BIDDING & CONTRACT REQUIREMENTS Section 00902 – AMENDMENT NUMBER 2
AMENDMENT NUMBER 2 00902-1
ISSUE DATE: 25 April 2016
TO: PROSPECTIVE OFFERORS AND PLAN HOLDERS
FROM: h. michael bohnsack ARCHITECTS 600 West Main Street Suite 2 Post office Box 820 Carbondale, Illinois 62901 618 457 5709 Fax 618 457 5638
SUBJECT: AMENDMENT NUMBER 2 TO THE SOLICITATION DOCUMENTS FOR:
AAFES SOLICITATION NO. PL-K-REC-11-042-16-008
MAIN STORE IMAGE UPGRADE FT. BUCHANAN, PUERTO RICO AAFES PN: 5256-10-000004
The following Amendment is supplemental to the Drawings and Specifications and shall be a part of the Solicitation Documents as per the general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Sections contained within the Project Manual dated 29 February 2016.
Receipt of this Amendment must be acknowledged in accordance with the instructions on the reverse of the amendment (AAFES Form 4400-18). Failure to acknowledge this Amendment on proposal OR returning signed amendment (with proposal) may result in proposal being determined non-responsive.
***************************************************************************************************************** DRAWINGS:
1. Sheet T-1.02, PHASING FLOOR PLAN; Delete Sheet T-1.02, PHASING FLOOR PLAN in entirety and insert the following into the original set of Drawings:
Sheet AMT-2/T-1.02, PHASING FLOOR PLAN dated 25 April 2016 attached to this Amendment.
2. Sheet AMT-1/D-1.01, DEMOLITION FLOOR PLAN AREA A; Delete Sheet AMT-1/D-1.01, DEMOLITION FLOOR PLAN AREA A as replaced by Amendment 01 in entirety and insert the following into the set of Drawings reflecting both AMT-1 and AMT-2 modifications:
Sheet AMT-2/D-1.01, DEMOLITION FLOOR PLAN AREA A dated 25 April 2016 attached to this Amendment.
3. Sheet D-1.02, DEMOLITION FLOOR PLAN AREA B; Delete Sheet D-1.01, DEMOLITION FLOOR PLAN AREA B in entirety and insert the following into the original set of Drawings:
Sheet AMT-2/D1.02, DEMOLITION FLOOR PLAN AREA B dated 25 April 2016 attached to this Amendment.
4. Sheet AMT-1/D-6.10, DEMOLITION INTERIOR ELEVATIONS; Delete Sheet AMT-1/D-1.02, DEMOLITION INTERIOR ELEVATIONS as replaced by Amendment 01 in entirety and inset the following into the set of Drawings reflecting both AMT-1 and AMT-2 modifications:
Sheet AMT-2/D-6.10, DEMOLITION INTERIOR ELEVATIONS dated 25 April 2016 attached to this Amendment.
5. Sheet A-7.02, REFLECTED CEILING PLAN AREA B; Delete Sheet A-7.02, REFLECTED CEILING PLAN AREA B in entirety and insert the following into the original set of Drawings:
AMENDMENT NUMBER 2 00902-2
Sheet AMT-2/A-7.02, REFLECTED CEILING PLAN AREA B dated 25 April 2016 attached to this Amendment.
6. Sheet A-9.11, FINISH FLOOR PLAN AREA B; Delete Sheet A-9.11, FINISH FLOOR PLAN AREA B in entirety and insert the following into the original set of Drawings:
Sheet AMT-2/A-9.11, FINISH FLOOR PLAN AREA B dated 25 April 2016 attached to this Amendment.
7. Sheet EQ-1.00, OVERALL EQUIPMENT PLAN; Delete Sheet EQ-1.00, OVERALL EQUIPMENT PLAN in entirety and insert the following into the original set of Drawings:
Sheet AMT-2/EQ-1.00, OVERALL EQUIPMENT PLAN dated 25 April 2016 attached to this Amendment.
8. Sheet EQ-1.01, EQUIPMENT PLAN & ELEVATIONS-CUSTOMER SERVICE; Delete Sheet EQ-1.01, EQUIPMENT PLAN & ELEVATIONS-CUSTOMER SERVICE in entirety and insert the following into the original set of Drawings:
Sheet AMT-2/EQ-1.01, EQUIPMENT PLAN & ELEVATIONS-CUSTOMER SERVICE dated 25 April 2016 attached to this Amendment.
9. Sheet AMT-1/E-1.01, FLOOR PLAN AREA A LIGHTING; Add the following TYPICAL NOTE:
TYPICAL NOTE: NEW VIRA WALL LIGHT FIXTURES WILL BE AAFES FURNISHED (AF) AND CONTRACTOR INSTALLED (CI) WHERE NEW LIGHT FIXTURES ARE INDICATED. EXISTING WALL MOUNTED WALL WASHER FIXTURES SHALL BE DISCONNECTED, REMOVED, SALVAGED, PROTECTED AND REINSTALLED BY CONTRACTOR.
10. Sheet AMT-1/E-1.02, FLOOR PLAN AREA B LIGHTING; Add the following TYPICAL NOTE:
TYPICAL NOTE: NEW VIRA WALL LIGHT FIXTURES WILL BE AAFES FURNISHED (AF) AND CONTRACTOR INSTALLED (CI) WHERE NEW LIGHT FIXTURES ARE INDICATED. EXISTING WALL MOUNTED WALL WASHER FIXTURES SHALL BE DISCONNECTED, REMOVED, SALVAGED, PROTECTED AND REINSTALLED BY CONTRACTOR.
11. Sheet AMT-1/E-2.01, FLOOR PLAN AREA A POWER; Delete Sheet AMT-1/E-2.01, FLOOR PLAN AREA A POWER as replaced by Amendment 01 in entirety and insert the following into the set of Drawings reflecting both AMT-1 and AMT-2 modifications:
Sheet AMT-2/E-2.01, FLOOR PLAN AREA A POWER dated 25 April 2016 attached to this Amendment.
12. Sheet AMT-1/E-2.02, FLOOR PLAN AREA B POWER; Delete Sheet AMT-1/E-2.02, FLOOR PLAN AREA B POWER as replaced by Amendment 01 in entirety and insert the following into the set of Drawings reflecting both AMT-1 and AMT-2 modifications:
Sheet AMT-2/E-2.02, FLOOR PLAN AREA B POWER dated 25 April 2016 attached to this Amendment.
13. Sheet AMT-1/E-3.01, FLOOR PLAN AREA A SPECIAL SYSTEMS; Delete Sheet AMT-1/E-3.01, FLOOR PLAN AREA A SPECIAL SYSTEMS as replaced by Amendment 01 in entirety and insert the following into the set of Drawings reflecting both AMT-1 and AMT-2 modifications:
Sheet AMT-2/E-3.01, FLOOR PLAN AREA A SPECIAL SYSTEMS dated 25 April 2016 attached to this Amendment.
AMENDMENT NUMBER 2 00902-3
14. Sheet AMT-1/E-5.01, RISER DIAGRAM ELECTRICAL; Delete Sheet AMT-1/E-5.01, RISER DIAGRAM ELECTRICAL as replaced by Amendment 01 in entirety and insert the following into the set of Drawings reflecting both AMT-1 and AMT-2 modifications:
Sheet AMT-2/E-5.01, RISER DIAGRAM ELECTRICAL dated 25 April 2016 attached to this Amendment.
***************************************************************************************************************** The original Solicitation Documents and Amendment 01 remain in full force and effect, except as modified herein.
Proposals are due as originally advertised.
Sincerely,
h. michael bohnsack ARCHITECTS
END OF AMENDMENT
This Amendment consists of three (3) Pages and attached Drawing Sheets AMT-2/T-1.02, AMT-2/D-1.01 w/AMT-1 Changes Included, AMT-2/D-1.02, AMT-2/D-6.10 w/AMT-1 Changes Included, AMT-2/A-7.02, AMT-2/A-9.11, AMT-2/EQ-1.00, AMT-2/EQ-1.01, AMT-2/E-2.01 w/AMT-1 Changes Included, AMT-2/E-2.02 w/AMT-1 Changes Included, AMT-2/E-3.01 w/AMT-1 Changes Included and AMT-2/E-5.01 w/AMT-1 Changes Included, all dated 25 April 2016.
MATCH LINE 1 MATCH LINE 1
LOCKER
ROOM
MEN WOMEN LOCKER
ROOM
STAIR MECHANICAL
ROOM
JAN.
RCF, JSS, DRS
LDH
Floor Plan
Area A
Power
AS SHOWN
RE-C
600 West Main Street Suite 2
Post Office Box 820
618 457 5709 Fax 618 457 5638
Carbondale, Illinois 62901
Main Store
Image Upgrade
Ft. Buchanan, Puerto Rico
LICENSE
SIGNATURE
EXPIRATION DATE
CURRENT DATE
30 November 2017
29 February 2016
25 April 2016
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main Street ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
6235161
A
B
C
MPA
ELEC.
RECEIVING
OFFICE STORAGE
CONVEYOR
AREA
SOFTLINES SOFTLINES
RETAIL
STORAGE
OPS
MANAGER
ELCC/ SECURE
ROOM
STORE
MANAGER
S&M
MANAGER
RECEPTION
BREAK ROOM
SAMS OFFICES
RPOS
STAIRS
MPA
MATCH LINE 1
MATCH LINE 2
MATCH LINE 1
MATCH LINE 2
JSS
RCF
Floor Plan
Area B
Power
AS SHOWN
RE-C
600 West Main Street Suite 2
Post Office Box 820
618 457 5709 Fax 618 457 5638
Carbondale, Illinois 62901
Main Store
Image Upgrade
Ft. Buchanan, Puerto Rico
LICENSE
SIGNATURE
EXPIRATION DATE
CURRENT DATE
30 November 2017
29 February 2016
25 April 2016
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main Street ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
6235161
A
B
C
CLASS SIX
CUSTOMER
SERVICE
TOBACCO
RETURN
CASHIER
VAULT
CHECKOUT
MAIN STORE
ENTRY
SOFTLINES
SOFTLINES
SOFTLINES
SOFTLINES SOFTLINES
SOFTLINES SOFTLINES
JEWELRY/
COSMETICS
HARDLINES
HARDLINES
FOOD/
CANDY
MATCH LINE 1 MATCH LINE 1
JSS
RCF
Floor Plan
Area A
Special Systems
AS SHOWN
RE-C
600 West Main Street Suite 2
Post Office Box 820
618 457 5709 Fax 618 457 5638
Carbondale, Illinois 62901
Main Store
Image Upgrade
Ft. Buchanan, Puerto Rico
LICENSE
SIGNATURE
EXPIRATION DATE
CURRENT DATE
30 November 2017
29 February 2016
25 April 2016
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main Street ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
6235161
A
B
C
MPA
ELEC.
RECEIVING
OFFICE STORAGE
CONVEYOR
AREA
SOFTLINES SOFTLINES
RETAIL
STORAGE
OPS
MANAGER
ELCC/
SECURE
ROOM
STORE
MANAGER
S&M
MANAGER
RECEPTION
BREAK ROOM
SAMS OFFICES
RPOS
STAIRS
MPA
LOCKER
ROOM
MEN WOMEN LOCKER
ROOM
STAIR MECHANICAL
ROOM
JAN.
OFFICE STORAGE
JSS,JDR, DRS
RCF
Riser Diagram
- Electrical
AS SHOWN
RE-C
600 West Main Street Suite 2
Post Office Box 820
618 457 5709 Fax 618 457 5638
Carbondale, Illinois 62901
Main Store
Image Upgrade
Ft. Buchanan, Puerto Rico
LICENSE
SIGNATURE
EXPIRATION DATE
CURRENT DATE
30 November 2017
29 February 2016
25 April 2016
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main Street ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
6235161