Thermal system design
assignmentSubmitted to: Dr.Demiss A.
Alemnew EbabuAka
M E K E L L E U N I V E R S I T Y , G R A D U A T E P R O G R A M - E N E R G Y T E C H N O L O G
7/29/2019 Assignment Ac-system1
2/12
Thermal system design assignment
2
Assignment -1-
Design of ventilation system .
The Restaurant shown below is to be maintained at a constant environmental temperature of
22o
C for a plant operation of 12 hours per day.The Restaurant area is on the ground floor of anSingle storey building located at 51.7
oNThe internal construction is lightweight partitions,
concrete hollow slab floors and suspended ceilings.it was desired to design a ventilation system
for the restaurant.
the following ste[ps are neccesary to be carried out the plan view of the restaurant is shown
belaow
Calculate Ventilation rates. Decide on number of fans and grilles/diffusers. Draw scale layout drawing and Position fan(s). Lay out ductwork. Lay out grilles and diffusers. Indicate flow rates on drawing. Size ductwork Size fan Size grilles and diffusers
14.0 m
7.7
9.5
FemaleToilet
MaleToilet
Receptio
Entranc
10.0Lobby
Restaurant
3.5
Kitchen
2.7m
Cold
Store
Prep.
Room
PLAN
South
Height of wall to
eaves
Height of
ceiling at
7/29/2019 Assignment Ac-system1
3/12
Thermal system design assignment
3
Fig: the elevation plan view
Table: ventilation system design data for occupancy, building category and exterior structure
dimensions
Sn.
Design data for the restaurant
1 Occupants 70
2 Infiltration 1.0 ACH
3 Outside air temperature 28oC.
4 Area of window 2.8 m2
5 Total area of glass 28.0 m
2
6 Area of glass facing South 28.0 m2
7 Area of wall facing South 28.0 m2
8 Floor area 140 m2
9 Room volume 623 m3
10 Building classification lightweight, fast response
building
South
7/29/2019 Assignment Ac-system1
4/12
Thermal system design assignment
4
Ventilation requirements;
In this design it is proposed to ventilate the kitchen, the preparation room and the restaurant
and toilets separately using 4 exhaust fans the position of the fans its to be decided after the
longest path for which the maximum pressure drop occurs is determined the supply fan should be
as far as possible from the restaurant to avoid noise creation
All rooms the cheaper alternative is an extract system with replacement air coming in through
doors and operable windows. Fans should be located in accessible positions; in the corridor,
above ceilings. In-duct axial flow fans take up less space than centrifugal fans. Possible use of
wall mounted fan in Food Prep. Room. Upward with diffusers installed in suspended ceilings.
Use separate extract systems so that smoke will not spread from room to room through ducts.
Consider fire dampers in ducts. Fans are positioned as far away from Conference room and
restaurant as possible. Choose fans from catalogue with decibel levels less than 85dB if possible.
ventilation requirements for restaurant rooms
Room or building type Recommended fresh air
supply rate
Recommended total air
supply rate(ACH)
Restaurant
Kitchen 10
Female toilet 8
Male toilet 8
Table: restaurant rooms ventilation requirements as recommended by the Table B2.3 (CIBSE
1986).
7/29/2019 Assignment Ac-system1
5/12
Thermal system design assignment
5
.
Table: calculated ventilation rates for the rooms suggested requiring ventilation
The next is to calculate the fresh rate this was done by assuming that the outdoor air supply per
person should suit for a heavy smoking area this is because of the possibility that heavy smokers
may arrive as consumers at restaurants. And since we are dealing with restaurants it is fair to
assume a heavy smoking area with a recommended air supply rate per person of 24 liters per
second. Therefore similarly like the ventilation requirements and assuming a peak of70 persons
the outdoor fresh air supply was found to be 1680
Table: recommended outdoor air supply rates.
ROOMS volume(m3) Recommended (ACH) ventilation rate (m3/hr) ventilation rate(m3/
kitchen 217 35 7595 2.10972
preparation room 47.25 10 472.5 0.1
male toilet 84 8 672 0.18666
female toilet 140 8 1120 0.31111
restaurant 980 10 9800 2.72222
12064.5 3.3
Level of Smoking
Outdoor air supply rate
(liter/s per person)
No smoking 8
Some smoking 16
Heavy smoking 24
Very heavy smoking 36
7/29/2019 Assignment Ac-system1
6/12
Thermal system design assignment
6
CALCULATING THE FRESH AIR RATE
occupants outdoor supply air(heavy smoking l/s/person) fresh air rate(l/s)
70 24 1680
Table: calculated outdoor air supply rate
Duct sizing
The recommended velocity for main duct and branch ducts for restaurants are 7.5m/s and 5m/s
respectively therefore by choosing a square duct with aspect ratio of 1 we can determine the
nearest standard sizes of the ducts and the following standard sizes were obtained for the main
duct and the branching ducts to the rooms which require ventilation.
As shown on the table below the main duct area is 0.45m2and the branching duct are also shown
by considering a square duct the nearest standard sizes were determined for the rooms kitchen,
preparation room ,restaurant and toilets respectively
Table: standard size duct selection
Branching ducts(m2) Main duct area(m2) Square duct size(m)
Nearest
std.size(mm)
0.421944444 0.446833333 0.649572509 300*300mm
0.02625 0.162018517 150*150mm
0.037333333 0.193218357 150*150mm
0.062222222 0.249443826 150*150mm
0.668455932
500mm*500mm(std.)
7/29/2019 Assignment Ac-system1
7/12
Thermal system design assignment
7
Design tool duct sizer
BuildingAir Velocity (m/s)
Main Duct Branch
Domestic 3 2
Auditoria 4 3Hotel bedroom, Conference hall 5 3
Private office, Library, Hospital ward 6 4
General office, Restaurant, Dept. store 7.5 5
Cafeteria, Supermarket, Machine room 9 6
Factory, Workshop 10-12 7.5
7/29/2019 Assignment Ac-system1
8/12
Thermal system design assignment
8
As t can be seen from the results of the duct sizer air at 370c and 23% relative humidity at 1
atm is assumed the results were found to be consistent with spreadsheet results moreover the
velocity pressure and the static pressure losses were found to be 0.749pa/m and 31.5pa for the
dynamic losses therefore the total head loss is given by
Total head loss= velocity pressure loss+ static head loss.
To compute the total pressure loss it is first necessary to identify the index run that is the longest
path of the duct work layout a suitable duct layout system is proposed next which roughly
identifies the longest path for which the highest pressure drop occurs and which is late used as a
selection criteria for the fan sizing.
Figure; rough duct layout system for the main and branching for the whole building to estimate
the index run.
The duct layout can be laid out as shown above to roughly estimate the index run from the
supply side of the fan therefore the maximum run could be the duct system from the fan position
at the reception site to the branch duct for the preparation room which runs half the perimeter of
the whole building so it is estimated as 22m.
7/29/2019 Assignment Ac-system1
9/12
Thermal system design assignment
9
the next step is therefore to estimate the total static head loss for the index run which enables to
select the appropriate fan type by using the flow rate already obtained for their and the total
pressure earlier the pressure loss length was found as 0.79pa/m which gives
Total static pressure loss across the index run=22*0.79=31.5pa
Total pressure loss=static head loss dynamic head loss=49pa
from the calculations and from the table above showing the standard duct size selection
unequal size of branching ducts with duct dimensions ranging from150mm*150mm-
300*300mm were selected and 500mm*500mm standards size square duct were chosen .the
total pressure loss that the supply fan must overcome is found to be 49pa
Fan selection
Given the total pressure drop along the index run and the air flow rate for the main supply duct it
is possible to choose the appropriate fan from available catalogs from the above design
calculations the operation criteria was found to be 12064m3/hr and 49pa.
Table; fan performance curves for various models obtained from catalog
7/29/2019 Assignment Ac-system1
10/12
Thermal system design assignment
10
the fan performance curve for the model 634-b model is suitable for the air flow rate and total as
as shown by the red lines corresponding to the flow rate and total pressure losses obtained from
calculations 12604m3/hr and 49pa.
Table; product specification of fans type cc 630
For more comprehensive design one can look at the power requirements and noise conditions by
referring to the specifications provided in the above table the model we have chosen has a noise
generation of71db which is acceptable for the restaurant compared to 85db limit.