Calculations for Saturday 26 Feb 10

Embed Size (px)

Citation preview

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    1/27

    CalculationsR1 + R2 + Ze give us a measured or calculated value for Zs.

    However to confirm your disconnection time anadjustment must by use of the rule of thumb" to allow

    for conductor temperature.When measuring R1 + R2 the temperature of the

    conductors will be different (normally) from the values inBS 7671 .

    For example in BS 7671 cable temperatures are at 70degrees C for Twin and Earth, their maximum operating

    temperature.

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    2/27

    BS 7671 Values

    The values in BS 7671 are the maximum valuesused by designers when designing installations.These values require adjusting by the person onsite to allow for the difference in resistance due

    to conductor and ambient temperatures.For the person on site a simple Rule of Thumb

    is used. This adjusts the tabulated values fromBS 7671 by a factor of 0.8

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    3/27

    Example 1

    The following 3 circuits where tested on site

    Circuit Maximumvalues toBS 7671

    Adjustedvalue x 0.8

    Measuredvalue

    Circuitcomplies

    1 Type B 32A1.44

    1.44 X 0.8= 1.16(rounded up)

    1.14 Yes

    2 BS 1361

    45A0.96

    0.96 X 0.8

    =0.77(rounded up)

    0.79 No

    3 BS 88-616A2.70

    2.70 X 0.8=2.16

    2.16 Yes

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    4/27

    Exercise

    The following circuits where tested.P rotective Device Measured Value Is the circuit acceptable ?

    BS 303645 A 1.19

    BS 88-625 A

    1.21

    BS 136115 A 2.98

    Type D63 A

    0.16

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    5/27

    Temperature adjustment

    Zs = Ze + (R1 + R2 )x 1.2If an installation has a Ze of 0.6 and a room

    temperature measurement of 25 and acircuit + R1 + R2 of 0.48Step 1 adjust cable resistance to 20 f rom

    table 9B pg 167 OSG0.48/1.02=0.47

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    6/27

    Step 2Use 1.2 adjustment0.47 x 1.2 = 0.56Step 3Add Ze to adjusted value to get Zs0.56 + 0.6 = 1.16Now check this against the Tabulated values in

    BS 7671 .No further adjustment is required.

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    7/27

    R1 + R2 Values.

    Table 9A from the OSGWhen measuring R1 and R2 we can determine the

    length of cable in the circuit.

    This can then be used to check for Volt Drop in thecircuit.

    NOTEA simple way of course would be to simply measure the voltage at the supplyAnd load ends.The difference is your volt drop..

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    8/27

    Example

    A twin and earth 2.5/1.5 cable is used for a socketoutlet 22m in length, from table 9A.

    2.5mm has a resistance of 7.41 m per metre

    1.5mm has a resistance of 12.10 m per metreAdd these two values together19.51 m per metre

    19.51x 22/1000=0.429

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    9/27

    ExerciseA circuit some 33m in length has been installed

    using 4mm single cables.Calculate the R1 + R2 .

    What would the value have been if 4mm/2.5mmhad been used?What is 4/2.5 ?

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    10/27

    Describe how to conduct safe isolationCheck with the client its safe work on the systemIdentify the part of the system to be isolatedPut out warning signsCheck DVI on proving unit or known supplyPower down (switch-off) system and lock off Remove coverTest supply side, E/L E/N N/L Live side

    Test load side, E/L E/N N/L Dead sideCheck DVI on proving unit/known supplyStart work

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    11/27

    Testing of MPBC (R2) test method 2Check with the client its safe work on the systemIdentify the part of the system to be isolatedPut out warning signs and carry out safe isolation.Disconnect all loads.Instrument and equipmentLROM, HSE GS 38 leads, R2 wander lead.Check instrument, leads, null leads with wander lead

    connected.Remove the MPBC from the MET and connect one of the

    test leads to the directly to the MPBCConnect the other test lead to the opposite connectionfor the MPBC on the BS 951 clamp.

    Test the circuit, reading should be in the order of 0.05Reconnect and identify the MPBC

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    12/27

    Testing of Radials C.P.C (R1+R2) method 1 .Check with the client its safe work on the system

    Identify the part of the system to be isolatedPut out warning signs and carry out safe isolation.Instrument and equipmentLROM, HSE GS 38 leads, linking lead.

    Check instrument, leads, null leads with linking leadconnected.

    Connect R1 and R2 together via linking lead at DBTest at all points in the circuit between R1 and R2 checking

    all switches for polarity (dead)Record highest value on test schedule.Remember to remove the link after testing

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    13/27

    Continuity of Ring Final Circuit conductors

    Check with the client its safe work on the systemIdentify the part of the system to be isolated

    Put out warning signs and carry out safe isolation.Disconnect all loads.

    Instrument and equipmentLROM, HSE GS 38 leads.Check instrument, null leads.Disconnect all conductors at DB

    Step 1Connect leads to end to ends of conductors and record as

    follows:

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    14/27

    Step 1Measure end to end using LROM r1 to r1, rn to rn,

    r2 to r2Step 2Connect the outgoing rn to the incoming r1 via

    secure connections and repeat with the

    remaining r1 and rn.Using LROM and socket adaptor test at ALL pointson the circuit including spurs checking operationof all switches. Readings should be

    R1 +RN/4 . Values should be within 0.05 of eachother, higher values require furtherinvestigation(spurs, loose connections etc).

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    15/27

    Step 3Connect the outgoing r2 to the incoming r1 via

    secure connections and repeat with theremaining r1 and r2.

    Using LROM and socket adaptor test at ALL

    points on the circuit including spurs checkingoperation of all switches. Readings should beR1 +R2/4 . Values should be within 0.05 of

    each other, higher values require furtherinvestigation(spurs, loose connections etc).

    Highest value to be recorded on test schedule.

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    16/27

    Socket L to N L to E Reason for reading

    A 0.41 0.54

    B 0.44 NoReading

    C 0.39 0.61

    D NoReading

    0.53

    E 0.60 0.79

    F 0.49 0.52

    G 0.40 0.51

    Ring Final Exercise. Cable is 2.5/1.5 twin and earth. End to End for L-L is 0.80 ohmsMaximum time allowance 6 mins

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    17/27

    Socket L to N L to E Reason for readingA 0.41 0.54 Socket is OK

    B 0.44 NoReading

    Reversed polarity L-N or CPC conductors twisted andnot in terminal.

    C 0.39 0.61 Loose connection on CPC

    D NoReading

    0.53 Reversed polarity L-CPC or Neutral conductorstwisted and not in terminal.

    E 0.60 0.79 Spur

    F 0.49 0.52 Loose connection to neutral

    G 0.40 0.51 Socket is OK

    Ring Final answers

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    18/27

    Insulation ResistanceCheck with the client its safe work on the systemIdentify the part of the system to be isolated

    Put out warning signs and carry out safe isolation.Disconnect all loads/equipment i.e. Dimmers, RCDs etc.

    If whole installation can be tested at the tails, ensure allprotective devices are in place and switched on, all switches,lights etc are closed.

    Instrument; Insulation Resistance Tester, HSE GS 38 leads.

    0 to 50 Volts ac 50v to 500v ac 500 to 1000v ac

    Test Voltage 250 V d.c 500V d.c 1000V d.c

    Min Value to 17 th

    Regs0.5 M 1 M 1 M

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    19/27

    Rt for multiple circuits

    There are 4 circuits with the following values

    2 M 4 M 8 M 12 M Calculate Rt

    Use product sum

    2 x 4 = 8 8 1.332 + 4= 6 6

    1.33 x 8=10.64 1.141.33 +8= 9.33

    1.14 x 12= 13.68 1.041.14 + 12=13.14

    RT= 1.04M

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    20/27

    RT using common denominator

    1/RT=1 / 2 + 1 / 4 + 1/8 + 1/12

    12 + 6 + 3 + 2

    24

    23

    24

    You are looking for RT not 1 over Rt. Swap Rt over

    RT= 1.04M

    Reciprocals

    2x + 4 x + 8x +12x =x =shift RT= 1.04M

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    21/27

    Test between L-L and L-EFor 3 line circuits link out all Live conductors.

    Testing of circuits with electronic devices connectedTest L/N to EFor SELV and 230v circuits tested together use 500V

    d.c. Test between the SELV live conductors and

    those of the other circuits live conductorsElectrical SeparationTest between live conductors of the E/S circuit and

    any other conductors within the same enclosureinc earth min 1 M

    Connect E/S circuit LN together and the other leadto any other conductors within the enclosure.

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    22/27

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    23/27

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    24/27

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    25/27

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    26/27

  • 8/8/2019 Calculations for Saturday 26 Feb 10

    27/27