Upload
others
View
37
Download
4
Embed Size (px)
Citation preview
MAINTENANCE NOTICE
NM-259 index 01 Page 1/48 March 2014
ACS LED SIGNALLING UNIT
www.definox.com
Version AS-I 2.1& 2.0 2I/1O & 4I/3O
Linear sensor version (AS-I or multi-voltage) 1I + linear sensor/3 O
Terminal version 2I/1O & 2I/3O
Multi-voltage version 2I/1O
ACS LED: Advanced
Control System
Double-acting (AS-I, multi-voltage, terminal) 2I/1O
MAINTENANCE NOTICE
NM-259 index 01 Page 2/48 March 2014
TABLE OF CONTENTS
1 CHANGE MANAGEMENT 4
2 SAFETY 5
2.1 Important information 5
2.2 General information 5
3 INTRODUCTION 6
3.1 Disassembling the signalling unit 6
3.1.1 Disassembling the unit/actuator 6
3.1.2 Disassembling the unit components 7
3.2 Reassembling the signalling unit 8
3.2.1 Reassembling the unit components 8
3.2.2 Reassembling the unit/actuator 10
Reassembling connector - base/actuator 10
Reassembling the cover 10
4 TERMINAL VERSIONS – 24VDC 11
4.1 Wiring to PLC & signalling unit internal wiring 11
4.1.1 Version with 2 sensors/1 solenoid valve 11
4.1.2 Version with 2 sensors/3 solenoid valves 12
4.2 Meaning of the LEDs in the upper part of the LED module 13
4.3 Electrical specifications 13
5 MULTI-VOLTAGE MODULE VERSIONS 14
5.1 The multi-voltage LED module functions 14
5.2 Selecting the multi-voltage LED module power supply version 14
5.3 24 VDC modules 15
5.3.1 Description of the different Input/Output wirings 15
5.3.2 Wiring diagrams 16
5.4 LED modules with 24VAC, 48VAC or 48VDC power supply 17
5.4.1 Description of the different Input/Output wirings 17
5.4.2 Wiring diagrams 18
5.5 Wiring to PLC & signalling unit internal wiring 20
5.6 Meaning of the LEDs in the upper part of the LED module 20
5.7 Technical specifications of the multi-voltage modules 21
5.8 1ST level maintenance 22
5.8.1 Power ON indicator light is off 22
5.8.2 Fault LED illuminated or flashing 22
5.8.3 Testing the solenoid valve 22
5.8.4 Testing the sensors 22
6 AS-i MODULE VERSIONS 23
6.1 Wiring to AS-i network 23
6.2 Internal wiring of the signalling unit 24
6.2.1 Version with 2 sensors/1 solenoid valve 24
6.2.2 Version with 2 sensors/3 solenoid valves 24
6.3 The AS-i network 25
6.3.1 AS-i power supplies 25
6.3.2 AS-i address programming 25
6.4 Meaning of the LEDs in the upper part of the LED module 26
MAINTENANCE NOTICE
NM-259 index 01 Page 3/48 March 2014
6.5 Meaning of I/O bits via AS-i 26
6.6 Technical specifications of AS-i modules 27
7 LINEAR SENSOR 28
7.1 Configuration and calibration 29
7.2 Calibration and configuration diagram 29
7.3 Possible faults during calibration 30
7.4 1st level maintenance 30
7.4.1 No signal from the linear sensor 30
7.4.2 Cam outside detection range 30
7.4.3 Calibration error 30
7.5 Wiring of the signalling unit 30
7.5.1 Internal wiring of the signalling unit 30
7.5.2 Description of AS-i cable 30
7.5.3 Description of the customer wiring for multi-voltage module 24 VAC / DC _ 48 VAC / DC 30
7.5.3.1 Module with 24 VDC power supply 31
7.5.3.2 Module with 24 VAC, 48 VAC, or 48 VDC power supply 32
7.6 Technical specifications of the multi-voltage linear sensor modules 34
7.7 AS-i linear sensor LED module specifications 35
7.8 Linear sensor specifications 35
8 CHANGE OF CONFIGURATION OF THE LIGHTING RETRO DATA 36
9 CONFIGURATION CHANGE: switch a valve to NC and a va lve to NO 37
10 ACS UNIT SPARE PARTS 38
10.1 ACS unit - Double-Acting - 2I/1O module - AS-I or multi-voltage, or terminal 38
10.2 ACS unit - 1SV - 2I/1O - AS-i or multi-voltage, or terminal 39
10.3 ACS unit - 2SV - module 4I/3O - AS-i, or terminal 40
10.4 ACS unit - 3SV - module 4I/3O - AS-i or terminal 41
10.5 ACS unit – 3SV - module 1I+lin. sens./3O - AS-I, or multi-voltage 42
10.6 List of ACS unit parts 43
10.7 Dimensions, assignment and reference of cams for ACS unit sensor(s) 45
10.7.1 For DPAX valves DN25 to 150 45
10.7.2 For DN8 full flow to 65 venturi DBAX valves 45
10.7.3 For DCX3 & 4 valves DN25 to 150 45
10.7.4 For VDCI PFA valves with breakaway cylinder DN38 to 150 46
10.7.5 For VDCI SP or VDCI PFA valves without breakaway cylinder DN38 to 150 46
10.7.6 For VDCI MC PFA DN38 to 125 valves 47
10.7.7 For VDCI MC SP/PMO valves DN38 to 125 47
10.7.8 For DMAX valves DN21.6 to 52 47
10.8 Dimensions, assignment and reference of cams for the linear sensor of ACS units 47
10.8.1 For VDCI MC PFA DN38 to 125 valves 47
10.8.2 For VDCI MC SP/PMO valves DN38 to 125 47
MAINTENANCE NOTICE
NM-259 index 01 Page 4/48 March 2014
1 CHANGE MANAGEMENT
CHANGES INDEX DATE PAGES INITIALS
Initial version 01 March 2014 / F. MERLET
MAINTENANCE NOTICE
NM-259 index 01 Page 5/48 March 2014
2 SAFETY
2.1 Important information
Always read the maintenance notice before manipulating the valve.
Failure to observe these instructions can result in serious bodily injury or loss of life.
This can also result in less serious injuries or damage to the equipment.
Electricity can result in serious bodily injury or loss of life.
This can also result in less serious injuries or damage to the equipment.
2.2 General information
The following advice is given to ensure optimum use of the equipment.
The tasks must be performed in the order specified.
Forbidden or permitted actions:
NOTE!
•
DANGER!
NOTE!
DANGER!
CAUTION!
OK
<0.5 m ≥ 0.5 m
NO
Cleaning
MAINTENANCE NOTICE
NM-259 index 01 Page 6/48 March 2014
DANGER!
MAINTENANCE NOTICE ACS signalling unit
3 INTRODUCTION
The ACS signalling unit fits onto NC, NO, double-acting and VDCI (double block and bleed) valves. It is available in 5 configurations: • 2I/1O or 4I/3O LED module _ AS-i 2.1 or AS-i 2.0. • Multi-voltage LED module 2I/1O _ 24 Vac/dc – 48Vac/dc. • LED module with 1I + linear sensor/3O _ AS-i 2.1 or AS-i 2.0, multi-voltage 24 Vac/dc – 48Vac/dc. • LED module 2I/1O or 4I/3O terminal. • Double-acting: 2I/1O LED terminal version; 2I/1O LED module version (AS-i or multi-voltage).
3.1 Disassembling the signalling unit
3.1.1 Disassembling the unit/actuator
Since the retro data LEDs are substantially diffusi ve, it is recommended not to look directly into the diffusion beam, otherwise there will be a risk of d azzling. CAUTION: Before starting any work on the box, it is importa nt to ensure that the mains supply is switched off, that the air supply is closed and tha t the circuit is purged.
�Disassembling the cover
• Turn 1 the cover to align the cover pin with the
pictogram, then remove the cover by pulling upwards 2.
�Disassembling connector - base/actuator
• Disconnect the air pipes from the box. • Unscrew the stuffing box assembly, locate and
disconnect the wires on the terminal or on the supply module, then remove the supply cable, or disconnect and remove the cable from the AS-i module.
• Unscrew3 the locking screw. • Turn4 the connector (with or without the cover) to
release the three keying studs of the base. • Separate5 by pulling upwards.
• Unscrew the two CHC screws. • Remove the actuator base.
NOTE!
Actuator
Cover
Connector
Base
1
1
2
2
Locking screw
3
5
4
Keying studs
MAINTENANCE NOTICE
NM-259 index 01 Page 7/48 March 2014
3.1.2 Disassembling the unit components
Before disassembling the components, locate and disconnect the wires connected to the LED terminal or multi-voltage module, and also those on the connector.
� Disassembling the module
• Unscrew the fastening screw of the LED module and remove the module.
� Dismantling the sensors
� Disassembling the SVs
• For each solenoid valve, unscrew the two fastening screws on the solenoid valve and remove the solenoid valve together with the seal.
• Unscrew the fastening screw from the sensor support sub-assembly and remove.
• Unclip and remove the upper and lower sensors from the support sub-assembly.
NOTE!
Connector
Screw
LED module 2I/1O_4I/3O or
1I+Lin. sens./3O Terminal, AS-i or
multi-voltage version
Connector
Screw
Lower sensor
Upper sensor
Sensor support sub-assembly
Connector
S.V. 2
Connector
S.V. 1
Screw
S.V. seal
S.V. 3
Screw
S.V. seal
Solenoid valve assembly
MAINTENANCE NOTICE
NM-259 index 01 Page 8/48 March 2014
� Disassembling the linear sensor (signalling unit v ersion with linear sensor)
• Remove the clamp plate to free the toothed segment
by removing the two fastening screws. 1
• Turn the linear sensor anti-clockwise to completely free the toothed segment 2.
• Pull the linear sensor upwards to disconnect it from
the signalling unit 3. 3.2 Reassembling the signalling unit
3.2.1 Reassembling the unit components
� Linear sensor specifications • Vertically fit the linear sensor in place, ensuring
that the toothed segment is still free.1 • Turn the linear sensor clockwise as far as it will
go. 2 • The toothed segment is no longer free.
• Reposition the clamp plate and fit the 2 fastening screws.3 The teeth of the plate must fit between the teeth of the toothed segment to prevent rotation.
• Tightening torque: 0.8 Nm or 8 kgf.cm
3
Linear sensor
Toothed segment not free
Toothed segment freed
2
Screw
Clamp plate
Linear sensor
1
Clamp plate teeth
Screw
Clamp plate
Linear sensor
3
1
Linear sensor
Toothed segment freed
2
Toothed segment not free
MAINTENANCE NOTICE
NM-259 index 01 Page 9/48 March 2014
� Reassembling the sensors
• Clip the upper and lower sensors on the support sub-assembly.
• Re-position the sensor support sub-assembly on the connector, fit the fastening screw.
• Tightening torque: 0.8 Nm or 8 kgf.cm. • Rewire the SVs and/or SPs on the connector. • Cam/sensor target adjustment: A fine and precise
adjustment is carried out using the adjustment screw for each sensor. The cam can be set anywhere within a range extending from the centre of the target to the full target. Adjust as needed!
� Reassembling the SVs
• Install SV1, then SV3 and lastly SV2. • Position the solenoid valve seal by aligning it with the centring pin on the connector seating plane. One side of the seal
will come up against an orientation wall. • Align the solenoid valve with the same centring pins. The body of the solenoid valve will come up against the orientation
wall or the body of the SV3. • Fit the two M2.5 fastening screws. • Tightening torque: 0.4 Nm or 4 kgf.cm
�Reassembling the module
As for removal, in reverse order:
• Position the AS-i or multi-voltage module in its housing in the connector. Fit the M3 screw on the fastening point corresponding to the module configuration.
• Tightening torque: 0.3 Nm or 3 kgf.cm
Centring pin
Alignment hole
Orientation wall
Full target
Fastening point on new unit, and version 2010.
Existing fastening point on new version of unit, and on 2010 and 2004 versions of unit.
Connector
Sensor adjustment screw
Sensor support fastening screw
Lower sensor
Upper sensor
Sensor support sub-assembly
Connector
Centre of target
MAINTENANCE NOTICE
NM-259 index 01 Page 10/48 March 2014
3.2.2 Reassembling the unit/actuator
� Reassembling connector - base/actuator As for removal, in reverse order:
• Position the base on the actuator. • Place the two M8 CHC screws. • Tightening torque: 1 Nm or 10 kgf.cm
• 1Position the connector (with or without its cover) on the keying studs on the base.
• 2Turn the connector to lock it on the base. • 3Tighten the locking screw to secure. • Connect the pneumatic system. • Remove the cover if necessary, and connect the
wiring according to the type of unit and in accordance with the diagrams given herein.
• Tighten the cable gland.
In order to ensure that it is mounted on the keying studs, position the shape with the letter "A" on the connector relative to the base as shown in the figure below:
�Reassembling the cover • As for removal, in reverse order: • 4Align the pin of the cover with the "open cover"
pictogram, and bring the cover into contact with the connector.
• 5Turn the cover in the direction of the arrow to lock the cover: move the pin above the “cover locked” pictogram.
Note: Under normal operation, the base, the connector and the cover can, if necessary, be lead-sealed by means of a wire or a screw in a hole passing through the entire signalling unit.
Locking screw
3 2
1
NOTE!
Actuator
Cover
Connector
Base
5
4
4
5
Keying studs
1
MAINTENANCE NOTICE
NM-259 index 01 Page 11/48 March 2014
Red
Black
Red
Lower sensor
Upper sensor Black
Red
Black SV1
(Main actuator)
Blue
Blue
4 TERMINAL VERSIONS – 24VDC
The terminal versions allow you to connect the sensors and the solenoid valves directly to the PLC. In this case the operating voltage of the sensors and the solenoid valves is only 24 VDC +/- 10%.
4.1 Wiring to PLC & signalling unit internal wiring
4.1.1 Version with 2 sensors/1 solenoid valve
Function
Solenoid valve 1 control (+24 VDC) (main actuator)
SV1
Solenoid valve earth SV-
Retro data valve open (PNP) I2
Retro data valve closed (PNP) I1
Sensor earth V-
+ Sensor supply (+24 VDC) V+
Function
Solenoid valve 1 control (+24 VDC) (main actuator)
SV1
Solenoid valve earth SV-
Retro data valve open (PNP) I2
Retro data valve closed (PNP) I1
Sensor earth V-
+ Sensor supply (+24 VDC) V+
Wiring version for two 3-wire sensors and 1 solenoi d valve on 2I/1O terminal (Standard version)
Wiring version for two 2-wire sensors and 1 solenoi d valve on 2I/1O terminal (Version on request)
V+ V+ V- V- I1 I2 O1 V-
Customer wiring Definox ex-works wiring
2I /1O
TERMINAL
LED
MODULE
Customer wiring Definox ex-works wiring
V+ V+ V- V- I1 I2 O1 V-
White
Black
White
Lower sensor
Upper sensor Black
Red
Black SV1
(Main actuator)
2I /1O
TERMINAL
LED
MODULE
MAINTENANCE NOTICE
NM-259 index 01 Page 12/48 March 2014
White
Black
White
Lower sensor
Upper sensor Black
Red Black
Red
Black
Red
Black
SV1 (Main actuator)
SV2 (Upper plug)
SV3 (Lower plug)
4.1.2 Version with 2 sensors/3 solenoid valves
Function
Solenoid valve 3 control (+24 VDC) (lower plug)
SV3
Solenoid valve 2 control (+24 VDC) (upper plug)
SV2
Solenoid valve 1 control (+24 VDC) (main actuator)
SV1
Solenoid valve earth SV-
Retro data valve open (PNP) I2
Retro data valve closed (PNP) I1
Sensor earth V-
+ Sensor supply (+24 VDC) V+
Function
Solenoid valve 3 control (+24 VDC) (lower plug)
SV3
Solenoid valve 2 control (+24 VDC) (upper plug)
SV2
Solenoid valve 1 control (+24 VDC) (main actuator)
SV1
Solenoid valve earth SV-
Retro data valve open (PNP) I2
Retro data valve closed (PNP) I1
Sensor earth V-
+ Sensor supply (+24 VDC) V+
Wiring version for two 2-wire sensors and 3 solenoi d valve on 2I/1O terminal (Version on request)
Wiring version for two 3-wire sensors and 3 solenoi d valves on 2I/3O terminal (Standard version)
V+ V+ V- V- I1 I2
O1
V-
I3 I4
O2 O3
V-
Customer wiring Definox ex-works wiring
V+ V+ V- V- I1 I2
O1
V-
I3 I4
O2 O3
V-
Red
Black
Red
Lower sensor
Upper sensor Black
Red
Black
Red
Black
Red
Black
SV1 (Main actuator)
SV2 (Upper plug)
SV3 (Lower plug)
Blue
Blue
Customer wiring
Definox ex-works wiring
2I /3O
TERMINAL
LED
MODULE
2I /3O
TERMINAL
LED
MODULE
MAINTENANCE NOTICE
NM-259 index 01 Page 13/48 March 2014
4.2 Meaning of the LEDs in the upper part of the LED mo dule
The upper part of the LED modules is fitted with LEDs that display the status of the inputs/outputs.
4.3 Electrical specifications General specifications
Supply voltage
• Sensors
• Solenoid valves Current consumed for: 1 active solenoid valve, 1 active sensor, and lighting retro data (upled) Electromagnetic compatibility Temperature
• operating • storage/transport
24 VDC +/- 10% 24 VDC +/- 10%
80 mA max
EN61000-6-2, EN61000-6-4 -10 to +60 °C -40 to +85 °C
Sensors
Supply voltage Output current Inductive sensor connection 2-wire: on request 3-wire: standard
24 VDC +/- 10% 50 mA max Yes
Solenoid valves Supply voltage Current consumed Switching frequency on inductive load
24 VDC +/- 10% 30 mA max 0.5 Hz
Electrical connections to PLC Connection type Conductor section
Spring cage terminal 0.75 mm² max. A cross section of 0.5 mm² is sufficient. Cable diameter: 4.5 to 10 mm.
On the upper part of the LED
module Version LED
status Meaning LED colour
parameterisation facility
RED LED * 2I/1O & 2I/3O Fixed Yes
BLUE LED * 2I/1O & 2I/3O Fixed Status of the valve closed sensor Yes
GREEN LED* 2I/1O & 2I/3O Fixed Status of the valve open sensor Yes
Main Actuator 2I/1O & 2I/3O Fixed Status of the main actuator solenoid valve output. Yellow LED illuminated = Solenoid valve controlled
No
PWR 2I/1O & 4I/3O Fixed Power supply present No
UPPER PLUG 2I/1O
2I/3O Fixed Status of the solenoid valve output of the actuator upper plug. Yellow LED illuminated = Solenoid valve controlled
No
LOWER PLUG 2I/1O
2I/3O Fixed Status of the solenoid valve output of the actuator lower plug. Yellow LED illuminated = Solenoid valve controlled
No
* parameterisation of the lighting retro data corresponding to ex-works parameterisation. In order to ensure standard-compliance for any modification(s) of the colours of the lighting retro data, refer to the “lighting retro data colour parameterisation” table.
MAINTENANCE NOTICE
NM-259 index 01 Page 14/48 March 2014
5 MULTI-VOLTAGE MODULE VERSIONS
The 24VAC/DC_48VAC/DC multi-voltage LED modules provide the interface between the peripherals (solenoid valves, sensors) and the command control system (PLC). Two different voltages can be used simultaneously on the module.
Terminology:
• The input signals correspond to the solenoid valve commands. • The output signals correspond to the retro data signals from the sensors.
5.1 The multi-voltage LED module functions
• It adapts the electrical signals between the PLC and the sensors/solenoid valve. Reminder: the sensors and the solenoid valve mounted in the signalling unit operate using 24 VDC only.
• The retro data signal type can be selected by means of jumpers positioned as required: PNP, NPN or NO.
• In the upper part, it displays the status of the SVs, the presence of the module power supply, the status of the valve, together with the faults. The latter two are also indicated, if required, by lighting retro data in the upper part of the signalling unit.
� It must be ensured that the connection cable has su fficient conductors so that the
module has a continuous power supply! (6 mini condu ctors for a unit with 1 solenoid valve and 2 sensors: 2 for the module power supply, 2 for the sensor retro data, 2 for the solenoid valve. To be adapted according to the numb er of solenoid valves).
5.2 Selecting the multi-voltage LED module power supply version
According to the voltages used on the installation, a power supply voltage will be chosen that will determine the choice of the different wiring diagrams.
Continuous power supply available at
24VDC?
Signal voltages
Solenoid valve 24VAC, 48VAC or 48VDC
and Sensor retro data
24VAC, 48VAC or 48VDC
Note: the supply voltage must be common to the solenoid valve or sensor
voltages.
Sensor retro data 24VDC?
Signal voltages
Solenoid valve 24VDC
and Sensor retro data
24VDC, 24VAC, 48VAC or 48VDC
YES NO
NO YES
See choice of different Input/Output wirings Module supplied at 24VDC
See choice of different Input/Output wirings Module supplied at 24VAC or 48 VDC or 48 VAC
Signal voltages
Solenoid valve 24VDC, 24VAC, 48VAC or 48VDC
and Sensor retro data
24VDC
I/O PLC
MULTI-VOLTAGE MODULE
Outputs
Inputs
Sensors
Solenoid valves
IMPORTANT
MAINTENANCE NOTICE
NM-259 index 01 Page 15/48 March 2014
5.3 24 VDC modules
• The electrical supply of the multi-voltage LED module must be 24 VDC and continuous . • The solenoid valve signals or the sensor signals may have a voltage (24VAC, 48VDC or 48VAC) other than 24VDC. •
5.3.1 Description of the different Input/Output wirings
The table below gives the following 8 possible wiring diagrams:
� the different voltages, � the signal types (PNP, NPN, NO, connector used, etc.).
Example: - Solenoid valve signals: 48VAC + independent connector, - Sensor signals + fault: 24VDC PNP output. The diagram to be used is therefore number 5.
Notes :
� Initially, the module is configured to be wired according to diagram number 3. � The bold marks on the wiring diagrams represent the jaws of the CO and CI connectors (use tool
7708097 to remove or move the jaws).
2-point wiring jaws that link:
� B1 and B2 imperative to 24 VDC supply. (Must be completely removed for other supply voltages).
� The CI and CO connectors to V+ or V-.
Table of the 8 possible wiring diagrams
SOLENOID VALVE SIGNALS
Connector (CO)
24 VDC Independent
SE
NS
OR
SIG
NA
LS +
FA
ULT
Output Voltage V+ V-
PNP
24 VDC Diagram No. 1 Diagram No. 3 Diagram No. 5
48 VDC Diagram No. 8 Diagram No. 7
NPN
24 VDC Diagram No. 2 Diagram No. 4 Diagram No. 6
48 VDC Diagram No. 8 Diagram No. 7
NO 24 VAC, 48 VAC Diagram No. 8 Diagram No. 7
NOTE!
CAUTION!
MAINTENANCE NOTICE
NM-259 index 01 Page 16/48 March 2014
5.3.2 Wiring diagrams
PNP OUTPUT SENSORS NPN OUTPUT SENSORS
PNP OUTPUT SENSORS NPN OUTPUT SENSORS
PNP, NPN OR NO OUTPUT SENSORS
O1
I2 I1
V+ V-
O1
I2
I1
V+
V-
DIAGRAM No. 1 Signals:
- Solenoid valves: connector (CO) to 24VDC - Sensors: 24VDC PNP outputs
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
I2 I1
V+ V-
DIAGRAM No. 2 Signals:
- Solenoid valves: connector (CO) to 24VDC - Sensors: 24VDC NPN outputs
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position of the valve
Control of the valve
SV Sensor
O1
I2 I1
V+
V-
DIAGRAM No. 3 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 24VDC PNP outputs
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor DIAGRAM No. 4 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 24VDC NPN outputs
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
CO
I2
I1
V+ V-
DIAGRAM No. 5 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 24VDC PNP outputs
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position of the valve
Control of the valve
SV Sensor
O1
CO
I2
I1
V+
V-
DIAGRAM No. 6 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 24VDC NPN outputs
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position of the valve
Control of the valve
SV Sensor
O1
I2
I1
CI
V+
V-
DIAGRAM No. 7 Signals:
- Solenoid valves: connector (CO) to GND - Sensor: PNP, NPN or NO outputs
independe nt connector.
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position of the valve
Control of the valve
SV Sensor
O1
I2
I1
CI
V+ V-
DIAGRAM No. 8 Signals:
- Solenoid valves: connector (CO) to 24VDC - Sensors: PNP, NPN or NO outputs
independent connector.
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power suppl y
Position of the valve
Control of the valve
SV Sensor
MAINTENANCE NOTICE
NM-259 index 01 Page 17/48 March 2014
5.4 LED modules with 24VAC, 48VAC or 48VDC power supply
• The electrical supply of the multi-voltage LED module must be 24 VAC, 48 VAC or 48 VDC, and continuous. • The solenoid valve signals or the sensor signals may have a voltage (24VAC, 48VAC or 48VDC) different from the power
supply.
5.4.1 Description of the different Input/Output wirings
The table below gives the following 14 possible wiring diagrams:
� the different voltages, � the signal types (PNP, NPN, NO, connector used, etc.).
Example:
- Power supply 48 VAC, - Solenoid valve signals: 48 VAC, - Sensor signals + fault: 24 VAC NO outputs.
The diagram to be used is therefore number 6.
Notes :
� Initially, the LED module is configured to be wired according to diagram number 1 or 2. � The bold marks on the wiring diagrams represent the jaws of the CO and CI connectors (use tool
7708097 to remove or move the jaws).
2-point wiring jaws that link:
� the CI and CO connectors to V+ or V-.
� Apart from a 24 VDC power supply, it is imperative to remove the comb wiring between B1 and B2, otherwise there is a risk of permanent damage to the module.
Table of the 14 possible wiring diagrams
SOLENOID VALVE SIGNALS
Connector (CO)
SE
NS
OR
SIG
NA
LS
+ F
AU
LT
Output Voltage 24 VAC 48 VAC 48 VDC
Independent V+ V-
NO 24 VAC Diagram No. 1 Diagram No. 6 Diagram No. 13
Diagram No. 14 Diagram No. 3
NO 48 VAC Diagram No. 5 Diagram No. 2 Diagram No. 13
Diagram No. 14 Diagram No. 4
PNP
48 VDC
Diagram No. 5 Diagram No. 6 Diagram No. 7
Diagram No. 8 Diagram No. 11
NPN Diagram No. 5 Diagram No. 6 Diagram No. 9
Diagram No. 10 Diagram No. 12
NOTE!
CAUTION!
CAUTION!
MAINTENANCE NOTICE
NM-259 index 01 Page 18/48 March 2014
5.4.2 Wiring diagrams
NO OUTPUT SENSORS
PNP, NPN OR NO OUTPUT SENSORS (independent connector)
O1
I2
I1
CI
24
Vac
DIAGRAM No. 5 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 48VDC PNP or NPN outputs 48VAC NO outputs
24 VAC
(V-)
(V+)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
I2
I1
CI
48
Vac
DIAGRAM No. 6 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 48VDC PNP or NPN outputs 24VAC NO outputs
48 VAC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
I2
I1
CO
48
Vac
DIAGRAM No. 4 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 48VAC NO outputs
Power supply
Position
of the valve
Control of the valve
SV Sensor
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
48 VAC
O1
I2
I1
48
Vac
DIAGRAM No. 2 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 48VAC NO outputs
Power supply
Position
of the valve
Control of the valve
SV Sensor
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
48 VAC
CO
O1
I2
I1
24 Vac
DIAGRAM No. 3 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 24VAC NO outputs
Power supply
Position
of the valve
Control of the valve
SV Sensor
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
24 VAC
O1
I2 I1
24 Vac
DIAGRAM No. 1 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 24VAC NO outputs
Power supply
Position
of the valve
Control of the valve
SV Sensor
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
24 VAC
MAINTENANCE NOTICE
NM-259 index 01 Page 19/48 March 2014
PNP OUTPUT SENSORS
O1
I2
I1
V+
V-
O1
I2
I1
CI
V+
V-
O1
I2
I1
V+
V-
DIAGRAM No. 7 Signals:
- Solenoid valves: connector (CO) to 48VDC - Sensors: 48VDC PNP outputs
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
I2
I1
V+
V-
DIAGRAM No. 8 Signals:
- Solenoid valves: connector (CO) to 48VDC - Sensors: 48VDC NPN outputs
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
DIAGRAM No. 9 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 48VDC PNP outputs
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
I2
I1
V+
V-
DIAGRAM No. 10 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 48VDC NPN outputs
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
CO
I2
I1
V+
V-
DIAGRAM No. 11 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 48VDC PNP outputs
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
CO
I2
I1
V+
V-
DIAGRAM No. 12 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 48VDC NPN outputs
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV Sensor
O1
I2
I1
CI
V+
V-
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
DIAGRAM No. 13 Signals:
- Solenoid valves: connector (CO) to 48VDC - Sensors: NO outputs independent connector
Power supply
Position
of the valve
Control of the valve
SV Sensor
NPN OUTPUT SENSORS
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
DIAGRAM No. 14 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: NO outputs independent connector
Power supply
Position
of the valve
Control of the valve
SV Sensor
NO OUTPUT SENSORS
MAINTENANCE NOTICE
NM-259 index 01 Page 20/48 March 2014
White
Black
White
Lower sensor
Upper sensor Black
Red
Black SV1
(Main actuator)
5.5 Wiring to PLC & signalling unit internal wiring
5.6 Meaning of the LEDs in the upper part of the LED mo dule
The upper part of the LED modules is fitted with LEDs that display the status of the inputs/outputs, as well as the presence of the power supply or a local fault.
On the upper part of the module Status Meaning
Colour parameterisation
facility
RED LED * Fixed Power supply fault
Yes Flashing Overload or short circuit fault on a
peripheral
BLUE LED * Fixed Status of the valve closed sensor Yes
GREEN LED* Fixed Status of the valve open sensor Yes
Main Actuator Fixed Status of the main actuator solenoid valve output. Yellow LED illuminated = Solenoid valve controlled
No
PWR Fixed Power supply present Green LED illuminated = module power supply on
No
UPPER PLUG
No
LOWER PLUG
No
* parameterisation of the lighting retro data corresponding to ex-works parameterisation. For any modification(s) of the colours of the lighting retro data in order to ensure standard-compliance, refer to the “lighting retro data colour parameterisation” table.
Function
Retro data valve open (PNP) I2
Retro data valve closed (PNP) I1
Solenoid valve control 1 (main actuator) O1
Retro data error FLT
Solenoid valve connector command (see wiring diagrams) CO
Shunt to be implemented with B1, if module has 24 VDC power supply B2
Shunt to be implemented with B2, if module has 24 VDC power supply B1
Common retro data (see wiring diagrams) CI
+ Power supply V+
- Power supply V-
MULTI-
VOLTAGE
LED
MODULE
FOR
UNIT
ACS
OR
ICS
2I/1O
VERSION
V+ V+ V- V- I1 I2 O1 V-
Customer wiring Definox ex-works wiring
MAINTENANCE NOTICE
NM-259 index 01 Page 21/48 March 2014
5.7 Technical specifications of the multi-voltage modul es
General specifications Supply voltage
• 24 VDC modules
• 24 VAC – 48 VAC/DC modules Current consumed for 1 active solenoid valve and 1 active sensor Electromagnetic compatibility Temperature
• operating • storage/transport
24 VDC +/- 5% 24 VAC – 48 VAC/DC +/- 10% ≤ 80 mA DC (24 VDC supply) ≤ 155 mA AC (24 VAC supply) ≤ 60 mA DC (48 VDC supply) ≤ 115 mA AC (48 VAC supply) EN61000-6-2, EN61000-6-4 -10 to +60 °C -40 to +85 °C
Diagnostic functions Supply voltage display Unit status display
Green “POWER” LED Red “FAULT” LED
Sensor inputs Nominal input voltage 2 wire (std) and 3 wire inductive sensor connection
24 VDC Yes
Solenoid valve outputs Output voltage Output current Switching frequency on inductive load Short-circuit protection
24 VDC 50 mA max 0.5 Hz Yes
Electrical connections to PLC Connection type Conductor section
Spring cage terminal 0.75 mm² max. A cross section of 0.5 mm² is sufficient. Cable diameter: Refer to the cable gland specifications to find out the maximum aperture diameter for the cable.
Solenoid valve signals from the PLC Number Nominal input voltage +/- 10% Minimum current Signal type
1 to 3 24 VAC/DC to 48 VAC/DC ≥ à 6mA PNP or NPN
Sensor signals to PLC Number Fault signal Output voltage +/- 10% Output current Signal type
1 to 4 Yes 24 VAC/DC to 48 VAC/DC 50 mA max PNP, NPN or NO
MAINTENANCE NOTICE
NM-259 index 01 Page 22/48 March 2014
5.8 1ST level maintenance
5.8.1 Power ON indicator light is off
• Check that the LED module power supply is wired correctly. • Check that the voltage between V+ and V- (two-stage terminal) is equal to 24 VDC +/- 5% or 24 VAC – 48
VAC/DC +/- 10% depending on the voltage chosen to power the LED module.
If the result of these actions is negative, replace the unit.
5.8.2 Fault LED illuminated or flashing
Reminder: red LED in ex-works configuration. • Red LED flashing = Overload or short circuit on sensor or solenoid valve. • Disconnect the sensor/solenoid valve connector and check that the fault has disappeared. Check the
sensors and solenoid valve one by one. • Red LED illuminated = supply voltage too low or overload or short circuit on a peripheral of the LED
module (faulty solenoid valve, etc.). • Check that the voltage between V+ and V- (two-stage terminal) is equal to 24 VDC +/- 5% or 24 VAC – 48
VAC/DC +/- 10% depending on the voltage chosen to power the LED module. • Disconnect the sensor/solenoid valve connector and check that the fault has disappeared. Check the
sensors and solenoid valve one by one.
5.8.3 Testing the solenoid valve
• The green LED on the LED module must be illuminated. • Control the solenoid valve coil using the PLC. • Measure the voltage on the peripheral connector using a voltmeter between the terminals O1 and CO.
Check that this voltage corresponds to the control voltage of the solenoid valves. If the result of this step is negative, check the wiring between the LED module and the PLC.
• If the “Main actuator” LED is illuminated, measure the voltage on the peripheral connector between the terminals SV1 and SV-. This voltage must be between 20 and 24VDC.
• If this voltage is correct, change the solenoid valve. • If not, disconnect the peripheral connector. If the “Main actuator” LED is extinguished, change the LED
module.
5.8.4 Testing the sensors
The LED module must be connected electrically to the PLC.
• Use a voltmeter to check that the voltage between terminals V+ and V- on the sensor side of the terminal is between 20 and 24 VDC.
• Place a metallic object in front of sensor target to check that the LED on the sensor illuminates correctly. • The LED does not illuminate: change the sensor and restart the tests at step 1. • The LED illuminates = measure the voltage using a voltmeter between terminals V- and I1 or I2 on the
peripheral terminal of the LED module in order to check that the voltage is ≥12 VDC. • Check that the LED on the unit corresponding to the sensor is illuminated correctly. • LED extinguished = change the LED module. • LED illuminated = check the voltage on the two stage connector between the terminals I1 and CI or I2 and
CI depending on the sensor to be tested. • If the voltage is correct, check the wiring between the LED module and the PLC, otherwise change the
LED module.
MAINTENANCE NOTICE
NM-259 index 01 Page 23/48 March 2014
6 AS-i MODULE VERSIONS
The AS-i LED modules provide the interface between the peripheral devices (solenoid valves, sensors) and the command control system (PLC) via the AS-i network. AS-i LED modules are compatible as standard with AS-i 2.1 and can on request be supplied in version 2.0 (limited to 31 slaves).
6.1 Wiring to AS-i network
The connection to the AS-i network is established via an M8 - M12 lead [1] and a vampire clip [3] (plastic standard – stainless steel optional).
The M12 connector can be used to disconnect the module from the AS-i network and to program the network address via the addressing terminal(7008215). If a vampire clip is not used temporarily or permanently, then insert the M12 stopper (7008123) [2].
Note: • At the end of the AS-i network, insert the seal
(7008228) [4] in the plastic vampire clip.
4
1
2
3
CAUTION!
MAINTENANCE NOTICE
NM-259 index 01 Page 24/48 March 2014
White
Black
White
Lower sensor
Upper sensor Black
Red
Black SV1
(Main actuator)
White
Black
White
Lower sensor
Upper sensor Black
Red Black
Red
Black
Red
Black
SV1 (Main actuator)
SV2 (Upper plug)
SV3 (Lower plug)
6.2 Internal wiring of the signalling unit
6.2.1 Version with 2 sensors/1 solenoid valve
6.2.2 Version with 2 sensors/3 solenoid valves
LED
MODULE
ASi
2I/1O
V+ V+ V- V- I1 I2 O1 V-
V+ V+ V- V- I1 I2
O1
V-
I3 I4
O2 O3
V-
LED
MODULE
ASi
4I/3O
Customer wiring Definox ex-works wiring
Customer wiring Definox ex-works wiring
MAINTENANCE NOTICE
NM-259 index 01 Page 25/48 March 2014
6.3 The AS-i network
The AS-i network can be wired according to a tree configuration, a linear configuration with sections or a star configuration.
These three architectures can be used simultaneously.
6.3.1 AS-i power supplies
An AS-i power supply is specific to the AS-i network.
• Output voltage between 31.6 VDC and 29.5 VDC • Output current:
− 4A for 31 installed slaves − 8A for 62 installed slaves
I = (No. of AS-i modules x 0.070) + gateway intensity
6.3.2 AS-i address programming
The AS-i address for the module is programmed either via the AS-i master (PLC coupling, gateway, etc.) or via the addressing terminal (7008215).
The M12 connector can be used to disconnect the module from the AS-i network and to program the network address via the 7008215 addressing terminal.
Notes:
The module is programmed to address 0 by default. Do not program two modules with the same network address. The AS-i 2.0 modules have an address between 1 and 31. The AS-i 2.1 modules have an address between 1A and 31A and 1B and 31B.
OR
OR
NOTE!
MAINTENANCE NOTICE
NM-259 index 01 Page 26/48 March 2014
6.4 Meaning of the LEDs in the upper part of the LED mo dule
The upper part of the LED modules is fitted with LEDs that display the status of the inputs/outputs, as well as the presence of the power supply, a zero addressing or a local fault.
6.5 Meaning of I/O bits via AS-i Bit I 0 = 1 when the valve closed sensor is at 1.
Bit I 1 = 1 when the valve open sensor is at 1.
Bit I 2 = 1 when the upper plug opening sensor is at 1.
Bit I 3 = 1 when the lower plug opening sensor is at 1.
Bit O0 = 1 to control the main actuator solenoid valve.
Bit O1 = 1 to control the upper plug opening solenoid valve.
Bit O2 = 1 to control the lower plug opening solenoid valve.
On the upper part of the LED module Version LED
status Meaning LED colour
parameterisation facility
RED LED * 2I/1O
4I/3O or 1I + linear sensor/3O Fixed Module with address 0
Yes Flashing AS-i power supply fault, or overload or
short circuit on a peripheral
BLUE LED * 2I/1O
4I/3O or 1I + linear sensor/3O Fixed Status of the valve closed sensor Yes
GREEN LED* 2I/1O
4I/3O or 1I + linear sensor/3O Fixed Status of the valve open sensor Yes
Main Actuator 2I/1O 4I/3O or 1I + linear sensor/3O Fixed
Status of the main actuator solenoid valve output. Yellow LED illuminated = Solenoid valve controlled
No
PWR 2I/1O 4I/3O or 1I + linear sensor/3O Fixed
Power supply present Green LED illuminated = module power supply on
No
UPPER PLUG
2I/1O
4I/3O or 1I + linear sensor/3O Fixed Status of the solenoid valve output of the actuator upper plug. Yellow LED illuminated = Solenoid valve controlled
No
LOWER PLUG
2I/1O
4I/3O or 1I + linear sensor/3O Fixed Status of the solenoid valve output of the actuator lower plug. Yellow LED illuminated = Solenoid valve controlled
No
* parameterisation of the lighting retro data corresponding to ex-works parameterisation. In order to ensure standard-compliance for any modification(s) of the colours of the lighting retro data, refer to the “lighting retro data colour parameterisation” table.
UPLED version 1I + linear sensor/3O
UPLED version 2I/1O or 4I/3O
MAINTENANCE NOTICE
NM-259 index 01 Page 27/48 March 2014
6.6 Technical specifications of AS-i modules
General specifications AS-i supply voltage Current consumed for 1 active solenoid valve and 1 active sensor
Electromagnetic compatibility Temperature
• operating • storage/transport
25 … 31.6 VDC ≤ 95 mA EN61000-6-2, EN61000-6-4 -10 to +60 °C -40 to +85 °C
Communication specifications
Protocol Profile AS-i 2.1 Profile AS-i 2.0 AS-i certificate according to C.S.3.0_Revision 4
Complies with AS-i specification V3.0 Rev. 4 IO code: 7 ID code: A ID2 code: E IO code: 7 ID code: 0 ID2 code: F N° 101001
Diagnostic functions AS-i voltage display Module status display
Green “POWER” LED Red “FAULT” LED
Sensor inputs Nominal input voltage 2-wire inductive sensor connection
24 VDC Yes
Solenoid valve output Output voltage Output current Switching frequency on inductive load Short-circuit protection
24 VDC 50 mA max 0.5 Hz Yes
MAINTENANCE NOTICE
NM-259 index 01 Page 28/48 March 2014
7 LINEAR SENSOR
The linear sensor, with an operating range of 80 mm, detects three valve positions:
• valve closed, • valve open, • lower plug opening
Note: upper plug opening is detected by means of a sensor external to the unit, located in the lantern of the valve: for more details, see the maintenance notice section IT-TDFX-164. A green LED on the top of the linear sensor indicates its status:
• Power LED illuminated = sensor switched on, • Power LED flashing = cam outside detection range.
Status and meaning of the elements on the upper par t of the module according to the cam position
On the upper part of the module Version LED status Meaning
LED colour parameterisation
facility
RED LED * linear sensor/3O Fixed Power supply fault Yes
Flashing Overload or short circuit fault on a peripheral
BLUE LED * linear sensor/3O Fixed Status of the valve closed sensor Yes Flashing Status of the enabled lower plug sensor Yes
GREEN LED* linear sensor/3O Fixed Status of the valve open sensor Yes Flashing Status of the enabled upper plug sensor Yes
Main Actuator linear sensor/3O Fixed Status of the main actuator solenoid valve output. Yellow LED illuminated = Solenoid valve controlled
No
PWR linear sensor/3O Fixed Power supply present Green LED illuminated = module power supply on No
UPPER PLUG linear sensor/3O Fixed Status of the solenoid valve output of the actuator upper plug. Yellow LED illuminated = Solenoid valve controlled
No
LOWER PLUG linear sensor/3O Fixed Status of the solenoid valve output of the actuator lower plug. Yellow LED illuminated = Solenoid valve controlled
No
MODE PB linear sensor/3O “Mode” pushbutton for calibration. SET PB linear sensor/3O “Set” pushbutton for calibration.
* parameterisation of the lighting retro data corresponding to ex-works parameterisation.
Cam out of flashing range of LEDs C,D and F.
NOTE: The colours mentioned opposite and in the table above correspond to the ex-works lighting retro data configuration! In order to ensure standard-compliance for any modification(s) of the colours of the lighting retro data, refer to the “lighting retro data colour parameterisation” table.
Valve closed
Valve closed + lower plug
Valve open
Blue LEDs illuminated
Blue LEDs blinking, and lower plug LED illuminated
Green, blue and red LEDs extinguished
Green LEDs and main actuator LED illuminated
Linear sensor
Cam
Detection range
Unit
MAINTENANCE NOTICE
NM-259 index 01 Page 29/48 March 2014
B
A
C
D
E
F
G
H
I
SET PB MODE PB
7.1 Configuration and calibration
The module has two operating modes: • Normal mode: this mode displays the status of inputs and outputs by default • Configuration mode: this mode is used for calibrating the sensor with the valve, and for
enabling or disabling the lower plug opening, valve closed and valve open retro data functions.
A learning phase must be performed for the sensor to memorize the operating positions of the associated valve. This calibration of the valve is performed manually or automatically. See installation guide IT-TDFX-260
Note:
• A double block and bleed valve fitted with a linear sensor version ACS signalling unit is calibrated ex-works. The lower plug, valve closed and valve open functions are enabled.
• All of the stages are shown in the document “Calibration and configuration sequence diagram”.
7.2 Calibration and configuration diagram
Hold down the Mode pushbutton Briefly press < 2 seconds Hold down the Set pushbutton Hold down the Mode pushbutton Hold down > 5 seconds Hold down the Set pushbutton
M*
M
S
S*
CONFIGURATION STATUS
Calibration
LEDs A and B flashing.
********************************
LEDs D,E,G
Illuminated: function enabled
Flashing: function disabled
Calibration function Exit configuration mode
M
M*
Exit configuration mode
CAUTION!
Entering configuration mode
will disable the solenoid valve
outputs
NORMAL MODE
LED A illuminated
LED B extinguished
***************************
LEDs C,D,E,F,G,H and
I illuminated according
to valve status.
Configuration mode (if keyboard unlocked otherwise LED B flashes for 3s) Unlocking/locking the keyboard
Fault acknowledgement if fault during
calibration
M*
M*
S*
S
+
CALIBRATION
FUNCTION
Calibration
LEDs A and B flashing.
******************************
LEDs D,E,G flashing
Bypass calibration function Calibration Exit configuration
M
S
M
*
LOWER PLUG OPENING
Calibration
LEDs A and B flashing.
*******************************
LED G
Illuminated: function enabled
Flashing: function disabled
Bypass lower plug function Enable lower plug function Disable lower plug function
Exit configuration
M
S
S*
M*
VALVE CLOSED
FUNCTION
Calibration
LEDs A and B flashing.
*****************************
LED E
Illuminated: function
enabled
Flashing: function disabled
Bypass valve closed function Enable valve closed function Disable valve closed function
Exit configuration
M
S
S*
M*
VALVE OPEN
FUNCTION
Calibration
LEDs A and B flashing.
********************************
LED D
Illuminated: function
enabled
Flashing: function disabled
Bypass valve open function Enable valve open function Disable valve open function
Exit configuration
M
S
S*
M*
MAINTENANCE NOTICE
NM-259 index 01 Page 30/48 March 2014
7.3 Possible faults during calibration
See “possible faults during a calibration” section in the installation notice documentation IT-TDFX-260.
7.4 1st level maintenance
Various faults can be displayed on the front face of the installation module
7.4.1 No signal from the linear sensor
Power LED (A) illuminated, Fault LED (B) extinguished and all yellow LEDs flashing.
Check that the Power LED on the linear sensor is illuminated. Check the connection between the linear sensor and the electronic module. • Use a voltmeter to check that the voltage between terminals V+ and V- on the sensor side of the terminal
is between 20 and 24 VDC. If the voltage and the wiring are OK and the sensor Power LED is extinguished then replace the
sensor.
7.4.2 Cam outside detection range
Power LED (A) illuminated, Fault LED (B) extinguished and yellow LEDs C, D and F flashing. • Check that the detection cam is installed on the valve. • Check the position of the cam in the linear sensor.
7.4.3 Calibration error
Power LED (A) and Fault LED (B) illuminated, all yellow LEDs flashing. • Hold down Set PB to acknowledge the fault. • The values recorded are inconsistent or outside the operating range of the linear sensor, check for air on
the ACS unit and on the valve. • Check the electrical and pneumatic operation of the solenoid valves.
7.5 Wiring of the signalling unit
7.5.1 Internal wiring of the signalling unit
7.5.2 Description of AS-i cable
See the preceding chapter describing the AS-i version.
7.5.3 Description of the customer wiring for multi-voltage module 24 VAC / DC _ 48 VAC / DC
According to the voltages used on the installation, a power supply voltage will be chosen that will determine the choice of the following different wiring diagrams.
Function
Retro data lower plug enabled (PNP) I4 Retro data upper plug enabled (PNP) I3 Retro data valve open (PNP) I2 Retro data valve closed (PNP) I1 Solenoid valve control 1 (actuator lower plug)
O3 Solenoid valve control 1 (actuator upper plug)
O2 Solenoid valve control 1 (main actuator)
O1
Retro data error FLT Common retro data (see wiring diagrams)
CI Solenoid valve connector command (see wiring diagrams)
CO
+ Power supply V+ - Power supply V- Shunt to be implemented with B1, if module has 24 VDC power supply B2 Shunt to be implemented with B2, if module has 24 VDC power supply B1
Brown
Black
Brown
Linear sensor
Upper plug sensor Black
Red
Black
Red
Black
Red
Black
SV1 (Main actuator)
SV2 (Upper plug)
SV3 (Lower plug)
Blue
Blue
V+ V+ V- V- I1 I2
O1
V-
I4
O2 O3
V-
I3 Not connected
Not connected
Customer wiring
Definox ex-works wiring
OR
MULTI-VOLTAGE
LED
MODULE
LED MODULE ASi
MAINTENANCE NOTICE
NM-259 index 01 Page 31/48 March 2014
7.5.3.1 Module with 24 VDC power supply
PNP OUTPUT SENSORS NPN OUTPUT SENSORS
PNP OUTPUT SENSORS NPN OUTPUT SENSORS
PNP, NPN OR NO OUTPUT SENSORS
O3 O2 O1
I4 I3 I2 I1
V+ V-
DIAGRAM No. 1 Signals:
- Solenoid valves: connector (CO) to 24VDC - Sensors : 24VDC PNP outputs
Ctrl_Upper_Plug (O2)
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position of the valve
Control of the valve
SV
Sensor
O3 O2 O1
I4 I3 I2 I1
V+
V-
DIAGRAM No. 3 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 24VDC PNP outputs
Ctrl_Upper_Plug (O2)
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position of the valve
Control of the valve
O3 O2 O1 CO I4 I3 I2 I1
V+ V-
DIAGRAM No. 5 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 24VDC PNP outputs
Ctrl_Upper_Plug (O2)
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV Sensor
Power supply
Position of the valve
Control of the valve
O3 O2 O1
I4 I3 I2 I1
CI
V+
V-
DIAGRAM No. 7 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: PNP, NPN or NO outputs
independent connector
SV Sensor
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Ctrl_Upper_Plug (O2)
Power supply
Position of the valve
Control of the valve
O3 O2 O1
I4 I3 I2
I1
CI
V+
V-
Signals:
- Solenoid valves: connector (CO) to 24VDC - Sensors: PNP, NPN or NO outputs
independent connector
SV Sensor
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Ctrl_Upper_Plug (O2)
DIAGRAM No. 8
Power supply
Position of the valve
Control of the valve
O3 O2 O1 CO I4 I3 I2 I1
V+
V-
DIAGRAM No. 6 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 24VDC NPN outputs
Ctrl_Upper_Plug (O2)
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV Sensor
Power supply
Position of the valve
Control of the valve
Ctrl_Upper_Plug (O2)
O3 O2 O1
I4 I3 I2 I1
V+ V-
DIAGRAM No. 4 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 24VDC NPN outputs
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position of the valve
Control of the valve
O3 O2 O1
I4 I3 I2 I1
V+
V-
DIAGRAM No. 2 Signals:
- Solenoid valves: connector (CO) to 24VDC - Sensors: 24VDC NPN outputs
Ctrl_Upper_Plug (O2)
24VDC (V+)
GND (V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position of the valve
Control of the valve
MAINTENANCE NOTICE
NM-259 index 01 Page 32/48 March 2014
7.5.3.2 Module with 24 VAC, 48 VAC, or 48 VDC power supply
2-point wiring jaws that link:
� the CI and CO connectors to V+ or V-.
� Apart from a 24 VDC power supply, it is imperative to remove the comb wiring between B1 and B2, otherwise there is a risk of permanent damage to the module.
NO OUTPUT SENSORS
48VAC
PNP, NPN OR NO OUTPUT SENSORS (independent connector)
O3 O2 O1
I4
I3
I2 I1
24
Vac
O3 O2 O1
I4 I3
I2
I1
48
Vac
24VAC
(V-)
DIAGRAM No. 1 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 24VAC NO outputs
Ctrl_Upper_Plug (O2)
(V+)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Power supply
Position
of the valve
Control of the valve
SV
Sensor
CO
O3
O2 O1
I4 I3 I2
I1
24
Vac
DIAGRAM No. 3 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 24VAC NO outputs
Ctrl_Upper_Plug(O2)
24VAC
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
O3 O2 O1
I4
I3
I2 I1
CI
24
Vac
DIAGRAM No. 5 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 48VDC PNP or NPN outputs 48VAC NO outputs
24VAC
Ctrl_Upper_Plug (O2)
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
O3 O2 O1
I4
I3
I2 I1
CI
48
Vac
DIAGRAM No. 6 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 48VDC PNP or NPN outputs 24VAC NO outputs
48VAC
Ctrl_Upper_Plug (O2)
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
O3
O2 O1
I4 I3 I2
I1
CO
48
Vac
DIAGRAM No. 4 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 48VAC NO outputs
48VAC
Ctrl_Upper_Plug (O2)
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
Ctrl_Upper_Plug (O2)
DIAGRAM No. 2 Signals:
- Solenoid valves: connector (CO) to V+ - Sensors: 48VAC NO outputs
(V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
CAUTION!
MAINTENANCE NOTICE
NM-259 index 01 Page 33/48 March 2014
PNP OUTPUT SENSORS NPN OUTPUT SENSORS
NO OUTPUT SENSORS
O3 O2 O1
I4
I3 I2
I1
V+
V-
O3 O2 O1
I4
I3 I2
I1
V+
V-
DIAGRAM No. 7 Signals:
- Solenoid valves: connector (CO) to 48VDC - Sensors: 48VDC PNP outputs
Ctrl_Upper_Plug (O2)
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
O3 O2 O1
I4
I3 I2
I1
V+
V-
DIAGRAM No. 9 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 48VDC PNP outputs
Ctrl_Upper_Plug (O2)
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
O3 O2 O1 CO I4
I3 I2 I1
V+
V-
DIAGRAM No. 11 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 48VDC PNP outputs
SV
Sensor
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Ctrl_Upper_Plug (O2)
Power supply
Position
of the valve
Control of the valve
O3 O2 O1
I4
I3 I2 I1
CI
V+ V-
DIAGRAM No. 13
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Ctrl_Upper_Plug (O2)
Signals:
- Solenoid valves: connector (CO) to 48VDC - Sensors: NO outputs independent connector
SV
Sensor
Power supply
Position
of the valve
Control of the valve
O3 O2 O1
I4
I3 I2 I1
CI
V+ V-
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
Ctrl_Upper_Plug (O2)
DIAGRAM No. 14 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: NO outputs independent connector
SV
Sensor
Power supply
Position
of the valve
Control of the valve
O3 O2 O1 CO I4
I3
I2 I1
V+
V-
DIAGRAM No. 12 Signals:
- Solenoid valves: independent connector (CO) - Sensors: 48VDC NPN outputs
Ctrl_Upper_Plug (O2)
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV Sensor
Power supply
Position
of the valve
Control of the valve
O3 O2 O1
I4
I3 I2 I1
V+ V-
DIAGRAM No. 10 Signals:
- Solenoid valves: connector (CO) to GND - Sensors: 48VDC NPN outputs
Ctrl_Upper_Plug (O2)
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
Ctrl_Upper_Plug (O2)
DIAGRAM No. 8 Signals:
- Solenoid valves: connector (CO) to 48VDC - Sensors: 48VDC NPN outputs
48VDC (V+)
(V-)
Open (I1)
Closed (I2)
Ctrl_Main Actuator (O1)
Connector_Control (CO)
Connector_Info (CI)
SV
Sensor
Power supply
Position
of the valve
Control of the valve
MAINTENANCE NOTICE
NM-259 index 01 Page 34/48 March 2014
7.6 Technical specifications of the multi-voltage linea r sensor modules
General specifications
Supply voltage
• 24 VDC modules
• 24 VAC – 48 VAC/DC modules Current consumed for 1 solenoid valve and 1 linear sensor Electromagnetic compatibility Temperature
• operating • storage/transport
24 VDC +/- 5% 24 VAC – 48 VAC/DC +/- 10% ≤ 115 mA DC (24 VDC supply) ≤ 210 mA AC (24 VAC supply) ≤ 80 mA DC (48 VDC supply) ≤ 146 mA AC (48 VAC supply) EN61000-6-2, EN61000-6-4 -10 to +60 °C -40 to +85 °C
Diagnostic functions
Supply voltage display Unit status display
Green “POWER” LED Red “FAULT” LED
Sensor inputs
Nominal input voltage Linear sensor input Connect a 2 or 3 wire inductive upper plug opening sensor
24 VDC 1 Yes
Solenoid valve output
Output voltage Output current Switching frequency on inductive load Short-circuit protection
24 VDC 50 mA max 0.5 Hz Yes
Electrical connections to PLC
Connection type Conductor section
Spring cage terminal 0.75 mm² max. A cross section of 0.5 mm² is sufficient. Cable diameter: 4.5 to 10 mm.
Solenoid valve signals from the PLC
Number Nominal input voltage +/- 10% Minimum current Signal type
3 24 VAC/DC to 48 VAC/DC ≥ 6mA PNP or NPN
Sensor signals to PLC
Number Fault signal Output voltage +/- 10% Output current Signal type
4 + 1 fault Yes 24 VAC/DC to 48 VAC/DC 50 mA max PNP, NPN or NO
MAINTENANCE NOTICE
NM-259 index 01 Page 35/48 March 2014
7.7 AS-i linear sensor LED module specifications
7.8 Linear sensor specifications
General specifications
AS-i supply voltage Current consumed for 1 solenoid valve and the linear sensor Electromagnetic compatibility Temperature
• operating • storage/transport
25 … 31.6 VDC ≤ 115 mA EN61000-6-2, EN61000-6-4
-10 to +60 °C -40 to +85 °C
Communication specifications
Protocol Profile AS-i 2.1 Profile AS-i 2.0 AS-i certificate according to C.S.3.0_Revision 4
AS-i IO code: 7 ID code: A ID2 code: E IO code: 7 ID code: 0 ID2 code: F N° 101201
Diagnostic functions
AS-i voltage display Module status display
Green “POWER” LED Red “FAULT” LED
Sensor i nputs
Nominal input voltage Linear sensor input Connect a 2 or 3 wire inductive upper plug opening sensor
24 VDC 1 Yes
Solenoid valve output
Output voltage Output current Switching frequency on inductive load Short-circuit protection
24 VDC 50 mA max 0.5 Hz Yes
General specifications
Supply voltage Current consumed for 1 linear sensor Electromagnetic compatibility Temperature
• operating • storage/transport
Linear sensor accuracy Minimum detectable lower plug opening Lower plug opening tolerance Open or closed position tolerance Detection range
24 VDC +/- 10% ≤ 25 mA DC (24 VDC supply) EN61000-6-2, EN61000-6-4 -10 to +60 °C -40 to +85 °C +/- 0.2 mm 0.6 mm 0.45 mm 1 mm 80 mm
MAINTENANCE NOTICE
NM-259 index 01 Page 36/48 March 2014
8 CHANGE OF CONFIGURATION OF THE LIGHTING RETRO DATA
O N O N O N N
10 �
9 �
8 �
7 �
6 �
5 �
4 �
3 �
2 �
1 �
SWITCH POSITION SWITCH POSITION SWITCH POSITION SWITCH POSITION
O
AC
S 4
I/3O
(2S
P/3
SV
) AC
S 2
I/1O
(2SP
/1 S
V) I1
I2
I3- b l inking f =xxxx Hz
FLT
I4- b l inking
f =xxxx Hz
ACS SIGNALLING UNIT2I/1O ⇔ 2SP/1 SV
4I/3O ⇔ 2SP/3 SV or LINEAR SENSOR + 1 SP lantern / 3SV
�
RETRO DATA
SWITCH
COLOURS
Ex -works configuration
BLUE GREEN INHIBITED RED
• Remove the transparent cover of the selector. • Using a small tool, move the white cursor to place it at the position “O” or “N” according to your choice of colour,
determined using the table above. • Replace the transparent cover of the selector.
OR
ACS 2I / 1O (2SP / 1O) TERMINAL ACS 2I / 1O (2SP / 1O) AS-I, MULTI-VOLTAGE ACS 2I / 3O (2SP / 3O) TERMINAL, AS-I, MULTI-VOLTAGE
ACS 4I / 3O (LINEAR SENSOR + 1 SP for lantern / 3EV) TERMINAL, AS-I, MULTI-VOLTAGE
MAINTENANCE NOTICE
NM-259 index 01 Page 37/48 March 2014
9 CONFIGURATION CHANGE: switch a valve to NC and a va lve to NO
Note: For the NC actuators fitted with a quick connect elbow connector other than 13-a, a transformation kit known as the “NC to NO _ ACS unit transition kit” is available 23. This kit is made up of the components 13, 15, and 24-a.
• Remove the air tubes ∅ 4/6 24 from the quick connect elbow connectors 13 of channels 1 and P of the signalling
unit and the actuator A. • After altering the actuator to a NO configuration: • On the actuator, remove the plain shank elbow, the quick connect elbow connector 13-a and the pierced cap 10. • Reassemble the quick connect elbow connector 13-a and the pierced cap 10 by inverting them. • Mount the signalling unit (base and connector) on the actuator. • Fit the extended plain shank elbow 15 on the quick connect elbow connector of channel 1 of the signalling unit. • Connect the extended plain shank elbow 15 to the actuator's quick connect elbow connector 13-a by means of a
60 mm long ∅ 4/6 pneumatic tube 24-a. • Connect the wiring according to the unit type and in accordance with the connection diagrams provided herein. • Re-pressurize channel P.
23
NOTE!
N.C. VALVE ASSEMBLY
N.O. VALVE ASSEMBLY
A
13
24-a
15
13-a
10
24
A
13
10
13-a
Plain shank elbow
MAINTENANCE NOTICE
NM-259 index 01 Page 38/48 March 2014
10 ACS UNIT SPARE PARTS
10.1 ACS unit - Double-Acting - 2I/1O module - AS-I or multi-voltage, or terminal
5b
22 21a 21c 1a 1b
5a
4
2c
10
14
3
20a
19a 19d
8
18
13
17b
26
17a
12
MAINTENANCE NOTICE
NM-259 index 01 Page 39/48 March 2014
10.2 ACS unit - 1SV - 2I/1O - AS-i or multi-voltage, or terminal
1b
1a 22
20a
21a
21c
19a
18
13
10
6
5a
4
5a
14
17b
26
17a
19d
2a
3
5b
5b
MAINTENANCE NOTICE
NM-259 index 01 Page 40/48 March 2014
10.3 ACS unit - 2SV - module 4I/3O - AS-i, or terminal
1b
1a
22
20b
21b
19b
18 13
10
6
5a
4
5a
14
17b
26
17a
19e
16
7
2b
3
5b
5b
MAINTENANCE NOTICE
NM-259 index 01 Page 41/48 March 2014
10.4 ACS unit - 3SV - module 4I/3O - AS-i or terminal
1b
1a
22
20b
21b
19b
18
13
10
6
5a
4
5a
14
17b
26
17a
19e
3
2b
7
5b
5b
MAINTENANCE NOTICE
NM-259 index 01 Page 42/48 March 2014
10.5 ACS unit – 3SV - module 1I+lin. sens./3O - AS-I, or multi-voltage
1b
1a
22
20b
21d
19c
18
13
10
6
25
14
17b
26
17a
19f
3
2b
7
MAINTENANCE NOTICE
NM-259 index 01 Page 43/48 March 2014
10.6 List of ACS unit parts
Ref Designation Material Qty
Reference 1 SV 2 SV 3 SV
1a ACS unit valve cover assembly _PSU version (standard) PSU 1 1 1 7160722
1b ACS unit valve cover assembly _ stainless steel version (optional) A2 1 1 1 7160723
2a ACS 1 SV unit connector assembly - 1 7160384
2b ACS 3 SV unit connector assembly - 1 1 7160383
2c ACS DA (Double-Acting) unit connector assembly - 1 7160387
3 ACS unit base assembly - 1 1 1 7160352
4 ACS unit sensor support assembly (body + rail + support + screw) - 1 1 1 7160375
5a 24 VDC 2-wire sensor - 1 / 2 (spec/std)
1 / 2 (spec/std)
1 / 2 (spec/std) 7008045
5b 24 VDC 3-wire sensor - 1 / 2 (spec/std)
1 / 2 (spec/std)
1 / 2 (spec/std) 7007922
6 ¼ turn lockable manually operated N.C. solenoid valve - 1 1 1 7009018
7 Manually pulse-controlled N.C. solenoid valve - 1 2 7009020
8 ¼ turn lockable manually operated D.A. solenoid valve - 1 7009059
10 1/8" pierced plastic cap 3 mm PA66 1 1 1 7002496
11 1/8” plastic cap PA66 1 7008904
12 4/6 stopper PA66 DA: 1 7160015
13 D6 1/8” quick connect elbow connection - 2 3 4 7010116
14 10 CHc M8 screws A2 2 2 2 7006756
15 Extended plain shank elbow Ø6_4/6 tube PA66 NC: 0
7009106 NO: 1
16 Blanking kit plate - 1 7009069
17a AS-i vampire clip - 1 1 1 7008227
17b AS-i stainless steel vampire clip - 1 1 1 7008268
18 AS-i cord M8 – M12 (length 0.7 m) - 1 1 1 7008226
19a AS-i 2.1_ACS 2I/1O LED module (addresses from 1A to 31A or 1B to 31B)
- 1 7160729
19b AS-i 2.1_ACS 4I/3O LED module (addresses from 1A to 31A or 1B to 31B)
- 1 1 7160732
19c AS-i 2.1_ACS LED module 1I+linear sensor/3O (addresses from 1A to 31A or 1B to 31B) - 1 1 7160734
19d AS-i 2.0_ACS LED module 2I/1O (addresses from 1 to 31) - 1 7160796
19e AS-i 2.0_ACS LED module 4I/3O (addresses from 1 to 31) - 1 1 7160797
19f AS-i 2.0_ACS LED module 1I+linear sensor/3O (addresses from 1 to 31)
- 1 1 7160798
20a ACS – 1SV unit module terminal - 1 7008251
20b ACS – 3SV unit module terminal - 1 1 7008250
21a ACS 2I/1O terminal LED module - 1 7160728
21b ACS 2I/3O terminal LED module - 1 1 7160731
21c ACS multi-voltage LED module 24 VAC/DC – 48 VAC/DC 2I/1O - 1 7160730
21d ACS multi-voltage LED module 24 VAC /DC – 48 VAC/DC 1I + linear sensor/ 3O - 1 1 7160733
22 25 TCL M3 screws A2 1 1 1 7006894
23 ACS unit NC to NO_transformation kit - NC: 0
7009155 NO: 1
24 Pneumatic tube ∅ 4/6 PTFE 7030497
25 IX 5005 linear sensor + fixing clamp - 0/1 0/1 7008207
26 AS-i cable Thermoplastic elastomer 7008024
MAINTENANCE NOTICE
NM-259 index 01 Page 44/48 March 2014
§ Designation Reference
Standard references incorporating the following com ponents:
§ 9.7 Assembled unit 1SV - LED module terminal version ACS – 2 SP: 1a+2a+4+5b+6+9a+10+13 7160739
§ 9.3 Assembled unit 1SV - - LED module version AS-I 2.1 ACS – 2 SP: 1a+2a+4+5b+6+9a+10+13 7160740
§ 9.9 Assembled unit 3SV - LED module terminal version ACS – 2SP: 1a+2b+4+5b+6+7+9b+10+13 7160741
§ 9.5 Assembled unit 3SV - LED module version AS-i 2.1 ACS – 2SP: 1a+2b+4+5a+6+7+10+13+20b+22 7160742
§ 9.6 Assembled unit 3SV- LED module version AS-i 2.1 – linear sensor: 1a+2b+6+7+10+13+20b+22+25 7160743
§ 9.2 Assembled connector 1SV double-acting – LED module version: 1a+2c+4+5b+8+9a+10+12+13 7160792
MAINTENANCE NOTICE
NM-259 index 01 Page 45/48 March 2014
10.7 Dimensions, assignment and reference of cams for AC S unit sensor(s)
10.7.1 For DPAX valves DN25 to 150
10.7.2 For DN8 full flow to 65 venturi DBAX valves
10.7.3 For DCX3 & 4 valves DN25 to 150
4846
M10 M12
8
Ø31.5 Ø31.5
8
43.5 63
M16 M16
Ø31.5
8
Ø31.5
19.5
Ø31.5
29 17
Ø20
17
Ø31.5
27 11
Ø20
20
Ø31.5
29 17
Ø20
17
Ø31.5
27 11
Ø20
20
Cam DN8 to 40 full flow ref.: 7002825 Cam DN15 to 50 venturi ref.: 7002825
Cam DN50 full flow ref.: 7002443 Cam DN65 venturi ref.: 7002443
Spacer DN8 to 40 full flow ref.: 70017 76 Spacer DN15 to 50 venturi ref.: 7001776
Fastening screw ref.: 7006770
Spacer DN50 full flow ref.: 7003014 Spacer DN65 venturi ref.: 7003014
Fastening screw ref.: 7006830
Spacer DN80 to 150 ref.: 7003014 Fastening screw ref.: 7006830
Spacer DN25 to 76 ref.: 7001776 Fastening screw ref.: 7006770
Cam DN25 to 76 ref.: 7002825 Cam DN80 to 150 ref.: 7002443
Cam DN25 to 38 ref.: 7005990
Cam DN51 to 76 ref.: 7005991
Cam DN80 to 104 ref.: 7005992
Cam DN125 to 150 ref.: 7300618
MAINTENANCE NOTICE
NM-259 index 01 Page 46/48 March 2014
10.7.4 For VDCI PFA valves with breakaway cylinder DN38 to 150
10.7.5 For VDCI SP or VDCI PFA valves without breakaway cylinder DN38 to 150
Ø31
10
24
39
Ø31
Ø31.5
Ø 10.3
Ø8.25
15.5
7
16.5
7
Ø31.5
Ø6.25
Ø31.5
39
10
24
Ø 31
Ø 31
15
Ø31.5
55.3
Ø 31.5
20 60
Ø 31.5
25
51
Cam DN38 to 51 ref.: 714 0222 Fastening screw ref.: 7006770
Cam DN63 to 76 ref.: 7140248 Fastening screw ref.: 7006741
Cam DN80 to 104 ref.: 7140249 Fastening screw ref.: 7006792
Cam DN125 to 150 ref.: 7140412
Spacer ref.: 7140434 Fastening screw ref.: 7006821
1 unit extensio n ref.: 7140433 2 extension screws ref.: 7380306 1 pierced cap ref.: 7002496 1 O-ring ref.: 7006064
+
Cam DN38 to 51 ref.: 7148038 Fastening screw ref.: 7380322
Cam DN63 to 76 ref.: 7142147 Fastening screw ref.: 7006729
Cam DN80 to 104 ref.: 7142393 Fastening screw ref.: 7006806
Cam DN125 to 150 ref.: 7140412
Spacer ref.: 7140434 Fastening screw ref.: 7006821
1 unit extension ref.: 7140493 2 unit fastening screws ref.: 7006758 +
MAINTENANCE NOTICE
NM-259 index 01 Page 47/48 March 2014
10.7.6 For VDCI MC PFA DN38 to 125 valves
10.7.7 For VDCI MC SP/PMO valves DN38 to 125
10.7.8 For DMAX valves DN21.6 to 52
10.8 Dimensions, assignment and reference of cams for th e linear sensor of ACS units
10.8.1 For VDCI MC PFA DN38 to 125 valves
10.8.2 For VDCI MC SP/PMO valves DN38 to 125
8 41
Ø 31.5
Ø31.5
7 15
.5
Ø8.25
Ø31.57
41
41
7
42
7
Cam DN21,6 to 52 ref.: 7110094 Fastening screw ref.: 7006850
Cam DN38 to 51 ref.: 7142144 Fastening screw ref.: 7380350
Cam DN63 to 125 ref.: 7142146 Fastening screw ref.: 7006734
Cam DN38 to 51 ref.: 7142144 Fastening screw ref.: 7380350
Cam DN63 to 125 ref.: 7142147 Fastening screw ref.: 7006729
Cam DN38 to 51 ref.: 7148633 Cam DN63 to 125 ref.: 7148634
Spacer DN38 to 51 ref.: 7148647 Spacer DN63 to 125 ref.: 7148635
Cam DN38 to 51 ref.: 7148633 Cam DN63 to 125 ref.: 7148634
31.5 31.5
MAINTENANCE NOTICE
NM-259 index 01 Page 48/48 March 2014
www.definox.com
FRANCE
DEFINOX SAS 3 Rue de la Pépinière - Z.I. Nord
44190 GETIGNE - France Tel: +33 (0)2 28 03 98 50 Fax: +33 (0)2 28 03 88 00
USA
DEFINOX INC. 16720 W. Victor Road
New Berlin – WISCONSIN 53151 – USA Tel: (1) 262 797 5730 - Fax: (1) 262 797 5735
CHINA
DEFINOX Beijing Stainless Steel Equipment Ltd No 18 Anningzhuang East Road – HAIDIAN District
BEIJING 100085 – CHINA Tel: (86) 10.6293.4909 - Fax: (86) 10.6293-4835
The product specifications contained in this document are given for information purposes only and may be modified at
any time without notice.
The photographs, drawings and diagrams represented in this document are not binding.
This document is our property and cannot be copied, reproduced, modified or translated without our express
authorisation.
DEFINOX is a registered trademark.