Upload
llpabilona
View
216
Download
0
Tags:
Embed Size (px)
Citation preview
OPTIMIZATION OF PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR REFRIGERANT R-410A AIR-CONDITIONER
A Thesis Presented to
The Academic Faculty
By
Kristinn A. Aspelund
In Partial Fulfillment of the Requirements for the Degree
Master of Science in Mechanical Engineering
Georgia Institute of Technology December 2001
ii
OPTIMIZATION OF PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR REFRIGERANT R-410A AIR-CONDITIONER
Approved:
________________________________ Samuel V. Shelton ________________________________ Sheldon M. Jeter
________________________________ William J. Wepfer
Date Approved____________________
iii
TABLE OF CONTENTS
TABLE OF CONTENTS III
LIST OF FIGURES V
NOMENCLATURE VI
SUMMARY XII
CHAPTER I. INTRODUCTION 1
RESEARCH OBJECTIVES 3
CHAPTER II. THE AIR-CONDITIONER MODEL 4
AIR CONDITIONING SYSTEM AND COMPONENT MODELING 4 Compressor 5 Condenser 9 Condenser Fan 18 Expansion Valve 19 Evaporator 20 Evaporator Fan 22 Refrigerant Mass Inventory 23
CHAPTER III. THE OPTIMIZATION ALGORITHM 27
THE FIGURE OF MERIT 27 SIMPLEX SEARCH METHOD 28 ONE ITERATION OF THE NELDER-MEAD SIMPLEX SEARCH ALGORITHM 29 SOFTWARE TOOLS 31
CHAPTER IV. OPTIMIZATION OF PARAMETERS 34
iv
OPTIMIZATION PARAMETERS 34 OPTIMAL CONDENSER DESIGN 44
CHAPTER V. CONCLUSIONS AND RECOMMENDATIONS 46
CONCLUSIONS 46 GENERAL DESIGN GUIDELINES 49 RECOMMENDATIONS 49
REFERENCES 51
v
LIST OF FIGURES
Figure 2-1: The Actual Vapor-Compression Refrigeration Cycle 6
Figure 2-2: Typical Cross Flow Heat Exchanger with 5 tubes per circuit, 3 circuits and 6 rows. 12
Figure 2-3: Hexagonal Fin Layout and Tube Array 17
Figure 3-1: Nelder-Mead simplex and all possible new points. 32
Figure 4-1: Optimization parameters 35
Figure 4-2: Seasonal COP as a function of maximum condenser cost for varying outer tube diameter and fixed 7.5 ft2 frontal area. 37
Figure 4-3: Seasonal COP, for an air-conditioner with a 5/16 tube condenser, as a function of maximum condenser cost for varying frontal area. 39
Figure 4-4: Number of horizontal rows with 5/16 tubing and max cost at $20 and COP versus frontal area. 40
Figure 4-5: Number of rows with 5/16 tubing versus condenser cost for fixed 7.5 ft2 frontal area. 41
Figure 4-6: Horizontal tube spacing ratio for 5/16 tubing versus condenser cost for fixed 7.5 ft2 frontal area. 42
Figure 4-7: Fin spacing versus number of rows. 43
Figure 4-8: Search for the optimal solution for a 5/16 tube condenser with fixed frontal area of 7.5 ft2 and maximum material cost of $20. 45
vi
NOMENCLATURE
Ac = Minimum free-flow cross sectional area.
Aci = Cross sectional area of the refrigerant-side of the tube.
Afin = Total fin surface area.
Afr,con = Frontal area of condenser.
Ao = Total air-side heat transfer area including the fin and tube areas.
C = Heat capacity.
Cmax = Maximum heat capacity between that of the air and the refrigerant.
Cmin = Minimum heat capacity between that of the air and the refrigerant.
COP = Coefficient of Performance
COPseas = Seasonal Coefficient of Performance
COP@82F = Coefficient of Performance for an air-conditioner running in 82 F ambient temperature.
cp = Specific heat at constant pressure.
cp,eff = Effective specific heat at constant pressure.
Cr = Ratio of the minimum heat capacity to the maximum heat capacity
H = Condenser height.
h1 = Specific enthalpy of refrigerant entering the compressor.
h2 = Actual specific enthalpy of refrigerant exiting the compressor.
h2a = Specific enthalpy of refrigerant exiting the superheated portion of the compressor.
vii
h2b = Specific enthalpy of refrigerant entering the sub-cooled portion of the compressor.
h2s = Ideal specific enthalpy of refrigerant exiting the compressor.
h3 = Specific enthalpy of refrigerant entering the expansion valve.
h4 = Specific enthalpy of refrigerant exiting the expansion valve.
ah = Air-side heat transfer coefficient.
rh = Refrigerant-side heat transfer coefficient.
k = Thermal conductivity.
k = Number of iterations.
L = Length.
l = Integral variable evaporating tube length.
Lcon,sc = Tube length of the sub-cooled portion of the condenser tubes.
Lcon,sh = Tube length of the superheated portion of the condenser tubes.
Levap,sh = Tube length of the superheated portion of the evaporator tubes.
Lsat = Tube length of the saturated portion of the heat exchanger tubes.
Ltot = Total tube length of the heat exchanger tubes.
m = Refrigerant mass flow rate through the compressor.
satam , = Mass of flow rate of air flowing over the saturated portion of the condenser.
totam , = total mass flow rate of air flowing over the condenser.
mcon,sc = Mass of refrigerant in the sub-cooled portion of the condenser.
mcon,sh = Mass of refrigerant in the superheated portion of the condenser.
viii
mes = Extended surface geometric parameter.
mevap,sh = Mass of refrigerant in the superheated portion of the evaporator.
n = Number of parameters
Nc = Number of parallel flow circuits.
Ntpc = Number of tubes per circuit
NTU = Number of transfer units.
PD = Piston Displacement.
Pe = Perimeter.
Prat = Ratio of condenser saturation pressure to the evapuratior saturation pressure
Q = Rate of total heat transferred between the refrigerant and the air.
qcon,sat = Amount of heat per unit mass transferred between the air and the refrigerant in the saturated portion of the condenser.
qcon,sc = Amount of heat per unit mass transferred between the air and the refrigerant in the sub-cooled portion of the condenser.
qcon,sh = Amount of heat per unit mass transferred between the air and the refrigerant in the superheated portion of the condenser.
maxQ = Maximum possible amount of heat transferred between the refrigerant and the air.
r = Outer radius of tube.
R = Aspect ratio.
Rcv,pd = Ratio of clearance volume to the piston displacement.
Re = Equivalent radius for a hexagonal fin.
Rf,a = Air-side heat exchanger fouling factor.
ix
Rf,r = Refrigerant-side heat exchanger fouling factor.
Rw = Tube wall thermal resistance.
Tc,i = Temperature of cold fluid entering the heat exchanger.
Th,i = Temperature of hot fluid entering the heat exchanger.
Trat = Ratio of condenser saturation temperature to the evapuratior saturation temperature.
Tsc = Sub-cool exiting condenser.
UA = Overall heat transfer coefficient.
W = Condenser width.
wa,com = Actual compressor work per unit mass of refrigerant.
confW , = Condenser fan power.
ws,com = Isentropic compressor work per unit mass of refrigerant.
v = Specific volume.
v1 = Refrigerant specific volume entering the compressor.
v2 = Refrigerant specific volume exiting the compressor.
Va,con = Velocity of the air flowing over the condenser.
vl = Specific volume of the fluid in the liquid phase.
vv = Specific volume of the fluid in the vapor phase.
x = Vapor quality.
xi = Vapor quality at the inlet of the heat exchanger.
Xf = Fin spacing
Xl = Transverse tube spacing.
Xt = Tube spacing normal to air flow.
x
Z = Number of rows.
= Coefficient of the empirical relation for determining the equivalent circular radius for hexagonal fins.
= Expansion.
hlat = Change in the latent enthalpy.
hsens = Change in the sensible enthalpy.
htot = Change in the total enthalpy.
Pa,con = Pressure drop on the air-side of the condenser.
= Fin effectiveness.
= Contraction.
= Fin parameter that is a function of the equivalent circular radius of a hexagonal fin
c = Compressor thermal efficiency.
f = Fin efficiency.
fan,con = Condenser fan efficiency.
s = Surface efficiency.
s,a = Air-side surface efficiency.
s,r = Refrigerant-side surface efficiency.
v = Compressor volumetric efficiency.
= reflection.
v = Density of the fluid in the vapor phase.
= Shrinkage.
xi
= Coefficient of the empirical relation for determining the equivalent circular radius for hexagonal fins.
xii
SUMMARY
Residential air-conditioning equipment currently uses HCFC refrigerant R-22.
Production of the refrigerant will be banned in 2010 except to service existing equipment.
The refrigerant R-410a is a strong candidate to replace R-22. While there is limited
information available on R-410a condenser coil design, a model of an air-conditioning
system with a focus on the finned-tube condenser design details using R-401a as the
working fluid has previously been developed by Wright (2000). The model evaluates the
performance for a specific and detailed condenser design, e.g. frontal area, tube diameter,
air velocity, etc.
An optimization algorithm for the fin-tube condenser design is needed. Due to
computational speed limitations an exhaustive search for the optimal design is not
practical. This research developed design search techniques to find the optimal
condenser design and controllable operational parameters with various constrains for a
given figure of merit. The Simplex Search Method (Nelder et. al., 1965) was
implemented to search and optimize the eight primary condenser design parameters. This
study found an optimum condenser design for various frontal area and cost constrains.
The software developed is appropriate for engineering design use in the air-conditioning
industry.
1
CHAPTER I.
INTRODUCTION
In the last decade public awareness on the destruction of the stratospheric ozone
layer grew and the most harmful materials were banned. Under the terms of the Montreal
Protocol, the United States agreed to meet certain obligations that have brought
challenges to the Heating Ventilation Air Conditioning and Refrigeration (HVAC&R)
industry. Chlorofluorocarbons (CFCs) were used to a large extent as refrigerants but
have high ozone-depletion potential (ODP) and they were completely phased out in the
USA in 1995. Though not harmless environmentally friendlier and inexpensive
hydrochlorofluorocarbons (HCFCs), such as HCFC-22 (R-22), are exclusively used as a
refrigerants in residential heat pumps and air-condition systems. However in the USA
the Environmental Protection Agency (EPA) has published regulations prohibiting the
production of R-22 after 2010 except for servicing equipment produced prior to 2010.
After 2020 the production of R-22 will be completely banned (EPA, 2001).
Due to zero ODP and many favorable performance characteristics, e.g., good
cycle efficiency, non-flammability and high working pressure, R-410a is a strong
candidate as a replacement for R-22. There is however limited information about
condenser coil design for air-conditioners using R-410a as a working fluid.
2
Due to its global warming impact environmental regulations have also focused on
the emission of CO2. Many countries have agreed to reduce their CO2 production. This
must be accomplished by reducing energy usage through higher efficiency energy
systems. In a warm climate, residential air-conditioners are responsible for a major
portion of a households total energy usage and since they are only run when the outside
temperatures are high, a peak electrical demand occurs only on hot days. Utilities must
invest in an electric power generation and distribution infrastructure to meet the air-
conditioner peak demand (Wenzel et. al 1997). This, along with public awareness, has
created pressure for the efficiency of air-conditioning equipment to improve.
Wright (2000) developed a detailed model for an air-conditioning system using R-
410a as a working fluid. The model has detailed simulation of the components of the air-
conditioner system for various designs, including the compressor, the condenser, the
evaporator and the expansion valve. The condenser is the focus of the model
incorporating the best available simulations for the air-side and refrigerant-side pressure
drops and heat transfer coefficients. While the effects of varying some design parameters
were studied an exhaustive design optimization search would have taken months to
execute.
3
Research Objectives
The primary objective of the current work is to study and optimize the geometric
design and operating parameters for a finned-tube condenser of a vapor compression
residential air-conditioning system using R-410a as a working fluid. More specifically
to:
Find and implement a design optimization search technique for the air-
conditioner condenser design.
Apply the optimization technique through software development to optimize
controllable operational and geometric design parameters.
Develop design guidelines for a condenser coil design
Develop a software tool for condenser designers to design coils for optimized
air-conditioner performance.
4
CHAPTER II.
THE AIR-CONDITIONER MODEL
The air-conditioner model used in the current study was developed by Wright
(Wright, 2000). The following development of the model is based on Wrights (2000)
thesis entitled Plate-Fin-and-Tube Condenser Performance and Design for Refrigerant
R-410A Air-Conditioner. This development is detailed here in this study for
completeness.
Air Conditioning System and Component Modeling
Heating, Ventilating, and Air-Conditioning (HVAC) systems that provide a
cooling effect depend on a refrigeration cycle. Both the control and performance of
HVAC systems are significantly affected by the performance of the refrigeration cycle.
Therefore a basic understanding of the refrigeration cycle is needed in the design and
optimization of HVAC systems. Of the three basic refrigeration cycles (vapor
compression, absorption, and thermo-electric), the cycle typically used in the HVAC
industry is the vapor compression cycle. Vapor compression refrigeration has many
complex variations, but only the basic compression cycle will be discussed here.
5
The vapor compression refrigeration cycle modeled for this study is shown in
Figure 2-1. As the figure shows, low pressure, superheated refrigerant vapor from the
evaporator enters the compressor (State 1) and leaves as high pressure, superheated vapor
(State 2). This vapor enters the condenser where heat is rejected to outdoor air that is
forced over the condenser coils. The refrigerant vapor is cooled to the saturation
temperature (State 2b), and then cooled to below the saturation point until sub-cooled
liquid is present (State 3). The high-pressure liquid then flows through the expansion
valve into the evaporator (State 4). The refrigerant then absorbs heat from warm indoor
air that is blown over the evaporator coils. The refrigerant is completely evaporated
(State 4a) and super heated above the saturation temperature before entering the
compressor (State 1). The indoor air is cooled and dehumidified as it flows over the
evaporator and returned to the living space.
Compressor
The purpose of the compressor is to increase the working pressure of the
refrigerant. The compressor is the major energy-consuming component of the
refrigeration system, and its performance and reliability are significant to the overall
performance of the HVAC system. In general there are two categories of compressors:
dynamic compressors and displacement compressors. Dynamic compressors convert
angular momentum into a pressure rise and transfer this pressure rise to the vapor
(McQuiston and Parker, 1994).
6
Figure 2-1: The Actual Vapor-Compression Refrigeration Cycle
Saturated Sub-cooled Superheated 2b 2a3
Expansion Valve
Saturated Superheated
4 4a
Compressor
Condenser
Evaporator
1
2
2b3
4
2a
2
4a
1
S
T
7
Positive displacement compressors increase the pressure of the vapor by reducing the
volume in a closed space. For this study, scroll type positive displacement compressors,
which dominate the residential air-conditioning industry, are considered.
The amount of specific work (work per unit mass of refrigerant) done by an ideal
compressor can be expressed with the following:
( )12, hhw scoms = (2-1)
where h1 is the refrigerant enthalpy entering compressor and h2s refrigerant enthalpy for
isentropic compressor. For a non-ideal compressor, the actual amount of work done
depends on the efficiency,
( )12,, hhwwc
comscoma ==
(2-2)
where c is the compressor isentropic efficiency. The subscripts hx refer to the state point
x on Figure 2-1. For a scroll type compressor, Klein and Reindl (1997) have determined
that the thermal efficiency is related to the pressure ratio and a temperature ratio by the
following relationship:
ratratratratratratc TPTTPP 061.331.503.111281.0814.325.6022 ++= (2-3)
8
where Prat is the pressure ratio and Trat is the temperature ratio, which are defined by
the following relationships:
evapsat
condsatrat P
PP
,
,= (2-4)
evapsat
condsatrat T
TT
,
,= (2-5)
The coefficients in this correlation are based on saturated temperatures and not on the
actual temperatures at the inlet and outlet of the compressor.
The volumetric efficiency is another important consideration in selecting and
modeling compressors. The volumetric efficiency is the ratio of the mass of vapor that is
compressed to the mass of vapor that could be compressed if the intake vapor volume
were equal to the compressor piston displacement. The volumetric efficiency is
expressed as:
= 1
vv1
2
1,v pdcvR (2-6)
where v is the compressor volumetric efficiency, Rcv,pd is the ratio of clearance volume
to the piston displacement, v1 is the specific volume entering the compressor and v2 the
specific volume at the compressor exit. The volumetric efficiency is used to determine
9
the mass flow rate of the refrigerant through the compressor,
m , for a given compressor
size by the following expression,
2v
PDm v= (2-7)
where PD is the Piston Displacement (Threlkeld, 1970).
Condenser
The condenser is a heat exchanger that rejects heat from the refrigerant to the
outside air. Although there are many configurations of heat exchangers, finned-tube heat
exchangers are the type most commonly used for residential air conditioning applications.
Refrigerant flows through the tubes, and a fan forces air between the fins and over the
tubes. The heat exchangers used in this study are of the cross-flow, plate-fin-and-tube
type. A schematic of this heat exchanger is shown in Figure 2-2. The tubing of the
condenser is one of the decisions that designer has to make. On Figure 2-2 tubes having
flow in the same direction are shown to have the same color. The flow can flow through
many parallel through many tubes simultaneously in a parallel circuit. The tubes are then
connected at the ends by bends. It is assumed that since the bends have no fins the heat
transfer is zero.
When the refrigerant exits the compressor, it enters the condenser as a
superheated vapor and exits as a sub-cooled liquid. The condenser can be separated into
10
three sections: superheated, saturated, and sub-cooled. The amount of heat per unit mass
of refrigerant rejected from each section can be expressed as the difference between the
refrigerant enthalpy at the inlet and at the outlet of each section:
,22, ashcon hhq = (2-8)
,22, basatcon hhq = (2-9)
and
.32, hhq bsccon = (2-10)
The total heat rejected from the hot fluid, which in this case is the refrigerant, to the cold
fluid, which is the air, is dependent on the heat exchanger effectiveness and the heat
capacity of each fluid:
( )icih TTCQ ,,min = (2-11)
where is the heat exchanger effectiveness; Cmin is the smaller of the heat capacities of
the hot and cold fluids, Ch and Cc respectively; Th,i is the inlet temperature of the hot
11
fluid; and Tc,i is the inlet temperature of the cold fluid. The heat capacity C, is expressed
as:
pcmC = (2-12)
where
m is the mass flow rate of fluid and cp is the specific heat of the fluid. The heat
capacity, C, is the extensive equivalent to the specific heat, and it determines the amount
of heat a substance absorbs or rejects for a given temperature change.
The amount of air flowing over each section of the condenser is proportional to
the tube length, L, corresponding to each specific section. For example, the mass of air
flowing over the saturated section of the condenser can be found by the following
relation:
tot
sat
tota
sata
LL
mm
=
,
,
(2-13)
The heat exchanger effectiveness discussed earlier in this chapter is the ratio of the actual
amount of heat transferred to the maximum possible amount of heat transferred,
maxQQ
= (2-14)
12
Figure 2-2: Typical Cross Flow Heat Exchanger with 5 tubes per circuit, 3
circuits and 6 rows.
w
d
h
Xl
Xt
Air flow
13
The heat exchanger effectiveness is dependent on the temperature distribution within
each fluid and on the paths of the fluids as the heat transfer takes place, i.e. parallel-flow,
counter-flow, or cross-flow. In most typical condensers and evaporators, the refrigerant
mass flow is separated into a number of discrete tubes and does not mix between fluids.
Furthermore, the plates of the heat exchanger prevent mixing of the air flowing over the
fins. Therefore, air at one end of the heat exchanger will not necessarily be the same
temperature as the air at the other end. For a cross flow heat exchanger with both fluids
unmixed, the effectiveness can be related to the number of transfer units (NTU) with the
following expression (Incropera & DeWitt, 1996):
( ) ( )( )[ ] ,1exp1exp1 78.022.0
= NTUCNTU
C rr (2-15)
where Cr is the heat capacity ratio:
.max
min
CCCr = (2-16)
In the saturated portion of the condenser, the heat capacity on the refrigerant side
approaches infinity and the heat capacity ratio, Cr, goes to zero. When Cr is zero, the
effectiveness for any heat exchanger configuration is expressed as:
14
( ).exp1 NTU= (2-17)
The NTU is a function of the overall heat transfer coefficient, U, and is defined as
,minC
UANTU = (2-18)
where A is the heat transfer area upon which the overall heat transfer coefficient, U, is
based. The overall heat transfer coefficient accounts for the total thermal resistance
between the two fluids and is expressed as follows.
,111
,,
",
,
",
, rrrsrrs
rfw
aas
af
aaas AhAR
RA
RAhUA
++++= (2-19)
where Rf,(a or r) is the fouling factor, Rw is the wall thermal conduction resistance, s(a or r)
is the surface efficiency defined below in equation 2-27, andh is the convective heat
transfer coefficient. There are no fins on the refrigerant side of the condensing tubes.
Therefore, the refrigerant side surface efficiency is 1. Neglecting the wall thermal
resistance, Rw (this value is usually 3 orders of magnitude lower than the other
resistances), and the fouling factors, Rf,(a or r), the overall heat transfer coefficient reduces
to:
15
.111
,
+=
rraaas AhAhUA
(2-20)
In the sub-cooled region the Dittus-Boelter equation is used to determine the
refrigerant side heat transfer coefficient (Incropera & DeWitt, 1996). In the super-heated
region the heat transfer correlation developed by Kays and London (1984) is used.
Correlation developed by Shah (1979) is then used for the two-phase flow condensing
heat transfer correlation. The work of McQuiston (McQuiston and Parker, 1994) is used
to evaluate the air-side convective heat transfer coefficient.
To determine the overall surface efficiency for a finned tube heat exchanger, it is
first necessary to determine the efficiency of the fins as if they existed alone. For a plate-
fin-and-tube heat exchanger with multiple rows of staggered tubes, the plates can be
evenly divided into hexagonal shaped fins as shown in Figure 2-3. Schmidt (1945)
analyzed hexagonal fins and determined that they can be treated as circular fins by
replacing the outer radius of the fin with an equivalent radius. The empirical relation for
the equivalent radius is given by
( ) ,3.027.1 2/1= rRe (2-21)
where r is the outside tube radius. The coefficients and are defined as
16
r
X t2
= (2-22)
and
,4
12/12
2
+= tl
t
XXX
(2-23)
where Xl is the tube spacing in the direction parallel to the direction of air flow, and Xt is
the tube spacing normal to the direction of air flow.
Once the equivalent radius has been determined, the equations for standard
circular fins can be used. For this study, the length of the fins is much greater than the fin
thickness. Therefore, the standard extended surface parameter, mes can be expressed as,
,2
2/12/1
=
=
kth
kAPehm a
ces (2-24)
where ha is the air-side heat transfer coefficient, k is the thermal conductivity of the fin
material, Pe is the fin perimeter, Ac is the fin cross sectional area, and t is the thickness of
the fin. For circular tubes, a parameter can be defined as:
17
Figure 2-3: Hexagonal Fin Layout and Tube Array
Tube Spacing Normal toAir Flow
Xt
Transverse Tube Spacing
Xl
Air Flow
18
.ln35.011
+
=
rR
rR ee (2-25)
The fin efficiency, f, for a circular fin is a function of mes, Re, and f, and can be
expressed as
( ) .tanh
ees
eesf Rm
Rm= (2-26)
The total surface efficiency of the fin, s is therefore expressed as:
( ),11 fo
fins A
A = (2-27)
where Afin is the total fin surface area, Ao is the total air-side surface area of the tube and
the fins.
Condenser Fan
Natural convection is not sufficient to attain the heat transfer rate required on the
air-side of the condenser used in a reasonably sized residential air-conditioning system.
Therefore a fan must be employed to maintain the airflow at a sufficient rate. Although
much of the electrical power consumed by the total system is due to the compressor, the
19
condenser fan also requires a significant amount of power. The power required by the
fan is directly related to the air-side pressure drop across the condenser and to the
velocity of air across the condenser:
confan
confrconaconaconf
APVW
,
,,,,
=
(2-28)
43 hh = (2-29)
where Va,con is the air velocity over the face of the condenser, Pa,con is the air-side
pressure drop over the condenser, Afr,con is the frontal area of the condenser, and fan,con is
the condenser fan Isentropic efficiency. The work of Rich (1973) and Zukauskas and
Ulinskas (1998) are used to evaluate the air-side pressure drop over the finned tubes in air
cross-flow.
Expansion Valve
The expansion valve is used to control the refrigerant flow through the system.
Under normal operating conditions, the expansion valve opens and closes in order to
maintain a fixed amount of superheat in the exit of the evaporator. In this study, the
superheat is set at the typical 10 F. Because the expansion valve can only pass a limited
volume of refrigerant, it cannot maintain the specified superheat at the evaporator exit if
the refrigerant is not completely condensed into liquid. If incomplete condensation in the
20
condenser occurs, the vapor refrigerant backs up behind the expansion valve and the
condenser pressure increases until the refrigerant is fully condensed. As a result, in some
cases the expansion valve cannot regulate the refrigerant mass flow rate, and cannot
maintain a fixed superheat at the evaporator exit. Wright found that this can occur when
the air-conditioner is run at low ambient temperature. In that case the evaporator
superheat varies above the desired 10 F.
Evaporator
The purpose of the evaporator is to transfer heat from the room air in order to
lower its temperature and humidity. Because the refrigerant enters the evaporator as a
liquid-vapor mixture, it is only divided into saturated and superheated sections. No sub-
cooled section is necessary. The analysis of the thermodynamic parameters of the
evaporator is nearly identical to that of the condenser. However, the dehumidification
process involving the evaporator results in some modifications of the analysis. To
maintain the simplicity of the evaporator heat transfer model, the evaporator coil is
assumed to be dry in calculating the air-side heat transfer coefficient. However, because
the air flowing over the evaporator is cooled to a temperature below the wet bulb
temperature, some of the heat rejected by the air causes water to condense out of the air
rather than simply lowering the temperature of the air. Therefore, the specific heat must
be modified to account for this condensation. The total enthalpy change of the air is thus
the sum of the enthalpy change due to the decrease in temperature (sensible heat), and the
enthalpy change due to condensation (latent heat).
21
latsenstot hhh += (2-30)
If the specific heat for dry air is utilized in the model for the evaporator, the
resulting exit temperatures will be too low for complete vaporization. Therefore, an
effective specific heat that takes into account both the latent heat and the sensible heat
must be utilized. Using an effective specific heat will result in a more accurate
determination of the evaporator exit temperature without the complications associated
with using the standard equations for air-water mixtures. Since the evaporator is not the
focus of this study, this approximation should not affect the condenser optimization
methodology.
Dividing (2-30) by the air temperature change gives the following:
T
hT
hT
h latsenstot
+
=
(2-31)
The ratio of the sensible heat enthalpy change to the temperature change is by definition,
the specific heat, cp. Therefore, after substituting cp into (2-31) and rearranging, the
following expression is obtained:
T
hcc latpeffp
+=, (2-32)
22
where cp is the specific heat ratio for dry air and cp,eff is the effective specific heat. To
maintain indoor humidity, the latent heat accounts for approximately 25% of the total
enthalpy change of the air flowing over an evaporator. The effective specific heat can
thus be expressed in terms of the specific heat for dry air only,
.33.175.0
25.0, p
tot
senslatpeffp ch
hT
hcc =
+= (2-33)
Evaporator Fan
Because the evaporator is not the primary focus of this study, introducing wet
coils would present unwelcome complications in the overall analysis. In addition to
affecting the heat transfer, wet coils also have an effect on the air-side pressure drop.
Although there are correlations available for determining the pressure drop over wet
coils, they are cumbersome to use and again, the evaporator is not the primary focus of
this investigation.
After the air flows over the evaporator, it enters a series of ducts that then return
the air back inside the living space. The power required by the evaporator fan depends
on the losses in these ducts and can vary from installation to installation. Therefore, the
default power requirement specified by the Air-conditioning and Refrigeration Institute
(ARI, 1989) of 365 Watts per 1000 ft3/minute of air will be used.
23
Refrigerant Mass Inventory
The amount of sub-cooling at the condenser exit are controlled by the system
operating conditions and the quantity of refrigerant mass in the system. The mass of
refrigerant in the tubes connecting the components is neglected. Since the compressor
contains only vapor, the mass of refrigerant in the compressor is also neglected.
Therefore the calculated total mass of refrigerant in the system includes the mass in the
sub-cooled, saturated, and superheated portions of the condenser, and in the saturated and
superheated portions of the evaporator.
The following text outlines the procedure for finding the refrigerant mass in the
saturated portion of the evaporator. The same procedure is also used to determine the
mass of refrigerant in the saturated portion of the condenser, however the boundary
conditions are different.
The mass of refrigerant can be expressed as
.v
=
L
cidlAm (2-34)
where, Aci is the cross sectional area of the refrigerant-side of the tube, and v is the
specific volume, which at saturated conditions is a function of quality expressed as
( ) ( ) .v1vv vl xx += (2-35)
24
The boundary conditions for the saturated portion of the evaporator are
( ) ixlx == 0 (2-36)
and
1)( == Llx (2-37)
where l is integral variable evaporating tube length and L is the total evaporating tube
length. Using the boundary conditions and assuming the quality varies linearly with tube
length, the following expression results
( ) .1 ii xlLxlx += (2-38)
Substituting (2-38) into (2-35) yields an expression for the specific volume as a function
of length,
( ) ( ) ( ).vv1vvvv lvilvil Lxlxl
++= (2-39)
25
For a uniform tube cross sectional area, substituting (2-39) into (2-34) yields
( ) ( )
.vv1vvv
1
0,
=
=
++
=
Ll
llv
ilvil
cievapsat dl
Lxlx
Am (2-40)
Integrating (2-40) yields the following expression
( )( ) ( ) ( ) .vv1vvvln
vv10v
,
Ll
llv
ilvil
li
cievapsat L
xlxx
LAm=
=
++
= (2-41)
Substituting for l, the expression for the final mass in the saturated portion of the
evaporator is expressed as:
( )( ) ( ) .vvvvln
vv1,
,
+=
llvi
v
lvi
evapsatcievapsat xx
LAm (2-42)
The mass of refrigerant in the superheated portions of the condenser and evaporator are
expressed simply as:
shconcivshcon LAm ,, = (2-43)
26
and
.,, shevapcivshevap LAm = (2-44)
Finally, the mass of refrigerant in the sub-cooled section of the condenser is expressed as
.,, scconcivsccon LAm = (2-45)
By using the above relations for the air-conditioning system components in a system
simulation program it is possible to evaluate the performance of an total air-conditioning
system for varying condenser design.
27
CHAPTER III.
THE OPTIMIZATION ALGORITHM
The figure of merit
To quantitatively evaluate the performance of an air-conditioning system there
must be a quantitative figure of merit established. The efficiency of vapor compression
refrigeration cycles is expressed as the Coefficient of Performances (COP). The COP is a
ratio of the rate of the cooling capacity to the electrical and mechanical power used to
drive the system.
=
i
e
WQ
COP (3-1)
The weighted average of the COP over a summer is referred to as the seasonal
COP (COPseas). Wright (2000) showed that for a air-conditioning system the seasonal
COP is very close and nearly identical to the COP for ambient temperature of 82 F.
Using COP@82F instead of the seasonal COP requires fewer calculation therefore
increases calculation speed and stability. In this research it is assumed that COPseas is
equal to COP@82F.
28
Simplex search method
In selection of an optimization algorithm the fact that the model of the air-
conditioner is complicated and solved numerically in EES must be considered. The
Simplex search method presented by Nelder and Mead (1965) has been widely used to
optimize complicated functions. This method was chosen for this study because it is
robust and relatively simple to implement and gives fairly good results even though it is
not yet known whether the Nelder-Mead method can be proved to converge to an
optimum value in all cases (Lagarias, et. al., 1998). Even though the Simplex search
method will find a good solution for the design of the condenser, like for other search
methods it cannot be proven that it is the global optimal design.
Because the Nelder-Mead algorithm uses only function values, to minimize
scalar-value function of n real variables it falls into the class of Direct Search Methods
(Reklaits, et. al., 1983). Each kth iteration (k > 0) of the simplex direct search method
begins with a simplex, specified by its n + 1 vertices and the associated function values.
Since the desired solution is the maximum seasonal COP of the air-conditioner, the COP
is calculated for all the vertices and they are then ordered and labeled x1(k) ,, xn+1(k) ,
such that
)COP( )COP( )COP( (k)1(k)2
(k)1 + nxxx (3-2)
where x1(k) is the best point or vertex in the simplex while the xn+1(k) is the worst.
29
To start the search, one base point is chosen. Preferably the base point is within
the optimization constrains and in the range of the air-conditioner simulation program.
The other vertices of the starting simplex are then set by adding % to one parameter for
each vertex so the initial vertex will span the whole space. Here was set to be 30 %.
In the Nelder-Mead method there are four scalar parameters defined: coefficients
of reflection (), expansion (), contraction () and shrinkage (). The recommended
values by Nelder and Mead (1965) are nearly universally used in the standard algorithm
(Lagarias, et. al., 1998):
= 1, = 2, = 0.5, and = 0.5 (3-3)
One iteration of the Nelder-Mead Simplex search algorithm
1. Order. Order the n +1 vertices to satisfy )COP( )COP( )COP( 121 + nxxx .
2. Reflect. When =
=
n
in
1/ixx is the center of the n best points, compute the
reflection point xr from
11 )1()( ++ +=+= nnr xxxxxx , (3-4)
Calculate COP for xr. If COP1 > COPr > COPn accept xr as new point and terminate
the iteration.
30
3. Expand. If COPr > COP1 calculate the expansion point xe and COP(xe) where:
11 )1()()( ++ +=+=+= nnr xxxxxxxxxe , (3-5)
If COPe > COPr accept xe and terminate the iteration, else accept xr and terminate the
iteration.
4. Contract.
a. Outside. If COPn > COPr > COPn+1 calculate:
11 )1()()( ++ +=+=+= nnrc xxxxxxxxx , (3-6)
If COPc > COPr then accept xc and terminate the iteration else perform
shrinking.
b. Inside. If COPr < COPn+1 calculate:
11 )1()( ++ +== nncc xxxxxx , (3-7)
If COPcc > COPn+1 accept xcc and terminate the iteration else perform
shrinking.
31
5. Shrinking. Calculate COP(vi) where vi = x1 + (xi - x1) and i = 2, , n+1. Then
next simplex has vertices x1, v2, , vn+1
Nelder and Mead did not discuss any tie-breaking rules, however, in this study
points with the same value are going to be ordered so that the newest vertex is the best. If
a parameter of the vertex doesnt fall within constraints the calculated COP is divided by
a relatively big number. The search comes to a halt when the new vertex is close to the
average point. This does not necessarily mean that the volume of the simplex is getting
close to zero, i.e. the vertices are converging to the same point, but rather that the simplex
is not changing between the latest two iterations. When the search comes to a stop it is
restarted with the previous best point as a starting point. This is repeated until the COP
for the best point in the restarted solution is the same as the COP for the base point.
Software Tools
Wrights (2000) air-conditioner model used in the current study was programmed in
EES (Engineering Equation Solver) (Klein and Alvarado 2001), a software tool that has
built-in thermodynamic and transport property relations. It solves numerically, multiple
equations for an equal number of unknown. While EES is useful for simulating the air-
conditioner it is not suitable for performing the optimization Simplex search. However,
EES does have the ability to communicate with other programs using Dynamic Data
Exchange (DDE) supported by many other programs.
32
Figure 3-1: Nelder-Mead simplex in two dimensions and all possible new points.
xr
x
xe
xc
xcc
x2
x3
x1
y1
y2
33
Therefore, in the current study, the Simplex search scheme was programmed in Microsoft
Visual Basic using Microsoft Excel to organize the inputs and the outputs of the search.
When starting the Simplex search program in Visual Basic, it copys the initial
simplex from the Excel sheet, opens the EES program pastes into a parametric table, and
then instructs EES to solve the table. Once solved the COP values are pasted back into
Excel again and the new vertex is calculated and sent again to EES. The COP value is
again sent back to Excel. The Simplex search program will send vertex information from
Excel to EES and the COP back to Excel until the simplex has converged.
34
CHAPTER IV.
OPTIMIZATION OF PARAMETERS
Optimization Parameters
The optimization parameters can be divided into two groups, geometric design
and controllable operational parameters. Geometric design parameters are decided when
the condenser is designed and after it is built they cannot be changed, when on the other
hand, it is possible to change the controllable operational parameters without much effort
after the condenser is built. As seen in Figure 2-1 both the height and the depth of the
condenser are dependent on other parameters. The height is dependent on number of
circuits, number of tubes per circuit and the tube vertical spacing. The depth is then
dependent on number of rows and horizontal tube spacing. Many of the geometric design
parameters are positive integer numbers but the Simplex search method only works for
continuous parameters. Even though it may not have a practical meaning, all parameters
are assumed to be continuous to optimize the design with the Simplex method. The
optimal solution found gives an idea about optimal design of a condenser that is possible
to build. The optimal integer design is then found by fixing the integer parameters and
performing a manual search close to the optimal solution.
35
Wright (2000) showed, by calculating COPseas for various degrees of sub-cool, that
the COP is not sensitive of varying sub-cool. In practice the sub-cool is set by charging
the system with refrigerant until a certain value of sub-cool condition is met with 95 F
air blowing through the coil. Also, Wright showed that 15 F sub-cool at 95 F is
approximately the optimal sub-cool. To reduce optimization parameters and speed up
calculations the sub-cool was fixed to 15 F at 95 F in the current study.
Figure 4-1: Optimization parameters
Geometric Design Parameters Operational Parameters W [ft] Width of condenser. Va,con [ft/s] Air velocity over condenser.
Xf [in] Spacing between fins . Tsc [F] Sub-cool exiting condenser.
Xl [in] Vertical tube spacing.
Xt [in] Horizontal tube spacing.
Nc Number of parallel flow circuits.
Ntpc Number of tubes per parallel flow circuit.
Z Number of rows
D [in] Tube diameter
36
Condenser coils in current air-conditioning systems are dominantly produced with
5/8 and 1/2 diameter tubes, but 3/8 and 5/16 tubes are also used (AAON, 2001). The
design was optimized for each of the tube diameters with constraints put on the cost and
the frontal area of the condenser. Wrights model found that the cost of the condenser
coil is directly linked to the material cost, which is calculated from the geometric design.
A fixed frontal area of 7.5 ft2 has been selected for a typical condenser design of a
30,000 Btu/hr air-conditioning system. A constraint is needed on the aspect ratio, i.e.
frontal width divided by frontal height:
3=HWR (4-1)
The maximum of 3 is a common design for the condenser of a residential air-conditioner
since they are often designed as a cube unit package where the condenser covers 3 sides.
Figure 4-2 shows that, for fixed frontal area and varying maximum material cost
in U.S. Dollars, the smallest tube, diameter 5/16 gives the best results. Smaller tubes
like 1/4 is not likely to give significantly better results. Also from Figure 4-2 it can be
seen that the optimum COPseas reaches a maximum where spending more money on a
bigger condenser will not result in higher efficiency.
37
3.7
3.8
3.9
4
4.1
4.2
4.3
4.4
15 20 25 30 35 40 45 50 55 60 65
Max Cost (USD)
CO
P sea
sona
l
5/16(in)3/8(in)1/2(in)5/8(in)
Figure 4-2: Seasonal COP as a function of maximum condenser cost for varying
outer tube diameter and fixed 7.5 ft2 frontal area.
38
As shown in Figure 4-3, the COP increases with increasing frontal area and the
best solution would have just one row, one circuit, and one tube per circuit, hence a
condenser composed of one long fined tube. It can be seen from Figure 4-4 that
increasing the frontal area for a condenser with maximum cost constraint makes the
condenser thinner until the condenser will become just one horizontal row. This will
reduce the air-side pressure drop and also the air that would flow across each tube would
be at the ambient temperature. That would though make the condenser far to big for most
residential applications and the size constrains are set to keep the design inside
practical limits. When the Simplex search was run with no constrains at all then the
solution was as expected one straight tube. This is because there is pressure drop in the
tube bends but there is no heat transfer.
For increasing maximum cost constraints values for a condenser with a fixed
frontal area the only way to increase the efficiency is to add more rows. Figure 4-5
shows that more rows are added until the air-side pressure drop becomes so high that
adding more rows will reduce the seasonal COP. From figure 4-6 it seems that when
adding more rows, the spacing between the rows becomes slightly smaller. Conversely,
it can be seen from Figure 4-7, when adding more rows, the spacing between the fins
becomes larger. This allows the air to pass easier through the condenser which has a
reducing effect on the air-side pressure drop.
39
4.18
4.2
4.22
4.24
4.26
4.28
4.3
4.32
4.34
15 20 25 30 35 40 45 50 55
Max Cost (USD)
CO
P sea
sona
l
Area= 8.5Area = 7.5Area = 6.5
Figure 4-3: Seasonal COP, for an air-conditioner with a 5/16 tube condenser,
as a function of maximum condenser cost for varying frontal area.
40
Figure 4-4: Number of horizontal rows with 5/16 tubing and max cost at $20
and COP versus frontal area.
0
1
2
3
4
5
6
7
6 8 10 12 14
Fixed Frontal Area [ft2]
Num
ber o
f row
s
4.19
4.2
4.21
4.22
4.23
4.24
4.25
4.26
4.27
4.28
4.29
CO
P
RowsCOP
41
0
5
10
15
20
25
15 20 25 30 35 40 45 50 55 60 65
Max Cost (USD)
Num
ber o
f Row
s
Figure 4-5: Number of horizontal rows with 5/16 tubing versus condenser cost
for fixed 7.5 ft2 frontal area.
42
0.7
0.8
0.9
1
1.1
1.2
1.3
15 20 25 30 35 40 45 50 55 60 65
Max Cost (USD)
Hor
izon
tal S
paci
ng/D
iam
eter
Figure 4-6: Horizontal tube spacing ratio for 5/16 tubing versus condenser cost
for fixed 7.5 ft2 frontal area.
43
8
9
10
11
12
13
14
0 5 10 15 20 25
Number of rows
fins/
in
Figure 4-7: Fin spacing versus number of horizontal rows.
44
Optimal Condenser Design
As discussed above, the Simplex method is not able to optimize the design using
integer values for the integer parameters. However the Simplex search method gives a
solution for the optimal design of a hypothetical fin-plate condenser with decimal values
that should be close to the optimal integer design. In order to find the optimal integer
solution, the Simplex search was run with number of rows, number of parallel circuits
and the number of tubes per circuit fixed to integer values on either side of the optimal
solution. The Simplex search was then used to find an optimal COP for each of the
possible design combinations of the three integer parameters. Figure 4-8 shows the
search for the optimal integer design of a condenser with 7.5 ft2 fixed frontal area and
5/16 tube and maximum coil cost set to $20.
In Wrights (2000) study, the vertical and horizontal tube spacing was held fixed
to 1.25 and 1.08 respectively, which are currently the widely used values in air-
conditioning condensers. In the current study it was shown that the optimal vertical tube
spacing is slightly larger but the horizontal optimal spacing is about 1/3 of the
conventional value. The tighter horizontal spacing makes it possible to fit in more tubes
with the same air-side pressure drop and the higher vertical spacing gives the air a higher
flow area through the condenser.
45
Figure 4-8: Search for the optimal solution for a 5/16 tube condenser with fixed
frontal area of 7.5 ft2 and maximum material cost of $20.
Tubes/circuits #rows #circuits Fin/inch Vair Spacingv Spacingh Width Height Cost COP [ft/s] [in] [in] [ft] [in] [USD] 4 5 2 14.23 14.38 2.37 0.46 4.74 18.98 19.98 4.154 5 3 13.29 12.83 1.68 0.41 4.46 20.19 19.97 4.214 6 2 13.34 14.44 2.36 0.37 4.73 18.92 19.99 4.174 6 3 13.17 13.16 1.68 0.29 4.46 20.17 19.99 4.205 5 2 15.14 13.63 1.90 0.39 4.74 18.98 20.00 4.205 5 3 11.38 13.13 1.44 0.41 4.16 21.65 19.98 4.215 6 2 12.11 14.06 1.89 0.36 4.72 18.90 19.99 4.215 6 3 12.86 13.91 1.67 0.30 3.59 25.04 19.97 4.22
46
CHAPTER V.
CONCLUSIONS AND RECOMMENDATIONS
Conclusions
The objective of the current work was to study and optimize the geometric design
and operating parameters for the finned-tube condenser of a 30,000 BTU/hr vapor
compression residential air-conditioning system using R-410a as a working fluid with
coil cost, aspect ratio and frontal area constraints. An optimization search technique was
implemented for the air-conditioner model. Also software was developed to optimize the
condenser design.
Consistent with Wrights study (2000), the condenser with the smallest tubing,
5/16 diameter, gives the best air-conditioner efficiency at any cost and frontal area.
Also consistent with Wrights study is that larger frontal area results in higher efficiency
until the design becomes one straight finned tube. On the other hand, to keep
computational time practical Wright used fixed spacing between the tubes. With the
Simplex search method the spacing was a design variable, and the best horizontal tube
spacing design was shown to be approximately three times smaller than the conventional
value with the vertical tube spacing 50-100% farther apart than conventional designs.
The result is that for a fixed frontal area of 7.5 ft2 the optimal number of horizontal rows
47
with no cost constraint is around 20. Adding a cost constraints of $20 the optimal design
is a 5/16 condenser with 5 tubes per circuits, 3 parallel circuits 12.9 fins per inch, 6
horizontal rows and with the coil 3.6 ft wide and 25 high. The horizontal and vertical
spacing between the tubes should be 0.3 and 1.7 respectively. The COP for this design
was calculated to be 4.2.
In the previous study (Wright, 2000), the best design found for a finned-tube
condenser using R-410a as a working fluid was also a condenser with 5/16 tubing but
having 3 rows of tubes 12 fins per inch and 5 tubes per circuit. Comparing the result
COP from Wrights study with the COP from the current study, using the Simplex Search
method has given a better design than both of those found for a fixed frontal area
problem. With a fixed cost of $26 Wright found a design with the COP equal to 4.23
compared to the 4.22 COP value found in the current study with the cost constraint set to
$20. Therefore the Simplex search method found a design that gives the same COP for
23% less condenser cost. For comparison with an air-conditioner using R-22 as a
working fluid (Saddler, 2000) studies the design in similar fashion as Wright. The best
design found for a condenser using R-22 had a COP of 4.18, 6 tubes per circuit and 12
fins per inch for a condenser with 5/16 tubes. As did Wright, Sadler fixed the tube
spacing as well. Therefore the COP for an air-conditioning system is similar for a system
using R-410a as one using R-22. Since R-410a is environmentally friendlier than R-22 it
is a very good replacement candidate
48
More specifically the conclusions drawn from this study are following:
The best tube diameter for the condenser of an air-conditioning system using R-
410a as a working fluid is 5/16, the smallest studied.
Even though it is not yet possible to prove that the Simplex search will give the
best global design available, it did find a better design than that found in the
previous manual search study and the software can be used by designers to find an
optimal design of an air-conditioner condenser.
For higher cost constraints, a condenser with fixed frontal area will have
increasing number of rows, until the number of rows reaches a point when the
airflow resistance becomes dominant (for 5/16 it is around 20). The higher heat
transfer created by additional rows beyond that point has less effect on the COP
than the increasing air-side pressure drop.
49
General Design Guidelines
1. A single row condenser has the highest efficiency for fixed cost and
unconstrained frontal area.
2. To minimize the pressure drop due to tube bends it is desirable to have the
aspect ratio as high as possible to minimize the number of tube bends.
3. For all the tube diameters and frontal area studied, coil cost higher than $30
will not significantly increase the condenser performance.
4. The smallest tube studied, 5/16, gives the best performance.
5. Airflow velocity should be approximately to 13 ft/s.
6. Horizontal tube spacing for 5/16 tubes should be approximately 0.3 and
vertical spacing approximately 1.7.
Recommendations
As previously described, the goal of this study was to find and implement an
optimization technique to the previously existing finned-tube air-conditioning system
model. The fins used in this study are flat plate fins, but in the industry enhanced surface
fins have become common. Therefore, for future studies, enhanced surface fins are a
recommended addition to the air-conditioning condenser simulation program. Though
the correlation used for calculating the fin efficiency is stated by Schmidt (1945) to be
50
accurate for non-symmetric fins, it should be validated for the highly non-symmetric
optimal design in the current study.
The circuiting of the condenser coil has a major effect on the air-conditioning
system total performance. In future studies there is an opportunity to enhance the air-
conditioner simulation program and allowing more design options for the circuiting such
as varying the number of tubes per parallel circuit through the condenser.
Due to limitations in air-side pressure drop and heat transfer correlations,
condensers with smaller tube diameter than 5/16 have not been studied. Since the
optimum in this study occurs for a condenser with 5/16 tubing it could be that a smaller
diameter would give higher COP. This could depend on the on the available smaller
diameter tubing wall thickness. It is therefore recommended that condensers with smaller
tubes be included in future studies, with valid pressure drop and heat transfer
correlations.
This study uses a system component models developed from experimental
correlations to simulate the air-conditioning system performance. No experiments have
been run to verify the system model. In future studies it is recommended that the air-
conditioner system model be compared to experimental system performance values.
51
REFERENCES
AAON, AAON Heating and Air-Conditioning Products web site, http://www.aaon.com/, 2001
EPA, United States Environmental Protection Agency: Ozone Depletion Home Page, http://www.epa.gov/ozone/, 2001.
Incropera, F. P. and DeWitt, D. P., Fundamentals of Heat and Mass Transfer, 4th Edition, John Wiley & Sons, New York, p. 445, 1996.
Kays, W. M. and London, A. L., Compact Heat Exchangers, 3rd Edition, McGraw-Hill, New York, 1984.
Klein, S. A. and Reindl, D. T., The Relationship of Optimum Heat Exchanger Allocation and Minimum Entropy Generation for Refrigeration Cycles, Proceedings of the ASME Advanced Energy Systems Division, vol. 37, pp. 87-94, 1997.
Lagarias, J. C., Reeds, J. A., Wright, M. H. and Wright, P. E., Convergence properties of the Nelder-Mead Simplex method in low dimensions, SIAM J. Optim., Vol. 9, No1, pp. 112-147, 1998.
McQuiston, F. C. and Parker, J. P., Heating Ventilating and Air-Conditioning-Analysis and Design, John Wiley & Sons, New York, 1994.
Nelder, J. A. and Mead, R., A Simplex Method for Function Minimization, Computer J., 7 308-313 (1965)
Reklaitis, G. V., Ravindran, A., Ragsdell, K. M., Engineering Optimization, Methods and Applications, John Wiley and Sons, 1983.
Rich, D. G., The Effect of Fin Spacing on the Heat Transfer and Friction Performance of Multi-Row, Smooth Plate Fin-and-Tube Heat Exchangers, ASHRAE Transactions, vol. 79, pt. 2, pp. 137-145, 1973.
Schmidt, T. E., La Production Calorifique des Surfaces Munies dailettes, Annexe Du bulletin De LInstitut International Du Froid, Annexe G-5, 1945.
Shah, M. M., A General Correlation For Heat Transfer During Film Condensation Inside Pipes, Heat and Mass Transfer, vol. 22, pp. 547-556, 1979.
Threlkeld, J. R., Thermal Environmental Engineering, 2nd Edition, Prentice Hall International, New York, pp.55, 1970.
Wenzel, T. P., Koomey, J. G., Rosenquist, J. G., Sanchez, M., and Hanford, J. W., Energy data sourcebook for the U.S. residential sector, Lawrence Berkeley National Laboratory, 1997. LBL-40297.
52
Wright, M. F., Plate-Fin-and-Tube Condenser performance and Design for Refrigerant R-410a Air-Conditioner, M.S. Thesis Georgia Institute of Technology, May 2000
Zukauskas, A. and Ulinskas, R., Banks of Plain and Finned Tubes, Heat Exchanger Design Handbook, G. F. Hewitt Edition, Begell House, Inc., New York, pp. 2.24-1 2.24-17, 1998.
Research ObjectivesAir Conditioning System and Component ModelingCompressorCondenserCondenser FanExpansion ValveEvaporatorEvaporator FanRefrigerant Mass Inventory
The figure of meritSimplex search methodOne iteration of the Nelder-Mead Simplex search algorithmSoftware ToolsOptimization ParametersOptimal Condenser DesignConclusionsGeneral Design GuidelinesRecommendations