ELECTRICAL LEGEND SYMBOL SYMBOL DESCRIPTION DESCRIPTION SURFACE/PENDANT/WALL MOUNTED FIXTURE. UPPER CASE INDICATES TYPE IN SCHEDULE. LOWER CASE INDICATES SWITCH. SURFACE/PENDANT/ WALL MOUNTED FIXTURE. DIAGONAL MARKING INDICATES EGRESS FIXTURE CONNECTED TO EMERGENCY POWER SUPPLY. UPPER CASE INDICATES TYPE IN SCHEDULE. LOWER CASE INDICATES SWITCH. RECESSED COMPACT FIXTURE. UPPER CASE INDICATES TYPE IN SCHEDULE. LOWER CASE INDICATES SWITCH. RECESSED COMPACT FIXTURE. DIAGONAL MARKING INDICATES EGRESS FIXTURE CONNECTED TO EMERGENCY POWER SUPPLY. UPPER CASE INDICATES TYPE IN SCHEDULE. LOWER CASE INDICATES SWITCH. PENDANT MOUNTED FIXTURE. UPPER CASE INDICATES TYPE IN SCHEDULE. LOWER CASE INDICATES SWITCH. EXIT SIGN AS SCHEDULED. CONNECTED TO EMERGENCY LIGHTING POWER SUPPLY. ARROWS INDICATE DIRECTIONAL ARROWS. PROVIDE SINGLE OR DOUBLE FACE AS REQUIRED OR INDICATED. UPPER CASE INDICATES TYPE IN SCHEDULE. "WG" INDICATES WIRE GUARD. GRAPHIC WALL SWITCH WITH A MINIMUM OF FOUR CHANNELS, nLIGHT NDX POD OR SIMILAR M CEILING MOUNTED OCCUPANCY SENSOR. CONDUCTORS IN CONDUIT. MINIMUM NUMBER IS (2) #12 AWG + #12 GND. PROVIDE NUMBER OF CONDUCTORS AS REQUIRED FOR SWITCHING INDICATED AND CONTINUING CIRCUITS. HOMERUN TO PANELBOARD. REFER TO SPECIFICATIONS FOR LIMITING NUMBER OF CONDUCTORS PER HOMERUN. NOTE: ITEMS SHOWN AS DASHED INDICATE ITEMS WHICH ARE TO BE REMOVED. CS ABOVE COUNTER AC ABOVE FINISHED FLOOR AFF ALARM ALM ALARM ANNUNCIATOR PANEL AAP ALTERNATING CURRENT AC AMERICAN NATIONAL STANDARDS INSTITUTE ANSI AMERICAN SOCIETY FOR TESTING AND MATERIALS ASTM AMERICAN STEEL WIRE GAUGE ASWG AMPERE AWG AMPHOUR AMP AMPERE INTERRUPTING CAPACITY AH AMPLIFIER AIC AMPS SHORT CIRCUIT AMPL ANNUNCIATOR ASC ANTENNA ANN ARCHITECT ANT ARMORED CABLE ARCH AUDIO FREQUENCY ARMC AUDIO VISUAL AF AUTHORITY HAVING JURISDICTION AV AUTO TRANSFORMER AHJ AUTOMATIC CONTROL PANEL AUTO XFMR AUTOMATIC DOOR CLOSER ACP AUTOMATIC FREQUENCY CONTROL ADC AUTOMATIC TRANSFER SWITCH AFC AUXILIARY ATS AUXILIARY POWER UNIT AUX APU AMERICAN WIRE GAUGE BACKBOARD BKBD BALLAST BLST BATTERY BAT BRAKE HORSEPOWER BHP BUCK - BOOST TRANSFORMER BB XFMR BUILDING AUTOMATION SYSTEM BAS CABLE TELEVISION CTV CANDLE POWER CAPACITOR CIRCUIT CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION COAXIAL CABLE COEFFICIENT OF UTILIZATION COLOR RENDERING INDEX COMMON GROUND COMMUNICATIONS CONDUIT CONTROL CONTROL CONTRACTOR CONTROL PANEL CONTROL POWER TRANSFORMER CONTROL RELAY CONTROL SWITCH COORDINATE COPPER COVER PLATE CURRENT CURRENT LIMITING FUSE CURRENT TRANSFORMER. CP CAP CKT CB CCTV COAX CU CRI CG COMM C CTRL CC CP CPT CR CS COORD CU COV PL CUR CLF CT DECIBEL dB DEMOLITION DEMO DETAIL DET DIRECT CURRENT DC DISCONNECT SWITCH DS DOUBLE POLE, DOUBLE THROW DPDT DOUBLE POLE, SINGLE THROW DPST EACH EA EASEMENT ESMT ELECTRIC ELEC ELECTRICAL METALLIC TUBING EMT ELECTRICAL NONMETALLIC TUBING ENT ENCLOSURE ENCL FIRE ALARM FA FIRE ALARM ANNUNCIATOR PANEL FAAP FIRE ALARM CONTROL PANEL FACP FIXTURE FIXT FLEXIBLE METALLIC CONDUIT FMC FLUORESCENT FLUOR FLUORESCENT FIXTURE FLUOR FIXT FLUORESCENT LIGHTING FLUOR LGHT FOOTCANDLE FC FREQUENCY FREQ FULL LOAD AMPS FLA GAUGE GA GENERATOR GEN GROUND FAULT CIRCUIT INTERRUPTER GFCI HEAVY DUTY HD HIGH OUTPUT HO HIGH VOLTAGE HV HORSEPOWER HP ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA IESNA INTERMEDIATE METAL CONDUIT IMC KILOVOLT kV KILOVOLT AMP kVA KILOWATT kW KILOWATT HOUR kWH LIQUIDTIGHT FLEXIBLE METAL CONDUIT LFMC LIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT LFNC LOW VOLTAGE LV LUMEN LM LUMENS PER WATT LPW MAIN CIRCUIT BREAKER MCB MAIN LUGS ONLY MLO MANUFACTURER MFR MINIMUM MIN MINIMUM CIRCUIT AMPS MCA MOTOR CONTROL CENTER MCC MOTOR STARTER MS NATIONAL ELECTRICAL CODE NEC NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEMA NATIONAL FIRE CODE NFC NATIONAL FIRE PROTECTION ASSOCIATION NFPA NIGHT LIGHT NL NORMALLY CLOSED NC NORMALLY OPEN NO NOTIFICATION APPLIANCE CIRCUIT NAC PANELBOARD PB PHASE PH PHOTOELECTRIC PE PHOTOELECTRIC CELL PEC POLY VINYL CHLORIDE PVC POWER PWR POWER AMPLIFIER PA POWER FACTOR PF RECEPTACLE RECEPT RIGID GALVANIZED STEEL RGS RIGID NONMETALLIC CONDUIT RNC SCHEDULE SCH SERVICE ENTRANCE SE SINGLE PHASE 1 SINGLE POLE, DOUBLE THROW SPDT SINGLE POLE, SINGLE THROW SPST SWITCHBOARD SWBD THREE PHASE 3 TWISTED SHIELDED PAIR TSP UNINTERRUPTIBLE POWER SUPPLY UPS UNLESS NOTED OTHERWISE UNO VARIABLE FREQUENCY DRIVE VFD VERY HIGH OUTPUT VHO VOLT, VOLTS, VOLTAGE V VOLT AMPERE VA VOLTAGE DROP VD WEATHERPROOF WP WIREWAY WW GROUND GND ELECTRICAL ABBREVIATIONS TRIM RING CEILING LAMP AS SPECIFIED SOCKET CUP SOCKET MOUNTING BRACKET HOUSING/MOUNTING ELECTRONIC BALLAST JUNCTION BOX ALZAK REMOVABLE REFLECTOR 3 5/8" METAL STUD FIELD VERIFY LOCATION SQUARE STEEL BOX GALVANIZED WIRE HANGER MIN. #22 AWG CONNECTED TO A MINIMUM OF FOUR POINTS ON FIXTURE PROVIDE FOUR HOLD DOWN CLIPS PER FIXTURE 2'X4' LAY - IN LIGHT FIXTURE LAY - IN CEILING 3/8" MIN. FLEX CONDUIT (LIMIT TO 6') SUPPORT EMT CONDUIT NOTES: WIRE HANGERS ARE ONLY REQUIRED IN AREAS WITH LAY - IN CEILINGS. ACTUAL MOUNTING MAY VARY DUE TO ACTUAL SITE CONDITIONS. # DATE DESCRIPTION - CLIENT PROJECT NO. Parkhill.com 9/16/2021 2:04:15 PM 1077.21 R_v21 ISSUE FOR BID 555 Walnut St. Abilene, TX 79601 City of Abilene E-001 Electrical Abbreviations & Legends Abilene City Council Chambers Renovations NTS A4 RECESSED DOWNLIGHT INSTALLATION DETAIL NTS A2 RECESSED LIGHT FIXTURE INSTALLATION DETAIL ELECTRICAL SPECIFICATIONS: CODE COMPLIANCE/WORKMANSHIP 1. CONTRACTOR SHALL COMPLY WITH ALL NATIONAL, STATE AND LOCAL CODES AND ACCEPTED GOOD PRACTICE. 2. ALL WORK SHALL BE PERFORMED BY LICENSED AND QUALIFIED PERSONNEL. EXISTING CONDITIONS 1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BID. BY SUBMITTING BID, CONTRACTOR STATES THAT HE HAS EXAMINED ALL EXISTING CONDITIONS. IF CONTRACTOR ENCOUNTERS EXISTING CONDITIONS WHICH NEED CLARIFICATION, CONTACT ENGINEER FOR RESOLUTION OR CLARIFICATION. PERMITS AND FEES 1. CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY ALL FEES AND CHARGES REQUIRED (INCLUDING UTILITY COMPANY CHARGES). GUARANTEE AND WARRANTIES 1. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL HAVE ONE (1) YEAR WRITTEN GUARANTEE FOR ALL MATERIALS AND WORKMANSHIP. MATERIALS 1. ALL MATERIALS SHALL BE NEW AND SPECIFICATION GRADE. OWNERS MANUAL 1. AT COMPLETION OF PROJECT, CONTRACTOR SHALL DELIVER TO OWNER ALL DOCUMENTS (INCLUDING BUILDING PERMITS, OPERATION AND MAINTENANCE MANUALS, WARRANTY, AS- BUILT ETC.). CONDUIT 1. ALL INTERIOR CONDUIT SHALL BE EMT. MINIMUM SIZE OF CONDUIT SHALL BE 3/4" FOR POWER AND 1" FOR COMMUNICATION. ALL CONDUIT SHALL BE ROUTED PERPENDICULAR TO BUILDING LINES WHERE EXPOSED TO VIEW. 2. LABEL ALL JUNCTION BOXES ABOVE CEILING WITH CIRCUIT DESIGNATION WITH BLACK INDELIBLE MARKER. 3. ALL EMPTY CONDUITS SHALL HAVE PULL WIRE FOR FUTURE USE. 4. ALL COMMUNICATION CONDUITS SHALL BE STUBBED UP ABOVE CEILING AND TERMINATED WITH A PLASTIC BUSHING. WIRE 1. ALL WIRE SHALL BE THHN/THWN COPPER UNLESS OTHERWISE INDICATED ON THE DRAWINGS. MINIMUM SIZE OF WIRE SHALL BE #12. FOR 20A CIRCUITS LONGER THAN 100', MINIMUM WIRE SIZE SHALL BE #10 AWG. DISCONNECT SWITCHES 1. ALL DISCONNECT SWITCHES SHALL BE HEAVY DUTY WITH NEMA CONFIGURATION AS INDICATED ON DRAWINGS OR AS REQUIRED BY N.E.C. PROVIDE FUSES IN SWITCHES AS INDICATED ON THE DRAWINGS. SWITCHES 1. ALL SWITCHES SHALL BE SPECIFICATION GRADE (HUBBELL 1221 OR APPROVED EQUAL). COLOR OF ALL SWITCHES SHALL SHALL BE GRAY AND COVERPLATES SHALL BE STAINLESS STEEL. MOUNTING HEIGHT OF ALL SWITCHES SHALL COMPLY WITH A.D.A. REQUIREMENTS. FUSED/NON-FUSED DISCONNECTS 1. ALL FUSED AND NON-FUSED DISCONNECTS SHALL BE HEAVY DUTY RATED OF THE AMPERAGE RATING REQUIRED BY NEC FOR REQUIRED SERVICE. 2. PROVIDE FUSES FOR EACH DISCONNECT. RECEPTACLES 1. ALL RECEPTACLES SHALL BE SPECIFICATION GRADE (HUBBELL 5352 OR APPROVED EQUAL). COLOR OF ALL RECEPTACLES SHALL BE GRAY AND COVERPLATES SHALL BE STAINLESS STEEL. MOUNTING HEIGHT OF RECEPTACLES SHALL COMPLY WITH A.D.A. REQUIREMENTS UNLESS SPECIFIC OR SPECIAL MOUNTING HEIGHT IS SHOWN ON DRAWINGS OR REQUIRED BY EQUIPMENT. 2. LABEL ALL RECEPTACLES WITH CIRCUIT DESIGNATION ON BACKSIDE OF FACEPLATE WITH BLACK INDELIBLE MARKER. GROUNDING 1. ENTIRE ELECTRICAL SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C. ARTICLE 250. ELECTRICAL EQUIPMENT 1. ALL BUSSING SHALL BE COPPER WITH FULL LENGTH GROUND BUS. OVERCURRENT DEVICES SHALL BE CIRCUIT BREAKER (CB) AS INDICATED. INTERRUPTING CURRENT OF EQUIPMENT AND DEVICES SHALL BE AS NOTED ON THE SCHEDULE. PANELBOARDS 1. PROVIDE TYPEWRITTEN DIRECTORIES IN ALL PANELBOARDS AFFECTED BY PROJECT AFTER PROJECT COMPLETION. HANDWRITTEN WILL NOT BE ACCEPTED. 2. PROVIDE MINIMUM INTEGRATED SHORT CIRCUIT RATING AS INDICATED ON PANELBOARD SCHEDULE. ALL CIRCUIT BREAKERS SHALL BE FULLY RATED. SERIES RATED SYSTEMS WILL NOT BE ALLOWED. 3. ALL NEW OVERCURRENT DEVICES SHALL MATCH EXISTING. LIGHTING FIXTURES 1. LIGHTING FIXTURES SHALL BE AS SCHEDULED ON THE DRAWINGS. FIXTURES SHALL BE COMPLETE WITH ALL LAMPS. 2. REFER TO THE DRAWINGS FOR MOUNTING RESTRICTIONS. SUBMITTALS AND SUBSTITUTIONS 1. CONTRACTOR SHALL FURNISH SUBMITTAL DATA TO ENGINEER FOR APPROVAL ON ALL FIXTURES AND EQUIPMENT PRIOR TO ORDERING ANY ITEMS. CONTRACTOR MAY OFFER SUBSTITUTIONS ON ITEMS FOR APPROVAL BY ENGINEER. SUBSTITUTIONS MUST BE EQUAL IN ALL RESPECTS TO ITEMS SCHEDULED OR SPECIFIED. 09/16/2021 09/16/2021

A2 A4 E-001 - abilenetx.gov

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: A2 A4 E-001 - abilenetx.gov

ELECTRICAL LEGENDSYMBOL SYMBOLDESCRIPTION DESCRIPTION

SURFACE/PENDANT/WALL MOUNTED FIXTURE.UPPER CASE INDICATES TYPE IN SCHEDULE.LOWER CASE INDICATES SWITCH.

SURFACE/PENDANT/ WALL MOUNTED FIXTURE. DIAGONAL MARKING INDICATES EGRESS FIXTURE CONNECTED TO EMERGENCY POWER SUPPLY. UPPERCASE INDICATES TYPE IN SCHEDULE. LOWER CASE INDICATES SWITCH.

RECESSED COMPACT FIXTURE.UPPER CASE INDICATES TYPE IN SCHEDULE.LOWER CASE INDICATES SWITCH.

RECESSED COMPACT FIXTURE. DIAGONAL MARKING INDICATES EGRESS FIXTURE CONNECTED TO EMERGENCY POWER SUPPLY. UPPERCASE INDICATES TYPE IN SCHEDULE. LOWER CASE INDICATES SWITCH.

PENDANT MOUNTED FIXTURE.UPPER CASE INDICATES TYPE IN SCHEDULE.LOWER CASE INDICATES SWITCH.

EXIT SIGN AS SCHEDULED. CONNECTED TO EMERGENCY LIGHTING POWER SUPPLY. ARROWS INDICATE DIRECTIONAL ARROWS. PROVIDE SINGLE OR DOUBLE FACE AS REQUIRED OR INDICATED. UPPER CASE INDICATES TYPE IN SCHEDULE. "WG" INDICATES WIRE GUARD.

GRAPHIC WALL SWITCH WITH A MINIMUM OF FOUR CHANNELS, nLIGHT NDX POD OR SIMILAR

M CEILING MOUNTED OCCUPANCY SENSOR.

CONDUCTORS IN CONDUIT. MINIMUM NUMBER IS (2) #12 AWG + #12 GND. PROVIDE NUMBER OF CONDUCTORS AS REQUIRED FOR SWITCHING INDICATED AND CONTINUING CIRCUITS.

HOMERUN TO PANELBOARD. REFER TO SPECIFICATIONS FOR LIMITING NUMBER OF CONDUCTORS PER HOMERUN.

NOTE:ITEMS SHOWN AS DASHED INDICATE ITEMS WHICH ARE TO BE REMOVED.

CS

ABOVE COUNTER ACABOVE FINISHED FLOOR AFFALARM ALMALARM ANNUNCIATOR PANEL AAPALTERNATING CURRENT ACAMERICAN NATIONAL STANDARDS INSTITUTE ANSIAMERICAN SOCIETY FOR TESTING AND MATERIALS ASTMAMERICAN STEEL WIRE GAUGE ASWG

AMPEREAWG

AMPHOURAMP

AMPERE INTERRUPTING CAPACITYAH

AMPLIFIERAIC

AMPS SHORT CIRCUITAMPL

ANNUNCIATORASC

ANTENNAANN

ARCHITECTANT

ARMORED CABLEARCH

AUDIO FREQUENCYARMC

AUDIO VISUALAF

AUTHORITY HAVING JURISDICTIONAV

AUTO TRANSFORMERAHJ

AUTOMATIC CONTROL PANELAUTO XFMR

AUTOMATIC DOOR CLOSERACP

AUTOMATIC FREQUENCY CONTROLADC

AUTOMATIC TRANSFER SWITCHAFC

AUXILIARYATS

AUXILIARY POWER UNITAUXAPU

AMERICAN WIRE GAUGE

BACKBOARD BKBDBALLAST BLSTBATTERY BATBRAKE HORSEPOWER BHPBUCK-BOOST TRANSFORMER BB XFMRBUILDING AUTOMATION SYSTEM BAS

CABLE TELEVISION CTVCANDLE POWERCAPACITORCIRCUITCIRCUIT BREAKERCLOSED CIRCUIT TELEVISIONCOAXIAL CABLECOEFFICIENT OF UTILIZATIONCOLOR RENDERING INDEXCOMMON GROUNDCOMMUNICATIONSCONDUITCONTROLCONTROL CONTRACTORCONTROL PANELCONTROL POWER TRANSFORMERCONTROL RELAYCONTROL SWITCHCOORDINATECOPPERCOVER PLATECURRENTCURRENT LIMITING FUSECURRENT TRANSFORMER.

CPCAPCKTCBCCTVCOAXCUCRICGCOMMCCTRLCCCPCPTCRCSCOORDCUCOV PLCURCLFCT

DECIBEL dBDEMOLITION DEMODETAIL DETDIRECT CURRENT DCDISCONNECT SWITCH DSDOUBLE POLE, DOUBLE THROW DPDTDOUBLE POLE, SINGLE THROW DPST

EACH EAEASEMENT ESMTELECTRIC ELECELECTRICAL METALLIC TUBING EMTELECTRICAL NONMETALLIC TUBING ENTENCLOSURE ENCL

FIRE ALARM FAFIRE ALARM ANNUNCIATOR PANEL FAAPFIRE ALARM CONTROL PANEL FACPFIXTURE FIXTFLEXIBLE METALLIC CONDUIT FMCFLUORESCENT FLUORFLUORESCENT FIXTURE FLUOR FIXTFLUORESCENT LIGHTING FLUOR LGHTFOOTCANDLE FCFREQUENCY FREQFULL LOAD AMPS FLA

GAUGE GAGENERATOR GEN

GROUND FAULT CIRCUIT INTERRUPTER GFCI

HEAVY DUTY HDHIGH OUTPUT HOHIGH VOLTAGE HVHORSEPOWER HP

ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICAIESNAINTERMEDIATE METAL CONDUIT IMC

KILOVOLT kVKILOVOLT AMP kVAKILOWATT kWKILOWATT HOUR kWH

LIQUIDTIGHT FLEXIBLE METAL CONDUIT LFMCLIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT LFNCLOW VOLTAGE LVLUMEN LMLUMENS PER WATT LPW

MAIN CIRCUIT BREAKER MCBMAIN LUGS ONLY MLOMANUFACTURER MFRMINIMUM MINMINIMUM CIRCUIT AMPS MCAMOTOR CONTROL CENTER MCCMOTOR STARTER MS

NATIONAL ELECTRICAL CODE NECNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEMANATIONAL FIRE CODE NFCNATIONAL FIRE PROTECTION ASSOCIATION NFPANIGHT LIGHT NLNORMALLY CLOSED NCNORMALLY OPEN NONOTIFICATION APPLIANCE CIRCUIT NAC

PANELBOARD PBPHASE PHPHOTOELECTRIC PEPHOTOELECTRIC CELL PECPOLY VINYL CHLORIDE PVCPOWER PWRPOWER AMPLIFIER PAPOWER FACTOR PF

RECEPTACLE RECEPTRIGID GALVANIZED STEEL RGSRIGID NONMETALLIC CONDUIT RNC

SCHEDULE SCHSERVICE ENTRANCE SESINGLE PHASE 1

∅SINGLE POLE, DOUBLE THROW SPDTSINGLE POLE, SINGLE THROW SPSTSWITCHBOARD SWBD

THREE PHASE 3

∅TWISTED SHIELDED PAIR TSP

UNINTERRUPTIBLE POWER SUPPLY UPSUNLESS NOTED OTHERWISE UNO

VARIABLE FREQUENCY DRIVE VFDVERY HIGH OUTPUT VHOVOLT, VOLTS, VOLTAGE VVOLT AMPERE VAVOLTAGE DROP VD

WEATHERPROOF WPWIREWAY WW

GROUND GND

ELECTRICAL ABBREVIATIONS

TRIM RINGCEILING

LAMP AS SPECIFIED

SOCKET CUP

SOCKET

MOUNTING BRACKET

HOUSING/MOUNTING

ELECTRONIC BALLAST

JUNCTION BOX

ALZAK REMOVABLE REFLECTOR

3 5/8" METAL STUD FIELD VERIFY LOCATION

SQUARE STEEL BOX

GALVANIZED WIRE HANGER MIN. #22 AWG CONNECTED TO A MINIMUM OF FOUR POINTS ON FIXTURE

PROVIDE FOUR HOLD DOWN CLIPS PER FIXTURE

2'X4' LAY-IN LIGHT FIXTURE

LAY-IN CEILING

3/8" MIN. FLEX CONDUIT (LIMIT TO

6')

SUPPORT

EMT CONDUIT

NOTES:• WIRE HANGERS ARE ONLY REQUIRED IN

AREAS WITH LAY-IN CEILINGS. ACTUAL MOUNTING MAY VARY DUE TO ACTUAL SITE CONDITIONS.

# DATE DESCRIPTION

-

CLIENT

PROJECT NO.

Parkhill.com

9/1

6/2

021

2:0

4:1

5 P

M

1077.21

R_v21

ISSUE FOR BID

555 Walnut St.Abilene, TX 79601

City of Abilene

E-001

ElectricalAbbreviations &Legends

Ab

ile

ne

Cit

y C

ou

nc

il C

ha

mb

ers

Re

no

vati

on

s

NTSA4RECESSED DOWNLIGHT INSTALLATION DETAIL

NTSA2RECESSED LIGHT FIXTURE INSTALLATION DETAIL

ELECTRICAL SPECIFICATIONS:

CODE COMPLIANCE/WORKMANSHIP1. CONTRACTOR SHALL COMPLY WITH ALL NATIONAL, STATE AND LOCAL CODES AND ACCEPTED

GOOD PRACTICE.2. ALL WORK SHALL BE PERFORMED BY LICENSED AND QUALIFIED PERSONNEL.

EXISTING CONDITIONS1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BID. BY

SUBMITTING BID, CONTRACTOR STATES THAT HE HAS EXAMINED ALL EXISTING CONDITIONS. IF CONTRACTOR ENCOUNTERS EXISTING CONDITIONS WHICH NEED CLARIFICATION, CONTACT ENGINEER FOR RESOLUTION OR CLARIFICATION.

PERMITS AND FEES1. CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY ALL FEES AND CHARGES REQUIRED

(INCLUDING UTILITY COMPANY CHARGES).

GUARANTEE AND WARRANTIES1. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL HAVE ONE (1) YEAR WRITTEN

GUARANTEE FOR ALL MATERIALS AND WORKMANSHIP.

MATERIALS1. ALL MATERIALS SHALL BE NEW AND SPECIFICATION GRADE.

OWNERS MANUAL1. AT COMPLETION OF PROJECT, CONTRACTOR SHALL DELIVER TO OWNER ALL DOCUMENTS

(INCLUDING BUILDING PERMITS, OPERATION AND MAINTENANCE MANUALS, WARRANTY, AS-BUILT ETC.).

CONDUIT1. ALL INTERIOR CONDUIT SHALL BE EMT. MINIMUM SIZE OF CONDUIT SHALL BE 3/4" FOR POWER

AND 1" FOR COMMUNICATION. ALL CONDUIT SHALL BE ROUTED PERPENDICULAR TO BUILDING LINES WHERE EXPOSED TO VIEW.

2. LABEL ALL JUNCTION BOXES ABOVE CEILING WITH CIRCUIT DESIGNATION WITH BLACK INDELIBLE MARKER.

3. ALL EMPTY CONDUITS SHALL HAVE PULL WIRE FOR FUTURE USE. 4. ALL COMMUNICATION CONDUITS SHALL BE STUBBED UP ABOVE CEILING AND TERMINATED

WITH A PLASTIC BUSHING.

WIRE1. ALL WIRE SHALL BE THHN/THWN COPPER UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

MINIMUM SIZE OF WIRE SHALL BE #12. FOR 20A CIRCUITS LONGER THAN 100', MINIMUM WIRE SIZE SHALL BE #10 AWG.

DISCONNECT SWITCHES1. ALL DISCONNECT SWITCHES SHALL BE HEAVY DUTY WITH NEMA CONFIGURATION AS

INDICATED ON DRAWINGS OR AS REQUIRED BY N.E.C. PROVIDE FUSES IN SWITCHES AS INDICATED ON THE DRAWINGS.

SWITCHES1. ALL SWITCHES SHALL BE SPECIFICATION GRADE (HUBBELL 1221 OR APPROVED EQUAL).

COLOR OF ALL SWITCHES SHALL SHALL BE GRAY AND COVERPLATES SHALL BE STAINLESS STEEL. MOUNTING HEIGHT OF ALL SWITCHES SHALL COMPLY WITH A.D.A. REQUIREMENTS.

FUSED/NON-FUSED DISCONNECTS1. ALL FUSED AND NON-FUSED DISCONNECTS SHALL BE HEAVY DUTY RATED OF THE

AMPERAGE RATING REQUIRED BY NEC FOR REQUIRED SERVICE.2. PROVIDE FUSES FOR EACH DISCONNECT.

RECEPTACLES1. ALL RECEPTACLES SHALL BE SPECIFICATION GRADE (HUBBELL 5352 OR APPROVED EQUAL).

COLOR OF ALL RECEPTACLES SHALL BE GRAY AND COVERPLATES SHALL BE STAINLESS STEEL. MOUNTING HEIGHT OF RECEPTACLES SHALL COMPLY WITH A.D.A. REQUIREMENTS UNLESS SPECIFIC OR SPECIAL MOUNTING HEIGHT IS SHOWN ON DRAWINGS OR REQUIRED BY EQUIPMENT.

2. LABEL ALL RECEPTACLES WITH CIRCUIT DESIGNATION ON BACKSIDE OF FACEPLATE WITH BLACK INDELIBLE MARKER.

GROUNDING1. ENTIRE ELECTRICAL SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C. ARTICLE

250.

ELECTRICAL EQUIPMENT1. ALL BUSSING SHALL BE COPPER WITH FULL LENGTH GROUND BUS. OVERCURRENT DEVICES

SHALL BE CIRCUIT BREAKER (CB) AS INDICATED. INTERRUPTING CURRENT OF EQUIPMENT AND DEVICES SHALL BE AS NOTED ON THE SCHEDULE.

PANELBOARDS1. PROVIDE TYPEWRITTEN DIRECTORIES IN ALL PANELBOARDS AFFECTED BY PROJECT AFTER

PROJECT COMPLETION. HANDWRITTEN WILL NOT BE ACCEPTED.2. PROVIDE MINIMUM INTEGRATED SHORT CIRCUIT RATING AS INDICATED ON PANELBOARD

SCHEDULE. ALL CIRCUIT BREAKERS SHALL BE FULLY RATED. SERIES RATED SYSTEMS WILL NOT BE ALLOWED.

3. ALL NEW OVERCURRENT DEVICES SHALL MATCH EXISTING.

LIGHTING FIXTURES1. LIGHTING FIXTURES SHALL BE AS SCHEDULED ON THE DRAWINGS. FIXTURES SHALL BE

COMPLETE WITH ALL LAMPS.2. REFER TO THE DRAWINGS FOR MOUNTING RESTRICTIONS.

SUBMITTALS AND SUBSTITUTIONS1. CONTRACTOR SHALL FURNISH SUBMITTAL DATA TO ENGINEER FOR APPROVAL ON ALL

FIXTURES AND EQUIPMENT PRIOR TO ORDERING ANY ITEMS. CONTRACTOR MAY OFFER SUBSTITUTIONS ON ITEMS FOR APPROVAL BY ENGINEER. SUBSTITUTIONS MUST BE EQUAL IN ALL RESPECTS TO ITEMS SCHEDULED OR SPECIFIED.

09/16/2021

09/16/2021

Page 2: A2 A4 E-001 - abilenetx.gov

DN

M M

MM

CHAMBER

202

IT

203

CE2

C2

C2

CE2

C2

CE2

C2

CE2

CE1 C1 C1 CE1

CE2 C2 C2 CE2

X XCSCS

1

1

B1

AE1 A1 A2

A1

AE1

A2A2A1AE1

A2

AE1

A1

2

3

C2 d d ddc

c

c

c

c

cC2 c c c c dC2

d

d

d

d

a

b b b

b

b

b

bbbb

b

b

1 3

2

4

A. LIGHTED EXIT SIGNS SHALL BE CONNECTED TO THE UNSWITCHED SIDE OF THE CIRCUIT SHOWN ON PLANS.

# DATE DESCRIPTION

-

CLIENT

PROJECT NO.

Parkhill.com

9/1

6/2

021

2:0

4:1

7 P

M

1077.21

R_v21

ISSUE FOR BID

555 Walnut St.Abilene, TX 79601

City of Abilene

E-111

Electrical FloorPlans - SecondFloor

Ab

ile

ne

Cit

y C

ou

nc

il C

ha

mb

ers

Re

no

vati

on

s

GENERAL NOTES

AS INDICATED BY: #

KEY NOTES

A. COORDINATE LOCATION OF LIGHT FIXTURES WITH ARCHITECTURAL AND MECHANICAL.

B. ALL EMERGENCY AND EGRESS LIGHTING SHALL BE CONNECTED TO THE SAME BRANCH CIRCUIT SERVING THE NORMAL LIGHTS AND SHALL BE ON THE LINE SIDE OF RELAYS OR SWITCHING DEVICES.

C. REFER TO KEYED NOTES FOR CONTROL OF ADDITIONAL EMERGENCY LIGHTING. ALL EXIT SIGNS SHALL BE CONNECTED FOR CONTINUOUS OPERATION.

D. AT LOCATIONS WHERE ROOM LIGHT FIXTURES ARE CONTROLLED THROUGH THE USE OF OCCUPANCY SENSORS, PROVIDE THE NUMBER OF SENSORS AND LOCATE THE UNITS AS REQUIRED FOR COMPLETE ROOM COVERAGE. WHERE MORE THAN ONE SENSOR IS LOCATED IN A COMMON SPACE, CONNECT THE UNITS SUCH THAT DETECTION OF OCCUPANCY FROM EITHER UNIT WILL ENERGIZE THE LIGHTING. WHERE SWITCHES ARE SHOWN IN CONJUNCTION WITH OCCUPANCY SENSORS, CONNECT THE SWITCHES TO DE-ENERGIZE THE LIGHTING INDICATED REGARDLESS OF OCCUPANCY. ADJUST ALL SENSOR TIME DELAYS AND MOTION SENSITIVITIES DURING PROJECT CLOSEOUT TO MEET THE OPERATIONAL FUNCTION OF THE OWNER.

E. EXACT LOCATION AND PLACEMENT OF EXIT LIGHTING SHALL BE FIELD DETERMINED TO ENSURE PROPER LINES OF SIGHT.

F. RECESSED DOWN LIGHT FIXTURES INSTALLED IN LAY-IN CEILINGS SHALL BE PROVIDED WITH ADJUSTABLE T-BAR ATTACHMENT ARMS MANUFACTURED BY THE LIGHT FIXTURE COMPANY.

G. PROVIDE DEDICATED NEUTRAL WIRE FOR ALL 120V OR 277V BRANCH CIRCUITS. NO MULTI-WIRE BRANCH CIRCUITS SHALL BE ALLOWED.

NORTH

0 8' 16'4'1/8" = 1'-0"A4Lighting Plan

1. EXTEND AND CONNECT TO EXISTING LIGHTING CIRCUIT BRANCH SERVING THIS AREA. PROVIDE NEW WIRE AND CONDUIT AS NECESSARY (MATCH EXISTING).

2. MOUNT FIXTURES AT 14'-0'' AFF. TYPICAL OF ALL TYPE A1 AND A2 FIXTURES.3. MOUNT FIXTURE AT 11'-0'' AFF.

NORTH

0 8' 16'4'1/8" = 1'-0"A3Electrical Demolition Plan

LIGHTING FIXTURE SCHEDULETYPE MANUFACTURER MODEL LAMP DESCRIPTION

A1 MARK LIGHTING S1LD--LCB-8FT-90CRI-40K-600LMF-I90CRI-I40K-I400LMF-MIN1-SCT-MVOLT-WHT

40.64W LED 8' LED DIRECT/INDIRECT LINEAR PENDANT FIXTURE WITH600LMF LUMEN PACKAGE AND 0-10V DIMMING DRIVER

A2 MARK LIGHTING S1LD--LCB-6FT-90CRI-40K-600LMF-I90CRI-I40K-I400LMF-MIN1-SCT-MVOLT-WHT

30.48W LED SAME AS TYPE A1 EXCEPT 6' LONG

AE1 MARK LIGHTING S1LD--LCB-8FT-90CRI-40K-600LMF-I90CRI-I40K-I400LMF-MIN1-SCT--MVOLT-WHT-WEC

40.64W LED SAME AS TYPE A1 EXCEPT WITH EMEGERGENCY BATTERYPACKAGE

B1 DELRAY UDC8-SL-W40-SR-D 267W LED 8' LED DIRECT/INDIRECT CIRCULAR PENDANT WITH WHITEFROSTED ACRYLIC LENS AND W40 LED PACKAGE

C1 GOTHAM EV04-40/25-AR-WD-LS-MVOLT-EZ10 25.70W LED 4'' LED ROUND DOWNLIGHT WITH 2500 LUMEN PACKAGE,WIDE DISTRIBUTION AND 0-10V DIMMING DRIVER

C2 GOTHAM EV04WW-40/25-AR-WD-LS-MVOLT-EZ10 25.70W LED SAME AS TYPE C1 EXCEPT WALLWASH

CE1 GOTHAM EV04-40/25-AR-WD-LS-MVOLT-EZ10-EL 25.70W LED SAME AS TYPE C1 EXCEPT WITH EMEGENCY BATTERYPACKAGE

CE2 GOTHAM EV04WW-40/25-AR-WD-LS-MVOLT-EZ10-EL 25.70W LED SAME AS TYPE C2 EXCEPT WITH EMEGENCY BATTERYPACKAGE

X LITHONIA LE-S-1-RSD 7W LED LED EMERGENCY EXIT SIGN WITH SELF DIAGNOSTICS

AS INDICATED BY: #

DEMOLITION NOTES

1. PROVIDE FOR THE COMPLETE REMOVAL OF EXISTING LIGHTS AND LIGHT CONTROLS IN AREA.

2. EXISTING POWER AND DATA DEVICES ON COUNTERTOP AND CABINET ARE TO BE DISCONNECT AND SALVAGED. DEVICES SHALL BE RE-INSTALLED UPON COMPLETION OF THE NEW CONTERTOP AND CABINET. COORDINATE WITH ARCHITECTURE FOR EXACT LOCATION OF DEVICES.

3. ALL EXISTING EQUIPMENT IN CEILING, OTHER THAN LIGHTING, SHALL BE REMOVED AND RE-INSTALLED BY THE ELECTRICAL CONTRACTOR AS AT PRESENT.

4. EXISTING LIGHTING AND CONTROLS IN IT ROOM TO REMAIN.