‐1962  Ready mixed paint, brushing, white lead, for priming and 

general purposes 104‐1979  Specification  for  ready  mixed  paint,  brushing,  zinc 

chrome, priming  133‐1993  Enamel,  interior  (a) under coating  (b)  finishing colour as 

required  137‐1965  Ready  mixed  paint,  brushing,  matt  or  egg‐shell  flat, 

finsihing, interior, to Indian Standard Colour, as required  158‐1981  Ready mixed paint, brushing, bituminous, black  lead free 

acid alkali, water and heat resisting for general purposes.  168‐1993  Ready mixed paint, air drying for general purpose.  217‐1988  Cut back bitumen 218‐1983  Creosote  and  anthrakene  oil  for  use  as  wood 

preservatives  290‐1961  Coal tar black paint 337‐1975  Varnish, finishing interior 338‐1952  Varnish, under coating exterior, natural resin  339‐1952  Varnish, under coating, exterior, synthetic resin 340‐1978  Varnish, mixing 341‐1973  Black Japan, type A, E, & C 345‐1952  Wood filler, Transparent, liquid  347‐1975  Varnish, shellac for general purpose 348‐1968  French polish 

Page 91: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 80 of 139

419‐1967  Putty for use of window frames  427‐1965  Distemper, dry, colour as required 428‐1969  Distemper, oil emulsion colour as required  524‐1983  Varnish, finishing, exterior, synthetic 525‐1968  Varnish, finishing, exterior and general purposes 533‐1973  Gum spirit of turpentine (oil of turpentine)  712‐1984  Specification for building limes IS‐1477(I  and II) 

Code of Practice for painting of ferrous metals in building 

2095‐1982  Gypsum plaster boards. 2096‐1992  Asbestos cement flat sheets. 2339‐1963  Aluminium paint for general purposes, in dual container IS  ‐  2395  (I and II) 

Code  of  Practice  for  painting  concrete,  masonry  and plaster surface 

2547‐1976  Gypsum building plaster 2932‐1994  Enamel  synthetic,  exterior  (a)    Under  coating    (b)  

Finishing.  2933‐1975  Enamel, Exterior (a)  Under coating  (b)  Finishing  5410‐1992  Cement paint, colour as required  5411‐(Pt.‐I)‐1974 

Plastic emulsion paint for interior use 

6278‐1971  Code of practice for white washing & colour washing  IS ‐ 13467  Specification for chlorinated rubber for paints BS ‐ 5493  Code  of  practice  for  protective  coating  of  Iron  &  Steel 

structure against corrosion   3.0    MATERIALS  3.1            Materials  shall  be  of  highest  grade  products  of  well‐known  approved 

manufacturer and shall be delivered to the site in original sealed containers, bearing  brand  name,  manufacture’s  name  and  colour  shade,  with  label intact  and  seals  unbroken.  All materials  shall  be  subject  to  inspection  & approval by the Consultant. It is desired that materials of one manufacturer only shall be used as far as possible and paint of one shade be obtained from the same manufacturing batch. 

 3.2    All paint  shall be  subjected  to analysis  from  random  samples  taken at  site 

from painters bucket, if so desired by the Consultant.  3.3                  All  prime  coats  shall  be  compatible  to  the material  of  the  surface  to  be 

finished  as  well  as  to  the  finishing  coats  to  be  applied.  All  unspecified materials  such  as  shellac,  turpentine or  linseed oil  shall be of  the highest 

Page 92: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 81 of 139

quality  available  and  shall  conform  to  the  reputed  recognised manufacturer’s and shall be approved by the Consultant. 

 3.4            All colour shall be as per painting schedule and tinting and matching shall be 

done to the satisfaction of the Consultant. In such cases, where samples are required, they shall be executed in advance with the specified materials for the approval of the Consultant. 

 4.0    WHITE WASHING  4.1           Shall  be  done  from  pure  shell  lime  or  fat  lime,  or  a mixture  of  both  as 

instructed by  the Consultant, and shall conform  to  IS:712. Samples of  lime shall be submitted to the Consultant for approval, and lime as per approved sample shall be brought to site  in unslaked condition. After slaking,  it shall be allowed  to  remain  in a  tank of water  for  two days, and  then stirred up with a pole, until it attains the consistency of thin cream. 100 grams of gum to 6  litres of white wash water and a  little quantity of  indigo or  synthetic ultramarine blue shall be added to the lime. 

 5.0  WATERPROOF CEMENT PAINT  5.1  Shall  be made  from  best  quality white  cement  and  lime  resistant  colours 

with  accelerators,  waterproofing  agents  and  fungicides.  The  paint  shall conform to IS:5410. 

 6.0    ACRYLIC EMULSION PAINT  6.1          Shall be water based acrylic copolymer emulsion with rutile titanium dioxide 

and  other  selected  pigments  and  fungicide.  It  shall  exhibit  excellent adhesion to plaster and surface and shall resist deterioration by alkali salts. The paint film shall allow the moisture  in wall to escape without peeling or blistering. The paint, after it is dried, shall be able to withstand washing with mild soap and water without any deterioration in colour, or without flaking, blistering or peeling. 

 7.0   SYNTHETIC ENAMEL PAINT  7.1          Shall be made from synthetic resin and drying oil with rutile titanium dioxide 

and  other  selected  pigments  to  give  a  smooth,  hard,  durable  and  glossy finish  to  all  exterior  and  interior  surfaces. White  and  pastel  shades  shall resist yellowing and darkening with aging. The paint shall conform to IS:2932 and IS:2933. 

  

Page 93: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 82 of 139

8.0     DRY DISTEMPER  8.1             Dry  distemper  of  required  colour  conforming  to  IS:427  and  of  approved 

brand  and manufacturer  shall  be  used.  The  primer  where  used  shall  be cement primer or distemper primer. The shade shall be got approved from the Consultant. Dry distemper as required shall be stirred slowly and in clean water  using  0.6  litre  of water  per  kg  of  distemper  or  as  specified  by  the manufacturer.  Distemper  shall  not  be  mixed  in  larger  quantity  than  is actually  required  for one day work. Warm water  shall preferably be used. The  treatment  shall  consists of  a priming  coat of whiting  followed by  the application of two or more coats of distemper till the surface shows an even colour. 

 9.0    OIL BOUND DISTEMPER  9.1                  Oil  bound  distemper  (IS:428‐1969)  of  approved  brand  and manufacturer 

shall be used. Any unevenness  in  surface  shall be made good by applying putty.  The patched  surface  shall be  allowed  to dry  thoroughly before  the coat of distemper  is applied. One  coat of distemper properly diluted with thinner as specified by the manufacturer applied with brushes in horizontal strokes  followed  immediately by vertical ones  together will constitute one coat. Two or more coats of distemper as found necessary shall be applied to obtain even shade. 

 10.0  COLOUR WASH  10.1                  It shall be done with mineral colours, not affected by  lime added to white 

wash. No colour wash shall be done until a sample of the colour wash to the required tint or shade has been approved by the Consultant. The colour shall be of even tint or shade over the whole surface. If it is blotchy or otherwise badly applied, it shall be redone by the Tenderer at no extra cost to Owner. 

 11.0    CHLORINATED RUBBER BASED PAINT  11.1    Chlorinated  rubber  is  the  product  obtained  from  the  reaction  of  chlorine 

with rubber. The product contains average chlorine content of about 65%. 11.2  Chlorinated rubber shall be formulated with resins (for adhesion and gloss), 

plasticizers  (for  flexibility and  toughness), pigments  (for  colour),  stabilizers and  solvents  (for  fluidity).  This  shall  meet  the  general  requirements  of IS:13467 & BS:5493. 

 12.0    STORAGE  12.1    The Tenderer shall arrange for safe and proper storage of all materials and 

Page 94: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 83 of 139

tools. Paints shall be kept covered at all  times and mixing shall be done  in suitable containers. All necessary precautions shall be taken by the Tenderer to prevent fire. 

 13.0    PREPARATION OF SURFACE  13.1    Before  starting  the  work  the  Tenderer  shall  obtain  the  approval  of  the 

Consultant  regarding  the  soundness  and  readiness  of  the  surface  to  be painted on. 

 13.2    Masonry, Concrete and Plastered Surfaces shall be free from all oil, grease, 

efflorescence,  mildew,  loose  paint  or  other  foreign  and  loose  materials. Masonry cracks shall be cleaned out and patch filled with mortar similar to the original surface and uniformly textured. Where this type of resurfacing may  lead  to  the  finishing  paint  being  different  in  shade  from  the  original surfaces,  the  resurfaced  area  shall  be  treated with minimum  one  coat  of cement  primer which  should  be  continued  to  the  surrounding  area  for  a distance of minimum 100 mm. 

 13.3    Surface with mildew, efflorescence shall be treated as ‐below.  

a) MILDEW:  All mildewed  surfaces  shall  be  treated  with  an  approved fungicide  such  as  ammoniacal  wash  consisting  of  7  gm  of  copper carbonate dissolved in 80 ml.liquid ammonia and diluted to 1 litre with water or 2.5 per cent magnesium silico‐fluoride solution and allowed to dry thoroughly before paint is applied. 

 b) EFFLORESCENCE: All efflorescence shall be removed by scrubbing the 

affected surfaces with a solution of muriatic acid in water (1 : 6 to 1 : 8) and washed fully with clear water and allowed to dry thoroughly. 

 13.4    METAL SURFACES  13.5    All metal surfaces shall be absolutely clean, dry and free from wax, grease or 

dried  soap  films. All  steel  and  iron  surfaces  in  addition  shall be  free  from rust.  All  galvanized  iron  surfaces  shall  be  pre‐treated  with  a  compatible primer according to the manufacturer’s direction. Any abrasion in shop coat shall be touched up with the same quality of paint as the original coat. 

 14.0    APPLICATION  14.1    The method of application shall be as recommended by the manufacturer in 

case  of  selection  of  special  shades  and  colour  (not  available  in  standard shades) the Tenderer shall mix different shades and prepare test panels of 

Page 95: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 84 of 139

minimum  size  1  metre  square  as  per  instruction  of  the  Consultant  and obtain his approval prior to application of finishing paints. 

 14.2    Proper  tools  and  implements  shall  be  used.  Scaffoldings  if  used  shall  be 

independent of the surface to be painted to avoid shade differences of the freshly repaired anchor holes. Painting shall be done by skilled labourers in a workman like manner. All materials shall be evenly applied, so as to be free of  sags,  runs,  crawls  or  other  defects.  All  coats  shall  be  of  proper consistency. In case of application by brush, no brush marks shall be visible. The brushes shall be clean and in good condition before application of paint. 

 14.3    All  priming  undercoats  for  painting  shall  be  applied  by  brush  only  and 

rollers, spray equipments etc. shall not be used.  14.4    No work shall be done under conditions that are unsuitable for production 

of good results. No painting shall be done when plastering is in progress or is drying. Application of paint which seals of surface to moisture shall be done after the moisture on and under the surface has dried out. 

 14.5                All coats shall be thoroughly dry before being sand papered or  before the 

succeeding coat  is applied. Coats of painting as specified are      intended  to cover surfaces  perfectly. 

 14.6                 In  case  the  surface  is  not  covered  properly  by  applying  the specified              

number of  coats,  further  coats  shall be  applied by  the  Tenderer when  so directed by the Consultant, without any extra cost to Owner. All primers and undercoats shall be tinted to approximate the colour of the finishing coats. Finished coats shall be of exact colour and shade as per approved samples and finish shall be uniform in colour and texture. All parts of mouldings and ornaments shall be left clean and true to finish. 

 14.7  White Washing: The surface where white washing  is to be applied shall be 

cleaned  of  all  loose materials  and  dirt.  All  holes  and  irregularities  of  the surface  shall  be  filled  up with  lime  putty  and  shall  be  allowed  to  dry  up before application of the lime solution. One coat of white wash shall consists of one stroke from top downwards, another from bottom upwards over the first stroke and another from left to right before the previous one dries up. Second coat shall be applied after the first dries up completely and similarly the third coat shall be applied and  in case the Consultant feels that one or more coats is required the Tenderer shall do so without any extra cost to the Owner.  No  brush  marks  shall  show  on  the  finished  surface.  The  inner plastered  surfaces  of  walls  shall  be  given  three  or more  coats  of  white washings. 

 

Page 96: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 85 of 139

14.8.    Waterproof Cement Paint: Surface to be coated with cement paint shall be washed and brushed down. As  soon as  the moisture has disappeared,  the surface shall be given one coat of paint. Care shall be taken so that the paint does not dry out too rapidly. After 4 to 6 hours, the water shall be sprinkled over the surface to assist curing and prevent cracking. After the first coat has dried (24 to 48 hours) the second coat shall be applied. In a similar manner the finished surface shall be kept moist by occasional sprinkling with water for seven days after painting. 

 14.9  Acrylic Enamel Paint: Lime gauged cement plastered  surfaces  shall not be 

painted  for  at  least  one month  after  plastering.  A  sample  patch  shall  be painted to check alkali reaction if so desired by the Consultant. Painting shall be strictly as per manufacturer’s specification. Minimum two coats shall be applied. 

 14.10  Synthetic  Enamel  Paint:  Shall  be  applied  on  properly  primed  surface. 

Subsequent  coats  shall  not  be  applied  till  the  previous  coat  is  dry.  The previous  coat  shall  be  lightly  sand  papered  for  better  adhesion  of subsequent coats. Minimum two coats shall be applied. 

 14.11    Dry Distemper:  The  treatment  shall  consists  of  a  priming  coat  of whiting 

followed  by  the  application  of  two  or  more  coats  of  distemper  till  the surface shows an even colour as per manufacturer’s  instruction. The entire surface shall be coated with the mixture uniformly, with proper distemper, in horizontal strokes followed  immediately by vertical ones, which together shall  constitute  one  coat.  Subsequent  coats  shall  be  applied  only  if  the previous coat has dried. 

 14.12    Oil Bound Distemper: Any unevenness in the surface shall be made good by 

applying  putty.  The  patched  surface  shall  be  allowed  to  dry  thoroughly before coat of distemper is applied. One coat of distemper properly diluted with thinner as specified by the manufacturer shall be applied with brushes in horizontal strokes followed  immediately by vertical ones, which together will  constitute  one  coat.  Two  or  more  coats  of  distemper,  as  found necessary shall be applied to obtain even shades. 

 14.13    Colour Washing: For new work, the priming coat shall be of white wash with 

lime or with whiting. Two or more coat shall than be applied on the entire surface  till  it  represents  a  smooth  and  uniform  finish.  The  finished  dry surface shall not be powdery and shall not readily come off on hand when rubbed. Indigo (neel) shall however, not to be added. 

   

Page 97: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 86 of 139

15.0    PAINTING OF IRON & STEEL WORKS  15.1    Paint to be used for various  items of work shall be of best quality and shall 

be obtained ready mixed in sealed containers from approved manufacturer. The Tenderer shall obtain the Consultant’s approval for the make and colour of the paint he proposes to use. 

 15.2    All surfaces shall be thoroughly cleaned of all dirt,  loose particles and rust, 

and approved prior  to application of paint. Workmanship  shall conform  to lS‐1477 (Part ‐ I & III). 

 15.3    Specific number of coats shall be applied and at  least 24 hours shall elapse 

between  the  applications of  successive  coats. No painting  shall be  carried out on exterior work  in wet weather or on surfaces which are not entirely dry. 

 16.0  CHEMICAL RESISTANT PAINT  16.1  For chemical resistant paint stipulation of BS: 5493 shall also be followed.  17.0    PROTECTION  17.1  Furniture and other movable objects, equipments,  fittings and  accessories 

shall  be moved,  protected  and  replaced  upon  completion  of  the  painting work. All  stationary  items of equipments  shall be well  covered  so  that no paint  can  fall  on  them.  All  protection  shall  be  as  per  instruction  of  the Consultant. 

 18.0    CLEANING UP  18.1    The Tenderer shall, upon completion of painting etc. remove all marks and 

make good the surface, where paint has been spilled, splashed or splattered, including  all  equipments,  fixtures,  glass,  furniture,  fittings  etc.  to  the satisfaction of the Consultant. 

 19.0    ACCEPTANCE CRITERIA  

a)  All painted surfaces shall be uniform and pleasing in appearance.  b)  The colour, texture etc. shall match exactly with approved samples.  c)     All  stains,  splashes  and  splatters  of  paints  shall  be  removed  from 

surrounding surfaces. 

Page 98: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 87 of 139

C‐15: DRAINAGE, SANITATION AND WATER SUPPLY  

1.0                 SCOPE  

This  section  covers  the  design,  layout  and  construction  of  drains  for  the entire plant area for foul water, surface water and sewage together with all fittings  and  fixtures  and  inclusive  of  ancillary works,  such  as  connections, manholes and  inspection  chambers used within  the building and  from  the building to the connection to Owner’s main sewer  line manholes stipulated here  or  elsewhere  in  these  specifications.  The  scope  is  also  inclusive  of design, supply, erection of all the tanks, pipes, fittings etc. required for the water supply to be taken from the terminal point to the respective buildings. 

 2.0    INSTALLATION 

 2.1    SURFACE DRAINAGE 

 The Tenderer shall construct the entire drainage scheme as per the drawings. Necessary slopes shall be provided in longitudinal drain. 

 2.2    GENERAL  

All pipelines,  locations of  fittings and  fixture etc.  shall be as per approved drawings  or  as  directed  by  the  Consultant.  Correctness  of  lines,  plumb, orientation, symmetry and levels shall be strictly ensured. All items shall be fully secured against movement  in any direction and so  located as to allow maintenance where desired by the Consultant.  All  pipelines  and  fittings  fixtures  shall  be  installed  leak  proof. When  the works under scope of this specification connect with others the connections shall  be  such  as  to  prevent  any  splashing  or  emission  of  foul  odour  and gases. 

 a) POLYETHYLENE WATER TANK 

 Tanks  shall meet  the  requirements  of  IS:12701.  Virgin  HDPE  granules  of approved  grade,  suitable  for  drinking water  shall  be  used  for making  the tank. Carbon black  shall be added with  the granules. Tanks  shall be  single piece,  seamless  construction,  moulded  by  rotational  moulding.  Shape  of tank shall be cylindrical ‐ vertical type with corrugation along the length and bottom of the tank. Tank shall have closed top provided with  lid. However, for  storage  inside,  the  rectangular  loft  tank  of  approved  colour  shall  be provided. Tank  shall be provided with all  fittings  for  inlet, overflow, outlet pipes and ball valves  including mosquito proof coupling. Tank shall be  leak 

Page 99: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 88 of 139

proof.  Tank  shall  be  installed  with  proper  support  and  anchorage  for installation and  it shall be carried out according to the recommendation of clause No. 13 of IS:12701‐1989. 

 2.3    RAINWATER DOWN COMERS  

Rainwater down comers shall be of PVC pipes of 6 kg/sqcm pressure class. Rainwater down comers shall run along and be secured to wall, column etc. Where desired by  the Consultant  these may have  to be  installed  in chases cut  in  the  structure.  All  pipes  shall  be  well  secured  and  supported  by adequately  strong  circumferential  clamps..  The  clamps  shall  be moulded plastics,  split  ring  type  or  perforated  strap  iron  type  as  approved  by  the Consultant. Suitable spacer shall be provided against the vertical surfaces to which the pipe is fixed. All bends and junctions shall be supplied with water tight cleanouts. All horizontal pipes shall have a minimum fall of 1 in 100. 

 2.4    SOIL AND DRAINAGE PIPES  2.4.1    GRADIENTS      The minimum gradients of soil and drainage pipe line shall be as follows     100 mm nominal dia  1 in 35     150 mm nominal dia  1 in 65     230 mm nominal dia  1 in 120     300 mm nominal dia  1 in 200  2.4.2  RELATION WITH WATER SUPPLY PIPELINE      Under  no  circumstances,  unless  specifically  cleared  by  the  Consultant  in 

special  cases,  drainage  and  soil  pipes  shall  be  allowed  to  come  close  to water supply pipelines. 

 2.4.3    LAYING  

Each separate pipe shall be individually set for line, level, plumb etc. Where lengths of sewer or drain pipes are laid in trench, properly painted sight‐rails shall be fixed across the trench at a height, equal to length of the boning rod to  be  used,  above  the  required  invert  level  of  the  drain  or  sewer  at  the point,  where  the  sight  is  fixed.  More  sight  rails  shall  be  required  at manholes, changes of gradient and intermediate positions if the distance of sighting  is  too  far,  which  shall  not  be  more  than  15.0  m  apart.  The excavation  shall be boned  in at  least once  in every 1.8 m. The  foot of  the boning rod shall be set on a block of wood of the exact thickness of the wall of  the  pipe.  Each  pipe  shall  be  separately  and  accurately  boned  between 

Page 100: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 89 of 139

sight rails.  2.4.4    For  water  pipelines, meticulous  care  shall  be  taken  to  avoid  chances  of 

airlock and water hammer. The layout of pipe work shall be such that there is no possibility of backflow  towards  the source of supply  from any cistern appliances  whether  by  siphonage  or  otherwise.  Where  desired  by  the Consultant, pipes shall be concealed in masonry or concrete of the structure. Chases, openings, conduits as necessary shall be cut or left in the masonry or concrete.  Clamps  and  fittings  shall  be  as  per  the  standard  practice  and approved by the Consultant. 

 2.4.5    SUPPORT AND PROTECTION TO PIPELINES  

All  drainage  and  sewer  pipes  shall  be  laid  with  spigot  leading  uphill. Preferably  the  pipes  shall  rest  on  solid  and  even  foundations  for  the  full length  of  the  barrel.  However,  the  pipe  manufacturer’s  instructions  as approved by the Consultant shall be followed  in the matter of support and jointing. Cast  Iron pipes and concrete pipes may be  supported on  suitable concrete or brick support, where specified. The supports shall be unyielding and strong enough. At least one support shall be located close to each joint. Spacing  of  intermediate  supports  shall  be  as  desired  by  Consultant.  Pipes shall be secured to the supports by approved means. 

 Anchoring of pipes where necessary shall be achieved by suitable concrete encasing designed for the expected thrust. 

 2.4.6    ENTRY INTO STRUCTURES  

For entry of  the pipelines  into any building or structures, suitable conduits under the structures, or sleeves shall be used. The conduits and sleeves shall be  such  as  to  allow  easy  repair  and  replacement  of  the  pipes.  When openings or  chases  are  required  to be made  in  the  structure  for  entry of pipelines,  locations  and  sizes  shall  be  marked  and  checked  by  the Consultant.  After  laying  of  the  pipeline  the  openings  and  chases  shall  be mended. 

 2.4.7  DUCTS  

Where solid, waste and ventilating pipes are accommodated in ducts, access to cleaning eyes  shall be provided. Connection  to drain  shall be  through a gully trap with sealed cover to guard against ingress of sewer gas, vermin or backflow. 

  

Page 101: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 90 of 139

2.4.8    TRAPS AND VENTILATING PIPES  

Pipes  for  carrying  of  the waste  from water  closets  and waste water  and overflow water  from  baths, wash  basins,  sinks  to  drains  shall  be  trapped immediately beneath such fixtures. Traps shall have minimum water seal of 50 mm  and  shall  be  ventilated whenever  such  ventilation  is  necessary  to maintain  water  seal  of  the  trap.  Ventilating  pipes  shall  be  carried  up vertically  from  the  drain  to  a  height  of  at  least  600 mm  above  the  outer covering of  the  roof of  the building or  as  shown on drawings. All  vertical ventilating, anti‐syphonage and similar pipe shall be covered on top with a cowl. The cowl shall be made of C.I. 

 2.4.9    MANHOLES AND INSPECTION CHAMBERS  

The  maximum  distance  between  manholes  shall  be  30  metres  unless specially  permitted  otherwise.  In  addition,  at  every  change  of  alignment, gradient or diameter  there shall be a manhole or  inspection chamber. The distance between manhole or  inspection chamber and gully chamber  shall not exceed 6 metres unless desired otherwise. Manhole shall be constructed so as to be watertight under test. The benching at the sides shall be carried out  in  such a manner as  to prevent  lodgment  for any  splashing  in  case of accidental  flashing of  the chamber. The channel or drain at  the bottom of chamber  shall  be  plastered  with  (1:2)  cement  sand mortar  and  finished smooth  to  the grade. The channels and drains  shall be  shaped and  laid  to provide smooth flow. 

 Connection  to  existing  sewer  lines  shall be  through  a manhole. Manholes shall be provided with C.I. standard covers. The covers shall be close fitting so as to prevent gases from coming out. 

 2.4.10    JOINTING                                   

Jointing  of  laid  pipes  shall  be  so  planned  as  to  avoid  completely  any movement or strain to the  joints already made.  If any  joint  is suspected to be damaged it shall be opened out and redone. 

 All  joints between pipes, pipe fittings and manholes shall be gastight when above ground and watertight when underground. Method of  jointing  shall be as per instruction of the pipe and fittings manufacturer and as approved by the Consultant. However in the absence of any instruction available from the manufacturer, methods as detailed hereunder shall be used. 

   

Page 102: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 91 of 139

a)  CAST IRON PIPES  

Socket and spigot pipes shall be joined by cast lead joints. The spigot shall be centered in the socket of the next pipe by tightly caulking in sufficient  turns of  tarred gasket or hemp yarn  to have unfilled half the  depth  of  socket.  When  the  gasket  or  hemp  yarn  has  been caulked tightly, a  jointing ring shall be placed round the barrel and tightened against  the  face of  the socket  to prevent airlock. Molten lead shall then be poured  in to fill the remainder of the socket and caulked  with  suitable  tools  right  round  the  joint  to make  up  for shrinkage of the molten metal on cooling and shall be finished 3 mm behind the socket face. 

 In special cases if flanged joints are accepted by the Consultant, the joints shall be made leak proof by inserting approved type of rubber or  other  gasket  not  less  than  1.5  mm  thick.  The  bolts  shall  be secured  in stages  to avoid uneven strain. Damaged gasket shall be replaced. 

 b)       G.I. PIPES 

 Threads shall be cut with sharp tools, and before  jointing, all scales shall be removed from pipes by suitable means. The screw threads of the pipe shall be cleaned out and the joints made by screwing the fittings  after  treating  the  threads  with  approved  pipe  jointing compound. Once a joint has been screwed up it shall not be backed off unless the threads are re‐cleaned and new compound applied. 

 c)            GLAZED STONEWARE PIPES  

 Tarred gasket or hemp yarn soaked in thick cement slurry shall first be placed round the spigot of each pipe and the spigot 

 2.5  INSTALLATION  

All  plumbing  fittings  and  fixtures  shall  be  installed  in most workman  like manner  by  skilled workers.  Those  shall  be  prefect  in  level,  plumb,  plane, locations  and  symmetry. All  items  shall  be  securely  anchored  to wall  and floors. All cuttings in walls and floors shall be made good by the Tenderer. 

 3.0    TESTING AND ACCEPTANCE  3.1    All pipes, fittings and fixtures shall be  inspected, before delivery at the site 

to  see  whether  they  conform  to  accepted  standards.  The  frequency  of 

Page 103: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 92 of 139

testing and sampling as given Table ‐ I of this Section. The pipes shall again be  inspected  on  site  before  laying  by  sounding  to  disclose  cracks.  All defective items shall be clearly marked and forthwith removed from the site. 

 3.2  TESTING OF PIPELINES FOR DRAINAGE & SANITATION  

Comprehensive test of all pipe  lines shall be made by simulating conditions of use. The method of actual  tests  shall be decided by  the Consultant. All test date shall be recorded and submitted to the Consultant for review and Instruction. The Consultant’s discretion regarding tolerance shall be final. 

 General guidance for the test are given below :‐ 

 a)   SMOKE TEST 

All soil pipes, waste pipes, vent pipes & all other pipes when above ground shall be approved gas tight by a smoke test conducted under a pressure of 25 mm of water and maintained for 15 minutes after all trap seals have been filled with water. The smoke is produced by burning oily waste or tar paper of similar material in the combustion chamber of a smoke machine. Chemical smoke is not allowed. 

 b)   FOR STRAIGHTNESS 

 i)  It shall be checked by inserting at the high end of the sewer 

or drain a smooth ball of a diameter 1.3 mm  less  than  the pipe  bore.  In  the  absence  of  obstruction,  such  as  yarn  or mortar projecting through the  joints, the ball will roll down the invert of the pipe and emerge at the lower end; and 

 ii)  By means of mirror at one end of  the  line and  lamp at  the 

other end.  If  the pipeline  is  straight,  the  full  circle of  light may be observed. The mirror will also indicate obstruction in the barrel if the pipeline is not straight. 

 3.3  TESTING OF WATER MAINS AFTER LAYING  

After laying and jointing, the main shall be slowly and carefully charged with water,  so  that all air  is expelled  from  the main, by providing 25 mm  inlet with  a  stop‐cock,  allowed  to  stand  full  of  water  for  a  few  days  if  time permits,  and  then  tested  under  pressure.  The  test  pressure  shall  be  5 Kg/sqcm. or double  the maximum working pressure, whichever  is greater. The pressure shall be applied by means of a manually operated test pump, or in the case of long mains or mains of a large diameter by a power driven test pump provided that the pump is not left unattended. In either case due 

Page 104: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 93 of 139

precaution  shall be  taken  to ensure  that  the  required  test pressure  is not exceeded. Pressure gauges shall be accurate and shall preferably have been recalibrated  before  the  test.  The  pump  having  been  stopped,  the  test pressure  shall  maintain  itself  without  measurable  loss  for  at  least  five minutes.  The  end  of  the  mains  shall  be  closed  by  fitting  a  watertight expanding plug and plug shall be secured by struts to resist end thrust of the water pressure in the mains. 

 3.4    TESTING OF SERVICE PIPES AND FITTINGS  

The service pipes shall be slowly and carefully charged with water allowing all air to escape avoiding all shock or water hammer. 

 3.5    FIXTURE ETC.  

All fixtures and fittings shall be connected by Water tight joints. No dripping shall be accepted. 

 4.0                   IS CODES     

 Some of the applicable Indian Standards, Codes are referred to here below: 

   Latest editions shall always be referred to.    

IS ‐ 1172  Basic  requirements  for  water  supply,  drainage  and sanitation. 

 IS ‐1239  (Part I & II)  Mild  Steel  Tubes  and  Mild  Steel  Tubulars 

and other wrought Steel Pipe fittings.  IS ‐3486  Cast Iron Spigot and Socket drain pipes 

 IS ‐ 3589  Electrically  welded  steel  pipe  for  water,  gas  and  sewage 

(200mm to 2000 mm nominal diameter).  

IS ‐ 1537  Vertically cast iron pressure pipe for water, gas and sewage.  IS ‐ 1742  Code of practice for building drainage. 

 IS ‐ 5329  Code  of  practice  for  sanitary  pipe work  above  ground  for 

building  

IS ‐ 1538  Cast  iron  fittings  for  pressure  pipes  for  water,  gas  and sewage. 

Page 105: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 94 of 139

 IS ‐ 1230  Cast iron rainwater pipes and fittings. 

 IS ‐ 1729  Sand cast  iron spigot and socket soil, waste and ventilating 

pipes, fittings and accessories.  

IS ‐ 1626  Asbestos cement building pipes, gutters.  

IS ‐ 2065  Code of practice for water supply in building.  

IS ‐ 1726  Cast iron manhole covers and frames intended for use in drainage works. 

 IS ‐ 5961  Cast  iron gratings for drainage purposes.  IS  : 5219  (Part  ‐  I) 

‘P’ and ‘S” traps, cast copper alloy traps   

IS ‐ 771    Glazed fire dry sanitary appliances  

IS ‐ 772  General requirements of enameled cast iron sanitary appliances 

 IS ‐ 774               Flushing  cistern  for  water  closets  and  urinals  (Valve  less 

Siphonic type)  

IS ‐ 775  Cast iron brackets and supports for wash basin and sinks.  

IS ‐ 2548    Plastic water closet seats and covers.  

IS ‐ 2527    Code  of  practice  for  fixing  ‐  rainwater  gutters  and downpipes for roof drainage. 

 IS –1068    Chromium plating 

 IS ‐ 1073    Ball valves including floats for water supply purpose. 

 

Page 106: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 95 of 139

C‐16: ROAD AND PAVEMENTS  1.0  SCOPE OF WORK  1.1  The work  contemplated under  these  specifications  refers  to earth work  in 

excavation,  forming  embankments,  soling,  WBM,  Bituminous  Macadam, Wearing course/sealing coat etc. for Road and pavement works. 

 2.0  EARTH WORK IN EXCAVATION:  2.1 The  specifications  for  “Excavation work &  Back  filling”  under  section  ‐  III, 

specified in C‐02 shall be generally followed.  2.2  FORMING EMBANKMENT:  2.2.1  The  work  shall  include  preliminaries  of  clearing  site,  setting  out  and 

preparing  the ground and  there after  forming embankment  for  the  roads, paths  etc. With  approved material  available  form  excavations  under  this contract  (excavation paid separately under  respective  items) or elsewhere, spreading  in  layers, watering  and  compacting  to  the  required density  and lines, curves, grades, chambered cross section and dimensions shown in the plan or as directed by the Consultant. When the embankment  is to be  laid on hill sides or slopes, the existing slopes are to be ploughed deeply.  If the cross  slopes are  steeper  than 1  in 3,  steps with  reverse  slope  shall be  cut into  the slopes  to give proper hold and seating  to  the bank as directed by the  Consultant.  The  top  15cm  of  soil  shall  be  scarified  and  watered  if directed  and  compacted  to  the  same  density  as  specified  for  the embankment before any material is laid for the embankment work. 

 2.2.2  Only the approved excavated earth shall be placed  in the embankments  in 

successive  horizontal  layers  not  exceeding  200mm,  extending  to  the  full width of the embankment including the slopes at the level of the particular layer  and  30  cm,  more  on  both  sides  to  allow  compaction  of  the  full specified section. The extra  loose stuff at  the edges shall be  trimmed  later after  completion  of  the  bank work without  extra  cost  leaving  the  correct section fully compacted. 

 2.2.3  Keeping the width of the bank initially less and widening it later by dumping 

loose earth on the slopes shall not be permitted as the additional width and slopes will remain loose and uncompacted. Similar procedure to extend the embankment  by  dumping  the  material  longitudinally  shall  also  not  be allowed.  Each  layer  of  the  embankment  shall  be  watered,  levelled  and compacted  as  specified  here‐in‐after,  before  the  succeeding  layers  are placed.  The  surface  of  the  embankment  shall  at  all  times  during 

Page 107: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 96 of 139

construction,  be maintained  in  such  a manner  so  as  to  prevent  ponding. Water to be used shall be free from all harmful elements which may cause efflorescence etc. and approved by the Consultant. 

 2.2.4  If  the material  for embankment  contains moisture  less  than  the optimum 

moisture, water shall be added in the 100mm, layers of the embankment to bring  moisture  uniformly  upto  requirement.  If  the  excavated  material contain more  than  required moisture,  it  shall  be  allowed  to  dry  until  the moisture is reduced to required extent. If due to the wetness, the moisture content  of  the  soil  cannot  be  reduced  to  the  appropriate  amount  by exposure,  embankment  work  shall  be  suspended  till  suitable  conditions prevail at no extra claim/compensation. 

 2.2.5  When  loose  layer  is  levelled manually  or mechanically  and moistened  or 

dried  to a uniform moisture  content  suitable  for maximum  compaction,  it shall be compacted by 8  to 10  tonne power  roller or  sheep  foot  rollers or heavy hauling or dozing equipment to give the specified 95% of the proctor density, if on testing, the density is found to be less than 95% of the proctor density,  the Tenderer  shall do additional  compaction necessary  to get  the specified  density  after  adding water  if  required.  If  the  density  cannot  be improved  by  such  reasonable  efforts,  the  work  may  be  accepted  as substandard work by the Consultant. If consultant thinks it is not harmful for the purpose and paid for at a reduce rate. Test shall be made to determine the maximum  density  of  the material  to  be  used  by  the  proctor method before  starting  the  work.  Density  test  shall  be  carried  out  for  the embankment work during  the progress of  the work. One set of  three core samples  for  every  1000  sqm.  (about  1000  sq.yd.)  area  of  each  layer  of embankment work shall be taken and tested. The average density shall not be less than 95% of the proctor density, obtained in the laboratory. 

 2.2.6  Arrangement  for  obtaining  the  samples  and  transporting  the  same  to 

laboratory, shall be made by the Tenderer  at his own cost.  2.2.7  Embankment  not  accessible  to  rollers,  such  as  those  adjoining  bridges, 

culverts  and  other works  shall  be  carried  out  independently  of  the main embankments and shall have the layers placed in 150 mm to 200 mm height and  each  layer  shall  to  moistened  and  thoroughly  compacted  with mechanical or manual tamper. Before placing the next  layer, the surface of the  under  layer  shall  be  moistened  and  scarified  so  as  to  provide  a satisfactory bond with the next layer. 

 2.2.8  The  embankment  shall  be  finished  and  dressed  smooth  and  even,  in 

conformity  with  the  alignment,  levels  and  cross  section,  and  dimensions shown  on  the  drawing.  On  curves,  section  shall  be  provided  with  super 

Page 108: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 97 of 139

elevation  and  increased width,  is  shown  on  the  plans  as  directed  by  the Consultant. 

 2.2.9  Joining of old and new embankment shall be done by stepping in an overall 

slope of about 1 to 5.  2.2.10  The Tenderer shall be responsible for maintaining the embankment work in 

satisfactory conditions at his own cost till finally accepted  including making good any damage. 

 3.0.0        SUB GRADE :  3.1      Preparation of Sub‐grade : The surface of the formation for a width of sub‐

base which  shall  be  as  per  drg.  shall  first  be  cut  to  a  depth  equal  to  the combine  depth  of  sub‐base  and  surface  courses  below  the  proposed finished level (due allowance being made for consolidation). It shall then be cleaned  of  all  foreign  substances.  Any  ruts  or  soft  yielding  patches  that appear  due  to  improper  drainage  conditions,  traffic  hauling  or  from  any other  cause,  shall  be  corrected  and  the  sub‐grade  dressed  off  parallel  to finished profile. 

 3.2      Consolidation: The sub grade shall be consolidated with a power road roller 

of 8 to 12 tonnes. The roller shall run over the sub grade till the soil is evenly and  densely  consolidated  and  behaves  as  an  elastic mass  (the  roller  shall pass a minimum of 5 runs on the sub grade). All undulations  in the surface that develop due to rolling shall be made good with fresh material or quarry spoils as the case may be and the sub grade is rerolled. 

 3.3      Surface Regularity  : The  finished  surface  shall be uniform and  conform  to 

the  lines,  grades  and  typical  cross  sections  shown  in  the  drawings. When tested with the template and straight edge, the variation shall be within the tolerances specified in the Table below : 

   

Permissible tolerances of surface regularity  

Longitudinal profile  Cross profile Maximum permissible undulation when measured with a 3 metre straight edge                                                  24 mm 

  Maximum permissible variation from specified profile when measured with a camber‐template                                            15 mm 

 

Page 109: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 98 of 139

3.4 Where  the  surface  irregularity of  the  sub‐grade  falls outside  the  specified tolerances, the Tenderer shall be liable to rectify these with fresh material or quarry  spoils  as  the  case  may  be,  and  the  sub  grade  rerolled  to  the satisfaction of the Consultant. 

 4.0      SUB‐BASES : 

 4.1.                      GRANULAR SUB–BASE    4.1.1      Scope  

This work  shall  consist  of  laying  and  compacting well‐graded material  on prepared  subgrade  in  accordance  with  the  requirements  of  these Specifications. The material shall be laid in one or more layers as sub‐base or lower  sub‐base  and  upper  sub‐base  (termed  as  sub‐base  hereinafter)  as necessary  according  to  lines,  grades  and  cross‐sections  shown  on  the drawings or as directed by the Engineer.  

4.1.2.     Materials  The material to be used for the work shall be natural sand, moorum, gravel, crushed  stone,  or  combination  thereof  depending  upon  the  grading required.  Materials  like  crushed  slag,  crushed  concrete,  brick  metal  and kankar may be allowed only with the specific approval of the Engineer. The material  shall  be  free  from  organic  or  other  deleterious  constituents  and conform to one of the three gradings given in Table 400‐1.  While  the  gradings  in  Table  400‐1  are  in  respect  of  close‐graded  granular sub‐base materials, one each  for maximum particle size of 75 mm, 53 mm and 26.5 mm,  the  corresponding gradings  for  the  coarse‐graded materials for each of the three maximum particle sizes are given at Table 400‐2. The grading to be adopted for a project shall be as specified in the Contract. 

   4.1.3      Physical requirements: The material shall have a 10 per cent fines value of 

50 kN or more (for sample in soaked condition) when tested in compliance with BS :812 (Part III) . The water absorption value of the coarse aggregate shall be determined as per IS : 2386 (Part 3);  if this value  is greater than 2 per cent, the soundness test shall be carried out on the material delivered to  site  as  per  IS  :  383.  For Grading  II  and  III materials,  the  CBR  shall  be determined at the density and moisture content  likely to be developed  in equilibrium  conditions which  be  taken  as  being  the  density  relating  to  a uniform air voids content of 5 percent. 

  

Page 110: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 99 of 139

TABLE 400‐1.  GRADING FOR CLOSE‐GRADED GRANULAR SUB‐BASE MATERIALS 

 

           IS Sieve        Per cent by weight passing the IS sieve                       ______________________________________________________  1.1.1.1.1 Designation      Grading I  Grading II  Grading III   75.0   mm          100  ‐  ‐ 53.0   mm         80‐100  100  ‐ 26.5   mm      55‐90           70‐100                     100 9.50   mm                                                 35‐65                                   50‐80                  65‐95 4.75   mm                                                  25‐55                                   40‐65                    50‐80 2.36   mm                                    20‐40                      30‐50               40‐65 0.425 mm  10‐25  15‐25  20‐35 0.075 mm  3‐10  3‐10  3‐10  CBR Value (Minimum)  30  25  20  TABLE 400‐2.  GRADING FOR COARSE GRADED GRANULAR SUB‐BASE MATERIALS 

 

           IS Sieve        Per cent by weight passing the IS Sieve                       ______________________________________________________  1.1.1.1.2 Designation      Grading I  Grading II  Grading III   75.0   mm          100  ‐  ‐ 53.0   mm           100   26.5   mm      55‐75           50‐80                     100 9.50   mm                                                                                       4.75   mm                                                  10‐30                                  15‐35                    25‐45 2.36   mm                                       0.425 mm       0.075 mm  <10  <10  <10  

Page 111: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 100 of 139

CBR Value (Minimum)  30  25  20  

Note :    The material passing 425 micron (0.425 mm) sieve for all the three gradings when   tested  according  to  IS  :  2720  (Part  5)  shall  have  liquid  limit  and plasticity index not more than 25 and 6 percent respectively. 

   4.1.3.   Strength of sub‐base  

It shall be ensured prior to actual execution that the material to be used in the  sub–base  satisfies  the  requirements  of  CBR  and  other  physical requirements when compacted  and finished.  When directed by  the  Engineer,  this  shall be  verified by performing CBR tests  in  the  laboratory  as  required  on  specimens  remoulded  at  field  dry density  and  moisture  content  and  any  other  tests  for  the  “quality”  of materials, as may be necessary. 

   4.1.4.      Construction Operations       4.1.4.1.   Preparation of subgrade:  Immediately prior to the  laying of sub‐base, the 

subgrade  already  finished  to  Clause  301  or  305  as  applicable  shall  be prepared by  removing all vegetation and other extraneous matter,  lightly sprinkled with water  if necessary and rolled with two passes of 80‐100 kN smooth wheeled roller. 

   4.1.4.2. Spreading and compacting: The sub‐base material of grading specified  in  the 

Contract  shall be  spread on  the prepared  subgrade with  the help of a motor grader  of  adequate  capacity,  its  blade  having  hydraulic  controls  suitable  for initial adjustment and for maintaining the required slope and grade during the operation or other means as approved by the Engineer. 

 When  the sub‐base material consists of combination of materials mentioned in  Clause  4.1.2.1.  mixing  shall  be  done  mechanically  by  the  mix‐in‐place method.  Manual  mixing  shall  be  permitted  only  where  the  width  of  laying  is  not adequate  for mechanical  operations,  as  in  small‐sized  jobs.  The  equipment used  for mix‐in‐place  construction  shall  be  a  rotavator  or  similar  approved equipment capable of mixing the material to the desired degree. If so desired by the Engineer, trial runs with the equipment shall be carried out to establish its suitability for the work.  Moisture content of the loose material shall be checked in accordance with IS : 2720 (Part 2) and suitably by sprinkling additional water from a truck mounted 

Page 112: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 101 of 139

or trailer mounted water tank and suitable for applying water uniformly and at controlled quantities to variable widths of surface or other means approved by the Engineer so that, at the time of compaction, it is from 1 percent above to 2 percent below the optimum moisture content corresponding to IS : 2720 (Part 8). While adding water, due allowance shall be made  for evaporation  losses. After water has been added, the material shall be processed by mechanical or other approved means like disc harrows, rotavators until the layer is uniformly wet.  Immediately  thereafter,  rolling  shall  start.  If  the  thickness of  the  compacted layer  does  not  exceed  100 mm,  a  smooth wheeled  roller  of  80  to  100  kN weight may be used. 

 For a compacted single layer upto 225 mm the compaction shall be done with the help of a vibratory roller of minimum 80 to 100 kN static weight with plain drum or pad  foot‐drum or heavy pneumatic  tyred  roller of minimum 200  to 300 kN weight having a minimum  tyre pressure of 0.7 MN/m2 or equivalent capacity  roller  capable  of  achieving  the  required  compaction.  Rolling  shall commence  at  the  lower  edge  and  proceed  towards  the  upper  edge longitudinally  for portions having unidirectional crossfall and super elevation and  shall  commence  at  the  edges  and  progress  towards  the  centre  for portions having crossfall on both sides.  Each pass of  the  roller shall uniformly overlap not  less  than one  third of  the track  made  in  the  preceding  pass.  During  rolling,  the  grade  and  crossfall (camber) shall be checked and any high spots or depressions, which become apparent, corrected by  removing or adding  fresh material. The  speed of  the roller shall not exceed 5 km per hour.  Rolling shall be continued till the density achieved is at least 98 percent of the maximum dry density for the material determined as per IS : 2720 (Part 8). The surface  of  any  layer  of material  on  completion  of  compaction  shall  be well closed,  free  from  movement  under  compaction  equipment  and  from compaction planes,  ridges,  cracks or  loose material. All  loose,  segregated or otherwise defective areas shall be made good to the full thickness of layer and re‐compacted.  

4.1.5.    Surface Finish and Quality Control of Work  The surface finish of construction shall conform to the requirements of Clause 902.  Control  on  the  quality  of  materials  and  works  shall  be  exercised  by  the Engineer in accordance with Section 900. 

Page 113: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 102 of 139

 4.1.6.    Measurements for Payment 

  Granular  sub‐base  shall  be measured  as  finished  work  in  position  in  cubic metres. .   The protection of edges of granular sub‐base extended over the full formation as  shown  in  the  drawing  shall  be  considered  incidental  to  the  work  of providing granular sub‐base and as such no extra payment shall be made for the same.  

4.1.7.   Rate  The  Contract  unit  rate  for  granular  sub‐base  shall  be  payment  in  full  for carrying out the required operations including full compensation for:  (i) making arrangements for traffic to Clause 112 except for initial treatment to  

verges, shoulders and construction of diversions;  (ii)  furnishing  all  materials  to  be  incorporated  in  the  work  including  all royalties, fees, rents where necessary and all leads and lifts;  (iii)all  labour,  tools, equipment and  incidentals  to  complete  the work  to  the 

Specifications;:  (iv)carrying out the work in part widths of road where directed; and  (v) carrying out the required tests for quality control.  

  4.2      Water Bound Macadam Sub‐base with stone aggregate  : Stone aggregate 

of size 90 mm shall be used. This consists of clean crushed coarse aggregate mechanically  interlocked by rolling using power road roller of 8 to 10 t and voids thereof filled with screening and blinding material with the assistance of water, laid on a prepared sub grade/ sub base. 

 4.2.1  Quantities  of  Materials  ‐  Quantities  of  coarse  aggregate,  screening  and 

blinding material required to be stacked for 100mm approximate compacted thickness of WBM  sub‐base  course  for 10  sqm  shall be as per  table given below: 

    

Page 114: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 103 of 139

Coarse Aggregate  Stone screenings Classification  Size  Loose Qty  Grading/Classific

ation and size Loose  Qty 

Binding  Material 

Grading‐1  90mm to 45mm 

       

 NOTE : Net Quantity = Loose quantity measured in stack minus 7.5% 

 4.2.2  Preparation  of  foundation  :  In  the  case  of  an  existing  unsurfaced  road, 

where new materials is to be laid, the surface shall be scarified and reshaped to the required grade, chambered shape as necessary. Weak places shall be strengthened,  corrugations  removed  and depressions  and pot holes made good with suitable materials, before spreading the aggregate for WBM. 

 4.2.3  Spreading Aggregate  : The coarse aggregate shall be spread uniformly and 

evenly upon the prepared base in required quantities with a twisting motion to avoid segregation. In no case shall these be dumped in heaps directly on the  area where  these  are  to  be  laid  nor  shall  their  hauling  over  a  partly completed base be permitted. The aggregates shall be spread uniformly to proper profile by using  templates placed across  the  road,  six metres part. Where specified, approved mechanical devices may be used  to spread  the aggregates uniformly. The levels along the longitudinal direction upon which the metal  shall be  laid,  shall be  first obtained at  site  to  the  satisfaction of Consultant and these shall be adhered to . 

 4.2.4      The surface of the aggregate spread shall be carefully trued up and all high 

spots by removing or adding aggregate as may be required.  4.2.5      The  WBM  sub‐base  shall  be  normally  constructed  in  layers  of  115  mm 

compacted  thickness.  No  segregation  of  large  or  fine  particles  shall  be allowed and  the  coarse aggregate as  spread  shall be of uniform gradation with no pockets of fine material. 

 4.2.6      The  coarse  aggregate  shall  normally  not  be  spread  in  lengths  exceeding 

three days average work ahead of the rolling and blending of the proceeding section. 

   

Page 115: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 104 of 139

4.3      ROLLING:  4.3.1  Immediately  following  the  spreading  of  the  coarse  aggregate,  it  shall  be 

compacted to the full width by rolling with either a three‐wheel power roller of 8 to 10t capacity or an equivalent vibratory roller. Initially,  light rolling  is to  be  done  which  shall  be  discontinued  when  the  aggregate  is  partially compacted  with  sufficient  void  space  in  them  to  permit  application  of screenings. 

 4.3.2      The  rolling shall begin  from  the edges with  the  roller  running  forward and 

backward  and  adding  the  screenings  simultaneously  until  the  edges  have been  firmly  compacted. The  roller    shall  then progress gradually  from  the edges to the centre paralled to the centre  line of the road and overlapping uniformly  each  preceding  rear  wheel  track  by  one  half  width  and  shall continue  until  the  entire  area  of  the  course  has  been  rolled  by  the  rear wheel. Rolling shall continue until the road metal  is  thoroughly keyed with no creeping of metal ahead of the roller. Only slight sprinkling of water may be done during rolling, if required. On super cleaved curves, the rolling shall proceed from the lower edge and progress gradually continuing towards the upper edge of the pavement. 

  4.2.3 Rolling shall not be done when the sub‐grade is soft or yielding or when the 

rolling causes a wave like motion in the sub‐base of sub‐grade. When rolling develops  irregularities  that exceed 12mm when  tested with a  three metre straight  edge,  the  irregular  surface  shall  be  loosened  and  then  aggregate added to or removed from  it as required and the area rolled until  it gives a uniform  surface  conforming  to  the  desired  cross‐section  and  grade.  The surface  shall also be  checked  transversely by  template  for  chambered any irregularities  corrected  in  the manner descried above.  In no  case  shall  the use of screenings to made up depressions be permitted. 

 4.4                APPLICATION OF SCREENING:   4.4.1  After  the  coarse  aggregate  has  been  lightly  rolled  to  the  required  true 

surface, screening shall be applied gradually over the surface to completely fill  the  interstices.  Dry  rolling  shall  be  continued while  the  screening  are being spread so that the jarring effect of the roller causes them to settle into the  voids of  the  coarse aggregates. The  screening  shall not be dumped  in piles  on  the  coarse  aggregate  but  shall  be  spread  uniformly  in  successive thin  layers  either  by  the  spreading  motion  of  the  hand  shovels  or  a mechanical spreader. 

 

Page 116: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 105 of 139

4.4.2      The screening shall be applied at a slow rate (in three or more applications) so as to ensure filling of all voids. Rolling and brooming shall continue with the spreading of the screenings. Either mechanical brooms or hand brooms or both may be used.  In no case shall the screening be applied, so fast and thick  as  to  form  cakes,  ridges  on  the  surface making  the  filling  of  voids difficult,  or  to  prevent  the  direct  bearing  of  the  roller  on  the  coarse aggregates.  The  spreading,  rolling  and  brooming  of  screening  shall  be performed on sections which can be completed within one day’s operation and shall continue until no more screening can be  forced  into  the voids of the coarse aggregate. Damp and wet screening shall not be used under any circumstances. 

 4.5  SPRINKLING AND GROUTING :   4.5.1  After  spreading  the  screening  and  rolling,  the  surface  shall  be  copiously 

sprinkled with water, swept and rolled. Hand brooms shall be used to sweep the  wet  screening  into  the  voids  and  to  distribute  them  evenly.  The sprinkling, sweeping and rolling operations shall be continued and additional screenings  applied  where  necessary  until  the  coarse  aggregates  are  well bonded  and  firmly  set  for  the  entire  depth  and  until  a  grout  has  been formed of  screenings and water  that will  fill all  voids and  form a wave of grout ahead of  the wheels of  the  roller. The quantity of water  to be used during the construction shall not be excessive so as to cause damage to the sub‐base or sub‐grade. 

 4.6  APPLICATION OF BLINDING MATERIAL :   4.6.1  After  the application of  screenings and  rolling, a  suitable blinding material 

shall be applied at a uniform and slow rate  in two or more successive thin layers.  After  each  application  of  blinding  material,  the  surface  shall  be copiously sprinkled with water and  the  resulting slurry swept‐in with hand brooms or mechanical brooms or both so as  to  fill  the voids properly. The surface  shall  then be  rolled by  a 8‐10  t  roller, water being  applied  to  the wheels  in order  to wash down  the blinding material  that may get stuck  to the wheels. The spreading of blinding material, sprinkling of water, sweeping with brooms and  rolling shall continue until  the slurry  that  is  formed well, after filling the voids form a wave ahead of wheels of the moving roller. 

 4.7  SETTING AND DRYING :   4.7.1  After  final  compaction  of  the  course,  the  road  shall  be  allowed  to  cure 

overnight. Next morning  defective  spots  shall  be  filled with  screenings  or blinding material,  lightly  sprinkled with water,  if  necessary  and  rolled. No traffic shall be allowed till the macadam sets. 

Page 117: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 106 of 139

4.8  SURFACE EVENNESS:   4.8.1  The surface evenness of completed WBM sub‐base  in  the  longitudinal and 

transverse directions shall be as specified in the table given below:    

Size of coarse aggregates  Longitudinal profile  Cross profile  

 45‐90mm 

   

Maximum  permissible undulation  when measured with  a  3 metre straight edge               15 mm 

Maximum  permissible variation  from  specified profile  when  measured with a camber‐template               12 mm 

   The longitudinal profile shall be checked with a 3M long straight edge at the 

middle of each traffic lane along a line parallel to the centre line of the road. The  transverse  profile  shall  be  checked  with  a  series  of  three  chamber boards at intervals of 10M. 

 4.9  Rectification of Defective Construction  : Where  the  surface  irregularity of 

the WBM  sub‐base  course  exceeds  the  tolerances  specified  in  the  table given above or where  the course    is otherwise defective due  to  sub‐grade soil  mixing  with  the  aggregates,  the  layer  to  its  full  thickness  shall  be scarified over the affected area, reshaped with added material or removed and replaced with fresh material as applicable, and recompacted. The area treated  in  the aforesaid manner  shall not be  less  than 10  sqm.  In no case shall depressions be filled up with screenings and blinding material. 

 5.0  RUBBLE SOLING   5.1  Rubble  soling  for  road work  including  foot paths,  culverts,  side drains etc. 

shall be carried out as  specified here‐in before under chapter‐04, para 3.3 for  rubble  stone  soling,  as  far  as  they  are  applicable, with  the  following additions. 

 5.2  Subgrade  for soling shall be prepared by cleaning of all  foreign substances 

including rank vegetation, if any. Any ruts or soft yielding places that appear due  to  improper  drainage  conditions,  traffic,  hauling  or  from  any  other cause shall be corrected by filling/cutting upto 150 mm and compacted and the Subgrade dressed off parallel to the finished profile and the same shall be approved by the Consultant, before laying of soling. Soling shall be laid in regular  lines  and  staggered  joints.  The  stones  shall  be  laid  as  closely  as possible and packed well. The stones shall be so  laid as to have their bases 

Page 118: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 107 of 139

and the target area resting on the Subgrade and in contact with each other.  5.3  Soling shall be laid to proper gradient and chamber, which shall be checked 

frequently to ensure accuracy. Rolling shall then be carried out by a 8 to 10 t power  roller  and  soling  consolidated  properly  shall  be  lightly  sprinkled during rolling, if ordered by the Consultant. 

 5.4  The  surface  thus  prepared  shall  first  be  passed  by  the  Consultant,  after 

which 40mm  to 50mm  thick  layer of selected hard murrum available  from excavation shall be spread over the soling as directed by the Consultant, and rolled  again  such  that  the  hard murrum  gets  into  the  interstices,  It  shall, however, be ensured  that a  thin  layer of murrum/grit  shall  remain on  the finished surface of soling. 

 5.5  The area of soling actually done of specified consolidated thickness  limiting 

to the dimensions as per drg. Shall be measured  in square metre upto two decimal places. 

 6.0  WATER BOUND MACADAM  6.1  Metal : Metal required for Water Bound Macadam surfacing shall be broken 

from the first sort rubble. The rubble shall be broken to required size by the Tenderer  at  his  own  cost.  However,  the metal  required  for water  bound  macadam shall conform to  IRC specification  in all respects.  It shall be hard, sound, trap stone metal free from decay and weathering and obtained from approved quarries, and shall be of 50 mm nominal size. 

 6.2  Collection of metal : Metal shall be of first sort black trap stone and shall be 

collected in stacks on level ground and stacked on the sides of the roads as directed.  The  metal  shall  be  free  from  all  earth,  rubbish  and  vegetable matter and graded before stacking and closely packed  in stacks. The metal supplied by  the Tenderer shall be arranged  in stacks  for measurement. No deductions will be made for voids. The size of stack shall  be 1m wide at top, 2.2m wide at bottom and 60m high. The  length shall be as directed by the Consultant.  The  Tenderer  shall  provide  the  templates  required  to  ensure, compliance with size of stack stipulated. 

 6.3  Supply  of Murrum  :  The  Tenderer  shall  be  permitted  to  excavate  in  the 

selected  areas  in  the  place  of  work,  as  approved  by  the  Consultant,  for collection  of murrum.  The  excavation  shall  be  done  by  the  Tenderer  to correct  line  and  level,  transport  and  stack  the  same  at  site  of  work  as directed by  the Consultant. Alternately,  the Tenderer will be permitted  to bring  from  outside,  approved  graded  hard murrum  10mm,  down  to  dust 

Page 119: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 108 of 139

(but  not  silt)  as  directed  by  the  Consultant  and  shall  also  be  collected  in stacks on level ground along side of the road.  

 6.4  LAYING AND PREPARATION OF WATER BOUND MACADAM SURFACE   6.4.1  After  preparation  of  the  existing  surface  as  specified  above,  50mm,  size 

metal  collected  in  stacks  shall  be  spread  to  uniform  thickness  over  the prepared surface and consolidated  to 75mm  thickness as specified here  in after. 

 6.4.2  Templates properly made of  full width and gauge or  templates  fitted with 

central plumb to each of edge fixed with  it must be used. The depth of the plank  forming  the gauge  shall be  the  thickness of  the metal  layer  in  loose state  so  that when  the metal  has  been  properly  spread,  the  gauges  are buried  just  flush with  the  surface.  The  intermediate work  shall  be  tested with cord stretched between the gauge. Three templates shall be provided and used with a distance of about 7.5m between each but not exceeding 15m.  A spirit level shall invariably be used with the templates to ensure that the  edges  of metalling  are  truly  levelled.  The metal  shall  be  spread  and rolled  with  8  to  10t  power  roller  until  well  compacted  and  there  is  no appreciable movement (in the metal) when walked upon, or no appreciable wave  in  front  of  the  advancing  roller,  Rolling  shall  be  done  by  roller perfectly, by a 8 to 10 t power roller, till proper internal packing of adjacent pieces of stones has been achieved. Excessive dry rolling shall be avoided. 

 6.4.3  Rolling shall commence from the edge to the centre of the road.  In case of 

super elevated  curve,  rolling  shall  commence  from  the  inside edge of  the centre  and  progress  towards  the  outside  edge.  Where  the  gradient  is steeper than 1 in 60, the roller shall run up grade, i.e. rolling shall be started from lower level to upward direction for the 1St rolling. 

 6.4.4  While  rolling  the surface  in  two or more parts, a strip of about 230mm  to 

30mm  along  the  predetermined  cross  section  shall  be  left  unrolled while consolidating the first half. This shall be properly  jointed when the metal  is being  spread  on  the  second  half  and  consolidated with  it.  Care must  be taken  to  avoid  the  occurrence  of  a  continuous  longitudinal  furrow  along cross section of the road. Full width of road will be rolled at a time. 

6.4.5  The metalling shall be moderately kept saturated and rolling continued until consolidation  is  completed.  Just  enough watering  shall  be  done  so  as  to flush the metal slurry into the interstices. Care shall be taken to avoid excess water softening  the subsoil. The  full consolidation stage shall be  tested by (a) putting a piece of metal about  the  size of wall not on  the  surface and roller  passed  over  it.  If  it  is  crushed  the  surface  shall  be  deemed  as well consolidated (b) there shall be no creeping of stone ahead of the roller. 

Page 120: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 109 of 139

 6.4.6  Until  the above  conditions are  satisfied, no blinding or  surfacing materials 

shall be put on  the  surface. No  rolling  shall be done where  signs of metal crushing are noticed or rolling causes wave  like motions  in the base course of  well  compacted.  Before  starting  rolling,  the  metal  shall  be  dressed accurately to camber. No fresh metal shall be added once dry consolidation has commenced. The part of  the  road must be  fully  racked up so  that  the metal is thoroughly incorporated into the body of road. 

 6.4.7  Blinding Course: When the required consolidation has been completed, the 

blinding  material  of  approved  graded  murrum/stone  grit  and  dust (unscreened)  as  specified  shall  be  spread  over  the  surface  and  brushed backwards and forwards to fill in the surface voids and rolling and watering continued  to  such an extent  that  the blinding materials are  formed  into a slurry  and  is  grouted  into  the  interstices.  After  the  road  has  been  fully consolidated,  the  surface  shall  be  covered  with  12mm  layer  of murrum/stone grit and dust (unscreened) and road opened to traffic after 4 days. The  road  shall be  kept watered  for 14 days or  such other period as specified  by  the  Consultant. Where  tracks  are  likely  to  be  formed  by  the traffic on the road, barriers such as tree branches etc. shall be put to divert the traffic. After 15 days, light watering and rolling shall be done. For joints across  the  road,  the end of each  layer  shall be given a  flat  slope and well consolidated together and hump formation must be avoided. 

6.4.8  Damages  to  the  Owner’s  Property  :  Any  damage  to  the  departmental property due  to negligence of  the Tenderer while executing  the work shall be made good to the original conditions at his own cost. 

 7.0  BITUMINOUS MACADAM  AND  BITUMINOUS  CONCRETE  SURFACING  FOR 

ROAD (GENERAL) :  7.1  The  work  covered  under  these  specifications  provides  for  bituminous 

treatment  for  roads  consisting  of  providing  38  mm  thick  bituminous Macadam and 12mm thick seal coat or bituminous concrete of thickness as specified in item in the schedule of quantities. 

 7.2  The  Tenderer  shall  make  at  his  own  cost,  all  the  arrangements  for 

controlling  the  traffic  during  the  execution  of  the work. All  arrangements such as proper barricading of  road, diversion of  road  if necessary,  red and green  flags during  the day  and    red  lights  at nights  shall be made by  the Tenderer at his own cost to control and safeguard the traffic. 

 7.3  BITUMINOUS MACADAM OVER WATER BOUND MACADAM :  7.3.1   Preparation of existing Water Bound Macadam surface :  

Page 121: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 110 of 139

 a)  The  existing  Water  Bound  Macadam  surface  shall  be  brushed, 

cleaned properly with wire brushes and coir brooms,  so as  to  free from all loose materials, murrum, earth, silt and caked mud etc. The surface shall then be dusted clean with gunny bags etc. if during the process  of  cleaning  the  sub  grade  (Water  Bound Macadam),  soft spots and packets, hollows etc. are  found,  such  spots/pockets will be  filled with  approved  precoated  bituminous  chips,  consolidated and  finished  to proper  level,  rolled with power  roller  if necessary. The  potholes  shall  be  excavated  properly  in  a  rectangular  or rhomboidal shape with vertical edges. The bottom and sides shall be cleaned  as  stated  above.  The  sides  and  bottom  shall  then  be thoroughly painted with heated 30/40 penetration bitumen. The pot holes  shall  thereafter be  filled with premixed bituminous  chips  so that  after  thorough  tamping  and  rolling,  the  surface  is  flush with surrounding road surface all as directed by the Consultant. It shall be the  responsibility  of  the  Tenderer  to  ensure  that  the  Subgrade  is even and is finished to camber and slope as shown on the drgs. or as directed by the Consultant. 

 b)  The  surface  of  the  Subgrade  shall  be  checked  for  its  trenches  by 

means of the scratch template resting on side forms having scratch points placed  at not  less  than 200mm.  apart  and  set  to  the exact profile of  the base  course. The  template  shall be drawn along  the forms at right angles to the road. 

 c)  Unevenness of the surfaces as  indicated by the scratch points shall 

not  exceed  10mm  in  30m.  The  area  of  depression  shall  then  be painted or  sprayed with 30/40 penetration bitumen at  the  rate of 0.75 kg per sqm and the levelling course applied by hand or machine to grade and chamber and rolled. If the depressions are deeper than 50mm,  the  levelling  course  shall be applied  in  two or more  layers and rolled as directed by the Consultant. 

 d) The prepared surface shall be closed to traffic and maintained fully clean 

and no asphalting work shall be started unless  this prepared surface  is approved by the Consultant. 

 7.3.2   MATERIALS  

Representative samples of materials proposed to be used shall be submitted to the Consultant and got approved.   No material shall be used unless  it  is approved by the Consultant. 

 

Page 122: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 111 of 139

7.3.3   HOT MIXED HOT LAID BITUMINOUS MACADAM:  

a)  COARSE AGGREGATE:  

i)    It shall consist of crushed hard  trap stone metal,  free  from coatings of clay, silt and any objectionable material.   Metal brought by Tenderer for different items of work shall strictly conform to I R C specifications in all respects.  The aggregate shall be obtained by crushing approved  stones of  specified type in mechanical crusher and shall be hard, close grained, sound  trap  stone metal,  free  from  decay  and weathering and obtained from approved quarries. 

 ii)  Metal shall be collected in stacks on level ground and neatly 

stacked  at  site  of mixing.  The metal  shall  be  free  from  all earth,  rubbish,  vegetation  and  other  foreign  matter  and graded before stacking and closely packed in stacks. 

 iii)  Tests  considered  necessary  shall  be  carried  out  in  an 

approved  laboratory  when  the  Consultant  considers  the quality to be doubtful or there  is dispute about the quality.  The cost of testing shall be borne by the Tenderer. 

 iv)  Aggregate grading  :   The requirements of base course shall 

be as under:  

B.S. Sieve Designation  Equivalent I S Sieves  Passing percentage 32 mm (about 1.25”)  40MM (1.5”)  100 20 mm (about ¾”)  20 mm  50 – 100 12 mm (about ½”)  12.5 mm   30 – 60 6 mm (about ¼”)  6.3 mm  18 – 30 No. 10  1.7 mm  10 – 20 No. 200  75 micron  0 – 5 

  

v)  The  aggregate/chips  shall  be  entirely  dry  at  the  time  of mixing. 

 b)  BITUMEN:    Bitumen  to  be  used  shall  conform  to  I.S:73.1992  for 

paving  bitumen,  with  30/40  penetrations  and  shall  be  from approved  manufacturers.  The  Tenderer  on  demand  by  the Consultant,  obtain  and  furnish  a  laboratory  test  certificate  to  the effect  that  the  material  conforming  to  the  requirement  of  the 

Page 123: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 112 of 139

specified  grade,  to  the  satisfaction  of  the  Consultant.    Bitumen (30/40 penetration) content 3.7% to 4.7% by weight of the total mix, shall be used in the mixture. 

 c)  TACK COAT  : Bitumen of  the  same  grade  as  that used  for premix 

shall be heated to a temperature of 1630 C to 1770C (3250 F to 350 F) in a bitumen boiler and the hot bitumen shall be applied evenly to the  thoroughly  cleaned  and  prepared  road  surface  (as  specified here‐in‐before)@ 7.5 kg per 10 sqm  leaving no part   of the surface unpainted.    Application  shall  be  done  by  a  mechanical  pressure sprayer or  if permitted, by perforated pouring cans.   The  tack coat shall be applied just before the macadam is laid.  Application of tack coat  shall  be  only  slightly  in  advance  of  laying  premixed  chips.  In case  of  surface  already  asphalted,  application  of  tack  coat  is  not necessary. 

 d)  PREMIXING CHIPS:   

 i)  The bitumen shall be heated to 1630 C to 1770 C (3250 F to 

350 F) in boiler The aggregate of the approved grading or as decided by  the preliminary shall be dried and heated  in an aggregate drier to a temperature of 1490 C to 1770 C (300 F to 350 F) and  fed  into a  twin  shaft peddle  type mixer at a temperature  not  less  than  1490  C  (about  300  F).    The bitumen,  the  approved  aggregate  and  the  filler  shall  be measured  separately  and  accurately  to  the  proportions  in which they are to be mixed and mixed  intimately till all the particles  are  completely  coated  with  bitumen. Asphalt/bituminous mixing  plant  proposed  to  be  used  by the  Tenderer  for  the  preparation  of  Asphalt/bituminous mixing  shall conform  to all of  the  requirements of  the  job, which  shall  produce  uniform  mixtures  of  the  required quality, an got approved by the Owner before mixing. 

 ii)  The temperature of the premix bituminous macadam when 

leaving the mixer shall not be less than 130 C (about 280 F) and it shall not be less than 1210 C (about 250F) at the time of laying. 

 iii)  Bituminous macadam shall be transported to site of work in 

suitable tipping vehicle  properly insulated and covered with canvas  or  other  suitable materials  to  protect  the mixture from weather conditions and  to  retain  the heat.   The  road surface  shall  be  suitably  marked  to  ensure  correct  and 

Page 124: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 113 of 139

uniform application.   Width of macadam to be  laid shall be slightly more (not exceeding 50 mm on each side) than the required carriage way as per drawing.  Excess on either side shall be neatly cut after full compaction to get final width of carriage  way  as  per  drawing.    The  premixed  bituminous macadam  shall  be  laid  by  a  mechanical  self  powdered spreader and compactor and finished to correct line, level, & final consolidation done by means of power  roller not  less than 10  tonne.   Any  irregularities shall be corrected during rolling. 

 e)  COMPACTION  :    The  base  bituminous  macadam  course  shall  be 

compacted thoroughly and evenly with 10 to 12 tonne power roller immediately  after  it  is  laid.    Compacted  thickness  shall  be  as specified in schedule of quantity. 

 7.3.4  The surface shall be checked for correct grade during and after rolling.  Any 

irregularities shall be corrected by adding precoated chips or removing the surplus.   The disturbed surface shall be well compacted again.   If necessary the  roller wheel  shall be  coated with oil  to prevent  the  coated  chip  from sticking    to  the wheels.   Rolling shall be continued  till no wheel marks are left  on  the  surface.    The  speed  of  the  roller  shall  be  sufficiently  slow  to prevent any pushing under the wheels. 

  8.0  HOT MIXED HOT  LAID BITUMINOUS  CONCRETE WEARING COURSE  (SEAL 

COAT)  8.1  Bituminous  concrete  :   Shall consist of mixture of mineral aggregate,  sand 

and filler, graded to fill the voids, mixed with bitumen binder to obtain the maximum  stability.    It  shall  be  spread  and  compacted  on  a  prepared bituminous macadam base in conformity with lines, grades and cross section shown  in  the  drawings.    The  aggregate  shall  be  preheated  temperature specified for the bitumen and the mixture shall be prepared and laid hot. 

 8.2  COARSE AGGREGATE :   8.2.1  The  coarse  aggregate brought by  Tenderer  shall be  I.R.C. hard black  trap, 

crushed  in mechanical  crushers  and  shall  be  clean,  strong,  tough,  dense, close grained, angular but not flaky, and free from soft, decayed, weathered portion, coating of dust, dirt or other objectionable matter.   Maximum size of  the  aggregate  shall  be  suitable  for  the  thickness  of  the  seal  coat (12mm/15mm or as specified). 

 

Page 125: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 114 of 139

8.2.2  The aggregate grading  composition and  characteristics of  surface  (wearing course mix) shall conform to standard code of practice.  The mix shall satisfy the following requirements: 

 8.3  Fine Aggregate:  The fine aggregate shall be clean, natural, river bank or pit 

sand  or  quarry  sand  produced  in  a  crushing  plant  and  satisfying  the requirement  of  the  grading  of  aggregate  for  the  bituminous  concrete  as stated above or as determined by the preliminary tests. 

 8.4  FILLER:   The  filler  shall be dry and clean  lime  stone powder hydrated  lime 

having  calcium  oxide  content  of  not  less  than  60%  both  passing  BS  sieve No.8.    It  shall  be  free  from  lumps  and  loosely  bonded  aggregate. When tested by  laboratory sieves, 100% shall pass through B S sieve No. 14, 80% shall pass through B S sieve No. 8 .  Fillers shall be added to the aggregate to give the above grading determined by preliminary tests. 

 8.5  BITUMEN:  Bitumen  shall  be  of  30/40  penetration  or  such  other  grade 

specified by the Consultant and shall conform to IS: 73‐1961.  8.6  PREPARATION  OF  BASE:  Dirt,  dust  and  other  foreign  materials  if 

accumulated  shall  be  cleared  off  leaving  the  surface  entirely  clean.    The prepared surface shall be closed to traffic and so maintained fully clean till the seal coat is applied. 

 8.7  MIXING AND LAYING WEARING COURSE:    8.7.1  Grade 30/40 bitumen shall be heated to a temperature of 1630 C to 1770 C 

(3250 F to 350 F) in a boiler.  The aggregate of the suitable approved grading or as decided by preliminary tests, shall be dried and heated in an aggregate drier  to a  temperature of 1490 C  to 1770 C  (300 F  to 350 F) and  fed  into a twin shaft peddle type mixer at a temperature not less than 1490 C (3000 F).  The bitumen, the aggregate and the filler shall be measured separately and accurately  to  the  proportions  in  which  they  are  to  be mixed  and mixed intimately  till  all  the  particles  are  completely  coated with  bitumen.    The quantities of aggregate, bitumen and the filler shall be such as to obtain the percentage of each as  specified above or decided after  tests.   Continuous batching and mixing plant  shall be used.   Asphalt/bituminous mixing plant proposed  to  be  used  by  the  Tenderer  for  the  preparation  of asphalt/bituminous mixes  shall  conform  to  all  of  the  requirements  of  the job, which shall produce uniform mixtures of the required quality. 

 8.7.2  The  temperature of bituminous concrete when  leaving  the mixer  shall not 

be less than 1380 C (280F) and it shall not be less than 1210 C (250 F) at the time of laying. 

Page 126: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 115 of 139

 8.7.3  The bituminous concrete shall be transported to the site of work in suitable 

tipping vehicles properly insulated and covered with canvas or other suitable materials to protect the mixture from weather conditions and to retain the heat. 

 8.7.4  The mixture  shall be  spread with mechanical  self powered  spreader.   The 

bituminous concrete shall be  laid to the specified  line, curve, grade camber  Any  irregularities  shall  be  corrected  immediately  before  rolling  is  started.  Before  laying  the mixture,  the  faces  of  the  joints  shall  be  painted with  a uniform coating of hot bitumen.   The bituminous concrete  shall be  laid  to such  loose depth as to give a compacted  layer of specified thickness as per item in the schedule of quantities. 

 8.8  COMPACTION  :    The bituminous  concrete  layers  shall  then be  allowed  to 

cool  sufficiently  such  that  it  does  not  spread  under wheel  load  of  10/12 tonne power roller.  The compaction shall be done by the roller till no wheel mark are left on the surface and no further compaction is possible.  The road shall  be  opened  to  traffic  on  cooling  of  the  concrete  to  the  atmospheric temperature or after a lapse of 24 to 40 hr after laying. 

 9.0  GENERAL REQUIREMENTS FOR BITUMEN MACADAM & SEAL COAT  9.1  TESTING :  The Tenderer shall have a well equipped testing laboratory with a 

competent laboratory staff.  Daily test (not less than two specimen per day) shall  be  made  by  them  on  the  bituminous  mixture  produced  to  ensure compliance with these specification and copy of the test results duly signed by  the  competent  authority  shall  be  submitted  to  Consultant  for  record.  Tests  shall  include  water  absorption,  stability,  filler  content  etc.  The Tenderer  shall  give  all  facilities  at  all  items  to  the  Consultant  or  his representative to inspect the work or testing done by him 

 9.2  WEIGHING :  Each lorry leaving the plant must be weighed on a weigh bridge 

in  the presence of  the  representative of  the Owner and a challan must be issued along with the  lorry  in duplicate showing the weight of the material loaded  in  the  lorry.   As  and when  required,  the  said  lorries  shall  also  be weighed at the Owners weigh bridge or any other weigh bridge approved by the Consultant to check the tonnage of the material stated on the challans.  In case of short fall, the same shall be made good by the Tenderer without extra cost. 

 9.3  TESTING SURFACE :  The completed surface when ready for acceptance shall 

be thoroughly compacted, smooth, true to line, grade, camber and free from irregularities when  tested by means of a  straight edge of 3m  long,  laid on 

Page 127: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 116 of 139

the  finished  surface  parallel with  the  centre  line  of  the  road,  the  surface shall in no place vary more than 6mm from the working edge. 

 9.4  The  defects  in  the  bituminous  paving which  the  Tenderer may  be  called 

upon to rectify are of the following type  

a) Deformation of bituminous pavement resulting in Waves or ruts  

b) Cracking of bituminous pavement resulting in admission of water to the  sub‐grade  and  the  deterioration  of  the  bituminous  pavement adjoining the cracks. 

 c) Disintegration/Revealing  of  bitumen  pavement  resulting  in  the 

formation of pot holes.  

d) Polishing  of  the  bitumen  pavement  under  traffic  resulting  in  a surface on which the vehicles are liable to skid. 

 9.5  Defects  in  areas  in  bitumen  pavement  under  guarantee  shall, when  they 

exceed  the  limits  specified  below,  be  remedied  immediately  by  the Tenderer.  The limiting values of the defects shall be the following 

 a) Deformation: 25mm in 3 m 

 b) Cracks: 1500 mm in lengths and 3mm in width 

 c) Disintegrated revealed patches: 2.00 sqm and/ or 12mm in depth. 

 10.0  CEMENT CONCRETE ROADS/PAVEMENTS  10.1  GENERAL :    The  subgrade/sub‐base  shall  have  no  soft  spots.  It  shall  be  uniformly 

compacted  using  mechanical  power  rollers  of  8  to  10  tones  capacity (minimum).  The  subgrade  shall  be  properly  drained  and  the  minimum modulus of sub‐grade reaction obtained with plate bearing test shall be 0.55 N/mm2. 

   The  construction  procedure  for  sub‐grade  or  sub‐base  should  follow 

relevant IRC (India Road Congress) specifications and quality control should be exercised as laid down in IRC: SP.11. Equivalent British Standards may be followed in lieu of IRC standards. 

 

Page 128: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 117 of 139

  The sub‐base or hardcore shall be of hard quarry stones of size 80mm and down  graded  laid  in  compact manner  to  the  required  camber  and  rolled using 8  to 10  tonnes power  roller  (both wet and dry  rolling). A  sand  layer shall be placed between  the sub‐base and concrete. A  layer of waterproof sheet shall be laid over the sand layer prior to concreting. 

 10.2  JOINTS  10.2.1  TRANSVERSE EXPANSION JOINTS    These joints shall extend over the entire width of the pavement as shown in 

relevant  drawings.  Dowel  bars  shall  be  as  per  dimensions,  locations  and spacing stipulated in the drawing. The pre moulded expansion joints filter, a compressible  material  used  to  fill  the  gap  between  adjacent  slab  at expansion joint shall conform to IS:1838. The height of the filler board shall be such that its top is 25mm below the surface of the pavement. The dowel bars shall be held accurately  in position during  the placement, compaction and  finishing  of  concrete  at  and  near  the  expansion  joints.  This  and  the protection  of  the  joint  grooves  during  construction may  be  achieved  by means of  sufficiently  strong bulkheads with holes drilled  along  the  centre line  to accommodate  the dowel bars and a mild steel section  respectively. The  later  shall  be  oiled  or  greased  before  placing  in  position  to  avoid bonding with concrete. The top and bottom edges of the bulkheads and mild steel section shall be shaped to correspond to the camber of the pavement. Bulkheads  shall be used  in pairs  to hold  the projecting ends of  the dowel bars and maintain their alignment. The bulkheads shall be securely staked in place at right angle to the centre line and surface of the pavement. 

   After the concrete has sufficiently hardened, the mild steel section shall be 

removed carefully without disturbing the edges.    Under no circumstance shall any concrete be left at the expansion joint filler 

or across the joint at any point.  10.2.2  TRANSVERSE CONTRACTION JOINTS    These shall be  the weakened plane or  ‘dummy’ groove  type. They shall be 

constructed by forming  in the surface of the slab, a slot not  less than 6mm wide and having a depth equal  to one  third  the depth of  the pavement at the  thinnest  part  of  its  section.  This  slot  shall  be  formed  in  a  manner approved by the Engineer‐in‐charge, such as by pushing into the concrete a flat bar or web of a  ‘T’ bar using a suitable vibratory device,  removing  the bar,  and  keeping  the  slot  open.  It  shall  be  ensured  that  no  spalling  of 

Page 129: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 118 of 139

concrete  occurs while  removing  the  bars.  The  edge  of  the  joint  shall  be rounded with an edging tool before the concrete hardens. 

 10.2.3    TRANSVERSE CONSTRUCTION JOINTS    These shall be placed whenever placing of concrete  is suspended  for more 

than 30 minutes. Excepting  in case of emergency, construction shall always be suspended at  the regular site of expansion or construction  joints.  If  the construction  joint  is  located  at  the  site  of  an  expansion  joint,  regular expansion joint shall be provided. 

 10.2.3.1 LONGITUDINAL JOINTS    These shall be of plain butt type and shall be formed by placing the concrete 

against the face of the slab concreted earlier. The face of the slab concreted earlier shall be painted with bitumen or approved debonding material prior to placing of fresh concrete. 

   The dowel bars used in longitudinal joints shall be suitably supported as not 

to be displaced during construction operation.  10.2.5   REINFORCEMENT    Reinforcement steel shall be of grade fe ‐ 415 and shall be free of rust, dirt, 

scale or other deleterious material. The width of  fabric  sheet or bar mats shall  be  such  that  when  properly  placed  into  the  work,  the  extreme longitudinal bars or wire of the sheets of mats will be  located not  less than 50mm  and not more  than 100mm  from  the  edges of  the  slab. Except  for ‘dummy’  joints,  the  length of  fabric  sheets or bar mats  shall be  such  that when properly placed  into the work, the reinforcement will be clear of the transverse  joints  by  not  less  than  50mm  and  not  more  than  10mm  as measured from the centre of the joint to the ends of the longitudinal bars or wires of the sheet or mat. 

   While  overlapping  the  sheets  or  bar mats  in  either  direction,  the  overlap 

shall be at least equal to the spacing between the bars or wires in respective direction or 40  times  the diameter of  the bar or wire, whichever  is more. The overlap of reinforcement shall be 50mm below the slab top surface. 

 10.2.6  COMPACTION    The pavement  shall  be  compacted by means of power driven  paver‐cum‐

finisher  or  by  vibrating  screen  along  with  internal  vibrators.  Compaction 

Page 130: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 119 of 139

with  wooden  hand  tampers  may  be  adopted  only  in  constricted  areas subject to the approval of the Engineer‐in‐charge. 

 10.2.7  FINISHING    After  the  concrete  has  been  compacted  and  as  soon  as  practicable,  its 

surface shall be smoothened by means of longitudinal floats, operated from a foot bridge. The  longitudinal float shall be worked with a sawing motion, while held in a floating position parallel to the carriage way’s centre line and passed gradually  from one side of  the pavement of  the other. Movements ahead  along  the  centre  line  of  the  carriage  way  shall  be  in  successive advances of not more than one half the length of the float. 

 10.2.8   CURING OF CONCRETE    INITIAL CURING: The surface of the pavement shall be covered with wetted 

burlaps, cotton or  jute mats, as soon as the concrete has set sufficiently to prevent  marring  of  the  surface,  as  per  the  directive  of  the  Engineer‐in‐Charge.  The  covering  shall  be maintained  in  fully wetted  condition  for  a period of not less than 48 hours.  

   FINAL CURING:  Upon  removal  of  the  wet  covering,  the  slab  shall  be thoroughly cured as follows: Exposed edges of the slab shall be banked with a berm of earth. Upon the slab shall then be laid a system of transverse and longitudinal  bunds  of  clay  about  50mm  high  immediately  covered with  a blanket of sandy soil, the rest of the slab shall then be kept covered with a blanket  of  sand  or  sandy  soil,  at  least  30mm  deep,  and  it  shall  be  kept saturated with water for a minimum period of 14 days. 

 10.2.9   SEALING OF JOINTS :    After  the  curing period  is over,  the  temporary  seal  and  all other  intruded 

materials in all expansion and construction joints, grooves shall be removed completely and then filled with approved joint sealing compound as per IRC‐57 ‘Recommended practice for Sealing of Joints in Concrete Pavement” or by any equivalent practice as per British Codes.  Joints sealing compound shall be  in accordance with  IS:1834 (Spcn. For hot applied sealing compound) or equivalent. 

   The joint opening shall be thoroughly cleaned of all foreign material before 

the primer is applied followed by placing of the sealing material.    Typical composition of primer is as follows: 

Page 131: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 120 of 139

     Percentage by weight  

1. Bitumen (200 penetration grade)  ‐  66             (blended hot)  

     2. Light creosote oil      ‐  14 (blended hot or  cold)       3. Solvent Naptha      ‐  80   (blended cold) 

 NB  : (a) The bitumen shall be melted and fluxed with the oil, and then cold 

solvent Naptha shall be added. (b) Bituminous emulsion shall not be used as primers. 

  The sealing compound shall be poured into joint opening carefully in accordance with  the manufacturer’s  specification. Any excess  filler on  the  surface  of  the  concrete  pavement  shall  be  removed immediately and the pavement surface cleaned. 

   In  order  to  prevent  tackiness  or  pick‐up  of  the  seal  under  traffic,  the 

exposed surface of the sealing compound shall be dusted with dry hydrated lime or by any other method approved by the Engineer ‐in‐charge. 

   The line of separation between adjacent concrete slabs shall be cleaned and  

painted  with  200  penetration grade bitumen.    SPACING OF JOINTS.    The  location  and  spacing  of  joints  shall  be  decided  by  the  Engineer‐in‐

charge. However, the following recommendation regarding spacing of joints may be followed. 

     TYPE OF JOINTS MAXIMUM SPACING    1.   Transverse expansion joints  ‐  50m   2.   Transverse contraction joints  ‐  12m      3.   Longitudinal joints                ‐    4m    

OPENING TO TRAFFIC    In general,  traffic  shall be excluded  from  the newly constructed pavement 

for a minimum period of 28 days. Before the pavement is opened to traffic, it shall be cleaned and all joints shall be sealed. 

   

Page 132: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 121 of 139

10.3   VACUUM COMPRESSED DE‐WATERED CONCRETE FLOORING  10.3.1   TECHNICAL ASSISTANCE/TRAINING OF LABOUR    During  the placement of  concrete,  the  Tenderer  shall have  a minimum of 

one  person  present  at  all  times  who  has  been  adequately  trained  by  a representative  of  the  equipment  manufacturer.  This  person  shall  be experience  in  the  vacuum dewatering process, and  in  the operation of all related equipment and shall direct all concrete dewatering work performed. 

   The  Tenderer  shall  provide  the  services  of  a  representative  from  the 

manufacturer of the vacuum dewatering equipment on site for a period of time  of  at  least  eight  (8)  hours.  The manufacturer’s  representative  shall provide  technical  assistance  for  the  vacuum  dewatering  process  on  the initial day of operation. 

 10.3.2   Equipment  for  Compacting,  Placing,  Vacuum  Processing  and  Finishing  of 

Slab    All process equipment to be used shall be of a design representative of the 

state  of  the  art,  and  shall  be  subjected  to  the  approval  of  the  engineer, Equipment  shall  be  Tremix  or  approved  equal.  System  shall  have  a demonstrated  five  years  history  of  performing  such  work.  The  vacuum pumps shall be able to generate a minimum vacuum of 69mm (24 inches) of mercury  (0.80  atmospheres)    in  actual  operation  using  the  maximum  number and size of suction mats required for this work. 

   The Tenderer shall have at the job site sufficient equipment (vacuum pumps, 

mats,  filter  pads  and  accessories)  to  ensure  that  the  vacuum  dewatering process  continues  uninterrupted  to  completion.  Stand  by  equipment  is sometimes required. 

 10.3.3   MIX DESIGN    The Tenderer  is  responsible  for  the mix design of  the class as called  for  in 

the  Contract Drawings  and must  submit  the mix  proposed  for  use  in  the works before any work is started. 

   The  Tenderers  shall  utilize  a  knowledgeable  and  experienced  concrete 

technician  for  the  design  and  production  of mix  (mixes) meeting  all  the requirements of the specifications. 

   

Page 133: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 122 of 139

10.3.4   QUALITY CONTROL  

  The  Tenderer  has  the  responsibility  for  achieving  the  quality  of  concrete specified  by  controlling  the  concrete  mixes,  placing,  vacuum  process finishing and curing. The concrete  technician  in charge must be present at the site when work is in progress. 

   The  Tenderer  shall  be  responsible  for  mix  adjustments,  performing 

necessary tests, correcting deficiencies and trouble shooting in general.    The Tenderer shall be required to maintain control charts showing individual 

test results for aggregate gradation, slump, air content, cement content and compressive strength. 

 10.3.5   PLANNING OF PLACING    The Tenderer shall submit for review shop drawings for floor slabs, detailing 

the  location  of  all  construction  joints  and  the  sequence  of  the  slab placement  and manufacturer’s  literature  describing  the  equipment  to  be used.  In  addition  to  the  shop  drawings,  the  Tenderer  shall  indicate  the quantity of each piece of dewatering equipment that will be  located at the construction site and shall include the dimensions of all suction mats. 

   Before  concreting  is  started  the work  should  be  planned with  a  view  to 

determine areas to be placed daily, the required amount of equipment, size of vacuum mats,  length of vacuum houses, arrangement of  rails,  if any, or screeds etc. Crew required  for  the vacuum process  is 2 men  to handle  the mats  and  the  pump. Note  that  placing,  vibration,  vacuum  treatment  and floating, follow immediately behind each other. 

   Check position of vacuum pump  in relation to vacuum mat  location to find 

whether extra vacuum houses are required.    10.3.6       CONCRETE MATERIALS        All materials such as cement, sand & aggregates etc. shall be as per relevant 

specification mentioned for concrete work.  10.3.7       EQUIPMENT SPECIFICATION TREMIX SYSTEM  10.3.8       EXECUTION OF TREMIX SYSTEM  10.3.9       GENERAL  

Page 134: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 123 of 139

      The work shall be planned and executed so that there  is no delay between the placement, screeding, dewatering and floating of the concrete. Concrete to  be  vacuum  dewatered  shall  be  handled  and  placed  so  as  to  prevent segregation. The concrete shall be internally vibrated prior to screeding. 

 10.3.9       LEVELING        Immediately  following  placement,  the  concrete  shall  be  levelled  with  a 

vibrating  screed  running  on  a  true  surface,  set  at  the  proper  elevation required  to  provide  the  specified  finished  elevation.  The  concrete  surface shall be screeded high by 2% of the slab’s thickness to compensate for the compaction  caused  by  the  vacuum  dewatering  process.  (Slabs  to  have  an aggregate hardener  shall have compensation made  to maintain elevation). The  vibrating  screed  shall  be  moved  forward  as  rapidly  as  proper consolidation allows. The proper surcharge of concrete must be maintained in front of the leading edge of the screed. 

 10.3.10      VACUUM        Immediately  after  levelling,  the  concrete  shall be  covered with  filter pads 

and  suction  mats  in  strict  accordance  with  the  recommendation  of  the manufacturer to have the slab fully dewatered. The suction mat shall extend 100mm beyond the edge of the filter pad on all sides. The pads shall extend to within  100mm  of  the  edge  of  concrete  slab,  and  the mats  shall  cover entire slab. Before connecting  the hose on  the suction mat  to  the vacuum pump, the edge of the mat shall be smoothed to enable an airtight seal to be created. A vacuum shall then   be applied to the mat. After a minute the gauge  on  the  vacuum  pump  should  indicate  a minimum  vacuum  of  0.70 atmospheres (24.0  in Hg) and  if not, the mat must be checked for  leakage. For concrete  that dewaters readily  the vacuum should  then be maintained at 0.70‐0.80  atmospheres  (24.0‐25.5  in. Hg).  For  concrete which dewaters less  efficiently  (e.g.  air  –  entrained  concrete)  the  vacuum  shall  then  be reduced  to 0.50‐0.60 atmospheres  (15.0‐18.0  in. Hg.). After approximately 10 minutes the vacuum can then be increased to 0.80 atmospheres. 

       The  vacuum  shall  be  maintained  for  at  least  3  minutes  per  25mm  of 

concrete  thickness  at  0.80  atmospheres.  (Where  aggregate  hardeners  are specified,  sufficient moisture  shall  be maintained  to meet manufacturer’s requirements). The suction mats and filter pads shall then be removed and moved to the next section in leapfrog manner. 

       Stop  the  vacuum  dewatering  when  light  foot  prints  only  are  left  in  the 

concrete when stepped upon. A suitable suction  time can also be checked with a Proctor apparatus which should show 1.5‐2 kg/cm2. 

Page 135: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 124 of 139

 10.3.11      FLOATING & HARDENER TOPPING  10.3.12      FINISHING    

The  waiting  time  after  the  floating  operation  depends  on  concrete temperature and humidity and varies from 10 minutes to 2 hours. 

       The  trowelling  operation  cannot  take  place  before  the  concrete  has 

hardened  enough  to  carry  the machine,  i.e  the  trowelling  blades will  not leave  any  marks  on  the  concrete.  Repeated  trowelling,  with  intervals between  the  passes  which  are  adapted  to  the  setting  of  the  concrete, greatly  improves the surface characteristics. The surface will be more wear resistant and less dusty. 

       At  least  two  passes  are  recommended  for  floors,  which  are  not  to  be 

covered. The top surface finish shall be in line and level or in gradient as per drawing. The undulation  in  the  finished surface shall not exceed+3mm per strip. 

 10.3.13      CURING    Vacuum dewatered concrete should be cured like any other quality concrete 

in order to achieve a good final result   11.0  IS / IRC CODES 

 IRC‐37    Guidelines for design of flexible pavements IRC‐73    Geometric design of roads IS – 73     Paving Bitumen 

  IS – 702   Industrial Bitumen IS – 1201   Methods of testing tar and Bituminous materials 

   

C‐17:  SUPPLY & LAYING RCC PIPES  

1.0    SCOPE  

This specification covers the supply and laying of R.C.C. Hume pipes as may be  required.  The  entire work  shall  be  carried  out  as  per  latest  edition  of Indian Standards IS: 783 and IS: 458. 

  

Page 136: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 125 of 139

2.0    SUPPLY OF PIPES  

The Tenderer shall supply the R.C.C. Hume pipes of various diameters along with complete fittings required for carrying out the work. R.C.C. Hume Pipes should conform to class NP3 of IS: 458 as may by required and should be in good  condition.  The  Tenderer  must  furnish,  on  being  demanded  by  the Consultant,  manufacturer’s  certificates  and/or  test  certificates  from recognized authorities. 

 3.0    ALIGNMENT, LEVELS AND GRADE  

The work shall be carried out  in conformance  to  the alignment,  levels and grades specified in the drawings. The layout and levels shall be made by him at  his  own  cost  from  one  reference  grid  and  bench  mark  given  by  the Consultant. Contracts shall give all help  in supplying  instruments, materials and men to the Consultant for checking the detailed layout and levels as and when  required.  Making  of  reference  layout  and  level  pillars  along  the pipeline route and maintaining  them upto completion of  the work shall be the responsibility of the Tenderer, at his own cost. 

 4.0  LAYING OF PIPES  4.1  GENERAL    The laying of R.C.C. Pipes shall conform to IS:783‐1985.  4.2  CONDITIONS FOR LAYING  

The conditions for laying of pipes to suit the conditions at site and/or as per drawings and instruction of the Consultant shall be as classified below: 

 4.2.1    CULVERT CONDITION 

 In this condition the pipe is laid under embankment and may project wholly or partly above the original ground surface. 

 4.2.2    TRENCH CONDITION  

In this condition the pipe  is  laid  in a trench excavated for the purpose. The trench  shall  be  refilled  with  thoroughly  tamped  earth  after  laying  and jointing of pipes in approved manner. 

   

Page 137: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 126 of 139

4.2.3  OPEN CONDITION  

In this condition the pipe  is  laid such that  it projects wholly or partly above original ground  surface,  there being no  super  imposed overburden on  the pipe. 

 4.3.  BEDDING AND SUPPORTS  4.3.1  CULVERT CONDITION  

In this condition the pipes shall be  laid generally as per sector B9 to B16 of Appendix‐B, of IS:783‐1985. 

 4.3.2  TRENCH CONDITION  

In this condition the pipes shall be  laid generally as per Section B1 to B8 of Appendix ‐ B of IS:783‐1985. 

 4.3.3  CONCRETE CRADLE BEDDING  

If specified in the drawing or as instructed by the Consultant, the pipes shall be  laid  on  Concrete  cradles,  conforming  to  section  B1  of  Appendix‐B  of IS:783‐1985  in  case  of  trench  condition  and  conforming  to  section  B5  of Appendix ‐ B of IS:783‐1985 in case of culvert condition. 

 4.3.4  OPEN CONDITION  

In  Open  conditions  the  pipe  laid  shall  be  supported  over  rigid  pedestals constructed at  intervals not greater than the  length of one  individual piece of pipe, as per drawings and  instruction of the Consultant.  In no case shall the  joint between to pieces of pipe shall  lie at the centre of span between the supports. The pedestals shall be of reinforced concrete with a properly shaped out top to receive one third perimeter of the pipe. 

 4.4    JOINTING OF PIPES  

Joints  shall be  flexible  type as per  IS:783‐1985. Rubber  ring, with material conforming to type  ‐ 1A of  IS:5382‐1967 shall be placed on the spigot with special  shape and  the  spigot  is  forced  into  the  socket previously  laid. This compresses  the  rubber  ring  as  it  rolls  into  the  annular  space  formed between the two surfaces of the spigot and socket. 

 4.5    HYDROSTATIC TESTING OF PIPES  

Page 138: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 127 of 139

The pipeline as laid shall be subjected to hydrostatic test as per clause 15.5 of IS:783‐1985 

   

C‐18: WATER PROOFING TREATMENT   1.0    SCOPE  1.1  This  work  covered  under  this  specification  consists   of  providing  and 

laying    ‘cement based water proofing  treatment’  to horizontal and vertical surfaces of various components like under ground trenches, tunnel, lift well, roof terraces, chajjas, water tank etc. 

 1.2  This  specification  also  covers  the  guarantee  to  be  given  by  the  executing 

agency for leakproofness of the treatment for a period of ten years.  2.0  APPLICABLE CODES & SPECIFICATIONS:  2.1  The relevant IS. specifications, standards and codes given below are made a 

part  of  this  specification.  All  standards,  specifications,  code  of  practices referred  to  herein  shall  be  the  latest  edition  including  all  applicable amendments, revisions and additional publications. 

   2.2  List of Indian Standards  

No.  I..S. No.  I.S. Particulars 1  I.S. 1200 (Part‐IX)  Method  of measurement  of  building  and  civil 

engineering works, (Roof covering) 2  I.S. 2645  Specification  for  integral  cement  water 

proofing compound  3.0  GENERAL:  3.1  The  work  of  water  proofing  treatment  shall  be  executed  through  a 

specialized  agency  having  sufficient  experience  in  the  field  of  all  types  of cement based water proofing works. 

 3.2  The contractor shall submit the detailed specifications and the agency to be 

appointed  for water proofing works  for approval of  the Engineer  Incharge before commencement of work. 

 3.3  The contractor shall provide at site a competent supervisor during execution 

of waterproofing works over areas and  shall ensure  the adequacies of  the 

Page 139: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 128 of 139

works carried out to be in line with the drawings and specifications.    3.2 The most effective method of waterproofing  is   not to allow water to pond 

over  the  surface.  Adequate  care  shall  be  exercised  during  the  laying  of cement  screed  to  ensure  that  waterproofing  compound  is  added  in  the measures required and that proper slope is provided for drainage of water. 

 3.3 Construction  joints are the most vulnerable from seepage point of view.    It 

shall  be  ensured  that  all  the  construction  joints  in  the  RCC  slab  ,  beams, gutters etc. shall be injection grouted prior to the laying of screed concrete. All efforts shall be put to see that the screed concrete is laid in one go as far as  possible  without  joints.  In  unavoidable  circumstances,  utmost  care regarding treatment of joints prior to resumption of concreting from the left over joints shall be exercised. The joints shall be chipped off loose materials and coated with chemicals like “NITOBOND” or equivalent to ensure proper adhesion between the joints.   

 3.6  He  shall  also bring  to  the notice of  the Engineer‐In‐charge,  the protective 

measures required for the protection of the water proofing for subsequent operations over it. 

 3.7    The performance guarantee bond  for all  the water proofing works  carried 

out by the water proofing agency will be required to be furnished by them through the contractors. 

 3.8  In addition to the above, the main civil contractor also shall have to submit 

the performance guarantee bond in the prescribed form for water proofing guarantee as specified in appendix ‘B’. 

 4.0        APP MODIFIED BITUMINOUS MEMBRANES WATER PROOFING TREATMENT 

OVER THE TERRACE:  4.1  Water proofing treatment shall be as specified in the schedule of items.   4.2  The concrete surfaces should be cleaned of all unwanted materials and the 

same shall be made rough.   4.3  The   construction    joints   or   cracks,    if any,   should   be    inspected   and  if 

found  necessary  ,“Damp  proof”  compound  with  cement  solution  as  per manufacturer’s specifications shall be  injected to seal off the cracks as well as any honey‐combs and cavities in the slab. 

 4.4  The  same  shall  then  be  subjected  to  terrace  method  of  water  proofing 

treatment as per manufacturer’s specifications. 

Page 140: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 129 of 139

 4.5  The  cleaned  terrace  shall  be  watered  properly  and  cement  screed  with 

water  proofing  compound  shall  be  laid  to  provide  necessary  gradient  for easy flow of rain water. 

 4.6 Over  the  surface,  APP  modified  bituminous  polyester  reinforced 

waterproofing membrane manufactured from a rich mixture of bitumen and selected  polymers  blended  together  to  obtain  excellent  heat  resistance, flexibility &  UV  resistance  shall  be  used. Modified  bitumen  then  shall  be coated  onto  a  dimensionally  stable  carrier  to  obtain  excellent  tensile strength,  tear  and  puncture  resistance.  The  membrane  should  be lightweight, UV resistant and self protective, weather resistant and  flexible enough to resist the movements  in cracks. The thickness shall be minimum 4mm and granule surfaced. The reinforcement within shall be of atleast 140 gms/sqm polyester mesh. 

 4.7                Surface Preparation                        Concrete, mortar surfaces must be clean,  free  from grease, oil and  loosely 

adhering  particles.  Steel  and  iron  surfaces must  be  free  from  scale,  rust, grease and oil. All surfaces must be as true as possible. 

 4.8 Apply bituminous primer to a clean, smooth and dry surface by brush, roller 

or  spray.  Unroll  and  align  and  re‐roll  correctly  before  torching.  Overlaps should be minimum 100mm. Use gas burner to heat the substrate and the thermo  fusible  film on  the underside on  lower  face of membranes. When the thermo fusible film melts after torching, the membrane is ready to stick.  Roll  forward and press  firmly against  the substrate  to bond. Heat both the overlaps  and use  the  round  tipped  trowel heating  the  same  to  smoothen and press  into seam. All angles and abutments should be sealed with extra care  to  ensure  full  bondage.  The  edges  should  be  sealed  well  into  the grooves. 

 4.9 Membrane will be applied  first  to  the rain water channels and  then  to  the 

sloped concrete  roof. The membrane  shall be  installed vertically  from  rain water  channel  towards  the  ridge of  the  roof.  End  joints  shall  be  laid  in  a scattered manner  so  that multiple overlapping of membranes at  the same location is avoided. 

 4.10  This  treatment  shall  be  continued  along  the  inner  sides  of  parapets  or 

adjoining walls  up  to  a  height  of  300 mm  to  375 mm  till  the  horizontal projection (gundi).   

 4.11  The construction joints shall be taken at ridges and should be made properly 

Page 141: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 130 of 139

watertight and monolithic.  4.12  Care  shall be  taken  to  finish  the  rain water  inlets etc. properly  so  that no 

leakage occurs.  4.13  The  terrace  shall  be  tested  for  leak  tightness  after  the  treatment  is 

completed and any defects shall be made good.   5.0  CEMENT  BASED  WATER  PROOFING  TREATMENT  TO  OVERHEAD  WATER 

TANK:  5.1               The  tank  is  to  be  treated  from  inside  as  per  ‘Injection’  and  ‘Surface’   

methods which includes the plaster finished smooth with trowel.  

5.2  Injection to be given to the floor and walls as and when found necessary and thereafter a  layer of  ‘Cetroof’ water proofing will be  laid on  the  floor and will be conformed along the side and partition walls to their full height. 

 5.3  The thickness of the treatment on the floor will be about 50 mm and on the 

wall about 20 mm.  5.4  After the treatment is completed the tank shall be filled with water and the 

water retained for 24 hours.  If any  leakage  is observed the contractor shall rectify the defects and the tank shall be retested for leak tightness. 

 6.0  CEMENT BASED WATER PROOFING TREATMENT TO THE BASEMENT:  6.1  The water proofing treatment for under ground trenches, walls, raft, lift pit, 

water tank etc. shall be done of basement type (Box Type).  6.2  The PCC surface below raft shall be thoroughly cleaned and a layer of water 

proofing treatment about 75 mm thick shall be laid.      The RCC raft shall then be cast over these surfaces. The side walls shall be 

cast  afterwards  and  the water  proofing  treatment  shall  be  continued  on these walls up to the required heights. 

 6.4  The thickness of treatment for vertical surfaces shall be 40 mm to 50 mm.  7.0  WATER PROOFING TREATMENT IN SUNKEN FLOORS OF TOILET AND BATH 

ROOM:  7.1  Water proofing treatment shall be as specified in the schedule of items over 

Page 142: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 131 of 139

sunken floors of toilets, bath rooms and washing places.  7.2  The RCC slab and other surfaces should be cleaned of all  foreign materials 

such as  loose mortar,  concrete,  local humps, bare metal pieces and other unwanted material. 

 7.3  The surface  to be  treated shall be hacked  to remove  loose mortar scalings 

and roughened. The surface should then be rubbed vigorously to remove all dust with the help of wire brush / brooms. 

 7.4  The  surface  thus prepared  shall  then be washed with  clean potable water 

before laying the water proofing treatment.  7.5  The cracks, honey combing  if any should be  located and should be treated 

with  injection,  grouting etc.  to  seal off  the  cracks,  air holes, honey  comb, etc. to the entire satisfaction of the Engineer‐In‐charge. 

 7.3 The  prepared  RCC  surface  shall  be  then  watered  again  thoroughly  and 

cement slurry shall be spread over the surface along with water proofing as per manufacturer’s specifications. 

  

ALTERNATE ‐ I  7.4             A  two  component  acrylic  polymer  based  flexible  cementitious  coating  of 

heavy duty flexible coating system with excellent waterproofing and shall be used for waterproofing sunken slabs. The product shall be similar to Dr. FIXIT Pidifin 2k or equivalent. 

 7.4.1                    METHODOLOGY :  7.4.1.1 Surfaces  to be applied upon, must be  clean, dry,  free  form dirt and  loose 

material. 7.4.1.2 Over  the  R.C.C  base  slab,  apply  polymer modified  cementitious  seamless 

waterproofing  membrane  at  a  rate  of  2‐2.5  square  meter  per  kg  to  all required areas,  at a thickness of 500 – 600 microns and allow to dry for 4 ‐6 hours.  

7.4.1.3 Apply  second  coat  in  the  opposite  direction  at  the  same  rate.  After application of second coat  it gives the total thickness shall be 1 to 1.2 mm. The treatment is left as it is for 72 hours for air cure.  

7.4.1.4 The waterproofing shall be carried at  least 300 mm‐on vertical surfaces, or at least 150mm above the floor finish level.  

7.4.1.5 After  3  days  of  air  curing,  a  layer  of  10mm  Cement/Sand  (Ratio  1:4) protective screed, using  Integral Waterproofing Compound @ 200ml/50 kg 

Page 143: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 132 of 139

bag of cement, shall be applied on top of the membrane. Care shall be taken whilst  laying  the protective screed so as not  to damage  the waterproofing membrane below.    

 ALTERNATE –II  

7.5  25 mm thick bedding of cement mortar 1:4 with water proofing compound @ 2% of weight of cement shall be  laid on the floor  in specialized manner. 18 mm  thick  cement  plaster  of  cement mortar  1:4  with  water  proofing compound © 2% by weight of cement shall then be applied over the vertical surfaces. 

     Finishing & Curing  7.6  The water proofing plaster so  laid should be allowed to set  for atleast one 

week and kept under water.  7.7  Any seepage/ dampness noticed on the under side of the ceiling should be 

treated again as detailed above,  7.8          Cinder fill as specified  in the schedule of  items shall be  laid over the water 

proof plaster to fill up the space/ voids of sunken floor areas.  7.9  The treatment shall be cured with clean water for a minimum period of 10 

days.  8.0  MODE OF MEASUREMENTS:  8.1  The measurement shall be for the actual area covered by the treatment.  8.2  The  length  and  breadth  shall  be  measured  along  the  walls  before  the 

treatment is laid.  8.3  The  height  of  cinder  fill  shall  be  considered  for  measurement  after 

deduction of  the average  thickness of  the  treatment  laid horizontally over the sunken slab and quantity of cinder fill shall be measured in cum. 

 8.4  The areas of all openings, cutouts etc. shall be deducted. 

      

Page 144: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 133 of 139

 C: 19 HEAT RESISTANT CONCRETE. 

 1)   HEAT RESISTING CONCRETE (HRC) 

 This Specification  lays down requirements of Heat Resisting Concrete of Mark M30 to withstand Temperature upto 700 Deg. C. This concrete  is required  to withstand high  temperature, such as  in  foundations  for coke ovens batteries,  furnaces,  flues, stoves, reheating furnaces, soaking pits etc. 

 2)   MATERIALS. 

 2.1 CEMENT: Cement to be used shall be Portland Blast Furnace Slag Cement confirming 

to I.S.455‐1989 with Slag content not less than 50%.  

2.2 AGGREGATES:  Course  Aggregates  shall  be  20mm  and  down  graded  Basalt Aggregates  containing  52  to  45%  Silica  and  free  from  quartz  and  shall  be  freshly quarried and free from dust and foreign materials. 

             GRAIN COMPOSITION OF BASALT COARSE AGGREGATE 

 MESH OF SIEVE (mm)  TOTAL RESIDUE IN % BY WEIGHT 

  20   0‐5   10  30‐60 4.75  100  

 

2.3  BASALT  SAND:  This  shall be  from  Fresh  and Good Quality Basalt Rock,  The Grain composition shall be as follows: 

 BASALT SAND 

MESH OF SIEVE (mm)  TOTAL RESIDUE IN % BY WEIGHT 4.75   0‐15 1.25  20‐55 0.14  80‐100 

 3)  MIX DESIGN. 

3.1 The approximate quantities of materials  required per Cubic Metre of Concrete to withstand a Temperature of 700 Deg. C are as follows: 

           BALAST FURNACE SLAG CEMENT  500 Kg. 

BASALT SAND  700 Kg. 

Page 145: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 134 of 139

BASALT COARSE GRADED AGGREGATES (20MM Down) 

1100 Kg. 

WATER  210 Ltrs. 

For a Guideline of how to adjust percentage Aggregates for Concrete Mix Design refer IS Cement,10262, Reaffirmed in 1999.  

 3.2 The Final Composition of HRC,  Grading of Aggregates, Cement Content, Water‐

Cement Ratio etc., shall be ascertained by means of a series of preliminary tests.  3.3 The following Test shall be carried out during Mix Design.  

A) TESTING:  Tests on HRC samples shall be conducted to find:  

• Residual compressive strength after heating. • Compressive Strength of concrete specimens cured under normal conditions. • Number of 10Cm Cubes specimens to be prepared and tested are as follows: 

 Tests for Compression at Natural Humidity after 7 days Tests for Compression after drying at 105 C after 7 days Test for   Compression after drying at 105 C and with subsequent  Heating   upto 700  C after 7 days Tests for Compression under Normal conditions after 28 days Control   Specimens  

B)   PREPARATION OF CONCRETE SPECIMENS.  

About  15  Nos.  of  10cm  Cubes  Specimens  to  be  prepared  for  testing.  Compaction  of  Concrete Mix  in  the moulds  shall  be made  on  a  vibrating platform, laying and vibrating of Concrete Mix  shall b done not later than 25 minutes after mixing.  Duration of vibration shall not exceed 1.5 minutes (90 Sec).    Curing  should  start  as  soon  as  the  surface  is  firm.    Under  normal  atmospheric  temperatures,  this will occur within 4  to 10 hour after mixing the concrete.   The Moulds with Concrete should then be moist for 48 hrs., covered with moist cloth by continuous spraying with water, thereafter the specimens  shall  be  taken  from moulds  and  kept  in  a  chamber with  90% humidity  at  a  temperature of  20 Deg. C  +  2 Deg.  C prior  to  testing.    The Specimens  shall  be  taken  out  from  the  chamber  not  earlier  than  1  hour before testing. 

     

Page 146: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 135 of 139

C)   TEST  FOR  COMPRESSIVE  STRENGTH  OF  SPECIMENS  CURED  UNDER NORMAL CONDITIONS. 

 3 Nos. of 10cm Cubes Specimens  shall be  tested  for compressive  strength after 7 days, and 3 Nos. Specimens shall be  tested for compressive strength after 28 days.   

 The  test  load shall be  increased continuously at  the  rate of 2  to 3 Kg/sqm per second till failure. 

 The compressive  strength  shall be  taken as  the average of    two maximum test  results   of  the  three  specimens.    The  compressive  strength of  10  cm Cubes shall be multiplied by a factor 0.9 to get the equivalent strength of 15 cm Cubes.  Mark 30 HRC shall have 28 days compressive strength of 30 N/sq mm and 7 days strength shall be 20N/sq.mm on 15cm Cubes.   

 D)   TEST FOR RESIDUAL COMPRESSIVE STRENGTH AFTER HEATING.  

Six Nos. of 10cm Cube Specimens cured under normal conditions (at 20 Deg. C + 2 Deg. C and 90% humidity) during 7 days shall be dried in an oven for 32 hrs., gradually raising the temperature up to 105 Deg. C as follows: 

 TIME IN HOURS  TEMPERATURE IN DEG. C 

0  25 1  75 2  100 30  100 32  105 

  Thereafter,  3  Specimens,  dried  as  above  shall  be  cooled  at  25  Deg.  C 

gradually  and  tested  for  compressive  strength  as  before.    The  equivalent compressive strength for 15 cm shall be corrected as explained above. Compressive strength of dried specimens (105 Deg. C) shall be the same as that of the specimens cured under normal conditions. 

  Other three specimens already dried by heating upto 105 Deg. C during 32 

hrs., shall be further heated to 700 De. C in a muffle oven as follows:    

TIME IN HOURS  TEMPERATURE IN DEG.C 0  105 1  150 2  300 

Page 147: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 136 of 139

3  450 4  550 5  650 6  700 7  700 8  700 

 This specimens shall then be cooled to 25 Deg.C and air cured for 7 days and tested for  compressive  strength  residual  compressive  strength  of  this  specimen  after normally  cured  specimens minimum    permissible  residual  strength  after  heating upton 700 Deg.C is 40%. 

 4)   ROUTINE TESTS. 

 4.1  12  samples of Concrete  from works  shall be  taken  for  test one  for every 50 Cum 

Pour of Concrete or part thereof and tests to be carried out for 7 days and 28 days compressive strength at normal conditions. 

 5)   MANUFACTURE, PLACEMENT AND CURING. 

 5.1 In the Manufacture of Heat Resistant Concrete difficulties may arise in workability of 

the mix because of porus aggregates absorbing water, this shall be considered in the mix design  as well,  in order  to obviate  this,  the  aggregates  shall be  sprayed with water  and  the  surplus water  then  allowed  to  run  off.    The  aggregates  should  be allowed to dry in air and used the following day. 

 5.2 Mixing period of Heat Resistant Concrete are longer, in Case where   it is found that 

the mix  is very  stiff and excessive water  is being absorbed by  the aggregate.   The coarser factions of the aggregate may be weighed and fed  into the mixer, together with one half of  the water.   These constituents are mixed  for 5 minutes  to ensure that    the  surfaces  of  the  aggregate  particles  are  fully wetted,  correct weights  of cement  and  fine  aggregates  together  with  remaining water  are  then  added  and thoroughly mixed  for  10 minutes,  taking  care  to  see  that  lumps  are  not  formed.  Water may also be added in stages.   

5.3 Placement   and compaction should be delayed until the aggregates are completely soaked.  This standing time should be within the setting time and in any case should not be more than 1 hour from the start of mixing process.  This will ensure that the concrete reaches higher strengths. 

 5.4 Concrete  shall  be  laid  in  layers  of  200  MM  and  well  compacted  using  needle 

vibrators at an approximate  rate of 1.5 minutes per Sqm.   The vibrator  should be 

Page 148: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 137 of 139

withdrawn slowly.  The stiffness of  the mix is correct for a particular vibrator if the concrete closes up when the vibrator is withdrawn slowly. 

 5.5 Wet curing of heat Resistant Concrete shall commence early depending on the Heat 

of Hydration.    Fresh Concrete  should be  covered  to prevent  loss of moisture  and avoid  surface  cracks,  curing  shall  be  continued  for  a  minimum  of  7  days  side shuttering  can  be  removed  early  to  facilitate  greater wetting  of  concrete  curing compounds may also be used to retain and prevent loss of water. 

 6)  DRYING AND COMMISSIONING: 

6.1 Heat Resistant Concrete should not be loaded until required strength of concrete is reached as determined by cube tests. 

 6.2  The drying and  raising of  temperature  to operating    temperature  should be done 

gradually and in stages as follows:  

Raise temperature to 150 Deg C at a rate of 5 to 10 Deg C/Hour.   Holding time at 150 Deg. C  : 7 days. 

  Raise temperature from 150 Deg. C to operating temperature at a rate of 25 

to 50 Deg. C/ Hour.  

Page 149: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 138 of 139

C:20  SITE LEVELLING AND LOAD BEARING FILLS.  1)  CUTTING AND FILLING FOR SITE LEVELING.  

Excavation and Filling Operations for Site Leveling shall be so planned and executed, that transportation and rehandling are minimized.   The sides of excavation and fills shall  be  maintained  in  stable  condition  by  adequate  batters,  stepping  and dewatering.    Materials  not  desirable  shall  be  disposed  off  in  area  indicated  by Engineer.   When  it  is  required  to blend  the material,  it  shall be done by  selective excavation and  filling operation.   Wells, Ponds, Cesspools and Water  logged areas shall be  emptied of water  and deslushed before  filling operation.    Filling  shall be done  in horizontal  layers not exceeding 500/300mm  in thickness as specified or as directed by  the  Engineer.   All  clods  shall be broken before placing  the  fill.    Earth moving  equipment  shall  be  allowed  to  ply  over  the  fill  to  permit  compaction.  Adequate allowance  shall be made  for  subsidence of  fill material.    Levels  shall be taken  and excess or shortfall shall be made good by appropriate cutting or filling. 

 2)           LOAD BEARING FILLS.  

Load Bearing fills include embankments for roads and railways and such other earth fills above ground  levels provided  for protection of  fuel oil  tanks, pads  for storage tanks,    drain,  bunds    and  the  like.    Fill materials  shall  either  be  selected  earth obtained  from  excavations  for  site  leveling,  trenches  and  foundations  or  from selected borrow areas as may be required.  Soils selected for filling in embankments shall  be  of  uniform  quality  and    free  from  boulders,  organic materials  and  other objectionable matter.   Soils having high silt and clay content and having  laboratory maximum dry density less than 1.44 gms per c.c. shall not be used for Load Bearing Fills.   For fills greater than 3m  in height soils shall have  laboratory density   not  less than 1.52 gms per c.c.  Soils for top 500 mm of fills for roads and railways shall have laboratory  density  not  less  than  1.65  gms  per  c.c.  and  shall    not  have  marked swelling and shrinkage properties. 

 3)  Foundation  preparation  for  embankments  shall  be  done  as  prescribed  under  site 

clearance.  The founding strata shall be compacted as much as possible by rolling or tamping  before  placement  of  fill material.  The water  content  of  founding  strata should be same as that specified for embankment fill.  Any  pockets of loose material or depressions left in founding strata as a result of clearing operation shall be filled and compacted with the same material as the surrounding  founding strata.   When an embankment  is to be placed on steep sloping ground the surface of the ground shall be trenched in steps or trenched or broken up in such a manner that the new materials bonds well with the founding strata. 

 4)  Fill material shall not be placed until  foundation has been  inspected and approved 

by Engineer.  Material shall be placed in even, continuous, horizontal layers over full 

Page 150: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 139 of 139

width of embankment  in well  compacted  layers not exceeding 200 mm  thickness.  Each layer shall be compacted by means of smooth rubber tyred rollers, sheep‐foot rollers,  tractors,  tampers or other mechanical means as may be  found suitable  for the  location.   Before  rolling,  the water  content  shall be checked and corrected by sprinkling with water or adding dry material or aeration as may be  required. This shall be  followed by mixing and  the  layer  left  for soaking before compaction.   The water  content  shall  be  within  plus  or  minus  2%  of  Standard  Proctor  Optimum.  Density  of  compacted  layers  shall  be  determined  by  sand  replacement method.  Average compacted density shall be at  least 95% of Standard Proctor Density.   The number of tests to be conducted for determination of moisture content and density shall be as prescribed by the Engineer.  Side slopes of embankments shall be formed along with the main embankment.  No side dumping shall be done for the formation of  slopes.   When  required  the width of each  layer  shall be  constructed  slightly  in excess of  required width and  slopes  trimmed  to  remove  loose edge materials and completed to lines shown in drawings or as directed by the Engineer.  Sub grades for road works shall be thoroughly wetted sufficiently in advance of placing of any base course and it shall be ensured that it is firm and moist for at least 50 mm below the surface.    Should  the  sub  grade  for  any  reason be  loose or have density  less  than required,  it  shall be  recompacted and  refinished. Excessive  loss of moisture  in  the sub  grade  shall  be  prevented  by  sprinkling  and/or  scaling.    No  traffic  or  hauling equipment shall be permitted to ply on finished sub grade and any damage caused to such portion shall be made good by the Contractor at his own cost.  

Page 151: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 1 of 1

Chapter‐ I 

SECTION ‐III   METHOD OF MEASUREMENT  1.0      GENERAL  1.1  The works executed shall be measured in stages. Approved billing schedule 

for civil works shall form the basis of identification of stages of construction.   1.2  The tenderer shall submit relevant backup calculations  for the quantum of 

work  considered  in  each  of  the  stages  considered  for  approval  of  billing schedule. 

 1.3  As  a  guideline  the  stages  of  work  shall  generally  be  considered  as 

Foundation, Lintel level, Floor slab/ roof slab level. Sanitary & water supply, Finishing, Site clearance & handing over. For other  items of work,  such as roads, drains, stages shall be considered as percentage of the entire work. 

 1.4  In case of requirement of detailed measurements to be taken, the method 

of measurement of work shall be in accordance with IS:  1200 (Part 1 to 28) – 1971 to 1993 / SP:27. 

 1.5  The measurement considered shall be purely for the purpose of clearance of 

stage payments and shall not in any way indicate change of scope. No claims shall be entertained on this account.  

    

 

Page 152: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 1 of 4

Chapter‐I  

SECTION – IV NORMS OF CEMENT CONSUMPTION  1.0    GENERAL 

 1.1    For  calculating  the  requirements  of  cement  in  various  items  of work  the 

following standards shall be adopted. Over the above theoretical quantity of cement, additional allowance upto plus or minus 3% shall also be allowed as certified by the Consultant. 

 1.2    For items not covered in this standard, CPWD standards shall be followed or 

calculated as per uses/requirement  in absence of standard norms. Cement required for enabling work and cement required for testing purposes will be taken  into  account  for  consumption  purpose.  However,  in  no  case  such quantity  should  exceed  5%  of  the  total  cement  used  in  the  work  or  as certified by the Consultant based on actual observation whichever is less. 

  2.0                    MASONRY WORK 

   

 Sl.No. 

 Description of Item 

   Cement requirement 

1.  Random Rubble Masonry in   CM (1:4)  1.255 quintals per cum 

2.  Random Rubble Masonry in   CM (1:6)  0.825 quintals per cum 

3.  Coursed Rubble Masonry in  CM (1:5)  0.98 quintals per cum 

4.  Brick work in  CM (1:5)  0.775 quintals per cum of BW 

5.  Brick work in  CM (1:6)  0.625 quintals per cum of BW 

6.  Half brick work in4  CM (1:3)  1.43 quintals per 10 sqm of area 

7.  Half brick work in  CM (1:4)  1.06 quintals per 10 sqm of area 

 3.0         PLAIN/REINFORCED CONCRETE  Sl.No. 

 Description of Item 

   Cement requirement 

1.  RCC/PCC  of  nominal  mix  (1:4:8) complete  (excluding  finishing  with CP) 

1.70  quintals per cum of concrete   

Page 153: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 2 of 4

2.  RCC/PCC  of  nominal  mix  (1:3:6) complete  (excluding  finishing  with CP) 

2.20              quintals per cum of concrete 

3.  RCC/PCC of nominal mix  (1:2:4)  complete  (excluding  finishing with CP) 

3.20  quintals per cum of concrete 

4.  RCC/PCC  of  nominal  mix  (1:1.5:3) complete  (excluding  finishing  with CP) 

4.00  quintals per cum of concrete 

 4.0         CONTROLLED CONCRETE – PLAIN AND REINFORCED  S.No. 

 Description of Item 

   Cement requirement 

        1. 

 Concrete grade 

 (i) M‐7.5B (ii)M‐10B 

 2. 

 Concrete grade 

 (i)  M‐15C (ii) M‐15D 

 3. 

 Concrete grade 

 (i)  M‐20C (ii) M‐20D 

      To be mutually agreed based on mix  design  to  be  prepared  by Tenderer  &  approved  by  the Consultant plus wastage  and  all incidentals as decided. 

 4. 

 Concrete grade 

 (i)  M‐25C (ii) M‐25D 

 5. 

 Concrete grade 

 (i)   M‐30C (ii)  M‐30D 

 To be mutually agreed based on mix  design  to  be  prepared  by Tenderer  and  approved  by  the Consultant plus wastage  and  all incidentals as decided. 

 5.0  FINISHING   S.No. 

  Description of Item 

    Cement requirement 

 1. 

 6 mm thick C.P. 1:4 

 0.280 quintal per 

 10 sqm area 

Page 154: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 3 of 4

 2. 

 12 mm thick C.P. 1:4 

 0.550 quintal per 

 10 sqm area 

 3. 

 12 mm thick C.P. 1:5 

 0.450 quintal per 

 10 sqm area 

 4. 

 15 mm thick C.P. 1:4 

 0.650 quintal per 

 10 sqm area 

 5. 

 15 mm thick C.P. 1:6 

 0.440 quintal per 

 10 sqm area 

 6.0      FLOORING  S.No. 

 Description of Item 

   Cement requirement 

 1. 

 40mm  thick  IPS  cement  concrete flooring (1:2:4) with 20mm and down stone  chips  finished  with  a  floating coat of neat cement 

   1.500 quintal per 

   10 sqm area 

 2. 

 40mm  thick  (IPS)  flooring with  base coat  30mm  thick  (1:2:4)  using  stone chips 10mm nominal  size and 10mm topping coat 1:1  (1 cement  : 1 stone chips  3  to  6mm  size) with  a  floating coat of neat cement 

     2.320 quintal per 

     10 sqm area 

 3. 

 Extra for each additional thickness of 5 mm  granolithic  layer  of  (1:2:4)  for flooring 

  0.016 quintal per  

  10 sqm area 

 7.0        MISCELLANEOUS  S.No. 

 Description of Item  

   Cement requirement 

 1. 

 Grouting with 

 

  

 CM (1:2) 

 7.18 quintal per cum  

Page 155: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 4 of 4

   CM (1:3) 

 5.40 quintal per cum  

 2. 

 Fixing  steel  windows  with  (1:2:4) concrete blocks 

  0.40 quintal per  

  10 sqm of area 

 3. 

 Cement‐sand mortar :‐  

   

 a) 

 (1:1) (1 cement : 1 sand) 

 10.2 quintal per cum  

 b) 

 (1:2) (1 cement : 2 sand) 

 6.8 quintal per cum  

 c) 

 (1:3) (1 cement : 3 sand) 

 5.1 quintal per cum  

 d) 

 (1:4) (1 cement : 4 sand) 

 3.8 quintal per cum  

 e) 

 (1:5) (1 cement : 5 sand) 

 3.1 quintal per cum  

 f) 

  (1:6) (1 cement : 6 sand) 

 2.5 quintal per cum  

      

 

Page 156: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 1 of 6

Chapter‐I  

SECTION – V DIMENSONAL TOLERANCE  1.0    GENERAL  1.1    The  materials  used  in  construction  shall,  besides  conforming  to  the 

specifications  and  standards mentioned, be  the best of  the  existing  kinds obtainable. Where  a  particular  ‘Brand’  or  ‘Make’  of material  is  specified such ‘Brand’ or ‘Make’ of material alone shall be used. 

 1.2    A  high  standard  of  workmanship  and  accuracy  shall  be  achieved  in  all 

sections  and  parts  of  the work.  The workmanship  shall  be  in  accordance with the latest and the best civil engineering practice. 

 1.3    The Tenderer shall ensure that all sections of the work are carried out with 

utmost care to achieve the dimensions shown in drawings or specifications. In  the  absence  of  such  specific  mention  in  drawings  the  following dimensional deviations may be  tolerated, provided  they do not  impair  the appearance  or  render  the  particular  section  of work  unacceptable  to  the purpose for which  it  is  intended. Tolerance for materials and workmanship not covered in this part as mentioned hereinafter will be in accordance with the relevant IS code. 

 Description    Permissible tolerance Building bricks in length, width & height  : As per IS:1077 Laterite stone, in length, width & height  : ± 5 mm Natural building stones     

Length, width : ± 5 mm Height : ± 3 mm 

Length & width : + 5 mm & ‐10 mm 

a) For stones required in  ashlar masonry   

b)  For  stones  required other  than  in  ashlar masonry 

Height : ± 5 mm 

Length : ± 1% of standard length 

Concrete  &  Reinforced concret pipes 

 Internal dia upto 300mm  : + 3 mm, ‐ 1.5 m Length of fittings : ± 10 mm Length of pipes : ± 20 mm 

Thickness : ‐ 1 mm Internal dia of socket : ± 3 mm 

Cast  iron  spigot  &  socket pipes and fittings 

Depth of socket : ± 10 mm 

Page 157: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 2 of 6

External dia upto 75mm : ± 3 mm 100 mm : ± 3.5 mm 150 mm : ± 4 mm 

Upto 75 cm dia  length    ± 10 mm Upto 90 cm dia  length    ± 15 mm In thickness of barrel & socket not exceeding 450 mm 

  ± 2 mm 

Stone ware pipes  

In thickness of berrel and socket between 50 to 600 mm 

  ± 3 mm 

Length of all four sides    ± 2.5 % Glazed tiles Individual dimensions and thickness 

  ± 2.5 % 

Metal  Doors,  Windows  & Ventilators 

In overall dimensions    ± 1.5 mm 

Wooden Doors Windows & Ventilators 

In overall dimensions     ± 3 mm 

  Width    ± 3 mm  

All  components  of shutter  except glazing bars 

Thickness    ± 1 mm 

  Glazing bars  Width & thickness    ± 1 mm 

1 Mild steel tubes, tubulars and other wrought steel fittings   Butt welded light tubes    + not limited , ‐ 8 %   Medium and heavy tubes    + not limited, ‐ 10 %  

Thickness 

Seamless tubes    + not limited, ‐ 12.5 %   Single tube (irrespective 

of the quality)   + 10 %, ‐ 8 % 

  For quantity of less than 150 m of one size  

  + 10 %, ‐ 8 % 

 

Weight 

For quantity of 150 m and over of one size 

  + 4 %, ‐ 4% 

Earth work   Finished level of site leveling in hard rock    ± 50 mm   Finished level of site leveling except for hard 

rock   ± 100 mm 

  Level of pits, trenches and foundations    ± 50 mm Concrete & reinforced concrete   1.01.01   Plan dimensions   + 50 mm, ‐ 12 mm 

Page 158: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 3 of 6

Eccentricity   0.2 times the dimension of footing in the direction limited to 50 mm 

Footings 

Thickness   ± 0.05 times the specified thickness 

Deviation of plane and lines of their intersection from vertical or inclination along full height  

  ± 20 mm 

Deviation of horizontal plane from horizontal line 

   

For 1 m of plane in any direction 

  ± 5 mm 

For the whole plane    ± 20 mm Sizes of cross section    ± 8 mm Surface of inserts to support loads 

  ± 5 mm 

  Foundations 

Length of elements    ±  20 mm Top level of bolts    + 20 mm Top level of foundation before grouting 

  ‐ 20 mm 

Axes of anchor bolts in plan 

  ± 5 mm 

Axis of foundation in either direction 

  ± 10 mm 

Deviation in vertical line along height 

  ± 5 mm 

Sizes of pits in plan    ± 20 mm Sizes of steps in plan    ‐ 20 mm Levels of steps, benches and pits 

  ‐ 20 mm 

Axes of inserts in plan    ± 10 mm 2 Basic 

dimensions in plan 

  ± 10 mm 

  Equipment foundations 

Deviation of horizontal plane from horizontal line  

   

Page 159: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 4 of 6

For 1 m of plane in any direction  

  ± 5 mm 

For whole plane    ± 20 mm Local deviation of top surface when checked with a 2 m long straight edge 

  ± 8 mm 

Surface when checked with a 2 m long straight edge 

  ± 8 mm 

Sizes of cross section    + 8 mm, ‐ 0 mm Length of elements    ± 20 mm Deviation from horizontal plane for whole building 

  ± 10 mm 

verticality    1 in 1000 of height For columns supporting floor beams 

  ± 10 mm 

  2.01.01  Buildings 

For frame columns linked with crane girders & beams 

  ± 10 mm 

Length    ± 20 mm Flatness of surface when checked with a 2 m long straight edge 

  ± 8 mm 

Level of top surface to support assembled elements 

  ± 5 mm 

Deviation in planes and lines of intersection from vertical 

  ± 15 mm 

  2.01.02  Reinforced concrete walls 

Size of cross section    ± 8 mm Length of bar upto 75 cm long (other that straight bars) 

  + 3 mm, ‐ 5 mm 

75 to 150 cm long    + 5 mm, ‐ 10 mm 150 to 250 cm long    + 6 mm, ‐15 mm 250 cm long and above    + 7 mm, ‐25 mm Straight bars, all lengths    ± 25 mm 

  2.01.03  Placement of reinforcement 

Spacing bars    + 5 mm   2.01.04   Shift in location in plan    ± 5 mm 

Page 160: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 5 of 6

Same when bolts are located outside of structural columns 

  + 10 mm 

Top level    ± 20 mm 

Anchor bolts 

Threaded length    + 30 mm Masonry work     For walls    For pillers   Width  ± 10 mm    ± 10 mm   Shift in axes   ± 10 mm       Deviation from 

horizontal line for every 10 m length 

± 15 mm     

  Flatness of surface when checked with a 2 m long straight edge 

± 10 mm    ± 5 mm 

  Deviation in lines separating storyes 

± 15 mm    ± 15 mm 

  Deviation of surface from vertical and at angles and corners for 1 storey 

±  10 mm    ± 10 mm 

  For whole building  ± 30 mm    ± 30 mm   Dimensions of 

openings for doors, windows, etc. 

+ 15 mm, ‐ 0mm     

Flooring, Skirting, Dado and Plastering     In situ flooring    4 mm     Concrete tile and mosaic 

in any 3 m length   3 mm 

    In large open area    15 mm   Wall tiling  surface should not vary 

from general plane by more than  

  1 in 200 

  In any 2 m length    1.5 mm  

Marble and such superior work   In any row    3 mm 

  Flatness when checked with a 2 m long straight edge 

  3 mm 

 

Plastered surfaces 

Vertical surfaces upto 1 storey 

  5 mm 

Page 161: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 6 of 6

  Over full height    10 mm Metallic inserts   On assembled 

components Length & width    ± 3 mm 

Road work 

  The  levels  of  subgrade  and  different  pavement  courses  should  not  vary from those calculated with reference to the longitudinal and cross sections of the road as shown on the drawing beyond the tolerance given below: 

    Subgrade    ± 25 mm     Sub base    + 20 mm     Base    ± 15 mm     Wearing coat    ± 6 mm 

                      

 

Page 162: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 1 of 4

Chapter‐I  

SECTION – VI: SAFETY REQUIREMNTS FOR CONSTRUCTION WORKS  1.0    GENERAL  1.1    This specification deals with the subject matter of safety and protection to 

be observed  in  the Civil Construction. This shall be  followed along with all related  statutory  requirements/obligation  including  Government  byelaws, codes, ordinance of  local or central authorities related  to  the construction work. 

 1.2    In case of complicated work  like deep excavation,  intricate  shuttering and 

formwork,  excavation  in  loose  soil  and  below  water  table,  stacking  of excavated  earth  etc., work  plan with  necessary  drawings  and  documents have to be prepared by the Tenderer and got approved by the Consultant. 

 1.3    Necessary reference shall be made to the following  Indian Standard Codes 

on safety requirements for various type of work:  

2.0    INDIAN STANDARD  

IS:4130 – 1991    Demolition of Buildings IS:3764 – 1992    Excavation Work IS:4014 – (P‐II) – 1967  Scaffolding, Steel Tubular IS:3696 – (P‐I & II)  Scaffolds and Ladders 1987 to 1991   IS:4138 – 1977    Working in Compressed Air IS:7293 – 1974    Working with Construction Machinery IS:8989 – 1978    Erection of Concrete Framed Structures  

3.0    EXCAVATIONS  3.1    No  excavation  or  earthwork  below  the  foundation  level  of  an  adjoining 

building  shall  be  taken  up  unless  adequate  steps  are  taken  to  prevent damage to the existing structure or fall of any part. 

 3.2    Every  accessible  part  of  an  excavation,  pit  or  opening  in  the  ground  into 

which  there  is  a danger of persons  falling  shall be  suitably  fenced with  a barrier  upto  a  height  of  one metre  suitably  placed  from  the  edge  of  the excavation as far as practicable. 

 

Page 163: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 2 of 4

3.3    No  material  or  load  shall  be  placed  or  stacked  near  the  edge  of  the excavation or opening  in  the ground. The excavated material  shall not be placed  within  1.5  m  of  the  trench  or  half  of  the  depth  of  the  trench whichever is more. 

3.4    Cutting  shall  be  done  from  top  to  bottom.  No  undercutting  of  sides  of excavation shall be allowed. 

 3.5    Materials shall not be dumped against existing walls or partition to a height 

that may endanger the stability of the walls.  3.6    While withdrawing piled materials like loose earth, crushed stone, sand, etc. 

from the stock piles, no over hanging shall be allowed to be formed  in the existing dump. 

 3.7    No material on any of the sites of work shall be so stacked or placed as to 

cause danger or inconvenience to any person or public or any other agency at work. 

 4.0    SCAFFOLDING, LADDERS & SHUTTERING  4.1    For all works that cannot be done from the ground level or from part of any 

permanent  structure  or  from  other  available means  of  support,  soundly constructed scaffoldings of adequate strength shall be used as a safe means of access to places of work. 

 4.2    All  scaffolding  shall  be  securely  supported  or  suspended  and  wherever 

necessary be properly braced to ensure stability.  4.3    All working platform and stages from which workers are liable to fall shall be 

of adequate width depending on the type of work done and closely boarded and planked. 

 4.4    Every ladder shall be securely fixed at top and bottom. A ladder more than 5 

m long shall have a prop.  4.5    No portable single ladder shall be over 8 m in length.  4.6                      Unfinished  scaffolding  which  is  under  construction  shall  be  prominently        

marked as unsafe and any access points shall be closed.  4.7                   Shuttering  

The above remarks shall be applicable for this also. Shuttering, particularly for  slabs,  should be  treated as a  scaffold. Unfinished  shuttering  should be 

Page 164: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 3 of 4

marked as dangerous similarly the finished form work should be adequately supported, care being taken to avoid trap door effects. 

 5.0    SAFETY APPLIANCE      Those engaged  in white washing and mixing or stacking of cement bags or 

any  materials  which  is  injurious  to  the  eyes,  shall  be  provided  with protective goggles. 

 5.2    The Tenderer shall not employ men or women below the age of 18, on the 

work of painting with products containing lead in any form. Whenever men / women above the age of 18 are employed on the work of lead painting the following precautions shall be taken: 

 5.3    All  necessary  personnel  safety  equipment  such  as  safety  helmets,  safety 

boots, safety belts, leather gloves for welders, clear glass safety goggles etc., as considered adequate by the Consultant have to be kept available for the use of persons employed at  the  site of work and maintained  in  condition suitable for  immediate use and Tenderer shall take steps to ensure proper use of equipment by the workers. 

 5.4    Sign boards 1 x 1.5 m in size with the following wording shall be erected at 

the  access  to  these  areas.  “CONSTRUCTION  AREA,  HELMET  REQUIRED BEYOND THIS POINT”. 

 5.4 Arrangement  for  rendering  prompt  and  adequate  first  aid  to  the  injured 

persons  shall  be maintained  at  every work  site  under  the  guidance  of  a medical officer‐in‐charge of the project. Depending upon the magnitude of the  work  the  availability  of  an  Ambulance  at  a  very  short  notice  (a telephone call) shall be ensured. 

 5.5  First‐aid arrangements commensurate with the degree of hazard and with 

the number of workers employed shall be maintained in a readily accessible place  throughout  the  working  hours.  At  least  one  experienced  first‐air attendant with his distinguishing badge  shall be available on each  shift  to take  care  of  injured  persons. Arrangements  shall  be made  for  calling  the medical  officer,  when  such  a  need  may  arise.  It  is  recommended  that foreman/assistant  foreman  /  supervisor  /  permanent  workmen  who  are normally  present  at  each working  place  in  each  shift  are  given  adequate training on first‐aid methods to avoid employment of a separate attendant. 

    

Page 165: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 4 of 4

6.0    MISCELLANEOUS  6.1    The Tenderer shall provide necessary fencing and lights to protect the public 

from accident.  

6.2    To  ensure  effective  enforcement  of  the  rules  and  regulations  relating  to safety precautions, the arrangements made by the Tenderer shall be open to inspection by the Consultant and Owner. 

 

6.3    All sources of  ignition shall be prohibited  in areas where flammable  liquids are  stored,  handled  and  processed.  Suitable warning  and  ‘NO  SMOKING’ signs  shall be pasted  in all  such places. Receptacles  containing  flammable liquids  shall be  stacked  in  such a manner as  to permit  free passage of air between them. 

 

6.4    All  combustible materials  shall  be  continuously  removed  from  such  areas where  flammable  liquids  are  stored,  handled  and  processed.  All  spills  of flammable liquids shall be cleared up immediately. Containers of flammable liquids shall be tightly capped. 

 

7.0    REPORTING OF ACCIDENT  

7.1    All accidents, major or minor must be reported immediately. The Tenderer, will  provide  first  aid  to  the  injured  person  immediately  and  the  injured person  shall  report  to  the  first  aid  station  along  with  the  ‘INJURED  ON WORK’ form duly filled in quintuplicate and submit to the Medical Officer of the First Aid Station”. 

 

7.2    Serious Injury  

7.3    In  case of  serious  injury,  the  following procedure  shall be adopted by  the Tenderer: 

 

a) Provide First Aid at his own First Aid Station. b) Take the injured person to the Hospital along with the “INJURED ON 

WORK” form duly filled in. c) Reporting the accident to the Owner/Consultant by the Tenderer.  

7.4    Fatal Accident Fatal accident must be  reported  immediately  to  the Consultant/Owner as well as to the Police. 

   

8.0    PENALTY  

Failure  to  observe  the  Safety  Rules  will  make  the  Tenderer  liable  to penalty by way of suspension of work, fine and termination of contract. 

Page 166: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 1 of 4

Chapter‐I  

SECTION – VII:  LIST OF RECOMMENDED MAKES/ MANUFACTURERS  1.0  GENERAL 

 1.1  The makes and manufacturers shall preferably be from the following list. In case the 

same is not available in the market or incase of a change in trade name, equivalent makes/ re‐designated manufacturer shall be used with the approval of Consultant. 

 1.2         In case of items not covered in the list, the material shall be the best available in the  

market and each item should have BIS certification mark.   Sl.No  Description  Manufacturers 1  TILES: 

i) Terrazzo and cement tiles.  M/s. NITCO; M/S. NEC; M/S. NIMCO. 

ii) White glazed tiles.  R   Johnson;       Somani Pilkington; Spartek . 

iii) PVC tiles.  M/s. Bhor Industries.,      M/s. Premier Vinyl Flooring Ltd  

2  METALLIC FLOOR HARDENR.  M/s. Triveni Color Industries (Floornate) M/s. Heatly & Gresham (India) Ltd M/s.  De‐Rust  Chemical  Corporation  of  Inida (Ferronite) M/s.  Cement  Research  Corporation  Pvt  Ltd. (Stilonite)  

3  WOODEN DOORS / BLOCK BOARDS / PLYWOOD/ PARTICLE BOARD. 

M/s. Indian Plywood Mfg. Co. Ltd M/s. Kit Ply Industries Ltd; M/s. Nuboard M/s. Sitapur,  M/s. Kutty Flush Doors M/s.  Mysore  Plywood  Ltd;  M/s.  Joinery Manufacturer; M/s Northern Doors M/s. Wood  India, Calcutta; M/s Pioneer Timber product, Chandigarh  M/s Sakti Flush doors or equivalent approved manufacturer 

4  STEEL DOORS & WINDOWS  M/s. Sen Harvic; M/s AGEW;  M/s. Hopes Metal; M/s. Multiwyn M/s NCL Seccolor Ltd.  or equivalent approved manufacturer 

5  ROLLING SHUTTERS  M/s. SwastikRollling Shutters &  Engg. Co. (P) Ltd., M/s Hercules Rolling Shutters &  

Page 167: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 2 of 4

Sl.No  Description  Manufacturers Engg Works.  or equivalent approved manufacturer  

6  ALUMINIUM DOORS, WINDOWS, WALL SPANS. 

M/s. Ajit India; M/s. Alumilite; M/s. Indal;;  M/s Jindal. 

7 GLASS. (Plain/Frosted, Garless, Bajra etc.) 

M/S Triveni  M/s Modigaurd M/s Sant gobain Or equivalent approved manufacturer 

8  HARDWARE FITTINGS & FIXTURES. 

M/s Jayant Metal Manufacturing Co. M/s Shalimar Hardware.  Everite.  M/s Godrej & Boyce mfg. Ltd.  or equivalent approved manufacturer. 

9.  A/C SHEETS.  M/s Asbestos Cement ltd. (Everest); M/s Charminar  or equivalent approved manufacturer. 

10.  WATERSTOPS. (PVC/RUBBER) 

M/s Basecon; M/s Pask;  M/s Asian Engg. Products;  M/s Capnhans india Ltd;  M/s Fixopan Engrs. Pvt. Ltd.  or equivalent approved manufacturer. 

11.  EXPANSION JOINT AND TARFELT WATERPROOFING 

M/s Shalitex; M/s Tiki Tar industries; M/ Shalimar Tar Products;  M/s Lloyd Insulation (I) or equivalent approved manufacturer. 

12.  INTEGRAL WATER: PROOFING COMPOUND 

Accoproof, Cico; Impermo or equivalent approved manufacturer. 

13.  CEMENT BASED: WATERPROOFING TREATMENT 

M/s India Waterproofing Co.; M/s All India Waterproofing Co; M/s Likproof India Pvt. Ltd.; M/s Modern Waterproofing Co.;  M/s  Nina Industries.  

14.  PAINTS AND VARNISH  M/s Asian Paints; M/s Goodlas Nerolac;  M/s Garware Paints Ltd.; M/s I.C.I. Paints;  M/s Berger (British) Paints;  M/s Jenson Nicholson; or equivalent approved manufacturer. 

15.  CEMENT BASED WATERPROOF PAINTS & RESINBASED  THERMO PLASTIC PAINTS 

M/s Snowcem India Ltd. M/s Nitco Paints Pvt. Ltd. (Nitcocent); M/s Hindustan Colour  Chemical Industries;  

Page 168: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 3 of 4

Sl.No  Description  Manufacturers M/s Terraco (Terraccin & Terracoat); M/s Surfa Coat Pvt. Ltd.  or equivalent approved manufacturer. 

16.  PRESSED STEEL DOOR: FRAMES 

M/s Sen Harvic  M/s Techome M/s  Madhu  Industries,  Bangalore  or equivalent approved manufacturer. 

17  FALSE CEILING / PANELING   INDIA GYPSUM LTD., 18  DECORATIVE LAMINATES  Decolam , Formica  19  PVC/ FRP DOORS  Rajashri plastic, Thermodeck 20 

DOOR CLOSERS Everite, Hardiwyn,  Dewan Industries 

21  SEALANTS  GE Silicon,Bostik 22  CONCRETE PAVER BLOCKS  Basant Belton,  

Adideep Interlock Pavers, PVt. Ltd.,  Designers Pavings & Tiles Pvt. Ltd.,  Bessers Concrete Paver Blocks. 

23  SANITARY APPLIANCES  Parraware,Hindustan 24  CP BRASS FITTINGS  Jaquar MBM, GEM, 

Kigston, 25  CP BRASS WASTE COUPLING, BOTTLE 

TRAPS Jaquar, ESSO, GEM, Kingston, 

26  PVC flushing cisterns  Parry ware, Hindware 

27  Mirror  Hindustan  Pilkinton,  Modigaurd.  Atul  glass Works , Golden fish 

28  Plastic seat and cover  Commander, 29  Stainless Sink  Nirali, Dayana, AMC, etc. 30  GI Pipes  ITC, Zenith, Ambica 31  GI Mallable fittings  PEC, MJM. Bimal 32  GM gate/ Globe valves  Neta, Sant, NEW,Leader 33  Ball Valves  MBM, Techno, Leader 34  CI water quality pipes  IISCO 35  CI soil quality pipes  IISCO, Neco 36  SW Pipes & Gulley traps  Perfect Kashmira, 37  RCC Hume Pipes  Indian Hume Pipes, Pranali Premier 38  HDPE Pipes & fittings  Prince, Gautam 39  PVC pipes & fittings  Flowgaurd 40  Modular floors  Unitile 41  CI manhole covers  Neco 42  PVC storage tanks  Sintex, Century, Polycon 43  CEMENT  ACC, COROMANDEL, RAJASHREE,  

ZUARI, L&T (ULTRA TECH CEMENT) 

Page 169: Civil Works Spec

BMM ISPAT LTD EXPANSION OF STEEL PLANT AT

DANAPUR VILLAGE NEAR HOSPET, BELLARY DIST, KARNATAKA

TECHNICAL SPECIFICATION FOR CIVIL WORKS

“Copyright © 2011. MECON Limited. All Rights Reserved”

Page 4 of 4

Sl.No  Description  Manufacturers 44  REINFORCEMENT STEEL  SAIL, TATA STEEL, RINIL 45  ADMIXTURES  FOSROC, SIKA, ROFF, 

46  Anti‐ termite  M/s Pest Control (I) Ltd., M/s Mysodet Pvt Ltd., 

  

 

Page 170: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

SECTION ‐ EW ‐ EARTHWORK

Earthwork in excavation and backfilling in layer of 30 cm for Foundations of buildings, pipe supports, equipments, tunnels, trenches,culverts, manholes, etc., in Oridnary soils including Soft rock / Disintegrated rock, in both Dry and Wet conditions, including Pumpingand Bailing out Surface and Subsoil water, Shoring, Strutting, Slush removal at all heights and depths as per Drawing andSpecifications wherever required , in Foundation pits and other places with excavated suitable surplus earth, including reclaiming fromspoil heaps kept elsewhere including dressing and levelling,watering and mechanical compaction etc.,Transporting surplusunserviceable soil to Dumping yards within plant site and spreading in layers as per Specifications and direction of Consultant. TheMeasurement for payment shall be for the Theoretical volume only i.e., the volume of the block of the excavation having maximumbottom dimension of the  foundation as  per Drawing and to actual depth.

( The Contractor shall take into account in his rate, the provision for excess excavation for necessary working space, slope etc.,required for excavation and other allied works and refilling the side slopes and working space)

a) For depth upto & including 2.00 m CUM 20329.00

b) For depth beyond 2.00 m and upto & including 4.00 m CUM 5083.00

c) For depth beyond 4.00 m and upto & including 6.00 m CUM 2033.00

Same as in item EW‐1but in hard rocks,excavation by blasting

a) For depth upto & including 2.00 m CUM 15247.00

b) For depth beyond 2.00 m and upto & including 4.00 m CUM 5083.00

c) For depth beyond 4.00 m and upto & including 6.00 m CUM 2033.00

Controlled earth filling under floors and other places with special compaction to achieve dry density of 95% standard proctor densitywith excavated surplus earth including cost of excavation reclaiming from spoil heaps within plant site as per instruction of theConsultant at all heights/depths, transporting, depositing, compacting and dressing, trimming complete as desired in layers notexceeding 15 cms including watering, consolidating by mechanical means as per specifications and instructions of the Consultant.

a) With available earth CUM 1017.00

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

EW1

EW2

EW‐3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 1 OF  28

Page 171: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

EW‐4

Controlled earth filling in site levelling, under floors and other places with earth brought from outside sources, with specialcompaction to achieve dry density of 95% of standard proctor density as per instruction of the Engineer Incharge at allheights/depths (lifts), transporting, depositing, compacting and dressing, trimming complete as desired in layers not exceeding250mm including watering, consolidating by mechanical means as per specifications and instructions of the Engineer Incharge.(Payment shall be made for consolidated  thickness only)

CUM 1017.00

EW‐5Supplying and filling approved quality sand in foundation or under floor, trenches, pits and other places, at all locations in layers of200 mm thickness including watering and ramming, all lead, lift and depth complete as per drawing and specification and direction ofthe Consultant

CUM 5083.00

SECTION TOTAL‐ EW

SECTION ‐ AT ‐ ANTITERMITE TREATMENT

AT‐1

Supplying and injecting with approved quality chemical emulsion at the rates and concentrations as per IS 6313‐1981 Part II forpreconstructional antitermite treatment and creating a chemical barrier under and alround the column pits, foundation, walltrenches, plinth filling, junctions of wall and floor, expansion joints, apron, surrounding of pipes, conduits etc., along the perimeter ofthe building including all byeworks complete as per specification and direction of Consultant(only ground floor plinth area of thebuilding will be measured for the payment in the following three stages. i) 50% after completion of the foundations ii) 30% aftercompletion of the ground floor flooring iii) 20% after completion of all treatment works including ground floor doors & windows.Work to be executed by M/s Pest Control (India) or any other approved agency and specified guarantee for 10 (ten) years shall befurnished by the tenderer.Payment will be cleared only after submission of Guarantee.

SQM 509.00

SECTION TOTAL‐ AT

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 2 OF  28

Page 172: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐ CC ‐ PLAIN AND REINFORCED CONCRETE

Supplying and Laying Plain Cement Concrete of following Grades (including Shuttering if required) in all levelling courses underFoundation, Floors, Pipelines, Pits etc., at all depths complete all as per Drawings and Specifications and instruction of the Consultant.

a) M‐5 Grade Concrete, using 40 mm down graded coarse aggregate. CUM 4435.00

b) M‐7.5 Grade Concrete, using 40 mm down graded coarse aggregate. CUM 4435.00

c) M‐10 Grade Concrete, using 40 mm down graded coarse aggregate. CUM 5913.00

CC2

Supplying and laying plain cement concrete of proportion 1:2:4 at all leads and lifts, in all floors, aprons, pits, drains and other similarworks, steps, coping of compound wall etc. by mechanical mixing using graded stone aggregate 20 mm max. size and down includingmechanical mixing, transporting, consolidation, including shuttering, if required, as per specifications, drawings and instructions of theEngineer Incharge.   

CUM 650.00

Supplying & laying reinforced cement concrete flooring of thickness as mentioned in the drawing of following grades in long panelswith necessary slope using screed vibrators, etc., in floors and any other works as directed. The rates shall include the cost ofnecessary shuttering (but excluding the cost of steel reinforcement) to maintain the line and level of the floor to achieve the flat andsmooth surface within the specified tolerance, cleaning and preparing the base surface and other necessary bye‐works, provision forconstruction joints, expansion joints, etc., all complete as per specification, drawings and direction of the Consultant.

a) M‐20 Grade, design mix, Concrete, using 20 mm down graded coarse aggregate. CUM 1525.00

Supplying and Laying of design mix, with minimum cement content per Cum of concrete to be not less than 320 kg) ReinforcedCement Concrete of following Grades (excluding Shuttering and Reinforcement) at all depths and heights in all types of Foundations,Footings, pile caps, equipment foundations, columns, lintels, ducts, beams, brackets, slabs, sloped roofs, walls, sills, parapets, bandsand any other works both in under ground and Superstructures all complete as per Drawings, Specification and instruction ofConsultant.

a) M‐25 Grade Design Mix Concrete, using 20 mm down graded coarse aggregate. CUM 66069.00

b) M‐30 Grade Design Mix Concrete, using 20 mm down graded coarse aggregate.(with cooling of aggregates/ use of ice for massconcreting of BF/ Stoves foundation)

CUM 5083.00

CC1

CC3

CC4

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 3 OF  28

Page 173: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

CC5Supplying and laying reinforced cement concrete grade M‐25 with stone aggregate of 20 mm and down graded (excluding shutteringand reinforcement) at all heights for super structures of silos, water tanks and chimneys of all shapes with all byeworks complete asper drawings, specification & instruction of the consultants.

CUM 1525.00

Providing, Fixing and Stripping of Shuttering of good quality plywood or steel plate on steel frame for all types of Structures notcovered in respective items including Centering / Scaffolding, all complete as per Drawings, Specifications and directions of theConsultant.

a) For Structures at all depths and heights. SQM 304932.00

b) For Structures at all depths and heights for curved shuttering. SQM 12198.00

CC7

Supplying and providing slip‐form shuttering for construction of cylindrical silos, water tank shafts, chimneys with sliding surfaces oninternal and external faces of the shaft with steel sheet form panels, with necessary widening at the bottom for ease of slidingupwards, with all necessary ribs, yoke frames, working platforms, suspended finishing platforms, hydraulic lifting jacks, pump sets,including jacking rods with all necessary accessories provided at designed centers, arrangements for verifying verticality, includingarrangements for correction of out of plumb movement and twist or rotation in plan, elevation control mechanism, including allnecessary bye‐works for provision of inserts, openings and dowel bars as directed by engineer (Both internal and external faces shallbe measured for payment. The scheme of slip‐form shuttering shall be got approved by the engineer in‐charge).

SQM 1017.00

Supplying, fabricating and fixing in position HIGH YIELD STRENGTH DEFORMED BARS ‐ TMT steel reinforcements of grade Fe 500 D atall levels and positions, all leads and lifts including the cost of transport, straightening, cutting, bending, cranking, binding, fixing, tyingin position with two nos. of 1.6 mm dia. soft drawn annealed binding wire, welding, provision of necessary chairs and spacers,including tying and bending dowel bars and their straightening upon deshuttering (wherever necessary) as per drawings andspecifications and including cost of binding wire, labour, cover blocks in CM 1:2 etc., all complete for reinforced concrete as perspecifications, drawings and instructions of the Engineer Incharge. The pins,chairs and spacer bars provided will be measured forpayment.  

a) Reinforcement conforming to Grade Fe‐500 D of IS : 1786‐2008 ( TMT‐EQR bars from SAIL or equivalent from RINL/TATA STEEL) MT 2135.00

CC9

Suppliying,Fabricating, Fixing at all levels and positions Steel embedment/ Inserts like Anchor bolts,Plates, chequerred plates,Channels, Anchor boxes, Bolt with nuts and washers Bolt caps, GI pipe Sleeves including Threading etc., including two coats ofapproved quality Synthetic enamel paint over a primer coat on the exposed Surfaces wherever necessary, complete as perDrawings, Specifications and directions of the Consultant. Insert materials shall conform to IS:2062 ( Jigs, Templates and Fixtureswill  not be paid  separately. )

KGS. 16264.00

CC10Supplying, Fabricating, Fixing at all levels and positions High tensile Bolt conforming to IS:1367‐1991with nuts and washers Bolt caps,including Threading etc., complete as per Drawings, Specifications and directions of the Consultant.( Jigs, Templates and Fixtureswill  not be paid  separately. )

KGS. 2033.00

CC6

CC8

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 4 OF  28

Page 174: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

Supplying and mixing approved water proofing admixture as per the manufacturer's specification including cost of material ,complete, with all byeworks as per drawing and instruction of the Consultant.

a) Liquid water proofing compound (conplast X421 IC or equivalent) conforming to IS:2645‐1975 LITER 5083.00

Construction of Anchor holes or Anchor pockets of following Cross sections including necessary Shuttering and its removal,Cleaning and keeping it covered till Erection of bolts etc., as per Specifications, Drawings and direction of the Consultant.

a) Cross section upto and equal to 200 sqcm. RM 204.00

b) Cross section more than 200 sqcm and upto 650 sqcm RM 102.00

Supplying & Grouting ( including tamping ) for Foundations, Structures, Equipments, Base plates, Anchor holes etc., with CementConcrete of the following Grades (including Shuttering wherever necessary) at all levels and as per Drawings, Specifications anddirection of the Consultant.

a) M‐30 Grade Design Mix Concrete,using 12 mm down graded coarse aggregate. CUM 26.00

CC11

CC12

CC13

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 5 OF  28

Page 175: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

CC‐14Supplying & grouting for foundations, equipment base plates, anchor bolts etc., with cement based non shrink compound such asShrinkomp of ACC or approved make including shuttering at all levels and as per drawings, specification and direction of Consultant.

CUM 6.00

CC‐15Supplying & laying roof screed with M‐15 grade concrete (12 mm down graded coarse aggregate) with smooth finish and requiredslope (ave.50 mm thick) including mixing of water proof compound as per manufacturer's specification (payment for water proofingcompound will be done under relevant item).

SQM 1017.00

CC‐16Providing and laying heat resistant concrete of grade M‐30 using basalt aggregates, basalt sand and Blast furnace slag cement, infoudations of Blastfurnace and stoves etc. as per specifications and direction of Consultant

CUM 1220.00

SECTION TOTAL ‐ CCSECTION ‐ MN ‐ STONE & BRICK MASONRY

MN1Supplying & Laying Random Rubble Masonry brought to courses with locally available stone in cement & sand mortar (1: 5) of anyshape in foundations, superstructure plinths, trenches, drains etc., at all depths & height, curing, including filling of joints with CM 1:5and racking of joints, etc. complete with all byeworks as per specification and drawings.

CUM 1525.00

MN2Supplying & Laying hollow cement concrete block work of 200 thk. (400x200x200‐D5 grade) in super structure,in cement mortar 1:5(1cement : 5 sand) including projections,pillars, parapet mantle all complete including cut work, scaffolding, curing etc.,with all bye‐works as per specifications, drawings and directions of the Consultant.

CUM 1525.00

MN3Same as item no.MN‐2 but with 100mm thk. partition wall (400x100x200) in cement & sand mortar 1:4(1 cement : 4 sand) includingRCC band 75mm thk. at every 5 courses with 2 bars of 8 mm dia.in each layer with one legged stirrup at every 300 c/c, with neccessaryshuttering for RCC band. 

SQM 204.00

SECTION TOTAL ‐ MN

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 6 OF  28

Page 176: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐ FN ‐PLASTERING & SURFACE FINISHES

FN1

Supplying and Laying 20 mm thick external sponge finish cement plaster 1:5 (1 cement : 5 sand) as per architectural shapes marked inthe drawings, at all depths and heights in two coats of 12mm & 8mm. 2nd coating 8mm shall be finished with sand faced plasteringon faces of walls, pillars, projection, bands, cornices, fins, sills, etc., including raking out joints if any left out, necessary dabbing,curing, scaffolding, providing chicken mesh at junctions of columns, beams etc., complete at all heights as per specification anddrawings, second layer with water proofing compound (to be paid under relevant items).

SQM 3050.00

FN2

Supplying & laying 12 mm thick cement plaster 1:4 (1 cement : 4 sand) smooth finish as per architectural shapes marked in thedrawings, at all depths and heights in one layer on internal faces of walls, pillars, projection, bands, cornices etc., including necessarydabbing, curing, scaffolding, providing chicken mesh at junctions of columns, beams etc., complete at all heights as per specificationand drawings.

SQM 5083.00

FN3Supplying and Laying 6 mm thick cement plaster 1:4 (1 cement : 4 sand) to ceiling of slabs, chajjas, bands, beams, columns, loft slabs,staircases, and any other location at all heights wherever required with all bye works dabbing, curing, scaffolding, including providingchicken mesh at junction of columns, beams,etc., complete at all heights and levels as per specification and drawings.

SQM 509.00

FN4Supplying and Laying 12mm thick cement plaster CM 1:4 (1 cement : 4 sand) to apron, drain and any other location at all heightsincluding floating coat of neat cement @ 2.2 kg/sqm wherever required with all bye‐works dabbing, curing, complete all heights andlevels as per specification and drawings and as directed by Consultant.

SQM 610.00

FN5

Providing two coats of water based 100% acrylic exterior emulsion paint over a coat of approved primer which in turn shall be appliedover a coat of colourless biowash of approved make over external concrete/masonry/plastered surfaces as antifungal treatmentincluding prior washing of the surface with clean water, removal of dirt, debris etc. at all heights and levels, including surfacepreparation, scaffolding at all locations and heights with all byeworks complete as per manufacturer's specification and direction ofthe Engineer Incharge.  

SQM 1525.00

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 7 OF  28

Page 177: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

FN6

Distempering with two coats of acrylic oil bound washable distemper over internal plastered surfaces, of approved shade & makeover one coat of approved cement primer, including preparing the surfaces by applying BIRLA WHITE Wall Care Putty (Fine finish) /Gypsum wall putty from Supreme Gypsum 1.5mm thick, surface preparation, cleaning and all byeworks, filling hair cracks with putty /approved filler wherever required, scaffolding & cleaning, cost of all materials, labour etc. at all heights and lifts, all as per drawing,specifications and as directed by Engineer Incharge etc. complete.

SQM 2033.00

FN7Supplying and applying waterproof cement paint of approved make and shade with textured finish in two coats at all locations overand including a priming coat over wall surface, etc., including preparation of surface complete with all bye works, specification anddirection of the Consultant.

SQM 1500.00

FN8Supplying and applying 3coats of white wash all heights and locations with all bye works including scaffolding complete as perspecifications

SQM 3050.00

FN9Supplying & laying flush cement pointing to stone masonry on external face, in cement mortar 1:3 at all locations to a minimum depthof 20 mm, complete as per specifications, drawings and directions of Consultant.

SQM 255.00

Supplying & Laying the following thickness lath plaster at all heights and locations for vertical fins, facias, bands, drops, etc., consistingof cement‐sand plaster of proportion 1:3, including finishing the exposed faces smooth, providing of wire mesh to reinforcement bars,necessary shuttering, surface preparations, etc., all complete as per drawings and directions of the Consultant. The steelreinforcements shall be paid for under reinforcement item.

a) 50 mm thick SQM 102.00b)75 mm thick SQM 51.00

FN‐11Supplying and painting two coats of Synthetic Enamel paint of approved colour and make over a coat of primer over new wooden/steel work, al all levels and heights, including preparation of surface for receiving the paint by surface scarping, rubbing, applying filler,etc., including cost of filler, etc., complete as per specification and direction of consultant.

SQM 102.00

FN‐12

Providing and applying two coats of Industrial grade hot bitumen 85/25 conforming to IS 702 over concrete surfaces includingcleaning of surfaces of all undesirable material, cutting and removal of binding wires etc, filling voids with cement mortar 1:4 andrendering the surface dry before application, as per specification and directions of Consultant, complete, for foundations, pedestals,pits, etc.

SQM 2033.00

FN‐13 Supplying and making 10 mm grooves in external wall plastering at the joints of beam/column and brick wall including scaffolding etc.. RM 509.00

FN‐14Providing drip mould of size 20mm x 8mm over cement plastering of chajjas, roof projections etc. at all heights and levels in cementmortar 1:3, hacking, curing, scaffolding etc at all heights and lifts, all complete as per specifications and instructions of the EngineerIncharge. 

RM 250.00

SECTION TOTAL ‐ FN

FN10

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 8 OF  28

Page 178: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐ FL ‐ FLOORING, PAVING & FACING

FL1

Supplying & laying hard core with hard granite stone boulders below floors and aprons including laying, packing, filling interstices withgood quality spalls, dry and wet consolidation with mechanical means, blinding with good quality moorum/ sand (cost inclusive) withall bye works complete for hard core upto 230 mm thick below floor and 115 mm thick, below apron as per specification andinstruction of the Consultant (Consolidated thickness will be paid).

CUM 2542.00

FL2

Supplying and laying 40 mm thick grey cement concrete flooring laid in panels with a maximum panel area of 2.50 sqm. at all locationsand levels including skirting, steps, nosing, landing slab etc., consisting of plain cement concrete 1:2:4 base (under bed) 30 mm thick(1 cement : 2 coarse sand : 4 stone chips 12 mm & down) and topping 10 mm thick (net after cutting) of mix 1:1:1 (1 cement : 1medium sand : 1 fine stone grit upto 3.0 mm size) and finished with a floating coat of neat cement 2.2 Kg of cement per Sqm offlooring, providing glass strips 4 mm thick upto 40 mm deep, complete with all bye works as per specification, drawing, (Chequerringin floor finish inclusive if required) and as directed by the Consultant.

SQM 10165.00

Supplying and laying granolithic flooring with total thickness as given below, laid monolithically over base concrete in panels with amaximum panel area of 2.50 sqm. at all locations and heights including skirting, treads of steps, nosing, landing slab etc., with underbed consisting of plain cement concrete 1:2:4(1cement: 2coarse sand:4stone chips, 12mm and down) and topping of mix1:1:1(1cement:1medium sand:1fine stone grit upto 3mm size), supplying and fixing 1.5mm thick aluminium strip for full depth,chequerring in floor finish inclusive if required, rounding, sloping, curing, finishing, preparation of slabs, steps, etc., all as perspecifications, drawings and directions of the Consultant. 

a) 25mm thick with 19mm under‐bed and 6mm topping mixed with non‐metallic floor hardener as per manufacturer's specificationand instructions (Fosroc, Sika or equivalent)

SQM 509.00

FL4

Providing and laying 21 mm thick grey cement skirting or dado on walls, risers of steps or in any other vertical surfaces at anylocations consisting of 15 mm thick back coat of cement mortar 1:3 (1 cement : 3 sand) and 6 mm topping (net) with 1:1 cement stonechips mix (1 cement : 1 medium sand : 1 fine stone chips 3 mm down graded) finishing with a floating coat of neat cement, in dado,etc. complete with all bye works as per specification and direction of the Consultant at all levels.

SQM 6000.00

FL3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 9 OF  28

Page 179: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

Providing and laying anti‐skid ceramic tiles tiles conforming to IS:13754 and of approved colour at all levels and locations usingapproved first quality tiles in flooring of toilets etc. and as shown in the drawing laid over and including minimum 35 mm bed (CM 1:3)joints filled with white cement mixed with matching shade of pigment etc. at all leads and lifts, complete with all byeworks as perspecification and direction of Engineer Incharge

a) 300mm x 300mm x minimum 7.7mm thk. in flooring

i) Light shades Sqm 100.00

ii) Dark shades Sqm 50.00

Providing and laying ceramic tiles conforming to IS:13754 of approved colour at all levels and locations with necessary specials etc.using approved first quality tiles as shown in the drawing laid over and including minimum 15 mm thk. CM 1:3) backing and tile fixingadhesive mixed to cement paste used for fixing the tiles, joints filled with white cement mixed with matching shade of pigment etc. atall leads and lifts,  complete with all byeworks as per specification and direction of Engineer Incharge.

a) In dado / skirting using 300x 400 mm Tiles.i) Light shades Sqm 50.00ii) Dark shades Sqm 10.00b) Dado using 300 x 200 mm tiles (Light shade) Sqm 50.00c) In skirting using 200x 100 mm Tiles. (Light Shade) Sqm 50.00

FL‐7

Supplying and laying white glazed tiles conforming to IS 13753 (Part II) of size 200 x 100 x 6 mm in skirting / dado including providingbands of approved shade and size with 12 mm thick CM bed 1:3 as shown in the drawing and joints filled with white cement withapproved colour pigment complete with all bye works as per specifications and direction of Consultant, fixing tiles with approvedfixing adhesive compounds as manufacture's specification.

SQM 153.00

Providing and laying vitrified ceramic tiles of approved colour and design at all levels and locations using approved first quality tiles in flooringwith or without spacers as shown in the drawing, laid over a bedding of cement mortar bed of mix 1:4 to achieve overall flooring thickness as40mm and a backcoat of white cement slurry and joints filled with white cement mixed with matching pigment complete with all byeworks likecovering with plaster of paris, curing etc. at all leads and lifts and as per specification / instructions of the Engineer Incharge.

a) Using 600mm x 600mm x minimum 8.50mm thk.with matt finish Sqm 127.00

b) Using 900mm x 900mm x minimum 11.50mm thk.with matt finish Sqm 127.00

c) Using 600mm x 600mm x minimum 8.50mm thk.with glossy finish Sqm 127.00

d) Using 900mm x 900mm x minimum 11.50mm thk.with glossy finish Sqm 127.00

FL5

FL‐6

FL‐8

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 10 OF  28

Page 180: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

Providing and laying vitrified ceramic tiles of approved colour and design at all levels and locations using approved first quality tiles in skirtingwith or without spacers as shown in the drawing, laid using approved tile fixing adhesive and joints filled with white cement mixed with matchingpigment complete with all byeworks, curing etc. at all leads and lifts and as per specification / instructions of the Engineer Incharge.

a) Using 600mm x 150mm x minimum 8.50mm thk.with matt finish Sqm 20.00

b) Using 900mm x 150mm x minimum 11.50mm thk.with matt finish Sqm 20.00

c) Using 600mm x 150mm x minimum 8.50mm thk.with glossy finish Sqm 20.00

d) Using 900mm x 150mm x minimum 11.50mm thk.with glossy finish Sqm 20.00

FL‐10Providing and laying 20 mm thick polished granite slabs with bull nosing and partly flamed, making curvature of all exposed edges andtheir due polishing, over 20 mm thick 1:3 CM backing for treads of staircase and entrance steps etc. at all leads and lifts, complete asper drawings, specifications and directions of Engineer Incharge. 

SQM 41.00

FL‐11Supplying and laying 8mm thick polished grey granite tiles, over 12 mm thick 1:3 CM backing for risers of steps and skirting ofstaircase and entrance steps etc. complete as per drawings and directions of Consultant.

SQM 11.00

Providing & laying/fixing in position 2.40m x 1.20m x 30 mm thick machine polished granite slabs of approved colour & qualityincluding machine/handcut, polishing, buffing the edges all in line, level, laid over 20mm thk. cement mortar 1:3 bedding and afloating coat of cement @4.39 Kg/sqm with best workmanship, finishing, curing, complete in flooring at all leads and lifts including allbyeworks like covering with plaster of paris, curing etc. as per drawings, specifications and instructions of the Engineer Incharge.

a) Black shade. Sqm 50.00

b) Other shades. Sqm 50.00

SECTION TOTAL ‐ FL

FL‐12

FL‐9

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 11 OF  28

Page 181: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐ WW ‐ WOOD WORK

Supplying and fixing exterior grade block board flush board shutters bonded with phenol formaldehyde hot pressed (solid core)including non standard size, single or double hung in doors, wardrobes, cupboards, conforming to IS 2202 specification from approvedmanufacturer with all bye works complete as per specification and drawing, at all locations with necessary sand blocks, cleatswherever required but including the cost of fittings & fixing. The shutters shall be supplied with teakwood internal edge lipping fromfactory and 6mm external edge lipping shall be provided at site

a) both faces teak veneered , 35 mm thick (including 4 heavy duty brass hinges with necessary screws & 6 levers godrej mortise deadlock with grip handle)

SQM 31.00

Providing & fixing colour coated aluminium hardware fittings with approved quality and shade as per IS specifications/as approved byConsultant to woodwork with cadmium plated MS screws, suitable sockets in masonry/concrete surface if required including all bye‐works complete as per specification, drawing and instruction of Consultants (fittings shall not be paid separately in composite itemswhich specify inclusions of fittings)

a) Butt hinges (extruded section 125 mm x 63 mm x 4 mm) Nos 41.00

b) Tower bolts (with barrel & bolts of extruded section ‐  

 (i) 250 mm x 12 mm (bolt size) Nos 31.00

(ii) 150 mm x 10 mm  Nos 31.00

c) Sliding door bolts including locking arrangement (aldrop)   Nos 16.00

(I) 250 mm long x 20 mm dia rod Nos 26.00

d) Grip handle without back plate of approved IS brand

 (i) 150 mm long  Nos 6.00

(ii) 100 mm long  Nos 21.00

e) floor stopper of double type for door shutters up to 40 mm thick

(I) rubber ‐ double type Nos 4.00

Providing & fixing Godrej Mortise dead lock with back plate, duplicate keys & other fixtures complete with all bye‐works as perspecification and instruction of the Consultant

a) with 2 levers (depth 65 mm) Nos 16.00

b) with 6 levers (depth 76 mm) Nos 16.00

SECTION  TOTAL ‐ WW 

WW‐1

WW‐2

WW‐3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 12 OF  28

Page 182: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐ ST ‐ STEEL & IRON WORK

Supplying and fixing pressed steel framesmanufactured from commercial steel sheet 1.6mm thick and butt welded at the corners, fordoor frames including SS hinges (KICH make as shown in drawings), lock jambs, beads, brace ties, adjustable lugs jammed in PCCblocks 1:2:4 , lock strike plate, shock absorbers, including two coats of synthetic anti corrosive enamel‐ Eco friendly paint with lowvolatile organic compounds ( limit not exceeding 250g/ )over a coat of primer consisting of volatile organic compounds less than250g/L, filling the frame with cement mortar 1:5 all complete at all heights and levels as per IS 4351 and drawings, specifications andinstruction of the Engineer Incharge. SS hinges shall be paid for under relevant item.

a) 105mm (Profile ‐ A) RM 30.00b) 125mm (Profile ‐ B) RM 50.00

ST‐2

Supplying, fabricating and fixing fully glazed MS windows and ventilators made of pre painted, colled rolled steel of 0.6 mm thickneessconforming to IS 513 of approved make in single or composite units both openable and fixed type as approved drawings, galvanisedon sides at 120 gm / sqm zinc coating primer of 5 microns with thermo setting expoxy resin and finish painted with a polyster basedpaint 20 microns thick. The size of profiles is 46 x46 mm approximate for internal frames, 46 x 52 mm approximate for externalframes, 46 x 70 mm for mullion / transoms for ourter frame, 18 x 31 mm for fixed frames., fixing of 4 mm float glass with EPDMgaskets with hinges, handle, corner brackets, peg stays, etc. complete including fixing to the walls/ sills/ columns/ lintels as may berequired with necessary grouting of hold fasts.

SQM 102.00

Providing & fixing in position steel Rolling Shutters of approved make conforming to IS 6248, made from M.S. Laths (80 mm wide and1.25mm thick) including all necessary fixtures, fittings, top hood, guide channels, shutters suspension shaft with tested springs,ceiling strips, locking arrangements, & painting with a coat of approved steel primer including fixing the guides in masonry/concretewith PCC 1:2:4 etc. or with necessary coach screws, nuts, bolts etc. making good the masonry/concrete complete generally, at allheights and levels, as per drawings, specifications and the instructions of the Engineer Incharge. Note: The measurement for Rollingshutters will be as per structural openings. Hood etc. will not be measured separately. Fabrication drawing for rolling shutters shall beprepared and got approved before taking up fabrication work.

a) Pull and Push type, hand operated Sqm 50.00

b) Gear type operated  Sqm 40.00

c) Electrically operated type Sqm 30.00

ST‐3

ST‐1

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 13 OF  28

Page 183: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

ST‐4 Providing & fixing Ball Bearing of approved make for pull & push  rolling shutters.           Each 10.00

ST‐5 Extra for providing grills in rolling shutters in lieu of MS laths.Sqm of grill

60.00

ST‐6 Extra for providing wicket gate in rolling shutters in lieu of MS laths.Sqm of grill

44.00

ST‐7

Supplying, fabricating and fixing MS doors made of pre painted, colled rolled steel profiled sheets of 1.6mm thickness conforming to IS513 and frames made of 0.6 mm deep drawing quality, galvanised on sides at 120 gm / sqm zinc coating primer of 5 microns withthermo setting expoxy resin and finish painted with a polyster based paint 20 microns thick. The size of profiles is 46 x46 mm(approximate) for internal frames, 46 x 52 mm (approximate) for external frames, 23 x 130 mm for middle and bottom jams of internalshutter frame, fixing of 5 mm float glass viewing window of 0.05 sqm with EPDM gaskets, the door shutters shall be fixed to the framewith four hinges , handle, corner brackets, locks, aldoprs, tower bolts etc. complete including fixing to the walls/ columns/ lintels asmay be the case with necessary grouting of hold fasts.

KGS 153.00

ST‐8

Supplying, transportation, Fabricating and fixing structural steel conforming to IS 2062, including all stiffeners, cleats, gussets, etc.,straightening if required, cutting to required length, drilling, welding, providing one shop coat of red oxide zinc chromate primerbefore erection, assembly, bolting and /or welding of joints, machining of joints when necessary, grinding, etc., a touchup coat aftererection, and another coat of red oxide zinc chromate primer plus two coats of synthetic enamel paint as per specification, drawings,and as directed by Consultant at all levels, for all light structural works such as hand rails, chequerred plates, cat ladders, platforms,etc., involving rolled steel sections, tubes, etc., complete

KGS 2033.00

ST‐9

Structural steel in door, window, ventilator, louvres, cover frames using M.S. angles, flats, channels etc. of required sizes, includingcutting, fabrication, welding, erecting & fixing in position with necessary M.S. holdfasts, embedding in concrete, painting all steel workwith a coat of approved steel primer etc. complete at all heights and levels, as per drawings, specifications and instructions of theEngineer Incharge. (M.S. hold fasts will not be measured separetely for payment).      

KGS 375.00

SECTION  TOTAL ‐ ST

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 14 OF  28

Page 184: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION AL ‐ ALUMINIUM WORK

Supplying and fixing in position colour anodised aluminium glazed window with sliding shutters with or without fixed glazing, usingthree track bottom section of size 92 x 45.5 x 1.5 mm (or nearest size) with water drainage cavity and matching sections for side, topand intermediate frames section and 40 x 27.7 x 1.10 m interlock section for shutter. The shutter should be mounted on nylon rollerswith approved quality fixtures such as aluminium handle, tower bolts, etc., providing 4.0 mm thick plain or pinheaded glass for shutterfitted with EPDM gasket. All aluminium sections shall be anodised minimum 15 microns and fabricated by reputed firm by cutting torequired length., joints mitered sub‐idviding the frame tenoned and reveled in the assembled frame to be stiffened with end clips,corner angles, etc., fixed to the wall, lintel, floor beam as the case may be with necessary stool screws, rawl plugs and teak woodguttas etc., including cutting masonry/ concrete and making good to the original surface using cement mortar.

All aluminium sections shall be coated with greasy material for non adhesion of mortar or any sticky material. The coating shall becleaned after installation with all lead and lift, all complete as per specifications and drawings and directions of the Consultant. Thefabrication drawing shall be got approved by Consultant. The rate shall also include giving a coat of bitumastic paint on the aluminiumsurfaces in contact with masonry / concrete and closing the gaps around the frame and the adjoining surface with approved siliconesealant on both faces to achieve watertightness.

SQM 153.00

Al‐2

Supplying and fixing in position colour anodised aluminium glazed ventilators/ windows with top hung shutters and with or withoutfixed glazing made of approved aluminium extruded sections sections. The shutter shall be provided with approved quality fixturessuch as aluminium handle, tower bolts, eye and hook etc., providing 4.0 mm thick plain glass for shutter fitted with glazing clips. Allaluminium sections shall be anodised minimum 15 microns and fabricated by reputed firm by cutting to required length., jointsmitered sub‐idviding the frame tenoned and reveled in the assembled frame to be stiffened with end clips, corner angles, etc., fixed tothe wall, lintel, floor beam as the case may be with necessary stool screws, rawl plugs and teak wood guttas etc., including cuttingmasonry/ concrete and making good to the original surface using cement mortar. All aluminium sections shall be coated with greasymaterial for non adhesion of mortar or any sticky material. The coating shall be cleaned after installation with all lead and lift, allcomplete as per specifications and drawings and directions of the Consultant. The fabrication drawing shall be got approved by Consul

SQM 21.00

AL1

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 15 OF  28

Page 185: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

Supplying and fixing colour anodised aluminium glazed door with standard aluminium "INDAL" / JINDAL / HINDALCO extruded frame(size 101.5mmx44.5x2.5mm) and standard "INDAL" /JINDAL/HINDALCO shutters with 5.50mm thick sheet glass of approved qualityfixed with standard glazing bead inside and outside including all fittings such as handles, 6 lever lock, bolts,2mm thick rubber gasketsaround, etc., as per specifications, drawings and directions of the Consultant. The measurement for payments shall be for the fullopening including frames. The payment for floor spring shall be made under relevant item:

a) Single shutter SQM 16.00

b) Double shutter SQM 11.00

Supplying and fixing heavy duty floor spring of approved make (Everite or equivalent)

a) Single action Nos. 6.00

b) Double action Nos. 6.00

Supplying and fixing colour anodised aluminium partition of following type with INDAL / JINDAL / HINDALCO standard extrudedanodised aluminium section as per drawing with 101.5 x 44.5 x 2.5mm standard colour anodised aluminium frames, firmly secured toRCC slab above with TW infills. Partitions shall be provided with glazed aluminium doors wherever shown in drgs. which will bemeasured and paid separately. (payment shall be made for net area of partition excluding area of door openings). Vertical frames atapprox. 0.6m to 0.8m c/c fixed rigidly at floor & ceiling and horizontal frames at floor levels, sill levels (1 m above floor level) & lintellevel (2.1m above FFL) & ceiling level, complet including all bye works as per directions of Consultant.

a) full height partitions with 12 mm thick pre laminated board from FFL to sill level (1m ht.) & lintel level to false ceiling level & glazedpanel with 5mm thick  float glass from sill level to lintel level

SQM 31.00

SECTION TOTAL ‐ AL

AL‐3

AL‐4

AL‐5

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 16 OF  28

Page 186: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐SW ‐ SANITARY & WATER SUPPLY

Supplying, fitting and fixing white glazed vitreous china wash basin of superior quality (HSW No. 10.007 or approved equivalent makewith ISI mark of nearest size) having single or double holes with 15 mm CP brass piller tap, CP brass chain and plugs, 32mm CP brasswaste coupling, PVC flexible waste pipe, 15mm PVC inlet water pipe connection, MS angle brackets painted with anti corrosive paint,15 mm CP brass angle cock, etc. all complete bye works as per specifications and direction of Consultant.

a) size 510 mm x 400 mm Nos. 6.00

SW‐2

Supplying, fitting and fixing white glazed vitreous china oval shaped wash basin of size 550 mm x 400 mm, without tap holes (HSWNo. 10.016 or approved equivalent make with ISI mark of nearest size) with 15 mm CP brass pillar cock long necked foam flow, 32mmCP brass waste coupling, PVC flexible waste pipe, 15mm PVC inlet water pipe connection, MS angle brackets painted with anticorrosive paint, 15 mm CP brass angle cock, etc. all complete bye works as per specifications and direction of Consultant.

Nos. 6.00

SW‐3

Supplying and fixing vitreous china white glazed Indian type water closet of superior quality 580mm size Orissa pan (HSW No. 20.004or approved equivalent make with ISI mark) with 'P' or 'S' trap, vent hole, with low level PVC cistern of 10 liters capacity (Slimline orequivalent), siphon & standard flush fittings, PVC connecting flush pipe 32mm dia, 15mm CP brass angle cock, 15mm dia flexible PVCinlet water connection etc. all complete.

Nos. 6.00

SW‐4

Supplying and fixing white glazed vitreous china European water closet (EWC) of superior quality 40cm high (HSW No. 20.007 orapproved equivalent make with ISI mark), double trap syphonic pattern, 'P' or 'S' trap, with low level cistern of 10 liters capacity (Slimline or equivalent with syphon and standard flush fittings, white colour solid plastic seat cover & lid of superior approved quality, CPbrass bar hinges, screws, bolts, rubber, buffers 15mm dia PVC inlet pipe connection and CP brass angle cock, fixing EWC to floor withnecessary teak wood block & brass screws, all complete as per drawings, specifications and directions of the Consultant.

Nos 6.00

SW‐5

Supplying and fixing white glazed vitreous china flat back, front lipped standing urinal size 610x400x380mm of superior quality HSWNo. 60.002 or equivalent approved make with ISI mark,with 10 liter capacity high level flushing cistern, 15 mm PVC flfexible inletconnection, 15mm CP brass angle cock, 15mm dia CP brass spreaders connceted to matching connecting pipe from cistern and 32mmdia PVC waste pipe upto floor all as per directions of the Consultant (partitions excluded):

Nos 6.00

SW‐6Supplying and fixing box type half‐round white glazed channels 100mm size with dead and outlet ends of approved make, set incement mortar 1:3 and joints finished with white cement.

RM 21.00

SW‐7Supplying 5.5mm thick, 600 x 450mm size polished plate glass mirror bevelled edge, of approved make fixed to with 6mm thickasbestos sheet backing with 4 nos SS dome screws including necessary drilling of mirror, fixing to wall by means of rawl plugs, allcomplete bye works

Nos 6.00

SW‐8 Supplying and fixing 600 x 120 x 5.5mm thick plate glass shelf with CP guard rail Nos 6.00

SW‐9 Supplying and fixing vitreous china white glazed soap tray of superior quality HSW No. 40.010 or approved equivalent Nos 6.00

SW‐10 Supplying and fixing CP brass soap container (Tilting type) Nos 6.00

SW‐1

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 17 OF  28

Page 187: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SW‐11Supplying and fixing recessed toilet paper roll holder including roller white glazed vitreous china, HSW No. 40.025 or approvedequivalent make

Nos 6.00

SW‐12 Supplying and fixing CP brass towel rail 600mm long, 20 mm dia with CP brackets fixed to wall with SS screws and TW guttas. Nos 6.00

SW‐13Supplying and fixing 100 x 75 mm HCI floor/Nahani trap of self cleansing type with CP hinged heavy brass grating to be fixed in PCCM15C and made water tight Cement shall be supplied by the OWNER. Contractor shall exclude the cost of cement in his quoted rate... 

Nos 6.00

Construction of brick masonry inspection chamber with full bricks, in CM 1:5, provided with a light duty CI covers conforming toIS:1726, 610 x 455 mm, weight not less than 52 kg, embedding the CI frame in 100 mm thick RCC top slab, neatly finished including12mm thick plastering on both faces in CM 1:6, rounding, float coat of neat cement finish on the inner side, PCC bedding etc., allcomplete including excavtion and backfilling, shuttering, painting the frame and cover with two coats of approved anti corrosive paintetc., as per specifications and direction of Consultant.

a) Internal size 600x600x900mm deep Nos 6.00

b) Extra over item SW‐14 a) for additional depth of inspection chamber including providing and fixing CI rungs.  RM 11.00

SW‐15Supplying yard gully trap 150x100mm with CI grating 150 x 150mm and water tight light weight CI covers conforming to IS:1726 ofsize 300x300mm including half‐brick masonry in CM (1:4) plastered neatly with CM (1:4) on both faces, 100mm thick PCC bed of markM‐10C, necessary excavation, complete as per direction of the Consultant.

Nos 6.00

SW‐16

Supplying and laying 50mm dia Polypropylene Random Copolymer pipes suitable for both hot and cold water supply, jointing withsockets using solvent cement as per IS 15801 / 7634 Part 3 ‐ 2003 of maximum thickness with all necessary fittings such as bends,tees, elbows, reducers, unions, nipples, plugs etc., laid below ground including excavation in soil, removal of sharp objects / stonesetc., testing for water tightness, anchoring, if required, with concrete anchor blocks of 1:2:2 proportion over a wrap of rubber /foamed polythene sheet, backfilling with suitably good soil in layers of 75mm, watering, compacting, placing of marker plates to showlocation etc. complete as per specification and direction of the Engineer Incharge.

RM 50.00

Supplying and laying Polypropylene Random Copolymer pipes suitable for both hot and cold water supply, jointing with socketsusing solvent cement as per IS 15801 / IS 7634 Part 3 ‐ 2003 of maximum thickness, with all necessary fittings such as bends, tees,elbows, reducers, unions, nipples, plugs, clamps, fixtures, etc., laid over ground including chasing and concealing in walls/floors withstraps / clamps over compressible material such as rubber / foamed polyethylene, testing for water tightness complete as perspecification and direction of the Engineer Incharge.

a) 50 mm nominal bore RM 30.00b) 40 mm nominal bore RM 250.00c) 32 mm nominal bore RM 150.00d) 25 mm nominal bore RM 100.00e) 20 mm nominal bore RM 75.00

SW‐17

SW‐14

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 18 OF  28

Page 188: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

f) 16 mm nominal bore RM 50.00

Supplying of UPVC pipes for rain water system (Type‐A pipes) , soil and waste discharge system (Type‐B pipes) of maximumthickness in accordance to IS 13592 and laying below ground including jointing with sockets using solvent cement in accordance to IS7634 Part 3 ‐ 2003, with all necessary fittings such as bends, tees, elbows, reducers, unions, nipples, plugs etc., inclusive of excavationin soil, removal of sharp objects / stones etc., testing for water tightness, anchoring, if required, with concrete anchor blocks of 1:2:2proportion over a wrap of rubber / foamed polythene sheet, backfilling with suitably good soil in layers of 75mm, watering,compacting, placing of marker plates to show location etc. complete as per specification and direction of the Engineer Incharge.

a) Type A Pipes ‐ 160mm dia RM 35.00b) Type B pipes ‐ 160mm dia RM 250.00

Supplying and laying UPVC pipes for rain water system (Type‐A pipes) , soil and waste discharge system (Type‐B pipes) of maximumthickness, capable of withstanding 6 Kg/sqm of pressure, jointing with sockets using solvent cement as per IS 13592 / IS 7634 Part 3 ‐2003, with all necessary fittings such as bends, tees, elbows, reducers, unions, nipples, plugs etc., laid over ground on walls/floorswith straps / clamps over compressible material such as rubber / foamed polyethylene, testing for water tightness complete as perspecification and direction of the Engineer Incharge.

a) Type A Pipes ‐ 75mm dia RM 450.00b) Type A Pipes ‐ 110mm dia RM 550.00c) Type B pipes ‐ 110mm dia RM 300.00

Supplying, fitting and fixing superior quality gun metal gate valve (full way) of "LEADER" make or equivalent with ISI mark

a) 40 mm dia Nos 4.00

b) 32mm dia Nos 4.00

c) 25mm dia Nos 4.00

SW‐20 Supplying  and fitting 15mm dia CP brass bib cock of superior quality of approved make with ISI mark Nos 4.00

SW‐21 Providing and fitting long body CP brass 15 mm bib tap of superior quality with ISI mark Nos 4.00

SW‐22 Supplying  and fixing in position Three pronged CP brass robe hooks in toilets/ bath rooms with necessary brass screws, etc. NOS 6.00

SW‐23Supplying and fixing 20 mm thick pre polished marble dividers in between two urinal stalls with all exposedv edges bull nosed, fixingto the wall. Rates shall include cutting of wall tiles and dado, grout the divider into the wall 100mm deep and making good thesurface. The exposed area will 900 mm x 450 mm (width).

NOS 5.00

Supplying ,laying and commissioning IHP septic tanks of 2.5m long from indian hume pipe Co. or equivalent below ground level withmanhole covers,scum boards, vents,inlet,outlet connections made of high quality concrete including all bye works complete

a) 1100 dia. NOS 4.00

SW‐18

SW‐24

SW‐19

SW‐20

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 19 OF  28

Page 189: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SW‐25

Construction of 230 thk.brick masonry circular soak pit of 1.0m inside diameter with full bricks, in CM 1:5, provided with RCC 100thk.precast cover slab neatly finished including 12mm thick plastering on both faces in CM 1:6, rounding, float coat of neat cementfinish on the inner side, PCC bedding etc., all complete including excavtion and backfilling, shuttering, painting the frame and coverwith two coats of approved anti corrosive paint etc., as per specifications and direction of Consultant.

NOS 4.00

Construction of brick masonry circular type manhole with bricks of designation 5.0, in CM 1:4, side cement plaster 12mm thick incement mortar 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound at 0.2% of weight of cement, finished with afloating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominl size),and necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finishedwith a floating coat of neat cement all complete as per standard design, as per IS 4111 at all leads and lifts as per drawings,specifications and instructions of the Engineer Incharge.

a) 900mm dia manhole for depths upto and including 1650mm from GL. Nos. 6.00

b) 1200mm dia manhole for depths from 1650mm upto  and including 2250mm. Nos. 11.00

c) 1500mm dia manhole for depths from 2250mm upto and including 3000mm. Nos. 2.00

d) 1500mm dia manhole for depths from 3000mm upto and including 5000mm. Nos. 2.00

e) 1500mm dia manhole for depths from 5000mm upto and including 9000mm. Nos. 2.00

SW‐26

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 20 OF  28

Page 190: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

Supplying and fixing CI manhole covers and frames conforming to IS 1726 including coating with material having base as blackbituminous material, locking devices, key holes, keys and lifting devices etc. and all byeworks as per specification and instructions ofthe Engineer Incharge.

a) Medium duty ‐ MD10 ‐ Circular shape 500mm dia Nos. 6.00

b) Heavy duty ‐  HD20 ‐ Circular shape 600mm dia Nos. 13.00

Providing and fixing brass ball valve with high pressure copper floats (horizontal plunger type) conforming to IS 1703 of the followingnominal bore along with necessary socket, backnut, reducers etc. complete with all byeworks at all leads and lifts as per drawings,specifications and instructions of the Engineer Incharge.

a) 32mm   Nos. 6.00

b) 25mm   Nos. 12.00

Providing and fixing sand cast iron fittings and accessories for soil and waste pipe conforming to IS 1729 including lead caulked jointsas per IS 3114, painting two coats of anticorrosive bitumastic black paint, both internally and externally complete at all leads and liftsas per drawings, specifications and instructions of the Engineer Incharge.

a) Floor trap with SS grating

1) 75mm dia of weight not less than 4.8 Kgs Nos 56.00

2) 100mm dia of weight not less than 7.5 Kgs Nos 94.00

SECTION TOTAL ‐ SW

SW‐28

SW-29

SW‐27

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 21 OF  28

Page 191: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐ RD ‐ ROAD WORKS

RD‐1

Earth work in box cutting for roads in all kinds of soils excluding boulder studded soil/ rock requiring blasting or chiseling for formationof subgrade in cutting to required camber, gradient, including rolling, compaction and dressing up the surface, breaking clods,removal of slush and water, transporting and depositing or stacking unserviceable earth, etc. elsewhere within the plant site/projectarea as directed by Consultant for all heights etc., complete as per specification.

CUM 9657.00

RD‐2

Filling with approved murrum / gravel brought from outside sources & filling in layers not exceeding 150 mm thick including breakingclods, watering, rolling each layer with power roller of minimum 8 tonnes capacity to attain atleast 95% of the proctor density,dressing the sides & top to the required profile & grade etc. complete as per specifications, drawings and instructions of the EngineerIncharge.

CUM 10299.00

RD‐3Supplying 50 mm I.R.C. hard trap stone metal in stacks at site of work for premeasurement complete as per specifications anddirections of the Engineer Incharge.          

CUM 1190.00

Forming WATER BOUND MACADAM including preparing the sub‐grade, spreading 50 mm graded metal in layers, blinding the surfacewith grit or murrum ,watering, compacting by power roller to proper camber and gradient including dry and wet rolling etc. completeas per specifications and directions of the Engineer Incharge.         

a) 75 mm consolidated  thickness in one layer as WBM 1st layer SQM 7928.00

b) 75mm consolidated thickness in second layer after necessary picking etc. SQM 7928.00

RD‐5supplying & laying 75 mm thick water bound macadam using 50 mm to 40 mm size quality metal, laid to proper camber and gradientwith templates, filling voids with approved quality moorum, dry and wet rolling wit 8 to 10 T roller, all as per specifications andirections of Consultant.

SQM 7420.00

RD‐6

Providing and laying 50mm premix carpet (hot process) using paving bitumen grade 60 / 70 @ not less than 3.5 % by weight of totalmix and aggregates as specified in the specifications including laying , rolling etc. over a tack coat at the rate of 7.50 Kgs / 10sqm usingmechanical pressure sprayer including cleaning of WBM surface prior to the application, all complete as per specifications anddirection of the Engineer Incharge.

SQM 7420.00

RD‐7Providing and laying 12mm thick premix sand seal coat using aggregate as per standard code of practice, bitumen of grade 60 / 70 ,notless than 7.0% by weight of total mix, including laying, rolling etc. complete including applying a coat of bitumen 60 / 70 grade over

the surface grade at the rate of 1.47 kg./m2 and and final consolidation with 8 to 10 ton power roller etc. complete.  SQM 7420.00

RD‐4

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 22 OF  28

Page 192: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

Supplying and fixing precast kerb stones made of PCC grade M15 using 20 mm down graded aggregate, properly cured, of thefollowing sizes, including making necessary casting yard, form work, machine mixing, compacting, finishing, submerged curing,conveying from casting yard to site of placing and fixing in position to correct line, level and curve, plumb over 20mm thick bedding inCM 1:6, jointing and pointing in CM 1:4 wherever required, painting with 2 coats of Yellow/ Black approved quality enamel paint forexposed surfaces, etc., all complete as directed. (The rate shall include the cost of excavation and backfilling for fixing kerb stones).

a) 555mm x 150mm x 450 mm NOS 1424.00

RD‐9

Earth work in forming embankment for roads for formation of subgrade to the full width of the road including slopes and cutting torequired camber, gradient, including rolling with 8 to 10t power roller compaction to get 95% proctor density and dressing up thesurface, breaking clods, removal of slush and water,removal of surplus earth after formation, transporting, etc.with selected andapproved earth with optimum water content and in 200mm layers complete as per drawings and specifications and directed by theconsultant.

CUM 5083.00

RD‐10

Construction of granular sub base by providing, laying, spreading and compacting of coarse graded material of grading 1 (minimumCBR value of 30%)spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator atOMC, and compacting with vibratory rollers 8 ‐ 10 tonne to achieve the desired density of 98% including protection of edges of GSBlayer, cost of all materials, labour, hire charges of machinery, lighting, guarding, barricading, all leads and lifts etc. complete asterdrawings/ as directed by engineer

CUM 1220.00

SECTION TOTAL ‐ RD

RD‐8

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 23 OF  28

Page 193: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

SECTION ‐ MS ‐ MISCELLANEOUS WORKS

MS‐1

Supplying and fixing 30 mm thick (Forex or equivalent) PVC panel door of approved shade and design made out of 5 mm thick Cchannel of width 50mm to form the styles and rails the inner panel shall be of min 5mm thick which is welded/sealed to the style andrails along with 5x25mm PVC beading on all sides and both faces . The shutter frames shall have square aluminium tube of heavygauge 20x20mm on all sides complete including necessary SS hinges of 100 mm size 3 nos,SS tower bolt 100 x 10 mm dia 2 nos, asper instructions and direction of consultant. (The work to be executed by specilised agency)

SQM 11.00

MS‐2

Suppying and fixing PVC door frame of size 50x47(Forex or equivalent) mm with a wall thickness of 5mm, made out of extruded 5mmrigid foam sheet, mitre cut at two corners and jointed with 2 nos. of 150mm long brackets of 15x15mm aluminium square tube in twocorners. The two vertical door profiles are to be reinforced with 19x19mm aluminium square tube & hardwood shall be inserted in thesquare tube, EPDM rubber gasket weather seal to be provided through out the frame. The door frame shall be fixed to the wall bydrilling 100mm long stainless screws through the frame by using PVC fasteners on each side of the verticals. A minimum of 4 nos. ofscrews to be provided for each vertical member. (The work to be executed by specilised agency)

RM 31.00

Supplying and fixing SINTEX or approved PVC water tank with PVC fittings for inlet, outlet, Over flow, scour float valve, connections ofrequired size and dia. Including connections and hoisting/fixing the same tank on roof and other places at all heights with all bye‐works complete as per manufacturer's specification and direction of the Consultant. (Support of tank on brick/RCC/PCC will be paidunder relevant items)

a) 1000 litres capacity Nos 4.00

b) 500 litres capacity Nos 4.00

MS‐4

Supplying and fixing in position false ceiling with 12.5 mm thick Gypsum tiles of India gypsum, of size 595 x 595 mm , with standardand approved aluminium supporting arrangement ( Eezilock or Bestlok or equivalent) suspended from RCC slab with all accessoriessuch as screws, cleats, adjustable suspension rods, runners and Tees etc., including making suitable openings for air‐conditioning grill,light fittings, troughs etc., and painting false ceiling board with two coats of approved make and shade acrylic/ plastic emulsionpaints over and a coat of primer complete with all bye works at all locations and heights and as per drawings and manufacturersspecifications and instruction of Consultant.  

SQM 407.00

MS‐5

Providing & laying/fixing in position first quality black 40 mm thick machine cut machine polished granite slab in single piece upto amaximum length of 1.80 metres laid over 20 mm thick cement mortar bedding 1:3 in support areas with best workmanship, makingcurvature of all exposed edges and their due polishing, providing necessary holes, finishing, curing etc. at all leads and lifts forplatforms in pantry etc.as per drawings, specifications and directions of Engineer Incharge. 

SQM 50.00

MS‐6

Supplying and installing 4mm thk. APP modified bituminous polyester reinforced (minimum 140 gsm) water proofing membrane, UVresistant, granule surfaced, self protective, weather and heat resistant, tear and puncture resistant and flexible of approved makeincluding necessary surface preparation with all byeworks complete as per manufacturer's specifications and instructions of theEngineer Incharge. Guarantee of minimum 10 years shall be funished by the contractor.

SQM 1220.00

MS‐3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 24 OF  28

Page 194: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

MS‐7Supply and laying over water proofing treatment, chicken mesh of 26SWG, and then with 20 mm thick CM in 1:5 in panels of size notexceeding 1.2m x 1.2m and sealing the joints UV resistant bitumastic filler  as directed by Consultant.

SQM 102.00

MS‐8Supplying and laying coarse aggregate (broken granite stone) of nominal size 40mm in the area of transformer , meter room, etc., asper drawing and as directed by Consultant.

CUM 26.00

MS‐9 Supplying & fixing approved quality hydraulic door closer conforming to IS:3564( Everite or equivqlent)  as directed by Consultant Nos 6.00

Supplying & erecting in position precast concrete trench cover units of specified sizes and thickness using reinforced cement concreteof grade M30 with 20 mm down graded coarse aggregates including formwork to give fair and smooth finish, casting, vibrating usingstoring, providing lifting arrangement, loading / unloading transporting, load testing etc., complete but excluding cost ofreinforcement, all as per specification and as directed by the consultant.

a) Unit weight upto and including 150 kg CUM 11.00

MS‐11Supplying & fixing heavy duty PVC water spouts of 40 mm dia of required length, including chamfering the ends at chajjas/ parapets/sunken slab/ tank foundations etc. as per drawing and instruction of Consultant

RM 11.00

MS‐12

Supplying and fixing 400 to 550 mm high cavity floor of modular 600 x 600 approximate with pre moulded infilled access floor tilemade from steel and cementatious infill material (M/s Unitile or equivalent), with edge beading and faced with 2 mm thick antistatichigh pressure laminates. The panels shall be placed on GI snap lock grid system stringers channels supported over MS galvanisedpedestal supports of 16mm ID at 600mm c/c approximate both ways. The pedestal supports shall be rigidly fixed on to the floor withglue and mechanical fasteners and shall be made of 100 x 100 x 8 mm thick base plate and minimum 19 mm thick MS stools with acoupling and check nut for level adjustment. The work includes necessary opening for cables and panel mounting and cutting of tilesto required size and strengthening of pedestals with 300 x 300 mm RCC pedestal at locations of panels. The floor panels and stringersshall be completely removable and shall remain in position without screwing. The shade of the flooring material shall be as specifiedin the drawing or as directed by Consultant. (The cost includes supply of 1% spare tiles and pedestals, lifting tools).

SQM 305.00

Providing, fixing, lowering & laying factory made RCC spun hume pipes (Class NP2 of ISI) with necessary collars, jointing with hempyarn & cement mortar 1:1 including embedding in walls, beams, floors etc. caulking the joints, curing, finishing, aligning to properlevel etc. complete as specified at all lifts. Excavation and PCC bedding,and encasing, if specified ,shall be paid under relevant items.

a) 150 mm dia. Rm 92.00b) 300 mm dia. Rm 30.00

MS‐10

MS‐13

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 25 OF  28

Page 195: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

Supplying and laying factory made RCC Hume pipe of NP3 class, for road crossings of the following diameters, including all incidentalslike collars & specials and jointing with CM 1:3, etc., as per drawings and directions of Consultant. Excavation and PCC bedding,aencasing if specified shall be paid under relevant items.

a) 250 mm dia RM 31.00

b) 300 mm dia RM 31.00

c) 450 mm dia RM 31.00

d) 600 mm dia RM 31.00

Supplying & laying water‐proofing system to reinforced concrete structures at all locations, depths and heights consisting of two coatsof approved acrylic polymer modified cementitious material over rendered blinding surface below base raft and over renderedexternal wall and roof surfaces in contact with soil placing of 15mm dia MS nozzles of suitable length all over the inside surfaces ofraft/wall/roof slab and all construction joints at regular intervals not exceeding 1.5m c/c, mixing approved super plasticizer cumcement water proofer during concreting and finally pressure injecting non‐shrink polymeric water‐proof grouting compond admixedwith cement milk throuth the nozzles and sealing the nozzles with approvd sealant after grouting all compleate with all bye‐works asrequired so as to make the structure water tight.(Manaufacturers specification shall be followed depending on approved materialsused and measurements shall be made on inside surface dimensions only and no separate payment will be made for rendering.)

a) For base slab raft SQM 885.00

b) For walls and  slab other than base raft SQM 2552.00

MS‐15

MS‐14

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 26 OF  28

Page 196: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

MS‐16

Designing, providing,installing and operating well point dewatering system consisting of borewells along the periphery of the facilityfor deep excavations of wagon tippler, tunnels / underground basements including design of the system based on permeability tests,for depths of excavation upto 9.5 m from the existing ground levels, for continuous operation of the system to keep the surface areaof the excavated portion dry and workable for a depth of 500 mm, including drilling of the wells at required spacing and insertion ofperforated pipes, filter media, connecting the pipes to headers and continuous pumping using pumps of appropriate capacities, forduration as direted by the consultant, including all bye works such as providing discharge pipes, channels to the drains, provision ofstandby arrangements for the pumps, cost of diesel, lubricants including necessary permiability test, etc (Payment will be made forthe theoretical area of excavation considering the largest possible dimensions of bed concrete. 10% of the cost to be paid oninstallation and completion of testing, 40% on completion of bed concrete and balance 50% on co

SQM 1281.00

MS‐17Supplying and laying rubble hard stones tightly held back for pitching,filling the joints with CM 1 :5 at all locations with stone size ofnot less than 200mm,including necessary dressing, cutting up to 300mm of top surface and disposal of unserviceable siol etc., within alead of 5 km and levelling complete with all bye‐works as per drawings and direction of Engineer.

CUM 1525.00

Installation of electrical concealed conduits (GI/ PVC) of the following sizes, including bends, clamps, junction boxes, pull boxesincluding pullling of GI wire/ Fish wire in RCC slabs, RCC walls,wall crossings, floors, etc. 

a) 32mm dia RM 509.00

b) 25 mm dia RM 1017.00

c) 20 mm dia RM 509.00

Installation of electrical conduits GI under floors, entrance ramps of the following sizes, including bending, threading the ends andplugging. 

a) 100mm dia RM 1525.00

b) 80 mm dia RM 2033.00

MS‐19

MS‐18

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 27 OF  28

Page 197: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

PART ‐ A:CIVIL WORKS

BMM ISPAT LIMITED

MS‐20

Providing and applying waterproofing treatment in sunken floors and vertical surfaces of toilets and bathrooms etc. with twocomponent acrylic polymer based flexible cementitious coating of heavy duty flexible coating system with excellent waterproofingusing products of approved make. 10mm Cement/Sand (Ratio 1:4) protective screed, using Integral Waterproofing Compound addedas per manufacturer's specifications, shall be applied on top of the membrane. All works shall be carried out as per specifications andmanufacturer's instructions including all byeworks and at all heights and levels and also as per the directions of the Engineer Incharge.

Sqm 1960.00

Providing cinder fill for filling in the depression of toilets, bath room etc., as per the specifications of specialised waterproofingagencies & finishing the surface even, so as to be suitable to receive the tiles etc at all heights and levels as per specifications andinstructions of the Engineer Incharge.       

Cum 780.00

Note :

The measurement shall be on cum  basis.  No deductions shall be made for the areas occupied by pans & other fittings & fixtures.         

MS‐22Providing & fixing 25mm thick PREMOULDED BITUMINOUS FILLER ('Shalitex or other approved manufacture) for expansion jointsincluding painting concrete surface with primer as per specifications, cutting, positioning, supporting, scaffolding & filling withapproved sealing compound etc. complete at all heights and levels as per specifications and instructions of the Engineer Incharge.         

Sqm 350.00

MS‐23Providing & applying polysulphide compound in 'V' grooves of sixe 20mm x 10 mm deep complete at all heights and levels as perspecifications and instructions of the Engineer Incharge.

Rm 100.00

MS‐24

Providing & fixing in position 1mm thick stainless steel (SS 304 grade) flats / angles / tees (of required size) of approved make forcovering the expansion joints in walls, floors, ceiling & columns etc. including drilling slotted holes on both sides, chasing the surfaceswherever required, fixing with wooden gutties, rawl plugs & C.P. brass screws, making good the surface etc. complete at all heightsand levels as per specifications and instructions of the Engineer Incharge.        

Kgs 335.00

MS‐25

Providing and placing in position suitable PVC water stops conforming to IS 12200 : 2001 of approved manufacturer, for constructionjoints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete, fusion jointing etc.complete at all leads and lifts. The water stop shall be serrated (minimum 225mm wide, 10mm thick) with central bulb of outer dia25mm).

Rm 1750.00

SECTION  TOTAL ‐ MSTOTAL(EW+AT+CC+MN+FN+FL+WW+ST+AL+SW+RW+MS)

MS‐21

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 28 OF  28

Page 198: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

SECTION ‐ EW ‐ EARTHWORK

Earthwork in excavation and backfilling in layer of 30 cm for Foundations of buildings, pipe supports, equipments, tunnels, trenches,culverts, manholes, etc., in Oridnary soils including Soft rock / Disintegrated rock, in both Dry and Wet conditions, including Pumping andBailing out Surface and Subsoil water, Shoring, Strutting, Slush removal at all heights and depths as per Drawing and Specificationswherever required , in Foundation pits and other places with excavated suitable surplus earth, including reclaiming from spoil heaps keptelsewhere including dressing and levelling,watering and mechanical compaction etc.,Transporting surplus unserviceable soil to Dumpingyards within plant site and spreading in layers as per Specifications and direction of Consultant. The Measurement for payment shall befor the Theoretical volume only i.e., the volume of the block of the excavation having maximum bottom dimension of the foundation asper Drawing and to actual depth.

( The Contractor shall take into account in his rate, the provision for excess excavation for necessary working space, slope etc., requiredfor excavation and other allied works and refilling the side slopes and working space)

a) For depth upto & including 2.00 m CUM 49398.00

b) For depth beyond 2.00 m and upto & including 4.00 m CUM 12350.00

c) For depth beyond 4.00 m and upto & including 6.00 m CUM 4940.00

Same as in item EW‐1but in hard rocks,excavation by blasting

a) For depth upto & including 2.00 m CUM 37048.00

b) For depth beyond 2.00 m and upto & including 4.00 m CUM 12350.00

c) For depth beyond 4.00 m and upto & including 6.00 m CUM 4940.00

Controlled earth filling under floors and other places with special compaction to achieve dry density of 95% standard proctor density withexcavated surplus earth including cost of excavation reclaiming from spoil heaps within plant site as per instruction of the Consultant atall heights/depths, transporting, depositing, compacting and dressing, trimming complete as desired in layers not exceeding 15 cmsincluding watering, consolidating by mechanical means as per specifications and instructions of the Consultant.

a) With available earth CUM 2500.00

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

EW1

EW2

EW‐3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 1 OF30

Page 199: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

EW‐4

Controlled earth filling in site levelling, under floors and other places with earth brought from outside sources, with special compaction toachieve dry density of 95% of standard proctor density as per instruction of the Engineer Incharge at all heights/depths (lifts),transporting, depositing, compacting and dressing, trimming complete as desired in layers not exceeding 250mm including watering,consolidating by mechanical means as per specifications and instructions of the Engineer Incharge. (Payment shall be made forconsolidated  thickness only)

Cum 2500.00

EW‐5Supplying and filling approved quality sand in foundation or under floor, trenches, pits and other places, at all locations in layers of 200mm thickness including watering and ramming, all lead, lift and depth complete as per drawing and specification and direction of theConsultant

CUM 12350.00

SECTION TOTAL‐ EW

SECTION ‐ AT ‐ ANTITERMITE TREATMENT

AT‐1

Supplying and injecting with approved quality chemical emulsion at the rates and concentrations as per IS 6313‐1981 Part II forpreconstructional antitermite treatment and creating a chemical barrier under and alround the column pits, foundation, wall trenches,plinth filling, junctions of wall and floor, expansion joints, apron, surrounding of pipes, conduits etc., along the perimeter of the buildingincluding all byeworks complete as per specification and direction of Consultant(only ground floor plinth area of the building will bemeasured for the payment in the following three stages. i) 50% after completion of the foundations ii) 30% after completion of theground floor flooring iii) 20% after completion of all treatment works including ground floor doors & windows. Work to be executed byM/s Pest Control (India) or any other approved agency and specified guarantee for 10 (ten) years shall be furnished by thetenderer.Payment will be cleared only after submission of Guarantee.

SQM 1234.93

SECTION TOTAL‐ AT

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 2 OF30

Page 200: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION ‐ CC ‐ PLAIN AND REINFORCED CONCRETE

Supplying and Laying Plain Cement Concrete of following Grades (including Shuttering if required) in all levelling courses underFoundation, Floors, Pipelines, Pits etc., at all depths complete all as per Drawings and Specifications and instruction of the Consultant.

a) M‐5 Grade Concrete, using 40 mm down graded coarse aggregate. CUM 4663.00

b) M‐7.5 Grade Concrete, using 40 mm down graded coarse aggregate. CUM 4663.00

c) M‐10 Grade Concrete, using 40 mm down graded coarse aggregate. CUM 6218.00

CC2

Supplying and laying plain cement concrete of proportion 1:2:4 at all leads and lifts, in all floors, aprons, pits, drains and other similarworks, steps, coping of compound wall etc. by mechanical mixing using graded stone aggregate 20 mm max. size and down includingmechanical mixing, transporting, consolidation, including shuttering, if required, as per specifications, drawings and instructions of theEngineer Incharge.   

CUM 1600.00

Supplying & laying reinforced cement concrete flooring of thickness as mentioned in the drawing of following grades in long panels withnecessary slope using screed vibrators, etc., in floors and any other works as directed. The rates shall include the cost of necessaryshuttering (but excluding the cost of steel reinforcement) to maintain the line and level of the floor to achieve the flat and smooth surfacewithin the specified tolerance, cleaning and preparing the base surface and other necessary bye‐works, provision for construction joints,expansion joints, etc., all complete as per specification, drawings and direction of the Consultant.

a) M‐20 Grade, design mix, Concrete, using 20 mm down graded coarse aggregate. CUM 3705.00

Supplying and Laying of design mix, with minimum cement content per Cum of concrete to be not less than 320 kg) Reinforced CementConcrete of following Grades (excluding Shuttering and Reinforcement) at all depths and heights in all types of Foundations, Footings, pilecaps, equipment foundations, columns, lintels, ducts, beams, brackets, slabs, sloped roofs, walls, sills, parapets, bands and any otherworks both in under ground and  Superstructures all  complete as per  Drawings, Specification and instruction of Consultant.

a) M‐25 Grade Design Mix Concrete, using 20 mm down graded coarse aggregate. CUM 160542.00

b) M‐30 Grade Design Mix Concrete, using 20 mm down graded coarse aggregate.(with cooling of aggregates/ use of ice for massconcreting of BF/ Stoves foundation)

CUM 12350.00

CC5Supplying and laying reinforced cement concrete grade M‐25 with stone aggregate of 20 mm and down graded (excluding shuttering andreinforcement) at all heights for super structures of silos, water tanks and chimneys of all shapes with all byeworks complete as perdrawings, specification & instruction of the consultants.

CUM 3705.00

Providing, Fixing and Stripping of Shuttering of good quality plywood or steel plate on steel frame for all types of Structures not coveredin respective  items including  Centering / Scaffolding, all complete as per Drawings, Specifications and directions of the Consultant.

a) For Structures at all depths and heights. SQM 740959.00CC6

CC3

CC4

CC1

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 3 OF30

Page 201: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

b) For Structures at all depths and heights for curved shuttering. SQM 29639.00

CC7

Supplying and providing slip‐form shuttering for construction of cylindrical silos, water tank shafts, chimneys with sliding surfaces oninternal and external faces of the shaft with steel sheet form panels, with necessary widening at the bottom for ease of sliding upwards,with all necessary ribs, yoke frames, working platforms, suspended finishing platforms, hydraulic lifting jacks, pump sets, including jackingrods with all necessary accessories provided at designed centers, arrangements for verifying verticality, including arrangements forcorrection of out of plumb movement and twist or rotation in plan, elevation control mechanism, including all necessary bye‐works forprovision of inserts, openings and dowel bars as directed by engineer (Both internal and external faces shall be measured for payment.The scheme of slip‐form shuttering shall be got approved by the engineer in‐charge).

SQM 2470.00

Supplying, fabricating and fixing in position HIGH YIELD STRENGTH DEFORMED BARS ‐ TMT steel reinforcements of grade Fe 500 D at alllevels and positions, all leads and lifts including the cost of transport, straightening, cutting, bending, cranking, binding, fixing, tying inposition with two nos. of 1.6 mm dia. soft drawn annealed binding wire, welding, provision of necessary chairs and spacers, includingtying and bending dowel bars and their straightening upon deshuttering (wherever necessary) as per drawings and specifications andincluding cost of binding wire, labour, cover blocks in CM 1:2 etc., all complete for reinforced concrete as per specifications, drawings andinstructions of the Engineer Incharge. The pins,chairs and spacer bars provided will be measured for payment.  

a) Reinforcement conforming to Grade Fe‐500 D of IS : 1786‐2008 ( TMT‐EQR bars from SAIL or equivalent from RINL/TATA STEEL) MT 5187.00

CC8

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 4 OF30

Page 202: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

CC9

Suppliying,Fabricating, Fixing at all levels and positions Steel embedment/ Inserts like Anchor bolts,Plates, chequerred plates, Channels,Anchor boxes, Bolt with nuts and washers Bolt caps, GI pipe Sleeves including Threading etc., including two coats of approved qualitySynthetic enamel paint over a primer coat on the exposed Surfaces wherever necessary, complete as per Drawings, Specificationsand   directions of the  Consultant. Insert materials shall conform to IS:2062  ( Jigs, Templates  and Fixtures  will  not be paid  separately. )

KGS. 39518.00

CC10Supplying, Fabricating, Fixing at all levels and positions High tensile Bolt conforming to IS:1367‐1991with nuts and washers Bolt caps,including Threading etc., complete as per Drawings, Specifications and directions of the Consultant.( Jigs, Templates and Fixtures willnot be paid  separately. )

KGS. 4940.00

Supplying and mixing approved water proofing admixture as per the manufacturer's specification including cost of material , complete,with all byeworks as per drawing and instruction of the Consultant.

a) Liquid water proofing compound (conplast X421 IC or equivalent) conforming to IS:2645‐1975 LITER 12350.00

Construction of Anchor holes or Anchor pockets of following Cross sections including necessary Shuttering and its removal, Cleaningand keeping it covered till Erection of bolts etc., as per Specifications, Drawings and direction of the Consultant.

a) Cross section upto and equal to 200 sqcm. RM 494.00

b) Cross section more than 200 sqcm and upto 650 sqcm RM 247.00

Supplying & Grouting ( including tamping ) for Foundations, Structures, Equipments, Base plates, Anchor holes etc., with CementConcrete of the following Grades (including Shuttering wherever necessary) at all levels and as per Drawings, Specifications and directionof the Consultant.

a) M‐30 Grade Design Mix Concrete,using 12 mm down graded coarse aggregate. CUM 62.00

CC13

CC11

CC12

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 5 OF30

Page 203: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

CC‐14Supplying & grouting for foundations, equipment base plates, anchor bolts etc., with cement based non shrink compound such asShrinkomp of ACC or approved make including shuttering at all levels and as per drawings, specification and direction of Consultant.

CUM 13.00

CC‐15Supplying & laying roof screed with M‐15 grade concrete (12 mm down graded coarse aggregate) with smooth finish and required slope(ave.50 mm thick) includingmixing of water proof compound as per manufacturer's specification (payment for water proofing compoundwill be done under relevant item).

SQM 2470.00

CC‐16Providing and laying heat resistant concrete of grade M‐30 using basalt aggregates, basalt sand and Blast furnace slag cement, infoudations of Blastfurnace and stoves etc. as per specifications and direction of Consultant

CUM 2964.00

SECTION TOTAL ‐ CCSECTION ‐ MN ‐ STONE & BRICK MASONRY

MN1Supplying & Laying Random Rubble Masonry brought to courses with locally available stone in cement & sand mortar (1: 5) of any shapein foundations, superstructure plinths, trenches, drains etc., at all depths & height, curing, including filling of joints with CM 1:5 andracking of joints, etc. complete with all byeworks as per specification and drawings.

CUM 3705.00

MN2Supplying & Laying hollow cement concrete block work of 200 thk. (400x200x200‐D5 grade) in super structure,in cement mortar 1:5(1cement : 5 sand) including projections,pillars, parapet mantle all complete including cut work, scaffolding, curing etc.,with all bye‐worksas per specifications, drawings and directions of the Consultant.

CUM 3705.00

MN3Same as item no.MN‐2 but with 100mm thk. partition wall (400x100x200) in cement & sand mortar 1:4(1 cement : 4 sand) including RCCband 75mm thk. at every 5 courses with 2 bars of 8 mm dia.in each layer with one legged stirrup at every 300 c/c, with neccessaryshuttering for RCC band. 

SQM 494.00

SECTION TOTAL ‐ MN

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 6 OF30

Page 204: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION ‐ FN ‐PLASTERING & SURFACE FINISHES

FN1

Supplying and Laying 20 mm thick external sponge finish cement plaster 1:5 (1 cement : 5 sand) as per architectural shapes marked in thedrawings, at all depths and heights in two coats of 12mm & 8mm. 2nd coating 8mm shall be finished with sand faced plastering on facesof walls, pillars, projection, bands, cornices, fins, sills, etc., including raking out joints if any left out, necessary dabbing, curing, scaffolding,providing chicken mesh at junctions of columns, beams etc., complete at all heights as per specification and drawings, second layer withwater proofing compound (to be paid under relevant items).

SQM 7410.00

FN2Supplying & laying 12 mm thick cement plaster 1:4 (1 cement : 4 sand) smooth finish as per architectural shapes marked in the drawings,at all depths and heights in one layer on internal faces of walls, pillars, projection, bands, cornices etc., including necessary dabbing,curing, scaffolding, providing chicken mesh at junctions of columns, beams etc., complete at all heights as per specification and drawings.

SQM 12350.00

FN3Supplying and Laying 6 mm thick cement plaster 1:4 (1 cement : 4 sand) to ceiling of slabs, chajjas, bands, beams, columns, loft slabs,staircases, and any other location at all heights wherever required with all bye works dabbing, curing, scaffolding, including providingchicken mesh at junction of columns, beams,etc., complete at all heights and levels as per specification and drawings.

SQM 1235.00

FN4Supplying and Laying 12mm thick cement plaster CM 1:4 (1 cement : 4 sand) to apron, drain and any other location at all heights includingfloating coat of neat cement @ 2.2 kg/sqm wherever required with all bye‐works dabbing, curing, complete all heights and levels as perspecification and drawings and as directed by Consultant.

SQM 1482.00

FN5

Providing two coats of water based 100% acrylic exterior emulsion paint over a coat of approved primer which in turn shall be appliedover a coat of colourless biowash of approvedmake over external concrete/masonry/plastered surfaces as antifungal treatment includingprior washing of the surface with clean water, removal of dirt, debris etc. at all heights and levels, including surface preparation,scaffolding at all locations and heights with all byeworks complete as per manufacturer's specification and direction of the EngineerIncharge.  

SQM 3700.00

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 7 OF30

Page 205: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

FN6

Distempering with two coats of acrylic oil bound washable distemper over internal plastered surfaces, of approved shade & make overone coat of approved cement primer, including preparing the surfaces by applying BIRLA WHITE Wall Care Putty (Fine finish) / Gypsumwall putty from Supreme Gypsum 1.5mm thick, surface preparation, cleaning and all byeworks, filling hair cracks with putty / approvedfiller wherever required, scaffolding & cleaning, cost of all materials, labour etc. at all heights and lifts, all as per drawing, specificationsand as directed by Engineer Incharge etc. complete.

SQM 4939.73

FN7Supplying and applying waterproof cement paint of approved make and shade with textured finish in two coats at all locations over andincluding a priming coat over wall surface, etc., including preparation of surface complete with all bye works, specification and directionof the Consultant.

SQM 3700.00

FN8Supplying and applying 3coats of white wash all heights and locations with all bye works including scaffolding complete as perspecifications

SQM 7410.00

FN9Supplying & laying flush cement pointing to stone masonry on external face, in cement mortar 1:3 at all locations to a minimum depth of20 mm, complete as per specifications, drawings and directions of Consultant.

SQM 618.00

Supplying & Laying the following thickness lath plaster at all heights and locations for vertical fins, facias, bands, drops, etc., consisting ofcement‐sand plaster of proportion 1:3, including finishing the exposed faces smooth, providing of wire mesh to reinforcement bars,necessary shuttering, surface preparations, etc., all complete as per drawings and directions of the Consultant. The steel reinforcementsshall be paid for under reinforcement item.

a) 50 mm thick SQM 247.00b)75 mm thick SQM 124.00

FN‐11Supplying and painting two coats of Synthetic Enamel paint of approved colour and make over a coat of primer over new wooden/ steelwork, al all levels and heights, including preparation of surface for receiving the paint by surface scarping, rubbing, applying filler, etc.,including cost of filler, etc., complete as per specification and direction of consultant.

SQM 247.00

FN‐12Providing and applying two coats of Industrial grade hot bitumen 85/25 conforming to IS 702 over concrete surfaces including cleaning ofsurfaces of all undesirable material, cutting and removal of binding wires etc, filling voids with cement mortar 1:4 and rendering thesurface dry before application, as per specification and directions of Consultant, complete, for foundations, pedestals, pits, etc.

SQM 4940.00

FN10

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 8 OF30

Page 206: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

FN‐13 Supplying and making 10 mm grooves in external wall plastering at the joints of beam/column and brick wall including scaffolding etc.. RM 1235.00

FN‐14Providing drip mould of size 20mm x 8mm over cement plastering of chajjas, roof projections etc. at all heights and levels in cementmortar 1:3, hacking, curing, scaffolding etc at all heights and lifts, all complete as per specifications and instructions of the EngineerIncharge. 

RM 250.00

SECTION TOTAL ‐ FNSECTION ‐ FL ‐ FLOORING, PAVING & FACING

FL1

Supplying & laying hard core with hard granite stone boulders below floors and aprons including laying, packing, filling interstices withgood quality spalls, dry and wet consolidation with mechanical means, blinding with good quality moorum/ sand (cost inclusive) with allbye works complete for hard core upto 230 mm thick below floor and 115 mm thick, below apron as per specification and instruction ofthe Consultant (Consolidated thickness will be paid).

CUM 6175.00

FL2

Supplying and laying 40 mm thick grey cement concrete flooring laid in panels with a maximum panel area of 2.50 sqm. at all locationsand levels including skirting, steps, nosing, landing slab etc., consisting of plain cement concrete 1:2:4 base (under bed) 30 mm thick (1cement : 2 coarse sand : 4 stone chips 12 mm & down) and topping 10 mm thick (net after cutting) of mix 1:1:1 (1 cement : 1 mediumsand : 1 fine stone grit upto 3.0 mm size) and finished with a floating coat of neat cement 2.2 Kg of cement per Sqm of flooring, providingglass strips 4 mm thick upto 40 mm deep, complete with all bye works as per specification, drawing, (Chequerring in floor finish inclusiveif required) and as directed by the Consultant.

SQM 24699.00

Supplying and laying granolithic flooring with total thickness as given below, laid monolithically over base concrete in panels with amaximum panel area of 2.50 sqm. at all locations and heights including skirting, treads of steps, nosing, landing slab etc., with under bedconsisting of plain cement concrete 1:2:4(1cement: 2coarse sand:4stone chips, 12mm and down) and topping of mix1:1:1(1cement:1medium sand:1fine stone grit upto 3mm size), supplying and fixing 1.5mm thick aluminium strip for full depth,chequerring in floor finish inclusive if required, rounding, sloping, curing, finishing, preparation of slabs, steps, etc., all as perspecifications, drawings and directions of the Consultant. 

a) 25mm thick with 19mm under‐bed and 6mm topping mixed with non‐metallic floor hardener as per manufacturer's specification andinstructions (Fosroc, Sika or equivalent)

SQM 1235.00

FL4

Providing and laying 21 mm thick grey cement skirting or dado on walls, risers of steps or in any other vertical surfaces at any locationsconsisting of 15 mm thick back coat of cement mortar 1:3 (1 cement : 3 sand) and 6 mm topping (net) with 1:1 cement stone chips mix (1cement : 1 medium sand : 1 fine stone chips 3 mm down graded) finishing with a floating coat of neat cement, in dado, etc. completewith all bye works as per specification and direction of the Consultant at all levels.

SQM 6300.00

FL3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 9 OF30

Page 207: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

Providing and laying anti‐skid ceramic tiles tiles conforming to IS:13754 and of approved colour at all levels and locations using approvedfirst quality tiles in flooring of toilets etc. and as shown in the drawing laid over and including minimum 35 mm bed (CM 1:3) joints filledwith white cement mixed with matching shade of pigment etc. at all leads and lifts, complete with all byeworks as per specification anddirection of Engineer Incharge

a) 300mm x 300mm x minimum 7.7mm thk. in flooring

i) Light shades Sqm 150.00

ii) Dark shades Sqm 50.00

Providing and laying ceramic tiles conforming to IS:13754 of approved colour at all levels and locations with necessary specials etc. usingapproved first quality tiles as shown in the drawing laid over and includingminimum 15 mm thk. CM 1:3) backing and tile fixing adhesivemixed to cement paste used for fixing the tiles, joints filled with white cement mixed with matching shade of pigment etc. at all leads andlifts,  complete with all byeworks as per specification and direction of Engineer Incharge.

a) In dado / skirting using 300x 400 mm Tiles.i) Light shades Sqm 50.00ii) Dark shades Sqm 10.00b) Dado using 300 x 200 mm tiles (Light shade) Sqm 75.00c) In skirting using 200x 100 mm Tiles. (Light Shade) Sqm 75.00

FL‐7

Supplying and laying white glazed tiles conforming to IS 13753 (Part II) of size 200 x 100 x 6 mm in skirting / dado including providingbands of approved shade and size with 12 mm thick CM bed 1:3 as shown in the drawing and joints filled with white cement withapproved colour pigment complete with all bye works as per specifications and direction of Consultant, fixing tiles with approved fixingadhesive compounds as manufacture's specification.

SQM 371.00

FL5

FL‐6

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 10 OF30

Page 208: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

Providing and laying vitrified ceramic tiles of approved colour and design at all levels and locations using approved first quality tiles in flooring with orwithout spacers as shown in the drawing, laid over a bedding of cement mortar bed of mix 1:4 to achieve overall flooring thickness as 40mm and abackcoat of white cement slurry and joints filled with white cement mixed with matching pigment complete with all byeworks like covering withplaster of paris, curing etc. at all leads and lifts and as per specification / instructions of the Engineer Incharge.

a) Using 600mm x 600mm x minimum 8.50mm thk.with matt finish Sqm 127.00

b) Using 900mm x 900mm x minimum 11.50mm thk.with matt finish Sqm 127.00

c) Using 600mm x 600mm x minimum 8.50mm thk.with glossy finish Sqm 127.00

d) Using 900mm x 900mm x minimum 11.50mm thk.with glossy finish Sqm 127.00

Providing and laying vitrified ceramic tiles of approved colour and design at all levels and locations using approved first quality tiles in skirting with orwithout spacers as shown in the drawing, laid using approved tile fixing adhesive and joints filled with white cement mixed with matching pigmentcomplete with all byeworks, curing etc. at all leads and lifts and as per specification / instructions of the Engineer Incharge.

a) Using 600mm x 150mm x minimum 8.50mm thk.with matt finish Sqm 20.00

b) Using 900mm x 150mm x minimum 11.50mm thk.with matt finish Sqm 20.00

c) Using 600mm x 150mm x minimum 8.50mm thk.with glossy finish Sqm 20.00

d) Using 900mm x 150mm x minimum 11.50mm thk.with glossy finish Sqm 20.00

FL‐8

FL‐9

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 11 OF30

Page 209: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

FL‐10Providing and laying 20 mm thick polished granite slabs with bull nosing and partly flamed, making curvature of all exposed edges andtheir due polishing, over 20 mm thick 1:3 CM backing for treads of staircase and entrance steps etc. at all leads and lifts, complete as perdrawings, specifications and directions of Engineer Incharge. 

SQM 99.00

FL‐11Supplying and laying 8mm thick polished grey granite tiles, over 12 mm thick 1:3 CM backing for risers of steps and skirting of staircaseand entrance steps etc. complete as per drawings and directions of Consultant.

SQM 25.00

Providing & laying/fixing in position 2.40m x 1.20m x 30 mm thick machine polished granite slabs of approved colour & quality includingmachine/handcut, polishing, buffing the edges all in line, level, laid over 20mm thk. cement mortar 1:3 bedding and a floating coat ofcement @4.39 Kg/sqm with best workmanship, finishing, curing, complete in flooring at all leads and lifts including all byeworks likecovering with plaster of paris, curing etc. as per drawings, specifications and instructions of the Engineer Incharge.

a) Black shade. Sqm 50.00

b) Other shades. Sqm 50.00

SECTION TOTAL ‐ FL

FL‐12

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 12 OF30

Page 210: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION ‐ WW ‐ WOOD WORK

Supplying and fixing exterior grade block board flush board shutters bonded with phenol formaldehyde hot pressed (solid core) includingnon standard size, single or double hung in doors, wardrobes, cupboards, conforming to IS 2202 specification from approvedmanufacturer with all bye works complete as per specification and drawing, at all locations with necessary sand blocks, cleats whereverrequired but including the cost of fittings & fixing. The shutters shall be supplied with teakwood internal edge lipping from factory and6mm external edge lipping shall be provided at site

a) both faces teak veneered , 35 mm thick (including 4 heavy duty brass hinges with necessary screws & 6 levers godrej mortise dead lockwith grip handle)

SQM 75.00

Providing & fixing colour coated aluminium hardware fittings with approved quality and shade as per IS specifications/as approved byConsultant to woodwork with cadmium plated MS screws, suitable sockets in masonry/concrete surface if required including all bye‐works complete as per specification, drawing and instruction of Consultants (fittings shall not be paid separately in composite items whichspecify inclusions of fittings)

a) Butt hinges (extruded section 125 mm x 63 mm x 4 mm) Nos 99.00

b) Tower bolts (with barrel & bolts of extruded section ‐  

 (i) 250 mm x 12 mm (bolt size) Nos 75.00

(ii) 150 mm x 10 mm  Nos 75.00

c) Sliding door bolts including locking arrangement (aldrop)   Nos 38.00

(I) 250 mm long x 20 mm dia rod Nos 62.00

d) Grip handle without back plate of approved IS brand

 (i) 150 mm long  Nos 13.00

(ii) 100 mm long  Nos 50.00

e) floor stopper of double type for door shutters up to 40 mm thick

(I) rubber ‐ double type Nos 8.00

Providing & fixing Godrej Mortise dead lock with back plate, duplicate keys & other fixtures complete with all bye‐works as perspecification and instruction of the Consultant

a) with 2 levers (depth 65 mm) Nos 38.00

b) with 6 levers (depth 76 mm) Nos 38.00SECTION  TOTAL ‐ WW 

WW‐1

WW‐2

WW‐3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 13 OF30

Page 211: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION ‐ ST ‐ STEEL & IRON WORK

Supplying and fixing pressed steel frames manufactured from commercial steel sheet 1.6mm thick and butt welded at the corners, fordoor frames including SS hinges (KICH make as shown in drawings), lock jambs, beads, brace ties, adjustable lugs jammed in PCC blocks1:2:4 , lock strike plate, shock absorbers, including two coats of synthetic anti corrosive enamel‐ Eco friendly paint with low volatileorganic compounds ( limit not exceeding 250g/ )over a coat of primer consisting of volatile organic compounds less than 250g/L, filling the frame with cement mortar 1:5 all complete at all heights and levels as per IS 4351 and drawings, specifications and instruction of theEngineer Incharge. SS hinges shall be paid for under relevant item.

a) 105mm (Profile ‐ A) RM 60.00b) 125mm (Profile ‐ B) RM 100.00

ST2

Supplying, fabricating and fixing fully glazed MS windows and ventilators made of pre painted, colled rolled steel of 0.6 mm thickneessconforming to IS 513 of approved make in single or composite units both openable and fixed type as approved drawings, galvanised onsides at 120 gm / sqm zinc coating primer of 5 microns with thermo setting expoxy resin and finish painted with a polyster based paint 20microns thick. The size of profiles is 46 x46 mm approximate for internal frames, 46 x 52 mm approximate for external frames, 46 x 70mm for mullion / transoms for ourter frame, 18 x 31 mm for fixed frames., fixing of 4 mm float glass with EPDM gaskets with hinges,handle, corner brackets, peg stays, etc. complete including fixing to the walls/ sills/ columns/ lintels as may be required with necessarygrouting of hold fasts.

SQM 247.00

Providing & fixing in position steel Rolling Shutters of approved make conforming to IS 6248, made from M.S. Laths (80 mm wide and1.25mm thick) including all necessary fixtures, fittings, top hood, guide channels, shutters suspension shaft with tested springs, ceilingstrips, locking arrangements, & painting with a coat of approved steel primer including fixing the guides in masonry/concrete with PCC1:2:4 etc. or with necessary coach screws, nuts, bolts etc. making good the masonry/concrete complete generally, at all heights andlevels, as per drawings, specifications and the instructions of the Engineer Incharge. Note: The measurement for Rolling shutters will be asper structural openings. Hood etc. will not be measured separately. Fabrication drawing for rolling shutters shall be prepared and gotapproved before taking up fabrication work.

a) Pull and Push type, hand operated Sqm 120.00

b) Gear type operated  Sqm 75.00

c) Electrically operated type Sqm 55.00

ST‐3

ST1

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 14 OF30

Page 212: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

ST‐4 Providing & fixing Ball Bearing of approved make for pull & push  rolling shutters.           Each 25.00

ST‐5 Extra for providing grills in rolling shutters in lieu of MS laths.Sqm of grill

60.00

ST‐6 Extra for providing wicket gate in rolling shutters in lieu of MS laths.Sqm of grill

44.00

ST‐7

Supplying, fabricating and fixing MS doors made of pre painted, colled rolled steel profiled sheets of 1.6 mm thickness conforming to IS513 and frames made of 0.6 mm deep drawing quality, galvanised on sides at 120 gm / sqm zinc coating primer of 5 microns with thermosetting expoxy resin and finish painted with a polyster based paint 20 microns thick. The size of profiles is 46 x46 mm (approximate) forinternal frames, 46 x 52 mm (approximate) for external frames, 23 x 130 mm for middle and bottom jams of internal shutter frame, fixingof 5 mm float glass viewing window of 0.05 sqm with EPDM gaskets, the door shutters shall be fixed to the frame with four hinges ,handle, corner brackets, locks, aldoprs, tower bolts etc. complete including fixing to the walls/ columns/ lintels as may be the case withnecessary grouting of hold fasts.

KGS 371.00

ST‐8

Supplying, transportation, Fabricating and fixing structural steel conforming to IS 2062, including all stiffeners, cleats, gussets, etc.,straightening if required, cutting to required length, drilling, welding, providing one shop coat of red oxide zinc chromate primer beforeerection, assembly, bolting and /or welding of joints, machining of joints when necessary, grinding, etc., a touchup coat after erection,and another coat of red oxide zinc chromate primer plus two coats of synthetic enamel paint as per specification, drawings, and asdirected by Consultant at all levels, for all light structural works such as hand rails, chequerred plates, cat ladders, platforms, etc.,involving rolled steel sections, tubes, etc., complete

Kg 4940.00

ST‐9

Structural steel in door, window, ventilator, louvres, cover frames using M.S. angles, flats, channels etc. of required sizes, includingcutting, fabrication, welding, erecting & fixing in position with necessary M.S. holdfasts, embedding in concrete, painting all steel workwith a coat of approved steel primer etc. complete at all heights and levels, as per drawings, specifications and instructions of theEngineer Incharge. (M.S. hold fasts will not be measured separetely for payment).      

KGS 375.00

SECTION  TOTAL ‐ ST

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 15 OF30

Page 213: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION AL ‐ ALUMINIUM WORK

Supplying and fixing in position colour anodised aluminium glazed window with sliding shutters with or without fixed glazing, using threetrack bottom section of size 92 x 45.5 x 1.5 mm (or nearest size) with water drainage cavity and matching sections for side, top andintermediate frames section and 40 x 27.7 x 1.10 m interlock section for shutter. The shutter should be mounted on nylon rollers withapproved quality fixtures such as aluminium handle, tower bolts, etc., providing 4.0 mm thick plain or pinheaded glass for shutter fittedwith EPDM gasket. All aluminium sections shall be anodised minimum 15 microns and fabricated by reputed firm by cutting to requiredlength., joints mitered sub‐idviding the frame tenoned and reveled in the assembled frame to be stiffened with end clips, corner angles,etc., fixed to the wall, lintel, floor beam as the case may be with necessary stool screws, rawl plugs and teak wood guttas etc., includingcutting masonry/ concrete and making good to the original surface using cement mortar.

All aluminium sections shall be coated with greasy material for non adhesion of mortar or any sticky material. The coating shall becleaned after installation with all lead and lift, all complete as per specifications and drawings and directions of the Consultant. Thefabrication drawing shall be got approved by Consultant. The rate shall also include giving a coat of bitumastic paint on the aluminiumsurfaces in contact with masonry / concrete and closing the gaps around the frame and the adjoining surface with approved siliconesealant on both faces to achieve watertightness.

SQM 371.00

Al‐2

Supplying and fixing in position colour anodised aluminium glazed ventilators/ windows with top hung shutters and with or without fixedglazing made of approved aluminium extruded sections sections. The shutter shall be provided with approved quality fixtures such asaluminium handle, tower bolts, eye and hook etc., providing 4.0 mm thick plain glass for shutter fitted with glazing clips. All aluminiumsections shall be anodised minimum 15 microns and fabricated by reputed firm by cutting to required length., joints mitered sub‐idvidingthe frame tenoned and reveled in the assembled frame to be stiffened with end clips, corner angles, etc., fixed to the wall, lintel, floorbeam as the case may be with necessary stool screws, rawl plugs and teak wood guttas etc., including cutting masonry/ concrete andmaking good to the original surface using cement mortar. All aluminium sections shall be coated with greasy material for non adhesion ofmortar or any sticky material. The coating shall be cleaned after installation with all lead and lift, all complete as per specifications anddrawings and directions of the Consultant. The fabrication drawing shall be got approved by Consultant. 

SQM 50.00

AL1

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 16 OF30

Page 214: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

Supplying and fixing colour anodised aluminium glazed door with standard aluminium "INDAL" / JINDAL / HINDALCO extruded frame (size101.5mmx44.5x2.5mm) and standard "INDAL" /JINDAL/HINDALCO shutters with 5.50mm thick sheet glass of approved quality fixed withstandard glazing bead inside and outside including all fittings such as handles, 6 lever lock, bolts,2mm thick rubber gaskets around, etc., asper specifications, drawings and directions of the Consultant. The measurement for payments shall be for the full opening includingframes. The payment for floor spring shall be made under relevant item:

a) Single shutter SQM 38.00

b) Double shutter SQM 25.00Supplying and fixing heavy duty floor spring of approved make (Everite or equivalenta) Single action Nos. 13.00

b) Double action Nos. 13.00

Supplying and fixing colour anodised aluminium partition of following type with INDAL / JINDAL / HINDALCO standard extruded anodisedaluminium section as per drawing with 101.5 x 44.5 x 2.5mm standard colour anodised aluminium frames, firmly secured to RCC slababove with TW infills. Partitions shall be provided with glazed aluminium doors wherever shown in drgs. which will be measured and paidseparately. (payment shall be made for net area of partition excluding area of door openings). Vertical frames at approx. 0.6m to 0.8m c/cfixed rigidly at floor & ceiling and horizontal frames at floor levels, sill levels (1 m above floor level) & lintel level (2.1m above FFL) & ceilinglevel, complet including all bye works as per directions of Consultant.

a) full height partitions with 12 mm thick pre laminated board from FFL to sill level (1m ht.) & lintel level to false ceiling level & glazedpanel with 5mm thick  float glass from sill level to lintel level

SQM 75.00

SECTION TOTAL ‐ AL

AL‐3

AL‐4

AL‐5

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 17 OF30

Page 215: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION ‐SW ‐ SANITARY & WATER SUPPLY

Supplying, fitting and fixing white glazed vitreous china wash basin of superior quality (HSW No. 10.007 or approved equivalent makewith ISI mark of nearest size) having single or double holes with 15 mm CP brass piller tap, CP brass chain and plugs, 32mm CP brasswaste coupling, PVC flexible waste pipe, 15mm PVC inlet water pipe connection, MS angle brackets painted with anti corrosive paint, 15mm CP brass angle cock, etc. all complete bye works as per specifications and direction of Consultant.

a) size 510 mm x 400 mm Nos. 13.00

SW‐2

Supplying, fitting and fixing white glazed vitreous china oval shaped wash basin of size 550 mm x 400 mm, without tap holes (HSW No.10.016 or approved equivalent make with ISI mark of nearest size) with 15 mm CP brass pillar cock long necked foam flow, 32mm CPbrass waste coupling, PVC flexible waste pipe, 15mm PVC inlet water pipe connection, MS angle brackets painted with anti corrosivepaint, 15 mm CP brass angle cock, etc. all complete bye works as per specifications and direction of Consultant.

Nos. 13.00

SW‐3

Supplying and fixing vitreous china white glazed Indian type water closet of superior quality 580mm size Orissa pan (HSW No. 20.004 orapproved equivalent make with ISI mark) with 'P' or 'S' trap, vent hole, with low level PVC cistern of 10 liters capacity (Slimline orequivalent), siphon & standard flush fittings, PVC connecting flush pipe 32mm dia, 15mm CP brass angle cock, 15mm dia flexible PVC inletwater connection etc. all complete.

Nos. 13.00

SW‐4

Supplying and fixing white glazed vitreous china European water closet (EWC) of superior quality 40cm high (HSW No. 20.007 or approvedequivalent make with ISI mark), double trap syphonic pattern, 'P' or 'S' trap, with low level cistern of 10 liters capacity (Slim line orequivalent with syphon and standard flush fittings, white colour solid plastic seat cover & lid of superior approved quality, CP brass barhinges, screws, bolts, rubber, buffers 15mm dia PVC inlet pipe connection and CP brass angle cock, fixing EWC to floor with necessaryteak wood block & brass screws, all complete as per drawings, specifications and directions of the Consultant.

Nos 13.00

SW‐5

Supplying and fixing white glazed vitreous china flat back, front lipped standing urinal size 610x400x380mm of superior quality HSW No.60.002 or equivalent approved make with ISI mark,with 10 liter capacity high level flushing cistern, 15 mm PVC flfexible inlet connection,15mm CP brass angle cock, 15mm dia CP brass spreaders connceted to matching connecting pipe from cistern and 32mm dia PVC wastepipe upto floor all as per directions of the Consultant (partitions excluded):

Nos 13.00

SW‐1

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 18 OF30

Page 216: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SW‐6Supplying and fixing box type half‐round white glazed channels 100mm size with dead and outlet ends of approved make, set in cementmortar 1:3 and joints finished with white cement.

RM 50.00

SW‐7Supplying 5.5mm thick, 600 x 450mm size polished plate glass mirror bevelled edge, of approved make fixed to with 6mm thick asbestossheet backing with 4 nos SS dome screws including necessary drilling of mirror, fixing to wall by means of rawl plugs, all complete byeworks

Nos 13.00

SW‐8 Supplying and fixing 600 x 120 x 5.5mm thick plate glass shelf with CP guard rail Nos 13.00

SW‐9 Supplying and fixing vitreous china white glazed soap tray of superior quality HSW No. 40.010 or approved equivalen Nos 13.00SW‐10 Supplying and fixing CP brass soap container (Tilting type) Nos 13.00

SW‐11Supplying and fixing recessed toilet paper roll holder including roller white glazed vitreous china, HSW No. 40.025 or approved equivalentmake

Nos 13.00

SW‐12 Supplying and fixing CP brass towel rail 600mm long, 20 mm dia with CP brackets fixed to wall with SS screws and TW guttas. Nos 13.00

SW‐13Supplying and fixing 100 x 75 mm HCI floor/Nahani trap of self cleansing type with CP hinged heavy brass grating to be fixed in PCC M15Cand made water tight Cement shall be supplied by the OWNER. Contractor shall exclude the cost of cement in his quoted rate... 

Nos 13.00

Construction of brick masonry inspection chamber with full bricks, in CM 1:5, provided with a light duty CI covers conforming to IS:1726,610 x 455 mm, weight not less than 52 kg, embedding the CI frame in 100 mm thick RCC top slab, neatly finished including 12mm thickplastering on both faces in CM 1:6, rounding, float coat of neat cement finish on the inner side, PCC bedding etc., all complete includingexcavtion and backfilling, shuttering, painting the frame and cover with two coats of approved anti corrosive paint etc., as perspecifications and direction of Consultant.

a) Internal size 600x600x900mm deep Nos 13.00

b) Extra over item SW‐14 a) for additional depth of inspection chamber including providing and fixing CI rungs.  RM 25.00

SW‐15Supplying yard gully trap 150x100mm with CI grating 150 x 150mm and water tight light weight CI covers conforming to IS:1726 of size300x300mm including half‐brick masonry in CM (1:4) plastered neatly with CM (1:4) on both faces, 100mm thick PCC bed of mark M‐10C,necessary excavation, complete as per direction of the Consultant.

Nos 13.00

SW‐16

Supplying and laying 50mm dia Polypropylene Random Copolymer pipes suitable for both hot and cold water supply, jointing withsockets using solvent cement as per IS 15801 / 7634 Part 3 ‐ 2003 of maximum thickness with all necessary fittings such as bends, tees,elbows, reducers, unions, nipples, plugs etc., laid below ground including excavation in soil, removal of sharp objects / stones etc., testingfor water tightness, anchoring, if required, with concrete anchor blocks of 1:2:2 proportion over a wrap of rubber / foamed polythenesheet, backfilling with suitably good soil in layers of 75mm, watering, compacting, placing of marker plates to show location etc. completeas per specification and direction of the Engineer Incharge.

RM 50.00

SW‐14

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 19 OF30

Page 217: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

Supplying and laying Polypropylene Random Copolymer pipes suitable for both hot and cold water supply, jointing with sockets usingsolvent cement as per IS 15801 / IS 7634 Part 3 ‐ 2003 of maximum thickness, with all necessary fittings such as bends, tees, elbows,reducers, unions, nipples, plugs, clamps, fixtures, etc., laid over ground including chasing and concealing in walls/floors with straps /clamps over compressible material such as rubber / foamed polyethylene, testing for water tightness complete as per specification anddirection of the Engineer Incharge.

a) 50 mm nominal bore RM 30.00b) 40 mm nominal bore RM 250.00c) 32 mm nominal bore RM 150.00d) 25 mm nominal bore RM 100.00e) 20 mm nominal bore RM 75.00f) 16 mm nominal bore RM 50.00

Supplying of UPVC pipes for rain water system (Type‐A pipes) , soil and waste discharge system (Type‐B pipes) of maximum thicknessin accordance to IS 13592 and laying below ground including jointing with sockets using solvent cement in accordance to IS 7634 Part 3 ‐2003, with all necessary fittings such as bends, tees, elbows, reducers, unions, nipples, plugs etc., inclusive of excavation in soil, removalof sharp objects / stones etc., testing for water tightness, anchoring, if required, with concrete anchor blocks of 1:2:2 proportion over awrap of rubber / foamed polythene sheet, backfilling with suitably good soil in layers of 75mm, watering, compacting, placing of markerplates to show location etc. complete as per specification and direction of the Engineer Incharge.

a) Type A Pipes ‐ 160mm dia RM 35.00b) Type B pipes ‐ 160mm dia RM 250.00

SW‐17

SW‐18

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 20 OF30

Page 218: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

Supplying and laying UPVC pipes for rain water system (Type‐A pipes) , soil and waste discharge system (Type‐B pipes) of maximumthickness, capable of withstanding 6 Kg/sqm of pressure, jointing with sockets using solvent cement as per IS 13592 / IS 7634 Part 3 ‐2003, with all necessary fittings such as bends, tees, elbows, reducers, unions, nipples, plugs etc., laid over ground on walls/floors withstraps / clamps over compressible material such as rubber / foamed polyethylene, testing for water tightness complete as perspecification and direction of the Engineer Incharge.

a) Type A Pipes ‐ 75mm dia RM 450.00b) Type A Pipes ‐ 110mm dia RM 550.00c) Type B pipes ‐ 110mm dia RM 300.00

Supplying, fitting and fixing superior quality gun metal gate valve (full way) of "LEADER" make or equivalent with ISI mark

b) 40 mm dia Nos 8.00

c) 32mm dia Nos 8.00

d) 25mm dia Nos 8.00

SW‐21 Supplying  and fitting 15mm dia CP brass bib cock of superior quality of approved make with ISI mark Nos 8.00

SW‐22 Providing and fitting long body CP brass 15 mm bib tap of superior quality with ISI mark Nos 8.00

SW‐23 Supplying  and fixing in position Three pronged CP brass robe hooks in toilets/ bath rooms with necessary brass screws, etc. NOS 13.00

SW‐24Supplying and fixing 20 mm thick pre polished marble dividers in between two urinal stalls with all exposedv edges bull nosed, fixing tothe wall. Rates shall include cutting of wall tiles and dado, grout the divider into the wall 100mm deep and making good the surface. Theexposed area will 900 mm x 450 mm (width).

NOS 10.00

Supplying ,laying and commissioning IHP septic tanks of 2.5m long from indian hume pipe Co. or equivalent below ground level withmanhole covers,scum boards, vents,inlet,outlet connections made of high quality concrete including all bye works complete

a) 1100 dia. NOS 8.00

SW‐20

SW‐25

SW‐19

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 21 OF30

Page 219: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SW‐26

Construction of 230 thk.brick masonry circular soak pit of 1.0m inside diameter with full bricks, in CM 1:5, provided with RCC 100thk.precast cover slab neatly finished including 12mm thick plastering on both faces in CM 1:6, rounding, float coat of neat cement finishon the inner side, PCC bedding etc., all complete including excavtion and backfilling, shuttering, painting the frame and cover with twocoats of approved anti corrosive paint etc., as per specifications and direction of Consultant.

NOS 8.00

Construction of brick masonry circular type manhole with bricks of designation 5.0, in CM 1:4, side cement plaster 12mm thick in cementmortar 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound at 0.2% of weight of cement, finishedwith a floating coat ofneat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominl size), and necessarychannel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coatof neat cement all complete as per standard design, as per IS 4111 at all leads and lifts as per drawings, specifications and instructions ofthe Engineer Incharge.

a) 900mm dia manhole for depths upto and including 1650mm from GL. Nos. 6.00

b) 1200mm dia manhole for depths from 1650mm upto  and including 2250mm. Nos. 11.00

c) 1500mm dia manhole for depths from 2250mm upto and including 3000mm. Nos. 2.00

d) 1500mm dia manhole for depths from 3000mm upto and including 5000mm. Nos. 2.00

e) 1500mm dia manhole for depths from 5000mm upto and including 9000mm. Nos. 2.00

Supplying and fixing CI manhole covers and frames conforming to IS 1726 including coating with material having base as black bituminousmaterial, locking devices, key holes, keys and lifting devices etc. and all byeworks as per specification and instructions of the EngineerIncharge.

a) Medium duty ‐ MD10 ‐ Circular shape 500mm dia Nos. 6.00

b) Heavy duty ‐  HD20 ‐ Circular shape 600mm dia Nos. 13.00

Providing and fixing brass ball valve with high pressure copper floats (horizontal plunger type) conforming to IS 1703 of the followingnominal bore along with necessary socket, backnut, reducers etc. complete with all byeworks at all leads and lifts as per drawings,specifications and instructions of the Engineer Incharge.

a) 32mm   Nos. 6.00

b) 25mm   Nos. 12.00

Providing and fixing sand cast iron fittings and accessories for soil and waste pipe conforming to IS 1729 including lead caulked joints asper IS 3114, painting two coats of anticorrosive bitumastic black paint, both internally and externally complete at all leads and lifts as perdrawings, specifications and instructions of the Engineer Incharge.

a) Floor trap with SS grating

1) 75mm dia of weight not less than 4.8 Kgs Nos 56.00

2) 100mm dia of weight not less than 7.5 Kgs Nos 94.00

SECTION TOTAL ‐ SW

SW‐27

SW‐28

SW‐29

SW-30

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 22 OF30

Page 220: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION ‐ RD ‐ ROAD WORKS

RD‐1

Earth work in box cutting for roads in all kinds of soils excluding boulder studded soil/ rock requiring blasting or chiseling for formation ofsubgrade in cutting to required camber, gradient, including rolling, compaction and dressing up the surface, breaking clods, removal ofslush and water, transporting and depositing or stacking unserviceable earth, etc. elsewhere within the plant site/project area as directedby Consultant for all heights etc., complete as per specification.

CUM 23464.00

RD‐2Filling with approved murrum / gravel brought from outside sources & filling in layers not exceeding 150 mm thick including breakingclods, watering, rolling each layer with power roller of minimum 8 tonnes capacity to attain atleast 95% of the proctor density, dressingthe sides & top to the required profile & grade etc. complete as per specifications, drawings and instructions of the Engineer Incharge.

CUM 22000.00

RD‐3Supplying 50 mm I.R.C. hard trap stone metal in stacks at site of work for premeasurement complete as per specifications and directionsof the Engineer Incharge.          

Cum 2890.00

Forming WATER BOUND MACADAM including preparing the sub‐grade, spreading 50 mm graded metal in layers, blinding the surfacewith grit or murrum ,watering, compacting by power roller to proper camber and gradient including dry and wet rolling etc. complete asper specifications and directions of the Engineer Incharge.         a) 75 mm consolidated  thickness in one layer as WBM 1st layer SQM 19265.00

b) 75mm consolidated thickness in second layer after necessary picking etc. SQM 19265.00

RD‐5supplying & laying 75 mm thick water bound macadam using 50 mm to 40 mm size quality metal, laid to proper camber and gradientwith templates, filling voids with approved quality moorum, dry and wet rolling wit 8 to 10 T roller, all as per specifications an directionsof Consultant.

SQM 18030.00

RD‐6

Providing and laying 50mm premix carpet (hot process) using paving bitumen grade 60 / 70 @ not less than 3.5 % by weight of total mixand aggregates as specified in the specifications including laying , rolling etc. over a tack coat at the rate of 7.50 Kgs / 10sqm usingmechanical pressure sprayer including cleaning of WBM surface prior to the application, all complete as per specifications and direction othe Engineer Incharge.

SQM 18030.00

RD‐7Providing and laying 12mm thick premix sand seal coat using aggregate as per standard code of practice, bitumen of grade 60 / 70 ,notless than 7.0% by weight of total mix, including laying, rolling etc. complete including applying a coat of bitumen 60 / 70 grade over the

surface grade at the rate of 1.47 kg./m2 and and final consolidation with 8 to 10 ton power roller etc. complete.  SQM 18030.00

RD‐4

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 23 OF30

Page 221: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

Supplying and fixing precast kerb stones made of PCC grade M15 using 20 mm down graded aggregate, properly cured, of the followingsizes, including making necessary casting yard, form work, machine mixing, compacting, finishing, submerged curing, conveying fromcasting yard to site of placing and fixing in position to correct line, level and curve, plumb over 20mm thick bedding in CM 1:6, jointing andpointing in CM 1:4 wherever required, painting with 2 coats of Yellow/ Black approved quality enamel paint for exposed surfaces, etc., allcomplete as directed. (The rate shall include the cost of excavation and backfilling for fixing kerb stones).

a) 555mm x 150mm x 450 mm NOS 3458.00

RD‐9

Earth work in forming embankment for roads for formation of subgrade to the full width of the road including slopes and cutting torequired camber, gradient, including rolling with 8 to 10t power roller compaction to get 95% proctor density and dressing up the surface,breaking clods, removal of slush and water,removal of surplus earth after formation, transporting, etc.with selected and approved earthwith optimum water content and in 200mm layers complete as per drawings and specifications and directed by the consultant.

CUM 12350.00

RD‐10

Construction of granular sub base by providing, laying, spreading and compacting of coarse graded material of grading 1 (minimum CBRvalue of 30%)spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC,and compacting with vibratory rollers 8 ‐ 10 tonne to achieve the desired density of 98% including protection of edges of GSB layer, costof all materials, labour, hire charges of machinery, lighting, guarding, barricading, all leads and lifts etc. complete aster drawings/ asdirected by engineer

CUM 2964.00

SECTION TOTAL ‐ RD

RD‐8

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 24 OF30

Page 222: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

SECTION ‐ MS ‐ MISCELLANEOUS WORKS

MS‐1

Supplying and fixing 30 mm thick (Forex or equivalent) PVC panel door of approved shade and design made out of 5 mm thick C channelof width 50mm to form the styles and rails the inner panel shall be of min 5mm thick which is welded/sealed to the style and rails alongwith 5x25mm PVC beading on all sides and both faces . The shutter frames shall have square aluminium tube of heavy gauge 20x20mmon all sides complete including necessary SS hinges of 100 mm size 3 nos,SS tower bolt 100 x 10 mm dia 2 nos, as per instructions anddirection of consultant. (The work to be executed by specilised agency)

SQM 25.00

MS‐2

Suppying and fixing PVC door frame of size 50x47(Forex or equivalent) mm with a wall thickness of 5mm, made out of extruded 5mm rigidfoam sheet, mitre cut at two corners and jointed with 2 nos. of 150mm long brackets of 15x15mm aluminium square tube in two corners.The two vertical door profiles are to be reinforced with 19x19mm aluminium square tube & hardwood shall be inserted in the squaretube, EPDM rubber gasket weather seal to be provided through out the frame. The door frame shall be fixed to the wall by drilling100mm long stainless screws through the frame by using PVC fasteners on each side of the verticals. A minimum of 4 nos. of screws to beprovided for each vertical member. (The work to be executed by specilised agency)

RM 75.00

Supplying and fixing SINTEX or approved PVC water tank with PVC fittings for inlet, outlet, Over flow, scour float valve, connections ofrequired size and dia. Including connections and hoisting/fixing the same tank on roof and other places at all heights with all bye‐workscomplete as per manufacturer's specification and direction of the Consultant. (Support of tank on brick/RCC/PCC will be paid underrelevant items)

a) 1000 litres capacity Nos 8.00

b) 500 litres capacity Nos 8.00

MS‐4

Supplying and fixing in position false ceiling with 12.5 mm thick Gypsum tiles of India gypsum, of size 595 x 595 mm , with standard andapproved aluminium supporting arrangement ( Eezilock or Bestlok or equivalent) suspended from RCC slab with all accessories such asscrews, cleats, adjustable suspension rods, runners and Tees etc., including making suitable openings for air‐conditioning grill, lightfittings, troughs etc., and painting false ceiling board with two coats of approved make and shade acrylic/ plastic emulsion paints overand a coat of primer complete with all bye works at all locations and heights and as per drawings and manufacturers specifications andinstruction of Consultant.  

SQM 988.00

MS‐3

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 25 OF30

Page 223: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

MS‐5

Providing & laying/fixing in position first quality black 40 mm thick machine cut machine polished granite slab in single piece upto amaximum length of 1.80 metres laid over 20 mm thick cement mortar bedding 1:3 in support areas with best workmanship, makingcurvature of all exposed edges and their due polishing, providing necessary holes, finishing, curing etc. at all leads and lifts for platformsin pantry etc.as per drawings, specifications and directions of Engineer Incharge. 

SQM 62.00

MS‐6

Supplying and installing 4mm thk. APP modified bituminous polyester reinforced (minimum 140 gsm) water proofing membrane, UVresistant, granule surfaced, self protective, weather and heat resistant, tear and puncture resistant and flexible of approved makeincluding necessary surface preparation with all byeworks complete as per manufacturer's specifications and instructions of the EngineerIncharge. Guarantee of minimum 10 years shall be funished by the contractor.

SQM 2964.00

MS‐7Supply and laying over water proofing treatment, chicken mesh of 26SWG, and then with 20 mm thick CM in 1:5 in panels of size notexceeding 1.2m x 1.2m and sealing the joints UV resistant bitumastic filler  as directed by Consultant.

SQM 247.00

MS‐8Supplying and laying coarse aggregate (broken granite stone) of nominal size 40mm in the area of transformer , meter room, etc., as perdrawing and as directed by Consultant.

CUM 62.00

MS‐9 Supplying & fixing approved quality hydraulic door closer conforming to IS:3564( Everite or equivqlent)  as directed by Consultant Nos 13.00

Supplying & erecting in position precast concrete trench cover units of specified sizes and thickness using reinforced cement concrete ofgrade M30 with 20 mm down graded coarse aggregates including formwork to give fair and smooth finish, casting, vibrating using storing,providing lifting arrangement, loading / unloading transporting, load testing etc., complete but excluding cost of reinforcement, all as perspecification and as directed by the consultant.

a) Unit weight upto and including 150 kg CUM 25.00

MS‐11Supplying & fixing heavy duty PVC water spouts of 40 mm dia of required length, including chamfering the ends at chajjas/ parapets/sunken slab/ tank foundations etc. as per drawing and instruction of Consultant

RM 25.00

MS‐10

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 26 OF30

Page 224: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

MS‐12

Supplying and fixing 400 to 550 mm high cavity floor of modular 600 x 600 approximate with pre moulded infilled access floor tile madefrom steel and cementatious infill material (M/s Unitile or equivalent), with edge beading and faced with 2 mm thick antistatic highpressure laminates. The panels shall be placed on GI snap lock grid system stringers channels supported over MS galvanised pedestalsupports of 16mm ID at 600mm c/c approximate both ways. The pedestal supports shall be rigidly fixed on to the floor with glue andmechanical fasteners and shall be made of 100 x 100 x 8 mm thick base plate and minimum 19 mm thick MS stools with a coupling andcheck nut for level adjustment. The work includes necessary opening for cables and panel mounting and cutting of tiles to required sizeand strengthening of pedestals with 300 x 300 mm RCC pedestal at locations of panels. The floor panels and stringers shall be completelyremovable and shall remain in position without screwing. The shade of the flooring material shall be as specified in the drawing or asdirected by Consultant. (The cost includes supply of 1% spare tiles and pedestals, lifting tools).

SQM 741.00

Providing, fixing, lowering & laying factory made RCC spun hume pipes (Class NP2 of ISI) with necessary collars, jointing with hemp yarn &cement mortar 1:1 including embedding in walls, beams, floors etc. caulking the joints, curing, finishing, aligning to proper level etc.complete as specified at all lifts. Excavation and PCC bedding,and encasing, if specified ,shall be paid under relevant items.

a) 150 mm dia. Rm 225.00

b) 300 mm dia. Rm 30.00

MS‐13

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 27 OF30

Page 225: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

Supplying and laying factory made RCC Hume pipe of NP3 class, for road crossings of the following diameters, including all incidentals likecollars & specials and jointing with CM 1:3, etc., as per drawings and directions of Consultant. Excavation and PCC bedding,a encasing ifspecified shall be paid under relevant items.

a) 250 mm dia RM 75.00

b) 300 mm dia RM 75.00

c) 450 mm dia RM 75.00

d) 600 mm dia RM 75.00

Supplying & laying water‐proofing system to reinforced concrete structures at all locations, depths and heights consisting of two coats ofapproved acrylic polymer modified cementitious material over rendered blinding surface below base raft and over rendered externalwall and roof surfaces in contact with soil placing of 15mm dia MS nozzles of suitable length all over the inside surfaces of raft/wall/roofslab and all construction joints at regular intervals not exceeding 1.5m c/c, mixing approved super plasticizer cum cement water prooferduring concreting and finally pressure injecting non‐shrink polymeric water‐proof grouting compond admixed with cement milk throuththe nozzles and sealing the nozzles with approvd sealant after grouting all compleate with all bye‐works as required so as to make thestructure water tight.(Manaufacturers specification shall be followed depending on approved materials used and measurements shall bemade on inside surface dimensions only and no separate payment will be made for rendering.)

a) For base slab raft SQM 2149.00

b) For walls and  slab other than base raft SQM 6200.00

MS‐15

MS‐14

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 28 OF30

Page 226: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

MS‐16

Designing, providing,installing and operating well point dewatering system consisting of borewells along the periphery of the facility fordeep excavations of wagon tippler, tunnels / underground basements including design of the system based on permeability tests, fordepths of excavation upto 9.5 m from the existing ground levels, for continuous operation of the system to keep the surface area of theexcavated portion dry and workable for a depth of 500 mm, including drilling of the wells at required spacing and insertion of perforatedpipes, filter media, connecting the pipes to headers and continuous pumping using pumps of appropriate capacities, for duration asdireted by the consultant, including all bye works such as providing discharge pipes, channels to the drains, provision of standbyarrangements for the pumps, cost of diesel, lubricants including necessary permiability test, etc (Payment will be made for thetheoretical area of excavation considering the largest possible dimensions of bed concrete. 10% of the cost to be paid on installation andcompletion of testing, 40% on completion of bed concrete and balance 50% on completion of the

SQM 3113.00

MS‐17Supplying and laying rubble hard stones tightly held back for pitching,filling the joints with CM 1 :5 at all locations with stone size of notless than 200mm,including necessary dressing, cutting up to 300mm of top surface and disposal of unserviceable siol etc., within a lead of5 km and levelling complete with all bye‐works as per drawings and direction of Engineer.

CUM 3705.00

Installation of electrical concealed conduits (GI/ PVC) of the following sizes, including bends, clamps, junction boxes, pull boxes includingpullling of GI wire/ Fish wire in RCC slabs, RCC walls,wall crossings, floors, etc. 

a) 32mm dia RM 1235.00

b) 25 mm dia RM 2470.00

c) 20 mm dia RM 1235.00

Installation of electrical conduits GI under floors, entrance ramps of the following sizes, including bending, threading the ends andplugging. 

a) 100mm dia RM 3705.00

b) 80 mm dia RM 4940.00

MS‐18

MS‐19

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 29 OF30

Page 227: Civil Works Spec

ITEM  NO

DESCRIPTION OF ITEM UNIT QUANTITY  RATE (Rs) AMOUNT (Rs)

BMM ISPAT LIMITED

PART ‐ B :CIVIL WORKS

MS‐20

Providing and applying waterproofing treatment in sunken floors and vertical surfaces of toilets and bathrooms etc. with two componentacrylic polymer based flexible cementitious coating of heavy duty flexible coating system with excellent waterproofing using products ofapproved make. 10mm Cement/Sand (Ratio 1:4) protective screed, using Integral Waterproofing Compound added as per manufacturer'sspecifications, shall be applied on top of the membrane. All works shall be carried out as per specifications and manufacturer'sinstructions including all byeworks and at all heights and levels and also as per the directions of the Engineer Incharge.

Sqm 1960.00

Providing cinder fill for filling in the depression of toilets, bath room etc., as per the specifications of specialised waterproofing agencies &finishing the surface even, so as to be suitable to receive the tiles etc at all heights and levels as per specifications and instructions of theEngineer Incharge.       

Cum 780.00

Note :

The measurement shall be on cum  basis.  No deductions shall be made for the areas occupied by pans & other fittings & fixtures.         

MS‐22Providing & fixing 25mm thick PREMOULDED BITUMINOUS FILLER ('Shalitex or other approved manufacture) for expansion jointsincluding painting concrete surface with primer as per specifications, cutting, positioning, supporting, scaffolding & filling with approvedsealing compound etc. complete at all heights and levels as per specifications and instructions of the Engineer Incharge.         

Sqm 350.00

MS‐23Providing & applying polysulphide compound in 'V' grooves of sixe 20mm x 10 mm deep complete at all heights and levels as perspecifications and instructions of the Engineer Incharge.

Rm 100.00

MS‐24

Providing & fixing in position 1mm thick stainless steel (SS 304 grade) flats / angles / tees (of required size) of approvedmake for coveringthe expansion joints in walls, floors, ceiling & columns etc. including drilling slotted holes on both sides, chasing the surfaces whereverrequired, fixing with wooden gutties, rawl plugs & C.P. brass screws, making good the surface etc. complete at all heights and levels asper specifications and instructions of the Engineer Incharge.        

Kgs 335.00

MS‐25Providing and placing in position suitable PVC water stops conforming to IS 12200 : 2001 of approved manufacturer, for constructionjoints between two RCC members and fixed to the reinforcement with bindingwire before pouring concrete, fusion jointing etc. completeat all leads and lifts. The water stop shall be serrated (minimum 225mm wide, 10mm thick) with central bulb of outer dia 25mm).

Rm 1750.00

SECTION  TOTAL ‐ MSTOTAL(EW+AT+CC+MN+FN+FL+WW+ST+AL+SW+RW+MS)

MS‐21

SPEC.NO.MEC/01/56/Q6WX/CIVIL WORKS/TS/201 Rev. 0(c) 2011, MECON LIMITED, All rights reserved.

PAGE 30 OF30

Page 228: Civil Works Spec

BMM ISPAT LIMITED, DANAPUR VILLAGE, HOSPET

SECTION TITLE  AMOUNT IN RUPEES

EW EARTHWORK

AT ANTITERMITE TREATMENT

CC PLAIN AND REINFORCEMENT CONCRETE

MN STONE AND BRICK MASONRY

FN PLASTERING AND SURFACE FINISHES

FL FLOORING, PAVING AND FACING

WW WOOD WORK

ST STEEL AND IRON WORK

AL ALUMINIUM  WORK

SW SANITARY & WATER SUPPLY

RW ROAD WORKS

MS MISCELLANEOUS

TOTAL FOR [ EW+AT+CC+MN+FN+FL+WW+ST+AL+SW+MS ] 

ABSTRACT OF CIVIL WORKS

Page 229: Civil Works Spec

BMM ISPAT LIMITED, DANAPUR VILLAGE, HOSPET

SECTION TITLE  AMOUNT IN RUPEES

EW EARTHWORK

AT ANTITERMITE TREATMENT

CC PLAIN AND REINFORCEMENT CONCRETE

MN STONE AND BRICK MASONRY

FN PLASTERING AND SURFACE FINISHES

FL FLOORING, PAVING AND FACING

WW WOOD WORK

ST STEEL AND IRON WORK

AL ALUMINIUM  WORK

SW SANITARY & WATER SUPPLY

RW ROAD WORKS

MS MISCELLANEOUS

TOTAL FOR [ EW+AT+CC+MN+FN+FL+WW+ST+AL+SW+MS ]

ABSTRACT OF CIVIL WORKS