ASME Section III NP Extract

Embed Size (px)

Citation preview

  • 7/24/2019 ASME Section III NP Extract

    1/6

    ASIIIE

    2011a SECTION

    IlI,

    DMSION

    1

    -

    NB

    tJ

    j

    U

    1

    c{

    (A

    I

    t$

    \,

    NB-3512.2 Alternative

    Design

    Rutes.

    A

    valve

    design

    may

    not

    satisfy

    all of

    the requirements

    of NB-3512.1. A

    design

    may

    be accepted

    provided

    it meets one

    of

    the

    alternatives listed in

    {a),

    ib),

    [cJ,

    or

    [d)

    below,

    faj

    When

    the

    valve

    design satisfies the rules of

    NB-3530

    through NB-3546.2 with thermal

    stresses neglected,

    the

    rules

    of

    NB-3200 relative

    to

    accounting

    for

    thermal

    secondary

    stresses

    and

    fatigue anaiysis

    [NB-37.22.2,

    NB-3222,3,

    and NB-3222.41 shall also

    be

    satisfied.

    @l

    When a valve is

    exempted

    from

    fatigue analysis

    by

    the ruies ol NB-3222.4[d),

    the

    design

    is

    acceptable,

    provided

    that

    the requirements

    of

    [1J

    or

    (2J

    below are

    met.

    (1)The

    rules ofNB-3530

    through NB-3546 shall be

    mel The

    rules of NB-3200

    may

    be

    substituted for

    those

    of NB-3545,2

    for

    evaluating secondary

    stresses,

    and

    NB-3545,3

    need

    not be considered.

    (Z)The

    rules of NB-3530

    and

    NB:3541shall

    be met.

    An

    experinrental stress analysis

    is

    periornred

    in accor-

    dance with

    Appendix

    ll,

    and the rules

    of

    NB-3200

    rvith

    respect

    to primary

    and

    secondary stresses

    resulting from

    pressure

    and

    mechanical

    loads shall be mel.

    Uniess

    otherwise

    specified

    in the Design Specifications,

    the

    pipe

    reaclions

    shall be

    taken as

    those loads which

    produce

    a

    stress

    [NB-3545,2[b]l

    of

    0.5

    times

    the

    yield

    srrength

    of

    the

    piping

    in tension

    for

    the

    direct or

    axial

    ioad

    and

    a

    stress o[

    1.0

    times the

    yield

    strehgth of

    the

    piping in

    bending

    and

    torsion,

    Thernral

    secondaty stresses shall

    be accounted for

    by

    either the rules of NB-3200

    or NB-3545,

    (cJ

    When

    a

    valve

    design

    sarisfies the rules

    of

    NB-3530

    and

    NB-3541,

    and

    when an experirnental

    stress

    analysis

    has been

    performed

    upon

    a

    simiiar

    valve in

    accordance

    with

    Appendix II,

    and an

    acceptable

    analytic

    method has

    been

    established,

    the results

    may be

    used

    in

    conjunction

    ents

    of

    NB-3200

    for

    pressrtre

    and

    mechanical

    ioads

    lish

    design

    acceptability.

    Accom-

    stress

    intensity

    at

    all

    points,

    including

    all

    other effects,

    shall

    be

    used

    for

    the

    analysis

    to

    satisfu

    the

    rules

    ol NB-3200.

    The

    valve

    Design

    Specification

    shall

    provide

    the

    loadings

    and

    operating

    requirements

    to

    be

    considered

    under

    Level B,

    C,

    and

    D

    Service

    Limits

    [NCA-3252ta](5Jl

    for which

    a design

    analysis

    is

    to

    be

    included in

    the Design

    Report.

    (2)

    ln

    place

    of using the values

    of

    S, to satisfy

    the

    rules

    oF

    NB-3200,

    the

    allowable

    stress

    intensity

    values

    for

    ferritic

    valve

    body and

    bonnet

    materiais shall

    be those

    allowable

    stress values

    given

    in

    Section

    II,

    Part D, Subpart

    1, Table

    1A For

    materials in Section

    ll,

    Parr

    D, Subpart

    1,

    Tables

    2A and

    28, a reduced

    allowable

    stress

    intensity

    based

    on

    applying

    a factor

    ol A,67 to

    the

    yield

    srrenEths

    lisled in Section

    li,

    Part

    D,

    Subpart

    1, Table

    Y-1

    shall

    be

    used.

    (3J

    The adequary

    of the sh.ess

    analysis

    of the body

    and

    bonnet

    shall be

    verified by

    experimental

    stress

    analysis

    conducted

    in

    accordance

    with the requirements

    of Il-1100 through

    II-1400,

    lndividual

    tests shdl

    be

    made

    to

    verify

    the

    adequacy

    of

    the

    shress

    analysis

    of

    internal

    pressure

    effects

    and

    pipe

    reaclion

    effects. Tests

    shall

    be

    made

    on

    at

    least

    one

    valve

    model

    of a

    given

    configuration,

    but

    a verified

    analytical

    procedure

    may then

    be

    applied

    to

    other

    valves

    of

    the

    same

    configuration,

    although they

    may

    be of different

    size

    or

    pressure

    raring. The

    geometrical

    differences shal)

    be

    accounted

    for

    in

    the extrapolation

    stress

    analysis.

    The analytical procedure

    shall

    have

    verified capability

    of

    providing

    this

    exrrapolarion.

    (4J

    A

    Design

    Report

    shall

    be

    prepared

    in

    sufficient

    detail to show

    that the valve

    satisfies

    all applicable

    requirements,

    f5J

    Prior

    to

    installation,

    the valve

    shall be

    hydro-

    stafically

    tested

    in

    accordance

    with

    NB-3531.2,

    For this

    purpose, the

    prinrary

    pressure rating shall

    be

    determined

    by

    interpolation

    in

    accordance

    with

    NB-35a3[cJ.

    NB-3513

    Acceptabil,ity of

    Small.

    Valves

    Valve

    designs

    having

    an

    inlet

    piping

    connecfion

    NPS

    4

    (DN

    100)

    or

    less

    are

    acceptable

    when they

    satisfy either

    the

    stanclard

    design

    rules

    or

    the

    alternalive design

    rules.

    NB-3513.I

    Standard

    Design

    Rules. The

    design

    shall

    be

    such

    that

    the

    requirements

    ol

    NB-3530

    and NB-3541

    shall

    be

    met for

    wall

    thicknes.ses

    corresponding

    to the

    applicable pressure-temperaftue

    rating. When

    the Special

    Class

    Ratings

    of

    ASlvlE

    816.34 apply,

    the

    NDE

    exemptions

    of NB-2510

    shall

    not

    be

    used,

    NB-35I:1.2

    Atternative Design

    Rul.es.

    i

    valve

    design

    shall

    satisfy

    the

    requirements of NB-3512.2.

    NB-3515

    Acceptabllity

    of Metat

    BeLlows

    and

    Metal

    Diaphragm

    Stem

    Sea[ed Valves

    Valves

    using metal

    bellolvs

    or metal diaphragm

    stem

    modation

    of

    thermal

    se-Enqgly stresses and

    pipe

    reac-

    tions

    shall be

    as

    given

    inlttXZ)f Requilements

    for farigue

    analysis of either

    NB-3200 or NB-3550 shall

    be met.

    [dJ

    When

    permitted

    by the

    Design Specification,

    a

    weld

    end

    valve that

    does

    nol

    meet

    all of

    the requirements

    of NB-3540

    may

    be

    designed

    so that it

    meets

    the

    requirements

    of

    NB-3200

    for all

    pressure-retaining palts

    and

    those

    parts

    defined

    by

    NB-3546.3[a),

    and shall also

    meet

    all

    of the foliowing requirements,

    fI]

    Pressure,

    thermal,

    artd

    mechanical effects, sucb

    as

    those resulting

    .from

    earthquake,

    maximnm

    stem

    force,

    closure force,

    assembly forces,

    and others

    tlut

    nray

    be

    defined

    in

    the

    Design

    Specification,

    shall

    be inclucied in thc

    design analysis.

    For

    l evel

    A

    Service

    Limits,

    the

    pipe

    reaction

    effects

    are to be

    determined by considering

    that

    thc maximum

    liber stress in

    the connected

    pipe

    is at

    one-half of its

    yield

    strength

    in

    direct tension

    and

    at

    its

    yielct

    sh'ength

    in

    torsion

    and

    in

    bending in

    the

    plane

    of

    the

    neck and

    run, and also in

    the

    plane

    of the

    run

    perpencli-

    seals shall

    be constru*ed

    in accorclance with

    the

    rules

    of

    individuai

    pipe

    reaction

    eifects

    thal rcsult in

    the

    maxinurnt or

    diaphr-agms

    do not retain

    pressure,

    and Design

    BZ

    D-6

  • 7/24/2019 ASME Section III NP Extract

    2/6

    Pa

    h

    tsr

    Ps

    Pt,

    Pz

    Qp

    Qrt

    Qrs

    Sn,lntaxl

    Spr

    tr

    -

    P.

    =

    generai

    primary

    membrane

    stress intensify

    at

    crotch region,

    calculated according

    to NB-

    3545.1(a),

    psi

    (MPa)

    =

    Desigin Pressure,

    psi

    (MPaJ

    =

    Pressure

    Rating Class Index,

    psi

    (MPa)

    =

    standard calcuiation

    pressure

    frorn

    NB-3545.1,

    psi

    (MPa)

    =

    rated

    pressures

    from

    tables

    oi

    ASNIE

    81.6.34

    corresponding

    to

    Pressure

    RaEing Class

    lndices

    p.1

    and

    p,2, psi (MPa)

    =

    sum

    of

    primary plus

    secondary stresses

    at

    crotch

    resulting

    from internal

    pressure

    [NB-35a5.2[a]1,

    psi

    (lvlPa)

    =

    maximum thermal

    srress component caused by

    through-wall temperafure

    gradient

    associated

    with

    100"F/hr

    [56'C/hr)

    fluid

    temperanrre

    change rate

    [NB-3545.2(cJ],

    psi

    (]vlPaJ

    =

    maximum thermal secondary membrane

    plus

    bending stress resulting

    from structural

    discon-

    tinuity

    and

    100'F/hr

    (56'C/hr)

    fluid

    tempera,

    ture

    change

    rate, psi

    (MPaJ

    =

    mean radius of

    body

    wall at

    crotch

    region

    [Fig.

    NB-3545.2[c)-1],

    in.

    (mm)

    =

    inside

    radius

    of body

    at crotch

    region for

    calculating

    Qp

    [NB-3545.2(a)J,

    in.

    [mmJ

    =

    fillet radius of external

    surface

    at

    crotch

    [NB-3545,1[aJ],

    in.

    (mmJ

    =

    assumed

    maximum stress

    in

    connected

    pipe

    for

    calculating the secondary

    stress

    due

    to

    pipe

    reaction

    INB-3545.2[bJ],

    psi

    (lvlPaJ

    =

    fatigue stress intensity range

    at crotch

    region

    resulting

    from step

    change in

    fluid

    temperature

    A?2

    and

    pressure

    AP,

    (NB-3550), psi

    (MPa)

    "

    design

    stress

    intensity

    (NB-3532),

    psi

    [MPa)

    '

    sum of

    primary

    plus

    secondary

    stress

    lntenslfies

    at crotch region

    resulting

    from

    100"F/hr

    (56"C/hr)

    temperature change

    rate

    INB-

    3545.2),

    psi

    (lvlPaJ

    '

    maximum range

    of

    sum of

    primary

    plus

    second-

    ary

    sfress,

    psi

    (MPa)

    ,

    fatigue stress intensity

    at

    inside

    surface

    in

    crotch region resulting

    frorn

    100"F/hr

    [56'C/hr)

    fluid temperature

    change rate

    (NB-354s.3),

    psi

    [MPa)

    ,

    fatigue

    stress

    intensity

    at

    outside

    surface

    in

    crotch region

    resulting

    from 100"F/hr

    (56'C/hr)

    fluid

    temperature

    change rare

    [NB-3545.3),

    psi

    (lvlPa)

    ,

    thickness

    ofvalve

    rvall adiacent to

    crotch

    region

    for

    calculating

    1,1

    and

    L7y

    [Fig.

    NB-35a5.1[a)-1],

    in,

    [mmJ

    maximum

    effective

    metal

    thickness

    in crotch

    region

    for

    calculating

    thermal stresses

    [Fig.

    NB-35a5.2ic)-1],

    in.

    (mrnJ

    thickness

    of

    bociy

    (run)

    rvall

    adjacent

    to

    crotch

    for calculating

    1,1

    and

    Lp

    [Fig.

    NB-35a5.1(a)-1],

    rn.

    ImmJ

    ASITIE 2011a

    SETflON

    lll, D|VISION

    I

    -

    NB

    te

    =

    minimum body

    wall thickness adjacent to

    crotch

    for

    calculating

    thermal

    stresses

    IFig.

    NB-

    35a5.2[c]-11,

    in.

    (rnm)

    fm

    =

    rninimum

    body

    wall

    thiclsress

    as determined

    by

    NB-3541, in.

    (mm)

    ty

    t2

    =

    minimum

    wall thicknesses

    from

    ASME

    816.34

    corresponding

    to

    Listed

    Pressure Rating

    Class

    Indices

    p71

    and

    pr2

    and inside diameter dm,

    itl.

    Imm)

    API

    =

    f1111

    range

    of

    pressure

    fluctuation

    associated

    wtth

    At1,

    psi

    [MPa)

    /Pi

    =

    5ps616ed

    range

    of

    pressure

    flucruation

    asso-

    ciated

    with

    A7,,

    psi

    [MPa)

    ATtr

    =

    2

    specihed step

    change

    in

    fluid temperature,

    oF

    ("C),

    where I

    =

    ,2,3,

    ...,

    n;

    used

    to

    determine

    the

    fatigue

    acceptability

    of a valve body

    (NB-35541

    ll"r

    =

    speclfied range

    of fluid temperarure,

    "F

    ("C),

    where

    i

    =

    7,7,3,..,,

    n;

    used to

    evaiuate

    normal

    valve

    usage

    [N8.3553)

    d?"'

    =

    maxirnum

    magnitude

    of the difference ln aver-

    age

    wall

    temperafures for walis

    of

    thicknesses

    t

    and

    I,, resulting

    from

    100"F/hr

    (56'C/hrJ

    fluid

    temperature

    change

    rate,

    "F

    ('C)

    NB.354O

    DESIGN OF

    PRESSURE-RETAINING

    PARTS

    NB-354f

    General Requirements

    for

    Body Wa[[

    Thickness

    The

    minimurn

    wall thickness

    of

    a

    valve

    body

    is to

    be

    determined

    by the rules of NB-3542

    or

    NB-3543,

    NB-3542

    Minimum WaLt

    Thickness of

    Listed

    Pressure

    Rated

    Valvesz3

    The

    lvall

    thickness requirements

    for

    listed

    pressure

    rated

    valves

    apply

    also

    to integral

    body

    venturi

    valves. For

    a

    valve

    designed

    to

    a listed

    pressure

    rating of

    ASME

    816.34,

    the

    minirnum thickness of its

    body wall, including

    the neck,

    is

    to be determined

    from ASME

    816.34,

    except

    that

    the inside

    diameter

    d-

    shall

    be the

    larger of the basic

    valve

    body inslde dianreters in

    the region near

    the

    weldirrg

    ends,

    Highly

    localized

    variations

    of

    inside

    diarneter

    assoclated

    wlth

    rveld

    preparation\lNB-3544.8(a)

    and

    -@f-,neeri

    noi

    be

    consicie'Fedfir

    esE#sin -

    --ifrmiffiiimT-alTlhickness f,,. ln all such

    cases,

    however,

    the

    requiremenls

    ol NB-3545.2[b)(6)

    shall be

    satisfied.

    N8-3543

    Minimum Watl

    Thickness

    of

    Vatves

    of

    Nonl,isted

    Pressure

    Ratinga

    To

    design a

    valve

    for Design

    Pressure

    and

    Design

    Temperature

    corresponding

    to other

    than

    one of the

    pressure

    ratings

    listed

    in the tables of

    ASivlE

    816.34,

    the

    procedure

    is

    the

    same as

    that

    of

    NB-3542

    except

    that

    interpolation

    is

    required

    as foliows.

    [oJ

    Based on

    the

    Design

    'l'emperature,

    linear interpola-

    -:lLoa errUeen,thelabulttgdJe1lp_Elatqre_j11tejaAiC.sXal_bq::=.,.

    '-:

    used

    to

    deterrnine

    the iisted

    pressure

    rating

    pl,

    next

    C

    sr

    sm

    JN

    Spz

    16

    f-'

    L

    sJ

    t/J

    r/l

    +

    c{)

    n

    T.

    b

    ly.

    (-.

    tt

    L-J

    *85

    D-1

  • 7/24/2019 ASME Section III NP Extract

    3/6

    [eJ

    For

    socket

    welding

    ends,

    valves

    NPS

    Z

    IDN

    50J

    and

    smaller for

    which

    the body

    cavity

    consists

    of

    rylindrically

    bored

    sections

    shall meet

    all

    of

    the following:

    fIJ

    d. shall

    be

    the

    port

    drill

    diameter;

    [2J

    the

    requiremenr

    of NB'3542

    shall

    be

    satisfied;

    and

    [3J

    socket

    welding

    end

    valves

    greatet'than

    NPS

    2

    (DN

    50J

    shall

    not

    be

    used.

    NB-3544,9

    Openings

    for Auxltiary

    Connections.

    Openings

    for

    auxiliary

    connections,

    such

    as

    for

    drains,

    bypasses,

    and

    vents,

    shall

    meet

    the

    requirements

    of

    ASME

    816.34 and the

    applicable

    reinforcement

    requirements

    of NB-3330,

    NB-3545

    Body

    Primary

    and

    Secondary

    Stress

    Limits

    The limits

    ol

    primary

    and

    secondary

    stresses

    are

    established

    in

    the following

    subparagraphs.

    NB-3545.1

    Primary Membrane

    Stress

    Due

    to

    lnter-

    nat

    Pressure.

    For

    valves meeting

    all

    requirements

    of this

    Subarticle,

    the most

    highly

    stressed

    porrion

    of

    the body

    under internal

    pressure

    is

    at

    the

    neck

    to

    flow

    passage

    junction

    and

    is

    characterized

    by

    circumierential

    tension

    normal

    to the

    plane

    of

    center

    lines,

    wlth

    the

    maximum

    value at

    the

    inside surface.

    The

    rules

    of this

    paragraph

    are

    intended

    to control

    the

    general

    primary nrembrane

    stress

    in

    this

    crotch

    region,

    The

    Standard

    Calculation

    Pressure

    p"

    to

    be used

    for

    satisfoing

    the requiremenls

    of

    NB-3545

    is

    found

    either

    directly

    or

    by

    interpolation

    from

    the

    tables

    in

    ASlvlE

    815.34

    as the

    pressure

    at 500oF

    l25A'C)

    for the

    given

    Pressure

    Rating

    Class

    Index

    p^

    [aJ

    ln

    the crotch

    region,

    the

    maximum

    primary

    mem'

    brane

    srress

    is to

    be

    deterinined

    by

    the

    pressure area

    method

    in

    accordance

    with

    the

    rules

    of

    [1]

    through

    [6J

    beiow

    using

    Fig. NB-3545.1[aJ-1.

    IIJ

    From an

    accurately

    drawn

    layoud

    of

    the

    valve

    body, depicting

    the finished

    section

    of

    the

    rotch

    region

    in

    the

    muilal

    plane

    of

    the bonnet

    and flolv

    passage

    center

    lines, deterrnine

    lhe

    fiuid

    area

    ,4/alld

    metal

    area

    A',

    Aland

    An

    are to

    be based

    on

    the

    internal

    surface

    after

    complete

    Ioss

    of

    metal

    assigned

    to

    corrosion

    allowance.

    f?)

    Calculale

    the

    crotch

    general primary

    membrane

    stress

    intensity:

    ,^

    =(+

    +

    o.s)p,

    \An /

    The

    allolvable

    value

    of lhis

    sEress

    intensity

    is

    S.

    for

    the

    vaive

    body

    material

    at

    500"F

    (250"C) as given

    in

    Section

    Il,

    Part D,

    Subpart

    1, Tables

    2A

    and

    2P,

    (3)

    The

    distances

    L1 and

    Lp which

    provide

    bottnds

    on

    thc fluid

    and

    metal

    areas

    are determined

    as

    follows,

    Use

    the

    larger

    value

    of:

    ASME

    2011a

    SESTION

    lll, DMSloN 1

    '

    NB

    or

    and

    use

    Le

    =7,

    L1

    =0.5d-76

    (

    NB-3545,2 Secondarv Stresses.

    In

    addition to

    salis-

    I

    tlns

    tli

    t;l;-=

    .*t7

    --'=

    body shall

    also satisfy

    the

    crlterion

    that

    the

    range of

    Lp

    =

    0.512

    +

    0.354

    W-;6

    where

    the

    dimensions

    are as shown

    in

    Fig.

    NB-3545.1(a)-1,

    ln

    establishing

    appropriate

    values for

    the

    above

    parameters,

    some

    judgment

    may

    be

    required

    if

    the

    valve

    body

    is

    irregular

    as

    it is

    for

    globe

    valves and

    others

    with

    nonsymmetric shapes.

    ln

    such

    cases,

    the internal bound-

    aries

    oflr.shall

    be the lines that trace the

    greatest

    width

    of

    internal

    wetted

    surfaces

    perpendicular

    to the

    plane

    of

    the

    stem and

    pipe

    ends

    [Fig.

    NB-3545.1[a)-1

    skelches

    (b),

    [d),

    and

    (eJl.

    (4)

    lf

    the calcr.rlated

    boundaries fot'

    47

    and

    .4,,,

    as

    defined by

    /,,1 and lp, fall

    beyond

    tire

    valve

    body

    IFig.

    NB'3545.1(a)-1

    sketch

    (bJ],

    the

    body surface

    becomes the

    proper

    boundary

    for

    establishin

    g

    41 and A^,

    No

    credit

    is

    to

    be taken

    for

    any

    area

    ol

    connected

    piping

    which

    may be

    included

    within

    the

    limits

    of

    1,4 and L,y.

    lf

    the

    flange is

    included

    with An,

    the area

    of one

    bolt hole is

    to be.

    subtracted for

    determining the

    net

    value of rl.,

    [5]

    Except

    as rnodified below web

    or

    fin-like

    exten-

    sions

    of

    the

    valve body

    are

    to

    be

    credited

    to

    .4.

    only

    to

    an

    effective

    length

    from the wall

    equal

    to the average

    thickness of the

    redited

    portion,

    The remaining

    web

    area

    is

    to

    be added to

    +

    [Fig.

    NB-35a5.1[a)-1

    sketch

    (bJ],

    However,

    to the

    extent

    that

    additional area wili

    pass

    the

    following tesq

    lt may

    also

    be

    included

    in

    A-.

    A

    line

    perpendicular

    to the

    plane

    oflhe

    stem and

    pipe

    ends

    from

    any

    poitrts

    in

    r4. does

    not break out

    of

    the

    wetted

    surface

    but

    passes

    through a

    continuum

    of

    metal

    until

    it

    breaks

    through

    the

    outer

    surface

    oi

    the body.

    [6J

    ln.most cases, it is

    expected

    that the

    portions

    defined

    by

    A^ in the

    several

    illustrations

    of

    Fig,

    NB-3545.1(a)-1

    rvill

    be

    most

    highly

    stressed. However,

    in

    the

    case

    of highly irregular

    valve

    bodies,

    it

    is

    recommended

    that

    all

    sections

    of the

    crotch

    be checked

    to

    ensure that

    the

    largest value of

    P. has been

    established

    considering

    both

    open

    and

    fully

    closed

    condifions.

    flrJ

    ln

    regions

    than

    the crotch,

    while the

    value

    ol

    P,

    calculated

    be

    the

    highest

    value of

    body

    general primary

    s

    all

    normal

    valve

    for

    possible

    higher

    stress

    regions.

    Suspected

    regions

    and

    28.

    "\

    J

    Ul

    -{'

    ,,

    be

    checked

    by

    the

    pressure

    area method

    applied to

    thti

    particular

    local

    .body

    contours.

    I'he aliolvabie

    vaiue of

    this

    stress

    intensily is

    S,n

    lor

    the

    valve body

    material at

    500'F

    (26O'Cl

    as

    given

    in

    Seclion

    Il,

    Part D, Subpart 1,

    Tables

    2A

    89

    o-E

  • 7/24/2019 ASME Section III NP Extract

    4/6

    ,*?;;

    fri,s,;tr

    i

    ,Y

    .t

    0

    t:

    l

    c

    .J

    ASJIIE 2011a

    SECTION

    lll,

    DIVISION

    L

    -

    NB

    19 These requirements for the acceptability

    of a valve design

    are

    not

    intended

    to

    ensure the

    functional

    adequary

    oithe

    valve.

    However,

    for

    pressure

    relief

    valves

    the

    Designer is

    cautioned

    that

    the requirements of

    NB-7000 relafive to

    set

    pressure,

    lift,

    blowdown, and ciosure

    shall be

    meL

    tu

    --

    i

    20

    |

    CAUTTON:

    Fertain

    types

    of

    double

    seated valves

    have tire

    capabillty

    of trapping liquid

    ln

    the

    body or bonnet cavlty

    in

    the closed

    7

    position,

    If

    such

    a carrity

    accunrulates

    liquid

    and

    ls

    ln the closed

    position

    at

    a

    time

    wlren

    adjacent

    system

    piping

    ls lncreasing

    ln

    temperature,

    a

    substantial

    and

    uncontrolled

    increase

    In

    pres.sure

    ln

    the body or bonnet cavlty may result. Where such

    a

    condltlon

    is

    posslble,

    lt

    i.s

    the

    responsibllity

    of the Owncr

    or

    the Orvner's

    dcsignee

    to

    provlde,

    or

    require

    to

    be

    proulded,

    protection

    agalnst

    harmfirl

    overpressure ln such valves.

    21

    The

    severity and

    frequency

    of

    specified

    fluid

    temperarure

    variations

    may

    be

    such

    that

    the

    period

    of

    calculated

    pressure

    integrity is

    less

    than

    plant

    design

    life.

    In

    such

    cases

    it is the responsibility of the Certiflcate Holder to

    state

    these conditions

    in

    the

    Design

    Report

    (NB-3550).

    22

    Special

    feahrres such

    as

    wear

    surfaces or

    seating surfaces may demand

    special

    alloys or

    proprietary

    lreaments.

    The

    absence

    ofsuch

    materials from Section II, Par"t

    D,

    Subpart

    1,

    Tables

    2A

    and

    2B

    shall notbe

    construed

    to

    prohibit

    their

    use and

    such nraterials do not

    require approval under

    Appendix IV

    [NB-z121),

    23 r\

    listecl

    pressrlre

    rated

    valve is one listed in the tables of ASIvIE 815.34.

    A

    nonlisted

    pressrrre

    rated

    valve

    is

    one

    whose

    Design

    Pressure

    and

    Temperarure do not

    specifically appear in

    those tables

    [NB-3543J.

    24

    For

    all

    listed

    pressure

    ralings

    except

    Class 150,

    the Pressure Rafing Class

    lndex

    is

    the same

    as

    the

    pressure

    rating

    ciass

    designation. For

    Class

    150 use 115

    for

    the

    Pressure

    Rating

    Class

    lndex.

    25

    Adjacent

    poirrfs

    are defined as

    points

    which

    are

    spaced

    less

    than

    the distance

    ZJF|

    from

    each

    other, where R and t

    are

    the

    mean radius and thickness, respectively, of

    the

    vessel,

    nozzle,

    flange,

    or other

    component in

    which

    the

    points

    are

    iocated,

    26

    For

    piping

    products,

    such as tees

    and branch connections,

    the

    second

    term of

    eqs. NB-3652[9), NB-3553.1(a)tf0),

    and

    NB-3653.2(aJ(11),

    namely

    that

    containing

    &16 is

    ro

    be

    calculated

    as

    referred

    to in

    NB-3583.1(d).

    27

    Socket welds

    shall

    not be

    used

    where

    the

    existence of crevices

    could accelerate corrosion.

    28

    The flexibility of a curved

    pipe

    or

    welding elbow

    is

    reduced

    by

    end

    effects,

    provided

    either

    by

    the

    adjacent

    stralght

    pipe

    or by the

    proximity

    of other relatively

    stiff

    members

    which

    inhibit

    ovalizalion of the cross section. in certain

    cases,

    these end effects

    may aiso

    reduce

    the stress.

    29 c

    equals

    nominal wall

    thickness,

    30

    Welds

    that

    are

    exposed to corrosive

    acbion

    should

    have a

    resistance

    to

    corrosion

    that

    is

    not

    substarrtialty less than

    that

    oF the cladding. Thc use of

    filler

    metal

    that

    will

    deposit

    weld

    metal

    which

    is

    similar

    to

    the composition

    of

    the

    cladding

    material

    is

    reconrmended.

    lf weld

    metal

    ol

    different composition

    is

    used, it

    should

    have

    properties

    compatible

    lvith

    the

    applicahon.

    31 An

    interntediate

    postweld

    heat

    treatntenr

    lor

    this

    purpose

    is

    defined

    as

    a

    poslweld

    heat

    lreatment

    performed

    on a

    weld

    wilhin

    a temperature

    range not lower

    than the rninimum

    holding temperature

    range

    to whrch the weld

    shall

    be

    subjected

    during the

    final

    postweld

    heat rreatment.

    32

    A

    radioglaphic examination

    [NB-5111(a)]

    is

    required; a

    preservice

    exarnination

    [NB-5111[b]]

    may

    ornray

    not be

    required

    lor

    compliance

    to the Design

    Specification

    INCA-3252(c)).

    33 SNT-TC-IA is a Recommended Practice

    for

    Nondestructive

    Testing Personnel

    Quaiificarion

    and

    Certification

    pttbiished

    by the American Sociely

    for

    Nondestructive'l'esting,

    1711 Arlingate

    Lane, P.0.

    Box

    28518, Columbus, 0H

    +3228-051-8.

    34 Personnel qualified

    by examination

    and

    certifled

    to the

    previous

    editions

    of SNT-TC-1A

    are

    considered to

    be

    qualified

    to

    the editiotr

    referenced

    in Tabie

    NCA-7100-2

    when

    the

    recertificatiorr

    is based

    on continuing satisfactory

    performance.

    Ail

    reexanrinations

    and

    new exanrinations

    shall be

    in accordance with

    the

    edition

    referenced

    in

    Tabie

    N

    CA-7 100-2.

    35

    Employer

    as

    used in

    this Articie

    shall include:

    N Certificdte Holders;

    Qualiry

    System Certificate Holdersj Ivlaterial

    Organizalions

    who hre

    qualified

    in

    accordance

    with NCi\-3842; and

    organizations

    rvbo provide

    subcontracted

    nondestructive

    exanrirration services

    to

    organizalions

    described

    above.

    274

    D-1

  • 7/24/2019 ASME Section III NP Extract

    5/6

    6,'f

    NL-ss

    //

    ASII{E

    2011a

    SECTI0N

    tll,

    DwIS|ON 1

    .NC

    Adjacent

    points are

    defined

    as

    points

    that

    are

    spaced

    less

    than

    lhe

    distance

    z.fRT

    fronr each other, where R and t are

    the mean

    radius

    and thickness,

    respectively,

    of

    the vessel,

    nozzle,

    flange,

    or dther

    part

    in which the

    points

    are located.

    The head

    design

    curves

    have been

    developed

    considering

    membrane

    stress

    requirements,

    plastic

    collapse,

    ryclic

    load

    conditions,

    and the

    effects of

    maximum

    allowable

    toierances

    in accordance lvith

    NC-4222,

    See A-4000 of Appendix

    A

    lor

    the

    design

    formulas

    for the curyes

    ol Fig,

    NC-3224.6-1'

    Heads

    having

    D/2h

    = 2 have

    equivalent

    torisphericai properties

    of

    a

    torisphere

    of

    L/D

    =

    0,90

    and

    rlD

    =

    0.17,

    The

    minimum

    thickness

    for

    ali

    pipe

    materials

    is

    the

    nominal

    thict

  • 7/24/2019 ASME Section III NP Extract

    6/6

    ,g

    i)

    7

    f1

    4

    d

    ?.

    D

    t:

    )

    n

    Q

    p"-L.

    "*

    N

    i:

    --3:,,

    I

    ASIIIE 2011a

    SECTION

    IIl, DIVISION

    1

    .

    ND

    18

    Side

    plates

    of

    a flat

    sided

    vessel are defined as

    any

    olthe

    flat

    plates

    forming

    an

    integral

    part

    of

    the

    pressure

    retaining

    enclosure.

    19

    Written for fittings with internal

    threads

    but

    also

    applicabie

    to

    externally

    threaded and

    socket

    or bun

    welded

    fittings.

    20

    tD

    is defined

    in

    XI-3130.

    21 All

    dimensions

    given,

    for

    size of vessel

    on which inspection

    openings

    are

    required,

    are

    nominal,

    22

    ltis

    recognized

    that

    other

    acceptable

    procedures

    may

    existthar

    also conslilute

    adequate design methods,

    and

    it is

    nol

    --r._th?

    intention

    to rule

    out

    these a-lternafive

    methods

    provided

    they can

    be

    shown to

    have been

    satisfactory by

    a*ual

    sqvrce

    expenence,

    23

    ICAUTION:

    pertain

    types

    of double

    seated

    valves

    have the

    capability

    of trapping

    liquid in the hody

    or

    bonnet

    carrity

    in

    the

    closed

    position.

    If

    such

    a cavity accumulates

    liquid and is

    in

    the

    closed

    position

    at

    a

    time when

    adjacenl system

    piping

    is

    increasing

    in tempera$re,

    a

    substantial and

    uncontrolled

    increase in

    pressure

    in

    the

    body

    or bonnet cavity

    may

    result. Where such a

    condltion

    is

    possible,

    it is the responsibility

    of the Owner

    or his designee

    to

    provide,

    or

    require to be

    provided,

    protection

    against

    harmful

    overpressure

    in

    such valves.

    24

    The

    minimum thicknesses of straight

    pipe

    shown in

    Table ND-3642.1(cJ-1

    should be sufficient to allow

    the

    pipe

    to

    meet the minlmum wall thickness

    requirements

    of

    ND-3641

    after

    having

    been bent

    on the radii

    shown.

    25 Expansion

    Joint

    Manufacturers Association,

    25

    North

    Broadway,

    Tarrytown,

    NY 10591.

    25

    See

    Appendix

    II, II-1520G),

    27

    The

    pressure

    term

    in

    eqs.

    ND-3652[8), ND-3653.1(aJ(9ai, ND-3653.1[bJ(9bJ

    and

    ND-3553,2(c)[11)

    may

    not apply

    tor bellows and expansion

    joints,

    28 Design Pressure nray

    be used

    lf

    the

    Design

    Specification

    states

    that

    peak pressure

    and

    earthquake

    need

    not

    be taken

    as acting

    concurrently,

    29

    Socket

    welded

    joints

    should

    not

    be used

    where the

    existence

    of

    crevices

    qould

    result in accelerated corosion.

    30

    Fillet and

    partial

    penerration

    welds should not be

    used

    where

    severe

    yibration

    is expected.

    31 These

    rules do not limit

    storage fanks

    from

    being

    installed below

    grade

    or

    below

    ground,

    provided

    the

    tanks

    are

    not

    subject to external

    pressure

    resulting

    from earth or fill,

    32 The limitalion of the

    Design

    Pressure to atmospheric

    is

    nol

    intended

    to

    preclude

    the use

    of these

    tanks

    at vapor

    pressure

    slightly

    above

    or

    below atmospheric

    within

    the

    range

    normally

    required

    to

    operate

    vent

    valves.

    If

    these

    pressures

    or

    vacuums

    exceed

    12

    ozf

    in.z,

    especially

    in

    combination

    with

    large

    diameter

    lank, the lorces

    involved

    may

    require special consideration

    in

    the

    desigrr.

    33

    Any

    specified corrosion allowance

    for the

    shell

    plates

    shall

    be

    added to

    the calculated

    thickness.

    34

    The nominal

    thickness

    of shell

    plates

    refers to

    the

    tank shell as

    constructed.

    The

    thicknesses

    specified

    are based

    on

    erection requirements.

    35 API

    Standard 2000,

    L96B Edition, Venting

    Atmospheric and

    Low Pressure

    Storage

    Tanks, American

    Perroleum

    lnstitute, 1220 L

    Street,

    NW, Washington,

    DC

    20005-4070.

    35

    The

    decrease

    in

    yteld

    stress at

    Design

    Temperature

    shall

    be

    taken

    into

    accounL

    37

    The formulas appiying to self-supporting

    roofs

    provide

    for

    a

    unifornr

    live

    load of 25

    lb/ftz

    (1.2

    kPaJ.

    3Mhenever

    a

    tank is to

    be operated

    with

    liquid

    levels that

    at no

    time

    reach the

    top

    of

    the rool

    but

    is

    to

    be

    filled to

    the

    very top

    of the

    roof

    during

    the

    hydrostatic

    test,

    it shall

    be designed

    for both

    of

    these

    maximum

    liquid

    level

    conditions,

    using

    in

    each

    case

    the density

    of

    the liquid employed.

    If

    a

    tank is

    not

    designed

    to be nlied to the very top of

    the

    roof,

    overfili

    protection

    is required,

    A

    suitable

    mat'gin

    shali

    be

    allowed between

    the

    pressure

    pormally

    existing

    in the

    gas

    or

    vapor

    space and

    the

    pressure

    at

    which the

    reliefvalves

    are sel, so

    as

    to

    allow for

    the

    increases

    in

    pressure

    caused by

    variations in

    the

    temperature

    or

    gravily

    of

    the

    liquid contents

    of

    the tank

    arrd

    other

    factors

    affecting

    the pressule

    in

    the

    gas

    or vapor

    space,

    J :

    plfi"lyi:uy'llill

    b='.q91 :l E1.tBt :y re, :9.-ys:te-tielr{-ygry.e='--?le-:s

    lglpl}

    39

    40

    L/b

    D-)3