W o r l d C l a s s P o w e r S y s t e m s
TelecomModular DC Power Supply Systems BLTwith remote monitoring system MCU DC-DC Converters, Inverters
With the increasing demands on powersupplies for today´s telecommunicationsindustry Benning have developed awide range of power modules.
Benning powersupply systemshave a modularstructure and can be adapted all customerrequirements.
Systems are available with wall-mountedcabinets and floor-standing cabinets.Using combination cabinets it is possible to build in batteries with theplug-in power supplies.
The following switched mode plug-inrectifiers and BLT-systems meet therequirements for compact and reliablepower supplies and have the followingprincipal features:
• efficiency ≥ 90 %• power factor ≥ 0,93 / 0,98• radio interference suppression to
EN 55022 level B• noise voltage
≤ 1 mV or 2 mV CCITT• excellent transient response • temperature-controlled voltage
characteristic
The modular structure of the BLT-systems allows adaptation to almostall requirements. All BLT-systems are
delivered with the monitoring systemMCU 500/1000 or MCU 2000+.
++
+
U<
DC StromversorgungBetriebStörung U < 2,1 V/ZErhaltungsladenLadenBatterietestBatterietest negativDringender AlarmNichtdringender AlarmNetzstörungGleichrichterstörungBatterie entl. U < 1,8 V/ZSicherung ausgelöstModemstörung
LED Test / Reset
La D
efen
se,P
aris
; –
BENN
ING
,po
wer
whe
re it
’s n
eede
d,
Flexible, modular Structure
BLT-Power Supply-Systems
PDT 800
24 V - 15 A
48 V - 15 A
60 V - 12 A
PDT 1800
24 V - 50 A
48 V - 33 A
60 V - 27 A
PDT 400
48 V - 7,5 A PDT 650
48 V - 12 A
60 V - 10 A
Rectifier range PDT 400,PDT 650, PDT 800, PDT 1800
This range is used for smaller powersystems. The mechanical layout allowsthe arrangement of 6 plug-in rectifiers(PDT 400 + PDT 650) side by side inone 19“ rack. (Only without MCU interface available.) The units PDT 800and PDT 1800 are with or without MCUinterface available, 4 plug-in rectifierscan be fitted in one 19“ rack.
Plug-in Rectifiers
Telecom_14S_2in1_eng.qxd 04.07.2001 9:30 Uhr Seite 2
Range PDD 3000
The forced-ventilated design is ratedfor an output power of 3000 W. Themechanical layout of this unit allowsthe arrangement of 3 rectifiers eachon one level of a 19“ rack. (with orwithout MCU interface)
PDT 3000
24 V - 75 A
48 V - 50 A
60 V - 40 A
BLT 150
Power supplies up to several thousandsAmps can be constructed with thisrange. The plug-in rectifiers have a19“ mechanical layout and are built
into corresponding cabinets. The tem-perature controlled forced ventilationallows a very compact design.(with MCU interface)
PDE 7200
24 V - 200 A
48 V - 125 A
60 V - 100 A
PDE 15000
48 V - 225 A
60 V - 200 A
BLT-Line 2500, threephase
Range PDE 7200 / 15000
Telecom_14S_2in1_eng.qxd 04.07.2001 9:31 Uhr Seite 3
DC-DC converters
PCT 300 PDC 960 - 1400Technical data
Type table
La D
efen
se,P
aris
; –
BENN
ING
,po
wer
s in
form
atio
n te
chno
logi
es
The following DC-DC converters canbe used in combination with the plug-in rectifiers in the same plug-in rack.The designs available are galvanicallyseparated and cover the ranges 24 V,48 V and 60 V.
Input voltage Output voltage Output current Type24 V 48 V 6 A G 24 G 48/ 6 PCT24 V 48 V 20 A G 24 G 48/20 PCD48 V 24 V 40 A G 48 G 24/40 PCD60 V 24 V 54 A G 60 G 24/54 PCD60 V 48 V 25 A G 60 G 48/25 PCD
Input voltage V see type tablePermissible deviation % + 20, - 10 I + 20, - 15Nominal output voltage V see type tableStability UoutputStatic % ± 1Dynamic (load 10-100-10) % + 4, - 5Output current A see type tableVoltage ripple Vpp < 1 %Noise voltage mV 1 or 2 frequency weighted with filter
A in accordance with CCITT 0.41Response time ms < 5Efficiency % 80Radio interference EN 55022 class B I EN 55022 class AAmbient temperature °C 0 to + 40Protection IP 20Protection class 1 - EN 60950Max. installation height m 2000 above sea levelMoisture class F in according with DIN 40040IndicationsDC voltage high red LED, automatic cut-off,
to reset switch-off mainsOperation green LEDInput – I yellow LED
I at DC voltage >TBDAlarm red LED I red LED (unit failure)
temperature monitoring I approx. > 30 sec. delayedCurrent indication (output) – I bargraphConnections:Input plugOutput plug
Cooling convectionDimensions mm H 291 x B 71 x T 300 I H 266 x B 145 x T 440Weight kg approx. 4 I approx. 11
PCT 300 W
24 / 48 V - 6 A
PDC 960, 1300, 1400
24 / 48 V - 20 A
48 / 24 V - 40 A
60 / 24 V - 54 A
60 / 48 V - 25 A
Telecom_14S_2in1_eng.qxd 04.07.2001 9:31 Uhr Seite 4
Input voltage range [V]
Input current [A]
Frequency [Hz]
Power factor
Output current
at 24 V [A]
at 48 V [A]
at 60 V [A]
Output voltages
Boost voltage [V/c]
Float voltage [V/c]
Direct supply [V/c]
Battery check [V/c]
Stability Uoutput
Static [%]
Dynamic load 10-100-10 [%]
(di/dt>200µs)
Response time [ms]
Efficiency
Characteristic
Noise voltage [mV]
Radio interference
Protection class
Safety
Protection
Cooling
Ambient temperature [°C]
Installation height [m]
Moisture class
Current measurement
Voltage measurement
Indications:/front panel
Mains
DC voltage high
Operation
Alarm
Fan failure
Common alarm/change-over contact
Connections:
Main input
Output
Alarms
Dimensions
Height (front panel) [mm]
Width [mm]
Depth [mm]
Weight [kg]
singlephase 196–264 I threephase 340–460
2,1 I 3,4 I 4,2 I 8,5 I 14 I 13,7 I 22
47–63
0,98 I 0,93
– I – I 15 I 50 I 75 I 200 I –
7,5 I 12 I 15 I 33 I 50 I 125 I 225
– I 10 I 12 I 27 I 40 I 100 I 200
externally adjustable
2,4
2,23
2,05
1,8
± 1
± 5
< 5
90 I 91 I 94
IU
1 for 24 V units, 2 for 48/60 V units
EN 55022 class B
1-EN 60950
EN 60950
IP 20
convection I fan behind the front panel, temperature controlled
0 – 40
up to 2000 m above sea level
F DIN 40040
– I test sockets*
– I – I test sockets*
yellow LED
red LED
green LED
red LED
I red LED
fault
plug I terminals 4 mm2
plug I M8 I M12
plug I plugterminal
267 I 267 I 267 I 267 I 267 I 177 I 267
71 I 71 I 107 I 107 I 146 I 485 I 485
250 I 250 I 250 I 350 I 440 I 400 I 400
3,0 I 3,6 I 5,5 I 9,5 I 12,5 I 26,5 I 40,0
* digital display: standard in PDE 7200 and PDE 15000
in PDT 800, PDT 1800 and PDD 3000 only in version with MCU interface
Technical data, Plug-in Rectifiers
Typemax. quantity per 19“ leveloutput power [W]
PDT 6
400
PDT 6
650
PDT 4
800
PDT 4
1800
PDD 3
3000
PDE 1
7200
PDE 1
15000
Telecom_14S_2in1_eng.qxd 04.07.2001 9:31 Uhr Seite 5
177
*2
TEBEVERT
EinAusOff
On
483
133,
4 *1
39390 *2 / 450 *3272 *1
GeneralThe inverters can be connected inparallel so systems with N+1 redundancy can be constructed.
Parallel connection can beused for increasing thepower, and thus systemextension on site is possiblefor increasing powerdemand.Systems with up to 5 invertersconnected in parallel arepossible.
The use of modern semicon-ductors with high switching frequen-cies provides compact construction,low weight and a very high efficiency.
All monitoring and control units aredesigned to be intrinsically safe so that an uninterrupted supply of theconnected load is ensured.
These products have a very gooddynamic range. At load peaks of 0 % - 100 % - 0 %, fluctuations andvoltage surges are corrected within avery short time.
The plug-in inverters are availablewith the output power 1000 VA, 1500 VA(only 24 V), 2500 VA and 5000 VA.
The cabinets can be installed side byside with rectifier cabinets of similardesign.
In order to increase the availability ofthe system a mechanical by-pass canbe provided. In case of inverter failureit automatically switches over to thepublic mains (fig. 1) with a low change-over time.
The EUE (static by-pass) is anothercomponent for increasing the systemsafety. Using the EUE the loads aredirectly switched to the mains in caseof overload or faults in the inverter (fig. 2 + 3). This switch-overis made almost without interruption.
Fig. 3 Inverters connected in parallel withstatic by-pass (EUE) for increasing thesystem safety
Dimensions diagram
* 1 1000 VA 48V/60V
* 2 2500 VA 48V/60V
* 2 1500 VA 24V
* 3 5000 VA 48V/60V
+
+
+
Fig. 2: Inverter with static by-pass (EUE)for the uninterrupted supply of theloads
Fig.1: Inverter with mechanical by-pass (SUE), voltage gap approx. 100 ms
Load
Battery
Load
Battery
Load
Battery
SUE
EUE
EUE
Inverter
Inverter
Inverter 1
Inverter 2
Inverter 5
Arresting hooks can be dismantled
Output
prese
nt
Mains s
ynch
roniza
tion /
Prese
nt
Overlo
ad
Paral
lel op
eratio
n
Fault
*3
Inverter range TEBEVERT
Operation mode
TEBEVERT
Inverter
5000 VA
Airp
ort F
rank
furt
/Mai
n,Be
nnin
g -
Pow
er to
Com
mun
ikat
ion
Telecom_14S_2in1_eng.qxd 04.07.2001 9:40 Uhr Seite 6
Loads of systems with EUE are permanently supplied via the inverter.
The voltage gap, arising in the event offailure in the inverter or overload, is < 1,5 ms, so even sensitive electronicloads can be supplied without any problems. The overload behaviour isapprox. 5 x I rated for 100 ms, therefo-re loads with high inrush currents canalso be connected.
483
466
246,5
3 U
= 13
3,4
444
Input DC voltage V see type tablePermissible deviation % + 20, -15Ripple of the input voltage % max. 5 rmsReverse smoothing mV 2Nominal power VA see type tableOutput voltage V 230Static deviation % ± 5Frequency Hz 50Frequency stability % ± 0,1 (crystal controlled)Mains control of frequency % ± 3Power factor range 0,7 ind. to 0,8 cap.Voltage form sine-waveDistortion factor % < 3 (at linear load)Overload capacity 2xInom for 1 sec.,
cut-off after 40 sec.Crest factor load 2,5 : 1Radio interference EN 55022Efficiency % 80–85Ambient temperature °C +5 to +40Installation height m up to 1000 above sea levelMoisture class FCooling temperature-controlled
forced ventilationProtection class 1 - EN 60950Protection IP 20 (without terminals)Painting (front panel) RAL 7032
IndicationsOutput current bargraphOutput voltage present LEDFault LEDOverload LEDMains synchronization LEDParallel operation LED
Pot.-free contact fault (delay approx. 10 sec.)
ConnectionsAC side plugs / terminalsDC side plugs / terminalsAlarm plugsRemote controlEarthing bolt M6EUE/parallel operation connector
Options SUE operationEUE operationparallel operation
Dimensions see type table
G 24 E 230/ 6,5/2rfg-PWE 24 V 57A 1500VA 177,0 x 483 x 390 18,5G 48 E 230/ 4,4/2rfg-PWE 48 V 20A 1000VA 133,4 x 483 x 256 10,5G 48 E 230/10,9/2rfg-PWE 48 V 50A 2500VA 177,0 x 483 x 390 18,5G 48 E 230/21,7/2rfg-PWE 48 V 92A 5000VA 177,0 x 483 x 450 28,0G 60 E 230/ 4,4/2rfg-PWE 60 V 16A 1000VA 133,4 x 483 x 256 10,5G 60 E 230/10,9/2rfg-PWE 60 V 40A 2500VA 177,0 x 483 x 390 18,5G 60 E 230/21,7/2rfg-PWE 60 V 74A 5000VA 177,0 x 483 x 450 28,0
Technical data TEBEVERT Static by-pass EUE
Dimensions EUE (Static By-Pass)
Type
Type
Nom
inal
pow
er[V
A]
Dim
ensi
ons
H x
W x
D [m
m]
Inpu
tvo
ltage
Inpu
t cur
rent
at
cos
ϕ 0
,8 a
.Nom
inal
inpu
t vol
tage
Outp
utpo
wer
Dim
ensi
ons
H x
W x
D [m
m]
Wei
ght [
kg]
Type table Tebevert Type table EUE
EUE E 230/ 32,60/2 - 24E 7500 133,4 x 483 x 300EUE E 230/ 21,74/2 - 48E (60E) 5000 133,4 x 483 x 300EUE E 230/ 54,35/2 - 48E (60E) 12500 133,4 x 483 x 300EUE E 230/ 108,7/2 - 48E (60E) 25000 133,4 x 483 x 300
Telecom_14S_2in1_eng.qxd 04.07.2001 9:40 Uhr Seite 7
Airp
ort M
ünch
en,B
enni
ng -
Pow
er to
Com
mun
ikat
ion
Remote Monitoring System MCU 500, 1000 und 2000+
Rectifier with (2)or without (1)interface
MCU 500
MCU 1000
MCU 2000 +
DC-Power-SupplyFloat
Boost
Battery test
Battery test negative
Rectifier failure
Mains failure
Fault U < 2,1 V/C
Battery disch. U < 1,9 V/C
LVD tripped
Battery fuse tripped
Load fuse tripped
Battery fault
(reserve)
LED test/reset
GeneralWith the increasing demand for power systems inthe telecommunication sector, and the need formore efficient use of operating and maintenancestaff, Benning have produced a range of systemmonitoring. The Benning MCU 500, MCU 1000 andMCU 2000+ offer the user a solution dependingon the customer requirements.
BLT 150 and BLT 400 power systems are fittedwith MCU 500 (Optional MCU 1000) monitoringsystem.By means of local indication (13 off LED´s) andnumerical display, the system status can bequickly assessed.The MCU 1000 additionally offers direct commu-nication, via a RS 485 interface, with the rectifiermodules.As an optional extra the MCU 1000 may be fittedwith a relay box having 8 volt free contact.
The BLT 2500/5000 has the MCU 2000+ monito-ring fitted as standard.
Both MCU 1000 and MCU 2000+ monitoringsystems have the facility to control and monitorthe power system via the public telephone network.
As an option, the MCU 1000 and MCU 2000+ sig-nals can be transmitted via modem to a centralcontrol station.
Using a PC and dedicated monitoring software,information can be sent and received by thecustomer based in the control station.
The MCU 2000+ provides a large range of super-visory functions, and enables easy monitoringand controlling of the power supply system.
Communication with the rectifiers is via an RS485 interface. Options include 8 additional voltfree alarm contacts, 24 external digital inputs and15 measurement channels.
Float
Boost
Battery test
Battery test negative
Rectifier failure
Mains failure
Fault U < 2,1 V/C
Battery disch. U < 1,9 V/C
LVD tripped
Battery fuse tripped
Load fuse tripped
Battery fault
(reserve)
LED test/reset
DC-Power-Supply
Float
Boost
Battery test
Battery test negative
Rectifier failure
Mains failure
Fault U < 2,1 V/C
Battery disch. U < 1,9 V/C
LVD tripped
Battery fuse tripped
Load fuse tripped
Battery fault
(reserve)
LED test/reset
DC-Power-Supply
Cont
acts
(1
)Co
ntac
ts
(1)
RS 4
85
(2)
RS 4
85
(2)
Telecom_14S_2in1_eng.qxd 04.07.2001 9:41 Uhr Seite 8
Base Unit
• 8 external digital inputs• 3 pot. free contacts• 3 measurement-value channel for
voltage, current or temperature
Telephone line
Base Unit
• 8 external digital inputs• 3 pot. free contacts• 3 measurement-value channel for
voltage, current or temperature
Option:
• Relay Box with 8 pot. free contacts
Base Unit
• 8 external digital inputs• 3 pot. free contacts• 3 measurement-value channel for
voltage, current or temperature
Option:
• Relay Box with 8 pot. free contacts• 24 external digital inputs• 15 measurement-value channel for
voltage, current or temperature
RS 232I2C-Bus
I2C-Bus
RS 232
RS 232
RS 232
RS 232
I2C-Bus
Telecom_14S_2in1_eng.qxd 04.07.2001 9:42 Uhr Seite 9
Kong
ress
zent
rum
Ber
lin,B
enni
ng -
Pow
er to
Com
mun
ikat
ion
General”BLT” Power Systems are designedwith the latest switch mode technologyand are suitable for all Telecom appli-cations.
The BLT 150 systems are able to feedsmaller DC loads (approx. 15 A up to150 A), while the BLT 400 systems areused for middle range (approx. 100 Aup to 400 A) and the BLT 2500/5000for the large range (approx. 500 A upto 5400 A).
The special features are good efficiency,high power factor as well as a gooddynamic behaviour.
Modular DC Power Supply Systems BLT 150, BLT 400 with MCU 500/1000
BLT 150
DC System BLT 150 BLT 150
Rectifier rangeNo. of rectifiersMonitoring system
InputVoltageCurrent (with 3 x 400 V)FrequencyPower factorOutputVoltageCurrent (max.)CharacteristicRipple voltageGeneral dataEfficiencyOperating temperatureProtectionDimensions
PDT 400n = 6MCU 500Option MCU 1000
3 x 400 V (± 15 %)4,2 A50 Hz (± 5 %)0,98
48 VDC / 60 VDC45 A / 30 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
90 %0 ÷ 40 °CIP 20670 x 534 x 400
PDT 650n = 6MCU 500Option MCU 1000
3 x 400 V (± 15 %)6,8 A50 Hz (± 5 %)0,98
48 VDC / 60 VDC72 A / 60 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
90 %0 ÷ 40 °CIP 20758 x 534 x 470
Telecom_14S_2in1_eng.qxd 04.07.2001 9:42 Uhr Seite 10
BLT 150 BLT 400 BLT 400
PDT 1800n = 4MCU 500Option MCU 1000
3 x 400 V (± 15 %)17 A50 Hz (± 5 %)0,98
24 VDC / 48 VDC / 60 VDC200 A / 132 A / 104 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
91 %0 ÷ 40 °CIP 20758 x 534 x 470
PDT 1800n = 8MCU 500Option MCU 1000
3 x 400 V (± 15 %)25,5 A50 Hz (± 5 %)0,98
24 VDC / 48 VDC / 60 VDC400 A / 264 A / 208 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
91 %0 ÷ 40 °CIP 202000 x 600 x 600
PDD 3000n = 6MCU 500Option MCU 1000
3 x 400 V (± 15 %)28 A50 Hz (± 5 %)0,98
24 VDC / 48 VDC / 60 VDC450 A / 300 A / 240 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
91 %0 ÷ 40 °CIP 202000 x 600 x 600
Kong
ress
zent
rum
Ber
lin,B
enni
ng -
Pow
er to
Com
mun
ikat
ion
BLT 400
Telecom_14S_2in1_eng.qxd 04.07.2001 9:42 Uhr Seite 11
La D
efen
se,P
aris
; –
BENN
ING
,po
wer
whe
re it
’s n
eede
d,
Modular DC Power Supply Systems BLT 2500/5000 with MCU 2000 +
DC System BLT 2500 BLT 2500
Rectifier rangeNo. of rectifiersMonitoring systemInputVoltageCurrent (with 3 x 400 V)FrequencyPower factorOutputVoltageCurrent (max.)CharacteristicRipple voltageGeneral dataEfficiencyOperating temperatureProtectionDimensions
PDE 7200n = 5MCU 2000 +
3 x 400 V (± 15 %)68,5 A50 Hz (± 5 %)0,93
48 VDC / 60 VDC625 A / 500 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
93 %0 ÷ 40 °CIP 202000 x 1800 x 600
PDE 7200n = 10MCU 2000 +
3 x 400 V (± 15 %)137 A50 Hz (± 5 %)0,93
48 VDC / 60 VDC1250 A / 1000 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
93 %0 ÷ 40 °CIP 202000 x 2400 x 600
BLT 2500
BLT 2500
Telecom_14S_2in1_eng.qxd 04.07.2001 9:43 Uhr Seite 12
BLT 2500 BLT 2500 BLT 2500/5000
PDE 15000n = 6MCU 2000 +
3 x 400 V (± 15 %)132 A50 Hz (± 5 %)0,94
48 VDC / 60 VDC1350 A / 1200 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
94 %0 ÷ 40 °CIP 202000 x 2400 x 600
PDE 15000n = 12MCU 2000 +
3 x 400 V (± 15 %)264 A50 Hz (± 5 %)0,94
48 VDC / 60 VDC2700 A / 2400 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
94 %0 ÷ 40 °CIP 202000 x 3000 x 600
PDE 15000n = 24MCU 2000 +
3 x 400 V (± 15 %)528 A50 Hz (± 5 %)0,94
48 VDC / 60 VDC5400 A / 4800 AIU in accordance with DIN 41773< 2 mV in accordance with CCITT 0.41
94 %0 ÷ 40 °CIP 202000 x 6000 x 600
La D
efen
se,P
aris
; –
BENN
ING
,po
wer
whe
re it
’s n
eede
d,
BLT 2500BLT 5000
Telecom_14S_2in1_eng.qxd 04.07.2001 9:43 Uhr Seite 13
B E N N I N G W o r l d C l a s s P o w e r S y s t e m s
BENNING worldwideAustriaBenning GmbH Elektrotechnik und ElektronikEduard-Klinger-Str. 9A-3423 St. Andrä-WördernTel. 0 22 42 / 3 24 16-0 Fax 0 22 42 / 3 24 23E-Mail: [email protected]
BelgiumBenning Belgium Power ElectronicsZ. 2 Essenestraat 16B-1740 TernatTel. 02 / 58 287 84 (85)Fax 02 / 58 287 69E-Mail: [email protected]
Czech RepublicBenning CR s.r.o.Zahradní ul. 894CZ-293 06 Kosmonosy(Mladá Boleslav)Tel. 03 26 / 72 10 03Fax 03 26 / 72 25 33E-Mail: [email protected]
FranceBenning Conversion d’énergie43, avenue Winston ChurchillB.P. 418F-27404 Louviers CedexTél. 02 / 32 25 23 94Fax 02 / 32 25 08 64E-Mail: [email protected]
GermanyTheo BenningElektrotechnik und Elektronik GmbH & Co.KGMünsterstr. 135-137D-46397 BocholtTel. 0 28 71/ 93-0 Fax 0 28 71/ 9 32 97http://www.benning.de
Great-BritainBenning UKOakley HouseHogwood LaneFinchampsteadGB-Berkshire RG 40 4 QWTel. 0 11 89 / 73 15 06 Fax 0 11 89 / 73 15 08E-Mail: [email protected]
HungaryBenning Kft.Power ElectronicsRákóczi út 262H-2541 LábatlanTel. 033 / 50 76 00Fax 033 / 50 76 01E-Mail: [email protected]
IndiaBenning SMC Power Systems (P) Ltd.10, Electronic City, Sec.-18,IND-Gurgaon -122015, HaryanaTel. 0124 / 6 45 52 03 – 09Fax 0124 / 6 45 52 12, 6 34 64 65E-Mail: [email protected]
IrelandTheo Benning GmbHNorth Industrial EstateWhitemill NorthIRE-Wexford / Rep. IrelandTel. 0 53 / 41 79 5 Fax 0 53 / 41 84 1E-Mail: [email protected]
IsraelLaor Energy ltd.P.O.B. 570IL-Nazereth Elite 17105Tel. 03 / 6 87 25 51Fax 03 / 6 87 11 10E-Mail: [email protected]
ItalyBenning Conversione di Energia S.r.l.Via E. Mattei, 7I-40138 BolognaTel. 0 51 / 53 19 55 Fax 0 51 / 53 09 23 E-Mail: [email protected]
NetherlandsBenning NLPower ElectronicsPeppelkade 42NL-3992 AK HoutenTel. 0 30 / 6 34 60 10 Fax 0 30 / 6 34 60 20E-Mail: [email protected]
PolandBenning Power Electronics Sp.z.o.o.Korczunkowa 30PL-05-503 GloskówTel. 0 22 / 7 57 84 53 / 7 57 36 68-70Fax 0 22 / 7 57 84 52E-Mail: [email protected]
P. R. of ChinaBenning V. GmbHShanghai Repr. Office1233 Si Ping Rd., Rm. 006PRC-200 092 ShanghaiTel. 021 5557 0609Fax 021 6504 1878E-Mail: [email protected]
Russian FederationOOO Benning Power ElectronicsSchtscholkovskoje Chaussee, 5RF-105122 MoscowTel. 0 95 / 9 67 68 50Fax 0 95 / 9 67 68 51E-Mail: [email protected]
South East AsiaBenning Power Electronics Pte Ltd1, Kaki Bukit View# 05-03/04 TechviewSGP-Singapore 415941Tel. (65) 6844 3133Fax (65) 6844 3279E-Mail: [email protected]
SwedenEldaco ABBox 990, Hovslagarev. 3BS-19129 SollentunaTel. 08 / 6239500Fax 08 / 969772E-Mail: [email protected]
SwitzerlandBenning Power Electronics GmbHIndustriestrasse 6CH-8305 DietlikonTel. 01/ 8057575Fax 01/ 8057580E-Mail: [email protected]
SpainBenning Conversión de Energía S.A.C/Pico de Santa Catalina 2Pol. Ind. Los LinaresE-28970 Humanes, MadridTel. 91/ 6048110Fax 91/ 6048402E-Mail: [email protected]
UkraineBenningul. Solomenskaja, 3BUA-252110 KiewTel. 044 / 246 10 25Fax 044 / 248 92 36E-Mail: [email protected]
U.S.A.Lucas-BenningPower Electronics, Inc.11120 Grader StreetUSA-Dallas, TX 75238Tel. 214 5531444Fax 214 5531355E-Mail: [email protected]
7841
65.0
0
03/2
002
pa
us D
esig
n &
Med
ien,
Boch
olt
Sub
ject
to a
ltera
tions
.Pr
inte
d on
chl
orin
e fre
e pa
per.
ISO
14
00
1