BW Clip 2 OR 3 YEAR H 2 S, CO, O 2 , SO 2 SINGLE-GAS DETECTOR Part Number 50115903-067 | OM-EN-PALO-A8 | BW Clip Operator Manual BW Clip is a portable, single-gas detector manufactured by BW Technologies by Honeywell (BW). BW Clip continuously measures the concentration of a specific gas in the ambient environment, and activates an alarm when concentrations exceed alarm setpoints. It is your responsibility to respond appropriately to the alarms. BW Clip is a member of the GasAlert family of products. It is compatible with IntelliDoX and MicroDock II automatic test and calibration stations, as well as Fleet Manager II software version 4.0 or higher. For more information, visit the product website at www.honeywellanalytics.com Safety Information: Read First 1. Substitution of components may impair Intrinsic Safety. 2. Periodically test the response of the sensor by exposing the detector to a target gas concentration that exceeds the low alarm setpoint. Manually verify that the audible and visual alarms are activated. 3. Detectors in hibernation mode are not functional. 1. Activate the detector before the activation date on the package. 2. This product is a gas detector, not a measurement device. 3. Ensure that the sensor grill is free of dirt, debris, and is not obstructed. 4. Clean the exterior with a soft, damp cloth. 5. Bump test the detector in a normal atmosphere that is free of hazardous gas. 6. For optimal performance, periodically zero the sensor in a normal atmosphere (20.9% v/v O 2 ) that is free of hazardous gas. Informations de sécurité – À lire au préalable AVERTISSEMENT 1. 2. Le remplacement d’un composant de l’appareil peut compromettre la sécurité intrinsèque du détecteur. Testez périodiquement la réponse du capteur en exposant le détecteur à une concentration de gaz supérieure au seuil d’alarme basse. Vérifiez manuellement que les alarmes sonores et visuelles sont activées. 3. Détecteurs en mode veille prolongée ne sont pas fonctionnels. MISE EN GARDE 1. Activez le détecteur avant la date d’activation sur l’emballage. 2. Ce produit est un détecteur de gaz, pas un dispositif de mesure. 3. Veillez à assurer que la grille du capteur est exempt de saleté, les débris, et ne soit pas obstrué. 4. Nettoyez l’extérieur de l’appareil à l’aide d’un chiffon doux et humide. 5. Veillez à effectuer un test fonctionnel du capteur dans une atmosphère normale qui est exempte de gaz dangereux 6. Pour des performances optimales, zéro périodiquement le capteur dans une atmosphère normale (20,9% v/v O 2 ) qui est exempte de gaz dangereux. BW Clip Factory Calibration Certificate This instrument was factory inspected, tested and calibrated in accordance with the conditions and requirements of our registered Quality System, Operating Standards and Sales Agreements. Getting Started Pushbutton Pushbutton Sensor and sensor grill Sensor and sensor grill Bubble label with product name and gas type Bubble label with product name and gas type Audible alarm Audible alarm LCD LCD LED visual alarms LED visual alarms Infrared port Alligator clip Product label LCD and Symbols Pushbutton prompt. When this symbol is displayed, press and hold the pushbutton until the symbol disappears. BW Clip O 2 models only. Oxygen concentration is measured as percent by volume. BW Clip H 2 S, CO and SO 2 models only. Toxic gas concentration is measured in parts per million. Low alarm and high alarm. These symbols are displayed when a gas concentration that exceeds alarm setpoints is detected. Non-compliance warning. This symbol is displayed when a diagnostic or compliance test fails; when the operating life countdown reaches 24 hours or less; and for up to 30 days after operating life expiry. It is also displayed when certain notifications are enabled through Fleet Manager II via an IntelliDoX station. Real-time clock. This symbol is displayed when real-time clock is enabled through Fleet Manager II via an IntelliDoX station. End of operating life warning. This symbol is displayed when the operating life countdown reaches 24 hours or less. Peak reading. This symbol is displayed when a maximum gas exposure event has occurred within the past 24 hours. Operating life remaining in months (MM) or days (DD). a WARNING a CAUTION Bump test reminder. If the detector is configured to display a bump test reminder, this symbol is displayed when a bump test is due. indicates a failed test. BW Clip O 2 models only. This symbol is displayed when more than 24 hours have elapsed since the last successful zero procedure was performed. indicates a failed test.

BW Clip Manual - Honeywell … · 1. Substitution of components may impair Intrinsic Safety. 2. Periodically test the response of the sensor by exposing the detector to a target gas

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BW Clip Manual - Honeywell … · 1. Substitution of components may impair Intrinsic Safety. 2. Periodically test the response of the sensor by exposing the detector to a target gas

BW Clip2 OR 3 YEAR H2S, CO, O2, SO2 SINGLE-GAS DETECTOR

Part Number 50115903-067 | OM-EN-PALO-A8 | BW Clip Operator Manual

BW Clip is a portable, single-gas detector manufactured by BW Technologies by Honeywell (BW). BW Clip continuously measures the concentration of a specific gas in the ambient environment, and activates an alarm when concentrations exceed alarm setpoints. It is your responsibility to respond appropriately to the alarms.

BW Clip is a member of the GasAlert family of products. It is compatible with IntelliDoX and MicroDock II automatic test and calibration stations, as well as Fleet Manager II software version 4.0 or higher. For more information, visit the product website at www.honeywellanalytics.com

Safety Information: Read First

1. Substitution of components may impair Intrinsic Safety.2. Periodically test the response of the sensor by exposing the detector to a

target gas concentration that exceeds the low alarm setpoint. Manually verify that the audible and visual alarms are activated.

3. Detectors in hibernation mode are not functional.

1. Activate the detector before the activation date on the package.2. This product is a gas detector, not a measurement device.3. Ensure that the sensor grill is free of dirt, debris, and is not obstructed.4. Clean the exterior with a soft, damp cloth.5. Bump test the detector in a normal atmosphere that is free of hazardous gas.6. For optimal performance, periodically zero the sensor in a normal atmosphere

(20.9% v/v O2) that is free of hazardous gas.

Informations de sécurité – À lire au préalableAVERTISSEMENT1.

2.

Le remplacement d’un composant de l’appareil peut compromettre la sécurité intrinsèque du détecteur.

Testez périodiquement la réponse du capteur en exposant le détecteur à une concentration de gaz supérieure au seuil d’alarme basse. Vérifiez manuellement que les alarmes sonores et visuelles sont activées.

3. Détecteurs en mode veille prolongée ne sont pas fonctionnels.

MISE EN GARDE1. Activez le détecteur avant la date d’activation sur l’emballage.2. Ce produit est un détecteur de gaz, pas un dispositif de mesure.3. Veillez à assurer que la grille du capteur est exempt de saleté, les

débris, et ne soit pas obstrué.4. Nettoyez l’extérieur de l’appareil à l’aide d’un chiffon doux et humide.5. Veillez à effectuer un test fonctionnel du capteur dans une atmosphère normale

qui est exempte de gaz dangereux6. Pour des performances optimales, zéro périodiquement le capteur dans une

atmosphère normale (20,9% v/v O2) qui est exempte de gaz dangereux.

BW Clip Factory Calibration CertificateThis instrument was factory inspected, tested and calibrated in accordance with the conditions and requirements of our registered Quality System, Operating Standards and Sales Agreements.

Getting Started

PushbuttonPushbutton

Sensor andsensor grillSensor andsensor grill

Bubble labelwith product name

and gas type

Bubble labelwith product name

and gas type

Audiblealarm

Audiblealarm

LCDLCD

LED visual alarms

LED visual alarms Infrared port

Alligatorclip

Product label

LCD and Symbols

Pushbutton prompt. When this symbol is displayed, press and hold the pushbutton until the symbol disappears.

BW Clip O2 models only. Oxygen concentration is measured as percent by volume.

BW Clip H2S, CO and SO2 models only. Toxic gas concentration is measured in parts per million.

Low alarm and high alarm. These symbols are displayed when a gas concentration that exceeds alarm setpoints is detected.

Non-compliance warning. This symbol is displayed when a diagnostic or compliance test fails; when the operating life countdown reaches 24 hours or less; and for up to 30 days after operating life expiry. It is also displayed when certain notifications are enabled through Fleet Manager II via an IntelliDoX station.

Real-time clock. This symbol is displayed when real-time clock is enabled through Fleet Manager II via an IntelliDoX station.

End of operating life warning. This symbol is displayed when the operating life countdown reaches 24 hours or less.

Peak reading. This symbol is displayed when a maximum gas exposure event has occurred within the past 24 hours.

Operating life remaining in months (MM) or days (DD).

a WARNING

a CAUTION

Bump test reminder. If the detector is configured to display a bump test reminder, this symbol is displayed when a bump test is due. indicates a failed test.

BW Clip O2 models only. This symbol is displayed when more than 24 hours have elapsed since the last successful zero procedure was performed. indicates a failed test.

Page 2: BW Clip Manual - Honeywell … · 1. Substitution of components may impair Intrinsic Safety. 2. Periodically test the response of the sensor by exposing the detector to a target gas

BW Clip2 OR 3 YEAR H2S, CO, O2, SO2 SINGLE-GAS DETECTOR

Activate a New Detector1. Move to a normal atmosphere (20.9% v/v O2) that is free of hazardous

gas.2. Press and hold the pushbutton until a 5 second countdown is displayed,

and then continue to hold until the countdown is complete.3. When the countdown is complete, the LCD and LEDs turn on and then

turn off. The detector performs an internal diagnostic test.4. When the diagnostic test is successful, the alarm setpoints are

displayed and the LEDs flash.5. The sensor stabilization countdown is displayed. During the countdown,

the detector vibrates continuously for 20 seconds. The time required to stabilize varies depending on sensor type. When the countdown reaches 0, the LEDs flash and the audible alarm beeps.

6. When the type of gas detected and the operating life countdown are displayed, the detector is in normal operating mode.

Normal Operating ModeWhen the detector is in normal operating mode, the type of gas detected is permanently displayed. The remaining operating life is displayed until it is disrupted by a pushbutton action, gas alarm, or error event.

Operating LifeWhen the detector is activated for the first time, the operating life countdown is displayed. The countdown displays remaining operating life in months until the countdown reaches 90 days or less before expiry.

90 Days or Less RemainingWhen the operating life countdown reaches 90 days or less before expiry, the countdown display changes to days. The countdown displays the remaining operating life in days until the countdown reaches 24 hours or less before expiry.

24 Hours or Less RemainingWhen the operating life countdown reaches 24 hours or less before expiry, the countdown display changes to hours, and the EXPIRY! warning and non-compliance symbol are displayed.

End of Operating LifeWhen the operating life countdown ends, the detector deactivates and detector safety functions are disabled. It is possible to retrieve event logs for a limited time after expiry. The EXPIRY! warning and non-compliance symbol are displayed for up to 30 days after expiry.

Internal Diagnostic TestsActivated detectors automatically perform one internal diagnostic test every 24 hours. If the internal diagnostic test fails, the diagnostic fail-safe begins.Diagnostic Fail-Safe1. The EXPIRY! warning and non-compliance symbol are displayed.2. The detector beeps and vibrates.3. The LEDs flash 2 times per second for 15 seconds.4. OFF or an error code is displayed. The detector is deactivated.It is possible to retrieve the event logs for a limited time after expiry. If youare unable to retrieve the event logs, contact BW.

Alarms and WarningsAn alarm is initiated when the sensor is exposed to a gas concentration that exceeds alarm setpoints. The alarm persists until the alarm gas concentration returns to an acceptable range. You can use Fleet Manager II via an IntelliDoX station to enable the display of the gas concentration reading during an alarm. Battery life decreases rapidly when the detector is in alarm condition. Low Alarm

Audible: 1 beep per secondVisual: 1 flash per secondVibration: 1 vibration per second

High AlarmAudible: 2 beeps per secondVisual: 2 flashes per secondVibration: 2 vibrations per second

Over-Limit and Under-Limit AlarmsIf the gas concentration is beyond the sensor range, OL (over-limit) or -OL (under-limit) is displayed.Audible: 2 beeps per secondVisual: 2 flashes per secondVibration: 2 vibrations per second

Automatic Zero Reminder for O2 ModelsFor O2 models only, the Automatic Zero Reminder is displayed when more than 24 hours have elapsed since the last successful zero procedure was performed.

Peak ReadingsThe peak readings symbol is displayed when the sensor is exposed to a gas concentration that exceeds the alarm setpoints. It is no longer displayed when more than 24 hours have passed since the last alarm, or when a

successful bump test is performed via an IntelliDoX or MicroDock II station.

Non-compliance Symbol and LED IndicatorsThe non-compliance warning symbol is displayed when:

• an internal diagnostic test fails;• a bump test or zero procedure fails;• a bump test is due, if enabled;• the sensor is exposed to a gas concentration that exceeds alarm

setpoints, if enabled.The non-compliance warning symbol is no longer displayed when more than 24 hours have passed since the last alarm, or when a successful bump test is performed via an IntelliDoX or MicroDock II station. The non-compliance warning symbol is permanently displayed when the service-life countdown reaches 24 hours or less before expiry, and for up to 30 days after expiry.When Non-compliance after gas exposure is enabled through Fleet Manager II via an IntelliDoX station, the LEDs flash in an alternating pattern when the non-compliance warning symbol is displayed. When the symbol is first displayed, the top LEDs flash. After 30 seconds, the side LEDs flash. After 30 seconds, the pattern repeats until the non-compliance warning symbol is no longer displayed.NOTE: When the detector is bump tested via a MicroDock II station, an abnormal test result may occur if non-compliance LEDs are flashing. To suspend the flashing for up to 10 minutes, press and release the pushbutton. When the flashing stops, insert the detector and perform the test. If the bump test fails, the LEDs resume flashing.

Page 3: BW Clip Manual - Honeywell … · 1. Substitution of components may impair Intrinsic Safety. 2. Periodically test the response of the sensor by exposing the detector to a target gas

Recall Events and SettingsWhen the detector is in normal operating mode, press the pushbutton at any time to scroll through events and settings that are not empty or disabled through Fleet Manager II via an IntelliDoX station. Events and settings are displayed in this order:1. Peak Reading, if available, and when a maximum gas exposure event

has occurred within the past 24 hours.2. Time of Peak Reading, if Real-time Clock display is enabled.3. Low Alarm Setpoint4. High Alarm Setpoint5. Real-time Clock, if enabled.6. Firmware Version7. Next Bump Due, if enabled.8. Hibernation, for 2-year H2S and CO hibernation models only.While an event or setting is displayed, press the pushbutton to scroll to thenext available event or setting. If you do not press the pushbutton, or if youhave reached the last available event or setting, the detector returns tonormal operation.

Zero the SensorOver time and through use, the sensor baseline at zero exposure may drift from the manufacturer’s baseline. For optimal performance of O2 models, BW recommends that you zero the O2 sensor once every 24 hours or when the Automatic Zero Reminder is displayed. For all other models, BW recommends that you zero the sensor periodically.Zero Procedure

1. Move to a normal atmosphere (20.9% v/v O2) that isfree of hazardous gas.

2. Press and hold the pushbutton until a 5 secondcountdown is displayed, and then continue to holduntil the countdown is complete.

3. When the countdown is complete, the Zero procedurebegins and ZErO is displayed.

4. When Zero is successful, PASS is displayed, and thenthe detector returns to normal operation.

5. If Zero is not successful, the non-compliance LEDflashes. FAIL and the non-compliance warning symbolare displayed. Press the pushbutton to acknowledgethe result and return to normal operation. The non-compliance warning symbol is displayed and the non-compliance LED flashes. Perform the Zero procedureagain. If the procedure fails again, contact BW.

Bump TestsWhen the detector is configured to display a bump test reminder, the bump test symbol is displayed when a bump test is due. For best results, bump test the detector via an IntelliDoX or MicroDock II station. Bump tests performed via an IntelliDoX or MicroDock II station are logged as bump tests. Manual bump tests are logged as unsafe gas concentrations.

Event LogsThe detector stores the last 35 events that occurred, including peak readings, bump tests and auto zeros. Each record contains:• detector serial number, sensor type and life-remaining;• total number of events that have occurred;• event type and duration;• alarm level(s) in ppm or %;• time elapsed since the alarm occurred in days/hours/minutes;• duration of the alarm (minutes/seconds).Use Fleet Manager II via an IntelliDoX or MicroDock II station to transfer event logs from the detector to a computer. When logs are transferred via an IntelliDoX station, the most recent 35 events are transferred. When logs are transferred via a MicroDock II station, the most recent 10 events are transferred.

Optional SettingsUse Fleet Manager II via an IntelliDoX station to enable the following optional settings for BW Clip detectors.Display Gas Reading During Alarm

When Display gas reading during alarm is enabled, the gas concentration is displayed when a gas alarm event is detected. The gas concentration is displayed until the alarm event ends.

Non-compliance After Gas ExposureWhen Non-compliance after gas exposure is enabled, the LEDs flash in an alternating pattern when the sensor is exposed to a gas concentration that exceeds alarm setpoints. When the gas exposure is detected, the top LEDs flash. After 30 seconds, the side LEDs flash. After 30 seconds, the pattern repeats until more than 24 hours have passed since the last alarm, or when a successful bump test is performed via an IntelliDoX or MicroDock II station.Real-time Clock Display

When Real-time Clock Display is enabled, you can display the current time by pressing the pushbutton to Recall Events and Settings, and then continuing to press the pushbutton until the time is displayed.Time may be displayed in 12-hour or 24-hour clock format.

HibernationHibernation is a factory installed feature that is available for 24-month H2S and CO detectors. When Hibernation is activated, the operating life countdown is suspended. Use Hibernation to deactivate the detector for 7 days or longer, up to a maximum of 12 months. When Hibernation is activated, all detector safety functions are disabled.Activate Hibernation via BW Clip Hibernation Case

1. Have ready a BW Clip Hibernation Case. To purchasea Case, contact BW or an authorized distributor.

2. Move to a normal atmosphere (20.9% v/v O2) that isfree of hazardous gas.

3. Verify that the detector is in normal operating mode.4. Press the pushbutton to Recall Events and Settings,

and then continue to press the pushbutton until Hibis displayed.

5. While Hib is displayed, press the pushbutton until a 5 secondcountdown is displayed. When the countdown is complete, the20-second Hibernation counter is displayed.

6. While the Hibernation counter is displayed, place the detector into aBW Clip Hibernation Case and then close the case firmly. The detectorenters Hibernation mode. All detector safety functions are disabled.

7. To reactivate the detector, open the case.

Activate Hibernation through Fleet Manager II via IntelliDoX1. Use Fleet Manager II to activate Hibernation on Insertion via an

IntelliDoX station, and then insert the detector in the configuredstation. The detector event logs are retrieved, and the detector entersHibernation mode. All safety functions are disabled, and the detectormay be removed from the IntelliDoX station.

2. To reactivate the detector, press and hold the pushbutton until a5 second countdown is displayed, and then continue to hold until theLCD and LEDs turn on and off. The detector performs a self-diagnostictest. When the test is successful, the type of gas detected and theremaining operating life are displayed. The detector is in normaloperating mode.

3. For more information, refer to the operator manuals for the IntelliDoXstation and Fleet Manager II software version 4.0 or higher.

Page 4: BW Clip Manual - Honeywell … · 1. Substitution of components may impair Intrinsic Safety. 2. Periodically test the response of the sensor by exposing the detector to a target gas

BW Clip2 OR 3 YEAR H2S, CO, O2, SO2 SINGLE-GAS DETECTOR

About this PublicationThis publication is an operator guide for BW Clip portable single-gas detectors manufactured by BW Technologies by Honeywell. It is intended for use with the following models:• 24- and 36-month H2S and CO Detectors• 24-month O2 detector• 24-month SO2 detector

Copyright, Notice, TrademarksWhile this information is presented in good faith and believed to be accurate, BW Technologies by Honeywell (BW) disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.

In no event is BW liable to anyone for any indirect, special or consequential damages. The content in this document is subject to change.

Contact UsCorporate Headquarters

BW Technologies by HoneywellSuite 110 4411-6 Street SECalgary, AlbertaCanada, T2G 4E8Toll-free: 1-800-663-4164

AmericasBW Technologies by Honeywell405 Barclay Blvd.Lincolnshire IL USA 60069Toll-free:1-888-749-8878

EuropeBW Technologies by HoneywellHatch Pond House4 Stinsford RoadNuffield Industrial EstatePoole Dorset BH17 0RZ United KingdomToll-free: +44(0)1295 700300

OtherBW Technologies by HoneywellToll-free: [email protected]

Warranty Registrationwww.honeywellanalytics.com/support/product-registration

Maximum Operating Life24-month Detector

2 years after activation, assuming 2 minutes of alarm time per day.Note: 24-month H2S and CO detectors that use hibernation may extend the service period of the detector up to an additional year. The service life will end once the detector reaches 24 months of actual operation. Hibernation provides a maximum service life of 36 months.

36-month Detector3 years after activation, assuming 1 minute of alarm time per day.

Detection RangeH2S 0 to 100 ppmCO 0 to 300 ppmO2 0 to 25% by volumeSO2 0 to 100 ppm

Factory Alarm SetpointsLow Alarm High Alarm

H2S 10 ppm 15 ppmCO 35 ppm 200 ppmO2 19.5% vol 23.5% volSO2 5 ppm 10 ppm

Use Fleet Manager II via an IntelliDoX station to adjust alarm setpoints. For more information, refer to the operator manuals for Fleet Manager II software version 4.0 and the IntelliDoX automatic test and calibration station.

Ratings and CertificationsThe BW Clip is in conformity with the following standards:

UL 913 8th Edition

UL

UL 60079-0:2013, UL 60079-11:2013CSA C22.2 No. 157-92:2012, CSA C22.2 No. 60079-0:2011,

CSA C22.2 No. 60079-11:2014EN 60079-0:2012 +A11:2013, EN 60079-11:2012

IEC 60079-0:2011 IEC 60079-11:2011

ABNT NBR IEC 60079-0:2008 ABNT NBR IEC 60079-11:2009

Classified by UL to both US and Canadian Standards as intrinsically safe for Class I, Division 1, Group A, B, C, D and Class I, Zone 0, Group IIC.

ATEXCE 0539 II 1GEx ia IIC T4 Ga IP66/67DEMKO 14 ATEX 1356

CEEuropean Conformity

EU Declaration of Conformitywww.honeywellanalytics.com

IECExEx ia IIC T4 Ga IP66/67 IECEx UL 14.0063

INMETROEx ia IIC T4 Ga DNV 15.0024

KTL15-KA4BO-03061

SpecificationsShelf Life

H2S One (1) year before activation CO One (1) year before activation O2 Six (6) months before activation SO2 One (1) year before activation

Instrument Weight alligator clip included

92 grams (3.2 ounces)Instrument Dimensions alligator clip included

41 x 50 x 87 millimeters (1.6 x 2.0 x 3.4 inches)

Operating TemperaturesH2S -40° to +50°C (-40° to +122°F)CO -30° to +50°C (-22° to +122°F)O2 -20° to +50°C (-4° to +122°F)SO2 -30° to +50°C (-22° to +122°F)

5% to 95% relative humidity (non-condensing)

1 http://www.honeywellanalytics.com/~/media/honeywell-analytics/products/bw-clip/docu-ments/certi icates/korea-certi ication_bw-clip-15ka-4bo0306

Visual AlarmFlashing, wide-angled alarm lens with red LEDs plus alarm LCD readout

DisplayLiquid crystal display (LCD)

Sensor TypeElectrochemical cells

BatteryLithium, non-replaceable

Ingress ProtectionIP 66/67

Alarm SetpointsInstant low and instant high

CalibrationH2S not requiredCO not requiredSO2 not requiredO2 Perform the Zero procedure

once every 24 hours or when the Automatic Zero Reminder is displayed.

Intended UseThis product is classified for use in hazardous atmospheres that are not more than 21% v/v O2

RecyclingThis instrument contains a lithium battery. Do not mix with the solid waste stream. Spent batteries should be disposed of by a qualified recycler or hazardous materials handler.

Products may contain materials that are regulated for transportation under domestic and international dangerous goods regulations. Return product in compliance with appropriate dangerous goods regulations. Contact freight carrier for further instructions.

Limited Warranty and Limitation of LiabilityBW Technologies (BW) warrants this product to be free from defects in material and workmanship under normal use and service for a period of two or three years (depending upon detector), beginning on the date of activation. 24-month H2S and CO detectors are covered for up to an additional 12 months when hibernation is used, limited by a total of 24 months of detector operation. This Warranty is valid only if the detector is activated by the date on the package. This warranty extends only to the sale of new and unused products to the original buyer.

BW’s warranty obligation is limited, at BW’s option, to refund of the purchase price, repair, or replacement of a defective product that is returned to a BW authorized service center within the warranty period. In no event shall BW’s liability hereunder exceed the purchase price actually paid by the buyer for the Product.

This warranty does not include: • fuses, disposable batteries or the routine

replacement of parts due to the normal wear and tear of the product arising from use;

• any product which in BW’s opinion, has been misused, altered, neglected or damaged by accident or abnormal conditions of operation, handling or use; or

The obligations set forth in this warranty are conditional on: 1) proper storage, installation, calibration,

use, maintenance and compliance with the product manual instructions and any other applicable recommendations of BW;

2) the buyer promptly notifying BW of any defect and, if required, promptly making the product available for correction. No goods shall be returned to BW until receipt by the buyer of shipping instructions from BW; and

3) the right of BW to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period.

THE BUYER AGREES THAT THIS WARRANTY IS THE BUYER’S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. BW SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING LOSS OF DATA, WHETHER ARISING FROM BREACH OF WARRANTY OR BASED ON CONTRACT, TORT OR RELIANCE OR ANY OTHER THEORY.

Since some countries or states do not allow limitation of the term of an implied warranty, or exclusion or limitation of incidental or consequential damages, the limitations and exclusions of this warranty may not apply to every buyer. If any provision of this warranty is held invalid or unenforceable by a court of competent jurisdiction, such holding will not affect the validity or enforceability of any other provisions.

Audible Alarm≈ 95 dB at 10 cm (3.9 in)

Internal Vibrating • any damage or defects attributable to repair of the product by any person other than an authorized dealer, or the installation of unapproved parts on the product.

Internal VibratingOperates to -10°C (+14°F)

Intrinsic Safety Temperature Range-40 °C to +50 °C (-40 °F to +122 °F)