64
OPTIMIZATION OF PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR REFRIGERANT R-410A AIR-CONDITIONER A Thesis Presented to The Academic Faculty By Kristinn A. Aspelund In Partial Fulfillment of the Requirements for the Degree Master of Science in Mechanical Engineering Georgia Institute of Technology December 2001

As Pelu Nd Thesis

Embed Size (px)

Citation preview

  • OPTIMIZATION OF PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR REFRIGERANT R-410A AIR-CONDITIONER

    A Thesis Presented to

    The Academic Faculty

    By

    Kristinn A. Aspelund

    In Partial Fulfillment of the Requirements for the Degree

    Master of Science in Mechanical Engineering

    Georgia Institute of Technology December 2001

  • ii

    OPTIMIZATION OF PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR REFRIGERANT R-410A AIR-CONDITIONER

    Approved:

    ________________________________ Samuel V. Shelton ________________________________ Sheldon M. Jeter

    ________________________________ William J. Wepfer

    Date Approved____________________

  • iii

    TABLE OF CONTENTS

    TABLE OF CONTENTS III

    LIST OF FIGURES V

    NOMENCLATURE VI

    SUMMARY XII

    CHAPTER I. INTRODUCTION 1

    RESEARCH OBJECTIVES 3

    CHAPTER II. THE AIR-CONDITIONER MODEL 4

    AIR CONDITIONING SYSTEM AND COMPONENT MODELING 4 Compressor 5 Condenser 9 Condenser Fan 18 Expansion Valve 19 Evaporator 20 Evaporator Fan 22 Refrigerant Mass Inventory 23

    CHAPTER III. THE OPTIMIZATION ALGORITHM 27

    THE FIGURE OF MERIT 27 SIMPLEX SEARCH METHOD 28 ONE ITERATION OF THE NELDER-MEAD SIMPLEX SEARCH ALGORITHM 29 SOFTWARE TOOLS 31

    CHAPTER IV. OPTIMIZATION OF PARAMETERS 34

  • iv

    OPTIMIZATION PARAMETERS 34 OPTIMAL CONDENSER DESIGN 44

    CHAPTER V. CONCLUSIONS AND RECOMMENDATIONS 46

    CONCLUSIONS 46 GENERAL DESIGN GUIDELINES 49 RECOMMENDATIONS 49

    REFERENCES 51

  • v

    LIST OF FIGURES

    Figure 2-1: The Actual Vapor-Compression Refrigeration Cycle 6

    Figure 2-2: Typical Cross Flow Heat Exchanger with 5 tubes per circuit, 3 circuits and 6 rows. 12

    Figure 2-3: Hexagonal Fin Layout and Tube Array 17

    Figure 3-1: Nelder-Mead simplex and all possible new points. 32

    Figure 4-1: Optimization parameters 35

    Figure 4-2: Seasonal COP as a function of maximum condenser cost for varying outer tube diameter and fixed 7.5 ft2 frontal area. 37

    Figure 4-3: Seasonal COP, for an air-conditioner with a 5/16 tube condenser, as a function of maximum condenser cost for varying frontal area. 39

    Figure 4-4: Number of horizontal rows with 5/16 tubing and max cost at $20 and COP versus frontal area. 40

    Figure 4-5: Number of rows with 5/16 tubing versus condenser cost for fixed 7.5 ft2 frontal area. 41

    Figure 4-6: Horizontal tube spacing ratio for 5/16 tubing versus condenser cost for fixed 7.5 ft2 frontal area. 42

    Figure 4-7: Fin spacing versus number of rows. 43

    Figure 4-8: Search for the optimal solution for a 5/16 tube condenser with fixed frontal area of 7.5 ft2 and maximum material cost of $20. 45

  • vi

    NOMENCLATURE

    Ac = Minimum free-flow cross sectional area.

    Aci = Cross sectional area of the refrigerant-side of the tube.

    Afin = Total fin surface area.

    Afr,con = Frontal area of condenser.

    Ao = Total air-side heat transfer area including the fin and tube areas.

    C = Heat capacity.

    Cmax = Maximum heat capacity between that of the air and the refrigerant.

    Cmin = Minimum heat capacity between that of the air and the refrigerant.

    COP = Coefficient of Performance

    COPseas = Seasonal Coefficient of Performance

    COP@82F = Coefficient of Performance for an air-conditioner running in 82 F ambient temperature.

    cp = Specific heat at constant pressure.

    cp,eff = Effective specific heat at constant pressure.

    Cr = Ratio of the minimum heat capacity to the maximum heat capacity

    H = Condenser height.

    h1 = Specific enthalpy of refrigerant entering the compressor.

    h2 = Actual specific enthalpy of refrigerant exiting the compressor.

    h2a = Specific enthalpy of refrigerant exiting the superheated portion of the compressor.

  • vii

    h2b = Specific enthalpy of refrigerant entering the sub-cooled portion of the compressor.

    h2s = Ideal specific enthalpy of refrigerant exiting the compressor.

    h3 = Specific enthalpy of refrigerant entering the expansion valve.

    h4 = Specific enthalpy of refrigerant exiting the expansion valve.

    ah = Air-side heat transfer coefficient.

    rh = Refrigerant-side heat transfer coefficient.

    k = Thermal conductivity.

    k = Number of iterations.

    L = Length.

    l = Integral variable evaporating tube length.

    Lcon,sc = Tube length of the sub-cooled portion of the condenser tubes.

    Lcon,sh = Tube length of the superheated portion of the condenser tubes.

    Levap,sh = Tube length of the superheated portion of the evaporator tubes.

    Lsat = Tube length of the saturated portion of the heat exchanger tubes.

    Ltot = Total tube length of the heat exchanger tubes.

    m = Refrigerant mass flow rate through the compressor.

    satam , = Mass of flow rate of air flowing over the saturated portion of the condenser.

    totam , = total mass flow rate of air flowing over the condenser.

    mcon,sc = Mass of refrigerant in the sub-cooled portion of the condenser.

    mcon,sh = Mass of refrigerant in the superheated portion of the condenser.

  • viii

    mes = Extended surface geometric parameter.

    mevap,sh = Mass of refrigerant in the superheated portion of the evaporator.

    n = Number of parameters

    Nc = Number of parallel flow circuits.

    Ntpc = Number of tubes per circuit

    NTU = Number of transfer units.

    PD = Piston Displacement.

    Pe = Perimeter.

    Prat = Ratio of condenser saturation pressure to the evapuratior saturation pressure

    Q = Rate of total heat transferred between the refrigerant and the air.

    qcon,sat = Amount of heat per unit mass transferred between the air and the refrigerant in the saturated portion of the condenser.

    qcon,sc = Amount of heat per unit mass transferred between the air and the refrigerant in the sub-cooled portion of the condenser.

    qcon,sh = Amount of heat per unit mass transferred between the air and the refrigerant in the superheated portion of the condenser.

    maxQ = Maximum possible amount of heat transferred between the refrigerant and the air.

    r = Outer radius of tube.

    R = Aspect ratio.

    Rcv,pd = Ratio of clearance volume to the piston displacement.

    Re = Equivalent radius for a hexagonal fin.

    Rf,a = Air-side heat exchanger fouling factor.

  • ix

    Rf,r = Refrigerant-side heat exchanger fouling factor.

    Rw = Tube wall thermal resistance.

    Tc,i = Temperature of cold fluid entering the heat exchanger.

    Th,i = Temperature of hot fluid entering the heat exchanger.

    Trat = Ratio of condenser saturation temperature to the evapuratior saturation temperature.

    Tsc = Sub-cool exiting condenser.

    UA = Overall heat transfer coefficient.

    W = Condenser width.

    wa,com = Actual compressor work per unit mass of refrigerant.

    confW , = Condenser fan power.

    ws,com = Isentropic compressor work per unit mass of refrigerant.

    v = Specific volume.

    v1 = Refrigerant specific volume entering the compressor.

    v2 = Refrigerant specific volume exiting the compressor.

    Va,con = Velocity of the air flowing over the condenser.

    vl = Specific volume of the fluid in the liquid phase.

    vv = Specific volume of the fluid in the vapor phase.

    x = Vapor quality.

    xi = Vapor quality at the inlet of the heat exchanger.

    Xf = Fin spacing

    Xl = Transverse tube spacing.

    Xt = Tube spacing normal to air flow.

  • x

    Z = Number of rows.

    = Coefficient of the empirical relation for determining the equivalent circular radius for hexagonal fins.

    = Expansion.

    hlat = Change in the latent enthalpy.

    hsens = Change in the sensible enthalpy.

    htot = Change in the total enthalpy.

    Pa,con = Pressure drop on the air-side of the condenser.

    = Fin effectiveness.

    = Contraction.

    = Fin parameter that is a function of the equivalent circular radius of a hexagonal fin

    c = Compressor thermal efficiency.

    f = Fin efficiency.

    fan,con = Condenser fan efficiency.

    s = Surface efficiency.

    s,a = Air-side surface efficiency.

    s,r = Refrigerant-side surface efficiency.

    v = Compressor volumetric efficiency.

    = reflection.

    v = Density of the fluid in the vapor phase.

    = Shrinkage.

  • xi

    = Coefficient of the empirical relation for determining the equivalent circular radius for hexagonal fins.

  • xii

    SUMMARY

    Residential air-conditioning equipment currently uses HCFC refrigerant R-22.

    Production of the refrigerant will be banned in 2010 except to service existing equipment.

    The refrigerant R-410a is a strong candidate to replace R-22. While there is limited

    information available on R-410a condenser coil design, a model of an air-conditioning

    system with a focus on the finned-tube condenser design details using R-401a as the

    working fluid has previously been developed by Wright (2000). The model evaluates the

    performance for a specific and detailed condenser design, e.g. frontal area, tube diameter,

    air velocity, etc.

    An optimization algorithm for the fin-tube condenser design is needed. Due to

    computational speed limitations an exhaustive search for the optimal design is not

    practical. This research developed design search techniques to find the optimal

    condenser design and controllable operational parameters with various constrains for a

    given figure of merit. The Simplex Search Method (Nelder et. al., 1965) was

    implemented to search and optimize the eight primary condenser design parameters. This

    study found an optimum condenser design for various frontal area and cost constrains.

    The software developed is appropriate for engineering design use in the air-conditioning

    industry.

  • 1

    CHAPTER I.

    INTRODUCTION

    In the last decade public awareness on the destruction of the stratospheric ozone

    layer grew and the most harmful materials were banned. Under the terms of the Montreal

    Protocol, the United States agreed to meet certain obligations that have brought

    challenges to the Heating Ventilation Air Conditioning and Refrigeration (HVAC&R)

    industry. Chlorofluorocarbons (CFCs) were used to a large extent as refrigerants but

    have high ozone-depletion potential (ODP) and they were completely phased out in the

    USA in 1995. Though not harmless environmentally friendlier and inexpensive

    hydrochlorofluorocarbons (HCFCs), such as HCFC-22 (R-22), are exclusively used as a

    refrigerants in residential heat pumps and air-condition systems. However in the USA

    the Environmental Protection Agency (EPA) has published regulations prohibiting the

    production of R-22 after 2010 except for servicing equipment produced prior to 2010.

    After 2020 the production of R-22 will be completely banned (EPA, 2001).

    Due to zero ODP and many favorable performance characteristics, e.g., good

    cycle efficiency, non-flammability and high working pressure, R-410a is a strong

    candidate as a replacement for R-22. There is however limited information about

    condenser coil design for air-conditioners using R-410a as a working fluid.

  • 2

    Due to its global warming impact environmental regulations have also focused on

    the emission of CO2. Many countries have agreed to reduce their CO2 production. This

    must be accomplished by reducing energy usage through higher efficiency energy

    systems. In a warm climate, residential air-conditioners are responsible for a major

    portion of a households total energy usage and since they are only run when the outside

    temperatures are high, a peak electrical demand occurs only on hot days. Utilities must

    invest in an electric power generation and distribution infrastructure to meet the air-

    conditioner peak demand (Wenzel et. al 1997). This, along with public awareness, has

    created pressure for the efficiency of air-conditioning equipment to improve.

    Wright (2000) developed a detailed model for an air-conditioning system using R-

    410a as a working fluid. The model has detailed simulation of the components of the air-

    conditioner system for various designs, including the compressor, the condenser, the

    evaporator and the expansion valve. The condenser is the focus of the model

    incorporating the best available simulations for the air-side and refrigerant-side pressure

    drops and heat transfer coefficients. While the effects of varying some design parameters

    were studied an exhaustive design optimization search would have taken months to

    execute.

  • 3

    Research Objectives

    The primary objective of the current work is to study and optimize the geometric

    design and operating parameters for a finned-tube condenser of a vapor compression

    residential air-conditioning system using R-410a as a working fluid. More specifically

    to:

    Find and implement a design optimization search technique for the air-

    conditioner condenser design.

    Apply the optimization technique through software development to optimize

    controllable operational and geometric design parameters.

    Develop design guidelines for a condenser coil design

    Develop a software tool for condenser designers to design coils for optimized

    air-conditioner performance.

  • 4

    CHAPTER II.

    THE AIR-CONDITIONER MODEL

    The air-conditioner model used in the current study was developed by Wright

    (Wright, 2000). The following development of the model is based on Wrights (2000)

    thesis entitled Plate-Fin-and-Tube Condenser Performance and Design for Refrigerant

    R-410A Air-Conditioner. This development is detailed here in this study for

    completeness.

    Air Conditioning System and Component Modeling

    Heating, Ventilating, and Air-Conditioning (HVAC) systems that provide a

    cooling effect depend on a refrigeration cycle. Both the control and performance of

    HVAC systems are significantly affected by the performance of the refrigeration cycle.

    Therefore a basic understanding of the refrigeration cycle is needed in the design and

    optimization of HVAC systems. Of the three basic refrigeration cycles (vapor

    compression, absorption, and thermo-electric), the cycle typically used in the HVAC

    industry is the vapor compression cycle. Vapor compression refrigeration has many

    complex variations, but only the basic compression cycle will be discussed here.

  • 5

    The vapor compression refrigeration cycle modeled for this study is shown in

    Figure 2-1. As the figure shows, low pressure, superheated refrigerant vapor from the

    evaporator enters the compressor (State 1) and leaves as high pressure, superheated vapor

    (State 2). This vapor enters the condenser where heat is rejected to outdoor air that is

    forced over the condenser coils. The refrigerant vapor is cooled to the saturation

    temperature (State 2b), and then cooled to below the saturation point until sub-cooled

    liquid is present (State 3). The high-pressure liquid then flows through the expansion

    valve into the evaporator (State 4). The refrigerant then absorbs heat from warm indoor

    air that is blown over the evaporator coils. The refrigerant is completely evaporated

    (State 4a) and super heated above the saturation temperature before entering the

    compressor (State 1). The indoor air is cooled and dehumidified as it flows over the

    evaporator and returned to the living space.

    Compressor

    The purpose of the compressor is to increase the working pressure of the

    refrigerant. The compressor is the major energy-consuming component of the

    refrigeration system, and its performance and reliability are significant to the overall

    performance of the HVAC system. In general there are two categories of compressors:

    dynamic compressors and displacement compressors. Dynamic compressors convert

    angular momentum into a pressure rise and transfer this pressure rise to the vapor

    (McQuiston and Parker, 1994).

  • 6

    Figure 2-1: The Actual Vapor-Compression Refrigeration Cycle

    Saturated Sub-cooled Superheated 2b 2a3

    Expansion Valve

    Saturated Superheated

    4 4a

    Compressor

    Condenser

    Evaporator

    1

    2

    2b3

    4

    2a

    2

    4a

    1

    S

    T

  • 7

    Positive displacement compressors increase the pressure of the vapor by reducing the

    volume in a closed space. For this study, scroll type positive displacement compressors,

    which dominate the residential air-conditioning industry, are considered.

    The amount of specific work (work per unit mass of refrigerant) done by an ideal

    compressor can be expressed with the following:

    ( )12, hhw scoms = (2-1)

    where h1 is the refrigerant enthalpy entering compressor and h2s refrigerant enthalpy for

    isentropic compressor. For a non-ideal compressor, the actual amount of work done

    depends on the efficiency,

    ( )12,, hhwwc

    comscoma ==

    (2-2)

    where c is the compressor isentropic efficiency. The subscripts hx refer to the state point

    x on Figure 2-1. For a scroll type compressor, Klein and Reindl (1997) have determined

    that the thermal efficiency is related to the pressure ratio and a temperature ratio by the

    following relationship:

    ratratratratratratc TPTTPP 061.331.503.111281.0814.325.6022 ++= (2-3)

  • 8

    where Prat is the pressure ratio and Trat is the temperature ratio, which are defined by

    the following relationships:

    evapsat

    condsatrat P

    PP

    ,

    ,= (2-4)

    evapsat

    condsatrat T

    TT

    ,

    ,= (2-5)

    The coefficients in this correlation are based on saturated temperatures and not on the

    actual temperatures at the inlet and outlet of the compressor.

    The volumetric efficiency is another important consideration in selecting and

    modeling compressors. The volumetric efficiency is the ratio of the mass of vapor that is

    compressed to the mass of vapor that could be compressed if the intake vapor volume

    were equal to the compressor piston displacement. The volumetric efficiency is

    expressed as:

    = 1

    vv1

    2

    1,v pdcvR (2-6)

    where v is the compressor volumetric efficiency, Rcv,pd is the ratio of clearance volume

    to the piston displacement, v1 is the specific volume entering the compressor and v2 the

    specific volume at the compressor exit. The volumetric efficiency is used to determine

  • 9

    the mass flow rate of the refrigerant through the compressor,

    m , for a given compressor

    size by the following expression,

    2v

    PDm v= (2-7)

    where PD is the Piston Displacement (Threlkeld, 1970).

    Condenser

    The condenser is a heat exchanger that rejects heat from the refrigerant to the

    outside air. Although there are many configurations of heat exchangers, finned-tube heat

    exchangers are the type most commonly used for residential air conditioning applications.

    Refrigerant flows through the tubes, and a fan forces air between the fins and over the

    tubes. The heat exchangers used in this study are of the cross-flow, plate-fin-and-tube

    type. A schematic of this heat exchanger is shown in Figure 2-2. The tubing of the

    condenser is one of the decisions that designer has to make. On Figure 2-2 tubes having

    flow in the same direction are shown to have the same color. The flow can flow through

    many parallel through many tubes simultaneously in a parallel circuit. The tubes are then

    connected at the ends by bends. It is assumed that since the bends have no fins the heat

    transfer is zero.

    When the refrigerant exits the compressor, it enters the condenser as a

    superheated vapor and exits as a sub-cooled liquid. The condenser can be separated into

  • 10

    three sections: superheated, saturated, and sub-cooled. The amount of heat per unit mass

    of refrigerant rejected from each section can be expressed as the difference between the

    refrigerant enthalpy at the inlet and at the outlet of each section:

    ,22, ashcon hhq = (2-8)

    ,22, basatcon hhq = (2-9)

    and

    .32, hhq bsccon = (2-10)

    The total heat rejected from the hot fluid, which in this case is the refrigerant, to the cold

    fluid, which is the air, is dependent on the heat exchanger effectiveness and the heat

    capacity of each fluid:

    ( )icih TTCQ ,,min = (2-11)

    where is the heat exchanger effectiveness; Cmin is the smaller of the heat capacities of

    the hot and cold fluids, Ch and Cc respectively; Th,i is the inlet temperature of the hot

  • 11

    fluid; and Tc,i is the inlet temperature of the cold fluid. The heat capacity C, is expressed

    as:

    pcmC = (2-12)

    where

    m is the mass flow rate of fluid and cp is the specific heat of the fluid. The heat

    capacity, C, is the extensive equivalent to the specific heat, and it determines the amount

    of heat a substance absorbs or rejects for a given temperature change.

    The amount of air flowing over each section of the condenser is proportional to

    the tube length, L, corresponding to each specific section. For example, the mass of air

    flowing over the saturated section of the condenser can be found by the following

    relation:

    tot

    sat

    tota

    sata

    LL

    mm

    =

    ,

    ,

    (2-13)

    The heat exchanger effectiveness discussed earlier in this chapter is the ratio of the actual

    amount of heat transferred to the maximum possible amount of heat transferred,

    maxQQ

    = (2-14)

  • 12

    Figure 2-2: Typical Cross Flow Heat Exchanger with 5 tubes per circuit, 3

    circuits and 6 rows.

    w

    d

    h

    Xl

    Xt

    Air flow

  • 13

    The heat exchanger effectiveness is dependent on the temperature distribution within

    each fluid and on the paths of the fluids as the heat transfer takes place, i.e. parallel-flow,

    counter-flow, or cross-flow. In most typical condensers and evaporators, the refrigerant

    mass flow is separated into a number of discrete tubes and does not mix between fluids.

    Furthermore, the plates of the heat exchanger prevent mixing of the air flowing over the

    fins. Therefore, air at one end of the heat exchanger will not necessarily be the same

    temperature as the air at the other end. For a cross flow heat exchanger with both fluids

    unmixed, the effectiveness can be related to the number of transfer units (NTU) with the

    following expression (Incropera & DeWitt, 1996):

    ( ) ( )( )[ ] ,1exp1exp1 78.022.0

    = NTUCNTU

    C rr (2-15)

    where Cr is the heat capacity ratio:

    .max

    min

    CCCr = (2-16)

    In the saturated portion of the condenser, the heat capacity on the refrigerant side

    approaches infinity and the heat capacity ratio, Cr, goes to zero. When Cr is zero, the

    effectiveness for any heat exchanger configuration is expressed as:

  • 14

    ( ).exp1 NTU= (2-17)

    The NTU is a function of the overall heat transfer coefficient, U, and is defined as

    ,minC

    UANTU = (2-18)

    where A is the heat transfer area upon which the overall heat transfer coefficient, U, is

    based. The overall heat transfer coefficient accounts for the total thermal resistance

    between the two fluids and is expressed as follows.

    ,111

    ,,

    ",

    ,

    ",

    , rrrsrrs

    rfw

    aas

    af

    aaas AhAR

    RA

    RAhUA

    ++++= (2-19)

    where Rf,(a or r) is the fouling factor, Rw is the wall thermal conduction resistance, s(a or r)

    is the surface efficiency defined below in equation 2-27, andh is the convective heat

    transfer coefficient. There are no fins on the refrigerant side of the condensing tubes.

    Therefore, the refrigerant side surface efficiency is 1. Neglecting the wall thermal

    resistance, Rw (this value is usually 3 orders of magnitude lower than the other

    resistances), and the fouling factors, Rf,(a or r), the overall heat transfer coefficient reduces

    to:

  • 15

    .111

    ,

    +=

    rraaas AhAhUA

    (2-20)

    In the sub-cooled region the Dittus-Boelter equation is used to determine the

    refrigerant side heat transfer coefficient (Incropera & DeWitt, 1996). In the super-heated

    region the heat transfer correlation developed by Kays and London (1984) is used.

    Correlation developed by Shah (1979) is then used for the two-phase flow condensing

    heat transfer correlation. The work of McQuiston (McQuiston and Parker, 1994) is used

    to evaluate the air-side convective heat transfer coefficient.

    To determine the overall surface efficiency for a finned tube heat exchanger, it is

    first necessary to determine the efficiency of the fins as if they existed alone. For a plate-

    fin-and-tube heat exchanger with multiple rows of staggered tubes, the plates can be

    evenly divided into hexagonal shaped fins as shown in Figure 2-3. Schmidt (1945)

    analyzed hexagonal fins and determined that they can be treated as circular fins by

    replacing the outer radius of the fin with an equivalent radius. The empirical relation for

    the equivalent radius is given by

    ( ) ,3.027.1 2/1= rRe (2-21)

    where r is the outside tube radius. The coefficients and are defined as

  • 16

    r

    X t2

    = (2-22)

    and

    ,4

    12/12

    2

    += tl

    t

    XXX

    (2-23)

    where Xl is the tube spacing in the direction parallel to the direction of air flow, and Xt is

    the tube spacing normal to the direction of air flow.

    Once the equivalent radius has been determined, the equations for standard

    circular fins can be used. For this study, the length of the fins is much greater than the fin

    thickness. Therefore, the standard extended surface parameter, mes can be expressed as,

    ,2

    2/12/1

    =

    =

    kth

    kAPehm a

    ces (2-24)

    where ha is the air-side heat transfer coefficient, k is the thermal conductivity of the fin

    material, Pe is the fin perimeter, Ac is the fin cross sectional area, and t is the thickness of

    the fin. For circular tubes, a parameter can be defined as:

  • 17

    Figure 2-3: Hexagonal Fin Layout and Tube Array

    Tube Spacing Normal toAir Flow

    Xt

    Transverse Tube Spacing

    Xl

    Air Flow

  • 18

    .ln35.011

    +

    =

    rR

    rR ee (2-25)

    The fin efficiency, f, for a circular fin is a function of mes, Re, and f, and can be

    expressed as

    ( ) .tanh

    ees

    eesf Rm

    Rm= (2-26)

    The total surface efficiency of the fin, s is therefore expressed as:

    ( ),11 fo

    fins A

    A = (2-27)

    where Afin is the total fin surface area, Ao is the total air-side surface area of the tube and

    the fins.

    Condenser Fan

    Natural convection is not sufficient to attain the heat transfer rate required on the

    air-side of the condenser used in a reasonably sized residential air-conditioning system.

    Therefore a fan must be employed to maintain the airflow at a sufficient rate. Although

    much of the electrical power consumed by the total system is due to the compressor, the

  • 19

    condenser fan also requires a significant amount of power. The power required by the

    fan is directly related to the air-side pressure drop across the condenser and to the

    velocity of air across the condenser:

    confan

    confrconaconaconf

    APVW

    ,

    ,,,,

    =

    (2-28)

    43 hh = (2-29)

    where Va,con is the air velocity over the face of the condenser, Pa,con is the air-side

    pressure drop over the condenser, Afr,con is the frontal area of the condenser, and fan,con is

    the condenser fan Isentropic efficiency. The work of Rich (1973) and Zukauskas and

    Ulinskas (1998) are used to evaluate the air-side pressure drop over the finned tubes in air

    cross-flow.

    Expansion Valve

    The expansion valve is used to control the refrigerant flow through the system.

    Under normal operating conditions, the expansion valve opens and closes in order to

    maintain a fixed amount of superheat in the exit of the evaporator. In this study, the

    superheat is set at the typical 10 F. Because the expansion valve can only pass a limited

    volume of refrigerant, it cannot maintain the specified superheat at the evaporator exit if

    the refrigerant is not completely condensed into liquid. If incomplete condensation in the

  • 20

    condenser occurs, the vapor refrigerant backs up behind the expansion valve and the

    condenser pressure increases until the refrigerant is fully condensed. As a result, in some

    cases the expansion valve cannot regulate the refrigerant mass flow rate, and cannot

    maintain a fixed superheat at the evaporator exit. Wright found that this can occur when

    the air-conditioner is run at low ambient temperature. In that case the evaporator

    superheat varies above the desired 10 F.

    Evaporator

    The purpose of the evaporator is to transfer heat from the room air in order to

    lower its temperature and humidity. Because the refrigerant enters the evaporator as a

    liquid-vapor mixture, it is only divided into saturated and superheated sections. No sub-

    cooled section is necessary. The analysis of the thermodynamic parameters of the

    evaporator is nearly identical to that of the condenser. However, the dehumidification

    process involving the evaporator results in some modifications of the analysis. To

    maintain the simplicity of the evaporator heat transfer model, the evaporator coil is

    assumed to be dry in calculating the air-side heat transfer coefficient. However, because

    the air flowing over the evaporator is cooled to a temperature below the wet bulb

    temperature, some of the heat rejected by the air causes water to condense out of the air

    rather than simply lowering the temperature of the air. Therefore, the specific heat must

    be modified to account for this condensation. The total enthalpy change of the air is thus

    the sum of the enthalpy change due to the decrease in temperature (sensible heat), and the

    enthalpy change due to condensation (latent heat).

  • 21

    latsenstot hhh += (2-30)

    If the specific heat for dry air is utilized in the model for the evaporator, the

    resulting exit temperatures will be too low for complete vaporization. Therefore, an

    effective specific heat that takes into account both the latent heat and the sensible heat

    must be utilized. Using an effective specific heat will result in a more accurate

    determination of the evaporator exit temperature without the complications associated

    with using the standard equations for air-water mixtures. Since the evaporator is not the

    focus of this study, this approximation should not affect the condenser optimization

    methodology.

    Dividing (2-30) by the air temperature change gives the following:

    T

    hT

    hT

    h latsenstot

    +

    =

    (2-31)

    The ratio of the sensible heat enthalpy change to the temperature change is by definition,

    the specific heat, cp. Therefore, after substituting cp into (2-31) and rearranging, the

    following expression is obtained:

    T

    hcc latpeffp

    +=, (2-32)

  • 22

    where cp is the specific heat ratio for dry air and cp,eff is the effective specific heat. To

    maintain indoor humidity, the latent heat accounts for approximately 25% of the total

    enthalpy change of the air flowing over an evaporator. The effective specific heat can

    thus be expressed in terms of the specific heat for dry air only,

    .33.175.0

    25.0, p

    tot

    senslatpeffp ch

    hT

    hcc =

    += (2-33)

    Evaporator Fan

    Because the evaporator is not the primary focus of this study, introducing wet

    coils would present unwelcome complications in the overall analysis. In addition to

    affecting the heat transfer, wet coils also have an effect on the air-side pressure drop.

    Although there are correlations available for determining the pressure drop over wet

    coils, they are cumbersome to use and again, the evaporator is not the primary focus of

    this investigation.

    After the air flows over the evaporator, it enters a series of ducts that then return

    the air back inside the living space. The power required by the evaporator fan depends

    on the losses in these ducts and can vary from installation to installation. Therefore, the

    default power requirement specified by the Air-conditioning and Refrigeration Institute

    (ARI, 1989) of 365 Watts per 1000 ft3/minute of air will be used.

  • 23

    Refrigerant Mass Inventory

    The amount of sub-cooling at the condenser exit are controlled by the system

    operating conditions and the quantity of refrigerant mass in the system. The mass of

    refrigerant in the tubes connecting the components is neglected. Since the compressor

    contains only vapor, the mass of refrigerant in the compressor is also neglected.

    Therefore the calculated total mass of refrigerant in the system includes the mass in the

    sub-cooled, saturated, and superheated portions of the condenser, and in the saturated and

    superheated portions of the evaporator.

    The following text outlines the procedure for finding the refrigerant mass in the

    saturated portion of the evaporator. The same procedure is also used to determine the

    mass of refrigerant in the saturated portion of the condenser, however the boundary

    conditions are different.

    The mass of refrigerant can be expressed as

    .v

    =

    L

    cidlAm (2-34)

    where, Aci is the cross sectional area of the refrigerant-side of the tube, and v is the

    specific volume, which at saturated conditions is a function of quality expressed as

    ( ) ( ) .v1vv vl xx += (2-35)

  • 24

    The boundary conditions for the saturated portion of the evaporator are

    ( ) ixlx == 0 (2-36)

    and

    1)( == Llx (2-37)

    where l is integral variable evaporating tube length and L is the total evaporating tube

    length. Using the boundary conditions and assuming the quality varies linearly with tube

    length, the following expression results

    ( ) .1 ii xlLxlx += (2-38)

    Substituting (2-38) into (2-35) yields an expression for the specific volume as a function

    of length,

    ( ) ( ) ( ).vv1vvvv lvilvil Lxlxl

    ++= (2-39)

  • 25

    For a uniform tube cross sectional area, substituting (2-39) into (2-34) yields

    ( ) ( )

    .vv1vvv

    1

    0,

    =

    =

    ++

    =

    Ll

    llv

    ilvil

    cievapsat dl

    Lxlx

    Am (2-40)

    Integrating (2-40) yields the following expression

    ( )( ) ( ) ( ) .vv1vvvln

    vv10v

    ,

    Ll

    llv

    ilvil

    li

    cievapsat L

    xlxx

    LAm=

    =

    ++

    = (2-41)

    Substituting for l, the expression for the final mass in the saturated portion of the

    evaporator is expressed as:

    ( )( ) ( ) .vvvvln

    vv1,

    ,

    +=

    llvi

    v

    lvi

    evapsatcievapsat xx

    LAm (2-42)

    The mass of refrigerant in the superheated portions of the condenser and evaporator are

    expressed simply as:

    shconcivshcon LAm ,, = (2-43)

  • 26

    and

    .,, shevapcivshevap LAm = (2-44)

    Finally, the mass of refrigerant in the sub-cooled section of the condenser is expressed as

    .,, scconcivsccon LAm = (2-45)

    By using the above relations for the air-conditioning system components in a system

    simulation program it is possible to evaluate the performance of an total air-conditioning

    system for varying condenser design.

  • 27

    CHAPTER III.

    THE OPTIMIZATION ALGORITHM

    The figure of merit

    To quantitatively evaluate the performance of an air-conditioning system there

    must be a quantitative figure of merit established. The efficiency of vapor compression

    refrigeration cycles is expressed as the Coefficient of Performances (COP). The COP is a

    ratio of the rate of the cooling capacity to the electrical and mechanical power used to

    drive the system.

    =

    i

    e

    WQ

    COP (3-1)

    The weighted average of the COP over a summer is referred to as the seasonal

    COP (COPseas). Wright (2000) showed that for a air-conditioning system the seasonal

    COP is very close and nearly identical to the COP for ambient temperature of 82 F.

    Using COP@82F instead of the seasonal COP requires fewer calculation therefore

    increases calculation speed and stability. In this research it is assumed that COPseas is

    equal to COP@82F.

  • 28

    Simplex search method

    In selection of an optimization algorithm the fact that the model of the air-

    conditioner is complicated and solved numerically in EES must be considered. The

    Simplex search method presented by Nelder and Mead (1965) has been widely used to

    optimize complicated functions. This method was chosen for this study because it is

    robust and relatively simple to implement and gives fairly good results even though it is

    not yet known whether the Nelder-Mead method can be proved to converge to an

    optimum value in all cases (Lagarias, et. al., 1998). Even though the Simplex search

    method will find a good solution for the design of the condenser, like for other search

    methods it cannot be proven that it is the global optimal design.

    Because the Nelder-Mead algorithm uses only function values, to minimize

    scalar-value function of n real variables it falls into the class of Direct Search Methods

    (Reklaits, et. al., 1983). Each kth iteration (k > 0) of the simplex direct search method

    begins with a simplex, specified by its n + 1 vertices and the associated function values.

    Since the desired solution is the maximum seasonal COP of the air-conditioner, the COP

    is calculated for all the vertices and they are then ordered and labeled x1(k) ,, xn+1(k) ,

    such that

    )COP( )COP( )COP( (k)1(k)2

    (k)1 + nxxx (3-2)

    where x1(k) is the best point or vertex in the simplex while the xn+1(k) is the worst.

  • 29

    To start the search, one base point is chosen. Preferably the base point is within

    the optimization constrains and in the range of the air-conditioner simulation program.

    The other vertices of the starting simplex are then set by adding % to one parameter for

    each vertex so the initial vertex will span the whole space. Here was set to be 30 %.

    In the Nelder-Mead method there are four scalar parameters defined: coefficients

    of reflection (), expansion (), contraction () and shrinkage (). The recommended

    values by Nelder and Mead (1965) are nearly universally used in the standard algorithm

    (Lagarias, et. al., 1998):

    = 1, = 2, = 0.5, and = 0.5 (3-3)

    One iteration of the Nelder-Mead Simplex search algorithm

    1. Order. Order the n +1 vertices to satisfy )COP( )COP( )COP( 121 + nxxx .

    2. Reflect. When =

    =

    n

    in

    1/ixx is the center of the n best points, compute the

    reflection point xr from

    11 )1()( ++ +=+= nnr xxxxxx , (3-4)

    Calculate COP for xr. If COP1 > COPr > COPn accept xr as new point and terminate

    the iteration.

  • 30

    3. Expand. If COPr > COP1 calculate the expansion point xe and COP(xe) where:

    11 )1()()( ++ +=+=+= nnr xxxxxxxxxe , (3-5)

    If COPe > COPr accept xe and terminate the iteration, else accept xr and terminate the

    iteration.

    4. Contract.

    a. Outside. If COPn > COPr > COPn+1 calculate:

    11 )1()()( ++ +=+=+= nnrc xxxxxxxxx , (3-6)

    If COPc > COPr then accept xc and terminate the iteration else perform

    shrinking.

    b. Inside. If COPr < COPn+1 calculate:

    11 )1()( ++ +== nncc xxxxxx , (3-7)

    If COPcc > COPn+1 accept xcc and terminate the iteration else perform

    shrinking.

  • 31

    5. Shrinking. Calculate COP(vi) where vi = x1 + (xi - x1) and i = 2, , n+1. Then

    next simplex has vertices x1, v2, , vn+1

    Nelder and Mead did not discuss any tie-breaking rules, however, in this study

    points with the same value are going to be ordered so that the newest vertex is the best. If

    a parameter of the vertex doesnt fall within constraints the calculated COP is divided by

    a relatively big number. The search comes to a halt when the new vertex is close to the

    average point. This does not necessarily mean that the volume of the simplex is getting

    close to zero, i.e. the vertices are converging to the same point, but rather that the simplex

    is not changing between the latest two iterations. When the search comes to a stop it is

    restarted with the previous best point as a starting point. This is repeated until the COP

    for the best point in the restarted solution is the same as the COP for the base point.

    Software Tools

    Wrights (2000) air-conditioner model used in the current study was programmed in

    EES (Engineering Equation Solver) (Klein and Alvarado 2001), a software tool that has

    built-in thermodynamic and transport property relations. It solves numerically, multiple

    equations for an equal number of unknown. While EES is useful for simulating the air-

    conditioner it is not suitable for performing the optimization Simplex search. However,

    EES does have the ability to communicate with other programs using Dynamic Data

    Exchange (DDE) supported by many other programs.

  • 32

    Figure 3-1: Nelder-Mead simplex in two dimensions and all possible new points.

    xr

    x

    xe

    xc

    xcc

    x2

    x3

    x1

    y1

    y2

  • 33

    Therefore, in the current study, the Simplex search scheme was programmed in Microsoft

    Visual Basic using Microsoft Excel to organize the inputs and the outputs of the search.

    When starting the Simplex search program in Visual Basic, it copys the initial

    simplex from the Excel sheet, opens the EES program pastes into a parametric table, and

    then instructs EES to solve the table. Once solved the COP values are pasted back into

    Excel again and the new vertex is calculated and sent again to EES. The COP value is

    again sent back to Excel. The Simplex search program will send vertex information from

    Excel to EES and the COP back to Excel until the simplex has converged.

  • 34

    CHAPTER IV.

    OPTIMIZATION OF PARAMETERS

    Optimization Parameters

    The optimization parameters can be divided into two groups, geometric design

    and controllable operational parameters. Geometric design parameters are decided when

    the condenser is designed and after it is built they cannot be changed, when on the other

    hand, it is possible to change the controllable operational parameters without much effort

    after the condenser is built. As seen in Figure 2-1 both the height and the depth of the

    condenser are dependent on other parameters. The height is dependent on number of

    circuits, number of tubes per circuit and the tube vertical spacing. The depth is then

    dependent on number of rows and horizontal tube spacing. Many of the geometric design

    parameters are positive integer numbers but the Simplex search method only works for

    continuous parameters. Even though it may not have a practical meaning, all parameters

    are assumed to be continuous to optimize the design with the Simplex method. The

    optimal solution found gives an idea about optimal design of a condenser that is possible

    to build. The optimal integer design is then found by fixing the integer parameters and

    performing a manual search close to the optimal solution.

  • 35

    Wright (2000) showed, by calculating COPseas for various degrees of sub-cool, that

    the COP is not sensitive of varying sub-cool. In practice the sub-cool is set by charging

    the system with refrigerant until a certain value of sub-cool condition is met with 95 F

    air blowing through the coil. Also, Wright showed that 15 F sub-cool at 95 F is

    approximately the optimal sub-cool. To reduce optimization parameters and speed up

    calculations the sub-cool was fixed to 15 F at 95 F in the current study.

    Figure 4-1: Optimization parameters

    Geometric Design Parameters Operational Parameters W [ft] Width of condenser. Va,con [ft/s] Air velocity over condenser.

    Xf [in] Spacing between fins . Tsc [F] Sub-cool exiting condenser.

    Xl [in] Vertical tube spacing.

    Xt [in] Horizontal tube spacing.

    Nc Number of parallel flow circuits.

    Ntpc Number of tubes per parallel flow circuit.

    Z Number of rows

    D [in] Tube diameter

  • 36

    Condenser coils in current air-conditioning systems are dominantly produced with

    5/8 and 1/2 diameter tubes, but 3/8 and 5/16 tubes are also used (AAON, 2001). The

    design was optimized for each of the tube diameters with constraints put on the cost and

    the frontal area of the condenser. Wrights model found that the cost of the condenser

    coil is directly linked to the material cost, which is calculated from the geometric design.

    A fixed frontal area of 7.5 ft2 has been selected for a typical condenser design of a

    30,000 Btu/hr air-conditioning system. A constraint is needed on the aspect ratio, i.e.

    frontal width divided by frontal height:

    3=HWR (4-1)

    The maximum of 3 is a common design for the condenser of a residential air-conditioner

    since they are often designed as a cube unit package where the condenser covers 3 sides.

    Figure 4-2 shows that, for fixed frontal area and varying maximum material cost

    in U.S. Dollars, the smallest tube, diameter 5/16 gives the best results. Smaller tubes

    like 1/4 is not likely to give significantly better results. Also from Figure 4-2 it can be

    seen that the optimum COPseas reaches a maximum where spending more money on a

    bigger condenser will not result in higher efficiency.

  • 37

    3.7

    3.8

    3.9

    4

    4.1

    4.2

    4.3

    4.4

    15 20 25 30 35 40 45 50 55 60 65

    Max Cost (USD)

    CO

    P sea

    sona

    l

    5/16(in)3/8(in)1/2(in)5/8(in)

    Figure 4-2: Seasonal COP as a function of maximum condenser cost for varying

    outer tube diameter and fixed 7.5 ft2 frontal area.

  • 38

    As shown in Figure 4-3, the COP increases with increasing frontal area and the

    best solution would have just one row, one circuit, and one tube per circuit, hence a

    condenser composed of one long fined tube. It can be seen from Figure 4-4 that

    increasing the frontal area for a condenser with maximum cost constraint makes the

    condenser thinner until the condenser will become just one horizontal row. This will

    reduce the air-side pressure drop and also the air that would flow across each tube would

    be at the ambient temperature. That would though make the condenser far to big for most

    residential applications and the size constrains are set to keep the design inside

    practical limits. When the Simplex search was run with no constrains at all then the

    solution was as expected one straight tube. This is because there is pressure drop in the

    tube bends but there is no heat transfer.

    For increasing maximum cost constraints values for a condenser with a fixed

    frontal area the only way to increase the efficiency is to add more rows. Figure 4-5

    shows that more rows are added until the air-side pressure drop becomes so high that

    adding more rows will reduce the seasonal COP. From figure 4-6 it seems that when

    adding more rows, the spacing between the rows becomes slightly smaller. Conversely,

    it can be seen from Figure 4-7, when adding more rows, the spacing between the fins

    becomes larger. This allows the air to pass easier through the condenser which has a

    reducing effect on the air-side pressure drop.

  • 39

    4.18

    4.2

    4.22

    4.24

    4.26

    4.28

    4.3

    4.32

    4.34

    15 20 25 30 35 40 45 50 55

    Max Cost (USD)

    CO

    P sea

    sona

    l

    Area= 8.5Area = 7.5Area = 6.5

    Figure 4-3: Seasonal COP, for an air-conditioner with a 5/16 tube condenser,

    as a function of maximum condenser cost for varying frontal area.

  • 40

    Figure 4-4: Number of horizontal rows with 5/16 tubing and max cost at $20

    and COP versus frontal area.

    0

    1

    2

    3

    4

    5

    6

    7

    6 8 10 12 14

    Fixed Frontal Area [ft2]

    Num

    ber o

    f row

    s

    4.19

    4.2

    4.21

    4.22

    4.23

    4.24

    4.25

    4.26

    4.27

    4.28

    4.29

    CO

    P

    RowsCOP

  • 41

    0

    5

    10

    15

    20

    25

    15 20 25 30 35 40 45 50 55 60 65

    Max Cost (USD)

    Num

    ber o

    f Row

    s

    Figure 4-5: Number of horizontal rows with 5/16 tubing versus condenser cost

    for fixed 7.5 ft2 frontal area.

  • 42

    0.7

    0.8

    0.9

    1

    1.1

    1.2

    1.3

    15 20 25 30 35 40 45 50 55 60 65

    Max Cost (USD)

    Hor

    izon

    tal S

    paci

    ng/D

    iam

    eter

    Figure 4-6: Horizontal tube spacing ratio for 5/16 tubing versus condenser cost

    for fixed 7.5 ft2 frontal area.

  • 43

    8

    9

    10

    11

    12

    13

    14

    0 5 10 15 20 25

    Number of rows

    fins/

    in

    Figure 4-7: Fin spacing versus number of horizontal rows.

  • 44

    Optimal Condenser Design

    As discussed above, the Simplex method is not able to optimize the design using

    integer values for the integer parameters. However the Simplex search method gives a

    solution for the optimal design of a hypothetical fin-plate condenser with decimal values

    that should be close to the optimal integer design. In order to find the optimal integer

    solution, the Simplex search was run with number of rows, number of parallel circuits

    and the number of tubes per circuit fixed to integer values on either side of the optimal

    solution. The Simplex search was then used to find an optimal COP for each of the

    possible design combinations of the three integer parameters. Figure 4-8 shows the

    search for the optimal integer design of a condenser with 7.5 ft2 fixed frontal area and

    5/16 tube and maximum coil cost set to $20.

    In Wrights (2000) study, the vertical and horizontal tube spacing was held fixed

    to 1.25 and 1.08 respectively, which are currently the widely used values in air-

    conditioning condensers. In the current study it was shown that the optimal vertical tube

    spacing is slightly larger but the horizontal optimal spacing is about 1/3 of the

    conventional value. The tighter horizontal spacing makes it possible to fit in more tubes

    with the same air-side pressure drop and the higher vertical spacing gives the air a higher

    flow area through the condenser.

  • 45

    Figure 4-8: Search for the optimal solution for a 5/16 tube condenser with fixed

    frontal area of 7.5 ft2 and maximum material cost of $20.

    Tubes/circuits #rows #circuits Fin/inch Vair Spacingv Spacingh Width Height Cost COP [ft/s] [in] [in] [ft] [in] [USD] 4 5 2 14.23 14.38 2.37 0.46 4.74 18.98 19.98 4.154 5 3 13.29 12.83 1.68 0.41 4.46 20.19 19.97 4.214 6 2 13.34 14.44 2.36 0.37 4.73 18.92 19.99 4.174 6 3 13.17 13.16 1.68 0.29 4.46 20.17 19.99 4.205 5 2 15.14 13.63 1.90 0.39 4.74 18.98 20.00 4.205 5 3 11.38 13.13 1.44 0.41 4.16 21.65 19.98 4.215 6 2 12.11 14.06 1.89 0.36 4.72 18.90 19.99 4.215 6 3 12.86 13.91 1.67 0.30 3.59 25.04 19.97 4.22

  • 46

    CHAPTER V.

    CONCLUSIONS AND RECOMMENDATIONS

    Conclusions

    The objective of the current work was to study and optimize the geometric design

    and operating parameters for the finned-tube condenser of a 30,000 BTU/hr vapor

    compression residential air-conditioning system using R-410a as a working fluid with

    coil cost, aspect ratio and frontal area constraints. An optimization search technique was

    implemented for the air-conditioner model. Also software was developed to optimize the

    condenser design.

    Consistent with Wrights study (2000), the condenser with the smallest tubing,

    5/16 diameter, gives the best air-conditioner efficiency at any cost and frontal area.

    Also consistent with Wrights study is that larger frontal area results in higher efficiency

    until the design becomes one straight finned tube. On the other hand, to keep

    computational time practical Wright used fixed spacing between the tubes. With the

    Simplex search method the spacing was a design variable, and the best horizontal tube

    spacing design was shown to be approximately three times smaller than the conventional

    value with the vertical tube spacing 50-100% farther apart than conventional designs.

    The result is that for a fixed frontal area of 7.5 ft2 the optimal number of horizontal rows

  • 47

    with no cost constraint is around 20. Adding a cost constraints of $20 the optimal design

    is a 5/16 condenser with 5 tubes per circuits, 3 parallel circuits 12.9 fins per inch, 6

    horizontal rows and with the coil 3.6 ft wide and 25 high. The horizontal and vertical

    spacing between the tubes should be 0.3 and 1.7 respectively. The COP for this design

    was calculated to be 4.2.

    In the previous study (Wright, 2000), the best design found for a finned-tube

    condenser using R-410a as a working fluid was also a condenser with 5/16 tubing but

    having 3 rows of tubes 12 fins per inch and 5 tubes per circuit. Comparing the result

    COP from Wrights study with the COP from the current study, using the Simplex Search

    method has given a better design than both of those found for a fixed frontal area

    problem. With a fixed cost of $26 Wright found a design with the COP equal to 4.23

    compared to the 4.22 COP value found in the current study with the cost constraint set to

    $20. Therefore the Simplex search method found a design that gives the same COP for

    23% less condenser cost. For comparison with an air-conditioner using R-22 as a

    working fluid (Saddler, 2000) studies the design in similar fashion as Wright. The best

    design found for a condenser using R-22 had a COP of 4.18, 6 tubes per circuit and 12

    fins per inch for a condenser with 5/16 tubes. As did Wright, Sadler fixed the tube

    spacing as well. Therefore the COP for an air-conditioning system is similar for a system

    using R-410a as one using R-22. Since R-410a is environmentally friendlier than R-22 it

    is a very good replacement candidate

  • 48

    More specifically the conclusions drawn from this study are following:

    The best tube diameter for the condenser of an air-conditioning system using R-

    410a as a working fluid is 5/16, the smallest studied.

    Even though it is not yet possible to prove that the Simplex search will give the

    best global design available, it did find a better design than that found in the

    previous manual search study and the software can be used by designers to find an

    optimal design of an air-conditioner condenser.

    For higher cost constraints, a condenser with fixed frontal area will have

    increasing number of rows, until the number of rows reaches a point when the

    airflow resistance becomes dominant (for 5/16 it is around 20). The higher heat

    transfer created by additional rows beyond that point has less effect on the COP

    than the increasing air-side pressure drop.

  • 49

    General Design Guidelines

    1. A single row condenser has the highest efficiency for fixed cost and

    unconstrained frontal area.

    2. To minimize the pressure drop due to tube bends it is desirable to have the

    aspect ratio as high as possible to minimize the number of tube bends.

    3. For all the tube diameters and frontal area studied, coil cost higher than $30

    will not significantly increase the condenser performance.

    4. The smallest tube studied, 5/16, gives the best performance.

    5. Airflow velocity should be approximately to 13 ft/s.

    6. Horizontal tube spacing for 5/16 tubes should be approximately 0.3 and

    vertical spacing approximately 1.7.

    Recommendations

    As previously described, the goal of this study was to find and implement an

    optimization technique to the previously existing finned-tube air-conditioning system

    model. The fins used in this study are flat plate fins, but in the industry enhanced surface

    fins have become common. Therefore, for future studies, enhanced surface fins are a

    recommended addition to the air-conditioning condenser simulation program. Though

    the correlation used for calculating the fin efficiency is stated by Schmidt (1945) to be

  • 50

    accurate for non-symmetric fins, it should be validated for the highly non-symmetric

    optimal design in the current study.

    The circuiting of the condenser coil has a major effect on the air-conditioning

    system total performance. In future studies there is an opportunity to enhance the air-

    conditioner simulation program and allowing more design options for the circuiting such

    as varying the number of tubes per parallel circuit through the condenser.

    Due to limitations in air-side pressure drop and heat transfer correlations,

    condensers with smaller tube diameter than 5/16 have not been studied. Since the

    optimum in this study occurs for a condenser with 5/16 tubing it could be that a smaller

    diameter would give higher COP. This could depend on the on the available smaller

    diameter tubing wall thickness. It is therefore recommended that condensers with smaller

    tubes be included in future studies, with valid pressure drop and heat transfer

    correlations.

    This study uses a system component models developed from experimental

    correlations to simulate the air-conditioning system performance. No experiments have

    been run to verify the system model. In future studies it is recommended that the air-

    conditioner system model be compared to experimental system performance values.

  • 51

    REFERENCES

    AAON, AAON Heating and Air-Conditioning Products web site, http://www.aaon.com/, 2001

    EPA, United States Environmental Protection Agency: Ozone Depletion Home Page, http://www.epa.gov/ozone/, 2001.

    Incropera, F. P. and DeWitt, D. P., Fundamentals of Heat and Mass Transfer, 4th Edition, John Wiley & Sons, New York, p. 445, 1996.

    Kays, W. M. and London, A. L., Compact Heat Exchangers, 3rd Edition, McGraw-Hill, New York, 1984.

    Klein, S. A. and Reindl, D. T., The Relationship of Optimum Heat Exchanger Allocation and Minimum Entropy Generation for Refrigeration Cycles, Proceedings of the ASME Advanced Energy Systems Division, vol. 37, pp. 87-94, 1997.

    Lagarias, J. C., Reeds, J. A., Wright, M. H. and Wright, P. E., Convergence properties of the Nelder-Mead Simplex method in low dimensions, SIAM J. Optim., Vol. 9, No1, pp. 112-147, 1998.

    McQuiston, F. C. and Parker, J. P., Heating Ventilating and Air-Conditioning-Analysis and Design, John Wiley & Sons, New York, 1994.

    Nelder, J. A. and Mead, R., A Simplex Method for Function Minimization, Computer J., 7 308-313 (1965)

    Reklaitis, G. V., Ravindran, A., Ragsdell, K. M., Engineering Optimization, Methods and Applications, John Wiley and Sons, 1983.

    Rich, D. G., The Effect of Fin Spacing on the Heat Transfer and Friction Performance of Multi-Row, Smooth Plate Fin-and-Tube Heat Exchangers, ASHRAE Transactions, vol. 79, pt. 2, pp. 137-145, 1973.

    Schmidt, T. E., La Production Calorifique des Surfaces Munies dailettes, Annexe Du bulletin De LInstitut International Du Froid, Annexe G-5, 1945.

    Shah, M. M., A General Correlation For Heat Transfer During Film Condensation Inside Pipes, Heat and Mass Transfer, vol. 22, pp. 547-556, 1979.

    Threlkeld, J. R., Thermal Environmental Engineering, 2nd Edition, Prentice Hall International, New York, pp.55, 1970.

    Wenzel, T. P., Koomey, J. G., Rosenquist, J. G., Sanchez, M., and Hanford, J. W., Energy data sourcebook for the U.S. residential sector, Lawrence Berkeley National Laboratory, 1997. LBL-40297.

  • 52

    Wright, M. F., Plate-Fin-and-Tube Condenser performance and Design for Refrigerant R-410a Air-Conditioner, M.S. Thesis Georgia Institute of Technology, May 2000

    Zukauskas, A. and Ulinskas, R., Banks of Plain and Finned Tubes, Heat Exchanger Design Handbook, G. F. Hewitt Edition, Begell House, Inc., New York, pp. 2.24-1 2.24-17, 1998.

    Research ObjectivesAir Conditioning System and Component ModelingCompressorCondenserCondenser FanExpansion ValveEvaporatorEvaporator FanRefrigerant Mass Inventory

    The figure of meritSimplex search methodOne iteration of the Nelder-Mead Simplex search algorithmSoftware ToolsOptimization ParametersOptimal Condenser DesignConclusionsGeneral Design GuidelinesRecommendations