Upload
kailyn-savery
View
238
Download
1
Tags:
Embed Size (px)
Citation preview
Chapter 16Chapter 16
Conditioning and Conditioning and Distribution of Compressed Distribution of Compressed AirAir
Controlling Dirt, Moisture, Controlling Dirt, Moisture, Temperature, and PressureTemperature, and Pressure
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.3
ObjectivesObjectives
Compare the various methods used to remove dirt from ambient air entering the compressor and in the final filtering of air distributed to the workstations.
Identify the benefits of controlling the temperature of compressed air and the methods used to remove excess heat.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.4
ObjectivesObjectives
Describe the problems caused by excess moisture in the compressed air of a pneumatic system.
Identify the source of moisture in a pneumatic system and various methods used to remove liquid water from a system.
Describe the functions of the pneumatic system receiver and identify construction features of typical designs.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.5
ObjectivesObjectives
Explain the factors that must be considered when establishing the size and location of a receiver for a pneumatic system.
Compare the various types of pipe, tubing, and hose used in pneumatic systems.
Identify and explain the factors that should be used when selecting a conductor for use in a pneumatic system.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.6
ObjectivesObjectives
Explain the design and construction of the various air distribution systems.
Describe the purpose, construction, and operation of the components used for the final preparation of compressed air at a pneumatic system workstation.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.7
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Maximum pneumatic system operating
efficiency is achieved when system compressed air is:– Consistently clean– Free from moisture– At a relatively uniform temperature
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.8
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Atmospheric air contains dirt under even the
best of operating conditions
DeVilbiss Air Power Company
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.9
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Pneumatic systems need to carefully filter the
air taken into the compressor intake to extend the service life of– Compressor– Other system components
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.10
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Correctly designed distribution system
IMI Norgren, Inc.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.11
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Filters used on the intake line of pneumatic
compressors may be– Dry element– Oil wetted– Oil bath
The filter used is based on the type of compressor, atmospheric conditions, and the final use of the compressed air
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.12
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Air at construction sites is dirty
Atlas Copco
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.13
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Painting requires
very clean air
DeVilbiss Air Power Company
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.14
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air The temperature of both the intake and
compressed air is important– Temperature changes are reflected in air pressure
and volume per the general gas law– Temperature influences the ability of air to retain
water vapor
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.15
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Air in a pneumatic system may be cooled
before, during, or after compression– Intake air temperature usually depends on the
location of the compressor air intake– Intercoolers and aftercoolers are used to remove
heat of compression
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.16
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Intercoolers cool compressed air between the
stages of a multiple-stage compressor Aftercoolers cool the air after the air has been
compressed Either air or water can be used as the cooling
medium in these devices
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.17
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Water vapor in air is referred to as humidity
– Essential to our natural environment– Can cause problems in a pneumatic system when
the temperature of the compressed air drops to the dew point and the vapor condenses into liquid water
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.18
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Free air at 70° Fahrenheit can hold 1.14 pounds
of water vapor per 1000 cubic feet By volume, this water is equal to approximately
one pint Retention of water vapor in compressed air is
based on the volume of air
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.19
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Liquid water in a pneumatic system can:
– Wash away lubricants– Increase component wear– Cause inconsistent system operation– Lower the finished quality of products directly
using the air in the manufacturing process
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.20
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Liquid water forms in system lines and
components whenever the air temperature decreases to the dew point
The first step in reducing the liquid water in compressed air is to locate the atmospheric air intake of the compressor in a protected area
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.21
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Condensation of the water vapor in compressed
air can occur in:– Aftercooler units– Moisture separator– System receiver– Distribution system
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.22
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Specific air driers can be used in pneumatic
systems to remove moisture– Chemical desiccant– Refrigeration units– Specialized membranes
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.23
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air The receiver is the storage unit for compressed
air Typically, the receiver is a metal, cylindrical tank
with domed ends In addition to air storage, the receiver:
– Dampens system pressure pulsations– Removes water vapor from system air– In smaller systems, serves as the mount for the prime
mover and compressor
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.24
Conditioning and Conditioning and Storing Pneumatic Storing Pneumatic
System AirSystem Air Formulas are available for calculating the
volume needed for a receiver These formulas consider:
– Cubic feet of free atmospheric air needed per minute
– Desired cycle time– Atmospheric, initial receiver, and final receiver
air pressures
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.25
Air-Distribution SystemAir-Distribution System
The air distribution system delivers high-pressure, conditioned air from the receiver to workstations with a minimum of pressure drop
The type of distribution system depends on the size of the facility and the level of demand for compressed air
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.26
Air-Distribution SystemAir-Distribution System
Four general categories of air distribution systems are used with pneumatic systems– Centralized grid with fixed piping– Decentralized grid with fixed piping– Loop system with fixed piping– Flexible hoses for portable compressor systems
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.27
Air-Distribution SystemAir-Distribution System
Centralized grid has one centralized compressor station and one line network for a facility
Decentralized grid has individual compressors in several locations providing air to smaller distribution networks
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.28
Air-Distribution SystemAir-Distribution System
Centralized grid
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.29
Air-Distribution SystemAir-Distribution System
Decentralized grid
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.30
Air-Distribution SystemAir-Distribution System
Loop system has a main line that forms a continuous loop with compressors located at one or more locations
This design provides maximum airflow with a minimum of pressure drop between the compressors and the individual workstations
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.31
Air-Distribution SystemAir-Distribution System
Loop system
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.32
Air-Distribution SystemAir-Distribution System
Special attention must given to the setup of a hose air distribution in order to minimize pressure drop– Minimize hose length– Reduce the number of couplings– Eliminate kinks in the hose
Care must be taken to protect the hoses from abrasion in the work environment
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.33
Air-Distribution SystemAir-Distribution System
Typical hose distribution system
DeVilbiss Air Power Company
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.34
Air-Distribution SystemAir-Distribution System
Proper sizing of pipe for a fixed air distribution system is difficult
Most systems operate under a variety of work conditions:– Multiple workstations– Varying actuator loads– Intermittent actuator operation
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.35
Air-Distribution SystemAir-Distribution System
Varying loads makes line sizing difficult
DeVilbiss Air Power Company
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.36
Air-Distribution SystemAir-Distribution System
Sizing is based on:– Rated actuator air consumption– Estimate of the time actuators are actually operating– Estimate of the percentage of maximum load
delivered during actuator operation
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.37
Air-Distribution SystemAir-Distribution System
The pipe in air distribution lines should be installed with a pitch of 1 per 10 of line– Allows liquid water to drain to water traps– Water can be remove from traps either manually
or with automatic drain devices
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.38
Air-Distribution SystemAir-Distribution System
Drop lines lead from the main air distribution line to the workstations– Should be attached to the top side of the distribution
line– This prevents water in the distribution lines from
entering the workstation lines
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.39
Air-Distribution SystemAir-Distribution System
Proper slope and drop line installation
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.40
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Final preparation of air at a workstation is accomplished by an FRL unit– Air filter– Pressure regulator– Lubricator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.41
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Typical FRL unit
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.42
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
FRL air filter removes:– Airborne dirt remaining in the atmospheric air
compressed in the system– Rust and scale from the interior of the distribution
lines– Liquid water that has condensed in the drop line– Atomized oil from the operating compressor
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.43
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Typical air filter uses centrifugal force and porous filter material to remove unwanted materials from system air– Inlet passageway swirls the incoming air, creating
a centrifugal force that separates air and contaminants
– Porous filter material traps other undesirable materials
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.44
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Typical FRL air filter
IMI Norgren, Inc.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.45
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
FRL filters typically have a drain
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.46
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
The pressure regulator in an FRL unit reduces system distribution line pressure to the level needed by workstation tools and circuit actuators
Unit is also necessary as air pressure in the distribution line fluctuates due to varying air demands and the characteristics of compressor-capacity control
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.47
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Several regulator designs are available for use in a pneumatic system– Direct-operated regulator– Basic, diaphragm-chamber regulator– Relieving-type regulator– Balanced-poppet valve regulator– Pilot-operated regulator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.48
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Regulators commonly use a flexible diaphragm to sense outlet line pressure and provide the balancing force needed to control airflow through a poppet valve
Only sufficient airflow to maintain the selected workstation pressure is allowed to pass through the poppet valve to the outlet port of the regulator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.49
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Direct-operated pressure regulator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.50
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Many regulators have a diaphragm-control chamber to separate the regulator side of the diaphragm from direct contact with distribution system air– Sensing orifice connects the control chamber and outlet
port– This dampens the reaction of the diaphragm, providing
more sensitive and efficient workstation pressure control
– Protects diaphragm from contaminants
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.51
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Diaphragm-chamber regulator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.52
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Some regulators contain a venting orifice located in the center of the diaphragm– Prevents pressure increase in the outlet port beyond
the regulator pressure setting– The relieving action automatically bleeds air from
the outlet port to the atmosphere– This design feature allows the regulator to act like a
small relief valve
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.53
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Relieving-type pressure regulator
IMI Norgren, Inc.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.54
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Balanced-poppet valve regulators have a design that subjects both ends of the valve poppet to equal air pressure– Allows the valve to be more accurately positioned – Produces better pressure control and improved
response to system load variations
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.55
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Balanced-poppet valve pressure regulator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.56
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Pilot-operated regulators have a sealed pilot-air chamber in place of a control spring and adjustment screw– A second, small, remotely located regulator is used
to control air pressure in the pilot-air chamber– The air pressure in the pilot-air chamber acts as an
air spring to establish the setting of the pilot-operated regulator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.57
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Pilot-operated pressure regulator
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.58
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Installation of a pilot-operated pressure regulator with a secondary regulator
IMI Norgren, Inc.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.59
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Factors to consider when selecting a system regulator are:– Regulator style– Pressure range– Airflow range– Conductor connection size
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.60
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
The lubricator in an FRL unit meters oil into pressurized system air at the workstation
This provides lubrication for system valves, actuators, and air-powered tools
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.61
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Typical FRL lubricator
IMI Norgren, Inc.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.62
Final Preparation of AirFinal Preparation of Airat the Workstationat the Workstation
Rapidly moving system air passing through a lubricator breaks up droplets of oil, forming a mist or fog
This mist is transported through the workstation lines to system components
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.63
Distribution System Distribution System Conductors and Conductors and
FittingsFittings Effectively moving compressed air through a
distribution system requires appropriate conductors and connectors
Conductors can be classified as– Rigid– Flexible
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.64
Distribution System Distribution System Conductors and Conductors and
FittingsFittings Pipe is the most common rigid conductor Hose is the most common flexible conductor Conductors must be properly sized and
assembled for compressed air to be transported from the compressor to actuators with minimal pressure drop
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.65
Distribution System Distribution System Conductors and Conductors and
FittingsFittings Conductors and the associated fittings must
be properly sized
IMI Norgren, Inc.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.66
Distribution System Distribution System Conductors and Conductors and
FittingsFittings Tables are available that provide data on air
pressure loss in standard rigid and flexible conductor sizes using various flow rates
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.67
Distribution System Distribution System Conductors and Conductors and
FittingsFittings Various types of hose are available
Atlas Copco
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.68
Distribution System Distribution System Conductors and Conductors and
FittingsFittings Hose selection, application, and maintenance
are critical to assure air distribution with a minimum loss of pressure– Hoses should be no longer than necessary– Hoses should be no larger than necessary– Use a minimum number of fittings– Layout lines to eliminate kinks and reduce the
number of bends
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.69
Distribution System Distribution System Conductors and Conductors and
FittingsFittings Proper hose selection is important
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.70
Review QuestionReview Question
Name five materials that may be used to make the element in a dry filter for use in pneumatic systems.
A. Paper, B. plastic, C. cloth, D. metal, and E. ceramic.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.71
Review QuestionReview Question
_____ is the temperature at which water vapor in the air begins to condense to form liquid water.
Dew point
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.72
Review QuestionReview Question
Name five places where liquid water may form in the pneumatic system.
A. Intercooler, B. aftercooler, C. moisture separator, D. receiver, and E. system distribution lines.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.73
Review QuestionReview Question
Name two things that occur when warm, humid, high-pressure air cools in the distribution lines of a pneumatic system.
A. The pressure of the air reduces according to the general gas law, and B. liquid water forms when the dew point of the air is reached.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.74
Review QuestionReview Question
In addition to air storage, the receiver dampens air _____ caused by compressor operation.
pulsations
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.75
Review QuestionReview Question
What can be used to supply compressed air to a section of the distribution system that contains equipment using a large volume of air on an intermittent basis without increasing the size of the system?
An auxiliary receiver.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.76
Review QuestionReview Question
What is the most common rigid conductor for major pneumatic systems?
Pipe.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.77
Review QuestionReview Question
Identify two factors that are critical to selecting the actual sizes of the lines used in an air distribution system.
A. Anticipated airflow rate through the lines, and B. pressure drop caused by the lines and fittings.
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.78
Review QuestionReview Question
The _____ compressed-air-distribution system distributes air from a single location to all workstations in a facility.
centralized grid
© Goodheart-Willcox Co., Inc. Permission granted to reproduce for educational use only.79
Review QuestionReview Question
Why is it necessary to use a pressure regulator in the final air preparation unit at a system workstation?
Air pressure in the distribution lines is higher than what is needed for operation of the workstation actuators. Also, the pressure in the distribution lines varies considerably because of the way the compressor-capacity control system functions.