7
Design and Experiment of a Back-To-Back (BTB) System Using Modular Multilevel Cascade Converters for Power Distribution Systems Pracha Khamphakdi, Student Member, IEEE, Kei Sekiguchi, Makoto Hagiwara, Member, IEEE, and Hirofumi Akagi, Fellow, IEEE Department of Electrical and Electronic Engineering Tokyo Institute of Technology, Tokyo, Japan E-mail: [email protected] Abstract— This paper presents an application of the modular multilevel cascade converter based on double-star chopper-cells (MMCC-DSCC) to a back-to-back (BTB) system for installation on 6.6-kV power distribution systems. The DSCC is characterized by a cascade connection of multiple chopper-cells per leg, leading to flexible circuit design, low voltage steps, low EMI emission, and low harmonic voltage and current. The DSCC-based BTB system is equipped with neither dc capacitor nor voltage sensor on the common dc link. The paper designs, constructs, and tests a three-phase, 200-V, and 10-kW downscaled system to verify and justify its operating principles and performance. Experimental and simulated results agree well with each other, showing a promising possibility of the DSCC-based BTB system. Index Terms —Back-to-back systems, grid-connected convert- ers, modular multilevel cascade converters (MMCC) I. I NTRODUCTION The global warming, one of critical issues in environment, has resulted in calling for review in a new way of electric power generation. The goal of the way is to reduce CO 2 emission by means of replacing a part of conventional fossil- fuel power plants with renewable energy sources such as solar power and wind power. This type of generation is called often as “distributed generators,” because most of them are installed on power distribution systems. Fig. 1 shows a simplified utility power distribution system consisting of two 6.6-kV radial feeders in Japan, where feeder 1 has no distributed generator whereas feeder 2 has many distributed generators. As a result, the so-called “back feed” may occur throughout feeder 2, so that the grid voltage at the load end of feeder 2 increases while that of feeder 1 decreases. This may cause voltage imbalance between the two feeders, thus making it difficult for both feeders to comply with the utility voltage code [1]. A back-to-back (BTB) system intended for installation between the ends of the two 6.6-kV distribution feeders, was designed, constructed, and tested to mitigate the voltage imbalance. This type of BTB system is referred to as a “loop balance controller” in [2]. However, the BTB system with a common dc-link voltage of 13.2 kV suffered from supply (line) harmonic currents as well as EMI emissions because it is based on traditional two-level PWM converters with a string of eight series-connected 3.3-kV IGBTs per arm. Recently, attention has been paid to the so-called “modular multilevel converter (MMC)” for high-voltage and high-power applications such as long-distance high-voltage direct-current BTB System Primary Distribution Transformer Distibuted Power Generators Loads Loads Feeder 1 Feeder 2 66 kV / 6.6 kV Fig. 1. A 6.6-kV power distribution system consisting of two radial feeders. (HVDC) transmission systems and BTB systems [3], [4]. However, the use of the MMC in either title or contents of technical papers or articles may cause confusion about termi- nology if the reader is not an expert of multilevel converters. To avoid this confusion, the author of [5] classified modular multilevel converters from circuit topology, combining the family name, “modular multilevel cascade converter” with different given names. For example, the modular multilevel cascade converter based on single-star bridge-cells (MMCC- SSBC) is suitable for STATCOMs and battery energy storage systems, while the modular multilevel cascade converter based on double-star chopper-cells (MMCC-DSCC) can achieve bidirectional (ac-to-dc and dc-to-ac) power conversion. Note that the MMCC-DSCC (hereinafter, just called as the DSCC) is the same in circuit configuration as the MMC in a narrow sense. Many technical papers described the DSCC, as well as its applications to HVDC and BTB systems, with focus on control, modeling, analysis, and/or system design [6]–[12]. However, their authors have confirmed the validity of their pa- pers by carrying out computer simulation without experimental verification. Siemens [13] has put the DSCC-based HVDC systems into practical use with a trade name of “HVDC- plus.” All the papers published from Siemens have made neither description of achieving dc-capacitor-voltage balancing of all the chopper-cells and regulating the common dc-link voltage, nor disclosure of presenting experimental waveforms. Moreover, no comparison has been made in voltage and current waveforms between experiment and simulation for the purpose of enhancing their reliability. This paper has an intensive discussion on a DSCC-based BTB system intended for installation on the 6.6-kV distribu- tion feeders. This BTB system is characterized by installing neither common dc-link capacitor nor voltage sensor on the 311 978-1-4799-0482-2/13/$31.00 ©2013 IEEE

Akagi - 2013

Embed Size (px)

Citation preview

  • Design and Experiment of a Back-To-Back (BTB) System Using Modular MultilevelCascade Converters for Power Distribution Systems

    Pracha Khamphakdi, Student Member, IEEE, Kei Sekiguchi, Makoto Hagiwara, Member, IEEE,and Hirofumi Akagi, Fellow, IEEE

    Department of Electrical and Electronic EngineeringTokyo Institute of Technology, Tokyo, Japan

    E-mail: [email protected]

    Abstract This paper presents an application of the modularmultilevel cascade converter based on double-star chopper-cells(MMCC-DSCC) to a back-to-back (BTB) system for installationon 6.6-kV power distribution systems. The DSCC is characterizedby a cascade connection of multiple chopper-cells per leg, leadingto flexible circuit design, low voltage steps, low EMI emission,and low harmonic voltage and current. The DSCC-based BTBsystem is equipped with neither dc capacitor nor voltage sensoron the common dc link. The paper designs, constructs, and tests athree-phase, 200-V, and 10-kW downscaled system to verify andjustify its operating principles and performance. Experimentaland simulated results agree well with each other, showing apromising possibility of the DSCC-based BTB system.

    Index Terms Back-to-back systems, grid-connected convert-ers, modular multilevel cascade converters (MMCC)

    I. INTRODUCTIONThe global warming, one of critical issues in environment,

    has resulted in calling for review in a new way of electricpower generation. The goal of the way is to reduce CO2emission by means of replacing a part of conventional fossil-fuel power plants with renewable energy sources such as solarpower and wind power. This type of generation is called oftenas distributed generators, because most of them are installedon power distribution systems.

    Fig. 1 shows a simplified utility power distribution systemconsisting of two 6.6-kV radial feeders in Japan, where feeder1 has no distributed generator whereas feeder 2 has manydistributed generators. As a result, the so-called back feedmay occur throughout feeder 2, so that the grid voltage at theload end of feeder 2 increases while that of feeder 1 decreases.This may cause voltage imbalance between the two feeders,thus making it difficult for both feeders to comply with theutility voltage code [1].

    A back-to-back (BTB) system intended for installationbetween the ends of the two 6.6-kV distribution feeders,was designed, constructed, and tested to mitigate the voltageimbalance. This type of BTB system is referred to as a loopbalance controller in [2]. However, the BTB system with acommon dc-link voltage of 13.2 kV suffered from supply (line)harmonic currents as well as EMI emissions because it is basedon traditional two-level PWM converters with a string of eightseries-connected 3.3-kV IGBTs per arm.

    Recently, attention has been paid to the so-called modularmultilevel converter (MMC) for high-voltage and high-powerapplications such as long-distance high-voltage direct-current

    BTBSystem

    PrimaryDistributionTransformer

    Distibuted Power Generators

    Loads

    Loads

    Feeder 1

    Feeder 2

    66 kV / 6.6 kV

    Fig. 1. A 6.6-kV power distribution system consisting of two radial feeders.

    (HVDC) transmission systems and BTB systems [3], [4].However, the use of the MMC in either title or contents oftechnical papers or articles may cause confusion about termi-nology if the reader is not an expert of multilevel converters.To avoid this confusion, the author of [5] classified modularmultilevel converters from circuit topology, combining thefamily name, modular multilevel cascade converter withdifferent given names. For example, the modular multilevelcascade converter based on single-star bridge-cells (MMCC-SSBC) is suitable for STATCOMs and battery energy storagesystems, while the modular multilevel cascade converter basedon double-star chopper-cells (MMCC-DSCC) can achievebidirectional (ac-to-dc and dc-to-ac) power conversion. Notethat the MMCC-DSCC (hereinafter, just called as the DSCC)is the same in circuit configuration as the MMC in a narrowsense.

    Many technical papers described the DSCC, as well asits applications to HVDC and BTB systems, with focus oncontrol, modeling, analysis, and/or system design [6][12].However, their authors have confirmed the validity of their pa-pers by carrying out computer simulation without experimentalverification. Siemens [13] has put the DSCC-based HVDCsystems into practical use with a trade name of HVDC-plus. All the papers published from Siemens have madeneither description of achieving dc-capacitor-voltage balancingof all the chopper-cells and regulating the common dc-linkvoltage, nor disclosure of presenting experimental waveforms.Moreover, no comparison has been made in voltage andcurrent waveforms between experiment and simulation for thepurpose of enhancing their reliability.

    This paper has an intensive discussion on a DSCC-basedBTB system intended for installation on the 6.6-kV distribu-tion feeders. This BTB system is characterized by installingneither common dc-link capacitor nor voltage sensor on the

    311978-1-4799-0482-2/13/$31.00 2013 IEEE

  • DSCC-A

    DSCC-B

    (= )

    1

    8

    9

    16

    1

    8

    9

    16

    cell

    cell

    cell

    cell

    cell

    cell

    cell

    cell

    cell

    cell

    cell

    cell

    ( : 1 16)

    a

    c

    b

    (a)

    (b) (c)

    Fig. 2. Circuit configuration for the DSCC-based BTB system with 16cells/leg. (a) Main power circuit. (b) Chopper-cell. (c) Center-tapped inductor(or coupled inductor).

    common dc link. Modeling and analysis are done for reg-ulating the common dc-link voltage to a preset referencevoltage. A three-phase, 200-V, and 10-kW downscaled systemis designed, constructed, and tested to verify the validity ofthe whole control system in steady and transient conditions.In addition, computer simulation using a software package ofPSCAD/EMTDC is executed under the same conditions asthe experiment using the downscaled system. Experimentalwaveforms agree with simulated ones well enough to guaran-tee the reliability of both experiment and simulation.

    II. CIRCUIT CONFIGURATION AND EQUATIONSA. Circuit Configuration

    Fig. 2(a) shows the circuit configuration for the DSCC-based BTB system. Each leg consists of a cascade connectionof 16 chopper-cells depicted in Fig. 2(b), and a center-tappedinductor in Fig. 2(c). Each chopper-cell consisting of a dccapacitor and two IGBTs forms the so-called bidirectionalchopper. Here, is the low-voltage-side voltage of eachchopper-cell, and is the high-voltage-side voltage ofeach chopper-cell. Two terminals of the center-tapped inductor,a and b are connected to the positive and negative arms,and terminal c is connected to an ac-link inductor sittingat the front end of the DSCC-A. The dc terminal at the backend is directly connected to that of the DSCC-B without anydc-link capacitor.

    Let the common dc-link current and voltage be and ,

    respectively. The instantaneous active power at the dc link,, is given by

    = . (1)

    B. Circuit EquationsIn Fig 2(a), and are the positive and negative

    arm currents, and is the supply current. The followingequations exist

    = + , (2)

    =1

    2( + ), (3)

    where is the circulating current along the dc loop in the-phase leg, which is defined in [6]. Note that containsonly a dc component under an ideal condition [6]. From (2)and (3), the arm currents and can be expressed byusing and as follows:

    = 12, (4)

    = +1

    2. (5)

    Note that , , and are the branch currents, while is the loop current that cannot be measured directly.

    The dc-link current can be expressed from Kirchhoffscurrent law (KCL) as follows:

    =

    =,,

    ,

    =

    =,,

    ( 12),

    =

    =,,

    . (6)

    where the relation of + + = 0 is utilized.Equation (6) means that the supply currents produce no effecton the dc-link current .

    Each arm of the DSCC in Fig. 2(a) is represented bya voltage source equal to the sum of the low-voltage-sidevoltages of the chopper-cells. For example, of the DSCC-A,the -phase collective positive-arm and negative-arm voltages, and , are expressed as follows:

    =

    /2=1

    , (7)

    =

    =1+2

    , (8)

    312

  • where is the number of the chopper-cells per leg. The-phase collective leg voltage of the DSCC-A, , isobtained from (7) and (8) as

    = + =

    =1

    . (9)

    The following equation exists in the -phase leg of the DSCC-A as

    = +

    . (10)

    The center-tapped inductor presents inductance only tothe circulating current , and no inductance to the supplycurrent [6]. In other words, provides no effect onthe voltage across the center-tapped inductor.

    Finally, making reference to the Appendix can express and as

    =1

    6

    ( =,,

    +

    =,,

    ), (11)

    =

    1

    2

    ( =,,

    =,,

    ). (12)

    Equation (11) means that is equal to the average valueof all the low-voltage-side voltages of the chopper-cells usedin the BTB system. Moreover, is independent of and. Equation (12) means that the dc-link current can becontrolled by adjusting a voltage difference between the sumof the low-voltage-side voltages of the DSCC-A and that ofthe DSCC-B.

    III. CONTROL METHODThe control method for the DSCC-based BTB system can

    be classified into the following four parts: control of instantaneous active and reactive power [16] at

    the ac mains, voltage control of the floating dc capacitors, control of the dc-link voltage, and control of the dc-link current.

    The power control is achieved by using the synchronousreference frames along with the decoupled current control.

    The voltage control of the dc capacitors can be achieved byapplying the control method proposed in [6] and [7]. Notethat the aim of the voltage control is not to regulate theinstantaneous voltage of each dc capacitor, but to regulatethe mean voltage with the help of a moving-average filterof 50 Hz [8].

    A. Control of the DC-Link VoltageThe following reasonable assumption is made in (11):

    =,,

    +

    =,,

    = 6. (13)

    This assumption is valid because the six legs are operatedin the same way, especially in terms of the dc components.Substituting (13) into (11) yields

    = . (14)Equation (9) indicates that contains no fundamental-frequency component, because those included in and cancel out each other. Hence, contains only adc component if the switching-ripple components are ignored.Let the dc component included in be (). Equation(14) is changed from (9) to

    = (). (15)The chopper-cell can produce an arbitrary dc voltage, so longas it is lower than the dc-capacitor voltage [6]. This paper sets() as follows:

    () =1

    2 , (16)

    where is the average value of all the dc-capacitor voltagesused for the BTB system. Substituting (16) into (15) yields

    =1

    2 . (17)

    Equation (17) means that can be regulated by adjusting . For example, is regulated at 400 V when = 50 Vand = 16. It is possible to force to follow the reference by applying an appropriate feedback control of the dc-capacitor voltages, which has already proposed in [6] and[7]. This method is characterized by indirectly regulating ,thus making it possible to eliminate a voltage sensor and a dccapacitor from the common dc-link of the BTB system.

    B. Control of the DC-Link CurrentEquation (6) means that the dc-link current is expressed

    by the circulating currents. This implies that can beadjusted indirectly by controlling these circulating currents.The reference for the dc-link current, , is given by

    =

    /2, (18)

    where is the active power reference and /2 correspondsto the dc-link voltage as predicted from (17). The referencesfor the circulating currents of the DSCC-A and the DSCC-B, and , are expressed as

    = = 3. (19)

    Note that each chopper-cell should produce an amount ofvoltage for adjusting the corresponding circulating current [6].For example, each chopper-cell in the -phase leg of theDSCC-A produces the voltage that is given by

    313

  • 200 V50 Hz

    200 V/200 V 200 V/200 V

    =

    (= 0)

    PT PT

    MUX MUX

    Fig. 2(a)

    DSCC-A DSCC-B

    2 2

    48

    6

    48

    66 6

    96 96

    gatesignals

    DSP(TMS320C6713)

    FPGA-A (Altera Cyclone II)A/D Converters

    FPGA-B (Altera Cyclone II)A/D Converters

    MUX : Multiplexer

    Fig. 3. Overview of the three-phase, 200-V, and 10-kW experimental system.

    =

    ( ), (20)where is the feedback gain. Considering the above equa-tion allows the -phase collective leg voltage of the DSCC-A,, to be changed from (14) to the following equation:

    = + . (21)The similar equations exist in the other five legs. Equations(6), (19), and (20) produce the following equation:

    =,,

    =

    =,,

    =

    ( ). (22)

    The dc-link current can be expressed from (12), (21), and (22)as follows:

    =

    1

    2

    [ =,,

    =,,

    ]

    =

    ( ). (23)

    Hence, the actual dc-link current exhibits a first-orderresponse to its reference with a time constant of / .Moreover, can be controlled, independent of .

    IV. EXPERIMENT AND SIMULATIONA. System Configuration Used for Experiment and Simulation

    Fig. 3 shows the overview of the three-phase, 200-V, and 10-kW experimental system, that is used as a downscaled systemof the 6.6-kV BTB system. Table I summarizes the circuitparameters used in experiment and simulation. Each DSCChas eight chopper-cells per arm. Hence, the total number ofchopper-cells used for the BTB system is 96 (= 862). EachDSCC is connected to the three-phase 200-V ac mains via

    TABLE ICIRCUIT PARAMETERS USED IN THE EXPERIMENT AND SIMULATION

    Rated power 10 kWNominal line-to-line rms voltage 200 V

    Nominal line frequency 50 HzAC-link inductor 2 mH (16%)*Coupled inductor 3 mH (24%)*

    Number of chopper-cells per leg 16DC-link voltage 400 V

    DC-capacitor voltage 50 V (= 400 V/8)DC-capacitor 6.6 mF

    Unit capacitance constant [15] 40 ms at 50 VPWM carrier frequency 450 Hz

    Switching-ripple frequency 16 7.2 kHz*These values are on a 200-V, 10-kW, and 50-Hz base.

    ac-link inductors = 2.0 mH (16%) and a line-frequencytransformer with unity voltage ratio for galvanic isolation. Thecenter-tapped inductor shown in Fig. 2(c) has an inductancevalue of = 3.0 mH (24%). Although the inductance valueof is larger than that of , the size of the center-tappedinductor is half of the ac-link inductor in volume because presents no inductance to the supply current. The capacitancevalue of the dc capacitor is = 6.6 mF, which correspondsto = 40 ms in the unit capacitance value [15]. Eachchopper-cell uses four power MOSFETs connected in parallelas a power switch for reducing the conduction loss, thusmaking the experimental system more reliable and effective asa downscaled system of the 6.6-kV BTB system. The referencevalue for the dc-capacitor voltage is set as = 50 V. Notethat neither electric capacitor nor film capacitor is connectedto the common dc-link terminals.

    The control systems consists of a digital signal processor(DSP) unit using the Texas Instruments TMS320C6713 andtwo field-programmable gate array (FPGA) units using theAltera Cyclone II. Each FPGA unit including A/D convertersdetects the 48 dc-capacitor voltages, the positive and negativearm currents, and the ac-mains voltages. These signals are sent

    314

  • 20 ms [V]

    400

    0-400

    [V]

    400

    0-400

    [A]

    50

    0

    -50

    THD of = 0.24%[A]

    50

    0-50

    [A]

    500

    -50

    [V]19

    755025

    0

    19

    [V]

    600400200

    0

    [A]

    50

    0-50

    () = 77.8 V

    24.7 A

    Fig. 4. Experimental waveforms during rectification ( = 10 kW, = 0kVA).

    to the A/D converters. Note that the dc-link voltage is notdetected. Here, the multiplexer (MUX) unit is used to reducethe number of A/D converters from 48 to six. The FPGA unitproduces 96-bit (= 2 48) gate signals in total, because eachchopper-cell includes two power switches.

    The experimental waveforms were taken by using a personalcomputer via the Yokogawa WE7000 PC-based data acquisi-tion system. The sampling frequency is 100 kHz in Figs. 4and 5, and 50 kHz in Figs. 6 and 7.

    The PSCAD/EMTDC software package is used for sim-ulation. The following conditions are considered:

    one-sampling delay of 140 s (= 1/(16 )) resultingfrom digital control, and a dead time of 8 s, and

    each chopper-cell uses ideal power switches with noswitching interval of time.

    B. Operating Performance Under Steady-State ConditionsFig. 4 shows the experimental waveforms when the DSCC-

    A acts as a rectifier ( = 10 kW and = 0 kVA). Here, and represent the power references for the instantaneousactive and reactive powers at the ac mains. Note that hasa positive value when active power is transferred from theDSCC-A to the DSCC-B, and vice versa.

    The ac-terminal (front-end) line-to-line voltages ,, and get multilevel PWM waveforms with avoltage step of 25 V (= 400 V/16). As a consequence,

    20 ms [V]

    400

    0-400

    [V]

    400

    0-400

    [A]

    50

    0

    -50

    THD of = 0.25%[A]

    50

    0-50

    [A]

    500

    -50

    [V]19

    755025

    0

    19

    [V]

    600400200

    0

    [A]

    50

    0-50

    () = 84.3 V

    24.6 A

    Fig. 5. Simulated waveforms during rectification ( = 10 kW, = 0kVA).

    they contain much less harmonic voltages and much lesscommon-mode voltage than a traditional two-level voltage-source PWM inverter. Since the carrier frequency of eachchopper-cell is 450 Hz, the switching-ripple frequency is7.2 kHz (= 450 Hz16). As a result, the waveforms of thesupply currents , , and look purely sinusoidalwith a 50-Hz fundamental-frequency component. The totalharmonic distortion (THD) value of is less than 1%.

    The arm currents, and , contain dc compo-nents, 50-Hz fundamental-frequency components, 3.6-kHz (=450 Hz8) switching-ripple components, and 100-Hz second-order harmonic components resulting from the control system[6]. However, no 100-Hz component appears in becausethose included in and cancel out each other. Thecirculating current contains a dc component of 8.3 A(= 10kW/(3 400V)), the 3.6-kHz switching-ripple com-ponent, and the 100-Hz second-order harmonic component.However, the 100-Hz component is small enough comparedto the dc component in terms of amplitude.

    The dc-capacitor voltages 1 and 9 contain bothdc and ac components, as shown in Fig. 4, where the voltagecontrol regulates the dc component at 50 V. The ac componentsconsist of the most dominant 50-Hz component and the seconddominant 100-Hz component. Both components are propor-tional to the amplitude of , and inversely proportionalto [18]. The mean dc-link voltage is regulated at 400V without any steady-state error because each dc-capacitor

    315

  • 100 ms [kW]

    100

    -10[V]

    400

    0

    -400

    [V]

    400

    0-400

    [A]

    50

    0

    -50

    [A]

    50

    0

    -50

    [A]

    50

    0

    -50

    [V]19

    755025

    0

    9 1

    [V]

    600400200

    0

    [A]

    50

    0-50

    () = 101.7 V

    24.6 A

    24.3 A

    Fig. 6. Experimental waveforms during transient state from the ratedrectification to inversion mode

    voltage is regulated at 50 V. The dc-link current has a dccomponent of 25 A, which agrees well with the theoreticalvalue obtained from (18).

    Fig. 5 shows the simulated waveforms when the DSCC-A acts as a rectifier ( = 10 kW and = 0 kVA).This simulation was carried out under the same conditionsas the experiment. Comparing Fig. 4 with 5 shows that bothwaveforms agree well with each other, bringing high reliabilityto both experiment and simulation.

    C. Operating Performance under a Transient-State ConditionFigs. 6 and 7 show the experimental and simulated wave-

    forms of the DSCC-A, in which the active-power referenceis changed from 10 kW to 10 kW under a ramp changein 100 ms. Here, is set to zero. This means that theDSCC-A changes its operation from rectification to inver-sion. Comparing Fig. 6 with 7 reveals that experiment andsimulation agree well with each other even under such atransient-state condition. No overcurrent occurs in the supplycurrents, the arm currents, the circulating current, and the dc-link current. Moreover, the dc-capacitor voltages and the dc-link voltage are well regulated to their references even duringthe transient period. Carefully looking into reveals thatthe switching-ripple component (), increases slightly

    100 ms [kW]

    100

    -10[V]

    400

    0

    -400

    [V]

    400

    0-400

    [A]

    50

    0

    -50

    [A]

    50

    0

    -50

    [A]

    50

    0

    -50

    [V]19

    755025

    0

    9 1

    [V]

    600400200

    0

    [A]

    50

    0-50

    () = 101.1 V

    24.3 A

    24.5 A

    Fig. 7. Simulated waveforms during transient state from the rated rectificationto inversion mode

    during the transient state. However, it is about 25% in peak-to-peak of the mean value of 400 V, which is within an acceptablevalue.

    V. CONCLUSION

    This paper has described an application of a modularmultilevel cascade converter based on double-star chopper-cells (MMCC) to a back-to-back (BTB) system, intended forinstallation on 6.6-kV power distribution systems. The derivedcircuit equations of the BTB system has shown that the dc-linkvoltage and current can be controlled independently withoutany mutual inference. Moreover, an indirect control of the dc-link voltage developed in this paper has eliminated neithera voltage sensor nor dc-link capacitors from the dc link.The validity and effectiveness of the BTB system has beenconfirmed and justified by both experiment using a three-phase, 200-V, and 10-kVA downscaled system and simulationusing the PSCAD/EMTDC software package.

    VI. ACKNOWLEDGEMENT

    The authors would like to thank the Japanese ministry ofeconomy, trade and industry for financially supporting thisresearch project.

    316

  • APPENDIXA. Derivation of equations (11) and (12)

    When attention is paid to either DSCC-A or DSCC-B,making reference to (10) allows to be expressed as follows:

    =1

    3

    ( =,,

    +

    =,,

    ), (24)

    =1

    3

    ( =,,

    +

    =,,

    ). (25)

    The dc-link current is expressed from Fig. 2(a) andKirchhoffs current law (KCL) as

    =

    =,,

    ,

    =

    =,,

    . (26)

    Substituting (26) into (24) and (25) yields

    =1

    3

    ( =,,

    ), (27)

    =1

    3

    ( =,,

    +

    ). (28)

    Equations (27) and (28) give (11) for and (12) for .

    REFERENCES[1] H. Akagi and S. Inoue, A bidirectional isolated dc-dc converter as a

    core circuit of the next-generation medium-voltage power conversionsystem, IEEE Trans. Power Electron., vol. 22, no. 2, pp. 535542,Mar. 2007.

    [2] N. Okada, M. Takasaki, H. Sakai, and S. Katoh, Development of a6.6-kV, 1-MVA transformerless loop balance controller, in Conf. Rec.IEEE PESC., pp. 10871091, 2007.

    [3] B. Gemmell, J. Dorn, D. Retzmann, and D. Soerangr, Prospects ofmultilevel VSC technologies for power transmission, in Conf. Rec.IEEE PES., pp. 116, 2008.

    [4] S. Allebrod, R. Hamerski, and R. Marquardt, New transformerless,scalable modular multilevel converters for HVDC-transmission, inConf. Rec. IEEE PESC., pp. 174179, 2008.

    [5] H. Akagi, Classification, terminology, and application of the modularmultilevel cascade converter (MMCC), IEEE Trans. Power Electron.,vol. 26, no. 11, pp. 31193130, Nov. 2011.

    [6] M. Hagiwara and H. Akagi, Control and experiment of pulsewidth-modulated modular multilevel converters, IEEE Trans. Power Electron.,vol. 24, no. 7, pp. 17371746, Jul. 2009.

    [7] M. Hagiwara, R. Maeda, and H. Akagi, Control and analysis of themodular multilevel cascade converter based on double-star chopper-cells (MMCC-DSCC), IEEE Trans. Power Electron., vol. 26, no. 6,pp. 16491658, Jun. 2011.

    [8] P. Munch, D. Gorges, M. Izak, and S. Liu, Integrated current control,energy control and energy balancing of modular multilevel converters,in Conf. Rec. IECON, pp. 150155, 2010.

    [9] H. Peng, M.Hagiwara, and H. Akagi, Modeling and analysis ofswitching-ripple voltage on the dc link between a diode rectifier anda modular multilevel cascade inverter (MMCI), IEEE Trans. PowerElectron., vol. 28, no.1, pp. 7584, Jan. 2013.

    [10] M. Saeedifard and R. Iravani, Dynamic performance of a modularmultilevel back-to-back HVDC system, IEEE Trans. Power Deliv.,vol. 25, no. 4, pp. 29032912, Oct. 2010.

    [11] M. Guan and Z. Xu, Modeling and control of a modular multilevelconverter-based HVDC system under unbalanced grid conditions, IEEETrans. Power Electron., vol. 27, no. 12, pp. 48584867, Dec. 2012.

    [12] Q. Tu, Z. Xu, Y. Chang, and L. Guan. Suppressing dc voltage ripplesof MMC-HVDC under unbalanced grid conditions, IEEE Trans. PowerDeliv., vol. 27, no. 3, pp. 13321338, Jul. 2012.

    [13] H. Knaak, Modular multilevel converters and HVDC/FACTS: a successstory, in Conf. Rec. IEEE EPE., pp. 16, 2011.

    [14] http://www.hvdc.ca/[15] H. Fujita, S. Tominaga, and H. Akagi, Analysis and design of a dc

    voltage-controlled static VAR compensator using quad-series voltage-source inverters, IEEE Trans. Ind. Appl., vol. 32, no. 4, pp. 970977,Jul./Aug. 1996.

    [16] H. Akagi, Y. Kanazawa, and A. Nabae, Instantaneous reactive powercompensators comprising switching devices without energy storagecomponents, IEEE Trans. Ind. Appl., vol. IA20, no. 3, pp. 625630,May/Jun. 1984.

    [17] K. Fujii, R. De Doncker, and S. Konishi, A novel dc-link voltagecontrol of PWM-switched cascade cell multi-level inverter applied toSTATCOM, in Conf. Rec. IEEE IAS., pp. 961967, vol. 2, 2005.

    [18] M. Hagiwara, K. Nishimura, and H. Akagi, A medium-voltage motordrive with a modular multilevel PWM inverter, IEEE Trans. PowerElectron., vol. 25, no. 7, pp. 17861799, Jan. 2010.

    317

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 200 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00333 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 400 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 600 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.00167 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing false /UntaggedCMYKHandling /UseDocumentProfile /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice