Author
phamlien
View
220
Download
4
Embed Size (px)
Know the Difference…
Basement or Elevated
This session is for education purposes only – NO Continuing Education credits will be provided
October, 2013
Please note: These materials may become dated as NFIP rules and regulations change
Objectives
After completion of this module, user will be able to:
Define a basement
Distinguish when a structure is elevated • Is there an enclosure below the elevated floor?
• If so, does the enclosure meet NFIP guidelines?
Determine which floor of the structure is used for rating purposes
Understand coverage limitations within a basement or an enclosure and when these coverage limitations apply
Basements and Sub-Grade Crawlspaces
Definition of a Basement Basement floor is partially or completely below
ground level on all four (4) sides more than 2 feet, or
Floor of the basement is below ground level within 2 feet of the LAG (Lowest Adjacent Grade) AND distance to the next higher floor is more than 5 feet
Definition of a Sub-Grade Crawlspace Crawlspace floor within 2 feet of the LAG (Lowest
Adjacent Grade)
Distance between the crawlspace floor and the next higher floor is within 5 feet
Diagram #9
Rated as “With Basement” rates
Sub-Grade Crawlspace vs Basement
No more than 2 feet below grade
No more than 5 feet below the next higher floor More than 2 feet below grade
More than 5 feet below the next higher floor
What is considered a basement?
Diagram 2 shows a basement building
C2a
Diagram #9 – Sub Grade Crawlspace
All buildings (other than split-level) elevated on a subgrade crawlspace, with or without attached garage
Why is the distinction important?
It is important to identify sub-grade crawlspace vs. basement
Both foundations identify buildings with lowest floors that are below
ground level - if the Base Flood Elevation (BFE) is higher than the
crawlspace floor (C2a) (elevation difference must be -1 or lower) less
expensive rates could be given if the policy is rated as a Submit-For-
Rate
Basement or Sub-grade Crawl?
100.3 – 102.9 = -2.5 (More than 2 ft below the
Lowest Adjacent Grade = Basement)
C2.f = 102.9 (LAG)
C2.a = 100.3 (Top of bottom floor)
**Sub-grade floor is ALWAYS the lowest floor for rating (LFE)**
Basement Coverage Limitations – Applies to ALL Buildings in ALL zones
Central air conditioners
Cisterns and the water in them
Drywall for walls and ceilings in a basement and the cost of labor to nail it, unfinished and unfloated and not taped, to the framing
Electrical junction and circuit breaker boxes
Electrical outlets and switches
Elevators, dumbwaiters, and related equipment, except for related equipment installed below the base flood elevation after September 30, 1987
Fuel tank and the fuel in them
Furnaces and hot water heaters
Heat pumps
Nonflammable insulation in a basement
Pumps and tanks used in solar energy systems
Stairways and staircases attached to the building not separated from it by elevated walkways
Sump pumps
Water softeners and the chemicals in them, water filters and faucets installed as an integral part of the plumbing system
Well water tanks and pumps
Required utility connections for any item in this list (electric, gas, sewer and water are he only NFIP required utilities)
Footings, foundations, posts, pilings, piers, or other foundation walls and anchorage systems required to support a building
Cleanup
Air conditioning units, portable or window type (under contents coverage only)
Clothes washers and dryers (under contents coverage only)
Food Freezers, other than walk-in and food in any freezer (under contents coverage only)
Element Not Covered
Content Items not Specifically Listed
Improvements such as Finished Walls, Floors, and Ceilings
Building Equipment and Fixtures not specifically Covered
What is an Elevated Building?
A building that has no basement and has its lowest elevated floor raised above ground level by means of foundation walls, shear walls, piers, posts, pilings or columns Shear walls are used for structural support, but are not structurally joined or
enclosed at the ends (except by breakaway walls); Shear walls are parallel (or nearly parallel) to the flow of the water and can be used in any zone
Solid perimeter foundation walls are used as a means of elevating the building in A Zones and must contain proper openings to allow for the unimpeded flow of floodwaters more than 1 foot deep; Solid perimeter foundation walls are not an acceptable means of elevating buildings in V/VE Zones
May or may not have an enclosure below the lowest elevated floor
Elevated No Enclosure
Elevated with no Enclosure – Diagram #5
Pilings
C2a
Elevated Without Enclosure
C2.a = 16.7 (Top of Bottom Floor)
BFE = 8.0
Mobile Homes
To be insurable, a mobile home cannot be supported
by wheels and/or axles
Mobile homes are considered elevated buildings when the
lowest living floor is elevated off the ground
Diagram 5
Diagram 8
Normal vinyl or metal skirting is not considered an obstruction to the flow of water and is therefore considered a diagram #5 – elevated with no enclosure
Other types of skirting (block/brick, etc) or enclosure material are considered obstructions and are therefore considered elevated with enclosure and fall into the diagram #8 category
Enclosure versus No Enclosure
What happens if diagram 5 building, Elevated No Enclosure, is improved or altered adding an enclosure below the lowest elevated floor?
Elevation Certificate, if applicable, should be updated to reflect the new enclosure
Verification enclosure has been built in compliance with NFIP guidelines
Policy re-underwritten / re-rated accordingly
If loss occurs, loss adjustment will depend on whether policy accurately reflects the enclosure and whether policy was underwritten / rated correctly • If not, policy adjustment will ensue prior to loss adjustment
Elevated Buildings – Partial Enclosures
Elevated with Partial Enclosure – Diagram #6 Constructed on pilings,
posts, piers, columns or parallel shear walls with lowest floor at or above Base Flood Elevation (BFE) • No basement or crawlspace • Adequately anchored to
foundation support system
Where is the lowest floor for rating? Vents? Usage?
Is enclosure adequately vented?
Venting Guidelines – A Zones Only
To be in compliance with NFIP guidelines, enclosures are to be adequately vented or have compliant flood openings
Guidelines for compliant vents/openings: Minimum 2 vents in the enclosure
Placed in/on different walls
1 square inch of venting, per square foot of enclosure space
Vents/openings are to be no more than one (1) foot off the ground
These guidelines can be found in the Elevation Certificate as well as the Agent’s Lowest Floor Guide
Elevated with Enclosure
C2a = 6.0 (Top of Bottom Floor)
BFE = 8.0
Enclosure Size = 240 Square Feet Number of Vents 1’ foot above the Lowest Adjacent Grade = 4 Total Square Inches of Vents = 272 Is the Enclosure compliant with NFIP Guidelines? What is the Elevation used for rating?
C2b = 16.7
Elevated Buildings - Walkouts
Another type of elevated building is
one that is raised on solid foundation
perimeter walls with a walk out at
grade / ground level. Diagram 7 shows
this type of elevated building.
C2a Top of Bottom Floor
C2b Next Higher Floor Vents?
Elevated Buildings - Crawlspace
An under-floor space that has its interior floor area (finished or not) no more than 5 feet below the top of the next-higher floor
Crawlspaces generally have solid perimeter foundation walls
Diagram 8
Is the enclosure Compliant?
C2b = 12.6 (Top of next higher floor)
BFE = 8.0
Enclosure Size = 720 Square Feet Number of Vents within 1’ foot of the Lowest Adjacent Grade = 12 Total Square Inches of Vents = 725
C2a = 9.0 (Top of bottom floor)
What is a V Zone?
An area that is inundated by tidal floods with high velocity water (coastal high hazard area)
A V zone is an area that will support a 3 ft breaking wave (or higher)
Structures should be elevated with the lowest living floor elevated above the Base Flood Elevation (BFE) with no enclosure and built to sustain wave action
An area inundated by 1% chance annual flooding
with velocity hazard (wave action)
Elevated Without Obstruction – V Zones
Area below the elevated floor is open
Insect screening, wooden or plastic lattice, slats or shutters are
permissible, if at least 40% of their area is open
Enclosures containing one solid breakaway wall and the remaining walls constructed of insect screening, lattice, slats or shutters
Any Machinery and/or Equipment must be elevated to at least the
BFE
Rate Table 3E
Lowest Floor for rating is the Bottom of the Lowest Horizontal Structure C2c from the EC
C2c
Elevated with Obstruction – V Zones
Buildings are rated with Obstruction if any of the following conditions are met:
Area below the elevated floor is enclosed fully by solid, breakaway walls
Enclosed by a combination of two or more solid, breakaway walls with insect screening, lattice or slats
Machinery and/or Equipment is below the BFE
Rate Table 3F
C2c
C2a
Lowest floor for rating is the lowest horizontal structural member (C2c), OR bottom of the slab (C2a)
Enclosure Compliance Guidelines – V Zones
299 square feet or less in size
Constructed of Breakaway Walls
Space used for Parking, Storage or Building Access only
Machinery and/or Equipment must be elevated to at least the Base Flood Elevation (BFE)
Unfinished Space
Drywall used for fire protection is permitted
Drywall mudded & taped is still unfinished as long as it’s not painted
C2c
bottom of the beam
C2a Top of Bottom Floor
What Makes an Enclosure Finished?
Enclosure has more than 20 linear feet of finished walls Painted Surfaces
Paneling
Wallpaper
Drywall that has been primed and/or painted
Used for any purpose other than vehicle parking, storage or building access
Elevated Building Coverage Limitations – within the Enclosure – Applies to Buildings in Zones A & V, Post-FIRM
Central air conditioners
Cisterns and the water in them
Drywall for walls and ceilings in a basement and the cost of labor to nail it, unfinished and unfloated and not taped, to the framing
Electrical junction and circuit breaker boxes
Electrical outlets and switches
Elevators, dumbwaiters, and related equipment, except for related equipment installed below the base flood elevation after September 30, 1987
Fuel tank and the fuel in them
Furnaces and hot water heaters
Heat pumps
Nonflammable insulation in a basement
Pumps and tanks used in solar energy systems
Stairways and staircases attached to the building not separated from it by elevated walkways
Sump pumps
Water softeners and the chemicals in them, water filters and faucets installed as an integral part of the plumbing system
Well water tanks and pumps
Required utility connections for any item in this list (electric, gas, sewer and water are he only NFIP required utilities)
Footings, foundations, posts, pilings, piers, or other foundation walls and anchorage systems required to support a building
Cleanup
Air conditioning units, portable or window type (under contents coverage only)
Clothes washers and dryers (under contents coverage only)
Food Freezers, other than walk-in and food in any freezer (under contents coverage only)
Element Not Covered
Content Items not Specifically Listed
Improvements such as Finished Walls, Floors, and Ceilings
Building Equipment and Fixtures not specifically Covered
National Flood Services Inc PO Box 2057 Kalispell, MT 59903-2057 800.637.3846
WYO Company NFIP / FEMA sites www.nfipiservice.com www.fema.gov/nfip www.floodsmart.gov www.agents.floodsmart.gov
Resources