AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft Meeting Wednesday, July 20, 2016 Hilton Fort Lauderdale Marina Fort Lauderdale, Florida 1. Call to order. Call meeting to order by Chair Carl Wren at 8:00 a.m. on July 20, 2016 at the Hilton Fort Lauderdale Marina, Fort Lauderdale, FL. 2. Introduction of committee members and guests. For a current committee roster, see page 2. 3. Approval of August 25-26, 2015 first draft meeting minutes. See page 6. 4. The process – staff PowerPoint presentation. See page 9. 5. Core chapters, second revisions of interest. 6. NFPA 101 Second Draft preparation. For Public Comments, see page 26. 7. NFPA 5000 First Draft preparation. For Public Comments, see page 51. 8. Committee Input Review. For Committee Inputs, see page 75. 9. Emerging issues, industry trends, 2021 preparation. 10. Other business. 11. Future meetings. 12. Adjournment. Enclosures

AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Embed Size (px)

Citation preview

Page 1: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

 

AGENDA NFPA Technical Committee on Industrial, Storage,

and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft Meeting

Wednesday, July 20, 2016 Hilton Fort Lauderdale Marina

Fort Lauderdale, Florida

1. Call to order. Call meeting to order by Chair Carl Wren at 8:00 a.m. on July 20, 2016 at the Hilton Fort Lauderdale Marina, Fort Lauderdale, FL.

2. Introduction of committee members and guests. For a current committee roster, see page 2.

3. Approval of August 25-26, 2015 first draft meeting minutes. See page 6.

4. The process – staff PowerPoint presentation. See page 9.

5. Core chapters, second revisions of interest.

 

6. NFPA 101 Second Draft preparation. For Public Comments, see page 26.  

7. NFPA 5000 First Draft preparation. For Public Comments, see page 51.

8. Committee Input Review. For Committee Inputs, see page 75.

9. Emerging issues, industry trends, 2021 preparation.

10. Other business.

11. Future meetings.

12. Adjournment.

Enclosures

Page 2: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Address List No PhoneIndustrial, Storage, and Miscellaneous Occupancies SAF-IND

Safety to Life

Kristin Bigda06/03/2016

SAF-IND

Carl D. Wren

ChairCity of AustinDevelopment Services DepartmentOne Texas Center, Suite 200505 Barton Springs RoadAustin, TX 78704

E 10/6/2000SAF-IND

Kristin Bigda

Secretary (Staff-Nonvoting)National Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

6/29/2007

SAF-IND

Franco Dino Altoe

PrincipalDupontFire Protection Consultant4211 Tara CircleMarcus Hook, PA 19061

U 04/05/2016SAF-IND

Raymond E. Arntson

PrincipalRayden Research, LLC1041 - 174th StreetHammond, WI 54015

SE 7/12/2001

SAF-IND

Donald C. Birchler

PrincipalFP&C Consultants, Inc.3770 BroadwayKansas City, MO 64111Alternate: Jeffrey A. Scott

SE 1/1/1991SAF-IND

Ryan Cummings

PrincipalUS Department of TransportationFAA EOSH Services - AJW-231950 L’Efant Plaza SWSuite 300, Room 091Washington, DC 20591

E 10/29/2012

SAF-IND

Alberto Cusimano

PrincipalGeneral Electric (Switzerland) GmbH/ALSTOM Power Inc.Brown Boveri Strasse 7Baden, 5400 Switzerland

M 08/17/2015SAF-IND

Stephen E. Dale

PrincipalCincinnati Insurance Company6200 South Gilmore RoadFairfield, OH 45014-5141Alternate: Justin Yates

I 08/09/2012

SAF-IND

Nicholas A. Dawe

PrincipalCobb County Fire Marshal’s Office1595 County Services ParkwayMarietta, GA 30008

E 10/20/2010SAF-IND

John Desrosier

PrincipalTyco Fire Protection Products1467 Elmwood AvenueCranston, RI 02910American Fire Sprinkler AssociationAlternate: Roland J. Huggins

IM 04/05/2016

SAF-IND

Jeffry T. Dudley

PrincipalNational Aeronautics & Space Administration503 Glenbrook CircleRockledge, FL 32955

U 10/20/2010SAF-IND

Robert E. Hanson

PrincipalSavannah River Nuclear Solutions739 Turning Leaf CircleAugusta, GA 30909-6063Alternate: Thomas L. Allison

U 12/08/2015

1Page 2 of 75

Page 3: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Address List No PhoneIndustrial, Storage, and Miscellaneous Occupancies SAF-IND

Safety to Life

Kristin Bigda06/03/2016

SAF-IND

Jonathan Humble

PrincipalAmerican Iron and Steel Institute45 South Main Street, Suite 312West Hartford, CT 06107-2402Alternate: Farid Alfawakhiri

M 10/6/2000SAF-IND

Aaron Johnson

PrincipalRural/Metro CorporationSpecialty Fire Division @ Sikorsky Aircraft285 SW Ridgecrest DrivePort St. Lucie, FL 34953-8305

E 04/08/2015

SAF-IND

Adam C. Jones

PrincipalBuechel Fire Protection District4101 Bardstown RoadLouisville, KY 40218

E 10/29/2012SAF-IND

Marshall A. Klein

PrincipalMarshall A. Klein & Associates, Inc.6815 Autumn View DriveEldersburg, MD 21784-6304Automotive Aftermarket Industry AssociationAlternate: Andrew S. Klein

U 10/6/2000

SAF-IND

Jeffrey Klinkhardt

PrincipalKiewit9401 Renner BoulevardLenexa, KS 66219

SE 10/23/2013SAF-IND

Richard J. Kobelski

PrincipalHanford Fire DepartmentMission Support Alliance, MSIN S3-97PO Box 650Richland, WA 99352

U 10/28/2008

SAF-IND

Neal W. Krantz, Sr.

PrincipalKrantz Systems & Associates, LLC30126 BrettonLivonia, MI 48152Automatic Fire Alarm Association, Inc.

M 1/1/1991SAF-IND

Richard S. Kraus

PrincipalAPI/Petroleum Safety Consultants210 East Fairfax Street, Apt. 600Falls Church, VA 22046-2909American Petroleum Institute

U 7/16/2003

SAF-IND

Todd Laberge

PrincipalLawrence Berkeley National Laboratory1929 Huxley StreetSan Jose, CA 95125-5907

U 08/17/2015SAF-IND

Bruce Lecair

PrincipalNational Fire Sprinkler Association, Inc.25417 Hyacinth StreetCorona, CA 92883Alternate: Sheldon Dacus

M 08/09/2012

SAF-IND

Roberto Lozano-Rosales

PrincipalDelphi Corporation48 Walter Jones Blvd.Mail Station 799-30B-104AEl Paso, TX 79906NFPA Industrial Fire Protection Section

U 10/23/2003SAF-IND

Patrick A. McLaughlin

PrincipalMcLaughlin & Associates2070 South Fox Glen WayEagle, ID 83616Semiconductor Industry AssociationAlternate: Bobbie L. Smith

U 7/20/2000

SAF-IND

Jerald Pierrottie

PrincipalLonza Group Ltd.1717 North Woodland Forest DriveLake Charles, LA 70611-3754

M 7/23/2008SAF-IND

Scot Pruett

PrincipalBlack & Veatch Corporation11401 Lamar AvenueOverland Park, KS 66211-1508

SE 8/2/2010

2Page 3 of 75

Page 4: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Address List No PhoneIndustrial, Storage, and Miscellaneous Occupancies SAF-IND

Safety to Life

Kristin Bigda06/03/2016

SAF-IND

Jerrold Sameth

PrincipalCompressed Gas Association, Inc.290 DeMott AvenueClifton, NJ 07011-3749Compressed Gas AssociationAlternate: Richard A. Craig

M 07/29/2013SAF-IND

Steven A. Sheldon

PrincipalFisher Engineering, Inc.3707 East Southern AvenueMesa, AZ 85206Alternate: Katherine A. Pothier

SE 08/09/2012

SAF-IND

Cleveland B. Skinker

PrincipalBechtel Infrastructure and Power Corporation12011 Sunset Hills RoadReston, VA 20190Alternate: Kathryn M. Cifa

SE 1/15/2004SAF-IND

Bruce J. Swiecicki

PrincipalNational Propane Gas Association21200 South LaGrange Road, Suite 353Frankfort, IL 60423National Propane Gas Association

IM 7/16/2003

SAF-IND

John Vosicky

PrincipalSherwin Williams101 West Prospect AvenueCleveland, OH 44115-1075Alternate: David C. Tabar

U 04/05/2016SAF-IND

Michael S. White

PrincipalSiemens Building Technologies85 Pinehurst DriveGranville, OH 43023-9338National Electrical Manufacturers Association

M 08/17/2015

SAF-IND

Farid Alfawakhiri

AlternateAmerican Iron and Steel Institute380 Cottonwood LaneNaperville, IL 60540-5020Principal: Jonathan Humble

M 7/23/2008SAF-IND

Thomas L. Allison

AlternateSavannah River Nuclear SolutionsBuilding 722 5AAiken, SC 29802Principal: Robert E. Hanson

U 4/17/2002

SAF-IND

Kathryn M. Cifa

AlternateBechtel National, Inc.5275 Westview DriveFrederick, MD 21703Principal: Cleveland B. Skinker

SE 3/2/2010SAF-IND

Richard A. Craig

AlternateCompressed Gas Association14501 George Carter Way, Suite 103Chantilly, VA 20151Compressed Gas AssociationPrincipal: Jerrold Sameth

M 8/9/2011

SAF-IND

Sheldon Dacus

AlternateSecurity Fire Protection Company4495 Mendenhall RoadMemphis, TN 38141National Fire Sprinkler AssociationPrincipal: Bruce Lecair

M 12/08/2015SAF-IND

Roland J. Huggins

AlternateAmerican Fire Sprinkler Association, Inc.12750 Merit Drive, Suite 350Dallas, TX 75251-1273American Fire Sprinkler AssociationPrincipal: John Desrosier

IM 10/6/2000

3Page 4 of 75

Page 5: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Address List No PhoneIndustrial, Storage, and Miscellaneous Occupancies SAF-IND

Safety to Life

Kristin Bigda06/03/2016

SAF-IND

Andrew S. Klein

AlternateMarshall A. Klein & Associates, Inc.2 Rose CourtPasco, WA 99301Automotive Aftermarket Industry AssociationPrincipal: Marshall A. Klein

U 10/29/2012SAF-IND

Katherine A. Pothier

AlternateFisher Engineering, Inc.10475 Medlock Bridge Road, Suite 520Johns Creek, GA 30097Principal: Steven A. Sheldon

SE 08/09/2012

SAF-IND

Jeffrey A. Scott

AlternateFP&C Consultants, Inc.3770 BroadwayKansas City, MO 64111Principal: Donald C. Birchler

SE 3/2/2010SAF-IND

Bobbie L. Smith

AlternateMicron Technology, Inc.8000 South Federal WayBoise, ID 83707Semiconductor Industry AssociationPrincipal: Patrick A. McLaughlin

U 3/2/2010

SAF-IND

David C. Tabar

AlternateNorthern Risk LLC2807 Waterfall WayWestlake, OH 44145The Sherwin-Williams CompanyPrincipal: John Vosicky

U 1/18/2001SAF-IND

Justin Yates

AlternateCincinnati Insurance Company8300 Sapphire DriveAlexander, AR 72002-9288Principal: Stephen E. Dale

I 08/17/2015

SAF-IND

Kristin Bigda

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

6/29/2007

4Page 5 of 75

Page 6: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

MINUTES

NFPA Technical Committee on Industrial, Storage,

and Miscellaneous Occupancies

NFPA 101 and NFPA 5000 First Draft Meeting August 25-26, 2015

InterContinental Milwaukee

Milwaukee, WI

1. Call to order. The meeting was called to order by Chair Carl Wren at 8:00 a.m. CT on

August 25, 2015 at the InterContinental Milwaukee Hotel, Milwaukee, WI.

2. Self-introductions were made by Committee Members and Guests.

TECHNICAL COMMITTEE MEMBERS PRESENT

NAME COMPANY

Carl Wren, Chair City of Austin and Austin Fire Department

Donald Birchler, Principal FP&C Consultants, Inc.

Ryan Cummings, Principal US Department of Transportation

Stephen Dale, Principal Cincinnati Insurance Company

Nicholas Dawe, Principal Cobb County Fire Marshal’s Office

Jonathan Humble, Principal American Iron and Steel Institute

Aaron Johnson, Principal Rural/Metro Corporation

Marshall Klein, Principal Marshall A. Klein & Associates

Rep.: Auto Care Association

Jeffrey Klinkhardt, Principal Kiewit

Richard Kraus, Principal API/Petroleum Safety Consultants

Raymond Lonabaugh, Principal National Fire Sprinkler Association, Inc.

Roberto Lozano-Rosales, Principal Delphi Corporation

Rep.: NFPA Industrial Fire Protection Section

Patrick McLaughlin, Principal McLaughlin & Associates

Jerald Pierrottie, Principal Lonza Group, Ltd.

Scot Pruett, Principal Black & Veatch Corporation

Steven Sheldon, Principal Fisher Engineering Inc.

Thomas Allison, Voting Alternate Savannah River Nuclear Solutions

Marko Saric, Alt. D. Tabar The Sherwin-Williams Company

Justin Yates, Alt. to S. Dale Cincinnati Insurance Company

Kristin Bigda, NFPA Staff National Fire Protection Association

Page 6 of 75

Page 7: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

TECHNICAL COMMITTEE MEMBERS NOT PRESENT

NAME COMPANY

Raymond Arntson, Principal Rayden Research, LLC

Jeffry Dudley, Principal National Aeronautics & Space Administration

James Golinveaux, Principal Tyco Fire Protection Products

Rep: American Fire Sprinkler Association

Adam Jones, Principal Buechel Fire Protection District

Richard Kobelski, Principal Hanford Fire Department

Neal Krantz, Principal Krantz Systems & Associates, LLC

Rep.: Automatic Fire Alarm Association, Inc.

Leonard Ramo, Alt. to T. Bellamy Telgian Corporation

Jerrold Sameth, Principal Compressed Gas Association, Inc.

Rep.: Compressed Gas Association

Cleveland Skinker, Principal Bechtel Power Corporation

Bruce Swiecicki, Principal National Propane Gas Association

GUESTS

NAME COMPANY

Robert Hanson Savannah River Nuclear Solutions

Douglas Freels Oak Ridge National Lab

3. Approval of June 26, 2013 second draft meeting minutes. The June 26, 2013 meeting

minutes were approved as written and distributed

4. The process – staff PowerPoint presentation. Staff used the PowerPoint presentation

included in the agenda to discuss the First Draft phase of the new codes and standards

development process.

5. Correlating committee minutes with direction for 2018 editions. Staff provided

updates on the issues related to the Industrial, Storage, and Miscellaneous Occupancies

Committee as identified in the correlating committee minutes.

6. Core chapters, first revisions of interest. Staff reviewed the relevant core chapter first

revisions and the committee created their first revisions as necessary.

7. NFPA 101 First Draft preparation. All public inputs were addressed. Additional First

Revisions and Committee Inputs were developed as needed. See First Draft ballot

package and draft.

8. NFPA 5000 First Draft preparation. All public inputs were addressed. Additional

First Revisions and Committee Inputs were developed as needed. See First Draft ballot

package and draft.

9. Other business. The committee addressed the miscellaneous issues included in items 7-

through 13 of the agenda. First revisions were developed as necessary.

10. Future meetings. The Second Draft meeting will be held sometime between May 16 and

July 25, 2016 at a location to be determined.

Page 7 of 75

Page 8: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

11. Adjournment. The meeting was adjourned by Chair, Carl Wren, at 3:00 pm CT on

August 25, 2015.

Meeting Minutes Prepared By:

Kristin Bigda, NFPA Staff Liaison

Page 8 of 75

Page 9: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

1

© National Fire Protection Association. All rights reserved.

NFPA 101® & NFPA 5000 ®

Second Draft MeetingsOccupancy Chapter Committees

July 18-22, 2016 - Fort Lauderdale, Florida

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

At this and all NFPA committee meetings we are concerned with your safety.

If the fire alarm sounds, please proceed to an exit.

2

Page 9 of 75

Page 10: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

2

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

3

Members, please verify/update your contact information.

Use of visual or audio recording devices capable of reproducing verbatim transcriptions of this or any NFPA meeting is not permitted.

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Sign in and identify affiliations

Participation Requested 7 days prior to the meeting, or

At the discretion of the Chair

Guest chairs are located around the room

Equal opportunity granted to opposing views

4

Guests

Page 10 of 75

Page 11: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

3

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Members categorized in ANY interest category who have been retained to represent the interests of ANOTHER interest category (with respect to a specific issue or issues that are to be addressed by a TC/CC) shall declare those interests to the committee and refrain from voting on any Public Input, Comment, or other matter relating to those issues throughout the process.

5

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Follow Robert’s Rules of Order

Discussion requires a motion

6

General Procedures

Page 11 of 75

Page 12: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

4

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Not in order when another has the floor

Requires a second

This motion is not debatable and DOES NOT automatically stop debate

A 2/3 affirmative vote immediately closes debate and returns to the original motion on the floor

Fewer then 2/3 allows debate to continue

7

Motions for Ending Debate, Previous Question, or “Call the Question”

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Member addresses the chair

Receives recognition from the chair

Introduces the motion

Another member seconds the motion

8

Committee member actions

Page 12 of 75

Page 13: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

5

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft MeetingTimeline: Annual 2017 Revision Cycle

Comment Stage (Second Draft):Public Comment Closing Date: May 16, 2016Second Draft Meetings: June 20-23 and July 18-22, 2016Posting of Second Draft for Balloting Date: September 5, 2016Posting of Second Draft for NITMAM: January 16, 2017

Tech Session Preparation:NITMAM Closing Date: February 20, 2017NITMAM /CAM Posting Date: April 17, 2017NFPA Annual Meeting: June 4-7, 2017

Standards Council Issuance:Issuance of Documents with CAM: August 10, 2017

9

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Resolving Public Comments

Committee Action and Committee Statement

Creating Second Revisions

10

Technical Committee Actions

Page 13 of 75

Page 14: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

6

11

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Committee develops a Committee Action Accept

Reject but see…

Reject

Reject but Hold

(See Regs §4.4.8.1)

12

Resolving Public Comments

Page 14 of 75

Page 15: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

7

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Committee must clearly indicate reasons for not accepting the recommendation and/or point to a relevant Second Revision

All Public Comment actions must have a Committee Statement

Must include a valid technical reason

13

Committee Statements

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

No vague references to “intent”

Explain how the submitter’s substantiation is inadequate

Neither Public Comment actions nor Committee Statements get balloted

14

Committee Statements (continued)

Page 15 of 75

Page 16: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

8

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

No “new material” after the Public Input Stage since it is not subject to public review

What constitutes “new material” is decided by the TC or Correlating Committee

Adding “new material” at the Comments Stage could successfully be challenged through appeal to the NFPA Standards Council

15

New Material

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Voting during meeting is used to establish a sense of agreement (simple majority)

Secured by letter ballot (≥2/3 agreement)

Only the results of the formal ballot determine the official position of the committee on the Second Draft

16

Formal Voting

Page 16 of 75

Page 17: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

9

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Second Revisions (SRs) ONLY• Public Comment actions and Committee Statements not balloted

• Reference materials are available

Second Draft, Public Comments, First Draft Report

Allowed vote: • Affirmative on all SRs

• Affirmative on all SRs with exceptions specifically noted

Ballot form provides a column for affirmative with comment• Note: This box only needs to be checked if there is an accompanying comment

Reject or abstain requires a reason17

Ballots

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Initial ballot

Circulation of negatives and comments

Members may change votes during circulation

Second Revision that fails letter ballot is designated as a Committee Comment in the Second Draft Report, marked as “Reject,” and not included in the Second Draft

18

Circulation

Page 17 of 75

Page 18: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

10

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

• If a Second Revision fails ballot and the subject text was a result of a First Draft change, a Supplementary Ballot is issued

• Supplementary Ballot asks TC if it still favors the First Revision change reported in the First Draft

• If yes, same change appears as a Second Revision and is included in the Second Draft

• If no, the change appears as a Committee Comment and the text reverts to previous edition

• See Regs §4.4.10.2.119

Failed Second Revisions

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Ballots are issued and submitted online

Alternates are strongly encouraged to return ballots

Ballot session will time out after 90 minutes

Use “submit” button to save your work

20

Electronic Balloting

Page 18 of 75

Page 19: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

11

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

21

Click link on the ballot email

Sign in with NFPA.org Committee Login and Password

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

22

Select either ‘Affirmative All’ or ‘Affirmative with Exception(s)’

Page 19 of 75

Page 20: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

12

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

Use “See FR/SR - #” link to review all First/Second Revisions

Use “Edit election” to change individual votes or to modify vote after submitting ballot

23

nfpa.org | © National Fire Protection Association. All rights reserved.

NFPA Second Draft Meeting

24

To complete ballot click Participant Consent and Submit

Return and edit any votes before ballot due date.

Page 20 of 75

Page 21: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

13

nfpa.org | © National Fire Protection Association. All rights reserved.

Legal

25

Antitrust Matters

It is the policy of the NFPA to strictly comply with state and federal antitrust laws.

NFPA expects all participants in its standards development activities to conduct themselves in strict accordance with these laws.

It is the obligation of each participant to read and understand NFPA’s Antitrust Policy. (You can access this policy at nfpa.org/regs.)

nfpa.org | © National Fire Protection Association. All rights reserved.

Legal

26

Antitrust Matters (cont’d)

Participants must avoid any conduct, conversation or agreement that would constitute an unreasonable restraint of trade.Conversation topics that are off limits include:

•Profit, margin, or cost data;•Prices, rates, or fees;•Selection, division or allocation of sales territories, markets or customers;•Refusal to deal with a specific business entity.

Page 21 of 75

Page 22: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

14

nfpa.org | © National Fire Protection Association. All rights reserved.

Legal

27

Antitrust Matters (cont’d)NFPA’s standards development activities are based on openness, honesty, fairness and balance.Participants must adhere to the Regulations Governing the Development of NFPA Standards and the Guide for the Conduct of Participants in the NFPA Standards Development Process. (You can access the Regulations and Guideat nfpa.org/regs.)Follow guidance and direction from your employer or other organization you may represent.Be sure to ask questions if you have them.

nfpa.org | © National Fire Protection Association. All rights reserved.

Legal

28

Manner is which standards development activity is conducted can be important.The Guide requires standards development activity to be conducted with openness, honesty and in good faith.Participants are not entitled to speak on behalf of NFPA.Participants must take appropriate steps to ensure their statements whether written or oral and regardless of the setting, are portrayed as personal opinions, not the position of NFPA.Be sure to ask questions if you have them.

Antitrust Matters (cont’d)

Page 22 of 75

Page 23: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

15

nfpa.org | © National Fire Protection Association. All rights reserved.

Legal

29

Patents

Disclosures of essential patent claims should be made by the patent holder.Patent disclosures should be made early in the process.Others may also notify NFPA if they believe that a proposed or existing NFPA standard includes an essential patent claim.NFPA has adopted and follows ANSI’s Patent Policy. It is the obligation of each participant to read and understand NFPA’s Patent Policy. (You can access this policy at nfpa.org/regs.)

TC Struggles with an Issue

• TC needs data on a new technology or emerging issue

• Two opposing views on an issue with no real data

• Data presented is not trusted by committee

Code Fund Lends a Hand

• TC rep and/or staff liaison submits a Code Fund Request

• Requests are reviewed by a Panel and chosen based on need / feasibility

Research Project Carried Out

• Funding for project is provided by the Code Fund and/or industry sponsors

• Project is completed and data is available to TC

www.nfpa.org/codefund

Page 23 of 75

Page 24: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

16

About

• Document scope• Table of contents• Articles• Research and statistical

reports• Latest codes and

standards news on NFPA Today blog feed

• Free access

Current and Previous Editions

• Issued TIAs, FIs, Errata• Archived revision

information such as meeting and ballot information, First Draft Reports (previously ROPs), Second Draft Reports (previously ROCs), and Standards Council and NITMAM information

Next Edition

• Revision cycle schedule

• Posting & closing dates• Submit public

input/comments via electronic submission system.

• Meeting and ballot information

• First Draft Report and Second Draft Report

• NITMAM information• Standard Council

Decisions• Private TC info (*red

asterisk)• Ballot circulations,

informational ballots and other committee info

Technical Committee

• Committee name and staff liaison

• Committee scope and responsibility

• Committee list with private information

• Committee documents (codes & standards) in PDF format

• Committees seeking members

• Online committee membership application

Document Information Pages

nfpa.org | © National Fire Protection Association. All rights reserved.

Questions

Page 24 of 75

Page 25: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

NFPA 101 & NFPA 5000 Second Draft Meetings

17

nfpa.org | © National Fire Protection Association. All rights reserved.

Thank You

Page 25 of 75

Page 26: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 42-NFPA 101-2016 [ New Section after 7.2.1.5.3 ]

New Section

Additional Proposed Changes

File Name Description Approved

101_CCN_45.pdf 101 CC Note #45 ✓

Statement of Problem and Substantiation for Public Comment

NOTE: This Public Comment appeared as CC Note No. 45 in the First Draft Report. The Correlating Committee directs the occupancy committees (AXM, BCF, DET, END, RES, MER, IND, HEA) to review the additional door locking allowances that are being proposed in FCR-6.

This action will be considered as a public comment.

Related Item

Correlating Committee Note No. 45-NFPA 101-2016 [New Section after 7.2.1.5.3]

Submitter Information Verification

Submitter Full Name: CC ON SAF_AAC

Organization: NFPA CC ON SAFETY TO LIFE

Street Address:

City:

State:

Zip:

Submittal Date: Thu Mar 03 15:06:01 EST 2016

Copyright Assignment

I, CC ON SAF_AAC, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including boththe Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power andauthority to enter into this copyright assignment.

By checking this box I affirm that I am CC ON SAF_AAC, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. Iunderstand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 5/20/2016 1:08 PM

Page 26 of 75

Page 27: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Correlating Committee Note No. 45-NFPA 101-2016 [ New Section after 7.2.1.5.3 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:51:19 EST 2016

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee directs the occupancy committees (AXM, BCF, DET, END, RES, MER, IND, HEA) to review theadditional door locking allowances that are being proposed in FCR-6.

This action will be considered as a public comment.

Ballot Results

This item has passed ballot

11 Eligible Voters

0 Not Returned

11 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Affirmative All

Bush, Kenneth E.

Hopper, Howard

Hrustich, Stephen

Hugo, Jeffrey M.

Kalie, Jr., J. Edmund

Koffel, William E.

Pauls, Jake

Quiter, James R.

Reiswig, Rodger

Reynolds, Ronald C.

Rosenbaum, Eric R.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 3/2/2016 12:05 PM

Page 27 of 75

Page 28: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

First Correlating Revision No. 6-NFPA 101-2016 [ New Section after 7.2.1.5.10.6 ]

7.2.1.5.10.7

Two releasing operations shall be permitted for educational occupancy classroom doors secured against unwanted entry inaccordance with the provisions of Chapter 15 .

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 07:55:19 EST 2016

Committee Statement and Meeting Notes

Committee Statement: The new provision of 7.2.1.5.10.7 is needed so that the new provisions of 15.2.2.2.4 do not conflict with Chapter 7.

Ballot Results

This item has passed ballot

11 Eligible Voters

0 Not Returned

11 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Affirmative All

Bush, Kenneth E.

Hopper, Howard

Hrustich, Stephen

Hugo, Jeffrey M.

Kalie, Jr., J. Edmund

Koffel, William E.

Pauls, Jake

Quiter, James R.

Reiswig, Rodger

Reynolds, Ronald C.

Rosenbaum, Eric R.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 6/1/2016 9:17 AM

Page 28 of 75

Page 29: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 16-NFPA 101-2016 [ New Section after 9.13 ]

Add New Section after 9.13

Additional Proposed Changes

File Name Description Approved

101_CCN_16.pdf 101 CC Note #16 ✓

Statement of Problem and Substantiation for Public Comment

NOTE: This Public Comment appeared as CC Note No. 16 in the First Draft Report. The Correlating Committee directs the TC on Fundamentals (FUN) and the occupancy committees (AXM, END, HEA, BCF, RES, DET, MER, IND) to review the proposed change and determine if further changes are needed in the Code. The Correlating Committee will revisit the scope of the TC on Building Service and Fire Protection Equipment (BSF) after they propose any desired changes.

This action will be considered as a public comment.

Related Item

Correlating Committee Note No. 16-NFPA 101-2016 [New Section after 9.13]

Submitter Information Verification

Submitter Full Name: CC ON SAF_AAC

Organization: NFPA CC ON SAFETY TO LIFE

Street Address:

City:

State:

Zip:

Submittal Date: Thu Mar 03 09:37:17 EST 2016

Copyright Assignment

I, CC ON SAF_AAC, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including boththe Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power andauthority to enter into this copyright assignment.

By checking this box I affirm that I am CC ON SAF_AAC, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. Iunderstand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 5/20/2016 1:10 PM

Page 29 of 75

Page 30: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Correlating Committee Note No. 16-NFPA 101-2016 [ New Section after 9.13 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:26:18 EST 2016

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee directs the TC on Fundamentals (FUN) and the occupancy committees (AXM, END, HEA, BCF, RES,DET, MER, IND) to review the proposed change and determine if further changes are needed in the Code. The CorrelatingCommittee will revisit the scope of the TC on Building Service and Fire Protection Equipment (BSF) after they propose any desiredchanges.

This action will be considered as a public comment.

Ballot Results

This item has passed ballot

11 Eligible Voters

0 Not Returned

11 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Affirmative All

Bush, Kenneth E.

Hopper, Howard

Hrustich, Stephen

Hugo, Jeffrey M.

Kalie, Jr., J. Edmund

Koffel, William E.

Pauls, Jake

Quiter, James R.

Reiswig, Rodger

Reynolds, Ronald C.

Rosenbaum, Eric R.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 3/2/2016 12:34 PM

Page 30 of 75

Page 31: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

First Revision No. 1006-NFPA 101-2015 [ New Section after 9.13 ]

9.14 Risk Analysis for Mass Notification Systems.

9.14.1 Where Required.

Where required by Chapters 11 through 43 , a risk analysis for mass notification systems shall be provided in accordance with therequirements of NFPA 72 and the provisions of 9.14.2 through 9.14.4 .

9.14.2 Considerations.

The risk analysis required by 9.14.1 shall additionally address all of the following considerations:

(1) Fire and non-fire emergencies

(2) Specific nature and anticipated risks of each facility

(3) Characteristics of associated buildings, areas, spaces, campuses, equipment, and operations

9.14.3 Emergency Communications System.

An emergency communications system in accordance with NFPA 72 shall be provided where need for such is identified by the riskanalysis required by 9.14.1 , commensurate with the likelihood, vulnerability, magnitude, and potential consequences ofemergencies.

9.14.4 Emergency Action Plan.

The completed emergency action plan in accordance with Section 4.8 shall be used for the design of the massnotification/emergency communications system.

Submitter Information Verification

Submitter Full Name: SAF-BSF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 29 18:09:15 EDT 2015

Committee Statement and Meeting Notes

CommitteeStatement:

This first revision seeks to provide a requirement to conduct a risk analysis and create an emergency action plan for occupancieswhere required by Chapters 11-43. The need for effective emergency communications in the United States came into sharp focus inthe 20th century in response to threats to homeland security and our educational occupancies. We have learned from the recentincidents that occurred in our college/university campuses, and other buildings, and have created installation guidelines to befollowed for life safety. [Aurora, CO. Theater 2012; Columbine 1999; Virginia Tech 2007; Sandy Hook 2012; WeatherTornadoes/Storms]. //

The National Fire Protection Association (NFPA) School Safety, Codes and Security Workshop was held December 3–4, 2014 inCollege Park, Maryland, and was sponsored and hosted by NFPA. The resulting report highlights the need for real timecommunication systems in appropriate occupancies. //

NFPA 72, National Fire Alarm and Signaling Code, has a chapter dedicated to emergency communication systems. This containsthe detailed information on the risk analysis and emergency action plan as required in the above proposed sections. //

This is NOT intended to require a mass notification system. There are many elements contained within a mass notification system.The process of the risk analysis will outline what is needed based on risk and engineering study for the occupancy. It will be theresponsibility of the occupancy to react to the risk assessment. //

A task group has been appointed to further review the location of the proposed material in Ch. 9. The committee requests theCorrelating Committee review this action in conjunction with any related actions by the TC on Fundamentals and the occupancychapter committees to ensure the provisions are appropriately coordinated. The committee also requests the Correlating Committeereview the scope of the TC on Building Service and Fire Protection Equipment to recommend any needed changes to accommodatethe addition of the proposed language.

ResponseMessage:

Ballot Results

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 6/1/2016 9:19 AM

Page 31 of 75

Page 32: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

This item has passed ballot

28 Eligible Voters

5 Not Returned

22 Affirmative All

0 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Chen, Flora F.

Donga, Paul M.

Grill, Raymond A.

Noveh, James

Szmanda, Michael R.

Affirmative All

Bradley, Harry L.

Brinkman, Kevin L.

Brock, Pat D.

Dale, Stephen E.

Hagood, Claudia

Hammerberg, Thomas P.

Hugo, Jeffrey M.

Hutton, Claude O.

Jardin, Joseph M.

Kellett, Michael

Killian, David A.

Klepitch, David L.

Lazarz, Daniel J.

Moore, Wayne D.

Panowitz, Scott E.

Reiswig, Rodger

Roberts, Richard Jay

Ruchala, Kurt A.

Shudak, Lawrence J.

Warner, Todd W.

Wren, Carl D.

Wyatt, David M.

Negative with Comment

Larrimer, Peter A.

As written, this is not ready to be accepted in the Life Safety Code. The text has numerous problems.

Editorial Comment

Click here

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 6/1/2016 9:19 AM

Page 32 of 75

Page 33: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 18-NFPA 101-2016 [ Section No. 11.3.4 ]

11.3.4 Additional Requirements for Airport Traffic Control Towers.

11.3.4.1 Definition: — Airport Traffic Control Tower.

See 3.3.291.1.

11.3.4.2 Use of Accessory Levels.

The levels located below the observation level shall be permitted to be occupied only for the following:

(1) Uses that support tower operations, such as electrical and mechanical equipment rooms, including emergency and standbypower, radar, communications, and electronics rooms

(2)

(3) Other approved existing airport traffic control tower uses

11.3.4.3 Minimum Construction Requirements.

New airport traffic control towers shall be of Type I or Type II construction. (See 8.2.1.)

11.3.4.4 Means of Egress.

11.3.4.4.1* Number of Means of Egress.

Airport traffic control towers shall be permitted to have a single exit, provided that all the following conditions are met in addition to therequirements of 11.3.2.4:

(1) Each level of new airport traffic control towers, served by a single exit, shall be subject to a calculated occupant load of 15 orfewer persons.

(2) The requirements of 11.3.4.4.1(1) shall not apply to existing airport traffic control towers.

(3) A fire alarm system shall be provided in accordance with Section 9.6. Smoke detection shall be provided throughout airporttraffic control towers to meet the requirements of partial coverage, as defined in 17.5.3.2 of NFPA 72 and shall include coverageof all of the following:

(4) Observation level

Means of egress

(a) Common areas

(b) All equipment rooms

(c) Incidental accessory uses

(d) Accessible utility shafts

(5) The requirements of 11.3.2.4.1(5) shall not apply.

(6) Rooms or spaces used for the storage, processing, or use of combustible supplies shall be permitted in quantities deemedacceptable by the authority having jurisdiction.

(7) Smokeproof exit enclosures shall be provided in accordance with 7.2.3.

11.3.4.4.2 Remoteness.

Where an airport traffic control tower is equipped throughout with an approved, supervised automatic sprinkler system in accordancewith Section 9.7, the minimum separation distance between two exits, or exit accesses, measured in accordance with 7.5.1.3.2 shallbe not less than one-fourth of the length of the maximum overall diagonal dimension of the building or area to be served.

11.3.4.4.3 Accessible Means of Egress.

Accessible means of egress shall not be required to serve the observation level and the floor immediately below the observation levelin airport traffic control towers.

11.3.4.4.4 Egress for Occupant Load.

Means of egress for airport traffic control towers shall be provided for the occupant load, as determined in accordance with 7.3.1.

11.3.4.4.5 Areas Excluded from Occupant Load.

Shafts, stairs, spaces, and floors not subject to human occupancy shall be excluded from consideration in determining the totalcalculated occupant load of the tower, as required by 11.3.2.4.1(1) and 11.3.4.4.1(1).

11.3.4.4.6 Single Means of Egress.

A single means of egress shall be permitted from the observation level of an airport traffic control tower to an exit, as permitted by11.3.2.4.2.

* Incidental accessory uses that support tower operations

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 259 5/17/2016 9:43 AM

Page 33 of 75

Page 34: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

11.3.4.4.7 Smokeproof Enclosures.

For other than approved existingairport traffic control towers, smokeproof exit enclosures complying with 7.2.3 shall be provided forall airport traffic control tower exit enclosures.

11.3.4.4.8 Discharge from Exits.

11.3.4.4.8.1

Airport traffic control towers shall comply with the requirements of 7.7.2, except as permitted by 11.3.4.4.8.2.

11.3.4.4.8.2

Existing, single-exit airport traffic control towers shall be permitted to have discharge of the exit comply with one of the following:

(1) Discharge of the exit in an approved existing, single-exit airport traffic control tower is permitted to a vestibule or foyer complyingwith the requirements of 7.7.2(4) (b).

(2)

11.3.4.5 Protection.

11.3.4.5.1 Detection, Alarm, and Communications Systems.

For other than approved existing, airport traffic control towers, airport traffic control towers shall be provided with a fire alarm systemin accordance with Section 9.6. Smoke detection shall be provided throughout the airport traffic control tower to meet therequirements for partial coverage, as defined in 17.5.3.2 of NFPA 72, and shall include coverage of all of the following:

(1) All equipment rooms

(2) Observation level

(3) Outside each opening into exit enclosures

(4) Along the single means of egress permitted from observation levels in 11.3.2.4.2

(5) Outside each opening into the single means of egress permitted from observation levels in 11.3.2.4.2

11.3.4.5.2 Extinguishing Requirements.

New airport traffic control towers shall be protected throughout by an approved, supervised automatic sprinkler system in accordancewith Section 9.7.

11.3.4.5.3 Standpipe Requirements.

New airport traffic control towers where the floor of the observation level is greater than 30 ft (9.1 m) above the lowest level of firedepartment vehicle access shall be protected throughout with a Class I standpipe system in accordance with Section 9.7. Class Istandpipes shall be manual standpipes as defined in NFPA 14 where permitted by the authority having jurisdiction.

11.3.4.6 Contents and Furnishings.

Contents and furnishings in airport traffic control towers shall comply with 10.3.1, 10.3.2, 10.3.6, and 10.3.7.

11.3.4.7 Uses.

Sleeping areas shall be prohibited in airport traffic control towers.

11.3.4.8 Emergency Command Center.

11.3.4.8.1

In other than approved existing airport traffic control towers, an emergency command center shall be provided in a location approvedby the fire department where the floor of an occupiable story is greater than 75 ft (23 m) above the lowest level of fire departmentvehicle access. The emergency command center is shall be permitted to be located in the airport traffic control tower or an adjacentcontiguous building where building functions are interdependent.

* Discharge of the exit in a single-exit airport traffic control tower is permitted within the building to a location where two meansof egress are available and are arranged to allow travel in independent directions after leaving the exit enclosure, so that bothmeans of egress do not become compromised by the same fire or similar emergency.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 259 5/17/2016 9:43 AM

Page 34 of 75

Page 35: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

11.3.4.8.2

The emergency command center shall contain the following:

(1) Fire department two-way telephone communication service panels and controls

(2) Fire detection and fire alarm system control unit and annunciator

(3) Elevator floor location and operation annunciators

(4) Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators

(5) Controls and annunciators for systems supporting smokeproof enclosures

(6) Sprinkler valve and waterflow annunciators

(7) Emergency generator status indicators

(8) Schematic building plans indicating a typical floor plan and detailing the building core, means of egress, fire protection systems,fire-fighting equipment, and fire department access as well as the locations of fire walls, fire barriers, fire partitions, smokebarriers- and smoke partitions.

(9) Fire pump status indicators

(10) Telephone for fire department use with controlled access to the public telephone system

(11) An approved building information card that contains, but is not limited to, the following information:

(a) General building information that includes property name, address, the number of floors in the building (above and belowgrade), use and occupancy classification (for mixed uses, identify the different types of occupancies on each floor),estimated building population (i.e., day, night, weekend)

(b) Building emergency contact information that includes a list of the building's emergency contacts (e.g., building manager,building engineer, etc.) and their respective work phone numbers, cell phone numbers, and email addresses

(c) Building construction information that includes the type of building construction (e.g., floors, walls, columns, and roofassembly)

(d) Exit stair information that includes number of exit stairs in the building, each exit stair designation and floors served,location where each exit stair discharges, exit stairs that are pressurized, exit stairs provided with emergency lighting, eachexit stair that allows reentry, and exit stairs providing roof access

(e) Elevator information that includes the number of elevator banks, elevator bank designation, elevator car numbers andrespective floors that they serve, location of elevator machine rooms, location of sky lobby, and location of freight elevatorbanks

(f) Building services and system information that includes the location of mechanical rooms, location of building managementsystem, location and capacity of all fuel oil tanks, location of emergency generator, and location of natural gas service

(g) Fire protection system information that includes locations of standpipes, location of fire pump room, location of firedepartment connections, floors protected by automatic sprinklers, location of different types of sprinkler systems installed(e.g., dry, wet, pre-action)

(h) Hazardous material information that includes location of hazardous material and quantity of hazardous material

(12) Worktable

11.3.4.9 Emergency Action Plans and Fire Drills.

11.3.4.9.1

All airport traffic control towers shall have written copies of an emergency action plan as required by Section 4.8.

11.3.4.9.2

Fire drills shall be conducted such that all employees participate at least once annually in accordance with Section 4.7.

11.3.4.9.3

Employees of airport traffic control towers shall be instructed at least annually in the emergency action plan.

11.3.4.9.4

The emergency action plan shall be updated at least annually.

Additional Proposed Changes

File Name Description Approved

101_CCN_18.pdf 101 CC Note No. 18

Statement of Problem and Substantiation for Public Comment

NOTE: This Public Comment appeared as CC Note No. 18 in the First Draft Report. The Correlating Committee directs the TC on Industrial and Storage Occupancies (IND) to do the following:

1. Consider the Affirmative with Comment ballot of Allison to add the word “such” to 11.3.4.2(1) so as to read: “Uses that support tower operations, such as electrical…”

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 259 5/17/2016 9:43 AM

Page 35 of 75

Page 36: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

2. Revise 11.3.4.4.1(3)(b) from “Means of egress” to the former term “Common areas” or something else that is definitive as“means of egress” includes ALL spaces where an occupant can be present.

3. Revise 11.3.4.4.2 to insert the word “diagonal” to read “…maximum overall diagonal dimension…”

4. Revise second sentence of 11.3.4.8.1 to change “is permitted’ to “shall be permitted” to read: “The emergency command center shall be permitted to be located…”

These actions will be considered as a public comment.

Related Item

Correlating Committee Note No. 18-NFPA 101-2016 [Section No. 11.3.4]

Submitter Information Verification

Submitter Full Name: CC ON SAF_AAC

Organization: NFPA CC ON SAFETY TO LIFE

Street Address:

City:

State:

Zip:

Submittal Date: Thu Mar 03 09:48:42 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 259 5/17/2016 9:43 AM

Page 36 of 75

Page 37: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Correlating Committee Note No. 18-NFPA 101-2016 [ Section No. 11.3.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:45:31 EST 2016

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee directs the TC on Industrial and Storage Occupancies (IND) to do the following:

1. Consider the Affirmative with Comment ballot of Allison to add the word “such” to 11.3.4.2(1) so as to read: “Uses thatsupport tower operations, such as electrical…”

2. Revise 11.3.4.4.1(3)(b) from “Means of egress” to the former term “Common areas” or something else that is definitive as“means of egress” includes ALL spaces where an occupant can be present.

3. Revise 11.3.4.4.2 to insert the word “diagonal” to read “…maximum overall diagonal dimension…”

4. Revise second sentence of 11.3.4.8.1 to change “is permitted’ to “shall be permitted” to read: “The emergency commandcenter shall be permitted to be located…”

These actions will be considered as a public comment.

Ballot Results

This item has passed ballot

11 Eligible Voters

0 Not Returned

11 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Affirmative All

Bush, Kenneth E.

Hopper, Howard

Hrustich, Stephen

Hugo, Jeffrey M.

Kalie, Jr., J. Edmund

Koffel, William E.

Pauls, Jake

Quiter, James R.

Reiswig, Rodger

Reynolds, Ronald C.

Rosenbaum, Eric R.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 3/2/2016 12:39 PM

Page 37 of 75

Page 38: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

First Revision No. 4012-NFPA 101-2015 [ Section No. 11.3.4 ]

Global FR-3006

11.3.4 Additional Requirements for Air Airport Traffic Control Towers.

11.3.4.1 Definition : — Air Airport Traffic Control Tower.

See 3.3.285.1 .

11.3.4.2 Use of Accessory Levels.

The levels located below the observation level shall be permitted to be occupied only for the following uses that support toweroperations :

(1) Use s that support tower operations as electrical and mechanical equipment rooms, including emergency and standby power,radar, communications, and electronics rooms

(2)

(3) Other approved existing airport traffic control tower uses

11.3.4.3 Minimum Construction Requirements.

New air airport traffic control towers shall be of Type I or Type II construction. (See 8.2.1 .)

11.3.4.4 Means of Egress.

11.3.4.4.1* Number of Means of Egress.

Air Airport traffic control towers shall be permitted to have a single exit, provided that all the following conditions are met in addition tothe requirements of 11.3.2.4 :

(1) Each level of new air airport traffic control towers, served by a single exit, shall be subject to a calculated occupant load of 15 orfewer persons.

(2) The requirements of 11.3.4.4.1(1) shall not apply to existing air airport traffic control towers.

(3) A fire alarm system shall be provided in accordance with Section 9.6 . Smoke detection shall be provided throughout air airporttraffic control towers to meet the requirements of partial coverage, as defined in 17.5.3.2 of NFPA 72 , National Fire Alarm andSignaling Code , and shall include coverage of all of the following:

(a) Occupiable areas Observation level

(b) Common areas Means of egress

(c) Work spaces All equipment rooms

(d) Equipment areas Incidental accessory uses

(e) Means of egress Accessible utility shafts

Accessible utility shafts

(4) The requirements of 11.3.2.4.1(5) shall not apply.

(5) Rooms or spaces used for the storage, processing, or use of combustible supplies shall be permitted in quantities deemedacceptable by the authority having jurisdiction.

(6) Smokeproof exit enclosures shall be provided in accordance with 7.2.3 .

11.3.4.4.2 Remoteness.

Where an airport traffic control tower is equipped throughout with an approved, supervised automatic sprinkler system in accordancewith Section 9.7 , the minimum separation distance between two exits, or exit accesses, measured in accordance with 7.5.1.3.2 shallbe not less than one-fourth of the length of the maximum overall dimension of the building or area to be served.

11.3.4.4.3 Accessible Means of Egress.

Accessible means of egress shall not be required to serve the observation level and the floor immediately below the observation level inairport traffic control towers.

11.3.4.4.4 Egress for Occupant Load.

Means of egress for air airport traffic control towers shall be provided for the occupant load, as determined in accordance with 7.3.1 .

11.3.4.4.5 Areas Excluded from Occupant Load.

Shafts, stairs, and spaces, and floors not subject to human occupancy shall be excluded from consideration in determining the totalcalculated occupant load of the tower , as required by 11.3.2.4.1(1) and 11.3.4.4.1(1) .

* Incidental accessory uses that support tower operations

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 7 6/1/2016 11:28 AM

Page 38 of 75

Page 39: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

11.3.4.4.6 Single Means of Egress.

A single means of egress shall be permitted from the observation level of an air airport traffic control tower to an exit , as permitted by11.3.2.4.2 .

11.3.4.4.7 Smokeproof Enclosures.

For other than existing, previously approved existing air airport traffic control towers, smokeproof exit enclosures complying with 7.2.3shall be provided for all air airport traffic control tower exit stair enclosures.

11.3.4.4.8 Discharge from Exits.

11.3.4.4.8.1

Air Airport traffic control towers shall comply with the requirements of 7.7.2 , except as permitted by 11.3.4.4.8.2 .

11.3.4.4.8.2

Existing, single-exit air airport traffic control towers shall be permitted to have discharge of the exit comply with one of the following:

(1) Discharge of the exit in a previously an approved existing , single-exit air airport traffic control tower is permitted to a vestibule orfoyer complying with the requirements of 7.7.2(4) (b).

(2)

Global FR-3006

11.3.4.5 Protection.

11.3.4.5.1 Detection, Alarm, and Communications Systems.

For other than existing, previously approved existing, air airport traffic control towers, air airport traffic control towers shall be providedwith a fire alarm system in accordance with Section 9.6 . Smoke detection shall be provided throughout the air airport traffic controltower to meet the requirements for selective partial coverage, as defined in 17.5.3.2 of NFPA 72 , National Fire Alarm and SignalingCode , and shall include coverage of all of the following:

(1) At All equipment areas rooms

(2) Observation level

(3) Outside each opening into exit enclosures

(4) Along the single means of egress permitted from observation levels in 11.3.2.4.2

(5) Outside each opening into the single means of egress permitted from observation levels in 11.3.2.4.2

11.3.4.5.2 Extinguishing Requirements.

New air airport traffic control towers shall be protected throughout by an approved, supervised automatic sprinkler system inaccordance with Section 9.7 .

11.3.4.5.3 Standpipe Requirements.

New air airport traffic control towers where the floor of the cab observation level is greater than 30 ft (9.1 m) above the lowest level offire department vehicle access shall be protected throughout with a Class I standpipe system in accordance with Section 9.7 . Class Istandpipes shall be manual standpipes as defined in NFPA 14 , Standard for the Installation of Standpipe and Hose Systems , wherepermitted by the authority having jurisdiction.

11.3.4.6 Contents and Furnishings.

Contents and furnishings in air airport traffic control towers shall comply with 10.3.1 , 10.3.2 , 10.3.6 , and 10.3.7 .

11.3.4.7 Uses.

Sleeping areas shall be prohibited in air airport traffic control towers.

11.3.4.8 Emergency Command Center.

11.3.4.8.1

In other than approved existing airport traffic control towers, an emergency command center shall be provided in a location approved bythe fire department where the floor of an occupiable story is greater than 75 ft (23 m) above the lowest level of fire department vehicleaccess. The emergency command center is permitted to be located in the airport traffic control tower or an adjacent contiguous buildingwhere building functions are interdependent.

* Discharge of the exit in a single-exit air airport traffic control tower is permitted within the building to a location where two meansof egress are available and are arranged to allow travel in independent directions after leaving the exit enclosure, so that bothmeans of egress do not become compromised by the same fire or similar emergency.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 7 6/1/2016 11:28 AM

Page 39 of 75

Page 40: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

11.3.4.8.2

The emergency command center shall contain the following:

(1) Fire department two-way telephone communication service panels and controls

(2) Fire detection and fire alarm system control unit and annunciator

(3) Elevator floor location and operation annunciators

(4) Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators

(5) Controls and annunciators for systems supporting smokeproof enclosures

(6) Sprinkler valve and waterflow annunciators

(7) Emergency generator status indicators

(8) Schematic building plans indicating a typical floor plan and detailing the building core, means of egress, fire protection systems,fire-fighting equipment, and fire department access as well as the locations of fire walls, fire barriers, fire partitions, smoke barriers-and smoke partitions.

(9) Fire pump status indicators

(10) Telephone for fire department use with controlled access to the public telephone system

(11) An approved building information card that contains, but is not limited to, the following information:

(a) General building information that includes property name, address, the number of floors in the building (above and belowgrade), use and occupancy classification (for mixed uses, identify the different types of occupancies on each floor), estimatedbuilding population (i.e., day, night, weekend)

(b) Building emergency contact information that includes a list of the building's emergency contacts (e.g., building manager,building engineer, etc.) and their respective work phone numbers, cell phone numbers, and email addresses

(c) Building construction information that includes the type of building construction (e.g., floors, walls, columns, and roofassembly)

(d) Exit stair information that includes number of exit stairs in the building, each exit stair designation and floors served, locationwhere each exit stair discharges, exit stairs that are pressurized, exit stairs provided with emergency lighting, each exit stairthat allows reentry, and exit stairs providing roof access

(e) Elevator information that includes the number of elevator banks, elevator bank designation, elevator car numbers andrespective floors that they serve, location of elevator machine rooms, location of sky lobby, and location of freight elevatorbanks

(f) Building services and system information that includes the location of mechanical rooms, location of building managementsystem, location and capacity of all fuel oil tanks, location of emergency generator, and location of natural gas service

(g) Fire protection system information that includes locations of standpipes, location of fire pump room, location of firedepartment connections, floors protected by automatic sprinklers, location of different types of sprinkler systems installed(e.g., dry, wet, pre-action)

(h) Hazardous material information that includes location of hazardous material and quantity of hazardous material

(12) Worktable

Global FR-3006

11.3.4.9 Emergency Action Plans and Fire Drills.

11.3.4.9.1

All airport traffic control towers shall have written copies of an emergency action plan as required by Section 4.8 .

11.3.4.9.2

Fire drills shall be conducted such that all employees participate at least once annually in accordance with Section 4.7 .

11.3.4.9.3

Employees of airport traffic control towers shall be instructed at least annually in the emergency action plan.

11.3.4.9.4

The emergency action plan shall be updated at least annually.

11.3.4.8 Emergency Command Center.

11.3.4.8.1

In other than approved existing airport traffic control towers, an emergency command center shall be provided in a location approvedby the fire department where the floor of an occupiable story is greater than 75 ft (23 m) above the lowest level of fire departmentvehicle access. The emergency command center is permitted to be located in the airport traffic control tower or an adjacent contiguousbuilding where building functions are interdependent.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

3 of 7 6/1/2016 11:28 AM

Page 40 of 75

Page 41: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

11.3.4.8.2

The emergency command center shall contain the following:

(1) Fire department two-way telephone communication service panels and controls

(2) Fire detection and fire alarm system control unit and annunciator

(3) Elevator floor location and operation annunciators

(4) Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators

(5) Controls and annunciators for systems supporting smokeproof enclosures

(6) Sprinkler valve and waterflow annunciators

(7) Emergency generator status indicators

(8) Schematic building plans indicating a typical floor plan and detailing the building core, means of egress, fire protection systems,fire-fighting equipment, and fire department access as well as the locations of fire walls, fire barriers, fire partitions, smokebarriers- and smoke partitions.

(9) Fire pump status indicators

(10) Telephone for fire department use with controlled access to the public telephone system

(11) An approved building information card that contains, but is not limited to, the following information:

(a) General building information that includes property name, address, the number of floors in the building (above and belowgrade), use and occupancy classification (for mixed uses, identify the different types of occupancies on each floor),estimated building population (i.e., day, night, weekend)

(b) Building emergency contact information that includes a list of the building's emergency contacts (e.g., building manager,building engineer, etc.) and their respective work phone numbers, cell phone numbers, and email addresses

(c) Building construction information that includes the type of building construction (e.g., floors, walls, columns, and roofassembly)

(d) Exit stair information that includes number of exit stairs in the building, each exit stair designation and floors served,location where each exit stair discharges, exit stairs that are pressurized, exit stairs provided with emergency lighting, eachexit stair that allows reentry, and exit stairs providing roof access

(e) Elevator information that includes the number of elevator banks, elevator bank designation, elevator car numbers andrespective floors that they serve, location of elevator machine rooms, location of sky lobby, and location of freight elevatorbanks

(f) Building services and system information that includes the location of mechanical rooms, location of building managementsystem, location and capacity of all fuel oil tanks, location of emergency generator, and location of natural gas service

(g) Fire protection system information that includes locations of standpipes, location of fire pump room, location of firedepartment connections, floors protected by automatic sprinklers, location of different types of sprinkler systems installed(e.g., dry, wet, pre-action)

(h) Hazardous material information that includes location of hazardous material and quantity of hazardous material

(12) Worktable

Supplemental Information

File Name Description

11.3.4_ATCT.docx For staff use only.

A.11.3.4.4.1.docx

Submitter Information Verification

Submitter Full Name: SAF-IND

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 25 12:36:38 EDT 2015

Committee Statement and Meeting Notes

CommitteeStatement:

All of the proposed changes are the recommendation of the Airport Traffic Control Tower Fire Life Safety Task Group, and reflect thecurrent approach to fire protection and life safety in airport traffic control towers (ATCT). The fire safety criteria applicable to ATCTsare originally based on an agreement between the operator of and controllers utilizing the ATCTs. Many of the changes relate toproviding extra protection for the controllers and fire service.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

4 of 7 6/1/2016 11:28 AM

Page 41 of 75

Page 42: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

ATCTs create a unique hazard. ATCTs typically have a limited number of occupants. In addition, occupants must be awake and alert.The hazard associated with ATCTs is affected by the building’s limited uses, height, and the potential delay in evacuation because ofthe handoff of flights.

The occupied levels of an ATCT are typically located at the top of the structure that typically contains support equipment and servicesbut has limited occupancy. In addition, the area of ATCTs has been increasing, even though the number of floors located on top of theshaft is still typically limited.

The terminology “previously approved” has been edited to “approved existing” which is the defined term which is the intent of thecriteria.

Section 11.3.4.2 is proposed to exclude existing uses in ATCTs that have been previously approved by the AHJ. Existing ATCTscontain uses that may not directly support ATCT operations however have been previously approved.

Section 11.3.4.4.1(3) is proposed to clarify the spaces that require automatic smoke detection where a single means of egress isprovided and that a fire alarm system is required to be provided. The majority of spaces in single exit towers would require detectionto provide an enhanced level of detection. The terminology is revised to provide consistency with Section 11.3.4.5.1.

Section 11.3.4.4.1(6) is proposed to require smoke proof enclosures for all single exit ATCTs, regardless of previous approval, toprovide an additional level of safety in occupancies where delayed evacuations are likely.

Section 11.3.4.4.2: ATCTs typically have a limited number of occupants. In addition, occupants must be awake and alert. The hazardassociated with ATCTs is affected by the building’s limited uses, size and height. The occupied levels of an ATCT are located at thetop of the structure that typically contains support equipment and services but has limited occupancy. The lower levels of the ATCTare typically limited in size with the upper levels are larger in size. This means that towards the upper floors of the building where thestructure flares out the diagonal distance of the building increases. This flared space is used for equipment that serves air trafficcontrol. Architectural analysis has shown that meeting the 1/3 diagonal distance separation requirement is possible by routing accessto one of the two means of egress through an equipment room. It is this task group’s judgment that an arrangement routing egressthough an equipment room creates a larger risk then reducing the diagonal separation requirement. The limited area and layout of thenormally unoccupied lower levels can make separation of the exit access by 1/3 of the diagonal of the floor plan difficult. This revisionreduces the required separation distance of multiple exit ATCTs in ATCTs that are typically low in occupancy and size.

Section 11.3.4.4.3: The proposed change is the recommendation of the Airport Traffic Control Tower Fire Life Safety Task Group, andreflect the current approach to fire protection and life safety in airport traffic control towers (ATCT). This change provides consistencywith the typical building practices for airport traffic control towers.

Section 11.3.4.4.6 is proposed to clarify the intent of the requirement that the travel distance limit is to the entrance of the exit and notthe exit discharge.

Section 11.3.4.4.7 is proposed to require smoke proof enclosures for all exit enclosures. While stairs are the primary means of egressprovided for ATCTs, this change provides protection for all exits due to the potential for delayed evacuation of tower operators.

Section 11.3.4.5.1 is proposed to provide consistent terminology with Section 11.3.4.4.1 as well as require smoke detection in theobservation level of all air traffic control towers regardless of the number of exits provided.

Section 11.3.4.5.3 is proposed to provide consistent terminology with the rest of the air traffic control tower section.

Section 11.3.4.8 is proposed to provide a control location for fire fighter operations due to the unique aspects of fighting fires inATCTs. It is proposed that the emergency command center be located in either the tower footprint or the adjacent base building(where provided). The base building supports the tower operations and is built contiguous to the ATCT. Requirements were takenfrom Section 11.8.6 with a few exceptions. The voice fire alarm system controls were removed as ATCTs are not provided with voicesystems. The fire alarm control unit would be located in the fire command center and provide status indicators for all associatedsystems. The requirement for elevator power selector switches was removed as ATCTs are typically designed with a single elevator.Controls for stairway door unlocking systems and video monitoring were not included as ATCTs are located in areas with restrictedaccess.

Section 11.3.4.9 is proposed to provide a regular requirement for emergency training for air traffic control tower operators. In theevent of an emergency, operators are potentially not able to immediately egress due to the necessity of handing off flights to otherlocations. Requiring regular training on the steps to take in the event of an emergency provides benefit to the controllers and thegeneral public.

ResponseMessage:

Committee Notes:

Date Submitted By

Sep 2, 2015 Kristin Bigda see attached word document for changes. with some changes being made to lists Terra was not displaying correctly.

Public Input No. 174-NFPA 101-2015 [New Section after A.11.3.4.2(2)]

Public Input No. 403-NFPA 101-2015 [Section No. 11.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

5 of 7 6/1/2016 11:28 AM

Page 42 of 75

Page 43: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Ballot Results

This item has passed ballot

30 Eligible Voters

1 Not Returned

26 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

1 Abstention

Not Returned

Jones, Adam C.

Affirmative All

Arntson, Raymond E.

Birchler, Donald C.

Cummings, Ryan

Cusimano, Alberto

Dale, Stephen E.

Dawe, Nicholas A.

Dudley, Jeffry T.

Golinveaux, James E.

Humble, Jonathan

Johnson, Aaron

Klein, Marshall A.

Klinkhardt, Jeffrey

Kobelski, Richard J.

Krantz, Sr., Neal W.

Kraus, Richard S.

Laberge, Todd

Lonabaugh, Raymond W.

Lozano-Rosales, Roberto

McLaughlin, Patrick A.

Pierrottie, Jerald

Saric, Jr., Marko J.

Sheldon, Steven A.

Skinker, Cleveland B.

Swiecicki, Bruce J.

White, Michael S.

Wren, Carl D.

Affirmative with Comment

Allison, Thomas L.

The change in 11.3.4.2 (1) is missing a word. It should say, "Uses that support tower operations, such as electrical and mechanical equipmentrooms, including emergency and standby power, radar, communications, and electronics rooms

Pruett, Scot

With the exception of FR-4009 text

Abstention

Sameth, Jerrold

CGA did not develop a consensus position.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

6 of 7 6/1/2016 11:28 AM

Page 43 of 75

Page 44: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Editorial Comment

Click here

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

7 of 7 6/1/2016 11:28 AM

Page 44 of 75

Page 45: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 122-NFPA 101-2016 [ Section No. 11.3.4.2 ]

11.3.4.2 Use of Accessory Levels.

The levels located below the observation level shall be permitted to be occupied only for the following:

(1) Uses that support tower operations such as electrical and mechanical equipment rooms, including emergency and standbypower, radar, communications, and electronics rooms

(2)

(3) Other approved existing airport traffic control tower uses

Statement of Problem and Substantiation for Public Comment

Editorial correction from the first draft proposal.

Related Item

Public Input No. 403-NFPA 101-2015 [Section No. 11.3.4]

First Revision No. 4012-NFPA 101-2015 [Section No. 11.3.4]

Submitter Information Verification

Submitter Full Name: Eric Rosenbaum

Organization: Jensen Hughes

Affilliation: Airport Traffic Control Tower Fire Life Safety Task Group

Street Address:

City:

State:

Zip:

Submittal Date: Thu May 05 10:57:20 EDT 2016

* Incidental accessory uses that support tower operations

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 259 5/17/2016 9:43 AM

Page 45 of 75

Page 46: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 220-NFPA 101-2016 [ Section No. 11.3.4.8.1 ]

11.3.4.8.1

In other than approved existing airport traffic control towers, an emergency command center shall be provided in a location approvedby the fire department where the floor of an occupiable story is greater than 75 ft (23 m) above the lowest level of fire departmentvehicle access. The emergency command center is shall be permitted to be located in the airport traffic control tower or an adjacentcontiguous building where building functions are interdependent.

Statement of Problem and Substantiation for Public Comment

The language was revised based on the technical committee recommendation.

Related Item

Public Input No. 403-NFPA 101-2015 [Section No. 11.3.4]

Submitter Information Verification

Submitter Full Name: Eric Rosenbaum

Organization: Jensen Hughes

Affilliation: Airport Traffic Control Tower Fire Life Safety Task Group

Street Address:

City:

State:

Zip:

Submittal Date: Mon May 16 22:31:58 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 259 5/17/2016 9:43 AM

Page 46 of 75

Page 47: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 112-NFPA 101-2016 [ Section No. 40.1.2.1.3 ]

40.1.2.1.3 * High-Hazard Industrial Occupancy.

High-hazard industrial occupancies shall include all of the following:

(1) Industrial Existing industrial occupancies that conduct industrial operations that use, process, store, or handle high-hazardcontents, as defined by 6.2.2.4

(2) New i ndustrial occupancies that conduct industrial operations that use, process, store, or handle high-hazard contents orhazardous materials in excess of the maximum allowable quantities (MAQ) as permitted by the fire code

(3) Industrial occupancies in which incidental high-hazard operations in low- or ordinary-hazard occupancies that are protected inaccordance with Section 8.7 and 40.3.2 are not required to be the basis for overall occupancy classification

Statement of Problem and Substantiation for Public Comment

Expanding the definition of high hazard industrial occupancy to include industrial occupancies that use, process, store, or handle hazardous materials in excess of the MAQ may change the classification of existing general industrial or special purpose industrial occupancies to high hazard industrial occupancies. Previous code cycles based the definition of high hazard contents only on the flammability and explosive potential of the contents. With the expansion of the scope of high hazard industrial occupancy to include chemicals with maximum allowable quantities (MAQ) in the fire code there are now chemicals that do not pose a high fire risk, such as corrosive and toxic materials, that could require an existing general or special purpose industrial occupancy to be reclassified as a high hazard industrial occupancy.

Reclassification as high hazard industrial may require significant physical changes to the building to meet high hazard industrial occupancy requirements such as no dead end corridors or common path of travel, maximum travel distance of 75 feet, increased capacity factors for stairways and level components, and increased separation of occupancies

The proposed rewording will remove the financial burden on existing buildings while allowing for new buildings to be designed to meet the requirements.

If accepted, the Committee will have to take action to change the definition of high hazard industrial occupancy in Section 3.3.190.8.2

Related Item

First Revision No. 4017-NFPA 101-2015 [Section No. 40.1.2.1.3]

Submitter Information Verification

Submitter Full Name: Robert Hanson

Organization: Savannah River Nuclear Solutions

Street Address:

City:

State:

Zip:

Submittal Date: Thu Apr 21 10:23:19 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

233 of 259 5/17/2016 9:43 AM

Page 47 of 75

Page 48: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 177-NFPA 101-2016 [ New Section after 40.2.1.2 ]

40.2.1.3

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with

the provisions of 7.1.6.5.

Statement of Problem and Substantiation for Public Comment

PLEASE NOTE THAT WHATEVER CHANGE IS MADE IN CHAPTER 18 OF NFPA 101, THE SAME CHANGE SHOULD BE MADE IN NFPA 500O FOR INDUSTRIAL OCCUPANCIES.

The proposed changes to the originally proposed text resulted from months of consultation with experts in the US and Canada, especially during a face-to-face meeting held in Toronto on March 31 and April 1, 2016. In addition, editorial changes are based on those suggested by one of the experts, Marsha Mazz, from the US Access Board and member of NFPA's Disability Advisory Review Committee. At the face-to-face meeting there was extensive discussion and consensus on provision of a vertical grab bar on the wall opposite the control-end wall, especially where (as is fairly common in smaller bathrooms) water supply and drainage, for toileting, bathing/showering and other washing, etc. are located on a common wall. This leads to a significant portion of the length of a typical bathtub, at the control wall end, being partly obstructed, typically by a water closet. The substantive revisions suggested in this comment address this issue effectively by providing more flexibility in grab bar provision than first proposed. Also reflecting expert input from the meeting, is the revision to the lower height threshold for vertical grab bars for bathtubs and bathtub-shower combinations used by shorter adults and children, especially in either the bathing mode or the shower mode. The additional grab bar length specified is not a major cost issue as wall-mounted (or other) grab bar length is not a large component of purchase cost and does not significantly affect installation cost. The combination of purchase and installation costs, per bathroom, is quite comparable to the average, per-household cost of bathing/showering/toileting-related fall injuries occurring over a two or three-year period in the USA. Usability is a benefit of at least similar value and this is especially significant for older users. The addition of toileting-related usability and safety in the considerations behind the proposals and comments is especially related to the dual benefits of the pole-type grab bars that can serve not only the bathing/showering transfer functions but the more pervasive use of water closets, particularly in smaller bathrooms that are found in large proportions of bathrooms in all types of facilities. There has also been much study of actual installations, especially as one of the original proponents travels extensively and uses many bathing/showering facilities in hotels around the world. This provided additional insights justifying and, in some respects, suggesting fine-tuning of the concepts at the core of the first revision proposal. Work has also been done especially on the addition of grab bars to existing bathtubs and bathtub-shower combinations — i.e., not just new facilities. The vertical poles (plus some horizontally-oriented poles at the back wall of bathtubs) show great promise for relatively inexpensive and highly functional grab bars in retrofit situations for existing facilities, including those in rental properties where holes cannot be made in walls (as is the case for conventional, wall-mounted grab bars. There has also been much attention given, in consultation with top experts on injury epidemiology and costs to the relatively high risks and consequences of falls involving not only bathing/showering but also toileting. Much of this will be reflected in national and international conferences being held in Canada, the US and the UK prior to or shortly after the public comments are addressed by NFPA committees. These include two national and international conferences focused on falls and two national conference focused on public health generally. More information on these will be shared directly with NFPA committee members responsible for this core menu item and for scoping in all or most occupancy chapters of NFPA 101 and NFPA 5000. Significantly, due to the crush of preparation for such conferences (in which the submitter of these comments is deeply involved as an organizer and presenter), it is not possible to submit parallel comments for NFPA 101. Therefore, it is explicitly requested that in all cases, the committees process these comments in relation to both codes. Finally, the conferences as well as the recent, face-to-face meeting of several US and Canadian experts are all documented with video. The first two videos in this series are available for streaming viewing by anyone, at no cost, at http://www.imagosentertainment.com/Under_Construction.html. These two early videos not only identify the experts, but provide an excellent introduction to the extensive evidence obtained in research performed over the last two decades.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 170-NFPA 101-2016 [Section No. 7.1.6.5]

Related Item

First Revision No. 5036-NFPA 101-2015 [New Section after 7.1.6.4]

Submitter Information Verification

Submitter Full Name: Jake Pauls

Organization: Jake Pauls Consulting Services

Street Address:

City:

State:

Zip:

Submittal Date: Sun May 15 02:27:19 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

234 of 259 5/17/2016 9:43 AM

Page 48 of 75

Page 49: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 178-NFPA 101-2016 [ New Section after 42.2.1.2 ]

42.2.1.3

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with the

provisions of 7.1.6.5.

Statement of Problem and Substantiation for Public Comment

PLEASE NOTE THAT WHATEVER CHANGE IS MADE IN CHAPTER 142 OF NFPA 101, THE SAME CHANGE SHOULD BE MADE IN NFPA 500O FOR STORAGE OCCUPANCIES.

The proposed changes to the originally proposed text of 7.1.6.5 resulted from months of consultation with experts in the US and Canada, especially during a face-to-face meeting held in Toronto on March 31 and April 1, 2016. In addition, editorial changes are based on those suggested by one of the experts, Marsha Mazz, from the US Access Board and member of NFPA's Disability Advisory Review Committee. At the face-to-face meeting there was extensive discussion and consensus on provision of a vertical grab bar on the wall opposite the control-end wall, especially where (as is fairly common in smaller bathrooms) water supply and drainage, for toileting, bathing/showering and other washing, etc. are located on a common wall. This leads to a significant portion of the length of a typical bathtub, at the control wall end, being partly obstructed, typically by a water closet. The substantive revisions suggested in this comment address this issue effectively by providing more flexibility in grab bar provision than first proposed. Also reflecting expert input from the meeting, is the revision to the lower height threshold for vertical grab bars for bathtubs and bathtub-shower combinations used by shorter adults and children, especially in either the bathing mode or the shower mode. The additional grab bar length specified is not a major cost issue as wall-mounted (or other) grab bar length is not a large component of purchase cost and does not significantly affect installation cost. The combination of purchase and installation costs, per bathroom, is quite comparable to the average, per-household cost of bathing/showering/toileting-related fall injuries occurring over a two or three-year period in the USA. Usability is a benefit of at least similar value and this is especially significant for older users. The addition of toileting-related usability and safety in the considerations behind the proposals and comments is especially related to the dual benefits of the pole-type grab bars that can serve not only the bathing/showering transfer functions but the more pervasive use of water closets, particularly in smaller bathrooms that are found in large proportions of bathrooms in all types of facilities. There has also been much study of actual installations, especially as one of the original proponents travels extensively and uses many bathing/showering facilities in hotels around the world. This provided additional insights justifying and, in some respects, suggesting fine-tuning of the concepts at the core of the first revision proposal. Work has also been done especially on the addition of grab bars to existing bathtubs and bathtub-shower combinations — i.e., not just new facilities. The vertical poles (plus some horizontally-oriented poles at the back wall of bathtubs) show great promise for relatively inexpensive and highly functional grab bars in retrofit situations for existing facilities, including those in rental properties where holes cannot be made in walls (as is the case for conventional, wall-mounted grab bars. There has also been much attention given, in consultation with top experts on injury epidemiology and costs to the relatively high risks and consequences of falls involving not only bathing/showering but also toileting. Much of this will be reflected in national and international conferences being held in Canada, the US and the UK prior to or shortly after the public comments are addressed by NFPA committees. These include two national and international conferences focused on falls and two national conference focused on public health generally. More information on these will be shared directly with NFPA committee members responsible for this core menu item and for scoping in all or most occupancy chapters of NFPA 101 and NFPA 5000. Significantly, due to the crush of preparation for such conferences (in which the submitter of these comments is deeply involved as an organizer and presenter), it is not possible to submit parallel comments for NFPA 101. Therefore, it is explicitly requested that in all cases, the committees process these comments in relation to both codes. Finally, the conferences as well as the recent, face-to-face meeting of several US and Canadian experts are all documented with video. The first two videos in this series are available for streaming viewing by anyone, at no cost, at http://www.imagosentertainment.com/Under_Construction.html. These two early videos not only identify the experts, but provide an excellent introduction to the extensive evidence obtained in research performed over the last two decades.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 170-NFPA 101-2016 [Section No. 7.1.6.5]

Related Item

First Revision No. 5036-NFPA 101-2015 [New Section after 7.1.6.4]

Submitter Information Verification

Submitter Full Name: Jake Pauls

Organization: Jake Pauls Consulting Services

Street Address:

City:

State:

Zip:

Submittal Date: Sun May 15 02:35:07 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

235 of 259 5/17/2016 9:43 AM

Page 49 of 75

Page 50: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 123-NFPA 101-2016 [ Section No. A.11.3.4.4.1 ]

A.11.3.4.4.1

Smoke detection in single exit airport traffic control towers is intended to include the following:

(1) Tower cab area

(2) Along all means of egress from the tower including exit access paths, lobbies and other egress components

(3) All rooms containing equipment serving the ATCT

(4) Mall Small office spaces or lounge areas and similar spaces used by tower employees

(5) Utility shafts that provide access for maintenance

Smoke detection should be provided except where environmental conditions dictate other detection methods.

Statement of Problem and Substantiation for Public Comment

Clarify a question brought by the technical committee regarding environmental concerns with smoke detection and correct a typographical error. It is the intent of the Air Traffic Control Tower Fire Life Safety Task Group that automatic smoke detection be provided everywhere noted in 11.3.4.4.1. Areas where smoke detection is not listed for use are addressed by this comment to the appendix section and NFPA 72.

Related Item

First Revision No. 4012-NFPA 101-2015 [Section No. 11.3.4]

Public Input No. 174-NFPA 101-2015 [New Section after A.11.3.4.2(2)]

Submitter Information Verification

Submitter Full Name: Eric Rosenbaum

Organization: Jensen Hughes

Affilliation: Airport Traffic Control Tower Fire Life Safety Task Group

Street Address:

City:

State:

Zip:

Submittal Date: Thu May 05 11:13:15 EDT 2016

Copyright Assignment

I, Eric Rosenbaum, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both theProposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power andauthority to enter into this copyright assignment.

By checking this box I affirm that I am Eric Rosenbaum, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. Iunderstand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 5/20/2016 12:54 PM

Page 50 of 75

Page 51: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 7-NFPA 5000-2016 [ Section No. 4.5.5.4 ]

4.5.5.4

Where required by Chapters 15 through 31 and 33, construction, alteration, and demolition operations shall comply with NFPA 241.

Additional Proposed Changes

File Name Description Approved

5000_CCN_5.pdf 5000 CC Note #5

Statement of Problem and Substantiation for Public Comment

NOTE: This Public Comment appeared as CC Note No. 5 in the First Draft Report. The Correlating Committee directs the occupancy Technical Committees to consider reviewing new Section 4.5.5.4 and consider for addition in their respective chapters correlative language to reference NFPA 241. The language would read as follows:

XX.1.1.6 Where construction, alteration, or demolition operations are conducted, the provisions of 4.5.5.4 shall apply.

These action will be considered as a public comment.

Related Item

Correlating Committee Note No. 5-NFPA 5000-2016 [New Section after 4.5.5.3]

Submitter Information Verification

Submitter Full Name: CC on BLD_AAC

Organization: NFPA CC ON BUILDING CODE

Street Address:

City:

State:

Zip:

Submittal Date: Fri Mar 04 11:01:00 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 185 5/17/2016 1:23 PM

Page 51 of 75

Page 52: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Correlating Committee Note No. 5-NFPA 5000-2016 [ New Section after 4.5.5.3 ]

Submitter Information Verification

Submitter Full Name: BLD-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 13:51:50 EST 2016

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee directs the occupancy Technical Committees to consider reviewing new Section 4.5.5.4 andconsider for addition in their respective chapters correlative language to reference NFPA 241. The language would read asfollows:

XX.1.1.6 Where construction, alteration, or demolition operations are conducted, the provisions of 4.5.5.4 shall apply.

These action will be considered as a public comment.

Ballot Results

This item has passed ballot

18 Eligible Voters

2 Not Returned

15 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Newman, Michael T.

Wooldridge, Jerry

Affirmative All

DiCristina, Salvatore

Frable, David W.

Francis, Sam W.

Hansen, Raymond N.

Harrington, John C.

Hopper, Howard

Hugo, Jeffrey M.

Humble, Jonathan

Jones, Gerald H.

Leavitt, Russell B.

Quiter, James R.

Roberts, Richard Jay

Shah, Faimeen

Vinci, Leon F.

Willse, Peter J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 3/2/2016 1:51 PM

Page 52 of 75

Page 53: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Affirmative with Comment

Laramee, Scott T.

No comment, but no way to accept as "affirmative" without accepting all as "affirmative in the ballot portal.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 3/2/2016 1:51 PM

Page 53 of 75

Page 54: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 32-NFPA 5000-2016 [ Section No. 31.6.13 ]

31.6.13 Additional Requirements for Air Traffic Control Towers.

31.6.13.1 Definition — Air Traffic Control Tower.

See 3.3.654.1.

31.6.13.2 Use of Accessory Levels.

The levels located below the observation level shall be permitted to be occupied only for the following uses:

(1) Use that support tower operations such as electrical and mechanical equipment rooms, including emergency and standbypower, radar, communications, and electronics rooms

(2)

31.6.13.3 Minimum Construction Requirements.

Air traffic control towers shall be of Type I or Type II construction. (See 7.2.1.)

31.6.13.4 Means of Egress.

31.6.13.4.1* Number of Means of Egress.

Air traffic control towers shall be permitted to have a single exit, provided that all the following conditions are met in addition to therequirements of 31.6.5:

(1) Each level of air traffic control towers, served by a single exit, shall be subject to a calculated occupant load of 15 or fewerpersons.

(2) A fire alarm system shall be provided in accordance with 55.2. Smoke detection shall be provided throughout air traffic controltowers to meet the requirements of partial coverage, as defined in 5.5.2.2 of NFPA 72, and shall include coverage of all of thefollowing:

(a) Observation level

(b) Means of egress

(c) All equipment rooms

(d) Incidental accessory uses

(e) Accessible utility shafts

(3) The requirements of 31.6.5.1(5) shall not apply.

(4) Rooms or spaces used for the storage, processing, or use of combustible supplies shall be permitted in quantities deemedacceptable by the authority having jurisdiction.

(5) Smokeproof exit enclosures shall be provided in accordance with 11.2.3.

31.6.13.4.2 Remoteness.

Where an air traffic control tower is equipped throughout with an approved, supervised automatic sprinkler system in accordancewith Section 9.7, the minimum separation distance between two exits, or exit accesses, measured in accordance with 7.5.1.3.2 shallbe not less than one-fourth of the length of the maximum overall dimension of the building or area to be served.

31.6.13.4.3 Accessible Means of Egress.

Accessible means of egress shall not be required to serve the observation level and the floor immediately below the observationlevel in air traffic control towers.

31.6.13.4.4 Egress for Occupant Load.

Means of egress for air traffic control towers shall be provided for the occupant load, as determined in accordance with 11.3.1.

31.6.13.4.5 Areas Excluded from Occupant Load.

Shafts, stairs, and spaces and floors not subject to human occupancy shall be excluded from consideration in determining the totalcalculated occupant load of the tower, as required by 31.6.5.1(1) and 31.6.13.4.1(1).

31.6.13.4.6 Single Means of Egress.

A single means of egress shall be permitted from the observation level of an air traffic control tower to an exit, as permitted by31.6.5.2.

31.6.13.4.7 Smokeproof Enclosures.

Smokeproof exit enclosures complying with 11.2.3 shall be provided for all air traffic control tower exit enclosures.

31.6.13.4.8 Discharge from Exits.

31.6.13.4.8.1

Air traffic control towers shall comply with the requirements of 11.7.2, except as permitted by 31.6.13.4.6.2.

31.6.13.5 Protection.

* Incidental accessory uses that support tower operations

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

136 of 185 5/17/2016 1:23 PM

Page 54 of 75

Page 55: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

31.6.13.5.1 Detection, Alarm, and Communications Systems.

Air traffic control towers shall be provided with a fire alarm system in accordance with Section 55.2. Smoke detection shall beprovided throughout the air traffic control tower to meet the requirements for partial coverage, as defined in 5.5.2.2 of NFPA 72, andshall include coverage of all of the following:

(1) All equipment rooms

(2) Observation level

(3) Outside each opening into exit enclosures

(4) Along the single means of egress permitted from observation levels in 31.6.5.2

(5) Outside each opening into the single means of egress permitted from observation levels in 31.6.5.2

31.6.13.5.2 Extinguishing Requirements.

Air traffic control towers shall be protected throughout by an approved, supervised automatic sprinkler system in accordance withSection 55.3.

31.6.13.5.3 Standpipe Requirements.

New air traffic control towers where the floor of the observation level is greater than 30 ft (9.1 m) above the lowest level of firedepartment vehicle access shall be protected throughout with a Class I standpipe system in accordance with Section 55.4. Class Istandpipes shall be permitted to be manual standpipes, as defined in NFPA 14, where the authority having jurisdiction has beendetermined to have sufficient capabilities to supply the system.

31.6.13.6 Prohibited Uses.

Sleeping areas shall be prohibited in air traffic control towers.

31.6.13.7 Emergency Command Center.

31.6.13.7.1

An emergency command center shall be provided in a location approved by the fire department where the floor of an occupiablestory is greater than 75 ft (23 m) above the lowest level of fire department vehicle access. Emergency command center is permittedto be located in the air traffic control tower or an adjacent contiguous building where building functions are interdependent.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

137 of 185 5/17/2016 1:23 PM

Page 55 of 75

Page 56: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

31.6.13.7.2

The emergency command center shall contain the following:

(1) Fire department two-way telephone communication service panels and controls

(2) Fire detection and fire alarm system control unit and annunciator

(3) Elevator floor location and operation annunciators

(4) Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators

(5) Controls and annunciators for systems supporting smokeproof enclosures

(6) Sprinkler valve and waterflow annunciators

(7) Emergency generator status indicators

(8) Schematic building plans indicating typical floor plan and detailing the building core, means of egress, fire protection systems,fire-fighting equipment and fire department access as well as the location of fire walls, fire barriers, fire partitions, smokebarriers, and smoke partitions

(9) Fire pump status indicators

(10) Telephone for fire department use with controlled access to the public telephone system

(11) An approved Building Information Card that contains, but is not limited to, the following information:

(a) General building information that includes: property name, address, the number of floors in the building (above and belowgrade), use and occupancy classification (for mixed uses, identify the different types of occupancies on each floor),estimated building population (i.e., day, night, weekend)

(b) Building emergency contact information that includes a list of the building's emergency contacts (e.g., building manager,building engineer) and their respective work phone numbers, cell phone numbers, email addresses

(c) Building construction information that includes the type of building construction (e.g., floors, walls, columns, and roofassembly)

(d) Exit stair information that includes: number of exit stairs in building, each exit stair designation and floors served, locationwhere each exit stair discharges, exit stairs that are pressurized, exit stairs provided with emergency lighting, each exitstair that allows re-entry, exit stairs providing roof access; elevator information that includes: number of elevator banks,elevator bank designation, elevator car numbers and respective floors that they serve, location of elevator machine rooms,location of sky lobby, location of freight elevator banks

(e) Building services and system information that includes location of mechanical rooms, location of building managementsystem, location and capacity of all fuel oil tanks, location of emergency generator, location of natural gas service

(f) Fire protection system information that includes locations of standpipes, location of fire pump room, location of firedepartment connections, floors protected by automatic sprinklers, location of different types of sprinkler systems installed(e.g., dry, wet, preaction)

(g) Hazardous material information that includes location of hazardous material and quantity of hazardous material

(12) Worktable

31.6.13.8 Emergency Action Plans and Fire Drills.

31.6.13.8.1

All air traffic control towers shall have written copies of an emergency action plan as required by Section 4.8.

31.6.13.8.2

Fire drills shall be conducted such that all employees participate at least once annually in accordance with Section 4.7.

31.6.13.8.3

Employees of air traffic control towers shall be instructed at least annually in the emergency action plan.

31.6.13.8.4

The emergency action plan shall be updated at least annually.

Additional Proposed Changes

File Name Description Approved

5000_CCN_31.pdf 5000 CC Note #31

Statement of Problem and Substantiation for Public Comment

NOTE: This public comment appeared as CC Note No. 31 in the First Draft Report. The Correlating Committee directs the TC on Industrial and Storage Occupancies (IND) to do the following:

1. Revise 31.6.13.4.1(2)(b) from “Means of egress” to the former term “Common areas” or something else that is definitive as “means of egress” includes ALL spaces where an occupant can be present.

2. Revise 31.6.13.4.2 to insert the word “diagonal” to read “…maximum overall diagonal dimension…”

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

138 of 185 5/17/2016 1:23 PM

Page 56 of 75

Page 57: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

3. Revise second sentence of 31.6.13.7.1 to change “is permitted’ to “shall be permitted” to read: “The emergency command center shall be permitted to be located…”

4. Change “air traffic control tower” to “airport traffic control tower” or “air traffic control towers” to “airport traffic control towers”

5. Consider deletion of Section 31.6.18.8 in its entirety as it relates to emergency action plans and fire drills which are outside the scope of NFPA 5000.

These actions will be considered as a public comment.

Related Item

Correlating Committee Note No. 31-NFPA 5000-2016 [Section No. 31.6.13]

Submitter Information Verification

Submitter Full Name: CC on BLD_AAC

Organization: NFPA CC ON BUILDING CODE

Street Address:

City:

State:

Zip:

Submittal Date: Mon Mar 07 13:15:39 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

139 of 185 5/17/2016 1:23 PM

Page 57 of 75

Page 58: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Correlating Committee Note No. 31-NFPA 5000-2016 [ Section No. 31.6.13 ]

Submitter Information Verification

Submitter Full Name: BLD-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 15:14:35 EST 2016

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee directs the TC on Industrial and Storage Occupancies (IND) to do the following:

1. Revise 31.6.13.4.1(2)(b) from “Means of egress” to the former term “Common areas” or something else that is definitive as“means of egress” includes ALL spaces where an occupant can be present.

2. Revise 31.6.13.4.2 to insert the word “diagonal” to read “…maximum overall diagonal dimension…”

3. Revise second sentence of 31.6.13.7.1 to change “is permitted’ to “shall be permitted” to read: “The emergency commandcenter shall be permitted to be located…”

4. Change “air traffic control tower” to “airport traffic control tower” or “air traffic control towers” to “airport traffic control towers”

5. Consider deletion of Section 31.6.18.8 in its entirety as it relates to emergency action plans and fire drills which are outsidethe scope of NFPA 5000.

These actions will be considered as a public comment.

Ballot Results

This item has passed ballot

18 Eligible Voters

2 Not Returned

15 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Newman, Michael T.

Wooldridge, Jerry

Affirmative All

DiCristina, Salvatore

Frable, David W.

Francis, Sam W.

Hansen, Raymond N.

Harrington, John C.

Hopper, Howard

Hugo, Jeffrey M.

Humble, Jonathan

Jones, Gerald H.

Leavitt, Russell B.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 3/2/2016 2:19 PM

Page 58 of 75

Page 59: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Quiter, James R.

Roberts, Richard Jay

Shah, Faimeen

Vinci, Leon F.

Willse, Peter J.

Affirmative with Comment

Laramee, Scott T.

No comment, but no way to accept as "affirmative" without accepting all as "affirmative in the ballot portal.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 3/2/2016 2:19 PM

Page 59 of 75

Page 60: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

First Revision No. 5019-NFPA 5000-2015 [ Section No. 31.6.13 ]

31.6.13 Additional Requirements for Air Traffic Control Towers.

31.6.13.1 Definition — Air Traffic Control Tower.

See 3.3.654.1 .

31.6.13.2 Use of Accessory Levels.

The levels located below the observation level shall be permitted to be occupied only for the following uses that support toweroperations :

(1) Use that support tower operations such as electrical and mechanical equipment rooms, including emergency and standby power,radar, communications, and electronics rooms

(2)

31.6.13.3 Minimum Construction Requirements.

Air traffic control towers shall be of Type I or Type II construction. (See 7.2.1 .)

31.6.13.4 Means of Egress.

31.6.13.4.1* Number of Means of Egress.

Air traffic control towers shall be permitted to have a single exit, provided that all the following conditions are met in addition to therequirements of 31.6.5 :

(1) Each level of air traffic control towers, served by a single exit, shall be subject to a calculated occupant load of 15 or fewer persons.

(2) A fire alarm system shall be provided in accordance with 55.2 . Smoke detection shall be provided throughout air traffic controltowers to meet the requirements of partial coverage, as defined in 5.5.2.2 of NFPA 72 , National Fire Alarm and Signaling Code ,and shall include coverage of all of the following:

(a) Occupiable areas Observation level

(b) Common areas Means of egress

(c) Work spaces All equipment rooms

(d) Equipment areas Incidental accessory uses

Means of egress

(e) Accessible utility shafts

(3) The requirements of 31.6.5.1 (5) shall not apply.

(4) Rooms or spaces used for the storage, processing, or use of combustible supplies shall be permitted in quantities deemedacceptable by the authority having jurisdiction.

(5) Smokeproof exit enclosures shall be provided in accordance with 11.2.3 .

31.6.13.4.2 Remoteness.

Where an air traffic control tower is equipped throughout with an approved, supervised automatic sprinkler system in accordance withSection 9.7, the minimum separation distance between two exits, or exit accesses, measured in accordance with 7.5.1.3.2 shall be notless than one-fourth of the length of the maximum overall dimension of the building or area to be served.

31.6.13.4.3 Accessible Means of Egress.

Accessible means of egress shall not be required to serve the observation level and the floor immediately below the observation levelin air traffic control towers.

31.6.13.4.4 Egress for Occupant Load.

Means of egress for air traffic control towers shall be provided for the occupant load, as determined in accordance with 11.3.1 .

31.6.13.4.5 Areas Excluded from Occupant Load.

Shafts, stairs, and spaces and floors not subject to human occupancy shall be excluded from consideration in determining the totalcalculated occupant load of the tower, as required by 31.6.5.1 (1) and 31.6.13.4.1 (1).

31.6.13.4.6 Single Means of Egress.

A single means of egress shall be permitted from the observation level of an air traffic control tower to an exit , as permitted by 31.6.5.2.

31.6.13.4.7 Smokeproof Enclosures.

Smokeproof exit enclosures complying with 11.2.3 shall be provided for all air traffic control tower exit stair enclosures.

31.6.13.4.8 Discharge from Exits.

31.6.13.4.8.1

Air traffic control towers shall comply with the requirements of 11.7.2 , except as permitted by 31.6.13.4.6.2.

* Incidental accessory uses that support tower operations

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 5 6/1/2016 11:38 AM

Page 60 of 75

Page 61: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

31.6.13.5 Protection.

31.6.13.5.1 Detection, Alarm, and Communications Systems.

Air traffic control towers shall be provided with a fire alarm system in accordance with Section 55.2 . Smoke detection shall be providedthroughout the air traffic control tower to meet the requirements for selective partial coverage, as defined in 5.5.2.2 of NFPA 72 ,National Fire Alarm and Signaling Code , and shall include coverage of all of the following:

(1) In All equipment areas rooms

(2) Observation level

(3) Outside each opening into exit enclosures

(4) Along the single means of egress permitted from observation levels in 31.6.5.2

(5) Outside each opening into the single means of egress permitted from observation levels in 31.6.5.2

31.6.13.5.2 Extinguishing Requirements.

Air traffic control towers shall be protected throughout by an approved, supervised automatic sprinkler system in accordance withSection 55.3 .

31.6.13.5.3 Standpipe Requirements.

New air traffic control towers where the floor of the cab observation level is greater than 30 ft (9.1 m) above the lowest level of firedepartment vehicle access shall be protected throughout with a Class I standpipe system in accordance with Section 55.4 . Class Istandpipes shall be permitted to be manual standpipes, as defined in NFPA 14 , Standard for the Installation of Standpipe and HoseSystems , where the authority having jurisdiction has been determined to have sufficient capabilities to supply the system.

31.6.13.6 Prohibited Uses.

Sleeping areas shall be prohibited in air traffic control towers.

31.6.13.7 Emergency Command Center.

31.6.13.7.1

An emergency command center shall be provided in a location approved by the fire department where the floor of an occupiable storyis greater than 75 ft (23 m) above the lowest level of fire department vehicle access. Emergency command center is permitted to belocated in the air traffic control tower or an adjacent contiguous building where building functions are interdependent.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 5 6/1/2016 11:38 AM

Page 61 of 75

Page 62: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

31.6.13.7.2

The emergency command center shall contain the following:

(1) Fire department two-way telephone communication service panels and controls

(2) Fire detection and fire alarm system control unit and annunciator

(3) Elevator floor location and operation annunciators

(4) Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators

(5) Controls and annunciators for systems supporting smokeproof enclosures

(6) Sprinkler valve and waterflow annunciators

(7) Emergency generator status indicators

(8) Schematic building plans indicating typical floor plan and detailing the building core, means of egress, fire protection systems,fire-fighting equipment and fire department access as well as the location of fire walls, fire barriers, fire partitions, smoke barriers,and smoke partitions

(9) Fire pump status indicators

(10) Telephone for fire department use with controlled access to the public telephone system

(11) An approved Building Information Card that contains, but is not limited to, the following information:

(a) General building information that includes: property name, address, the number of floors in the building (above and belowgrade), use and occupancy classification (for mixed uses, identify the different types of occupancies on each floor),estimated building population (i.e., day, night, weekend)

(b) Building emergency contact information that includes a list of the building's emergency contacts (e.g., building manager,building engineer) and their respective work phone numbers, cell phone numbers, email addresses

(c) Building construction information that includes the type of building construction (e.g., floors, walls, columns, and roofassembly)

(d) Exit stair information that includes: number of exit stairs in building, each exit stair designation and floors served, locationwhere each exit stair discharges, exit stairs that are pressurized, exit stairs provided with emergency lighting, each exit stairthat allows re-entry, exit stairs providing roof access; elevator information that includes: number of elevator banks, elevatorbank designation, elevator car numbers and respective floors that they serve, location of elevator machine rooms, locationof sky lobby, location of freight elevator banks

(e) Building services and system information that includes location of mechanical rooms, location of building managementsystem, location and capacity of all fuel oil tanks, location of emergency generator, location of natural gas service

(f) Fire protection system information that includes locations of standpipes, location of fire pump room, location of firedepartment connections, floors protected by automatic sprinklers, location of different types of sprinkler systems installed(e.g., dry, wet, preaction)

(g) Hazardous material information that includes location of hazardous material and quantity of hazardous material

(12) Worktable

31.6.13.8 Emergency Action Plans and Fire Drills.

31.6.13.8.1

All air traffic control towers shall have written copies of an emergency action plan as required by Section 4.8.

31.6.13.8.2

Fire drills shall be conducted such that all employees participate at least once annually in accordance with Section 4.7.

31.6.13.8.3

Employees of air traffic control towers shall be instructed at least annually in the emergency action plan.

31.6.13.8.4

The emergency action plan shall be updated at least annually.

Supplemental Information

File Name Description

A.31.6.13.4.1.docx

Submitter Information Verification

Submitter Full Name: BLD-IND

Organization: [ Not Specified ]

Street Address:

City:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

3 of 5 6/1/2016 11:38 AM

Page 62 of 75

Page 63: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

State:

Zip:

Submittal Date: Wed Sep 02 13:51:40 EDT 2015

Committee Statement and Meeting Notes

CommitteeStatement:

Correlative changes with NFPA 101 Section 11.3.4.

Section 31.6.13.4.1(2) is proposed to clarify the spaces that require automatic smoke detection where a single means of egress isprovided and that a fire alarm system is required to be provided. The majority of spaces in single exit towers would require detectionto provide an enhanced level of detection. The terminology is revised to provide consistency with Section 11.3.4.5.1.

Section 31.6.13.4.2: ATCTs typically have a limited number of occupants. In addition, occupants must be awake and alert. The hazardassociated with ATCTs is affected by the building’s limited uses, size and height. The occupied levels of an ATCT are located at thetop of the structure that typically contains support equipment and services but has limited occupancy. The lower levels of the ATCTare typically limited in size with the upper levels are larger in size. This means that towards the upper floors of the building where thestructure flares out the diagonal distance of the building increases. This flared space is used for equipment that serves air trafficcontrol. Architectural analysis has shown that meeting the 1/3 diagonal distance separation requirement is possible by routing accessto one of the two means of egress through an equipment room. It is this task group’s judgment that an arrangement routing egressthough an equipment room creates a larger risk then reducing the diagonal separation requirement. The limited area and layout of thenormally unoccupied lower levels can make separation of the exit access by 1/3 of the diagonal of the floor plan difficult. This revisionreduces the required separation distance of multiple exit ATCTs in ATCTs that are typically low in occupancy and size.

Section 31.6.13.4.3: The proposed change is the recommendation of the Airport Traffic Control Tower Fire Life Safety Task Group,and reflect the current approach to fire protection and life safety in airport traffic control towers (ATCT). This change providesconsistency with the typical building practices for airport traffic control towers.

Section 31.6.13.4.6 is proposed to clarify the intent of the requirement that the travel distance limit is to the entrance of the exit andnot the exit discharge.

Section 31.6.13.4.7 is proposed to require smoke proof enclosures for all exit enclosures. While stairs are the primary means ofegress provided for ATCTs, this change provides protection for all exits due to the potential for delayed evacuation of tower operators.

Section 31.6.13.5.1 is proposed to provide consistent terminology with Section 31.6.13.4.1 as well as require smoke detection in theobservation level of all air traffic control towers regardless of the number of exits provided.

Section 31.6.13.5.3 is proposed to provide consistent terminology with the rest of the air traffic control tower section.

Section 31.6.13.7 is proposed to provide a control location for fire fighter operations due to the unique aspects of fighting fires inATCTs. It is proposed that the emergency command center be located in either the tower footprint or the adjacent base building(where provided). The base building supports the tower operations and is built contiguous to the ATCT. Requirements were takenfrom Section 11.8.6 with a few exceptions. The voice fire alarm system controls were removed as ATCTs are not provided with voicesystems. The fire alarm control unit would be located in the fire command center and provide status indicators for all associatedsystems. The requirement for elevator power selector switches was removed as ATCTs are typically designed with a single elevator.Controls for stairway door unlocking systems and video monitoring were not included as ATCTs are located in areas with restrictedaccess.

Section 31.6.13.8 is proposed to provide a regular requirement for emergency training for air traffic control tower operators. In theevent of an emergency, operators are potentially not able to immediately egress due to the necessity of handing off flights to otherlocations. Requiring regular training on the steps to take in the event of an emergency provides benefit to the controllers and thegeneral public.

ResponseMessage:

Ballot Results

This item has passed ballot

30 Eligible Voters

2 Not Returned

27 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

1 Abstention

Not Returned

Jones, Adam C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

4 of 5 6/1/2016 11:38 AM

Page 63 of 75

Page 64: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Krantz, Sr., Neal W.

Affirmative All

Allison, Thomas L.

Arntson, Raymond E.

Birchler, Donald C.

Cummings, Ryan

Cusimano, Alberto

Dale, Stephen E.

Dawe, Nicholas A.

Dudley, Jeffry T.

Golinveaux, James E.

Humble, Jonathan

Johnson, Aaron

Klein, Marshall A.

Klinkhardt, Jeffrey

Kobelski, Richard J.

Kraus, Richard S.

Laberge, Todd

Lonabaugh, Raymond W.

Lozano-Rosales, Roberto

McLaughlin, Patrick A.

Pierrottie, Jerald

Pruett, Scot

Saric, Jr., Marko J.

Sheldon, Steven A.

Skinker, Cleveland B.

Swiecicki, Bruce J.

White, Michael S.

Wren, Carl D.

Abstention

Sameth, Jerrold

CGA did not develop a consensus position.

Editorial Comment

Click here

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

5 of 5 6/1/2016 11:38 AM

Page 64 of 75

Page 65: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 122-NFPA 5000-2016 [ New Section after 31.6.13.3 ]

31.6.13.3.1 Construction of Inside Exit Stairs and Elevator Hoistway Enclosures.

Enclosures for inside exit stairs and elevator hoistways in air traffic control towers with an occupiable story greater than 75 ft above thelowest level of fire department access shall comply with the following:

(1) Soft Body Impact Classification Level 2 in accordance with ASTM C 1629 shall be met or exceeded for wall assembliesconstructed for inside exit stairs and elevator hoistways.

(2) Wall assembly materials forming the exterior of the enclosure shall be in accordance with one of the following:

(3) Hard Body Impact Classification Level 2 in accordance with ASTM C 1629/C 1629M shall be met or exceeded where a wallassembly includes at least two layers of impact-resistant construction board.

(4) Hard Body Impact Classification Level 3 in accordance with ASTM C 1629/C 1629M shall be met or exceeded where a wallassembly includes at least one layer of impact-resistant construction material.

(5) Hard Body Impact Classification Level 3 in accordance with ASTM C 1629/C 1629M shall be met or exceeded where a wallassembly is composed of multiple layers tested in tandem of any material.

(6) The requirements of 31.6.13.3.1(1) and 31.6.13.3.1(2) shall not apply to concrete and masonry walls.

(7) Where the impact resistance for Hard Body Impact Classification Level 3 in accordance with ASTM C 1629/C 1629M is met orexceeded, the wall assembly shall be permitted.

Statement of Problem and Substantiation for Public Comment

The proposed changes are included as the recommendation of the Technical Committee on Industrial, Storage and Miscellaneous Occupancies. The details are proposed by the Airport Traffic Control Tower Fire Life Safety Task Group, and reflect the current approach to fire protection and life safety in high rise buildings in general, but are applied to airport traffic control towers (ATCT). The proposed changes relate to providing extra protection for the controllers and fire service and providing consistency with other building codes and standards.

ATCTs create a unique hazard. ATCTs typically have a limited number of occupants. In addition, occupants must be awake and alert. The hazard associated with ATCTs is affected by the occupied levels being typically located at the top of the structure and the potential delay in evacuation because of the handoff of flights.

Section 31.6.13.3.1 is proposed to provide additional protection of vertical shafts used for travel of occupants and is recommended by NIST based on the WTC research performed (see recommendation 18 from the WTC Disaster Study Recommendations). Adding structural integrity criteria to these vertical shafts provides additional protection in an occupancy where delayed evacuations may be required. These requirements are common to high-rise buildings in New York City and jurisdictions adopting the International Building Code.

Related Item

Committee Input No. 5003-NFPA 5000-2015 [New Section after 31.6.13.3]

Submitter Information Verification

Submitter Full Name: Eric Rosenbaum

Organization: Jensen Hughes

Affilliation: Airport Traffic Control Tower Fire Life Safety Task Group

Street Address:

City:

State:

Zip:

Submittal Date: Mon May 16 16:30:55 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

140 of 185 5/17/2016 1:23 PM

Page 65 of 75

Page 66: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 63-NFPA 5000-2016 [ New Section after 31.6.13.3 ]

31.6.13.3.2 Sprayed fire-resistive materials (SFRM)

In air traffic control towers with an occupiable story greater than 75 ft above the lowest level of fire department vehicle access, thebond strength of SFRM installed shall be 430 psf.

Statement of Problem and Substantiation for Public Comment

The proposed changes are included as the recommendation of the Technical Committee on Industrial, Storage and Miscellaneous Occupancies. The details are proposed by the Airport Traffic Control Tower Fire Life Safety Task Group, and reflect the current approach to fire protection and life safety in high rise buildings in general, but are applied to airport traffic control towers (ATCT). The proposed changes relate to providing extra protection for the controllers and fire service and providing consistency with other building codes and standards.

ATCTs create a unique hazard. ATCTs typically have a limited number of occupants. In addition, occupants must be awake and alert. The hazard associated with ATCTs is affected by the occupied levels being typically located at the top of the structure and the potential delay in evacuation because of the handoff of flights.

Section 31.6.13.3.2 is proposed to provide additional structural protection by increasing the minimum bond strengths for sprayed fire-resistant materials as recommended by NIST based on the WTC research performed (see recommendation 6 from the WTC Disaster Study Recommendations). This raises the minimum bond strength to 430 psf for all ATCTs with an occupiable story more than 75 ft above the lowest level of fire department access and puts the requirement in line with the IBC. The proposed requirement provides additional protection of the structural frame where delayed evacuations may be required. These requirements are common to high-rise buildings in jurisdictions adopting the International Building Code.

Related Item

Committee Input No. 5003-NFPA 5000-2015 [New Section after 31.6.13.3]

Submitter Information Verification

Submitter Full Name: Eric Rosenbaum

Organization: Jensen Hughes

Affilliation: Airport Traffic Control Tower Fire Life Safety Task Group

Street Address:

City:

State:

Zip:

Submittal Date: Tue May 03 11:43:08 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

141 of 185 5/17/2016 1:23 PM

Page 66 of 75

Page 67: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 33-NFPA 5000-2016 [ New Section after 34.3.2.4.6 ]

Additional Proposed Changes

File Name Description Approved

5000_CCN_33.pdf 5000 CC Note #33

Statement of Problem and Substantiation for Public Comment

NOTE: This Public Comment appeared as CC Note No. 33 in the First Draft Report. The Correlating Committee directs the TC on Industrial, Storage, and Miscellaneous Occupancies (IND) to consider theNegative ballot of Pruett to determine if the values proposed in NFPA 5000 for common path of travel are in conflict with NFPA 101.

This action will be considered as a public comment.

Related Item

Correlating Committee Note No. 33-NFPA 5000-2016 [New Section after 34.3.2.4.5]

Submitter Information Verification

Submitter Full Name: CC on BLD_AAC

Organization: NFPA CC ON BUILDING CODE

Street Address:

City:

State:

Zip:

Submittal Date: Mon Mar 07 13:26:21 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

145 of 185 5/17/2016 1:23 PM

Page 67 of 75

Page 68: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Correlating Committee Note No. 33-NFPA 5000-2016 [ New Section after 34.3.2.4.5 ]

Submitter Information Verification

Submitter Full Name: BLD-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 15:19:53 EST 2016

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee directs the TC on Industrial, Storage, and Miscellaneous Occupancies (IND) to consider theNegative ballot of Pruett to determine if the values proposed in NFPA 5000 for common path of travel are in conflict with NFPA101.

This action will be considered as a public comment.

Ballot Results

This item has passed ballot

18 Eligible Voters

2 Not Returned

15 Affirmative All

0 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Newman, Michael T.

Wooldridge, Jerry

Affirmative All

DiCristina, Salvatore

Frable, David W.

Francis, Sam W.

Hansen, Raymond N.

Harrington, John C.

Hopper, Howard

Hugo, Jeffrey M.

Humble, Jonathan

Jones, Gerald H.

Leavitt, Russell B.

Quiter, James R.

Roberts, Richard Jay

Shah, Faimeen

Vinci, Leon F.

Willse, Peter J.

Negative with Comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 3/2/2016 2:20 PM

Page 68 of 75

Page 69: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Laramee, Scott T.

Any conflicts in travel distance between 5000 and 101 should be resolved prior to acceptance of that change.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 3/2/2016 2:20 PM

Page 69 of 75

Page 70: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Public Comment No. 38-NFPA 5000-2016 [ New Section after 55.12 ]

Additional Proposed Changes

File Name Description Approved

5000_CCN_38.pdf

NOTE: This Public Comment appeared as CC Note No. 38 in the First Draft Report. The Correlating Committee directs the TC on Fundamentals (FUN) and the occupancy committees (AXM, END, HEA, BCF, RES, DET, MER, IND) to review the proposed change and determine if further changes are needed in the Code. The Correlating Committee will revisit the scope of the TC on Building Service and Fire Protection Equipment (BSF) after they propose any desired changes.

This action will be considered as a public comment.

Statement of Problem and Substantiation for Public Comment

NOTE: This Public Comment appeared as CC Note No. 38 in the First Draft Report. The Correlating Committee directs the TC on Fundamentals (FUN) and the occupancy committees (AXM, END, HEA, BCF, RES, DET, MER, IND) to review the proposed change and determine if further changes are needed in the Code. The Correlating Committee will revisit the scope of the TC on Building Service and Fire Protection Equipment (BSF) after they propose any desired changes.

This action will be considered as a public comment.

Related Item

Correlating Committee Note No. 38-NFPA 5000-2016 [New Section after 55.12]

Submitter Information Verification

Submitter Full Name: CC on BLD_AAC

Organization: NFPA CC ON BUILDING CODE

Street Address:

City:

State:

Zip:

Submittal Date: Mon Mar 07 14:37:28 EST 2016

Copyright Assignment

I, CC on BLD_AAC, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both theProposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power andauthority to enter into this copyright assignment.

By checking this box I affirm that I am CC on BLD_AAC, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. Iunderstand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 5/23/2016 11:35 AM

Page 70 of 75

Page 71: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Correlating Committee Note No. 38-NFPA 5000-2016 [ New Section after 55.12 ]

Submitter Information Verification

Submitter Full Name: BLD-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 15:26:03 EST 2016

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee directs the TC on Fundamentals (FUN) and the occupancy committees (AXM, END, HEA, BCF, RES,DET, MER, IND) to review the proposed change and determine if further changes are needed in the Code. The CorrelatingCommittee will revisit the scope of the TC on Building Service and Fire Protection Equipment (BSF) after they propose any desiredchanges.

This action will be considered as a public comment.

Ballot Results

This item has passed ballot

18 Eligible Voters

2 Not Returned

15 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Newman, Michael T.

Wooldridge, Jerry

Affirmative All

DiCristina, Salvatore

Frable, David W.

Francis, Sam W.

Hansen, Raymond N.

Harrington, John C.

Hopper, Howard

Hugo, Jeffrey M.

Humble, Jonathan

Jones, Gerald H.

Leavitt, Russell B.

Quiter, James R.

Roberts, Richard Jay

Shah, Faimeen

Vinci, Leon F.

Willse, Peter J.

Affirmative with Comment

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 3/2/2016 2:25 PM

Page 71 of 75

Page 72: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Laramee, Scott T.

No comment, but no way to accept as "affirmative" without accepting all as "affirmative in the ballot portal.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 3/2/2016 2:25 PM

Page 72 of 75

Page 73: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

First Revision No. 1505-NFPA 5000-2015 [ New Section after 55.12 ]

55.13 Risk Analysis for Mass Notification Systems.

55.13.1 Where Required.

Where required by another section of this Code , a risk analysis for mass notification systems shall be provided in accordance withthe requirements of NFPA 72 and the provisions of 55.13.2 through 55.13.4 .

55.13.2 Considerations.

The risk analysis required by 55.13.1 shall additionally address all of the following considerations:

(1) Fire and non-fire emergencies

(2) Specific nature and anticipated risks of each facility

(3) Characteristics of associated buildings, areas, spaces, campuses, equipment, and operations

55.13.3 Emergency Communications System.

An emergency communications system in accordance with NFPA 72 shall be provided where the need for such a system is identifiedby the risk analysis required by 55.13.1 , commensurate with the likelihood, vulnerability, magnitude, and potential consequences ofemergencies.

55.13.4 Emergency Action Plan.

The completed emergency action plan shall be used for the design guideline for the mass notification/emergency communicationssystem.

Submitter Information Verification

Submitter Full Name: BLD-BSF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 12:08:23 EDT 2015

Committee Statement and Meeting Notes

CommitteeStatement:

The purpose of this revision is to provide a requirement to conduct a risk analysis and create an emergency action plan for thefacility. The need for effective emergency communications in the United States came into sharp focus in the 20th century inresponse to threats to homeland security and our educational occupancies. We have learned from the recent incidents that occurredin our college/university campuses and other buildings, and have created installation guidelines to be followed for life safety. [Aurora,CO. Theater 2012; Columbine 1999; Virginia Tech 2007; Sandy Hook 2012; Weather Tornadoes/Storms]. //

The National Fire Protection Association (NFPA) School Safety, Codes and Security Workshop, was held December 3–4, 2014, inCollege Park, Maryland, and was sponsored and hosted by NFPA. This report highlights the need for real time communicationsystems in appropriate occupancies. //

NFPA 72, National Fire Alarm and Signaling Code, has a chapter dedicated to Emergency Communication Systems. This containsthe detailed information on the risk analysis and emergency action plan as required in the above proposed sections. //

This is NOT intended to require a mass notification system. There are many elements contained within a mass notification syste, theprocess of the risk analysis will outline what is needed based on risk and engineering study for the occupancy. It will be theresponsibility of the occupancy to react to the risk assessment. //

A task group has been appointed to further review the location of the material in Ch. 55. The committee requests the CorrelatingCommittee review this action in conjunction with related actions by the TC on Fundamentals and the occupancy committees toensure the provisions are appropriately coordinated. The committee also requests the CC review the scope of BLD-BSF torecommend any needed changes to accommodate the addition of the proposed language. //

The task group will also address the reference to an emergency action plan, which is not currently required by NFPA 5000.

ResponseMessage:

Public Input No. 73-NFPA 5000-2015 [New Section after 55.2]

Ballot Results

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 6/1/2016 9:59 AM

Page 73 of 75

Page 74: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

This item has passed ballot

28 Eligible Voters

5 Not Returned

23 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Chen, Flora F.

Donga, Paul M.

Grill, Raymond A.

Noveh, James

Szmanda, Michael R.

Affirmative All

Bradley, Harry L.

Brock, Pat D.

Dale, Stephen E.

Hagood, Claudia

Hammerberg, Thomas P.

Hugo, Jeffrey M.

Hutton, Claude O.

Jardin, Joseph M.

Kellett, Michael

Killian, David A.

Klepitch, David L.

Larrimer, Peter A.

Lazarz, Daniel J.

Moore, Wayne D.

Nuschler, Gary L.

Panowitz, Scott E.

Reiswig, Rodger

Roberts, Richard Jay

Ruchala, Kurt A.

Shudak, Lawrence J.

Warner, Todd W.

Wren, Carl D.

Wyatt, David M.

Editorial Comment

Click here

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 6/1/2016 9:59 AM

Page 74 of 75

Page 75: AGENDA NFPA Technical Committee on Industrial, … · AGENDA NFPA Technical Committee on Industrial, Storage, and Miscellaneous Occupancies NFPA 101 and NFPA 5000 Second Draft …

Committee Input No. 5003-NFPA 5000-2015 [ New Section after 31.6.13.3 ]

31.6.13.XX Structural integrity of Airport Traffic Control Towers exceeding 75 ft in height.(reserved)

31.6.13.XX.1 Walls. (reserved)

31.6.13.XX.2 Wall materials. (reserved)

31.6.13.XX.3 Concrete and masonry walls. (reserved)

31.6.13.XX.4 Other walls. (reserved)

31.6.13.XX.5 Sprayed fire-resistive materials (SFRM). (reserved)

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 25 14:35:21 EDT 2015

Committee Statement

CommitteeStatement:

This Committee Input adds requirements for structural integrity/impact resistance of AirportTraffic Control Towers, with a focus on interior exit stairs and elevator hoistways. This isbeing included as a placeholder so the topic of structural integrity can be developed furtherduring the Second Draft phase. The committee is seeking additional public comment on theissue.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 1 10/26/2015 2:29 PM

Page 75 of 75