28
Brought to you by: Connecticut Energy Code Frederick F. Wajcs Senior Energy Engineer Northeast Utilities February 10, 2011

Brought to you by: Connecticut Energy Code Frederick F. Wajcs Senior Energy Engineer Northeast Utilities February 10, 2011

Embed Size (px)

Citation preview

Brought to you by:

Connecticut Energy CodeFrederick F. WajcsSenior Energy EngineerNortheast Utilities

February 10, 2011

2

Current ConnecticutEnergy Code

2006 International Energy Conservation Code (IECC)

with ASHRAE/IESNA Standard 90.1-2004

as reference document

3

Next ConnecticutEnergy Code

2009 IECC

With Standard 90.1-2007as reference document

Anticipated implementation: Second half 2011

4

Next ConnecticutEnergy CodeRequired for receipt of the American

Recovery and Reinvestment Act (ARRA) funds

ARRA also requires 90% compliance by December 2017• www.energycodes.gov/arra/

compliance_evaluation.stm• On site surveys anticipate participation of

building officials, design professionals, contractors and suppliers

5

Compliance ChecklistsCommercial Building Data Collection Checklist

ANSI/ASHRAE/IESNA Standard 90.1-2007

Date: Name of Evaluator(s):

Building Name & Address: Conditioned Floor Area: ft2

Building Contact: Name: Phone: Email:

Compliance Approach: Prescriptive Trade-Off (Section 5.6) Performance (ECB Section 11)

State: Jurisdiction:

Building Use: Office Retail Storage Education Lodging Dining Public Health Residential Other

Project Type: New Construction Addition Renovation Valuation (If Renovation): $

Complies Item Number Plan Review Y N N/A Comments/Notes/Findings

PR1 [4.2.2]1

Plans and/or specifications provide all information with which compliance can be determined for the building envelope and delineate and document where exceptions to the standard are claimed.

PR2 [4.2.2]1

Plans and/or specifications provide all information with which compliance can be determined for the mechanical systems and equipment and delineate and document where exceptions to the standard are claimed.

PR3 [4.2.2]1

Plans and/or specifications provide all information with which compliance can be determined for the service water heating systems and equipment and delineate and document where exceptions to the standard are claimed.

PR4 [4.2.2]1

Plans and/or specifications provide all information with which compliance can be determined for the lighting and electrical systems and equipment and delineate and document where exceptions to the standard are claimed. Information provided should include interior and exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices.

PR5 [6.4.2]1

HVAC load calculations submitted.

PR6 [7.4.01]1

Service water heating load calculations submitted.

PR7 [6.7.2.4]1

Detailed instructions for HVAC systems commissioning included on the plans or specifications.

PR8 [6.7.2.1]1

Construction documents require HVAC “as-built” drawings submitted within 90 days of system acceptance.

PR9 [8.4.1.1, 8.4.1.2]1

Feeder and branch circuit load and sizing calculations provided that allow verification of voltage drop.

PR10 [8.7.1 8.7.2]1

Construction documents require as-built drawings for electric power systems and O&M manual for electrical power systems and equipment.

Additional Comments:

6

2009 IECC Administration

Applies to residential and commercial buildings

Regulates the design and construction of buildings for the effective use of energy

7

2009 IECC Administration

Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to provisions for new construction

Change in occupancy or use• That increases either fossil fuel or electrical

energy

• Lighting shall comply when space changes from one lighting building area type to another

8

Exceptions

Storm windows over existing fenestration and glass only replacement

Cavities completely filled with insulation or not exposed Reroofing

• Roofs without insulation in cavity and where sheathing or insulation is exposed shall comply

Replacement of existing exterior door does not require installation of vestibule as long as existing vestibule is not removed

Alteration that replaces less than 50% of luminaires in a space as long as installed interior lighting power is not increased

Lamp and ballast replacement within existing luminaires as long as installed interior lighting power is not increased

9

Commercial Projects Shall Comply

Entirely with Chapter 5Or

Entirely with Standard 90.1-2007

10

ConstructionDocumentation Information Insulation material and their R-value Fenestration U-factors and SHGCs Area-weighted U-factor and SHGC calculations Mechanical system design criteria Mechanical and service water heating system and equipment

types, sizes and efficiencies Economizer description Equipment and systems controls Fan motor horsepower and controls Duct sealing, duct and pipe insulation and location Lighting fixture schedule with wattage and control

narrative Air sealing details

11

Envelope

IECC, 90.1Residential and 90.1 Non- Residential Requirements are essentially the same (except skylights) and more stringent than 2006 IECC

90.1 has requirements for semi-heated spaces

Projects with vertical fenestration area (40%) or skylight area (3%) exceeding IECC allowances must use 90.1

IECC has no SHGC requirements for fenestration with projection factor ≥0.25

12

Mechanical

Air cooled air conditioner & heat pumps• Efficiency requirements higher than 2006

IECC• 90.1 has IEER requirements for

≥65,000Btu/hWater & evaporatively cooled air

conditioner• Efficiency requirements are mostly the same

as 2006 IECC• 90.1 has IEER requirements

Efficiency requirements for SPVAC and SPVHP in 90.1

13

Mechanical

Compliance paths for water chillers• Path A for chillers expected to operate a

significant time near full load conditions• Path B for chillers expected to operate a

significant time at part load conditionsEfficiency requirements for water chillers

• kW/ton for water cooled• Higher full load values but lower part load

values• Air cooled cannot be used for Path B

compliance

14

Mechanical

Some boilers have combustion efficiency & thermal efficiency requirements in 2009 IECC

Efficiency requirements for boilers are generally higher in 90.1

Heat rejection equipment requirements are in 90.1 but not in IECC

15

Mechanical – Controls

Zone thermostatic controlsOff-hour

• Setback/Shutdown• Optimum start (Systems >10,000 cfm)

only in 90.1• Exceptions for systems:

<6,800 in IECC <15,000 in 90.1

16

Mechanical – Controls

Ventilation system• Gravity dampers allowed on outside air

supply & exhaust in buildings <3 stories• Gravity dampers allowed on stair and

elevator shafts in buildings <3 stories in IECC

• Motorized dampers required elsewhere and must have shutoff control

• Ventilation fans Capability to reduce to minimum required in IECC Off-hour shutdown for fans >3/4 hp in 90.1

17

Mechanical - Controls

Demand control ventilation for spaces >500 sf & design occupancy >40 persons/ 1,000 sf

Single zone VAV for chilled water AHU ≥5 hp in 90.1

18

Mechanical

Duct and pipe insulation requirements are different in IECC and 90.1

Duct sealing requirementsDuct leakage tests

19

HVAC Completion Requirements

Record drawings covered in 90.1Operating manualMaintenance manualSystem balancingSystem commissioning for

conditioned area >50,000 sf in 90.1

20

Mechanical

Economizers• Air side ≥54,000 Btu/h in IECC

Total capacity without economizers not to exceed 480,000Btu/h or 20% economizer capacity

• Air side ≥135,000 Btu/h in 90.1Fan power limitations in IECC and

90.1Speed control on VAV fan motors

≥10 hp

21

Mechanical – Hydronic Systems

Flow modulation (≥300,000 Btu/h for IECC)

Speed control on variable flow systems (>50 hp Pumps in 90.1)

Equipment isolationTemperature reset controlsTwo-way valves on hydronic heat

pumps (>10 total pump system power in IECC)

22

Mechanical

Energy recoveryExhaust hoodsRadiant heating systems required

for unenclosed spacesHot gas bypass limitations

23

Service Water Heating

Equipment efficienciesPool heatersPipe insulationPool coversHeat trapsAllowed for space heating in 90.1

24

Lighting

Building area method lighting power densities in IECC and 90.1

Space-by-space method lighting power densities in 90.1

Meet lighting power densities requirements when replacing ≥50% of luminaires

Exterior lighting power allowances

25

Lighting – Controls

Automatic interior lighting shutoff in all spaces • Holiday scheduling included in IECC

Space controls• Bi-level capability in IECC• Automatic controls in defined spaces in 90.1• For each interior enclosed space

Individual independent controls in daylight zones in IECC

26

Detailed Comparison

On Connecticut Chapter of ASHRAE web page www.ctashrae.org

Spreadsheet showing requirements in 90.1-2001, 90.1-2004 and 90.1-2007

Spreadsheet showing requirements in 2006 IECC, 2009 IECC and 90.1-2007

27

Training

International Code Council training sponsored by State of Connecticut Office of Education and Data Management

To register for :

http://www.iccsafe.org/Education/Courses/Pages/CT-Energy-list.aspx

28

Thank You!

Fred WajcsSenior Energy EngineerConservation and Load [email protected]