4
ATEX/IECEx: Zone 1 and 2 II 2 GD ATX CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, Contactors For Increased Safety Enclosures Applications Useful as back-up circuit breaker protection or as main circuit breaker protection for hazardous areas. To be fitted inside increased safety Ex e enclosures. Features Up to 40 A for 2-pole circuit breaker versions. Up to 63 A for 2-pole with GFI, 3-pole and 4-pole circuit breaker versions. Up to 63 A for switch versions. Breaking capacity 10 kA – 400 V according to EN/IEC 60947-2 standard. Breaking capacity 6 kA-400 V according to EN/IEC 60898 standard. Supplied with front rotary control handle padlockable in OFF position. Terminal capacity: 1 x 25 mm 2 (0.002 x0.039 in 2 ). Mounting in polyester (ECEP series) or in 316L stainless steel (ECES series) enclosures. Can be fixed either on the door or at the back of the enclosure. Standard Materials • Housing: polyamide ATEX/IECEx Certifications and Compliances Certification Type IT40U (2-pole versions) — Gas, Zones 1 and 2 (Authorized to be used in an approved dustproof enclosure) Conforming to ATEX 94/9/CE: II 2 G — Type of Protection: Ex de IIC Service Temperature: -20 °C to +55 °C (-4 °F to +131 °F) CE Declaration of Conformity: 5C216 — ATEX Certificate: LCIE 02 ATEX 0035U — IECEx Certificate: IECEx LCI 04.0033U Certification Type CBU (2-pole GFI, 3-pole and 4-pole versions) — Gas, Zones 1 and 2 (Authorized to be used in an approved dustproof enclosure) Conforming to ATEX 94/9/CE: II 2 G — Type of Protection: Ex de IIC Service Temperature: -20 °C to +55 °C (-4 °F to +131 °F) CE Declaration of Conformity: 5C244 — ATEX Certificate: LCIE 09 ATEX 3068U — IECEx Certificate: IECEx LCI 09.0023L EURASEC Certification Certification Type IT40U (2-pole versions) — EURASEC N° TC RU C-FR.ГБ05.B.00909 Certification Type CBU (2-pole GFI, 3 and 4-pole versions) — EURASEC N° TC RU C-FR.ГБ05.B.00909 Other Certification Certification Type IT40U (2-pole versions) — INMETRO Certificate: BVC 11.0594-U Certification Type CBU (2-pole GFI, 3 and 4-pole versions) — INMETRO Certificate: BVC 10.0011-U 2-Pole Circuit Breaker with GFI 4-Pole Circuit Breaker 2-Pole Circuit Breaker 4-Pole Switch INMETRO certification available on special request only. Contact your local sales representative for more information. DISTRIBUTION EQUIPMENT: ATEX/IECEx INCREASED SAFETY CIRCUIT BREAKERS Visit our website at www.emerson.com or contact us at (800) 621-1506. © June 2017 277

Appleton™ ATX™ CBU, SWU, RCU Series Branch Circuit ......ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, Contactors For Increased Safety Enclosures Applications

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Appleton™ ATX™ CBU, SWU, RCU Series Branch Circuit ......ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, Contactors For Increased Safety Enclosures Applications

ATEX/IECEx: Zone 1 and 2

II 2 GD

ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, ContactorsFor Increased Safety Enclosures

Applications• Useful as back-up circuit breaker protection or as main circuit

breaker protection for hazardous areas.• TobefittedinsideincreasedsafetyExeenclosures.

Features• Up to 40 A for 2-pole circuit breaker versions.• Up to 63 A for 2-pole with GFI, 3-pole and 4-pole

circuit breaker versions.• Up to 63 A for switch versions. • Breaking capacity 10 kA – 400 V according to EN/IEC

60947-2 standard.• Breaking capacity 6 kA-400 V according to EN/IEC 60898

standard.• Supplied with front rotary control handle padlockable

in OFF position.• Terminal capacity: 1 x 25 mm2 (0.002 x0.039 in2).• Mounting in polyester (ECEP series) or in 316L stainless steel

(ECESseries)enclosures.Canbefixedeitheronthedoororatthe back of the enclosure.

Standard Materials• Housing: polyamide

ATEX/IECEx Certifications and Compliances• CertificationTypeIT40U (2-pole versions)

—Gas,Zones1and2(Authorized to be used in an approved dustproof enclosure)

—Conforming to ATEX 94/9/CE: II 2 G—TypeofProtection: Ex de IIC—Service Temperature: -20 °C to +55 °C (-4 °F to +131 °F)—CE Declaration of Conformity: 5C216—ATEXCertificate:LCIE02ATEX0035U—IECExCertificate:IECExLCI04.0033U

• CertificationType CBU (2-pole GFI, 3-pole and 4-pole versions)—Gas,Zones1and2(Authorized to be used in an approved

dustproof enclosure)—Conforming to ATEX 94/9/CE: II 2 G—TypeofProtection: Ex de IIC—Service Temperature: -20 °C to +55 °C (-4 °F to +131 °F)—CE Declaration of Conformity: 5C244—ATEXCertificate:LCIE09ATEX3068U—IECExCertificate:IECExLCI09.0023L

EURASEC Certification• CertificationTypeIT40U(2-poleversions)

—EURASECN°TCRUC-FR.ГБ05.B.00909• CertificationTypeCBU(2-poleGFI,3and4-poleversions)

—EURASECN°TCRUC-FR.ГБ05.B.00909

Other Certification • CertificationTypeIT40U(2-poleversions)

—INMETROCertificate:BVC11.0594-U• CertificationTypeCBU(2-poleGFI,3and4-poleversions)

—INMETROCertificate:BVC10.0011-U

2-Pole Circuit Breaker with GFI 4-Pole Circuit Breaker

2-Pole Circuit Breaker 4-Pole Switch

INMETRO certification available on special request only. Contact your local sales representative for more information.

DISTRIBUTION EQUIPMENT: ATEX/IECEx INCREASED SAFETY CIRCUIT BREAKERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © June 2017

277

Page 2: Appleton™ ATX™ CBU, SWU, RCU Series Branch Circuit ......ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, Contactors For Increased Safety Enclosures Applications

ATEX/IECEx: Zone 1 and 2

II 2 GD

ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, ContactorsFor Increased Safety Enclosures

Catalog Numbering Guide — ATEX/IECEx Certified Branch Circuit Breakers, Switches

CBU 1 01 B R1 5

Circuit Breaker Series:CBU - Circuit Breaker

2P, 3P and 4P

CBUN - Circuit Breaker 2P+GFI version

Switch Series:SWU - Switch

Intensity: GFI:R1 - 30 mAR2 - 300 mA01 - 1 A

02 - 2 A03 - 3 A04 - 4 A06 - 6 A10 - 10 A16 - 16 A 20 - 20 A25 - 25 A32 - 32 A40 - 40 A50 - 50 A63 - 63 A

Number of Poles:1 - 1-Pole2 - 2-Poles3 - 3-Poles4 - 4-Poles9 - 1-Pole + Neutral

Curve Type:B - Curve BC - Curve CD - Curve D

Options:5 - 440 Vac6 - 480 VacF3 - 1 NO/NC Fault Indication

ContactF5 - NO Fault Indication ContactF9 - NC Fault Indication ContactS3 - 1 NO/NC Auxiliary ContactS5 - 2 NO Auxiliary ContactS9 - 2 NC Auxiliary ContactM - 15 kA Breaking CapacityP - 25 kA Breaking Capacity

Catalog Numbering Guide — ATEX/IECEx Certified Relays and Contactors

RCU 1 01 B R1

RCU : Relay and Contactor Intensity: Coil voltage:24 - 24VAC (for 20,24,40 Amps only)23 - 230VAC (for 20,24,40 Amp)20 - 20 A

24 - 24 A40 - 40 A

Number of Poles:2 - 2-Poles3 - 3-Poles4 - 4-Poles

Number of contacts:- For 20 Amps only:

20 - 2NO02 - 2NC11 - 1NO+1NC

- For 24 Amps only:40 - 4NO04 - 4NC13 - 1NO+3NC22 - 2NO+2NC31 - 3NO+1NC

- For 40 Amps only:40 - 4NO22 - 2NO+2NC31 - 3NO+1NC

SWU Series Switches: Up to 40 Amps for 2-pole version. Up to 63 Amps for 3- and 4-pole versions. Example: 3-pole, 25 Amp switch – SWU325.

DIST

RIBU

TION

EQUI

PMEN

T: AT

EX/I

ECEx

INCR

EASE

D SA

FETY

CIR

CUIT

BREA

KERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © June 2017

278

Page 3: Appleton™ ATX™ CBU, SWU, RCU Series Branch Circuit ......ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, Contactors For Increased Safety Enclosures Applications

ATEX/IECEx: Zone 1 and 2

II 2 GD

ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, ContactorsFor Increased Safety Enclosures

Circuit Breakers – CBU Series

Weight kg (lbs) Volume dm2 (in2) Certified Type Catalog Number

2-Pole Branch Circuit Breaker – 230/240 Vac – Tripping Curve C

2 x 6 A 1.9 (4.19) 1.1 (0.002) IT40U CBU206C

2 x 10 A 1.9 (4.19) 1.1 (0.002) IT40U CBU210C

2 x 16 A 1.9 (4.19) 1.1 (0.002) IT40U CBU216C

2 x 20 A 1.9 (4.19) 1.1 (0.002) IT40U CBU220C

2 x 25 A 1.9 (4.19) 1.1 (0.002) IT40U CBU225C

2 x 32 A 1.9 (4.19) 1.1 (0.002) IT40U CBU232C

2-Pole GFI Branch Circuit Breaker – 230/240 Vac – Tripping Curve C

2 x 10 A/30 mA 1.9 (4.19) 3.1 (0.005) CBU CBUN210CR1

2 x 16 A/30 mA 1.9 (4.19) 3.1 (0.005) CBU CBUN216CR1

2 x 20 A/30 mA 1.9 (4.19) 3.1 (0.005) CBU CBUN220CR1

2 x 10 A/300 mA 1.9 (4.19) 3.1 (0.005) CBU CBUN210CR2

2 x 16 A/300 mA 1.9 (4.19) 3.1 (0.005) CBU CBUN216CR2

2 x 20 A/300 mA 1.9 (4.19) 3.1 (0.005) CBU CBUN220CR2

3-Pole Branch Circuit Breaker – 380/415 Vac – Tripping Curve C

3 x 6 A 1.9 (4.19) 3.1 (0.005) CBU CBU306C

3 x 10 A 1.9 (4.19) 3.1 (0.005) CBU CBU310C

3 x 16 A 1.9 (4.19) 3.1 (0.005) CBU CBU316C

3 x 20 A 1.9 (4.19) 3.1 (0.005) CBU CBU320C

3 x 25 A 1.9 (4.19) 3.1 (0.005) CBU CBU325C

3 x 32 A 1.9 (4.19) 3.1 (0.005) CBU CBU332C

4-Pole Branch Circuit Breaker – 380/415 Vac – Tripping Curve C

4 x 6 A 1.9 (4.19) 3.1 (0.005) CBU CBU406C

4 x 10 A 1.9 (4.19) 3.1 (0.005) CBU CBU410C

4 x 16 A 1.9 (4.19) 3.1 (0.005) CBU CBU416C

4 x 20 A 1.9 (4.19) 3.1 (0.005) CBU CBU420C

4 x 25 A 1.9 (4.19) 3.1 (0.005) CBU CBU425C

4 x 32 A 1.9 (4.19) 3.1 (0.005) CBU CBU432C

Relays and Contactors – RCU Series

2 and 4-pole versions:• Rated current: 20 A, 24 A, 40 A and 63 A.• Rated voltage: Up to 415 V - 50/60 Hz.• Coil voltage: Up to 240 V - 50/60 Hz.• Consult factory for further details.

CBU and SWU Bracket

Description Catalog Number

Bracket for door fixing for 2-pole MCB 096650

DISTRIBUTION EQUIPMENT: ATEX/IECEx INCREASED SAFETY CIRCUIT BREAKERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © June 2017

279

Page 4: Appleton™ ATX™ CBU, SWU, RCU Series Branch Circuit ......ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, Contactors For Increased Safety Enclosures Applications

ATEX/IECEx: Zone 1 and 2

II 2 GD

ATX™ CBU, SWU, RCU Series Branch Circuit Breakers, Switches, Relays, ContactorsFor Increased Safety Enclosures

Dimensions in Millimeters (Inches)

54.6(2.15)

69.0(2.72)

163.

4(6

.43)

131.0(5.16)

Fix

112.

5(4

.43)

4.5(0.18)

Fix 39.0(1.54)

135.5(5.33)

183.

0(7

.21)

75.5(2.97) 4.5(0.18)

Fix

133.

0(5

.24)

Fix 81.5(3.21)

100.0(3.94)

2 Poles Circuit breaker with GFI2 Poles + Aux Circuit Breaker with GFi

Fix

118.

0(4

.65)

4.5(0.18)

100.0(3.94)

168.

0(6

.62)

Fix 81.5(3.21)

75.5(2.97)

100.5(3.96)

2 / 3 / 4 Poles Contactor

4.5(0.18)

Fix

118.

0(4

.65)

100.0(3.94)113.3(4.46)

Fix 81.5(3.21)

168.

0(6

.60)

136.0(5.34)

75.5(2.97)

2 / 3 / 4 Poles + Aux. Circuit Breaker3 / 4 Poles Circuit Breaker

1 / 2 Poles Circuit Breaker1 Pole + Aux. Circuit Breaker

42.0(1.65)

125.

0(4

.92)

42.5(1.67)

126.1(4.96)

6(0

.24)

163.

0(6

.43)

WIth fixing kit 2 Poles 096650

4.5(0.18)

Fix

118.

0(4

.65)

Fix 81.5(3.21)

100.0(3.94)

168.

0(6

.62)

136.0(5.34)

75.5(2.97)

3 / 4 Poles Switch Breaker3 / 4 Poles + Aux. Switch Breaker

113.3(4.46)

100.0(3.94)

Fix

118.

0(4

.65)

4.5(0.18)

Fix 81.5(3.21)

168.

0(6

.62)

75.5(2.97)

136.0(5.34)

4 Poles Switch with Earth Leakage4 Poles + Aux. Switch with Earth Leakage

DIST

RIBU

TION

EQUI

PMEN

T: AT

EX/I

ECEx

INCR

EASE

D SA

FETY

CIR

CUIT

BREA

KERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © June 2017

280